145 KV Current Transformer Type: Imb 145: Description SR. NO. Rev
145 KV Current Transformer Type: Imb 145: Description SR. NO. Rev
1 2 3 4 5 6 425
CLIENT:
SR. OFREFERENCE
STD DRGS/ REV. DESCRIPTION
(AS APPLICABLE) NO. DOCUMENTS
END CUSTOMER: 1. 1HYT903320-017 A GENERAL ARRANGEMENT
APTRANSCO 2. 1HYT903320-018 A RATING PLATE
3. 1HYT903320-019 B SECONDARY TERMINAL BOX
B W.O. NO.: B
(AS APPLICABLE)
JAKKALA Digitally signed by
JAKKALA DEVANAND
PROJECT:
Chief Engineer/Construction
(AS APPLICABLE)
(AS APPLICABLE)
QTY.:
(AS APPLICABLE)
1 2 3 4 5 6
64
1 2 3 4 5 6
425
This drawing is a COMPUTER ORIGINAL
28 85 8
Ø12
A (4X)
A-A 35
18
and does not require signature
A A
5 100
6 28
Ø35
for its authentication
13 8
1 75
50
12
DETAILS OF EARTHING TERMINAL
DETAILS OF LIFTING LUG
1:4
1:4
11
Min. 80 Ø30±0.1
M43x1.5
2628±25
B B
2328±25 8 DETAILS OF PRIMARY TERMINAL
1:4
16 CORE STACK 1 -
15 BOTTOM TANK & TANK COVER 1 M.S HDG*
14 2
17 14 LIFTING LUG 4 M.S HDG*
9 16
13 TOP CHAMBER 1 M.S HDG*
400±5 Ø22(4X)
prepared.
Sr No. Material
ATMOSPHERE ARE HDG.
We resreve all rights in this document and in the
NOTE : DRAWING APPROVAL SUBJECT TO VALID TYPE TEST DEVANAND Date: 2021.02.04
strictly forbidden. © ABB
17:22:39 +05'30'
250
for its authentication
P1 P2
D3
E
1S1 1S2
RATIO 300/1 AUX. REACTOR CONNECTION DETAIL FOR CORE - ONLY
CORE-1 1S1-1S2 1.CONNECT SHORTING LINK BETWEEN FOR THE RATIO OF
CORE-2 - RESPECTIVELY.
CORE-3 - TAKE OUTPUT FROM .
CORE-4 - 2.DO NOT CONNECT SHORTING LINK FOR THE RATIO OF . 165
CORE-5 -
CORE CORE-1 CORE-2 CORE-3 CORE-4 CORE-5
I A 300/1 - - - -
Vk V/ B VA 5 - - - -
Cl 0.2S - - - -
ISF/ALF <5 - - - -
Io mA - - - - -
Rct Ω - - - - -
D3
6 COPPER WIRE
4 EPDM GASKET
Revision Details:
A New Drawing
NOTES : -
2 DRAIN TUBE
1) DEGREE OF PROTECTION IP 55
2) THE SECONDARY TERMINAL BOX IS HDG. 1 COVER
3) D3 TERMINAL IS FOR THE MEASUREMENT OF POWER FACTOR AND LOSS ANGLE SR NO ITEM DESCRIPTION
4) THE BOX IS SUITABLE FOR ACCOMMODATING SECONDARY CABLES OF 1100 V
and in the information contained there
We reserve all rights in this document
JAKKALA
5) STEEL SHEET 3.15 mm THICK HOT ROLLED Digitally signed by
6) ALL DIMENSIONS ARE IN mm. GENERAL TOLERANCE AS PER ISO: 2768-c JAKKALA DEVANAND
7) NO. OF WIRES SHOWN IN THE TERMINAL BLOCK ARE INDICATIVE ONLY
DEVANAND Date: 2021.02.04
is strictly forbidden ©ABB.
17:23:10 +05'30'
NOTE : DRAWING APPROVAL SUBJECT TO VALID TYPE TEST
S-Shorting link Chief Engineer/Construction
REPORTS, TO BE CHECKED DURING ACCEPTANCE TESTS.
Revision DRAWN: CHECKED: APPRD.: file: 3320-019 TOTAL SH.
CURRENT TRANSFORMER 1
SR PDS SN
A 2020-01-11 TYPE : IMB 145 SEC.
B 2021-01-21 TERMINAL BOX : DETAILS
APPSIL 1HYT903320-019 Sh. NO.
1
NOTE : DRAWING APPROVAL SUBJECT TO VALID TYPE TEST 67
4252620/2021/EEMRT-ENE51
REPORTS, TO BE CHECKED DURING ACCEPTANCE TESTS.
Annexure-A
GUARANTEED TECHNICAL PARTICULARS FOR
CURRENT TRANSFORMERS (145kV CT: 300 / 1 A)
1 Type of tank/Installation Dead/Live Tank Type Dead tank, Single phase, Oil Filled, Outdoor
Type
2 Type of mounting Pedestal Mounting
3 Manufacturer's Name and address and APPSIL (Formerly - ABB India Ltd)
Country of Manufacture Maneja, Vadodara – 390013 India
4 Whether Conforming to IEC 61869 standard Yes
5 a) i) Primary and Secondary winding made out of Primary – Aluminum,
Secondary – Copper
ii) Primary windings Aluminum
-Design density for short circuit current - 42.8 Amp/mm2 (approx.)
-Conductivity of metal used - - As per IEC
b) i) Area of cross section of primary winding 736 mm2 (approx.)
ii) Area of cross section of secondary winding Metering : 0.82 mm2 (approx.)
c) Material used for providing secondary Brass
terminals (Primary Terminal will be Al)
d) Material used for providing secondary Brass
terminals
e) Whether Primary is Rigid Bar type in case of Not applicable
live tank
6 Rated primary voltage (kV rms) 132 KV / root3
7 Rated highest voltage (kV rms) 145 KV
8 Rated frequency (Hz) 50 Hz
9 Rated primary current (A) 300 A
10 Rated secondary current (A) 1
11 Ratio taps (on secondary side only) On Secondary Side
12 Type of insulation Class A
13 Seismic acceleration (g) 0.3 g vertical
14 RIV at 1.1 x Rated voltage (mv) < 500 micro volts
15 Tank material and Tank coating Mild Steel, HDG
16 Hardware exposed to atmosphere HDG
17 Bolts, Nuts and Washers MS Hot dip galvanized.
18 Porcelain housing and it make (Single piece Hollow type,
only) IEC/BHEL/ABIL/ADI/Modern or Equivalent
Make
19 Sealing (Nitrogen gas cushion/Metal bellow Nitrogen cushion
20 Instrument security factor <5 (For Metering core only)
21 Whether Tan Delta test tap provided Yes
22 Whether secondary terminal plate is of Yes
molded epoxy resin type
23 Whether primary terminal bushings are of Molded cast resin & Porcelain
molded Epoxy cast resin/Glass fiber
reinforced Polymer
24 Whether all seals are of “O” ring type Yes “O” ring & Flat gasket
25 Whether all “O” Rings are fixed in machined Yes
grooves with adequate space for
compression’
26 Whether the main hollow insulator has the Yes
Chief Engineer/Construction
NOTE : DRAWING APPROVAL SUBJECT TO VALID TYPE TEST
68
4252620/2021/EEMRT-ENE51REPORTS, TO BE CHECKED DURING ACCEPTANCE TESTS.
flanges cemented at both ends
27 Whether “O” Rings are of Nitrile butyl rubber Yes (NBR)
or Viton
28 Whether the Short circuit Ampere-turns of the Yes
CT being supplied is same as type tested CTs
29 Tan Delta Shall be less than 0.350%
37 Rated continuous thermal current (pu) where 120% of rated primary current
pu = rated current
38 1.2/50 micro second impulse withstand 650
voltage (kVp)
39 One minute power frequency withstand 275
voltage (kV rms) of primary winding (Dry)
40 One minute power frequency withstand 3
voltage of secondary winding (kV rms)
41. a) Minimum total creepage distance of insulator 3625 mm (25mm/kV) Porcelain Insulator
bushing (mm)
b) Protected creepage of distance of bushing Not Applicable
(mm)
42 Details of Cores Core-I Core Core-III
-II
42.1 Current Ratios A/A 300/1
42.2 Output burden (VA) 5
42.3 Class of accuracy 0.2S
42.4 Accuracy limit factor / ISF 5
42.5 Min. knee point voltage (kpv) in volts -
42.6 Secondary resistance corrected to 75 deg.C in -
ohms
42.7 Max. Exciting current (mA) at
- 20% of knee point voltage -
- 50% of knee point voltage -
- 100% of knee point voltage -
42.8 Application Metering
43 Weight of oil (Kg.) 75 Kg (approx.)
44 Approximate weight of Copper used (Kgs) 1.6 Kg.
45 Approximate weight of Steel used (Kgs) 160 kg.
46 Total Weight (Kg.) 550 kG. (approx.)
47 Mounting details 400x500 (Please refer GA enclosed)
Chief Engineer/Construction
69
4252620/2021/EEMRT-ENE51
48 Overall dimensions Please refer GA drawing enclosed
49 Characteristics (whether graphs enclosed):
a) Ratio and phase angle curves Yes
b) Magnetization curves Yes
c) Ratio correction factor curves NA
50 Core
a) Area of cross section (sq.cm.) NA
b) Flux density at rated primary current and As per Standard design practice
rated burden
c) Grade Nano Core For Metering Core
Digitally signed by
JAKKALA JAKKALA DEVANAND
DEVANAND Date: 2021.02.04
17:23:58 +05'30'
Chief Engineer/Construction