Features
Sensors
(B)
● Simple operation type Fiber
● ON/OFF and proportional control Optic
Sensors
● Input correction, offset correction, manual reset,
cooling/heating operation functions (C)
Door/Area
● PV deviation indicator Sensors
(D)
Proximity
Sensors
(E)
Pressure
Sensors
Specifications (L)
Panel
Meters
Model TC3YT-B4R3 TC3YT-B4R16
(M)
Power supply 100-240VAC 50/60Hz Tacho /
Allowable voltage range 90 to 110% of rated voltage Speed / Pulse
Meters
Power consumption Approx. 4VA
(N)
Display method 7Segment Red LED Display [Deviation "■" signal(Green), unit display(Yellow)] Display
Units
Character size W7.4 × H15mm
Input type※1 TC:K(CA), J(IC), RTD: DPt100Ω(DIN)
(O)
Control output Relay output 250VAC 3A 1c Relay output 250VAC 16A 1c Sensor
Controllers
Control method ON/OFF and proportional control (common use)
Hysteresis 1 to 100℃ (P)
Switching
Proportional band 0 to 100% Mode Power
Supplies
Offset correction 0 to 100%
(Q)
Control period 1 to 120sec Stepper Motors
& Drivers
Display method ±1digit with a bigger one of ±0.5% of PV or ±1℃ & Controllers
Setting type Setting by front push buttons
(R)
Sampling period 500ms Graphic/
Logic
Dielectric strength 2000VAC 60Hz for 1 minute(between external terminal and case) Panels
Vibration 0.75mm amplitude at frequency of 10 to 55Hz in each of X, Y, Z directions for 1 hour (S)
Field
Relay Mechanical Min.10,000,000 operations Network
Devices
life cycle Malfunction Min.100,000 operations(250VAC 3A resistive load) Min.100,000 operations(250VAC 16A resistive load)
Insulation resistance Min. 100MΩ(at 500VDC megger) (T)
Noise strength ±2kV R-phase and S-phase (pulse width: 1μs) Software
Memory retention Approx. 10 years (When using non-volatile semiconductor memory type)
Environ- Ambient temperature -10 to 50℃, storage: -20 to 60℃
ment Ambient humidity 35 to 85%RH
Protection IP65
Approval
Unit weight Approx. 99g Approx. 103g
※1: NTC sensor input is optional.
※Environment resistance is rated at no freezing or condensation.
H-113
TC3YT
Connections
N.C. N.O.
COM
1 2 3 4 5 6 7 8 9 10 11
※250VAC 3/16A 1c
A B B' Resistive load
RTD SOURCE
100-240VAC
TC(※NTC:Option) 4VA 50/60Hz
※TC3YT-B4R3 : 250VAC 3A
TC3YT-B4R16 : 250VAC 16A
+0.5
0
31.5
Min. 40
36
30
+0.7
68 0
Unit Description
2 1 1. PV(Process value) display(Red)
2. Minus display(Red)
3. Controlling a set value(MD, UP, DOWN)
5 4. Display an operation of control output(Red)
3
5. Display a deviation between PV(Process value) and SV(Set value)
: , (Red) / (Green)
6. PV(Process value) ℃/℉ unit display(Yellow)
4 6
※A temperature sensor converts temperature into electrical signal so that a controller can do ON/OFF the control output.
※The setting is available with the using range.
※The setting range of the SV is limited within the using temperature range.
※Using temperature : It can be set as ℃, ℉ are displayed on the front side.
Power ON
Current temperature
H-114
Simple Operation Type
250 (C)
Door/Area
Press one time Sensors
(D)
Displays SV Flashes Proximity
②SV flashes(twice) or initial value ④Set by (every 1 sec.) Sensors
, keys
SV -300 -280 (E)
Pressure
Sensors
flashes
(every 1 sec.)
⑤Setting finished (F)
Rotary
③To check SV Encoders
(G)
Connectors/
①PV is displayed on operation mode, Sockets
②Press key, the SV is indicated after "SV" is flashing 2 times.
③In case of checking the SV only, after check it pressing key, then it returned to the drive mode. (H)
④In case of changing and setting the SV, set it with , keys. If you press , keys continuously, the SV is increased/decreased with Temperature
Controllers
high-speed.
⑤If press key after setting, the set value is saved and the mode returns to operation.
(I)
※When there is no input for 1 min. for setting operation, it returns to operation mode and the parameter set value is not changed SSRs / Power
Controllers
the prior value is saved.
over 3 sec.
Run mode
(K)
for 2 sec. Set value and initial Timers
value flashes
key key
P Proportional band 0 0 to 100% (L)
Panel
Meters
(M)
Tacho /
The period of proportional key key Speed / Pulse
T control 10 Meters
1 to 120s
(N)
Display
Units
The correction value of key key
RST offset for proportional control 50 0 to 100%
(O)
Sensor
Controllers
(Q)
Stepper Motors
key key & Drivers
InB Input correction value 0 -30 to 30℃ & Controllers
(R)
Graphic/
Logic
● In operation mode, if press key for 2 sec., it enters setting group 1. Panels
At the beginning of key input, SVsignal is displayed. And then Psignal, the first mode of group 1 is displayed for 2 to 3 sec. (S)
Field
It enters the first mode of group 1 for finishing press . Network
Devices
● Parameter will be displayed when entering setting mode.
● Press key one time, parameter move to the next. Moreover for changing a set value, press key. (Set value is flashing
(T)
every one sec.) Software
● Press a key after changing a set value or for the statue of setting change, the setting value is saved and the parameter is
changed to the next.
● In any moment during the setting operation, if press key for 3 sec., the changed value is saved and the mode is changed
to operation mode.
● When there is no input for 1 min. for setting operation, it returns to operation mode and the parameter set value is not
changed the prior value is saved.
●When Pis not "0", [ HYS] parameter is not displayed.
●When Pis "0", ON/OFF control, [ T] and [ RST] parameter is not displayed.
※When it is entered to the setting mode for all cases, applicable parameters will be displayed.
H-115
TC3YT
Parameter 2 Group
over 3 sec.
Run mode Set value and initial
value flashes
over 4 sec.
PtL PtH
High-limit value of
hSC using temperature 400 key key
Low-limit value of
lSC using temperature 0 key key
Cooling/Heating
oFT operation HET COL
LC3 LC2
Factory Default
Parameter 1 group
Parameter Description Setting range Unit Factory default
P Proportional band 0 to 100 % 0
T The period of proportional control 1 to 120 sec 10
RST The correction value of offset forproportional control 0 to 100 % 50
HYS Hysteresis for ON/OFF control 2 to 100 ℃ 2
InB Input correction value -30 to 30 ℃ 0
Parameter 2 group
Parameter Description Setting range Unit Factory default
InT Temperature sensor KCA, JIC, PtH, PtL - JIC
hSC High-limit value of using temperature Refer " Input specifications ℃ 400
lSC Low-limit value of using temperature and range." ℃ 0
oFT Cooling/Heating operation HET COL - HET
oER Output for error ON OFF - OFF
UNT Temperature unit ?C ?F - ?C
LOC Lock OFF, LC1, LC2, LC3 - OFF
H-116
Simple Operation Type
Functions (A)
Photoelectric
Input correction [ InB] Sensors
● Input revise corrects the deviation, occurred from temperature sensor such as thermocouples, RTD, Analogue sensor etc. (B)
Fiber
● There are grades for temperature sensor and high accuracy one is a high price, normal products are usually used. Check the deviation of Optic
Sensors
every thermo sensor precisely to measure temperature accurately.
● Use this mode after measuring deviation occurred from temperature sensor exactly because if measured deviation value is not correct, (C)
displayed temperature will be too high or too low. Door/Area
Sensors
● Setting range : -49 to 50℃(Factory default : 0℃)
E.g.)When even though current temperature is 80℃, display value is 78℃, input correction value should be 2 to display 80℃.
(D)
Proximity
Hysteresis [ HYS ] Sensors
● In the ON/OFF control, the ON/OFF interval of the output is required, this interval is hysteresis. When this interval is too narrow, it causes
(E)
hunting such as chattering by external noise. Pressure
Sensors
● For ON/OFF control, even when control is stable, there is hunting.
Because the hunting is generated by combined cause, HYS set value, response spec, sensor position, etc., it is not regular. To minimize it,
(F)
proper HYS value, the capacity and characteristic of heater, and response and position of sensor need to be considered. Rotary
● Setting range : 1 to 100℃(Factory default : 2℃) Encoders
Setting range
● Hysteresis / proportional band / proportional period is set on parameter (K)
Timers
● Setting range of hysteresis [ HYS ] : 1 to 100℃
● Setting range of proportional band [ P ] : 0 to 100%
● Setting range of control period [ T ] : 1 to 120sec (L)
Panel
● ON/OFF control ↔ Proportional control conversion:When P is 0%, it is ON/OFF control: if there is a value for P, is proportional control. The Meters
parameter of hysteresis [HYS] appears when [P], proportional band, is 0%.
(M)
Tacho /
Offset correction / Manual reset [ RST ] Speed / Pulse
Meters
● When use the proportional control, even when it is stable statue, deviation can occur because of heat capacity and heater capacity. It is
called offset. (N)
Display
● Offset is set on the parameter of inner manual reset [ RST ]. Units
● Offset correction is used only for proportional control. (Not for [ P ]=0%). Therefore if proportional band [ P ] is set as 0%, manual reset
parameter [ RST ] is not shown. (O)
Sensor
● Setting range : 0 to 100% (Factory default : 50%) Controllers
● Set a value as 50% when PV is equal to SV. After control is stable, if measured temperature is lower than SV, set value is over than 50%,
otherwise lower than 50%. (P)
Switching
● Controlling a manual reset[ RST] by control result Mode Power
Supplies
Set a reset lower than 50
(Q)
Stepper Motors
& Drivers
Set temperature Steady-state deviation range & Controllers
(SV) (R)
Graphic/
Measured Set a reset higher than 50 Logic
temperature(PV) Panels
(S)
Field
H-117
TC3YT
Display PV deviation
● It displays the deviation between the PC and the SV.
● When the PV is higher than the SV(PV > SV+2℃), is lighted.
● When the PV is lower than the SV(PV < SV-2℃), is lighted.
● When the deviation of the PV is within ±2℃, is lighted.
Error display
●If Error occurs during the operation, error display flashes every 1 sec.
Display Description
When the input sensor is not connected or its wire is cut.
OPN
(Normal operation after connecting a sensor)
LLL When the measured input temperature is lower than input range of the sensor.
HHH When the measured input temperature is higher than input range of the sensor.
H-118