Busbar Protection
Busbar Protection
Busbar Protection
Basic Concepts
© ABB Group
May 11, 2017 | Slide 1
Indian Reference…New publication no.328
© ABB Group
May 11, 2017 | Slide 2
International Reference
© ABB Group
May 11, 2017 | Slide 3
Task Force Document
© ABB Group
May 11, 2017 | Slide 4
BUS BAR PROTECTION
§ Introduction
§ Protection requirements
§ Busbar Faults
§ Working principle
§ External/Internal fault conditions
§ Brief discussion on various BB protection schemes
§ Overview of REB500
§ABB Group
§May 11, 2017 | Slide 5
BUS BAR PROTECTION..Types
§ABB Group
§May 11, 2017 | Slide 6
BUS BAR PROTECTION..Types
§ABB Group
§May 11, 2017 | Slide 7
BUS BAR PROTECTION..Types
Basic features
SETTING VR > IF ( RCT + 2 RL)
VK > 2 VR
RL
RCT
VR
A B
§ABB Group
§May 11, 2017 | Slide 8
BUS BAR PROTECTION..Types
REB500 - Numerical Busbar and Breaker ABB Network Partner AG REB 500
Failure Protection
C
E
Central Unit
Distributed installation
ABB Netw ork Partner AG REB 500 ABB Netw ork Partner AG REB 500 ABB Netw ork Partner AG REB 500 ABB Netw ork Partner AG REB 500
C C C C
E E E E
E E
§ABB Group
§May 11, 2017 | Slide 9
BUS BAR PROTECTION..Types
REB500 - Numerical Busbar and Breaker Failure Protection
Central installation C
Network Control
Cubicle
Cubicle
SCS/SMS
REB004aE
§ABB Group
§May 11, 2017 | Slide 10
BUS BAR PROTECTION..Types
REB670 - Numerical Busbar and Breaker Failure Protection
Centralized installation
§ABB Group
§May 11, 2017 | Slide 11
BUS BAR PROTECTION..Types
REB670 - Numerical Busbar and Breaker Failure Protection
Centralized installation
§ABB Group
§May 11, 2017 | Slide 12
BUS BAR PROTECTION..Types
§ABB Group
§May 11, 2017 | Slide 13
BUS BAR PROTECTION..Types
§ABB Group
§May 11, 2017 | Slide 14
Considerations…
§ Where Centralized Busbar is preferred and where Decentralized
§ Check zone where it is applicable
§ Busbar Differential pickup based on minimum Bus fault
§ What is minimum Bus fault and maximum bus fault?
§ High impedance Busbar is not good for complex bus arrangements
§ End fault and when it is required?
§ Open CT block or supervise mode?
§ Sipat case Busbar to be explained
§ CT saturation, how busbar can be stable with numerical technology
§ Open CT, how busbar can be stable with numerical technology
§ CT demands for different types of Busbar protections
§ABB Group
§May 11, 2017 | Slide 15
BUSBAR Protection
Bus bar have often been left without specific protection for one or
more of the following reasons
§ The bus bars and switchgear have a high degree of reliability,to the point of
being regarded as insitrinsically safe.
§ It was feared that the accidental operation of bus bar protection cause
widespread dislocation 0f the power system which if not quickly
cleared,would cause more loss than would very infrequent actual bus faults.
§ It was hoped that the system protection or the back up protection would
provide sufficient bus protection if needed.
§ABB Group
§May 11, 2017 | Slide 16
Possible faults on Busbar
§ABB Group
§May 11, 2017 | Slide 17
Protection requirements
§ABB Group
§May 11, 2017 | Slide 18
Measuring Principle
Who knows
Mr. Kirchhoff ?
§ABB Group
§May 11, 2017 | Slide 19
Measuring Principle
Kirchhoffs 1st Law: Node Rule
I1 + I2 + I3 = S I = 0
§ABB Group
§May 11, 2017 | Slide 20
Measuring Principle
Kirchhoffs 1st Law: Node Rule
If
I1 + I2 + I3 = S I
¹0
ABB Group
May 11, 2017 | Slide 21
Measuring Principle
Differential current measurement
S I = I1 + I2 + I3
If
ABB Group
May 11, 2017 | Slide 22
Measuring Principle
Stabilised differential current measurement
S I > Ikmin ; and Þ Trip Busbar
If
(S I / S ½ I ½) > k
Differential current Idiff= | S I |
Protection
k= 1
k= 0,85
Low impedance
measuring
principle !!!
no fault
Ikmin
0
Restraint current IRest = S | I|
ABB Group
May 11, 2017 | Slide 23
Measuring Principle
Stabilised differential current measurement
Advantage:
load depending tripping value
as more (load / fault) current is flowing on the
busbar
as more differential current is required to generate
a tripping signal
Þ system is very stable in case of
CT failure
CT saturation
ABB Group
May 11, 2017 | Slide 24
§Measuring Principle §load depending tripping value
§ABB Group
§May 11, 2017 | Slide 25
Measuring Principle load depending tripping value
Busbar fault condition single injection
I1 =
1000A
ABB Group
May 11, 2017 | Slide 26
Measuring Principle load depending tripping value
DI = + I1
=+1
= 1 kA
Sl = + ½+ I1½
= + 1 kA
= 1 kA
ABB Group
May 11, 2017 | Slide 28
Measuring Principle load depending tripping value
no fault
Ikmin
0
Restraint current IRest = S | I |
I1 = I2 = I3 = I4 =
1000A 2500A 1500A 2000A
ABB Group
May 11, 2017 | Slide 30
Measuring Principle load depending tripping value
DI = + I1 + I2 + I3 + I4
= + 1 kA + 2.5 kA + 1.5 kA + 2 kA
= 7 kA
Sl = + ½+ I1½+ ½+ I2½ + ½+ I3½ + ½+ I4½
= + 1 kA + 2.5 kA + 1.5 kA + 2 kA
= 7 kA
ABB Group
May 11, 2017 | Slide 32
Measuring Principle load depending tripping value
no fault
Ikmin
0
Restraint current IRest = S | I |
I1 =
6000A
I2 = I3 = I4 =
2500A 1500A 2000A
ABB Group
May 11, 2017 | Slide 34
Measuring Principle External fault condition
DI = + I1 + I2 + I3 + I4
= - 6 kA + 2.5 kA + 1.5 kA + 2 kA
= 0 kA
Sl = + ½+ I1½+ ½+ I2½ + ½+ I3½ + ½+ I4½
= + 6 kA + 2.5 kA + 1.5 kA + 2 kA
= 12 kA
ABB Group
May 11, 2017 | Slide 36
Measuring Principle External fault condition
no fault
Ikmin
0
Restraint current IRest = S | I |
CT shorted !!!
I1 =
6000A
I2 = I3 = I4 =
2500A 1500A 2000A
ABB Group
May 11, 2017 | Slide 38
Measuring Principle Current transformer failure
DI = + I1 + I2 + I3 + I4
=
=
Sl = + ½+ I1½+ ½+ I2½ + ½+ I3½ + ½+ I4½
=
=
ABB Group
May 11, 2017 | Slide 40
Measuring Principle Current transformer failure
DI = + I1 + I2 + I3 + I4
= + 0 kA + 2.5 kA + 1.5 kA + 2 kA
= 6 kA
Sl = + ½+ I1½+ ½+ I2½ + ½+ I3½ + ½+ I4½
= + 0 kA + 2.5 kA + 1.5 kA + 2 kA
= 6 kA
ABB Group
May 11, 2017 | Slide 41
Measuring Principle Current transformer failure
no fault
Ikmin
0
Restraint current IRest = S | I |
ABB Group
May 11, 2017 | Slide 42
Measuring Principle Current transformer failure
no fault
Ikmin
0
Restraint current IRest = S | I |
Þ trip measurement system !!!
(worst case condition)
ABB Group
May 11, 2017 | Slide 43
Measuring Principle Current transformer failure
during load condition
CT shorted !!!
I1 =
600A
I2 = I3 = I4 =
250A 150A 200A
ABB Group
May 11, 2017 | Slide 44
Measuring Principle Current transformer failure
DI = + I1 + I2 + I3 + I4
=
=
Sl = + ½+ I1½+ ½+ I2½ + ½+ I3½ + ½+ I4½
=
=
ABB Group
May 11, 2017 | Slide 46
Measuring Principle Current transformer failure
DI = + I1 + I2 + I3 + I4
= + 0 kA + 250 A + 150 A + 200 A
= 600 A
Sl = + ½+ I1½+ ½+ I2½ + ½+ I3½ + ½+ I4½
= + 0 kA + 250 A + 150 A + 200 A
= 600 A
ABB Group
May 11, 2017 | Slide 47
Measuring Principle Current transformer failure
no fault
Ikmin
0
Restraint current IRest = S | I |
ABB Group
May 11, 2017 | Slide 48
Measuring Principle Current transformer failure
no fault
Ikmin
0
Restraint current IRest = S | I |
Þ measurement system stable !!!
Þ differential current alarm !!!
ABB Group
May 11, 2017 | Slide 49
How is it possible to detect
failures in the CT circuits
???
ABB Group
May 11, 2017 | Slide 50
Differential Current Supervision
Þ Differential Current Alarm
ABB Group
May 11, 2017 | Slide 51
Differential Current Supervision
ABB Group
May 11, 2017 | Slide 53
Differential Current Supervision
ABB Group
May 11, 2017 | Slide 54
Differential Current Supervision
SP = 400A
100A 300A
SN = 400A
Iin = Max ( SP & SN) = 400A
200A 200A
Iout = Min (SP & SN) = 400A
Id = 0A
ABB Group
May 11, 2017 | Slide 55
Differential Current Supervision
SP = 20kA
10kA 5kA
SN = 0A
Iin = Max ( SP & SN) = 20kA
5kA 0kA
Iout = Min (SP & SN) = 0A
Id = 20kA
ABB Group
May 11, 2017 | Slide 56
Differential Current Supervision
ABB Group
May 11, 2017 | Slide 57
Differential Current Supervision
SP = 15kA
10kA 5kA
SN = 0A
15kA
CT Iin = Max ( SP & SN) = 15kA
Saturated
0kA
Iout = Min (SP & SN) = 0A
Id = 15kA
ABB Group
May 11, 2017 | Slide 58
Differential Current Supervision
ABB Group
May 11, 2017 | Slide 59
Differential Current Supervision
SP = 400A
100A 300A
SN = 200A
200A
CT Iin = Max ( SP & SN) = 400A
Opened
200A
Iout = Min (SP & SN) = 200A
Iin will not change
Iout will reduce
ABB Group
May 11, 2017 | Slide 60
Differential Current Supervision
ABB Group
May 11, 2017 | Slide 61
Differential Current Supervision
Slow OCT Fast OCT
• Lasts for few seconds • Iin = Iout one cycle before
• No load current changes • Iin is unchanged
• Iin >> Iout • Iout drops more when OCT
level
• Wait till tslow OCT
• Id increases OCT level
• Iout + Id = Iin once cycle
before
ABB Group
May 11, 2017 | Slide 63
Intertripping
Tripping flow chart
Measurement Intertripping
system system
TRIP CB
TRIP BBP
trip all CBs TRIP CB
zone x
connected TRIP CB
to zone x
ABB Group
May 11, 2017 | Slide 65
Local breaker backup
21
LBB REB500
F
ABB Group
May 11, 2017 | Slide 66
Nadeem, ABB Ltd., Bangalore, May 11, 2017
© ABB Group
May 11, 2017 | Slide 67
SLD.. Initial condition
ABB Group
May 11, 2017 | Slide 68
What happened…
ABB Group
May 11, 2017 | Slide 70
SLD.. After fault
ABB Group
May 11, 2017 | Slide 71
Solution-1
ABB Group
May 11, 2017 | Slide 72
Solution-2
ABB Group
May 11, 2017 | Slide 73
Solution-3
ABB Group
May 11, 2017 | Slide 74