Tekhnicheskie Kharakteristiki Tide Power FB2000 Q1
Tekhnicheskie Kharakteristiki Tide Power FB2000 Q1
May 2018
Engine Alternator Generator Model
Cummins QSK60-G4 Leroy-Somer LSA 52.3 S6 FB2000-Q1 / Open TCN2000C1/Silent
Key Features:
- High efficient water cooled diesel engine.
- Single bearing with brushless alternators (Class H, with AVR).
- Radiator with pressure cap and drain point.
- Fully guarded engine-driven fan.
- Fully welded steel skid base with lifting holes and fork lift legs.
- Integral fuel tank with filler cap and gauge (≤650kVA).
- Heavy duty rubber anti-vibration mountings.
- 12V or 24V maintenance free starter battery and connecting cables.
- Separate engine-driven battery charging alternator.
- Spin on oil and fuel filters and dry type air filter element.
- Industrial silencer (15dBA reduction) supplied loose.
- Auto start control system with LCD show.
- Battery charger provided.
- Main line 3P circuit breaker.
- Rigorous factory test wiring with IEC standard.
- Operation & Maintenance manual & Wiring diagrams.
Photo For Reference Only - Wide range of optional extra features available.
L W
Ratings: All three phase generator sets are rated at 0.8 power factor. All single-phase generator sets are rated at 0.8 or 1.0 power factor.
Prime Power: Available continuously at variable load in lieu of commercially purchased power for an unlimited number of hours per year
accordance with ISO8528-1, and an overload of 10% permitted for one hour in every twelve hours of operation in accordance with ISO 3046-1.
Standby Power: Emergency Standby Power in variable load applications in accordance with ISO8528-1 in the event of a utility power failure.
No overload available for this service as relevant alternators are peak continuous rated at 27 ℃ .
TIDE Power reserves the right to change the design or specifications without notice and without any obligation or liability.
Alternator 50Hz/1500R.P.M
Units
Manufacture / Brand Leroy-Somer
Model LSA 52.3 S6
Coupling / No. of Bearings Direct / Single Bearing
Phase / Poles 3-Phase / 4-Pole
Power Factor Cos Φ = 0.8
AVR Regulation Yes
General Data
Voltage Regulation ± 0,5 %
Insulation Class H
Drip Proof IP23
Excitation AREP
Altitude m ≤1000
Overspeed min -1 2250
Controller Photos
Standard Supply × × ● ○
Viewable Parameters
Phase Voltage × 3 3 3
Current Instrumentation ● ● ●
Frequency ● ● ● ●
Active Power × ● ● ●
Reactive Power × ● ● ●
Apparent Power × ● ● ●
Power Factor × ● ● ●
Electric Energy Metering × ● ● ●
Generator Protection
Abnormal Voltage ● ● ● ●
Over-current Warning × ● ● ●
Over current Protection ● ● ● ●
Over Frequency Protection ● ● ● ●
Short Circuit Protection MCCB / ● MCCB / ● MCCB / ● MCCB / ●
Engine Figure
Oil Pressure ● ● ● ●
Water Temperature ● ● ● ●
Fuel Meter / Fuel Sensor ●/○ ●/○ ●/○ ●/○
Speed ● ● ● ●
Battery Voltage ● ● ● ●
Elapsed Time ● ● ● ●
Engine Protection
Low Oil Pressure Warning × ● ● ●
Low Oil Pressure Protection ● ● ● ●
High Temperature Warning × ● ● ●
High Temperature Protection ● ● ● ●
Overspeed Warning × ● ● ●
Overspeed Protection × ● ● ●
Alternator Charger ● ● ● ●
Functions
Remote Start ● ● ● ●
AMF (Auto Main Failure) ● ● ● ●
Programmable Intput ● ● ● ●
Programmable Output ● ● ● ●
Expand Module × ○ ○ ○
Communication Function × ○ ○ ●/ RS232 / 485
Communication Port USB ○ ○ RS232 / 485
CAN ● × ● ●
Service Indicate × × ● ●
Fault History ● ● ● ●
Gen-Gen Synchronising × × × ●
Gen-Mains Synchronising × × × ●
Transportability
H
▪ Lifting four points on top to move genset easily.
System Advantages
▪ Automatically transfer and re-transfer load from main power to gen-power without
operator intervention.operation(Both automatic and manual).
▪ ATS Controller (AMF function), seamless integration with AMF25
▪ Available from 32 – 4000A, better protection for 4 pole switch.
▪ Available in standard, bypass isolation and service-entrance configurations.
▪ Configurable in open, closed and programmed transition operating modes.
▪ Designed to interface seamlessly with TIDE POWER generators and switchgear.
▪ Drip proof IP42 enclosure.
▪ Easy installation: wall-mounted & floor standing
▪ Comes fully loaded with the technology to do the job.
Dimensions : mm
A:400×200×500 B:500×300×650 C:600×400×1200 D:800×600×1400 E:1000×800×1600
Genset: Genset:
Diesel Engine/ Baseframe Mounted Accessories: Diesel Engine/ Baseframe Mounted Accessories:
Filters Filters
Ÿ- Extra air filters for time-maintenance -Ÿ
Mounted heavy duty air filter
- Double heavy duty air filters
Ÿ- Extra fuel filters for time-maintenance
Ÿ- Extra oil filters for time-maintenance
Exhaust Exhaust
Ÿ- Residential silencer for open type genset Ÿ- Mounted heavy duty air filter
Ÿ- Stainless steel silencer and kits
- Heat protection guard
Control System & Power Termination: Control System & Power Termination:
Weather protective & Sound proof Weather protective & Sound proof
Ÿ- R series -Ÿ
Super silent enclosure
-Ÿ
ISO 20ft containerized Ÿ- Weather proof enclosure
Ÿ- ISO 40ft containerized -Ÿ
Flat sponge sound absorber enclosure
- Stainless steel locks and hinges -Ÿ
Porous sheet with rockwool sound absorber enclosure
Please refer to Tide Power sales department for full details of the above options.
Warranty