Test Report of Pressure Vessels

This document is a test report for two pressure vessels - Pressure Vessel-1 and Pressure Vessel-2 - located at a factory in Jharsuguda, Odisha. It provides details of the vessels such as manufacturer, date of construction, dimensions, test dates, and inspection results. The inspection found the vessels to be in good external condition with no defects, and ultrasonic thickness tests confirmed the minimum wall thickness was sufficient to sustain the maximum working pressure. No repairs were required.

Uploaded by

Deepak Mallik
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
551 views

Test Report of Pressure Vessels

This document is a test report for two pressure vessels - Pressure Vessel-1 and Pressure Vessel-2 - located at a factory in Jharsuguda, Odisha. It provides details of the vessels such as manufacturer, date of construction, dimensions, test dates, and inspection results. The inspection found the vessels to be in good external condition with no defects, and ultrasonic thickness tests confirmed the minimum wall thickness was sufficient to sustain the maximum working pressure. No repairs were required.

Uploaded by

Deepak Mallik
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

Mithun Mitra, B.

Tech (Mechanical)
Competent Person under Section 28, 29 & 31 including Hazardous Chemicals
(Approved by Directorate of Factories and Boilers, Govt. Of Odisha)

Ref: MM/VAL/RRLLP/PV/2021/09 FORM NO.- 8 Dated: 02.09.2021


TEST REPORT OF PRESSURE VESSELS
(Sub Section-2 of Section 31 of the factory Act 1948, See Rule – 56 of the Orissa Factories Rules 1950)
1. Name of Occupier (or Factory) M/S RUNAYA REFINING LLP
2. Situation and address of factory M/s. VEDANTA LIMITED, Smelter-1,
Bhurkhamunda,
Jharsuguda, Odisha
3. Name, description and distinctive number of Name: Pressure Vessel-1
pressure vessel or plant Equipment No.- SHI-700
Location: Dross Shed Cast House -3
Capacity- 272.0 Ltr
4. Name and address of manufacturer of the vessel M/s Ingersoll Rand
5. Nature of Process in which it is used For Pneumatic Process Control
6. Particulars of pressure vessel or plant
a) Date of Construction 2019
b) Thickness of walls Thickness of Wall as per Manufacturer
Cylindrical Portion Dished End-A Dished End-B
Original Thickness Data not available
c) Date on which the pressure vessel was first 2019
taken into use
d) Maximum permissible working pressure 11.22 Kg/cm²
recommended by the manufacturer.
e) Design pressure, if known (the history should N.A
be briefly given and examiner should state
whether he has seen the last previous report
7. Date of last hydrostatic test (if any) and pressure 08.07.2019 at 16.30 Kg/cm2
applied.
8. Is the pressure vessel or plant in open or Under the shed
otherwise exposed to weather or to damp?
9. What parts (if any) were inaccessible? Internally not accessible
10. What examinations and tests were made? External Examination: Done
(Specify pressure if hydrostatic test was carried) Internal Examination: Not done
Hydrostatic Test: NA
Pneumatic Test: Not done
Ultrasonic Thickness Test: Done
Cylindrical Portion Dished End-A Dished End-B
5.0 5.0 6.0 6.0 6.1 6.0
11. Condition of pressure vessel or plant (state any Externally:
defects materially affecting the maximum Pressure Vessel-1 Is in good condition and no external
permissible working pressure of the safe working defects found during the examination.
of the pressure vessel or plant).
12. Are the required fittings or appliances provided in Yes
accordance with the rules?
13. Are all the fittings and appliances properly All the fittings are properly maintained.
maintained and in good condition? Have the
pressure settings being checked and corrected?

Address: Samridhi Vihar Apartment, 508, 5th Floor, Sundarpada, Bhubaneswar – 751 002
Mb: 9830354052/8240149465, Email: [email protected]
Mithun Mitra, B.Tech (Mechanical)
Competent Person under Section 28, 29 & 31 including Hazardous Chemicals
(Approved by Directorate of Factories and Boilers, Govt. Of Odisha)

14. Repairs if any required; and the period within At present no repairs required.
which they should be executed and any other
condition which the person conducting the
examination found it necessary to specify for
securing safe working.
15. Maximum permissible working pressure, Lowest Thickness of the Cylindrical Portion: 5.0 mm
calculated from dimensions and from the Lowest Thickness of Dished End A: 6.0 mm
thickness and other data ascertained by the Lowest Thickness of Dished End B: 6.0 mm
present examination, due allowance being made Measured wall thickness of the cylindrical portion (5.0 mm)
for conditions of working if unusual or is sufficient to sustain the maximum working pressure of
exceptionally severe. (State minimum thickness of 11.22 Kg/cm².
walls measured during the examination).
16. Where repairs affecting the maximum working Not Applicable
pressure are required, state the working pressure;
a) Before the expiration of period specified in (14) --
b) After the expiration of such period if required --
repairs have not been completed.
c) After the completion of the required repairs. --
17. Other Observations  The Receiver and all the fittings are in good condition.
 Visual inspection of weld joints found OK and no distortion in shape of the receiver.

I certify that on 02.09.2021, this pressure vessel was thoroughly examined so for their construction permitted hand the test/examination
as were necessary made on the same day and that the above.

Signature of the Competent Person


Carrying out the test & examination
Name : Mithun Mitra
Next Due Date: 01.03.2022 Qualification : Mechanical Engineer

Address: Samridhi Vihar Apartment, 508, 5th Floor, Sundarpada, Bhubaneswar – 751 002
Mb: 9830354052/8240149465, Email: [email protected]
Mithun Mitra, B.Tech (Mechanical)
Competent Person under Section 28, 29 & 31 including Hazardous Chemicals
(Approved by Directorate of Factories and Boilers, Govt. Of Odisha)

Ref: MM/VAL/RRLLP/PV/2021/10 FORM NO.- 8 Dated: 02.09.2021


TEST REPORT OF PRESSURE VESSELS
(Sub Section-2 of Section 31 of the factory Act 1948, See Rule – 56 of the Orissa Factories Rules 1950)
1. Name of Occupier (or Factory) M/S RUNAYA REFINING LLP
2. Situation and address of factory M/s. VEDANTA LIMITED, Smelter-1,
Bhurkhamunda,
Jharsuguda, Odisha
3. Name, description and distinctive number of Name: Pressure Vessel-2
pressure vessel or plant Equipment No.- SHI-837
Location: Dross Shed Cast House -2(Compressor for 45000
3
M /h Bag House)
Capacity- 272.0 Ltr
4. Name and address of manufacturer of the vessel M/s Ingersoll Rand
5. Nature of Process in which it is used For Pneumatic Process Control
6. Particulars of pressure vessel or plant
a) Date of Construction 2019
b) Thickness of walls Thickness of Wall as per Manufacturer
Cylindrical Portion Dished End-A Dished End-B
Original Thickness Data not available
c) Date on which the pressure vessel was first 2019
taken into use
d) Maximum permissible working pressure 11.22 Kg/cm²
recommended by the manufacturer.
e) Design pressure, if known (the history should N.A
be briefly given and examiner should state
whether he has seen the last previous report
7. Date of last hydrostatic test (if any) and pressure 16.08.2019 at 16.30 Kg/cm2
applied.
8. Is the pressure vessel or plant in open or Under the shed
otherwise exposed to weather or to damp?
9. What parts (if any) were inaccessible? Internally not accessible
10. What examinations and tests were made? External Examination: Done
(Specify pressure if hydrostatic test was carried) Internal Examination: Not done
Hydrostatic Test: NA
Pneumatic Test: Not done
Ultrasonic Thickness Test: Done
Cylindrical Portion Dished End-A Dished End-B
5.0 5.0 6.0 6.0 6.0 6.0
11. Condition of pressure vessel or plant (state any Externally:
defects materially affecting the maximum Pressure Vessel-2 Is in good condition and no external
permissible working pressure of the safe working defects found during the examination.
of the pressure vessel or plant).
12. Are the required fittings or appliances provided in Yes
accordance with the rules?
13. Are all the fittings and appliances properly All the fittings are properly maintained.
maintained and in good condition? Have the
pressure settings being checked and corrected?

Address: Samridhi Vihar Apartment, 508, 5th Floor, Sundarpada, Bhubaneswar – 751 002
Mb: 9830354052/8240149465, Email: [email protected]
Mithun Mitra, B.Tech (Mechanical)
Competent Person under Section 28, 29 & 31 including Hazardous Chemicals
(Approved by Directorate of Factories and Boilers, Govt. Of Odisha)

14. Repairs if any required; and the period within At present no repairs required.
which they should be executed and any other
condition which the person conducting the
examination found it necessary to specify for
securing safe working.
15. Maximum permissible working pressure, Lowest Thickness of the Cylindrical Portion: 5.0 mm
calculated from dimensions and from the Lowest Thickness of Dished End A: 6.0 mm
thickness and other data ascertained by the Lowest Thickness of Dished End B: 6.0 mm
present examination, due allowance being made Measured wall thickness of the cylindrical portion (5.0 mm)
for conditions of working if unusual or is sufficient to sustain the maximum working pressure of
exceptionally severe. (State minimum thickness of 11.2 Kg/cm².
walls measured during the examination).
16. Where repairs affecting the maximum working Not Applicable
pressure are required, state the working pressure;
a) Before the expiration of period specified in (14) --
b) After the expiration of such period if required --
repairs have not been completed.
c) After the completion of the required repairs. --
17. Other Observations  The Receiver and all the fittings are in good condition.
 Visual inspection of weld joints found OK and no distortion in shape of the receiver.

I certify that on 02.09.2021, this pressure vessel was thoroughly examined so for their construction permitted hand the test/examination
as were necessary made on the same day and that the above.

Signature of the Competent Person


Carrying out the test & examination
Name : Mithun Mitra
Next Due Date: 01.03.2022 Qualification : Mechanical Engineer

Address: Samridhi Vihar Apartment, 508, 5th Floor, Sundarpada, Bhubaneswar – 751 002
Mb: 9830354052/8240149465, Email: [email protected]
Mithun Mitra, B.Tech (Mechanical)
Competent Person under Section 28, 29 & 31 including Hazardous Chemicals
(Approved by Directorate of Factories and Boilers, Govt. Of Odisha)

Ref: MM/VAL/RRLLP/PV/2021/11 FORM NO.- 8 Dated: 02.09.2021


TEST REPORT OF PRESSURE VESSELS
(Sub Section-2 of Section 31 of the factory Act 1948, See Rule – 56 of the Orissa Factories Rules 1950)
1. Name of Occupier (or Factory) M/S RUNAYA REFINING LLP
2. Situation and address of factory M/s. VEDANTA LIMITED, Smelter-1,
Bhurkhamunda,
Jharsuguda, Odisha
3. Name, description and distinctive number of Name: Pressure Vessel-3
pressure vessel or plant Equipment No.- SHI-941
Location: Dross Shed Cast House -2(Compressor for 36000
3
M /h Bag House)
Capacity- 272.0 Ltr
4. Name and address of manufacturer of the vessel M/s Ingersoll Rand
5. Nature of Process in which it is used For Pneumatic Process Control
6. Particulars of pressure vessel or plant
a) Date of Construction 2019
b) Thickness of walls Thickness of Wall as per Manufacturer
Cylindrical Portion Dished End-A Dished End-B
Original Thickness Data not available
c) Date on which the pressure vessel was first 2019
taken into use
d) Maximum permissible working pressure 11.22 Kg/cm²
recommended by the manufacturer.
e) Design pressure, if known (the history should N.A
be briefly given and examiner should state
whether he has seen the last previous report
7. Date of last hydrostatic test (if any) and pressure 01.08.2019 at 16.30 Kg/cm2
applied.
8. Is the pressure vessel or plant in open or Under the shed
otherwise exposed to weather or to damp?
9. What parts (if any) were inaccessible? Internally not accessible
10. What examinations and tests were made? External Examination: Done
(Specify pressure if hydrostatic test was carried) Internal Examination: Not done
Hydrostatic Test: NA
Pneumatic Test: Not done
Ultrasonic Thickness Test: Done
Cylindrical Portion Dished End-A Dished End-B
5.0 5.0 6.0 6.0 6.1 6.0
11. Condition of pressure vessel or plant (state any Externally:
defects materially affecting the maximum Pressure Vessel-3 Is in good condition and no external
permissible working pressure of the safe working defects found during the examination.
of the pressure vessel or plant).
12. Are the required fittings or appliances provided in Yes
accordance with the rules?
13. Are all the fittings and appliances properly All the fittings are properly maintained.
maintained and in good condition? Have the
pressure settings being checked and corrected?

Address: Samridhi Vihar Apartment, 508, 5th Floor, Sundarpada, Bhubaneswar – 751 002
Mb: 9830354052/8240149465, Email: [email protected]
Mithun Mitra, B.Tech (Mechanical)
Competent Person under Section 28, 29 & 31 including Hazardous Chemicals
(Approved by Directorate of Factories and Boilers, Govt. Of Odisha)

14. Repairs if any required; and the period within At present no repairs required.
which they should be executed and any other
condition which the person conducting the
examination found it necessary to specify for
securing safe working.
15. Maximum permissible working pressure, Lowest Thickness of the Cylindrical Portion: 5.0 mm
calculated from dimensions and from the Lowest Thickness of Dished End A: 6.0 mm
thickness and other data ascertained by the Lowest Thickness of Dished End B: 6.0 mm
present examination, due allowance being made Measured wall thickness of the cylindrical portion (5.0 mm)
for conditions of working if unusual or is sufficient to sustain the maximum working pressure of
exceptionally severe. (State minimum thickness of 11.2 Kg/cm².
walls measured during the examination).
16. Where repairs affecting the maximum working Not Applicable
pressure are required, state the working pressure;
a) Before the expiration of period specified in (14) --
b) After the expiration of such period if required --
repairs have not been completed.
c) After the completion of the required repairs. --
17. Other Observations  The Receiver and all the fittings are in good condition.
 Visual inspection of weld joints found OK and no distortion in shape of the receiver.

I certify that on 02.09.2021, this pressure vessel was thoroughly examined so for their construction permitted hand the test/examination
as were necessary made on the same day and that the above.

Signature of the Competent Person


Carrying out the test & examination
Name : Mithun Mitra
Next Due Date: 01.03.2022 Qualification : Mechanical Engineer

Address: Samridhi Vihar Apartment, 508, 5th Floor, Sundarpada, Bhubaneswar – 751 002
Mb: 9830354052/8240149465, Email: [email protected]
Mithun Mitra, B.Tech (Mechanical)
Competent Person under Section 28, 29 & 31 including Hazardous Chemicals
(Approved by Directorate of Factories and Boilers, Govt. Of Odisha)

Ref: MM/VAL/RRLLP/PV/2021/12 FORM NO.- 8 Dated: 02.09.2021


TEST REPORT OF PRESSURE VESSELS
(Sub Section-2 of Section 31 of the factory Act 1948, See Rule – 56 of the Orissa Factories Rules 1950)
1. Name of Occupier (or Factory) M/S RUNAYA REFINING LLP
2. Situation and address of factory M/s. VEDANTA LIMITED, Smelter-1,
Bhurkhamunda,
Jharsuguda, Odisha
3. Name, description and distinctive number of Name: Pressure Vessel-4
pressure vessel or plant Equipment No.- 70279013
Location: Dross Shed Cast House -1(Compressor for 45000
3
M /h Bag House)
Capacity- 272.0 Ltr
4. Name and address of manufacturer of the vessel M/s Ingersoll Rand
5. Nature of Process in which it is used For Pneumatic Process Control
6. Particulars of pressure vessel or plant
a) Date of Construction 2019
b) Thickness of walls Thickness of Wall as per Manufacturer
Cylindrical Portion Dished End-A Dished End-B
Original Thickness Data not available
c) Date on which the pressure vessel was first 2019
taken into use
d) Maximum permissible working pressure 11.22 Kg/cm²
recommended by the manufacturer.
e) Design pressure, if known (the history should N.A
be briefly given and examiner should state
whether he has seen the last previous report
7. Date of last hydrostatic test (if any) and pressure 10.08.2019 at 16.30 Kg/cm2
applied.
8. Is the pressure vessel or plant in open or Under the shed
otherwise exposed to weather or to damp?
9. What parts (if any) were inaccessible? Internally not accessible
10. What examinations and tests were made? External Examination: Done
(Specify pressure if hydrostatic test was carried) Internal Examination: Not done
Hydrostatic Test: NA
Pneumatic Test: Not done
Ultrasonic Thickness Test: Done
Cylindrical Portion Dished End-A Dished End-B
5.0 5.0 6.0 6.0 6.1 6.0
11. Condition of pressure vessel or plant (state any Externally:
defects materially affecting the maximum Pressure Vessel-1 Is in good condition and no external
permissible working pressure of the safe working defects found during the examination.
of the pressure vessel or plant).
12. Are the required fittings or appliances provided in Yes
accordance with the rules?
13. Are all the fittings and appliances properly All the fittings are properly maintained.
maintained and in good condition? Have the
pressure settings being checked and corrected?

Address: Samridhi Vihar Apartment, 508, 5th Floor, Sundarpada, Bhubaneswar – 751 002
Mb: 9830354052/8240149465, Email: [email protected]
Mithun Mitra, B.Tech (Mechanical)
Competent Person under Section 28, 29 & 31 including Hazardous Chemicals
(Approved by Directorate of Factories and Boilers, Govt. Of Odisha)

14. Repairs if any required; and the period within At present no repairs required.
which they should be executed and any other
condition which the person conducting the
examination found it necessary to specify for
securing safe working.
15. Maximum permissible working pressure, Lowest Thickness of the Cylindrical Portion: 5.0 mm
calculated from dimensions and from the Lowest Thickness of Dished End A: 6.0 mm
thickness and other data ascertained by the Lowest Thickness of Dished End B: 6.0 mm
present examination, due allowance being made Measured wall thickness of the cylindrical portion (5.0 mm)
for conditions of working if unusual or is sufficient to sustain the maximum working pressure of
exceptionally severe. (State minimum thickness of 11.2 Kg/cm².
walls measured during the examination).
16. Where repairs affecting the maximum working Not Applicable
pressure are required, state the working pressure;
a) Before the expiration of period specified in (14) --
b) After the expiration of such period if required --
repairs have not been completed.
c) After the completion of the required repairs. --
17. Other Observations  The Receiver and all the fittings are in good condition.
 Visual inspection of weld joints found OK and no distortion in shape of the receiver.

I certify that on 02.09.2021, this pressure vessel was thoroughly examined so for their construction permitted hand the test/examination
as were necessary made on the same day and that the above.

Signature of the Competent Person


Carrying out the test & examination
Name : Mithun Mitra
Next Due Date: 01.03.2022 Qualification : Mechanical Engineer

Address: Samridhi Vihar Apartment, 508, 5th Floor, Sundarpada, Bhubaneswar – 751 002
Mb: 9830354052/8240149465, Email: [email protected]
Mithun Mitra, B.Tech (Mechanical)
Competent Person under Section 28, 29 & 31 including Hazardous Chemicals
(Approved by Directorate of Factories and Boilers, Govt. Of Odisha)

Ref: MM/VAL/RRLLP/PV/2021/13 FORM NO.- 8 Dated: 02.09.2021


TEST REPORT OF PRESSURE VESSELS
(Sub Section-2 of Section 31 of the factory Act 1948, See Rule – 56 of the Orissa Factories Rules 1950)
1. Name of Occupier (or Factory) M/S RUNAYA REFINING LLP
2. Situation and address of factory M/s. VEDANTA LIMITED, Smelter-1,
Bhurkhamunda,
Jharsuguda, Odisha
3. Name, description and distinctive number of Name: Pressure Vessel-7
3
pressure vessel or plant Location: Cast House -1(FCA for 36000 M /h Bag House)
Capacity- 272.0 Ltr
4. Name and address of manufacturer of the vessel M/s Ingersoll Rand
5. Nature of Process in which it is used For Pneumatic Process Control
6. Particulars of pressure vessel or plant
a) Date of Construction 2019
b) Thickness of walls Thickness of Wall as per Manufacturer
Cylindrical Portion Dished End-A Dished End-B
Original Thickness Data not available
c) Date on which the pressure vessel was first 2019
taken into use
d) Maximum permissible working pressure 11.22 Kg/cm²
recommended by the manufacturer.
e) Design pressure, if known (the history should N.A
be briefly given and examiner should state
whether he has seen the last previous report
7. Date of last hydrostatic test (if any) and pressure 10.08.2019 at 16.30 Kg/cm2
applied.
8. Is the pressure vessel or plant in open or Under the shed
otherwise exposed to weather or to damp?
9. What parts (if any) were inaccessible? Internally not accessible
10. What examinations and tests were made? External Examination: Done
(Specify pressure if hydrostatic test was carried) Internal Examination: Not done
Hydrostatic Test: NA
Pneumatic Test: Not done
Ultrasonic Thickness Test: Done
Cylindrical Portion Dished End-A Dished End-B
5.0 5.0 6.0 6.0 6.1 6.0
11. Condition of pressure vessel or plant (state any Externally:
defects materially affecting the maximum Pressure Vessel-7 Is in good condition and no external
permissible working pressure of the safe working defects found during the examination.
of the pressure vessel or plant).
12. Are the required fittings or appliances provided in Yes
accordance with the rules?
13. Are all the fittings and appliances properly All the fittings are properly maintained.
maintained and in good condition? Have the
pressure settings being checked and corrected?

Address: Samridhi Vihar Apartment, 508, 5th Floor, Sundarpada, Bhubaneswar – 751 002
Mb: 9830354052/8240149465, Email: [email protected]
Mithun Mitra, B.Tech (Mechanical)
Competent Person under Section 28, 29 & 31 including Hazardous Chemicals
(Approved by Directorate of Factories and Boilers, Govt. Of Odisha)

14. Repairs if any required; and the period within At present no repairs required.
which they should be executed and any other
condition which the person conducting the
examination found it necessary to specify for
securing safe working.
15. Maximum permissible working pressure, Lowest Thickness of the Cylindrical Portion: 5.0 mm
calculated from dimensions and from the Lowest Thickness of Dished End A: 6.0 mm
thickness and other data ascertained by the Lowest Thickness of Dished End B: 6.0 mm
present examination, due allowance being made Measured wall thickness of the cylindrical portion (5.0 mm)
for conditions of working if unusual or is sufficient to sustain the maximum working pressure of
exceptionally severe. (State minimum thickness of 11.2 Kg/cm².
walls measured during the examination).
16. Where repairs affecting the maximum working Not Applicable
pressure are required, state the working pressure;
a) Before the expiration of period specified in (14) --
b) After the expiration of such period if required --
repairs have not been completed.
c) After the completion of the required repairs. --
17. Other Observations  The Receiver and all the fittings are in good condition.
 Visual inspection of weld joints found OK and no distortion in shape of the receiver.

I certify that on 02.09.2021, this pressure vessel was thoroughly examined so for their construction permitted hand the test/examination
as were necessary made on the same day and that the above.

Signature of the Competent Person


Carrying out the test & examination
Name : Mithun Mitra
Next Due Date: 01.03.2022 Qualification : Mechanical Engineer

Address: Samridhi Vihar Apartment, 508, 5th Floor, Sundarpada, Bhubaneswar – 751 002
Mb: 9830354052/8240149465, Email: [email protected]
Mithun Mitra, B.Tech (Mechanical)
Competent Person under Section 28, 29 & 31 including Hazardous Chemicals
(Approved by Directorate of Factories and Boilers, Govt. Of Odisha)

Ref: MM/VAL/RRLLP/PV/2021/14 FORM NO.- 8 Dated: 02.09.2021


TEST REPORT OF PRESSURE VESSELS
(Sub Section-2 of Section 31 of the factory Act 1948, See Rule – 56 of the Orissa Factories Rules 1950)
1. Name of Occupier (or Factory) M/S RUNAYA REFINING LLP
2. Situation and address of factory M/s. VEDANTA LIMITED, Smelter-1,
Bhurkhamunda,
Jharsuguda, Odisha
3. Name, description and distinctive number of Name: Pressure Vessel-8
3
pressure vessel or plant Location: Cast House -1(Briquiette Plant for 45000 M /h
Bag House)
Capacity- 272.0 Ltr
4. Name and address of manufacturer of the vessel M/s Ingersoll Rand
5. Nature of Process in which it is used For Pneumatic Process Control
6. Particulars of pressure vessel or plant
a) Date of Construction 2019
b) Thickness of walls Thickness of Wall as per Manufacturer
Cylindrical Portion Dished End-A Dished End-B
Original Thickness Data not available
c) Date on which the pressure vessel was first 2019
taken into use
d) Maximum permissible working pressure 11.22 Kg/cm²
recommended by the manufacturer.
e) Design pressure, if known (the history should N.A
be briefly given and examiner should state
whether he has seen the last previous report
7. Date of last hydrostatic test (if any) and pressure 10.08.2019 at 16.30 Kg/cm2
applied.
8. Is the pressure vessel or plant in open or Under the shed
otherwise exposed to weather or to damp?
9. What parts (if any) were inaccessible? Internally not accessible
10. What examinations and tests were made? External Examination: Done
(Specify pressure if hydrostatic test was carried) Internal Examination: Not done
Hydrostatic Test: NA
Pneumatic Test: Not done
Ultrasonic Thickness Test: Done
Cylindrical Portion Dished End-A Dished End-B
5.0 5.0 6.0 6.0 6.1 6.0
11. Condition of pressure vessel or plant (state any Externally:
defects materially affecting the maximum Pressure Vessel-8 Is in good condition and no external
permissible working pressure of the safe working defects found during the examination.
of the pressure vessel or plant).
12. Are the required fittings or appliances provided in Yes
accordance with the rules?
13. Are all the fittings and appliances properly All the fittings are properly maintained.
maintained and in good condition? Have the
pressure settings being checked and corrected?

Address: Samridhi Vihar Apartment, 508, 5th Floor, Sundarpada, Bhubaneswar – 751 002
Mb: 9830354052/8240149465, Email: [email protected]
Mithun Mitra, B.Tech (Mechanical)
Competent Person under Section 28, 29 & 31 including Hazardous Chemicals
(Approved by Directorate of Factories and Boilers, Govt. Of Odisha)

14. Repairs if any required; and the period within At present no repairs required.
which they should be executed and any other
condition which the person conducting the
examination found it necessary to specify for
securing safe working.
15. Maximum permissible working pressure, Lowest Thickness of the Cylindrical Portion: 5.0 mm
calculated from dimensions and from the Lowest Thickness of Dished End A: 6.0 mm
thickness and other data ascertained by the Lowest Thickness of Dished End B: 6.0 mm
present examination, due allowance being made Measured wall thickness of the cylindrical portion (5.0 mm)
for conditions of working if unusual or is sufficient to sustain the maximum working pressure of
exceptionally severe. (State minimum thickness of 11.2 Kg/cm².
walls measured during the examination).
16. Where repairs affecting the maximum working Not Applicable
pressure are required, state the working pressure;
a) Before the expiration of period specified in (14) --
b) After the expiration of such period if required --
repairs have not been completed.
c) After the completion of the required repairs. --
17. Other Observations  The Receiver and all the fittings are in good condition.
 Visual inspection of weld joints found OK and no distortion in shape of the receiver.

I certify that on 02.09.2021, this pressure vessel was thoroughly examined so for their construction permitted hand the test/examination
as were necessary made on the same day and that the above.

Signature of the Competent Person


Carrying out the test & examination