Code Fault DSC
Code Fault DSC
Analog Sensor Fault Speed limit The ground connection to the DSC or PSC
:13 Yes
Analog I/O card has been lost
The 10 volt DC power to the DSC or PSC Ana-
:14 Yes
log I/O card has been lost
The ground fault amps output from DSC or
:15 Yes
PSC Analog I/O card is out of range
Alternator tertiary amps from DSC or PSC Ana-
:16 Yes
log I/O card is out of expected range
:17 INV3 Link Volts Yes
The grid blower motor 1 current is out of
:21 Yes
expected range
The grid blower motor 2 (if equipped) current is
:22 Yes
out of expected range
:23 Link I T2 - Range Yes
015 :02 DC Link Amps Sensor Fault No power The DC Link current is out of expected range No
Inverter 21 Phase A Fault Inverter 2 Disable Inverter 11 or 21, Phase A+ has experienced
:04 Yes
an overcurrent (saturation) condition
Inverter 11 or 21, Phase A- has experienced an
:05 Yes
overcurrent (saturation) condition
117/ Inverter 11 or 21, Phase Module A+ did not turn
:01 Yes
217 OFF when commanded
During VI Test, Inverter 11 or 21, Phase Module
:02 No
A+ did not turn OFF when expected
Inverter 11 or 21, Phase Module A+ was
:03 No
detected as failed during VI test
Inverter 11 Phase A+ Fault Inverter 1 Disable
Inverter 11 or 21 Phase Module A+ turned ON
:04 Yes
while Phase Module A- was detected ON
Inverter 21 Phase A+ Fault Inverter 2 Disable
During VI Test, Inverter 11 or 21 Phase Module
:05 Yes
A+ did not turn ON when commanded
While running, Inverter 11 or 21, Phase Module
:06 Yes
A+ did not turn ON when commanded
Inverter 11 or 21, Phase Module A+ gate driver
:07 Yes
power supply problem detected
118/ :02-
INV A+ NR AUP Temp Short, Open, Warm, Hot Yes
218 05
Inverter 11 Phase A+ Event
Inverter 11 or 21, Phase Module A+ is not OFF
:06 System event Yes
when expected with the DC Link energized
Inverter 21 Phase A+ Event
Inverter 11 and 12 (or 21 and 22), Phase Mod-
:07 Yes
ule A+ current-sharing limit was reached
119/ Inverter 11 or 21, Phase Module A- did not turn
:01 Yes
219 OFF when commanded
During VI Test, Inverter 11 or 21, Phase Module
:02 No
A- did not turn OFF when expected
Inverter 11 or 21, Phase Module A- was
:03 No
detected as failed during VI test
Inverter 11 Phase A- Fault Inverter 1 Disable
Inverter 11 or 21 Phase Module A- turned ON
:04 Yes
while Phase Module A+ was detected ON
Inverter 21 Phase A- Fault Inverter 2 Disable
During VI Test, Inverter 11 or 21 Phase Module
:05 Yes
A- did not turn ON when commanded
While running, Inverter 11 or 21, Phase Module
:06 Yes
A- did not turn ON when commanded
Inverter 11 or 21, Phase Module A- gate driver
:07 Yes
power supply problem detected
120/ :02-
INV A- NR ADN Temp Short, Open, Warm, Hot Yes
220 05
Inverter 11 Phase A- Event
Inverter 11 or 21, Phase Module A- is not OFF
:06 System event Yes
when expected with the DC Link energized
Inverter 21 Phase A- Event
Inverter 11 and 12 (or 21 and 22), Phase Mod-
:07 Yes
ule A- current-sharing limit was reached
Inverter 21 Phase A Current Fault Inverter 2 Disable Current feedback from Inverter 11 or 21, Phase
:03 Yes
A Phase Modules is higher than expected
:04,
INV A current sensor Phase A open/short Yes
05
123/ Inverter 1 or 2, Phase A voltage sensor was
:01 Inverter 1 Phase A Voltage Fault Inverter 1 Disable Yes
223 determined failed during VI test
Inverter 2 Phase A Voltage Fault Inverter 2 Disable Inverter 11 or 21, Phase A voltage feedback is
:02 Yes
higher than expected
125/ Inverter 11 or 21, Phase B Phase Modules did
:01 Yes
225 not turn OFF when commanded
Inverter 11 or 21, Phase B Phase Modules
:02 Inverter 11 Phase B Fault Inverter 1 Disable Yes
excessive overcurrent condition detected
Inverter 21 Phase B Fault Inverter 2 Disable Inverter 11 or 21, Phase B+ has experienced
:04 Yes
an overcurrent (saturation) condition
Inverter 11 or 21, Phase B- has experienced an
:05 Yes
overcurrent (saturation) condition
126/ Inverter 11 or 21, Phase Module B+ did not turn
:01 Yes
226 OFF when commanded
During VI Test, Inverter 11 or 21, Phase Module
:02 No
B+ did not turn OFF when expected
Inverter 11 or 21, Phase Module B+ was
:03 No
detected as failed during VI test
Inverter 11 Phase B+ Fault Inverter 1 Disable
Inverter 11 or 21 Phase Module B+ turned ON
:04 Yes
while Phase Module B- was detected ON
Inverter 21 Phase B+ Fault Inverter 2 Disable
During VI Test, Inverter 11 or 21 Phase Module
:05 Yes
B+ did not turn ON when commanded
While running, Inverter 11 or 21, Phase Module
:06 Yes
B+ did not turn ON when commanded
Inverter 11 or 21, Phase Module B+ gate driver
:07 Yes
power supply problem detected
127/ :02-
INV B+ Temp Short, Open, Warm, Hot Yes
227 05
Inverter 11 Phase B+ Event
Inverter 11 or 21, Phase Module B+ is not OFF
:06 System event Yes
when expected with the DC Link energized
Inverter 21 Phase B+ Event
Inverter 11 and 12 (or 21 and 22), Phase Mod-
:07 Yes
ule B+ current-sharing limit was reached
Inverter 21 Phase B Current Fault Inverter 2 Disable Current feedback from Inverter 11 or 21, Phase
:03 Yes
B Phase Modules is higher than expected
:04,
INV B current sensor Phase B open/short Yes
05
132/ Inverter 1 or 2, Phase B voltage sensor was
:01 Inverter 1 Phase B Voltage Fault Inverter 1 Disable Yes
232 determined failed during VI test
Inverter 2 Phase B Voltage Fault Inverter 2 Disable Inverter 11 or 21, Phase B voltage feedback is
:02 Yes
higher than expected
134/ Inverter 11 or 21, Phase B Phase Modules did
:01 Yes
234 not turn OFF when commanded
Inverter 11 or 21, Phase C Phase Modules
:02 Inverter 11 Phase C Fault Inverter 1 Disable Yes
excessive overcurrent condition detected
Inverter 21 Phase C Fault Inverter 2 Disable Inverter 11 or 21, Phase C+ has experienced
:04 Yes
an overcurrent (saturation) condition
Inverter 11 or 21, Phase C- has experienced an
:05 Yes
overcurrent (saturation) condition
Inverter 21 Phase C Current Fault Inverter 2 Disable Current feedback from Inverter 11 or 21, Phase
:03 Yes
C Phase Modules is higher than expected
:04,
INV C current sensor Phase B open/short Yes
05
Inverter 2 Phase C Voltage Fault Inverter 2 Disable Inverter 11 or 21, Phase C voltage feedback is
:02 Yes
higher than expected
Traction Motor 1 (TM1) Speed Sensor 1 (SS1)
143/
:01 or Traction Motor 2 (TM2) Speed Sensor 2 Yes
243
(SS2) rate of change is too high
Traction Motor 1 (TM1) Speed Sensor 1 (SS1)
or Traction Motor 2 (TM2) Speed Sensor 2
:02 No
(SS2) indicates 0 speed, other sensors show
TM1 Speed Sensor Fault Inverter 1 Disable speed
Traction Motor 1 (TM1) Speed Sensor 1 (SS1)
:03 TM2 Speed Sensor Fault Inverter 2 Disable or Traction Motor 2 (TM2) Speed Sensor 2 No
(SS2) feedback signal is intermittent
:04 Overcurrent on A Yes
:05 Overcurrent on B Yes
:06 Overcurrent on C Yes
:07 Link volts above PTL Yes
144/
:01 Tach 1 single channel operation Yes
244
TM1 Speed Sensor Event System event
:02 Tach 1 high rate of change Yes
:03 Tach 1 no frequency input Yes
147/
:01 Chopper 1 did not turn off Yes
247
:02 Overcurrent on chopper 1 Yes
:04 IGBT sat flt on chopper 1 Yes
Chopper Module 1 Speed limit
:05 IGBT ps flt on chopper 1 Yes
:06 Chopper 1 on-state current high Yes
:07 Chopper 1 on-state current low Yes
:08 Chopper 1 on-state current out of range Yes
148/ Chopper Module 1 (CM1) not OFF when com-
:01 Yes
248 manded, Inverter 1 or 2 controlling
Chopper Module 1 (CM1) not ON when com-
:02 Yes
manded, Inverter 1 or 2 controlling
:03-
Chopper Module 1 Fault Speed limit INV DB1 Chop A temp short, open, warm, hot Yes
06
Chopper Module 1 (CM1) not OFF when
:07 expected with DC Link energized, Inverter 1 or Yes
2 controlling
:08 Chopper 1 off state current short Yes
Inverter 22 Phase A Fault Inverter 2 Disable Inverter 12 or 22, Phase A+ has experienced
:04 Yes
an overcurrent (saturation) condition
Inverter 12 or 22, Phase A- has experienced an
:05 Yes
overcurrent (saturation) condition
Inverter 22 Phase B Fault Inverter 2 Disable Inverter 12 or 22, Phase B+ has experienced
:04 Yes
an overcurrent (saturation) condition
Inverter 12 or 22, Phase B- has experienced an
:05 Yes
overcurrent (saturation) condition
Inverter 22 Phase C Fault Inverter 2 Disable Inverter 12 or 22, Phase C+ has experienced
:04 Yes
an overcurrent (saturation) condition
Inverter 12 or 22, Phase C- has experienced an
:05 Yes
overcurrent (saturation) condition