Ficha Tecnica. Cable Cu BT Ttu 75ºc Elecon
Ficha Tecnica. Cable Cu BT Ttu 75ºc Elecon
TYPE TTU
CONSTRUCTION ELEMENTS
C
A. Solid or stranded bare copper conductor
B. PE Insulation
C. PVC Jacket
STANDARDS
Standar for nonshielded power cables rated 2000 volts or
less for the distribution of electrical energy ICEA S-95-
658/NEMA WC 70
CABLE DATA
Size Construction Conductor Thickness (inches) Aprox. outside Aprox.
AWG/ Diameter diameter Total weight
Ampacity (A)
Diameter of Insulation Jacket
kcmil N° of wires (inches) (inches) 1
wires (inches) (inches) (inches) (pounds/kft)
14 1 0.064 0.064 0.032 0.018 0.163 21 20
12 1 0.081 0.081 0.032 0.018 0.179 30 25
10 1 0.102 0.102 0.032 0.018 0.201 42 35
8 1 0.129 0.128 0.047 0.018 0.258 68 50
14 7 0.024 0.073 0.032 0.018 0.171 22 20
12 7 0.031 0.092 0.032 0.018 0.191 31 25
10 7 0.039 0.115 0.032 0.018 0.215 45 35
8 7 0.049 0.146 0.047 0.018 0.274 71 50
6 7 0.061 0.183 0.047 0.031 0.340 113 65
4 7 0.077 0.232 0.047 0.031 0.388 168 85
2 7 0.097 0.292 0.047 0.031 0.449 253 115
1/0 19 0.074 0.362 0.057 0.047 0.411 402 150
2/0 19 0.084 0.408 0.057 0.047 0.614 498 175
3/0 19 0.094 0.457 0.057 0.047 0.663 613 200
4/0 19 0.106 0.512 0.057 0.047 0.719 757 230
250 37 0.082 0.559 0.067 0.067 0.827 922 255
300 37 0.090 0.612 0.067 0.067 0.879 1089 285
350 37 0.097 0.661 0.067 0.067 0.929 1253 310
400 37 0.104 0.707 0.067 0.067 0.974 1416 335
500 37 0.116 0.789 0.067 0.067 1.096 1743 380
600 61 0.099 0.866 0.082 0.067 1.163 2092 420
750 61 0.111 0.970 0.082 0.067 1.267 2585 475
1000 61 0.128 1.118 0.082 0.067 1.415 3384 545
1 Ampacity of not more than three conductors in raceway or directly buried, based on ambient temperature of 30°C (86 F) Table 310-16 of the National Electrical
Code.
Optional: 9 Extra – flexible conductor (class C) for size ( 14 AWG - 500 kcmil).
9 PVC external Jacket, flame retardant, low smoke and low emition toxic and corrosive gasses.
(Pass vertical tray test – UL 1581)
The data listed above is approximate and subject to normal manufacturing tolerances. Specifications are subject to change without notice.
HC640 / 01 /OCT-05
ELECTROCONDUCTORES, C.A - Office: a/c Av. Valencia, Qta. Elecon. Urb. Las Palmas, Caracas - Apartado 6441 -
Phone: (0212) 7823812 - 3245 – 3411, E-mail: [email protected] - Web Page: www.elecon.com.ve