Design Mix (HSC)
Design Mix (HSC)
BASIC DATA :
General
Grade of concrete 40 N/mm2
Workability 0.8 Compacting factor
Quality control Good
Exposure Mild
Accepted Proportion of Low Results 1 in 20 (Table 2 of IS : 10262)
Note
Aggregate if used in saturated surface dry (SSD) condition, it will absorb water, amount of mixing water to be increased.
Aggregate if not used in SSD condition, allowance for free surface moisture to be made, amount of mixing water to be decreased.
Cement
Brand -
Type OPC
Grade 43
Minimum cement content 300 kg/m3 (Table-5 of IS : 456-2000)
Maximum water cement ratio 0.55 (Table-5 of IS : 456-2000)
Specific Gravity 3.15
Fine Aggregate(SSD)
Source
Zone II
Specific Gravity 2.65
Water absorption 1%
Free moisture 0%
600 micron 60
300 micron 12
150 micron 2
Coarse Aggregate
Source
Size 20 mm
Shape Angular
Specific Gravity 2.74
Water absorption 0.5 %
Free moisture 0%
Water
Density of water 1 gm/cc
Air
Entrapped air percentage 1%
Admixture
Admixture dosage 0.78 %
CALCULATION :
STEP 1 : Target Mean Strength of Concrete
Target mean strength = fck' = fck + ts (clause 4.2 of IS : 10262)
fck' = Target average compressive strength at 28days
fck = Characteristic compressive strength at 28days 40 N/mm2
s = Standard Deviation from IS 456 : 2000 5 N/mm2
X =factor based on the grade of the concrete 6.6 N/mm2
s = Standard Deviation considered 5 N/mm2 (Table 1 of IS : 10262)
t = Tolerance factor 1.65
fck' = Target average compressive strength at 28days 48.25 N/mm2
b) Sand 38.55 kg
d) Water
i) For water cement ratio = 0.35 17.5 litre
ii) Extra water for absorption by sand @ 0.5% by mass = 0.39 litre
iii) Extra water for absorption by coarse aggregate @ 0.5% by mass = 0.65 litre
iv) Deduct water for free moisture present in sand @ 2% by mass = 0.00 litre
v) Deduct water for free moisture present in coarse aggregate @ 2% by mass = 0.00 litre
Actual quantity of water 18.5 litre
e) Actual quantity of sand after allowing for mass of free moisture 38.55 kg
ACTUAL QUANTITY
Water 18.5 litre
Cement 50 kg
Sand 38.55 kg
Coarse Aggregate - Fraction I 77.47 kg
Coarse Aggregate - Fraction II 51.64 kg
MIX DESIGN
BASIC DATA :
General
Grade of concrete 65 N/mm2
Workability 120 mm (Slump)
Quality control Good
Exposure Severe
Mineral Admixture Flyash Conforming to IS 3812 (Part I):2013
Silica fume Conforming to IS 15388-2003
Chemical Admixture Superplasticizer (Polycarboxylate ether based)
Method of concrete placing Pumping
Type of Aggregate Crushed Angular Aggregate
Accepted Proportion of Low Results 1 in 20 (Table 2 of IS : 10262)
Note
Aggregate if used in saturated surface dry (SSD) condition, it will absorb water, amount of mixing water to be increased.
Aggregate if not used in SSD condition, allowance for free surface moisture to be made, amount of mixing water to be decreased.
Cement
Brand -
Type OPC
Grade 53
Minimum cement content 320 kg/m3 (Table-5 of IS : 456-2000)
Maximum water cement ratio 0.45 (Table-5 of IS : 456-2000)
Specific Gravity 3.15
Flyash
Dose 15 % (Table-9 of IS : 10262-2019)
Specific Gravity 2.2
Silica fume
Dose 5% (Table-9 of IS : 10262-2019)
Specific Gravity 2.2
Fine Aggregate(SSD)
Source
Zone II
Specific Gravity 2.65
Water absorption 1%
Free moisture 0%
Coarse Aggregate
Source
Size 20 mm
Shape Angular
Specific Gravity 2.74
Water absorption 0.5 %
Free moisture 0%
Water
Density of water 1 gm/cc
Air
Entrapped air percentage 0.5 % (Table-6 of IS : 10262-2019)
CALCULATION :
STEP 1 : Target Mean Strength of Concrete
Target mean strength = f ck' = fck + ts (clause 4.2 of IS : 10262)
fck' = Target average compressive strength at 28days
fck = Characteristic compressive strength at 28days 65 N/mm2
s = Standard Deviation from IS 456 : 2000 5 N/mm2
X =factor based on the grade of the concrete 8 N/mm2 (Table 1 of IS : 10262)
s = Standard Deviation considered 5 N/mm2 (Table 2 of IS : 10262)
t = Tolerance factor 1.65
fck' = Target average compressive strength at 28days 73.25 N/mm2
Mix Calculations
b) Sand 77.53 kg
d) Water
i) For water cement ratio = 0.285337662337662 14.2668831168831 litre
ii) Extra water for absorption by sand @ 1% by mass = 0.78 litre
iii) Extra water for absorption by coarse aggregate @ 0.5% by mass = 0.78 litre
iv) Deduct water for free moisture present in sand @ 2% by mass = 0.00 litre
v) Deduct water for free moisture present in coarse aggregate @ 2% by mass = 0.00 litre
Actual quantity of water 15.8 litre
e) Actual quantity of sand after allowing for mass of free moisture 77.53 kg
BASIC DATA :
General
Grade of concrete 65 N/mm2
Workability 120 mm (Slump)
Quality control Good
Exposure Severe
Mineral Admixture GGBS Conforming to IS 16714 :2018
Chemical Admixture Superplasticizer (Polycarboxylate ether based)
Method of concrete placing Pumping
Type of Aggregate Crushed Angular Aggregate
Accepted Proportion of Low Results 1 in 20 (Table 2 of IS : 10262)
Note
Aggregate if used in saturated surface dry (SSD) condition, it will absorb water, amount of mixing water to be increased.
Aggregate if not used in SSD condition, allowance for free surface moisture to be made, amount of mixing water to be decreased.
Cement
Brand -
Type OPC
Grade 53
Minimum cement content 320 kg/m3 (Table-5 of IS : 456-2000)
Maximum water cement ratio 0.45 (Table-5 of IS : 456-2000)
Specific Gravity 3.15
GGBS
Dose 40 % (Table-9 of IS : 10262-2019)
Specific Gravity 3
Fine Aggregate(SSD)
Source
Zone II
Specific Gravity 2.65
Water absorption 1%
Free moisture 0%
Coarse Aggregate
Source
Size 20 mm
Shape Angular
Specific Gravity 2.74
Water absorption 0.5 %
Free moisture 0%
Water
Density of water 1 gm/cc
Air
Entrapped air percentage 0.5 % (Table-6 of IS : 10262-2019)
CALCULATION :
STEP 1 : Target Mean Strength of Concrete
Target mean strength = f ck' = fck + ts (clause 4.2 of IS : 10262)
fck' = Target average compressive strength at 28days
fck = Characteristic compressive strength at 28days 65 N/mm2
s = Standard Deviation from IS 456 : 2000 5 N/mm2
X =factor based on the grade of the concrete 8 N/mm2 (Table 1 of IS : 10262)
s = Standard Deviation considered 5 N/mm2 (Table 2 of IS : 10262)
t = Tolerance factor 1.65
fck' = Target average compressive strength at 28days 73.25 N/mm2
Mix Calculations
d) Water
i) For water cement ratio = 0.45 22.5 litre
ii) Extra water for absorption by sand @ 1% by mass = 1.18 litre
iii) Extra water for absorption by coarse aggregate @ 0.5% by mass = 1.18 litre
iv) Deduct water for free moisture present in sand @ 2% by mass = 0.00 litre
v) Deduct water for free moisture present in coarse aggregate @ 2% by mass = 0.00 litre
Actual quantity of water 24.9 litre
e) Actual quantity of sand after allowing for mass of free moisture 117.91 kg
g) Mineral admixture
GGBS 33.33 kg
ACTUAL QUANTITY
Water 24.9 litre
Cement 50 kg
Sand 117.91 kg
Coarse Aggregate - Fraction I 141.29 kg
Coarse Aggregate - Fraction II 94.19 kg
GGBS 33.33 kg
Table 5
Maximum
Minimum
free water-
Exposure Cement
cement
content
ratio
Mild 300 0.55
Moderate 300 0.5
Severe 320 0.45
Very Severe 340 0.45
Extreme 360 0.4
Entrapped air
Nominal
as % of
Maximum size
volume of
of aggregate
concrete
10 1
12.5 0.8
20 0.5
Target
Water
Compressive
cementitious
strength at 28
material ratio
days
70 0.33
75 0.31
80 0.29
85 0.27
90 0.26
100 0.24
Nominal
maximum size Water Content
of aggregate (kg)
(mm)
10 208
20 186
40 165