Test Report of Pressure Vessels
Test Report of Pressure Vessels
Tech (Mechanical)
Competent Person under Section 28, 29 & 31 including Hazardous Chemicals
(Approved by Directorate of Factories and Boilers, Govt. Of Odisha)
Address: Samridhi Vihar Apartment, 508, 5th Floor, Sundarpada, Bhubaneswar – 751 002
Mb: 9830354052/8240149465, Email: [email protected]
Mithun Mitra, B.Tech (Mechanical)
Competent Person under Section 28, 29 & 31 including Hazardous Chemicals
(Approved by Directorate of Factories and Boilers, Govt. Of Odisha)
14. Repairs if any required; and the period within At present no repairs required.
which they should be executed and any other
condition which the person conducting the
examination found it necessary to specify for
securing safe working.
15. Maximum permissible working pressure, Lowest Thickness of the Cylindrical Portion: 5.0 mm
calculated from dimensions and from the Lowest Thickness of Dished End A: 6.0 mm
thickness and other data ascertained by the Lowest Thickness of Dished End B: 6.0 mm
present examination, due allowance being made Measured wall thickness of the cylindrical portion (5.0 mm)
for conditions of working if unusual or is sufficient to sustain the maximum working pressure of
exceptionally severe. (State minimum thickness of 11.22 Kg/cm².
walls measured during the examination).
16. Where repairs affecting the maximum working Not Applicable
pressure are required, state the working pressure;
a) Before the expiration of period specified in (14) --
b) After the expiration of such period if required --
repairs have not been completed.
c) After the completion of the required repairs. --
17. Other Observations The Receiver and all the fittings are in good condition.
Visual inspection of weld joints found OK and no distortion in shape of the receiver.
I certify that on 02.09.2021, this pressure vessel was thoroughly examined so for their construction permitted hand the test/examination
as were necessary made on the same day and that the above.
Address: Samridhi Vihar Apartment, 508, 5th Floor, Sundarpada, Bhubaneswar – 751 002
Mb: 9830354052/8240149465, Email: [email protected]
Mithun Mitra, B.Tech (Mechanical)
Competent Person under Section 28, 29 & 31 including Hazardous Chemicals
(Approved by Directorate of Factories and Boilers, Govt. Of Odisha)
Address: Samridhi Vihar Apartment, 508, 5th Floor, Sundarpada, Bhubaneswar – 751 002
Mb: 9830354052/8240149465, Email: [email protected]
Mithun Mitra, B.Tech (Mechanical)
Competent Person under Section 28, 29 & 31 including Hazardous Chemicals
(Approved by Directorate of Factories and Boilers, Govt. Of Odisha)
14. Repairs if any required; and the period within At present no repairs required.
which they should be executed and any other
condition which the person conducting the
examination found it necessary to specify for
securing safe working.
15. Maximum permissible working pressure, Lowest Thickness of the Cylindrical Portion: 5.0 mm
calculated from dimensions and from the Lowest Thickness of Dished End A: 6.0 mm
thickness and other data ascertained by the Lowest Thickness of Dished End B: 6.0 mm
present examination, due allowance being made Measured wall thickness of the cylindrical portion (5.0 mm)
for conditions of working if unusual or is sufficient to sustain the maximum working pressure of
exceptionally severe. (State minimum thickness of 11.2 Kg/cm².
walls measured during the examination).
16. Where repairs affecting the maximum working Not Applicable
pressure are required, state the working pressure;
a) Before the expiration of period specified in (14) --
b) After the expiration of such period if required --
repairs have not been completed.
c) After the completion of the required repairs. --
17. Other Observations The Receiver and all the fittings are in good condition.
Visual inspection of weld joints found OK and no distortion in shape of the receiver.
I certify that on 02.09.2021, this pressure vessel was thoroughly examined so for their construction permitted hand the test/examination
as were necessary made on the same day and that the above.
Address: Samridhi Vihar Apartment, 508, 5th Floor, Sundarpada, Bhubaneswar – 751 002
Mb: 9830354052/8240149465, Email: [email protected]
Mithun Mitra, B.Tech (Mechanical)
Competent Person under Section 28, 29 & 31 including Hazardous Chemicals
(Approved by Directorate of Factories and Boilers, Govt. Of Odisha)
Address: Samridhi Vihar Apartment, 508, 5th Floor, Sundarpada, Bhubaneswar – 751 002
Mb: 9830354052/8240149465, Email: [email protected]
Mithun Mitra, B.Tech (Mechanical)
Competent Person under Section 28, 29 & 31 including Hazardous Chemicals
(Approved by Directorate of Factories and Boilers, Govt. Of Odisha)
14. Repairs if any required; and the period within At present no repairs required.
which they should be executed and any other
condition which the person conducting the
examination found it necessary to specify for
securing safe working.
15. Maximum permissible working pressure, Lowest Thickness of the Cylindrical Portion: 5.0 mm
calculated from dimensions and from the Lowest Thickness of Dished End A: 6.0 mm
thickness and other data ascertained by the Lowest Thickness of Dished End B: 6.0 mm
present examination, due allowance being made Measured wall thickness of the cylindrical portion (5.0 mm)
for conditions of working if unusual or is sufficient to sustain the maximum working pressure of
exceptionally severe. (State minimum thickness of 11.2 Kg/cm².
walls measured during the examination).
16. Where repairs affecting the maximum working Not Applicable
pressure are required, state the working pressure;
a) Before the expiration of period specified in (14) --
b) After the expiration of such period if required --
repairs have not been completed.
c) After the completion of the required repairs. --
17. Other Observations The Receiver and all the fittings are in good condition.
Visual inspection of weld joints found OK and no distortion in shape of the receiver.
I certify that on 02.09.2021, this pressure vessel was thoroughly examined so for their construction permitted hand the test/examination
as were necessary made on the same day and that the above.
Address: Samridhi Vihar Apartment, 508, 5th Floor, Sundarpada, Bhubaneswar – 751 002
Mb: 9830354052/8240149465, Email: [email protected]
Mithun Mitra, B.Tech (Mechanical)
Competent Person under Section 28, 29 & 31 including Hazardous Chemicals
(Approved by Directorate of Factories and Boilers, Govt. Of Odisha)
Address: Samridhi Vihar Apartment, 508, 5th Floor, Sundarpada, Bhubaneswar – 751 002
Mb: 9830354052/8240149465, Email: [email protected]
Mithun Mitra, B.Tech (Mechanical)
Competent Person under Section 28, 29 & 31 including Hazardous Chemicals
(Approved by Directorate of Factories and Boilers, Govt. Of Odisha)
14. Repairs if any required; and the period within At present no repairs required.
which they should be executed and any other
condition which the person conducting the
examination found it necessary to specify for
securing safe working.
15. Maximum permissible working pressure, Lowest Thickness of the Cylindrical Portion: 5.0 mm
calculated from dimensions and from the Lowest Thickness of Dished End A: 6.0 mm
thickness and other data ascertained by the Lowest Thickness of Dished End B: 6.0 mm
present examination, due allowance being made Measured wall thickness of the cylindrical portion (5.0 mm)
for conditions of working if unusual or is sufficient to sustain the maximum working pressure of
exceptionally severe. (State minimum thickness of 11.2 Kg/cm².
walls measured during the examination).
16. Where repairs affecting the maximum working Not Applicable
pressure are required, state the working pressure;
a) Before the expiration of period specified in (14) --
b) After the expiration of such period if required --
repairs have not been completed.
c) After the completion of the required repairs. --
17. Other Observations The Receiver and all the fittings are in good condition.
Visual inspection of weld joints found OK and no distortion in shape of the receiver.
I certify that on 02.09.2021, this pressure vessel was thoroughly examined so for their construction permitted hand the test/examination
as were necessary made on the same day and that the above.
Address: Samridhi Vihar Apartment, 508, 5th Floor, Sundarpada, Bhubaneswar – 751 002
Mb: 9830354052/8240149465, Email: [email protected]
Mithun Mitra, B.Tech (Mechanical)
Competent Person under Section 28, 29 & 31 including Hazardous Chemicals
(Approved by Directorate of Factories and Boilers, Govt. Of Odisha)
Address: Samridhi Vihar Apartment, 508, 5th Floor, Sundarpada, Bhubaneswar – 751 002
Mb: 9830354052/8240149465, Email: [email protected]
Mithun Mitra, B.Tech (Mechanical)
Competent Person under Section 28, 29 & 31 including Hazardous Chemicals
(Approved by Directorate of Factories and Boilers, Govt. Of Odisha)
14. Repairs if any required; and the period within At present no repairs required.
which they should be executed and any other
condition which the person conducting the
examination found it necessary to specify for
securing safe working.
15. Maximum permissible working pressure, Lowest Thickness of the Cylindrical Portion: 5.0 mm
calculated from dimensions and from the Lowest Thickness of Dished End A: 6.0 mm
thickness and other data ascertained by the Lowest Thickness of Dished End B: 6.0 mm
present examination, due allowance being made Measured wall thickness of the cylindrical portion (5.0 mm)
for conditions of working if unusual or is sufficient to sustain the maximum working pressure of
exceptionally severe. (State minimum thickness of 11.2 Kg/cm².
walls measured during the examination).
16. Where repairs affecting the maximum working Not Applicable
pressure are required, state the working pressure;
a) Before the expiration of period specified in (14) --
b) After the expiration of such period if required --
repairs have not been completed.
c) After the completion of the required repairs. --
17. Other Observations The Receiver and all the fittings are in good condition.
Visual inspection of weld joints found OK and no distortion in shape of the receiver.
I certify that on 02.09.2021, this pressure vessel was thoroughly examined so for their construction permitted hand the test/examination
as were necessary made on the same day and that the above.
Address: Samridhi Vihar Apartment, 508, 5th Floor, Sundarpada, Bhubaneswar – 751 002
Mb: 9830354052/8240149465, Email: [email protected]
Mithun Mitra, B.Tech (Mechanical)
Competent Person under Section 28, 29 & 31 including Hazardous Chemicals
(Approved by Directorate of Factories and Boilers, Govt. Of Odisha)
Address: Samridhi Vihar Apartment, 508, 5th Floor, Sundarpada, Bhubaneswar – 751 002
Mb: 9830354052/8240149465, Email: [email protected]
Mithun Mitra, B.Tech (Mechanical)
Competent Person under Section 28, 29 & 31 including Hazardous Chemicals
(Approved by Directorate of Factories and Boilers, Govt. Of Odisha)
14. Repairs if any required; and the period within At present no repairs required.
which they should be executed and any other
condition which the person conducting the
examination found it necessary to specify for
securing safe working.
15. Maximum permissible working pressure, Lowest Thickness of the Cylindrical Portion: 5.0 mm
calculated from dimensions and from the Lowest Thickness of Dished End A: 6.0 mm
thickness and other data ascertained by the Lowest Thickness of Dished End B: 6.0 mm
present examination, due allowance being made Measured wall thickness of the cylindrical portion (5.0 mm)
for conditions of working if unusual or is sufficient to sustain the maximum working pressure of
exceptionally severe. (State minimum thickness of 11.2 Kg/cm².
walls measured during the examination).
16. Where repairs affecting the maximum working Not Applicable
pressure are required, state the working pressure;
a) Before the expiration of period specified in (14) --
b) After the expiration of such period if required --
repairs have not been completed.
c) After the completion of the required repairs. --
17. Other Observations The Receiver and all the fittings are in good condition.
Visual inspection of weld joints found OK and no distortion in shape of the receiver.
I certify that on 02.09.2021, this pressure vessel was thoroughly examined so for their construction permitted hand the test/examination
as were necessary made on the same day and that the above.