AIR HANDLERS

CBA25UH
MERIT® Series
R-410A - Upflow / Horizontal
Bulletin No. 210814
P R O D U C T S P E C I F I C AT I O N S March 2019
February 2019

Nominal Capacity - 1.5 to 5 Tons


Optional Electric Heat - 5 to 20 kW

MODEL NUMBER IDENTIFICATION

CB A 25 UH - 030 - 230 - 10

Unit Type Minor Revision Number


CB = Air Handler

Refrigerant Type
Voltage
A = Aluminum Coil/R-410A
230 = 208/230V-1 phase-60hz
Series

Configuration Nominal Cooling Capacity


UH = Upflow/Horizontal 018 = 1.5 tons
024 = 2 tons
030 = 2.5 tons
036 = 3 tons
042 = 3.5 tons
048 = 4 tons
060 = 5 tons
FEATURES

CONTENTS
Blower Data.................................................................. 7 H
Dimensions - Accessories.......................................... 16
Dimensions - Unit - Upflow......................................... 14
G
Electrical Data.............................................................. 6 D
Electric Heat Data......................................................... 9
Features....................................................................... 2
Installation Clearances With Electric Heat.................... 5
Model Number Identification......................................... 1 F
Optional Accessories.................................................... 6
Specifications............................................................... 6

WARRANTY A
All covered components - Limited five years in
residential applications, one year in non-residential
applications. C
Refer to Lennox Limited Warranty Certificate included
with each unit for additional details.
E
APPLICATIONS
1.5 to 5 ton nominal sizes.
Upflow or horizontal applications. Downflow applications
with optional conversion kit. B
CBA25UH models are applicable to R-410A expansion
valve systems in cooling applications and check and
expansion valve systems in heat pump applications.
See bulletins in section Air Conditioners for cooling
capacities.
See bulletins in section Heat Pump Outdoor Units for Check and Expansion Valve Furnished
cooling and heating capacities. CBA25UH models have non-chlorine, ozone friendly,
R-410A valve.
Optional field installed electric heaters available in
several sizes for additive heating capacity. Wide range valve.
Chatleff style fitting.
APPROVALS
Factory installed on all models
Tested with matching air conditioners and heat pump internal to cabinet.
units in the Lennox Research Laboratory environmental
test room in accordance with AHRI Standard 210/240. C Quantum™ Coil
Optional electric heaters are rated in accordance with Lennox designed and fabricated coils.
US Department of Energy (DOE) test procedures and Enhanced aluminum alloy tube/enhanced fin coil for
Federal Trade Commission (FTC) labeling regulations. superior corrosion resistance.
Air handlers and components within are bonded for Aluminum tubing, hairpins, distributor and header tubes.
grounding to meet safety standards for servicing Ripple-edged aluminum fins.
required by ETL, NEC and CEC.
Twin coil construction assembled in a “A” configuration
Units are ETL certified for the U.S. and Canada. for large surface area.
Air handler units are approved for installation in Provides excellent heat transfer and low air resistance
manufactured housing and mobile homes. for maximum efficiency.
ISO 9001 Registered Manufacturing Quality System. Precise circuiting for uniform refrigerant distribution.
REFRIGERANT SYSTEM Lanced fins provide maximum exposure of fin surface to
air stream.
B Refrigerant Line Connections
Suction (vapor) and liquid lines have sweat connections Rifled tubing provides superior heat transfer.
that extended outside of the cabinet for ease of Coil thoroughly factory tested under high pressure to
connection. ensure leakproof construction.
See dimension drawing for locations.
CBA25UH - 1.5 to 5 ton Air Handlers / Page 2
FEATURES

D CABINET Optional Accessories


Constructed of heavy gauge galvanized steel.
Downflow Conversion Kit
Pre-painted cabinet finish. Required for field conversion to downflow position. Kit
Completely insulated with foil faced fiberglass consists of insulated downflow drain pan, insulated
insulation. drain pan drip shields, coil drip shields, seal plates and
Removable panels provide complete service access. support brackets for repositioning coil and drain pan.
Filter access door for easy filter replacement. See Optional Accessories table.
Thumbscrews hold filter door in place. Horizontal Support Frame Kit
Electrical inlets provided in sides and top of cabinet. Provides support of unit in horizontal applications.
See dimension drawing for locations. Consists of (2) 1 x 1-1/2 x 32-5/8 in. and (2) 1 x 3 x
Plugs in cabinet for drain connections for upflow (left 53-7/8 in. painted heavy gauge cold rolled steel support
and right) and horizontal applications. See dimension channels with assembly and suspending holes.
drawing. Bolts and nuts furnished for field assembly.
Low Leakage Cabinet Suspending rods must be field provided.
All models have less than 2% air leakage and meet
ANSI/ASHRAE Standard 193-2010 “Method of Test for Side Return Unit Stand (Upflow Only)
Determining the Air Tightness of HVAC Equipment.” Raises unit 16 in. above floor for side return air duct
connection.
Upflow/Horizontal Capability (Optional Downflow) Eliminates need for wooden platform construction.
Shipped for upflow and horizontal left-hand discharge.
All aluminum construction.
May be field converted to horizontal right-hand air
Two adjustable frames fit all sizes.
discharge by repositioning horizontal drain pan.
See Dimension Drawing.
Optional Downflow Conversion Kit available for field
conversion. Wall Hanging Bracket Kit (Upflow Only)
Allows unit to be hung on wall at any height.
EAnti-Microbial Dual Position Drain Pans Consists of heavy gauge steel support brackets (one for
Anti-Microbial additive resists
growth of mold and mildew on air handler unit, one for wall mount).
drain pan which improves indoor Screws furnished for fastening one bracket to unit.
air quality and reduces drain line blockage. Bolts for fastening one bracket to wall are field provided.
Factory installed drain pans designed for upflow or
horizontal applications. High Performance Economizer
(Commercial Applications Only)
Deep, corrosion resistant high temperature engineered Designed for applications requiring outdoor air to be
polymer drain pans have dual pipe drains. utilized in a commercial HVAC system. Allows the
See dimension drawing. entry of fresh outdoor air for free cooling, reducing the
requirement for mechanical cooling.
Heavy gauge galvanized steel cabinet lined with thick
fiberglass insulation.
Mixed air sensor, outdoor air sensor and 24VAC
transformer furnished.
Approved for California Title 24 building standards.
ASHRAE 90.1-2010 compliant.
See separate Product Specifications bulletin for additional
information and available control and sensor options.
FILTER
Disposable 1 inch filter is furnished.
Filter rack furnished in cabinet for easy filter installation.
See Specifications tables for filter sizes.

CBA25UH - 1.5 to 5 ton Air Handlers / Page 3


FEATURES

F BLOWER LCD display with backlight shows the current and set
temperature, time, inside relative humidity, system
Permanent Split Capacitor (PSC) Motor status (operating mode and schedules) and outside
(018 Through 042 Models) temperature (optional outdoor sensor required).
Multi-speed PSC motor.
Smooth Setback Recovery starts system early to
Choice of blower speeds. See blower performance achieve setpoint at start of program period.
tables.
Compressor short-cycle protection (5 minutes).
Speed changes easily accomplished by a simple wiring
change. Up to four separate schedules are available plus
Schedule IQ™.
Blower is easily removed from unit for servicing.
One-Touch Away Mode - A quick and easy way to set
Constant Torque Blower Motor the cooling and heating setpoints while away.
(048 and 060 Models) Smart Away™ - Uses geo-fencing technology
Programmable high efficiency multi-speed blower motor. to determine when the homeowner is within a
By maintaining constant torque output, blower motor predetermined distance from the home to operate the
can deliver more uniform (but not constant) airflow over system when leaving, away and arriving.
the static pressure range.
Amazon® Alexa-enabled, smart-home-compatible. It
Programmable multi-speed operation is achieved by works with Amazon Echo, Echo Dot and Tap devices.
the use of an ECM (Electronically Commutated Motor)
Wi-Fi remote monitoring and adjustment through a
motor.
home wireless network for desktop PCs, laptops and
Leadless blower motor features simple plug-in apps for smartphones or tablets.
connections.
See the iComfort® M30 Smart Wi-Fi Thermostat Product
Choice of blower speeds is available. See Blower Data Specifications bulletin in the Controls section for more
tables. information.
Time Delay Blower Relay Remote Outdoor Temperature Sensor
Relay allows one second blower “on” delay before Used with the iComfort® M30 Smart Thermostat.
continuous fan or cooling operation and 45 second
When installed outdoors, sensor
blower “off” delay after continuous fan or cooling
allows thermostat to display outdoor
operation.
temperature. Sensor is auto-detected
CONTROLS when connected to thermostat.
G Transformer and Blower Cooling Relay NOTE - Sensor is required for the
24 volt transformer and blower cooling relay furnished Enhanced Dehumidification
as standard. Accessory (EDA).
Factory installed in the unit control box. Thermostat
Optional Accessories Thermostat (programmable/non-programmable) is not
furnished with unit.
iComfort® M30 Smart Wi-Fi Thermostat
See Thermostat bulletins in Controls Section and
Wi-Fi-enabled, electronic 7-day, universal, multi-stage,
Lennox Price Book for selection.
programmable, touchscreen thermostat.
4 Heat/2 Cool.
Auto-changeover.
Dual-fuel control with
optional outdoor sensor.
Controls dehumidification
during cooling mode and
humidification during
heating mode.
Offers enhanced capabilities including humidification /
dehumidification / dewpoint measurement and control,
Humiditrol® control, and equipment maintenance
reminders.
Easy to read 4.3 in. color touchscreen (measured
diagonally).

CBA25UH - 1.5 to 5 ton Air Handlers / Page 4


FEATURES

ELECTRICAL Circuit Breaker Models


Optional Accessories ECBA25-5CB, ECBA25-7.5CB, ECBA25-10CB,
ECBA25-12.5, ECBA25-15CB, ECBA25-20CB heaters
H Electric Heat are equipped with circuit breakers for overload and
Field install internal to unit short circuit protection.
cabinet. Factory wired and mounted on electric heat unit.
Available in several kW sizes. Current sensitive and temperature actuated.
See Electric Heat tables. Manual reset.
Helix wound nichrome Flexible plastic circuit breaker cover protects circuit
heating elements exposed breaker in areas with high humidity or unconditioned
directly in air stream resulting areas to prevent nuisance tripping.
in instant heat transfer, low
element temperatures and Circuit breakers qualify as disconnect means at unit
long service life. in many areas, eliminate the need for field provided
disconnect.
Each element equipped with accurately located limit
control with fixed temperature off setting and automatic Consult local electrical code in your area.
reset. Circuit Breaker Cover Kit
Thermal sequencer relay brings elements on and off Flexible plastic cover protects circuit breaker.
line, in sequence and equal increments, with time delay Recommended in areas with high humidity or
between each. unconditioned areas to prevent nuisance tripping.
Initiates and terminates blower operation.
Single-Point Power Source Control Box
Heating control relay(s) furnished as standard.
Control Box may be used with optional electric heat
Factory assembled with controls installed and wired. when single power supply is connected to multi-circuit
Electric heat control wiring plugs into mating connector electric heat.
on air handler unit. Field installs external to the unit cabinet on either side
or top.
Constructed of heavy gauge steel, baked enamel finish,
prepunched mounting holes, electrical inlet knockouts,
and terminal strip.
Removeable cover provides easy access.
Dimensions (H x W x D) - 7 x 7 x 4 in.

INSTALLATION CLEARANCES WITH ELECTRIC HEAT


Cabinet 0 inch (0 mm)
To Plenum 0 inch (0 mm)
To Outlet Duct within 3 feet (914 mm) 0 inch (0 mm)
Floor 0 inch (0 mm) See Note #1
Service / Maintenance See Note #2
1
 nits installed on combustible floors in the downflow position with electric heat do not require a downflow combustible
U
flooring base.
2
Front service access - 24 inches (610 mm) minimum.
NOTE - If cabinet depth is more than 24 inches (610 mm), allow a minimum of the cabinet depth plus 2 inches (51 mm).

CBA25UH - 1.5 to 5 ton Air Handlers / Page 5


SPECIFICATIONS
General Model Number CBA25UH-018 CBA25UH-024 CBA25UH-030 CBA25UH-036
Data Nominal tonnage 1.5 2 2.5 3
Connections Suction/Vapor line (o.d.) - in. sweat 3/4 3/4 3/4 7/8
Liquid line (o.d.) - in. sweat 3/8 3/8 3/8 3/8
Condensate - in. fpt (2) 3/4 (2) 3/4 (2) 3/4 (2) 3/4
Indoor Net face area - ft.2 3.30 3.77 4.72 5.66
Coil Tube outside diameter - in. 3/8 3/8 3/8 3/8
Number of rows 3 3 3 3
Fins per inch 15 15 15 15
Blower Wheel nominal diameter x width - in. 9x6 9x6 10 x 8 10 x 8
Blower motor output - hp 1/5 1/3 1/2 1/3
1
Filters Size of filter - in. 15 x 20 x 1 15 x 20 x 1 15 x 20 x 1 18 x 20 x 1
Shipping Data -1 package - lbs. 129 136 143 169
ELECTRICAL DATA
Voltage - 1 phase (60 hz) 208/230V 208/230V 208/230V 208/230V
2
Maximum overcurrent protection (unit only) 15 15 15 15
3
Minimum circuit ampacity (unit only) 5.0 5.0 5.0 5.0
Blower Motor Full Load Amps 1.1 1.6 2.2 2.0

SPECIFICATIONS
General Model Number CBA25UH-042 CBA25UH-048 CBA25UH-060
Data Nominal tonnage 3.5 4 5
Connections Suction/Vapor line (o.d.) - in. sweat 7/8 7/8 7/8
Liquid line (o.d.) - in. sweat 3/8 3/8 3/8
Condensate - in. fpt (2) 3/4 (2) 3/4 (2) 3/4
Indoor Net face area - ft.2 5.66 6.13 7.08
Coil Tube outside diameter - in. 3/8 3/8 3/8
Number of rows 3 3 3
Fins per inch 15 15 15
Blower Wheel nominal diameter x width - in. 10 x 8 12 x 10 12 x 10
Blower motor output - hp 1/2 1 1
1
Filters Size of filter - in. 18 x 20 x 1 18 x 20 x 1 18 x 20 x 1
Shipping Data -1 package - lbs. 169 179 190
ELECTRICAL DATA
Voltage - 1 phase (60 hz) 208/230V 208/230V 208/230V
2
Maximum overcurrent protection (unit only) 15 15 15
3
Minimum circuit ampacity (unit only) 5.0 9.5 9.5
Blower Motor Full Load Amps 2.5 7.6 7.6
1
Disposable filter.
2
HACR type circuit breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.

OPTIONAL ACCESSORIES - ORDER SEPARATELY


Model -018 -024 -036 -042
-030 -048
-060
iComfort® M30 Smart Wi-Fi Thermostat 15Z69 15Z69 15Z69 15Z69
Remote Outdoor Temperature Sensor X2658 X2658 X2658 X2658
Downflow Conversion Kit Y9658 Y9658 Y9659 Y9659
Horizontal Support Frame Kit 56J18 56J18 56J18 56J18
Side Return Unit Stand (Upflow Only) 45K32 45K32 45K32 45K32
Single-Point Power Source Control Box (for Electric Heat) 21H39 21H39 21H39 21H39
Wall Hanging Bracket Kit (Upflow Only) 45K30 45K30 45K30 45K30
High Performance Economizer (Commercial Only) 10U53 10U53 10U53 10U53
CBA25UH - 1.5 to 5 ton Air Handlers / Page 6
BLOWER DATA

CBA25UH-018 PERFORMANCE

External Static Air Volume / Watts at Various Blower Speeds


Pressure High Medium Low
in. w.g. cfm Watts cfm Watts cfm Watts
0.10 920 264 690 190 540 144
0.20 880 251 670 183 525 140
0.30 855 238 640 176 505 136
0.40 790 224 605 167 470 130
0.50 710 210 550 155 420 122
NOTE - All air data measured external to unit with dry coil and 1 inch non-pleated air filter in place.
Electric heaters have no appreciable air resistance.

CBA25UH-024 PERFORMANCE

External Static Air Volume / Watts at Various Blower Speeds


Pressure High Medium Low
in. w.g. cfm Watts cfm Watts cfm Watts
0.10 1105 342 1010 280 675 210
0.20 1045 322 980 262 675 202
0.30 1000 307 940 247 655 192
0.40 915 284 805 235 630 180
0.50 855 268 740 216 590 170
NOTE - All air data measured external to unit with dry coil and 1 inch non-pleated air filter in place.
Electric heaters have no appreciable air resistance.

CBA25UH-030 PERFORMANCE

External Static Air Volume / Watts at Various Blower Speeds


Pressure High Medium Low
in. w.g. cfm Watts cfm Watts cfm Watts
0.10 1310 496 1080 391 870 310
0.20 1260 466 1055 378 870 301
0.30 1215 449 1025 361 855 288
0.40 1155 431 985 343 810 278
0.50 1085 408 935 325 770 265
NOTE - All air data measured external to unit with dry coil and 1 inch non-pleated air filter in place.
Electric heaters have no appreciable air resistance.

CBA25UH-036 PERFORMANCE

External Static Air Volume / Watts at Various Blower Speeds


Pressure High Medium Low
in. w.g. cfm Watts cfm Watts cfm Watts
0.10 1560 532 1275 402 1020 295
0.20 1520 518 1240 388 970 287
0.30 1445 502 1190 375 955 280
0.40 1395 480 1150 363 910 270
0.50 1325 460 1085 346 805 254
NOTE - All air data measured external to unit with dry coil and 1 inch non-pleated air filter in place.
Electric heaters have no appreciable air resistance.

CBA25UH - 1.5 to 5 ton Air Handlers / Page 7


BLOWER DATA

CBA25UH-042 PERFORMANCE

External Static Air Volume / Watts at Various Blower Speeds


Pressure High Medium Low
in. w.g. cfm Watts cfm Watts cfm Watts
0.10 1815 674 1525 498 1300 394
0.20 1755 652 1495 486 1275 387
0.30 1695 634 1450 473 1250 376
0.40 1605 607 1390 455 1210 367
0.50 1530 582 1345 441 1155 356
NOTE - All air data measured external to unit with dry coil and 1 inch non-pleated air filter in place.
Electric heaters have no appreciable air resistance.

CBA25UH-048 PERFORMANCE (Less Filter)


External Air Volume / Watts at Various Blower Speeds
Static High Medium-High Medium Medium-Low Low
Pressure
in. w.g. cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
0.10 1895 597 1770 493 1715 454 1500 315 1250 211
0.20 1860 629 1735 510 1670 470 1465 331 1210 222
0.30 1835 632 1700 529 1635 487 1435 348 1185 231
0.40 1795 656 1670 544 1615 504 1400 364 1130 239
0.50 1760 667 1650 552 1575 514 1360 379 1110 251
NOTE - All air data measured external to unit with dry coil and 1 inch non-pleated air filter in place.
Electric heaters have no appreciable air resistance.

CBA25UH-060 PERFORMANCE (Less Filter)


External Air Volume / Watts at Various Blower Speeds
Static High Medium-High Medium Medium-Low Low
Pressure
in. w.g. cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
0.10 1980 624 1905 538 1815 484 1625 354 1100 132
0.20 1955 644 1870 563 1785 493 1595 365 1050 140
0.30 1925 643 1835 568 1760 507 1565 385 1000 144
0.40 1895 663 1810 585 1730 527 1520 398 925 162
0.50 1860 673 1765 595 1685 542 1490 398 830 172
NOTE - All air data measured external to unit with dry coil and 1 inch non-pleated air filter in place.
Electric heaters have no appreciable air resistance.

CBA25UH - 1.5 to 5 ton Air Handlers / Page 8


ELECTRIC HEAT DATA
SINGLE PHASE CBA25UH-018
Blower
Input Minimum
2 3
Maximum
Motor
Description Circuit Overcurrent
Full Load
Ampacity Protection
Volt kW 1
Btuh Amps
5 kW ECBA25-5 (16Y36) 208 3.6 12,300 1.1 23 25
Terminal Block
220 4.0 13,800 1.1 24 25
ECBA25-5CB (16Y39)
30A Circuit Breaker 230 4.4 15,000 1.1 25 25
240 4.8 16,400 1.1 26 30
7.5 kW ECBA25-7.5 (16Y37) 208 5.6 19,200 1.1 35 35
Terminal Block
220 6.3 21,500 1.1 37 4
40
ECBA25-7.5CB (16Y41)
45A Circuit Breaker 230 6.9 23,500 1.1 39 4
40
240 7.5 25,600 1.1 40 4
40
10 kW ECBA25-10 (16Y38) 208 7.2 24,600 1.1 45 4
45
Terminal Block
220 8.0 27,500 1.1 47 4
50
ECBA25-10CB (16Y42)
60A Circuit Breaker 230 8.8 30,000 1.1 49 4
50
240 9.6 32,700 1.1 51 60
SINGLE PHASE CBA25UH-024
Blower
Input Minimum
2 3
Maximum
Motor
Description Circuit Overcurrent
Full Load
Ampacity Protection
Volt kW 1
Btuh Amps
5 kW ECBA25-5 (16Y36) 208 3.6 12,300 1.6 24 4
25
Terminal Block
220 4.0 13,800 1.6 25 4
25
ECBA25-5CB (16Y39)
30A Circuit Breaker 230 4.4 15,000 1.6 26 30
240 4.8 16,400 1.6 27 30
7.5 kW ECBA25-7.5 (16Y37) 208 5.6 19,200 1.6 36 4
40
Terminal Block
220 6.3 21,500 1.6 38 4
40
ECBA25-7.5CB (16Y41)
45A Circuit Breaker 230 6.9 23,500 1.6 39 4
40
240 7.5 25,600 1.6 41 45
10 kW ECBA25-10 (16Y38) 208 7.2 24,600 1.6 45 4
45
Terminal Block
220 8.0 27,500 1.6 48 4
50
ECBA25-10CB (16Y42)
60A Circuit Breaker 230 8.8 30,000 1.6 50 4
50
240 9.6 32,700 1.6 52 60
NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.
1
Electric heater capacity only - does not include additional blower motor heat capacity.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
3
HACR type breaker or fuse.
4
Bold indicates that the circuit breaker on “CB” circuit breaker models must be replaced with size shown. See tablepage 9.

REPLACEMENT CIRCUIT BREAKERS


Voltage Description Catalog No.
208/240V - 1 Phase 25 amp, 2 pole 41K13
30 amp, 2 pole 17K70
35 amp, 2 pole 72K07
40 amp, 2 pole 49K14
45 amp, 2 pole 17K71
50 amp, 2 pole 41K12
60 amp, 2 pole 17K72
CBA25UH - 1.5 to 5 ton Air Handlers / Page 9
ELECTRIC HEAT DATA
SINGLE PHASE CBA25UH-030
2
Minimum 3
Maximum
Single Point
Input Blower Circuit Overcurrent
Power Source
Motor Ampacity Protection
Description
Full Load Minimum 3 Maximum
2

Volt kW 1
Btuh Amps Ckt 1 Ckt 2 Ckt 1 Ckt 2 Circuit Overcurrent
Ampacity Protection

5 kW ECBA25-5 (16Y36) 208 3.6 12,300 2.2 24 --- 4


25 --- --- ---
Terminal Block
ECBA25-5CB (16Y39) 220 4.0 13,800 2.2 26 --- 30 --- --- ---
30A Circuit Breaker 4.4 15,000
230 2.2 27 --- 30 --- --- ---

240 4.8 16,400 2.2 28 --- 30 --- --- ---

7.5 kW ECBA25-7.5 (16Y37) 208 5.6 19,200 2.2 37 --- 4


40 --- --- ---
Terminal Block
ECBA25-7.5CB (16Y41) 220 6.3 21,500 2.2 39 --- 4
40 --- --- ---
45A Circuit Breaker 6.9 23,500
230 2.2 40 --- 4
40 --- --- ---

240 7.5 25,600 2.2 42 --- 45 --- --- ---

10 kW ECBA25-10 (16Y38) 208 7.2 24,600 2.2 46 --- 4


50 --- --- ---
Terminal Block
ECBA25-10CB (16Y42) 220 8.0 27,500 2.2 49 --- 4
50 --- --- ---
60A Circuit Breaker 8.8 30,000
230 2.2 51 --- 60 --- --- ---

240 9.6 32,700 2.2 53 --- 60 --- --- ---

12.5 kW ECBA25-12.5CB (16Y43) 208 9.4 32,000 2.2 40 19 4


40 4
20 59 60
(1) 50A and
(1) 25A Circuit Breaker 220 10.5 35,800 2.2 43 20 4
45 4
20 62 70

230 11.5 39,200 2.2 44 21 4


45 25 65 70

240 12.5 42,600 2.2 46 22 50 25 68 70

15 kW ECBA25-15CB (16Y44) 208 10.8 36,900 2.2 46 22 4


50 25 68 70
(1) 60A and
(1) 25A Circuit Breaker 220 12.1 41,300 2.2 49 23 4
50 25 72 80

230 13.2 45,100 2.2 51 24 60 25 75 80

240 14.4 49,100 2.2 53 25 60 25 78 80


NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.
1
Electric heater capacity only - does not include additional blower motor heat capacity.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
3
HACR type breaker or fuse.
4
Bold indicates that the circuit breaker on “CB” circuit breaker models must be replaced with size shown. See tablepage 9.

CBA25UH - 1.5 to 5 ton Air Handlers / Page 10


ELECTRIC HEAT DATA
SINGLE PHASE CBA25UH-036
2
Minimum 3
Maximum
Single Point
Input Blower Circuit Overcurrent
Power Source
Motor Ampacity Protection
Description
Full Load 2
Minimum 3 Maximum
Volt kW 1
Btuh Amps Ckt 1 Ckt 2 Ckt 1 Ckt 2 Circuit Overcurrent
Ampacity Protection

5 kW ECBA25-5 (16Y36) 208 3.6 12,300 2.0 24 --- 4


25 --- --- ---
Terminal Block
ECBA25-5CB (16Y39) 220 4.0 13,800 2.0 25 --- 4
25 --- --- ---
30A Circuit Breaker 4.4 15,000
230 2.0 26 --- 30 --- --- ---

240 4.8 16,400 2.0 28 --- 30 --- --- ---

7.5 kW ECBA25-7.5 (16Y37) 208 5.6 19,200 2.0 36 --- 4


40 --- --- ---
Terminal Block
ECBA25-7.5CB (16Y41) 220 6.3 21,500 2.0 38 --- 4
40 --- --- ---
45A Circuit Breaker 6.9 23,500
230 2.0 40 --- 4
40 --- --- ---

240 7.5 25,600 2.0 42 --- 45 --- --- ---

10 kW ECBA25-10 (16Y38) 208 7.2 24,600 2.0 46 --- 4


50 --- --- ---
Terminal Block
ECBA25-10CB (16Y42) 220 8.0 27,500 2.0 48 --- 4
50 --- --- ---
60A Circuit Breaker 8.8 30,000
230 2.0 50 --- 4
50 --- --- ---

240 9.6 32,700 2.0 53 --- 60 --- --- ---

12.5 kW ECBA25-12.5CB (16Y43) 208 9.4 32,000 2.0 40 19 4


40 4
20 59 60
(1) 50A and
(1) 25A Circuit Breaker 220 10.5 35,800 2.0 42 20 4
45 4
20 62 70

230 11.5 39,200 2.0 44 21 4


45 25 65 70

240 12.5 42,600 2.0 46 22 50 25 68 70

15 kW ECBA25-15CB (16Y44) 208 10.8 36,900 2.0 46 22 4


50 25 68 70
(1) 60A and
(1) 25A Circuit Breaker 220 12.1 41,300 2.0 48 23 4
50 25 71 80

230 13.2 45,100 2.0 50 24 4


50 25 74 80

240 14.4 49,100 2.0 53 25 60 25 78 80


NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.
1
Electric heater capacity only - does not include additional blower motor heat capacity.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
3
HACR type breaker or fuse.
4
Bold indicates that the circuit breaker on “CB” circuit breaker models must be replaced with size shown. See tablepage 9.

CBA25UH - 1.5 to 5 ton Air Handlers / Page 11


ELECTRIC HEAT DATA
SINGLE PHASE CBA25UH-042
2
Minimum 3
Maximum
Single Point
Input Blower Circuit Overcurrent
Power Source
Motor Ampacity Protection
Description
Full Load 2
Minimum 3 Maximum
Volt kW 1
Btuh Amps Ckt 1 Ckt 2 Ckt 1 Ckt 2 Circuit Overcurrent
Ampacity Protection

5 kW ECBA25-5 (16Y36) 208 3.6 12,300 2.5 25 --- 4


25 --- --- ---
Terminal Block
ECBA25-5CB (16Y39) 220 4.0 13,800 2.5 26 --- 30 --- --- ---
30A Circuit Breaker 4.4 15,000
230 2.5 27 --- 30 --- --- ---

240 4.8 16,400 2.5 28 --- 30 --- --- ---

7.5 kW ECBA25-7.5 (16Y37) 208 5.6 19,200 2.5 37 --- 4


40 --- --- ---
Terminal Block
ECBA25-7.5CB (16Y41) 220 6.3 21,500 2.5 39 --- 4
40 --- --- ---
45A Circuit Breaker 6.9 23,500
230 2.5 41 --- 45 --- --- ---

240 7.5 25,600 2.5 42 --- 45 --- --- ---

10 kW ECBA25-10 (16Y38) 208 7.2 24,600 2.5 46 --- 4


50 --- --- ---
Terminal Block
ECBA25-10CB (16Y42) 220 8.0 27,500 2.5 49 --- 4
50 --- --- ---
60A Circuit Breaker 8.8 30,000
230 2.5 51 --- 60 --- --- ---

240 9.6 32,700 2.5 53 --- 60 --- --- ---

12.5 kW ECBA25-12.5CB (16Y43) 208 9.4 32,000 2.5 41 19 4


45 4
20 60 60
(1) 50A and
(1) 25A Circuit Breaker 220 10.5 35,800 2.5 43 20 4
45 4
20 63 70

230 11.5 39,200 2.5 45 21 4


45 25 66 70

240 12.5 42,600 2.5 47 22 50 25 68 70

15 kW ECBA25-15CB (16Y44) 208 10.8 36,900 2.5 46 22 4


50 25 68 70
(1) 60A and
(1) 25A Circuit Breaker 220 12.1 41,300 2.5 49 23 4
50 25 72 80

230 13.2 45,100 2.5 51 24 60 25 75 80

240 14.4 49,100 2.5 53 25 60 25 78 80


NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.
1
Electric heater capacity only - does not include additional blower motor heat capacity.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
3
HACR type breaker or fuse.
4
Bold indicates that the circuit breaker on “CB” circuit breaker models must be replaced with size shown. See tablepage 9.

CBA25UH - 1.5 to 5 ton Air Handlers / Page 12


ELECTRIC HEAT DATA
SINGLE PHASE CBA25UH-048-060
2
Minimum 3
Maximum
Single Point
Input Blower Circuit Overcurrent
Power Source
Motor Ampacity Protection
Description
Full Load 2
Minimum 3 Maximum
Volt kW 1
Btuh Amps Ckt 1 Ckt 2 Ckt 1 Ckt 2 Circuit Overcurrent
Ampacity Protection

5 kW ECBA25-5 (16Y36) 208 3.6 12,300 7.6 31 --- 4


35 --- --- ---
Terminal Block
ECBA25-5CB (16Y39) 220 4.0 13,800 7.6 32 --- 4
35 --- --- ---
30A Circuit Breaker
230 4.4 15,000 7.6 33 --- 4
35 --- --- ---

240 4.8 16,400 7.6 35 --- 4


35 --- --- ---

7.5 kW ECBA25-7.5 (16Y37) 208 5.6 19,200 7.6 43 --- 45 --- --- ---
Terminal Block
ECBA25-7.5CB (16Y41) 220 6.3 21,500 7.6 45 --- 45 --- --- ---
45A Circuit Breaker
230 6.9 23,500 7.6 47 --- 4
50 --- --- ---

240 7.5 25,600 7.6 49 --- 4


50 --- --- ---

10 kW ECBA25-10 (16Y38) 208 7.2 24,600 7.6 53 --- 60 --- --- ---
Terminal Block
ECBA25-10CB (16Y42) 220 8.0 27,500 7.6 55 --- 60 --- --- ---
60A Circuit Breaker
230 8.8 30,000 7.6 57 --- 60 --- --- ---

240 9.6 32,700 7.6 60 --- 60 --- --- ---

12.5 kW ECBA25-12.5CB (16Y43) 208 9.4 32,000 7.6 47 19 50 4


20 66 70
(1) 50A and
(1) 25A Circuit Breaker 220 10.5 35,800 7.6 49 20 50 20 69 70
4

230 11.5 39,200 7.6 51 21 4


60 25 72 80

240 12.5 42,600 7.6 53 22 4


60 25 75 80

15 kW ECBA25-15CB (16Y44) 208 10.8 36,900 7.6 53 22 60 25 75 80


(1) 60A and
(1) 25A Circuit Breaker 220 12.1 41,300 7.6 55 23 60 25 78 80

230 13.2 45,100 7.6 57 24 60 25 81 90

240 14.4 49,100 7.6 60 25 60 25 85 90

20 kW ECBA25-20CB (16Y46) 208 14.4 49,200 7.6 53 43 60 4


45 96 100
(1) 60A and
(1) 50A Circuit Breaker 220 16.1 55,000 7.6 55 46 60 50 101 110

230 17.6 60,100 7.6 57 48 60 50 105 110

240 19.2 65,500 7.6 60 50 60 50 110 110


NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.
1
Electric heater capacity only - does not include additional blower motor heat capacity.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
3
HACR type breaker or fuse.
4
Bold indicates that the circuit breaker on “CB” circuit breaker models must be replaced with size shown. See tablepage 9.

CBA25UH - 1.5 to 5 ton Air Handlers / Page 13


DIMENSIONS - UNIT - UPFLOW

1 (25)
DETAIL OF PIPING PLATE
3/4 (19) 4-3/4
(121)
SUCTION
LINE
SUPPLY AIR
LIQUID
OPENING LINE CONDENSATE
14-1/2
DRAINS (2)
(368) 2-3/8 (Horizontal)
(60)
1 (25) C 1 (25) CONDENSATE
DRAINS (2)
4-3/8
(Upflow and
(111)
2-3/4 Downflow)
LOW VOLTAGE (70)
INLETS
(Top and Right Side) 3-1/2
LINE VOLTAGE 1-3/4 (89)
INLETS (44)
(Top and Left Side)
TOP VIEW
3/4
(19) B 22
(559)
LINE VOLTAGE
INLETS
(Top and Right Side)

CIRCUIT LOW VOLTAGE


BREAKER INLETS
COVER (Either Side)

AIR FLOW

PIPING
PLATE

CONDENSATE DRAIN SUCTION


PIPING PLATE (3) LINE
(2-1/4 x 3-3/4)
LIQUID
FILTER LINE
ACCESS

1/2
1-1/8
(29)
D 1-1/8
(29) (13)
20-3/8
(518)
1-1/8
(29)
OPENING
OPENING

FRONT VIEW SIDE VIEW

018 024 030 036, 042 048 060


Dimensions
in. mm in. mm in. mm in. mm in. mm in. mm
A 43-1/2 1105 45-1/2 1156 47 1194 53-5/8 1362 55 1397 59-3/4 1518
B 18-1/2 470 18-1/2 470 18-1/2 470 21-1/2 546 21-1/2 546 21-1/2 546
C 16-1/2 419 16-1/2 419 16-1/2 419 19-1/2 495 19-1/2 495 19-1/2 495
D 16-1/4 413 16-1/4 413 16-1/4 413 19-1/4 489 19-1/4 489 19-1/4 489

CBA25UH - 1.5 to 5 ton Air Handlers / Page 14


DIMENSIONS - UNIT - HORIZONTAL

1-1/8
(29)
DETAIL OF PIPING PLATE
CONDENSATE
CONDENSATE DRAINS (2)
DRAINS (2) (Upflow and
4-3/4 (Horizontal)
(121) Downflow) 3-1/2
(89)

20-3/8
22 (518)
(559) OPENING
1-3/4
3/4 (44)
(19)

SUCTION 2-3/4
LINE LIQUID (70)
LINE 2-3/8 4-3/8
(60) (111)
LOW VOLTAGE INLETS
LINE VOLTAGE INLETS 1/2
(Either Side)
(Top and Right Side) (13)
SUCTION LIQUID
TOP VIEW LINE LINE

CONDENSATE DRAIN
PIPING PLATE (3)
LOW VOLTAGE (2-1/4 x 3-3/4) 1-1/8
FILTER
INLETS (29)
1 (25) ACCESS
(Top and Right Side)

C
SUPPLY AIR
OPENING B D
CIRCUIT AIR FLOW PIPING
PLATE OPENING
BREAKER
COVER
14-1/2
1 (25)
(368)

1 (25)
LINE VOLTAGE
3/4 A 1-1/8
(19) (29)
INLETS
(Top and Left Side)

END VIEW FRONT VIEW

018 024 030 036, 042 048 060


Dimensions
in. mm in. mm in. mm in. mm in. mm in. mm
A 43-1/2 1105 45-1/2 1156 47 1194 53-5/8 1362 55 1397 59-3/4 1518
B 18-1/2 470 18-1/2 470 18-1/2 470 21-1/2 546 21-1/2 546 21-1/2 546
C 16-1/2 419 16-1/2 419 16-1/2 419 19-1/2 495 19-1/2 495 19-1/2 495
D 16-1/4 413 16-1/4 413 16-1/4 413 19-1/4 489 19-1/4 489 19-1/4 489

CBA25UH - 1.5 to 5 ton Air Handlers / Page 15


DIMENSIONS - ACCESSORIES

SIDE RETURN UNIT STAND


(Upflow Only)

16
(406)

6
(152)

E
SID
FRONT
ADJUSTABLE
21-1/4 20 (508) to
(540) 25 (635)
ALL UNITS

REVISIONS
Sections Description of Change

Approvals Added approval for installation in manufactured housing and mobile homes.

Optional Accessories Added iComfort® M30 Smart Thermostat.

Visit us at www.lennox.com
For the latest technical information, www.LennoxPROs.com