LSIS VFD Firmware Flash Procedure: Purpose
LSIS VFD Firmware Flash Procedure: Purpose
iS7
Purpose
This document provides the step by step procedure for flashing firmware on an LSIS iS7 VFD using the Smart Copier.
This procedure should be followed whenever an application demands custom application specific firmware or an update to
the latest factory firmware.
For questions or assistance with this procedure please contact LSIS Technical Support.
Phone: 800-891-2941 Email: [email protected]
1. Necessary Items
Smart Copier (the below items are included with purchase) LSIS Order Code: 64090112
o 4 qty AA Batteries
o SD Card
Smart Copier Gender (order both this and the Smart Copier!) LSIS Order Code: 64090124
o 10-pin cable
o Gender Connectors for S100, H100, and iS7
No file extension
Computer with SD card slot
Flash File
LSIS iS7 VFD
Figure 1
Figure 2
1
10-pin
Gender ribbon cable
Smart
Copier
Figure 3
e. Power down the VFD. The VFD must be powered down when flashing the firmware.
f. Slide the Gender housing back to expose the pins which will be connected to the drives flash port. See
Figure 4.
Plastic housing
slides back
Figure 4
g. Gain access to the flash port by removing the keypad and the front cover. See Figure 5.
Figure 5
h. Connect the “iS7 Main” Gender to the VFD flash port. Take note that the Gender connection direction
and placement must be correct. This is printed on the Gender board and also explained in Figure 6
below. The GND pin should be on the bottom and all 7 pins should be plugged in to the right side of the
flash port.
Left
portion of
flash port
is not
used
Ground
pin is
DOWN
Figure 6
f. In the MAK Group enter the correct drive Capacity (kW) and Voltage in MAK01 (use the VFDs nameplate
to verify the drive kW size first, use the HD kW rating). i.e. 0.75kW-2 = 75kW, 230V
g. Complete.