This document provides information on a simple operation type temperature controller model TC3YT-B4R3. The key details are: 1) It is a simple operation type temperature controller with ON/OFF and proportional control functions. 2) It has inputs for thermocouples and RTD sensors, and control outputs of either 3A relay or 16A relay. 3) The controller has features like input correction, offset correction, and manual reset.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
181 views6 pages

Controlador Temperatura TC3YT

This document provides information on a simple operation type temperature controller model TC3YT-B4R3. The key details are: 1) It is a simple operation type temperature controller with ON/OFF and proportional control functions. 2) It has inputs for thermocouples and RTD sensors, and control outputs of either 3A relay or 16A relay. 3) The controller has features like input correction, offset correction, and manual reset.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

TC3YT Simple Operation Type

DIN W72×H36mm Simple Operation Type (A)


Photoelectric

Features
Sensors

(B)
● Simple operation type Fiber
● ON/OFF and proportional control Optic
Sensors
● Input correction, offset correction, manual reset,
cooling/heating operation functions (C)
Door/Area
● PV deviation indicator Sensors

(D)
Proximity
Sensors

(E)
Pressure
Sensors

Ordering Information (F)


Rotary
Encoders
TC 3 Y T B 4 R 3
(G)
Relay capacity 3 250VAC 3A 1c Connectors/
Sockets
16 250VAC 16A 1c
Control output (H)
R Relay output Temperature
Controllers
Power supply
4 100-240VAC 50/60㎐
Control mode (I)
SSRs / Power
B ON/OFF and proportional control(common use) Controllers
Setting type
T Touch S/W single setting type
Size (J)
Counters
Y DIN W72×H36mm
Digit
3 999(3digit)
(K)
Item Timers
TC Temperature Controller

Specifications (L)
Panel
Meters
Model TC3YT-B4R3 TC3YT-B4R16
(M)
Power supply 100-240VAC 50/60Hz Tacho /
Allowable voltage range 90 to 110% of rated voltage Speed / Pulse
Meters
Power consumption Approx. 4VA
(N)
Display method 7Segment Red LED Display [Deviation "■" signal(Green), unit display(Yellow)] Display
Units
Character size W7.4 × H15mm
Input type※1 TC:K(CA), J(IC), RTD: DPt100Ω(DIN)
(O)
Control output Relay output 250VAC 3A 1c Relay output 250VAC 16A 1c Sensor
Controllers
Control method ON/OFF and proportional control (common use)
Hysteresis 1 to 100℃ (P)
Switching
Proportional band 0 to 100% Mode Power
Supplies
Offset correction 0 to 100%
(Q)
Control period 1 to 120sec Stepper Motors
& Drivers
Display method ±1digit with a bigger one of ±0.5% of PV or ±1℃ & Controllers
Setting type Setting by front push buttons
(R)
Sampling period 500ms Graphic/
Logic
Dielectric strength 2000VAC 60Hz for 1 minute(between external terminal and case) Panels

Vibration 0.75mm amplitude at frequency of 10 to 55Hz in each of X, Y, Z directions for 1 hour (S)
Field
Relay Mechanical Min.10,000,000 operations Network
Devices
life cycle Malfunction Min.100,000 operations(250VAC 3A resistive load) Min.100,000 operations(250VAC 16A resistive load)
Insulation resistance Min. 100MΩ(at 500VDC megger) (T)
Noise strength ±2kV R-phase and S-phase (pulse width: 1μs) Software

Memory retention Approx. 10 years (When using non-volatile semiconductor memory type)
Environ- Ambient temperature -10 to 50℃, storage: -20 to 60℃
ment Ambient humidity 35 to 85%RH
Protection IP65
Approval
Unit weight Approx. 99g Approx. 103g
※1: NTC sensor input is optional.
※Environment resistance is rated at no freezing or condensation.

H-113
TC3YT

Connections
N.C. N.O.
COM

1 2 3 4 5 6 7 8 9 10 11
※250VAC 3/16A 1c
A B B' Resistive load
RTD SOURCE
100-240VAC
TC(※NTC:Option) 4VA 50/60Hz
※TC3YT-B4R3 : 250VAC 3A
TC3YT-B4R16 : 250VAC 16A

Dimensions (unit: mm)


87 84 ●Panel cut-out
72 7 65 12 Min. 91

+0.5
0
31.5
Min. 40
36

30
+0.7
68 0

Unit Description
2 1 1. PV(Process value) display(Red)
2. Minus display(Red)
3. Controlling a set value(MD, UP, DOWN)
5 4. Display an operation of control output(Red)
3
5. Display a deviation between PV(Process value) and SV(Set value)
: , (Red) / (Green)
6. PV(Process value) ℃/℉ unit display(Yellow)
4 6

Input Type And Range


Input sensor Display Temperature range (℃) Temperature range (℉)
K KCA 0 to 999 32 to 999
Thermocuople
J JIC 0 to 400 32 to 752
DPt H PtH 0 to 400 32 to 752
RTD
DPt H PtL -99.9 to 199.9 -146 to 390

※A temperature sensor converts temperature into electrical signal so that a controller can do ON/OFF the control output.
※The setting is available with the using range.
※The setting range of the SV is limited within the using temperature range.
※Using temperature : It can be set as ℃, ℉ are displayed on the front side.

Display For Power ON


For power ON, it displays current temperature after temperature sensor and the type of control output flashes twice(every 1 sec). In case of
error, Error signal flashes instead of current temperature.

Power ON
Current temperature

JIC RLY 250

Displays Flashing twice


temperature (every 1 sec)
sensor

H-114
Simple Operation Type

Checking And Setting SV (A)


Photoelectric
Sensors
● SV can be checked and set on operation mode.
● Press key on operation mode. (B)
Fiber
①Operation mode(display a current temperature) Optic
Sensors

250 (C)
Door/Area
Press one time Sensors

(D)
Displays SV Flashes Proximity
②SV flashes(twice) or initial value ④Set by (every 1 sec.) Sensors

, keys
SV -300 -280 (E)
Pressure
Sensors
flashes
(every 1 sec.)
⑤Setting finished (F)
Rotary
③To check SV Encoders

(G)
Connectors/
①PV is displayed on operation mode, Sockets
②Press key, the SV is indicated after "SV" is flashing 2 times.
③In case of checking the SV only, after check it pressing key, then it returned to the drive mode. (H)
④In case of changing and setting the SV, set it with , keys. If you press , keys continuously, the SV is increased/decreased with Temperature
Controllers
high-speed.
⑤If press key after setting, the set value is saved and the mode returns to operation.
(I)
※When there is no input for 1 min. for setting operation, it returns to operation mode and the parameter set value is not changed SSRs / Power
Controllers
the prior value is saved.

Parameter 1 Group (J)


Counters

over 3 sec.
Run mode
(K)
for 2 sec. Set value and initial Timers
value flashes
key key
P Proportional band 0 0 to 100% (L)
Panel
Meters

(M)
Tacho /
The period of proportional key key Speed / Pulse
T control 10 Meters
1 to 120s
(N)
Display
Units
The correction value of key key
RST offset for proportional control 50 0 to 100%
(O)
Sensor
Controllers

Hysteresis for ON/OFF key key (P)


HYS control 2 1 to 100℃ Switching
Mode Power
Supplies

(Q)
Stepper Motors
key key & Drivers
InB Input correction value 0 -30 to 30℃ & Controllers

(R)
Graphic/
Logic
● In operation mode, if press key for 2 sec., it enters setting group 1. Panels

At the beginning of key input, SVsignal is displayed. And then Psignal, the first mode of group 1 is displayed for 2 to 3 sec. (S)
Field
It enters the first mode of group 1 for finishing press . Network
Devices
● Parameter will be displayed when entering setting mode.
● Press key one time, parameter move to the next. Moreover for changing a set value, press key. (Set value is flashing
(T)
every one sec.) Software

● Press a key after changing a set value or for the statue of setting change, the setting value is saved and the parameter is
changed to the next.
● In any moment during the setting operation, if press key for 3 sec., the changed value is saved and the mode is changed
to operation mode.
● When there is no input for 1 min. for setting operation, it returns to operation mode and the parameter set value is not
changed the prior value is saved.
●When Pis not "0", [ HYS] parameter is not displayed.
●When Pis "0", ON/OFF control, [ T] and [ RST] parameter is not displayed.
※When it is entered to the setting mode for all cases, applicable parameters will be displayed.

H-115
TC3YT

Parameter 2 Group
over 3 sec.
Run mode Set value and initial
value flashes
over 4 sec.

Int Temperature sensor KCA JIC

PtL PtH
High-limit value of
hSC using temperature 400 key key

Low-limit value of
lSC using temperature 0 key key

Cooling/Heating
oFT operation HET COL

oER Output for error OFF ON

UNT Temperature unit ?C ?F

LOC Lock OFF LC1

LC3 LC2

● In operation mode, if press key for 4 sec., it enters setting group 2.


At the beginning of key input, SVsignal is displayed. And then Psignal, the first mode of group 1, is displayed for 2 to 3 sec. for the
moment of 4 sec past, IN.T, the first mode of setting group 2, is displayed. It enters the first mode of group 2 for finishing press key.
● Parameter will be displayed when entering setting mode.
● Press key one time, parameter move to the next. Moreover for changing a set value, press key. (Set value is flashing every 1 sec.)
● Press a key after changing a set value or for the statue of setting change, the setting value is saved and the parameter is changed to
the next.
● In any moment during the setting operation, if press key for 3 sec., the changed value is saved and the mode is changed to operation
mode.
● When there is no input for 1 min. for setting operation, it returns to operation mode and the parameter set value is not changed the prior
value is saved.
※When it is entered to the setting mode for all cases, applicable parameters are displayed.
※When the unit of the using temperature is changed, the SV is changed as 0℃.

Factory Default
Parameter 1 group
Parameter Description Setting range Unit Factory default
P Proportional band 0 to 100 % 0
T The period of proportional control 1 to 120 sec 10
RST The correction value of offset forproportional control 0 to 100 % 50
HYS Hysteresis for ON/OFF control 2 to 100 ℃ 2
InB Input correction value -30 to 30 ℃ 0
Parameter 2 group
Parameter Description Setting range Unit Factory default
InT Temperature sensor KCA, JIC, PtH, PtL - JIC
hSC High-limit value of using temperature Refer " Input specifications ℃ 400
lSC Low-limit value of using temperature and range." ℃ 0
oFT Cooling/Heating operation HET COL - HET
oER Output for error ON OFF - OFF
UNT Temperature unit ?C ?F - ?C
LOC Lock OFF, LC1, LC2, LC3 - OFF

H-116
Simple Operation Type

Functions (A)
Photoelectric
Input correction [ InB] Sensors

● Input revise corrects the deviation, occurred from temperature sensor such as thermocouples, RTD, Analogue sensor etc. (B)
Fiber
● There are grades for temperature sensor and high accuracy one is a high price, normal products are usually used. Check the deviation of Optic
Sensors
every thermo sensor precisely to measure temperature accurately.
● Use this mode after measuring deviation occurred from temperature sensor exactly because if measured deviation value is not correct, (C)
displayed temperature will be too high or too low. Door/Area
Sensors
● Setting range : -49 to 50℃(Factory default : 0℃)
E.g.)When even though current temperature is 80℃, display value is 78℃, input correction value should be 2 to display 80℃.
(D)
Proximity
Hysteresis [ HYS ] Sensors

● In the ON/OFF control, the ON/OFF interval of the output is required, this interval is hysteresis. When this interval is too narrow, it causes
(E)
hunting such as chattering by external noise. Pressure
Sensors
● For ON/OFF control, even when control is stable, there is hunting.
Because the hunting is generated by combined cause, HYS set value, response spec, sensor position, etc., it is not regular. To minimize it,
(F)
proper HYS value, the capacity and characteristic of heater, and response and position of sensor need to be considered. Rotary
● Setting range : 1 to 100℃(Factory default : 2℃) Encoders

Proportional band[ P ] (G)


Connectors/
Sockets
● If current temperature(PV) is within the proportional control, it controls the ratio of ON and OFF during proportional control. At this moment
the term of proportional control for set value is called proportional band
(H)
● Setting range : 0 to 100%(Factory default : 0%) Temperature
Controllers

Control period (Proportional control)[ T ]


(I)
SSRs / Power
● When output the control value by using relay and SSR on the proportional control, it repeats ON for set time and OFF. Controllers
● The set time is called proportional control period.
● Setting range : 1 to 120s(Factory default: 10s) (J)
Counters

Setting range
● Hysteresis / proportional band / proportional period is set on parameter (K)
Timers
● Setting range of hysteresis [ HYS ] : 1 to 100℃
● Setting range of proportional band [ P ] : 0 to 100%
● Setting range of control period [ T ] : 1 to 120sec (L)
Panel
● ON/OFF control ↔ Proportional control conversion:When P is 0%, it is ON/OFF control: if there is a value for P, is proportional control. The Meters
parameter of hysteresis [HYS] appears when [P], proportional band, is 0%.
(M)
Tacho /
Offset correction / Manual reset [ RST ] Speed / Pulse
Meters
● When use the proportional control, even when it is stable statue, deviation can occur because of heat capacity and heater capacity. It is
called offset. (N)
Display
● Offset is set on the parameter of inner manual reset [ RST ]. Units
● Offset correction is used only for proportional control. (Not for [ P ]=0%). Therefore if proportional band [ P ] is set as 0%, manual reset
parameter [ RST ] is not shown. (O)
Sensor
● Setting range : 0 to 100% (Factory default : 50%) Controllers
● Set a value as 50% when PV is equal to SV. After control is stable, if measured temperature is lower than SV, set value is over than 50%,
otherwise lower than 50%. (P)
Switching
● Controlling a manual reset[ RST] by control result Mode Power
Supplies
Set a reset lower than 50
(Q)
Stepper Motors
& Drivers
Set temperature Steady-state deviation range & Controllers

(SV) (R)
Graphic/
Measured Set a reset higher than 50 Logic
temperature(PV) Panels

(S)
Field

Control mode switch Network


Devices

● User can choose ON/OFF and proportional control.


● ON/OFF control - Proportional control conversion: (T)
Software
When P is 0%, it is ON/OFF control: if there is a value for P, is proportional control.
● Factory default : ON/OFF control( P : 0%)

The conversion of temperature unit(℃ / ℉)[ UNT]


● By choosing ?C or ?F on temperature unit setting parameter, [ UNT] conversion is available.
● After choosing a temperature unit, LED is ON.
● Factory default : ?C

H-117
TC3YT

Cooling / Heating operation


● Generally there are two ways to control temperature, one(heat-function) is to heat when PV is getting down(heater). The other(cool-
function) is to cool when PV is getting high refrigerator).
● Setting range: HET(Heat) / COL(Cool) (factory default : HET)

Display PV deviation
● It displays the deviation between the PC and the SV.
● When the PV is higher than the SV(PV > SV+2℃), is lighted.
● When the PV is lower than the SV(PV < SV-2℃), is lighted.
● When the deviation of the PV is within ±2℃, is lighted.

High/low limit setting for using temperature


● Set a high/low limit of temperature and the set range is within using range.
● If setting a high-limit of temperature on [ hSC ], it is a high-limit SV
● If setting a low-limit of temperature on [ lSC ], it is a low-limit SV.
● lSC ≤ SV ≤ hSC. In case of lSC= SV = hSC, the output is OFF.
● If change L.SC and H.SC, the using range and proportional band also are changed.

Error display
●If Error occurs during the operation, error display flashes every 1 sec.

Display Description
When the input sensor is not connected or its wire is cut.
OPN
(Normal operation after connecting a sensor)
LLL When the measured input temperature is lower than input range of the sensor.
HHH When the measured input temperature is higher than input range of the sensor.

● When error [ OPN ] / [ HHH ] / [ LLL ] occur


After the causes of error is solved, it operates normally.
● The priority of 'Error' display : OPN → HHH, LLL

Output setting for error[ oER ]


For error, the statue of output is set by [ oER ] of setting group 2.
● For setting OFF: Output is always OFF for error.
● For setting ON: Output is always ON for error.
● Factory default : OFF

Lock setting[ LOC ]


● This function limits the change of parameters on each setting group.
It can be set setting group 2.
● For setting[ LC1 ], changing the parameter, "Setting group 2", is not available.
● For setting[ LC2 ], changing the parameter, "Setting group 1 + Setting group 2", is not available.
● For setting[ LC3 ], changing the parameter, "Setting group 1 + Setting group 2 + SV setting parameter", is not available.
● For setting [ OFF ], Lock off for all setting group