Etna - Fire Pump Systems in Accordance With EN 12845 Standard Technical Leaflet
Etna - Fire Pump Systems in Accordance With EN 12845 Standard Technical Leaflet
Information about EN 12845 fire protection standard via fixed fire extinguishing systems
Contents
Fire Regulations 3
Fire Standard “EN 12845”
Example Documents 29
2
1. FIRE STANDARD “EN 12845”
y/Pressure
2
1
2
100 % 3 2
1
1
70 %
4
Figure 1
3 www.etna.com.tr
If the pump operates against a closed valve, Eccentric Suction Kit
arrangements should be applied to allow constant
sufficient water flow in order to prevent over- In EN 12845 standard, the eccentric suction kit
heating. This flow should be considered in system’s is obliged to be attached to the suction flange
hydraulic calculation and pump selection. The outlet separately for each pump. Suction performance
should be clearly visible, and outlets should be is improved in this manner as well as air pocket
separated where there are multiple pumps formation in the pipe during suction is prevented.
Figure 26 demonstrates the points to consider
Diesel motor cooling circuits commonly use the
when connecting the eccentric suction kit. In order
same water. However this issue should be taken into
account if additional water has been used. Where to improve suction performance, the other end of
a pressure gauge is assembled on the pump for suction kit should be two or three times bigger
inlet and outlet pressure gauges should be readily than the pump’s suction flange. If the pump’s
reached. suction flange is 50 mm, then other end of the
eccentric suction kit should be at least 65 mm.
Starting Fire Pump Up Also the suction valve should always face the larger
side.
P Max
Graphic 2
4
FIRE PUMP SYSTEMS IN LINE WITH THE
FIRE STANDARD
1. Water, of at least two third capacity, is required In other words, the pump’s NPHS value should be
to occur over the suction axis of the reserve 1 meter more than the NPSH value at the pump’s
tank. maximum capacity. As you know, NPSH shows the
net positive suction pressure.
2. Minimum water level of the pump’s suction axis
(x) should not be higher than 2 m. The assembly, So it indicates the net hydraulic load on the pump’s
to which the pump would be connected, should
suction. While NPSHd showing the value calculated
be bound with a cuff. Furthermore the pump
at the pump’s suction orifice, NPSHr indicates the
pipe should connected to the tank with an
upwards sloping in order to prevent air pocket minimum NPSH value allowing to pump to operate
formation in the pipeline. An eccentric suction without cavitation. EN 12845 demonstrates this
kit is necessary to put to the pump suction in EN condition using the following formula;
12845 norm. This kit would prevent air pocket
formation in the suction pipe. This part should NPSHd = Pa + H - ∑Y
be provided together with the fire pump. A
Pa = atmospheric pressure
flange with a larger diameter than the pump
suction diameter should be welded to the end H = geodesic difference
of special pipe of a length two times the pump
suction diameter with flat top and tapered ∑Y = defines suction pressure losses at pipes, valves,
fittings and elbows.
5 www.etna.com.tr
12
Figure 5
6
3. Reserve Tank (for Positive Water Line)
A single reserve tank is needed for each main This reserve tank to be used for pumps to suck water
pump. (For negative suction pumps only) This is not from the negative suction will prevent any possible
applicable for a pilot pump. water losses in the suction pipe, and the pump will
be prevented to operate dry.
Reserve tank capacities as per the risk classes are indicated below; Comments
Comments
3 Rp1”
10 4 1. Reserve tank
Rp1” 1/2 5
2. Water recirculation pipe
3. Float valve
900 mm
1 Rp1” 1/4
4. Filling valve
7 6
1300 mm
5. Main water supply network
6. Level indicator
Rp1”
Rp1” 7. Drainage outlet
Rp2” Rp2”
8. Non return valve
9
9. Reserve tank valve
8 10. Overflow pipe
11
11. Pressure switch
2 14 7
12. Main pump
Figure 7
7 www.etna.com.tr
Figure 8 demonstrates the reserve tank application system pressure drops down. EN 12845 requires
diagram in a negative suction fire pump assembly the electrical control panel of pilot pumps to be
according to EN 12845 standard. manufactured separately from the electrical control
panel of main pumps. Pilot pumps connected to
12 the system should suck independently. Suction line
5
3 4 of the pilot pumps should not be connected to the
main pumps’ suction line. Consequently following
6 7 2/3L
L results would be prevented;
8 13 14
10 Assuming the Pilot Pump suction pipe (4) is
2
connected to the main pump suction pipe (3) (Figure
9 9), when the pilot pump sucks water, it would not
suck water from the main pump suction pipe only
but from positive level tank as well (1). Main pump
suction line is connected to the positive level tank.
If the positive level tank is emptied, as the system
1 suction line turns to be dry, main pumps and pilot
11 pump would be broken. If there is no electronic level
switch on this tank, the pilot pump would not stop
A and operate dry. So the tank would empty and an
undesired condition would occur. If we think there
is a level switch also, when the level gets low, the
main pumps will enable to fill the tank, and the fire
Figure 8
alarm will enable as well. As it is known, in EN 12845,
3
5 4 as the main fire pumps enable when the pressure
drops down, the fire alarm enables, furthermore
6 L 13
Comments 2/3L these pumps are stopped manually.
8 14 15
1. Test and discharge valve 10
2. Air discharge from
2 the pump, and water
recirculation 9
3. Reserve tank
4. Tank filling
5. Tank overflow pipe
6. Drainage valve pressure switch 1
7. Low level switch to start-up
1 the
B pump
8. Stop valve
9. Ball valve
10. Pump start-up pressure switch
11. Main suction water tank
12. Outlet to sprinkler installation
13. Signal from main pump body
14. Pressure Guage
8
5. Connecting the Pump to Water Supply Network 5.1 Additional Pressurizing Pump
The water supply network can be used for the Here what is called as pressurizing pump is a
pumps to get water. However, in this case, seamless pump enabling when there occur no sufficient
water existence in the water supply network and pressure. Such connections should be realized as
constantly available sufficient water should be demonstrated in Figure 10.
guaranteed. The line coming from the water supply
network is connected to the main pump delivery Comments
collector; when the pressure from the water supply
network becomes insufficient, the main pump will 1. Non return valve size connected to delivery
enable. collector should not be lower than the pipe
diameter.
2. Bypass valve
3 3. Bypass line for water coming from the water
supply network.
4. Non return valve to prevent water returning to
the water supply network.
5. Water supply network (Municipality should
1 guarantee that in this line there would be water
2 with constant and sufficient pressure and flow
rate)
4
Figure 10
5
3
4
Figure 11
9 www.etna.com.tr
6. Diesel Pump 6.1 Underground Diesel Pump
Considering for the cases of the water supply Diesel pumps may be placed underground fire rooms when
network being cut by authorities during a fire or the necessary. In this case, a ventilator should be positioned to
network getting disabled, EN 12845 proposes a diesel throw the heated air inside out for the air cooling Diesel motor
and fresh air should be supplied to inside through another vent
pump to be put next and in parallel to the electrical
as demonstrated in Figure 12.
pump. In this case, the diesel pump is required to
be of same capacity as the electrical pump; and the
diesel pump is designed to immediately enable with 1
the pressure dropping when the electrical pump
gets disabled. Thus seamless water supply to the 2
sprinkler system would be possible.
5
There are number of points to consider regarding
diesel pump assembly and surrounding environment.
These are, in the order; 3
4
3
1
Figure 15
Remote controlled
alarm panel should
11 www.etna.com.tr
7.3 Fuel tank Particularly these openings being above and
near the ceiling would be appropriate in terms of
If there is a pump connected to a diesel motor in the ventilation and room cooling as the heated air rises
fire pump room, special precautions for the fuel tank up. Opening surface should not be lower than 0.1
should be taken. The leading risk regarding fuel tank m². A more accurate calculation should be made for
use is fuel leakage. A flammable liquid around the each location separately. (Figure 17)
diesel motor introduces a fire risk at any moment.
Fuel tank should be assembled away from the
diesel motor and onto the foot, aligned to the fuel
pump of the diesel motor, without allowing any fuel
leakage. Diesel motor should not suck the fuel from Constantly open
a deeper level, in contract, the fuel should arrive the venting
Constantly open
pump with a positive pressure. In this way air pocket venting
12
7.6 Cooling Diesel Motor Down 7.6.1.1 Water-to-water Cooling System Connection
Diesel motors can be cooled down in two ways: A heat exchanger with a capacity suitable for water-
cooling the water with air via radiator or cooling the to-water cooling system should be picked. Picked
water with water via heat exchanger. Diesel motor exchanger should be able to prepare cooling water
is cooled down with air in air cooling diesel motors. which would seamlessly cool the diesel pump when
Such cooling motors are much cheaper and simpler. operating at full capacity. A pressure dropper (3)
But these have lower capacities than water radiator should be put in the circuit and the pressure should
or water exchanger motors. Water cooling motors be prevented to increase over 10 bar in order to
are especially preferred at 20 kW sizes. For both block any exchanger damage. A bypass line should
systems, proper heated air removal is substantial. definitely put within the assembly established
Air temperature inside should be prevented to between the diesel motor and exchanger. In case
increase. (Figure 20) of any problem with the main line, the bypass line
should be opened manually. Electrical solenoid
valve (4) put in the circuit should be opened upon
main pump enabling. Solenoid valve opening should
be monitored with the signal lamp and on the panel
in the main panel room. (Figure 22)
Cold air inlet
3 2 1
Figure 20
Drainage
Figure 21
13 www.etna.com.tr
COMPLEMENTARY PRODUCTS
Figure 23
Figure 25
Comments
14
GENERAL PROPERTIES OF ETNA FIRE PUMP
SYSTEMS IN LINE WITH EN 12845
• Our products are modular, and each module is manufactured in accordance with EN
12845 standard.
• Water speed in fire pumps, especially within the suction line, is substantial, and EN
12845 standard approach to the subject is more precise than other standards. Water
speed should not exceed 1.8 m/s in a positive suction system and 1.5 m/s in a negative
suction system.
• Eccentric reduction suction kit is standard, including negative suction condition.
• Motor powers are designated to operate with a capacity of 140% of the nominal flow
rate. When pumps operate at 140% capacity, the pressure should not drop down than
70%.
• Negative code suction may be forced using end suction type pumps. However it is
always necessary to employ an “operation tank” for each pump.
• Pumps start-up with the command taken from the pressure switch and then stopped by
hand (manually).
• Diesel pump module is activated in line with EN 12845 standard.
• Diesel pump emergency manual operation is also in line with the standard.
• Main pump modules have inlets that are suitable to be connected to 1" forward-
feed tanks (operation tank) in case they will be operated by drawing water from
underground tank (negative suction).
• To prevent mechanical seals to be damaged due to overheating during closed valve
test operations, pump modules would be able to circulate back to the water tank or the
operation tank.
• The sections allocated for pump modules should be sprinkler protected.
• EN 12845 Fire-fighting booster sets are factory-calibrated and tested. Thus they enable
fast and easy assembly.
• Remotely monitored alarm panel provides audio and visual warnings.
• All measurements and calculations are for clean water at +20°C.
• Motors are picked for constant operation conditions.
• Even the power is out in the building, electrical motors should supply from a separate
panel.
• Required diesel motor shaft power is calculated to be 10% higher.
• Motor-pump connection is made with flexible coupling.
• Pumps are back-pull out type and easy to maintain.
• Suction and delivery line valves are butterfly valves, and these valves can be established
together with monitoring keys, if necessary.
• Pilot pump involved in the system should be picked to provide a flow rate with a
capacity of 10% of the nominal value and a pressure with a capacity of 110% of the
nominal value.
15 www.etna.com.tr
www.etna.com.tr
CODING OF ETNA FIRE PUMP SYSTEMS IN LINE
WITH EN 12845
YE - EN 12845
Norm YN - NFPA 20
YA - Alarm Kit
16
ELECTRIC DRIVEN FIRE PUMP
Specifications
17 www.etna.com.tr
ELECTRIC / DIESEL DRIVEN FIRE PUMP
Specifications
18
FIRE PUMP ELECTRICAL SUPPLY ASSEMBLY
Fire Pump Supply Main Switch Panel Each monitoring situations should be separately
and visibly defined in the pump room. On the same
Main switch panel of the building and its extension place, also pump operation and failure alarms should
should be located to the fire section to be not used be acoustically and visually shown to the watching
for any purpose another than supplying power. principal staff.
When the connections on the main switch panel Visible failure notification should be yellow. Audio
providing power to the building and its extension signals should be of at least 75 dB signal strength
are cut, power supply to the control circuit should and able to be muted. A lamp experiment should be
not be closed. Each key at power supplies of spray performed to check signal lamps.
pumps should be labeled as follows:
Diesel Motor Pump Modules
DO NOT TURN OFF THE POWER Diesel motor should be able to operate at full capacity
at a high place with a constant power output in line
SUPPLY TO THE FIRE PUMP MOTOR with ISO 3046. The pump reaches full capacity 15
DURING FIRE! seconds after it starts to operate. Horizontal pumps
can be driven directly. Fuel tank is made of welded
Letter height within the expression above should be steel sheet, and if multiple machinery are being
at least 10 mm and in white on a red backplane. The used, their fuel tank and supplies are positioned
switch should be protected against breakage. separately. The fuel tank is positioned to a location
higher than the fuel pump of the motor in a way
Main Switch Panel and Pump Control Mechanism that will provide positive pressure. However, this
location is not just above the motor. There should be
When calculating the cable thickness to be used, the enough fuel for the fuel tank to meet the following
current should be estimated by taking 150% of the conditions and to operate at full capacity.
maximum possible full load current.
• 3 hours for DT
a) It should be able to automatically operate the (Low danger class, water tank volume 15 m3)
motor when received a signal from pressure
keys, • 4 hours for ST
b) Motor should be able to operate when activated (Standard danger class, water tank volume
manually, 23 m3)
c) It should be able to stop the motor only by
manual activating. • 6 hours for YTI and YTD
(High danger class, water tank volume over
An ammeter should be installed to the control 23 m3)
mechanism.
Emergency Manual Operation System
Monitoring Pump Operation
The emergency manual operation systems that
Following conditions should be monitored. are operated with the power supplied from both
• Three phase alternating current (AC) power accumulators should have breakable covers. For
supply for the motor, periodic inspections, system operation should be in
• The pump desired to operate, line with the rules defined in EN 12845.
• Pump operation,
• Startup failure.
19 www.etna.com.tr
ELECTRIC DRIVEN PUMP PROTECTION -
CONTROL PANEL IN ACCORDANCE WITH EN 12845
20
DIESEL DRIVEN PUMP PROTECTION -
CONTROL PANEL IN ACCORDANCE WITH EN 12845
21 www.etna.com.tr
Alarm Panel and Valve Monitoring Panel Valves
Fire-fighting booster sets must always have an alarm Relevant technicians should follow whether those
panel. Fire-fighting booster sets, which are not used valves on the booster set are open. Therefore, thanks
for most of the time, should be kept ready for a fire. to the micro switch to be installed to the on/off arms
Therefore an alarm panel is put and added to the of the butterfly valves used, the valves are readily
system to warn the authorized staff for maintenance monitored at the technicians’ location via remote
in case the booster set does not operate or fall from monitoring panel. This feature is conducted with a
being ready. Following signals are required to be rising stem valve in NFPA 20 but whether the valve
received within EN 12845 norm. is fully open or closed cannot be understood. Thanks
• Energy on to this system, a signal will come to the remote
• Pump enabling request monitoring panel when the valve is tampered, and
• Pump is running technicians will be warned with a visual and audio
• Operation error warning.
This alarm panel receives all these warnings from the
booster set but in order to allow relevant technicians
to see or hear these warnings, alarm panels should 1 Remote Monitoring Alarm Panel (standard)
be built separately and put to the locations, at which • All panel outlets are 12 Vdc. Inlet 230 Vac.
technicians stand, through an extension cord. In this • Rectifier inlet 230 Vac – outlet 12 Vdc 7Ah.
way any problem which may arise in the booster set Led light visual warning.
would be realized by relevant technicians and the • 95 dB. audio warning.
required maintenance would be provided. • Led test button.
• Alarm silencing button:
• Battery charge ON – OFF switch.
• Electrical and diesel with 2 pieces of 5 m multi-
plug cable. Connected to the pump panels.
• When desired, 5 m extension cables are optional
together with male/female end plugs..
Figure 48
22
Operation Alarm Indicator Alarms for Diesel Pump Set
Each of the below given status is displayed in the pump 1. Automatic mode is closed YELLOW (visual and
set location and maintenance room. audio alarm)
a) Using a key preventing the automatic operation of 2. Operation failure YELLOW (visual and audio alarm)
the motor. 3. Operating (water flow) (fire alarm) RED (visual and
b) Not being able to operate the motor after six audio alarm)
attempts. 4. Failure in the control system YELLOW (visual and
c) Pump operation. audio alarm)
d) Diesel motor control mechanism failure. Warning 5. Pump suction valve is open GREEN (visual alarm)
lights should operate as required. 6. Pump suction valve is closed RED (visual alarm)
7. Pump outlet valve is open GREEN (visual alarm)
Alarm Transmission 8. Pump outlet valve is closed RED (visual alarm)
9. No water in the water tank RED (visual and audio
Alarms, of which functions to be monitored and alarm alarm stopping the pump is not allowed EN 12845)
levels are stated in EN 12845 standard, are assembled 10. No fuel in the fuel tank RED (visual and audio alarm)
to an alarm panel in the sprinkler control room or pump (when nominal filling level drops to 25%,”MIN YAKIT
room and offer visually or acoustically (75 dB) warning as (MIN FUEL)” warning is displayed).
per the alarm significance. Alarm systems are mounted to
a fixed control spot in or out of the facility to transmit the Pilot (Jockey) Panel
alarm to the responsible individual for intervention.
All its outlets are low voltage except for motor connection.
Alarm and Valve Control Panel
• Energy warning lamp
Alarms can be monitored remotely as defined in the • Pump running lamp
standard based on their significance. • Failure lamp
• Signals that can be indications of fire like water flow • Automatic-Manual removable key switch
signal are displayed as fire alarm (red alarm). • Phase sequence
• In case of fire, the technical failures like power failure • Other electrical value are monitored from Main
that prevents the system to work correctly are displayed Electrical motor panel
as failure alarms (yellow alarm):
23 www.etna.com.tr
EN 12845 & NFPA 20 NORMS COMPARISON TABLE
SPECIFICATIONS EN 12845
PUMP BODY Rear Suction Back Pull Out Type
MATERIAL PROPERTIES
a given pressure.
WATER FLOW RATE Flow rate should not exceed 1.8 m/s in positive suction and 1.5 m/s in negative suction.
When the pressure in the mains drops to a value that is not lower than 0.8 P (P; Pressure
in Closed Valve Condition), the first pump set should not automatically start-up. In a two-
STARTING THE PUMP UP
pump set, the second pump should start-up before the pressure drops to a value not lower
than 0.6 P. The pump should operate until stopped manually once starts-up.
YES (They are used for each pump in systems intended for negative suction. It should
OPERATION TANK be 100 L in DT and 100 and 500 L in ST and YT, respectively. Pumps would automatically
enable when the water level in tanks drops to 2/3.)
YES (Pump suction diameter cannot be smaller than DN80 in negative suction and than
DN 65 in positive suction. To this end, the suction part of pump should be connected to a
ELECTRICAL SUCTION KIT linear or tapered pipe of two diameters long. Tapered pipe should have a horizontal cap
part and maximum immersing angle not exceeded 20°. Valves should be installed to this
AUXILIARY EQUIPMENT
24
NFPA 20 NOTES
Detachable Body or Rear Suction Type
GG25 or GGG40
Bronze or AISI 304
AISI 316
Soft Seal (5 Lines)
Grease Lubrication Rolling Bearing
Connecting Coupling
There is no certain limitation. 100% back-up for pumps is inevitable in terms of fire safety.
YES
YES
YES
YES
Provided that an operation tank is used, the negative code
suction pump should be prevented to operate dry. EN 12845
NO
allows such application. In NFPA 20, there is no application for
negative code suction with norm pumps.
YES (For each single pump)
YES (It should be separate in suction and delivery line.)
YES (Is is used for body cooling.)
Eccentric suction kit use ensures the water directed to the
pump to flow in laminar flow, air like flow-breaking factors to be
prevented to reach the pump, flow rate to be dropped down due
NO to a passage to a level bigger diameter than anticipated, and
frictional losses to be declined. With EN 12845 eccentric suction
kit use, a substantial advantage is acquired for the pump suction
line.
YES
YES
YES
YES
Locked in the Panel
YES
YES
YES
YES
NO
Accessible on the Panel
YES
YES
YES
YES
25 www.etna.com.tr
EN 12845 BOOSTER SET VERSIONS
Description
Description
Description
Description
Description
MODULAR SYSTEM
A B C
2 2
3 4 3 4
3 4
1 1 2
1
Diesel pump module A Diesel main pump module Horizontal pump module Vertical pump module
Diesel pump module A
B Diesel main pump
Pilot pump modulemodule Horizontal pump module Vertical pump module
B
C Pilot pump main
Electrical module
pump module
C Electrical main pump module
26
SAMPLE DOCUMENTS
E
PL
M
SA
E
PL
M
SA
27 www.etna.com.tr
Dudullu Organize Sanayi Bölgesi 2. Cadde No: 14
34775 Ümraniye İstanbul / Turkey
Tel : +90 216 561 47 74 (Pbx) • Fax : +90 216 561 47 50
www.etna.com.tr/en • [email protected] customer service
28