loads (AC-1), 4-pole, 4 NO, 60 ... 140 A - in the Catalog
4/18 3TK1 contactors for resistive loads Add-On IC 10 AO · 2012
(AC-1), 4-pole, 4 NO, 200 ... 1000 A at the Information and Download
Center
4/22 3TK20 contactors, 4-pole, 4 kW
- in the interactive catalog CA 01
4/29 SIRIUS 3RT25 contactors, 4-pole,
2 NO + 2 NC, 4 ... 11 kW - in the Industry Mall
4/33 SIRIUS 3RT15 contactors, 4-pole,
2 NO + 2 NC, 18.5 kW
4/35 SIRIUS 3RT16 capacitor contactors,
12.5 ... 50 kvar
Contactors with extended
operating range 0.7 ... 1.25 × Us
for railway applications
4/39 SIRIUS 3RT20 motor contactors,
5.5 ... 18.5 kW
4/43 SIRIUS 3RT10 motor contactors,
18.5 ... 45 kW
4/46 3TB5 motor contactors, 55 ... 200 kW
4/48 3TC contactors for switching
DC voltage, 2-pole
Ch.5 SIRIUS 3RH21 contactor relays
Ch.5 3TH4 contactor relays
- Contactors for switching
DC voltage
4/50 3TC contactors,1- and 2-pole,
32 ... 400 A
Coupling contactors
Ch.3 SIRIUS 3RT20 coupling contactors
(interface), 3-pole, 3 ... 15 kW
Ch.5 SIRIUS 3RH21 coupling relays
for switching auxiliary circuits,
4-pole
Siemens
Siemens
IC 10
IC· 10
2012
· 2012
© Siemens AG 2012
Introduction
■ Overview
Size S00 S0
Type 3RT23 1, 3RT25 1 3RT23 2, 3RT25 2
4-pole 3RT23, 3RT25 contactors
Type 3RT23 16 3RT23 17 3RT25 16 3RT25 17 3RT25 18 3RT23 25 3RT23 26 3RT23 27 3RT25 26
4
Introduction
Size -- 00 --
4
Type 3TK1 3TK20 3TG10
3TK, 3TG contactors
Type 3TK10 3TK11 3TK12 3TK13 3TK14 3TK15 3TK17 3TK20 3TG10
AC, DC operation (p. 4/20) (p. 4/27) (p. 4/62)
AC-1 (40 °C, ≤ 690 V)
Ie A 200 250 300 350 550 800 1000 18 20
400 V kW 132 165 197 230 362 527 658 10 13
230 V kW 76 95 114 132 308 303 378 6 7.5
500 V kW 165 206 247 288 452 658 828 13 --
690 V kW 227 284 341 397 624 908 1135 17 --
AC-2 and AC-3
Ie/AC-3/400 V A 120 145 210 210 400 550 700 8.4 8.4
400 V kW 55 75 110 110 200 280 370 4 4
127 V kW -- -- -- -- -- -- -- 1.4 --
230 V kW 30 45 75 75 110 160 220 2.5
500 V kW 4
690 V kW 4
Note:
Safety characteristics for contactors
see "Appendix" ➞ "Standards and Approvals" ➞ "Overview"
Connection methods
The contactors are available with screw terminals (box terminals
or flat connectors) or with spring-type terminals.
Devices of the 3TK2 series are also available for connection with
flat connectors and solder pin connectors.
As an option the devices of the 3RT2 series are also available for
connection with ring terminal lugs, particularly versions for North
America and Japan.
Screw terminals
Spring-type terminals
Flat connectors
■ Overview
Standards Size S3: AC or DC operation
Sizes S6 to S12: AC/DC operation
IEC 60947-1, EN 60947-1,
IEC 60947-4-1, EN 60947-4-1, The following applies for sizes S6 to S12:
IEC 60947-5-1, EN 60947-5-1 (auxiliary switches) • Withdrawable coils
The contactors are suitable for use in any climate. They are fin- • Integrated coil circuit (varistor)
ger-safe according to EN 50274. • Main conductors: Busbar connections
• Auxiliary and control conductors: Screw terminals
3RT14 contactors are used for switching resistive loads (AC-1)
or as contactors, for example for variable-speed operating The accessories for the 3RT10 contactors can also be used
mechanisms that normally only have to carry the current. here.
General descriptions of the sizes S3 to S12 see Chapter 3,
"Power contactors for switching motors" ➞ "SIRIUS 3RT10
4
■ Technical specifications
Type 3RT14 46 3RT14 56 3RT14 66 3RT14 76
Size S3 S6 S10 S12
H
W
• With mounted auxiliary switch block mm 70 x 146 x 183 120 x 172 x 145 x 210 x 160 x 214 x
217 251 271
General technical specifications
Permissible mounting positions
NSB0_00478c
360° 22,5° 22,5°
NSB0_00649a
22,5° 22,5°
The contactors are designed for operation on a 90° 90°
vertical mounting surface.
NSB0_00477a
4
Short-circuit current Ik = 400 A acc. to IEC 60947-5-1
Control circuit
Coil operating range (AC/DC) 0.8 ... 1.1 x Us 0.8 x Us min ... 1.1 x Us max
Power consumption of the solenoid coils (when coil is cold and 1.0 x Us)
Standard version:
• AC operation, 50 Hz Closing VA 270 --
P.f. 0.68 --
Closed VA 22 --
P.f. 0.27 --
• AC operation, 50/60 Hz Closing VA 298/274 --
P.f. 0.7/0.62 --
Closed VA 27/20 --
P.f. 0.29/0.31 --
For USA and Canada:
• AC operation, 50 Hz Closing VA 270 --
P.f. 0.68 --
Closed VA 22 --
P.f. 0.27 --
• AC operation, 60 Hz Closing VA 300 --
P.f. 0.52 --
Closed VA 21 --
P.f. 0.29 --
• DC operation Closing = Closed W 15 --
Power consumption of the solenoid operation
(when coil is cool and rated range Us min ... Us max)
• Conventional operating mechanisms
- AC operation Closing at Us min VA/p.f. -- 250/0.9 490/0.9 700/0.9
Closing at Us max VA/p.f. -- 300/0.9 590/0.9 830/0.9
Closed at Us min VA/p.f. -- 4.8/0.8 5.6/0.9 7.6/0.9
Closed at Us max VA/p.f. -- 5.8/0.8 6.7/0.9 9.2/0.9
- DC operation Closing at Us min W -- 300 540 770
Closing at Us max W -- 360 650 920
Closed at Us min W -- 4.3 6.1 8.5
Closed at Us max W -- 5.2 7.4 10
• Solid-state operating mechanism
- AC operation Closing at Us min VA/p.f. -- 190/0.8 400/0.8 560/0.8
Closing at Us max VA/p.f. -- 28/0.8 530/0.8 750/0.8
Closed at Us min VA/p.f. -- 3.5/0.5 4/0.5 5.4/0.8
Closed at Us max VA/p.f. -- 4./0.4 5/0.4 7/0.8
- DC operation Closing at Us min W -- 250 440 600
Closing at Us max W -- 320 580 800
Closed at Us min W -- 2.3 3.2 4
Closed at Us max W -- 2.8 3.8 5
PLC control input (IEC 61131-2/type 2) V DC 24, at ≤ 30 mA power consumption
• Operating range V DC 17 ... 30
Operating times for 0.8 ... 1.1 x Us1)
Total break time = Opening delay + Arcing time
• AC operation - Closing delay ms 17 ... 90 --
- Opening delay ms 10 ... 25 --
• DC operation - Closing delay ms 90 ... 230 --
- Opening delay ms 14 ... 20 --
• Arcing time ms 10 ... 15 --
Operating times for 1.0 x Us1)
• AC operation - Closing delay ms 18 ... 30 --
- Opening delay ms 11 ... 23 --
• DC operation - Closing delay ms 100 ... 120 --
- Opening delay ms 16 ... 20 --
1)
The OFF-delay of the NO contact and the ON-delay of the NC contact are
increased if the contactor coils are attenuated against voltage peaks
(varistor +2 to 5 ms, diode assembly: 2 to 6 times).
- For Us min ... Us max Closing delay ms -- 100 ... 120 110 ... 130 125 ... 150
Opening delay ms -- 80 ... 90 80 ... 100 80 ... 100
• Solid-state operating mechanism, actuated via PLC input
- For 0.8 x Us min ... 1.1 x Us max Closing delay ms -- 35 ... 75 45 ... 80 60 ... 90
Opening delay ms -- 80 ... 90 80 ... 100 80 ... 100
- For Us min ... Us max Closing delay ms -- 40 ... 60 50 ... 65 65 ... 80
Opening delay ms -- 80 ... 90 80 ... 100 80 ... 100
• Arcing time ms -- 10 ... 15 10 ... 15 10 ... 15
4
Rear clamping point • Finely stranded with end sleeve mm² 2.5 ... 50
connected • Finely stranded without end sleeve mm² 10 ... 50
• Solid mm² 2.5 ... 16
NSB0_00480
Both clamping points • Finely stranded with end sleeve mm² 1 x 50, 1 x 70 --
connected • Finely stranded without end sleeve mm² 1 x 50, 1 x 70 --
4
• Stranded mm² 2 x 70 --
NSB0_00481
• AWG cables, solid or stranded AWG 6 ... 250 kcmil 3/0 ... 600 kcmil
• Ribbon cable conductors mm 3 x 9 x 0.8 ... 10 x 15.5 x 0.8 Min. 6 x 9 x 0.8, max. 20 x 24 x 0.5
(Number x Width x Thickness)
Rear clamping point • Finely stranded with end sleeve mm² 10 ... 120 120 ... 185
connected • Finely stranded without end sleeve mm² 16 ... 120 120 ... 185
• Stranded mm² 16 ... 120 120 ... 240
NSB0_00480
• AWG cables, solid or stranded AWG 6 ... 250 kcmil 250 ... 500 kcmil
• Ribbon cable conductors mm 3 x 9 x 0.8 ... 10 x 15.5 x 0.8 Min. 6 x 9 x 0.8, max. 20 x 24 x 0.5
(Number x Width x Thickness)
Both clamping points • Finely stranded with end sleeve mm² Max. 1 x 95, 1 x 120 Min. 2 x 50, max. 2 x 185
connected • Finely stranded without end sleeve mm² Max. 1 x 95, 1 x 120 Min. 2 x 50, max. 2 x 185
• Stranded mm² max. 2 x 120 Min. 2 x 70, max. 2 x 240
NSB0_00481
• AWG cables, solid or stranded AWG Max. 2 x 3/0 Min. 2 x 2/0, max. 2 x 500 kcmil
• Ribbon cable conductors mm Max. 2 x (10 x 15.5 x 0.8) Max. 2 x (20 x 24 x 0.5)
(Number x Width x Thickness)
• Terminal screws M10 (hexagon socket, A/F4) M12 (hexagon socket, A/F 5)
- Tightening torque Nm 10 ... 12 20 ... 22
lb.in 90 ... 110 180 ... 195
Without box terminal/busbar connection 1) 2)
3RT14 46-1A. .0
4
Size Rated data AC-1, Auxiliary Rated control DT Screw terminals PU PS* PG
Tu: 40 °C contacts supply voltage (UNIT,
Opera- Rating of AC loads (p f. = 0.95) at Us SET, M)
tional Version Order No. Price
current Ie per PU
Up to
690 V 230 V 400 V 500 V 690 V
A kW kW kW kW NO NC V
For screw fixing and snap-on mounting onto
TH 35 and TH 75 standard mounting rail
AC operation
A1(+) 1/L1 3/L2 5/L3
A2(–)
2/T1 4/T2 6/T3
A2(–)
2/T1 4/T2 6/T3
3RT14 6.
4
Size Rated data AC-1, Auxiliary Rated control DT Screw terminals PU PS* PG
Tu: 40 °C contacts supply voltage (UNIT,
Opera- Rating of AC loads (p f. = 0.95) at Us SET, M)
tional Version Order No. Price
current Ie per PU
Up to
690 V 230 V 400 V 500 V 690 V
A kW kW kW kW NO NC V
Conventional operating mechanisms
A2(–)
2/T1 4/T2 6/T3 14 22
S6 275 105 180 225 310 1 1 96 ... 127 B 3RT14 56-6PF35 1 1 unit 41B
200 ... 277 B 3RT14 56-6PP35 1 1 unit 41B
S10 400 151 263 329 454 1 1 200 ... 277 B 3RT14 66-6PP35 1 1 unit 41B
S12 690 261 454 568 783 1 1 200 ... 277 B 3RT14 76-6PP35 1 1 unit 41B
With AS-Interface interface and remaining lifetime indicator (RLT)
1/L1 3/L2 5/L3 13 21
A1(+)
A2(–)
2/T1 4/T2 6/T3 14 22
S6 275 105 180 225 310 1 1 96 ... 127 B 3RT14 56-6QF35 1 1 unit 41B
200 ... 277 B 3RT14 56-6QP35 1 1 unit 41B
S10 400 151 263 329 454 1 1 200 ... 277 B 3RT14 66-6QP35 1 1 unit 41B
S12 690 261 454 568 783 1 1 200 ... 277 B 3RT14 76-6QP35 1 1 unit 41B
■ Overview ■ Application
Standards The contactors are suitable
IEC 60947-1, EN 60947-1, • For switching of resistive loads
IEC 60947-4-1, EN 60947-4-1, • For isolating systems with ungrounded or poorly grounded
IEC 60947-5-1, EN 60947-5-1 (auxiliary switches) neutral conductors
The contactors are suitable for use in any climate. They are fin- • For system transfers when alternative AC power supplies are
ger-safe according to EN 50274. used
The accessories for the 3-pole SIRIUS 3RT20 contactors can • For use as contactors which only carry current and do not
also be used for the 4-pole versions. have to switch in case of inductive loads – e.g.variable-speed
operating mechanisms
Size S0 contactors have 2 auxiliary contacts 1 NO and 1 NC • For switching mixed loads in distribution systems (e.g. for sup-
integrated in the basic unit. plying heaters, lamps, motors, PC power supply units) with
4
Mountable auxiliary contacts p.f. > 0.8 according to IEC 60947-4-1, test conditions for utili-
zation category AC-1.
Size S00
General descriptions of the sizes S00 and S0 see Chapter 3,
4 auxiliary contacts, including no more than 3 NC. "Power contactors for switching motors" ➞ "SIRIUS 3RT20
Size S0 contactors, 3-pole, 3 to 18.5 kW".
■ Technical specifications
Type 3RT23 16 3RT23 17 3RT23 25 3RT23 26 3RT23 27
Size S00 S0
Dimensions (W x H x D)1) mm 45 x 57.5 x 73 / 60 x 85 x 97 /
H
45 x 70 x 73 60 x 101.5 x 97
• With mounted auxiliary switch block mm 45 x 57.5 x 116 / 60 x 85 x 141 /
D
W
45 x 70 x 121 60 x 101.5 x 144
General technical specifications
Permissible mounting positions
The contactors are designed for operation on a vertical
NSB0_00478c
NSB0_00477a
- P.f. -- 0.82
- Closed VA -- 9.8
- P.f. -- 0.25
• AC operation, 50/60 Hz, standard version
- Closing VA 27/24.3 37/33 81/79
- P.f. 0.8/0.75 0.8/0.75 0.72/0.74
- Closed VA 4.2/3.3 5.7/4.4 10.5/8.5
- P.f. 0.25/0.25 0.25/0.25 0.25/0.28
• AC operation, 60 Hz, USA, Canada
- Closing VA 31.7 43 87
- P.f. 0.77 0.77 0.76
- Closed VA 4.8 6.5 9.4
- P.f. 0.25 0.25 0.28
• DC operation (closing = closed) W 4 5.9
Operating times for 0.8 ... 1.1 x Us1)
Total break time = Opening delay + Arcing time
• AC operation
- Closing delay ms 8 ... 35 8 ... 33 9 ... 38 8 ... 40
- Opening delay ms 3.5 ... 14 4 ... 15 4 ... 16 4 ... 16
• DC operation
- Closing delay ms 30 ... 100 50 ... 170
- Opening delay ms 7 ... 13 15 ... 17.5
• Arcing time ms 10 ... 15 10
Main circuit
AC capacity
Utilization category AC-1, switching resistive loads
• Rated operational currents Ie At 40 °C, up to 690 V A 18 22 35 40 50
At 60 °C, up to 690 V A 16 20 30 35 42
• Rated power for AC loads At 230 V kW 6.5 7.5 11 13 16
P.f. = 0.95 (at 40 °C) 400 V kW 12 14.5 23 26 33
• Minimum conductor cross-section At 40 °C mm2 2.5 2.5 10 10 10
for loads with Ie At 60 °C mm2 2.5 2.5 10 10 10
Utilization categories AC-2 and AC-3
• Rated operational currents Ie At 60 °C, up to 400 V A 9 12 15.5 17 17
• Rated power for At 230 V kW 3 3 4 4 4
slipring or squirrel-cage motors 400 V kW 4 5.5 7.5 9 9
at 50 and 60 Hz
1) With size S00, DC operation: Operating times for 0.85 ... 1.1 x Us.
4
3RT23 1.-1A.00 3RT23 1.-2A.00 3RT23 2.-1A.00 3RT23 2.-2A. 00
Rated data AC-1, Auxiliary contacts Rated control DT Screw terminals DT Spring-type
Tu: 40/60 °C supply voltage terminals
Opera- Ratings of AC loads Ident. Version Us
tional (p.f. = 0.95) No.
current Ie at 50 Hz and Order No. Price Order No. Price
per PU per PU
400 V
A kW NO NC V AC
For screw fixing and snap-on mounting onto TH 35 standard
mounting rail
Size S001)
1/L1 3/L2 5/L3 7/L4
A1(+)
A2(–)
2/T1 4/T2 6/T3 8/T4
A2(–)
2/T1 4/T2 6/T3 8/T4 14 22
2)
35 / 30 22 / 20 11 1 1 24, 50 Hz B 3RT23 25-1AB00 B 3RT23 25-2AB00
110, 50 Hz B 3RT23 25-1AF00 B 3RT23 25-2AF00
230, 50 Hz A 3RT23 25-1AP00 A 3RT23 25-2AP00
40 / 352) 26 / 23 11 1 1 24, 50 Hz B 3RT23 26-1AB00 B 3RT23 26-2AB00
110, 50 Hz B 3RT23 26-1AF00 B 3RT23 26-2AF00
230, 50 Hz A 3RT23 26-1AP00 A 3RT23 26-2AP00
502) 33 11 1 1 24, 50 Hz B 3RT23 27-1AB00 B 3RT23 27-2AB00
110, 50 Hz B 3RT23 27-1AF00 B 3RT23 27-2AF00
230, 50 Hz A 3RT23 27-1AP00 A 3RT23 27-2AP00
1)
For size S00: Coil operating range
at 50 Hz: 0.8 ... 1.1 x Us,
at 60 Hz: 0.85 ... 1.1 x Us.
2) Minimum conductor cross-section 10 mm².
A2(–)
2/T1 4/T2 6/T3 8/T4
A2(–)
2/T1 4/T2 6/T3 8/T4 14 22
1)
35 / 30 22 / 20 11 1 1 24 A 3RT23 25-1BB40 A 3RT23 25-2BB40
220 B 3RT23 25-1BM40 B 3RT23 25-2BM40
40 / 351) 26 / 23 11 1 1 24 A 3RT23 26-1BB40 A 3RT23 26-2BB40
220 B 3RT23 26-1BM40 B 3RT23 26-2BM40
501) 33 11 1 1 24 A 3RT23 27-1BB40 A 3RT23 27-2BB40
220 B 3RT23 27-1BM40 B 3RT23 27-2BM40
1) Minimum conductor cross-section 10 mm².
Other voltages according to page 4/38 on request.
Accessories and spare parts see "3RT20 Contactors",
Chapter 3.
■ Overview
Standards The accessories for the 3-pole 3RT10 contactors can also be
used for the 4-pole versions.
IEC 60947-1, EN 60947-1,
IEC 60947-4-1, EN 60947-4-1, The contactors are suitable for switching mixed loads in distribu-
IEC 60947-5-1, EN 60947-5-1 (auxiliary switches) tion systems (e.g. for supplying heaters, lamps, motors, PC
power supply units) with p.f. > 0.8 according to IEC 60947-4-1,
The contactors are suitable for use in any climate. They are fin- test conditions for utilization category AC-1.
ger-safe according to EN 50274.
■ Technical specifications
Type 3RT13 36 3RT13 44 3RT13 46
Size S2 S3 S3
4
H
Dimensions (W x H x D) mm 61 x 85 x 86 73 x 112 x 110 93 x 146 x 134
D
• With mounted auxiliary switch block W mm 61 x 85 x 135 73 x 112 x 160 93 x 146 x 183
3RT13 3.-1A.00
Rated data AC-1, Rated control supply DT Screw terminals DT Spring-type
Tu: 40/60 °C voltage Us terminals
Operational current Ratings of AC loads (p.f. = 0.95) Order No. Price Order No. Price
Ie at 50 Hz and per PU per PU
400 V
A kW V AC
For screw fixing and snap-on mounting onto TH 35 standard
mounting rail
Size S2
1/L1 3/L2 5/L3 7/L4
A1(+)
A2(–)
2/T1 4/T2 6/T3 8/T4
A2(–)
2/T1 4/T2 6/T3 8/T4
4
3RT13 36-1. . .0 3RT13 4.-1. . .0
Rated data AC-1, Rated control supply DT Screw terminals DT Spring-type
Tu: 40/60 °C voltage Us terminals
Operational current Ratings of AC loads (p.f. = 0.95) Order No. Price Order No. Price
Ie at 50 Hz and per PU per PU
400 V
A kW V DC
For screw fixing and snap-on mounting onto TH 35 standard
mounting rail
Size S2
1/L1 3/L2 5/L3 7/L4
A1(+)
A2(–)
2/T1 4/T2 6/T3 8/T4
60 / 55 39 / 36 24 } 3RT13 36-1BB40 --
220 B 3RT13 36-1BM40 --
Size S3
1/L1 3/L2 5/L3 7/L4
A1(+)
A2(–)
2/T1 4/T2 6/T3 8/T4
■ Overview
Standards The contactors are used mainly for resistive loads (AC-1 and
p.f. > 0.95). They are also suitable for switching mixed loads in
IEC 60947-1, EN 60947-1, distribution systems (e.g. for supplying heaters, lamps, motors,
IEC 60947-4-1, EN 60947-4-1, PC power supply units) with p.f. > 0.8 according to
IEC 60947-5-1, EN 60947-5-1 (auxiliary switches) IEC 60947-4-1, test conditions for utilization category AC-1.
The contactors also comply with the requirements of the stan-
dards NFC 63-110 and NFC 20–040. Control circuits
The contactors are suitable for use in any climate. They are fin- The solenoid coils of the 3TK10 to 3TK13 contactors (operating
ger-safe according to EN 50274. Terminal covers may have to currents up to 350 A) are designed as plug-in coils.
be fitted onto the connecting bars, depending on the configura- Surge suppression
tion with other devices.
The solenoid coils of the 3TK1 contactors can be connected at
4
■ Technical specifications
Contactors Type 3TK1
Rated data of the auxiliary contacts according to IEC 60947-5-1
Rated insulation voltage Ui V 690
(pollution degree 3)
Conventional thermal current Ith = A 10
Rated operational current Ie/AC-12
AC load
Rated operational current Ie/AC-15/AC-14
• For rated operational voltage Ue
24 V A 6
110 V A 6
125 V A 6
220 V A 6
230 V A 6
380 V A 4
400 V A 4
500 V A 1
660 V A 1
690 V A 1
DC load
Rated operational current Ie/DC-12
• For rated operational voltage Ue
24 V A --
60 V A --
110 V A --
125 V A --
220 V A --
440 V A --
600 V A --
Rated operational current Ie/DC-13
• For rated operational voltage Ue
24 V A 6
60 V A 6
110 V A 1.8
125 V A --
220 V A 0.6
440 V A --
600 V A --
s and u rated data of the auxiliary contacts
Rated voltage V AC, 600
max.
Switching capacity A 600, P 600
H
x 155 x 155
D
W
NSB0_00649a
22,5° 22,5°
Upright mounting position also permissible 90° 90°
4
Rated insulation voltage Ui (pollution degree 3) V 1000
Ambient temperature
• During operation °C -25 ... +55
• During storage °C -50 ... +70
Degree of protection acc. to IEC 60947-1, Appendix C IP00
Touch protection acc. to EN 50274 Finger-safe with cover
Shock resistance, sine pulse g/ms 10/15
Short-circuit protection
Main circuit
Fuse links, operational class gG:
LV HRC, type 3NA; DIAZED, type 5SB; NEOZED, type 5SE
according to IEC 60947-4-1/EN 60947-4-1
• Type of coordination "1" A 250 355 800 1000
• Type of coordination "2" A 250 315 630 850
Auxiliary circuit
Short-circuit test with fuse links of gG operational class: A 10
DIAZED, type 5SB; NEOZED, type 5SE
with short-circuit current Ik = 1 kA acc. to IEC 60947-5-1
Control circuits
Coil operating range 0.85 ... 1.1 x Us
Power consumption of the solenoid coils
(when coil is cold and 1.0 x Us)
• 50 Hz
- Closing VA 820 1100 3500
- P.f. 0.4 0.35 0.26
- Closed VA 44 52 125
- P.f. 0.34 0.35 0.4
• 60 Hz
- Closing VA 990 1200 4000
- P.f. 0.35 0.31 0.22
- Closed VA 52 65 140
- P.f. 0.35 0.34 0.43
Operating times for 1.0 x Us
• Closing delay ms 20 ... 40 30 ... 60
• Opening delay ms 7 ... 15 10 ... 20
• Arcing time ms 10 10
Main circuit
AC capacity
Utilization category AC-1, switching resistive loads
• Rated operational currents Ie At 40 °C up to 690 V A 200 250 300 350 550 800 1000
At 50 °C up to 690 V A 180 230 270 310 470 650 850
• Rated power for AC loads At 230 V kW 76 95 114 132 208 303 378
with p.f. = 0.95 (at 40°C) 400 V kW 132 165 197 230 362 527 658
500 V kW 165 206 247 288 452 658 828
690 V kW 227 284 341 397 624 908 1135
• Minimum conductor cross-section At 40 °C mm² 95 150 185 240 185 240 300
for load with Ie
Utilization categories AC-2 and AC-3
• Rated operational currents Ie Up to 400 V A 120 145 210 210 400 550 700
• Rated power of squirrel-cage At 230 V kW 30 45 75 75 110 160 220
or slipring motors at 400 V kW 55 75 110 110 200 280 370
50 Hz and 60 Hz
• Short-time current at 40° C in cold state up to 10 s A 900 1200 1600 1600 5300 5300 6400
Switching frequency1)
Switching frequency z in operating cycles/hour
• Contactors without overload relays No-load switching 1/h 3600
frequency
AC-1 1/h 300
AC-3 1/h 300
1) Dependence of the switching frequency z ' on the operational current I '
and operational voltage U ' : z ' = z ⋅ (Ie/I ') ⋅ (400 V/U ')1.5 ⋅ 1/h.
3TK13
Rated data AC-1 Auxiliary Rated control supply DT Screw terminals PU PS* PG
contacts voltage Us (UNIT,
Operational Rating of AC loads (p f. = 0.95) Version SET, M)
current Ie at Order No. Price
up to 690 V per PU
(at 40 °C)
230 V 400 V 690 V 1000 V
A kW kW kW kW NO NC V AC
AC operation
1/L1 3/L2 5/L3 7/L4 13 21 31 43
A1
A2
2/T1 4/T2 6/T3 8/T4 14 22 32 44
200 75 130 225 205 2 2 220 ... 230, 50 Hz B 3TK10 42-0AP0 1 1 unit 41B
230 ... 240, 50 Hz D 3TK10 42-0AU0 1 1 unit 41B
110/120, 50/60 Hz D 3TK10 42-0AF0 1 1 unit 41B
24, 50 Hz D 3TK10 42-0AB0 1 1 unit 41B
250 90 165 280 200 2 2 220 ... 230, 50 Hz B 3TK11 42-0AP0 1 1 unit 41B
230 ... 240, 50 Hz D 3TK11 42-0AU0 1 1 unit 41B
110/120, 50/60 Hz D 3TK11 42-0AF0 1 1 unit 41B
24, 50 Hz D 3TK11 42-0AB0 1 1 unit 41B
300 110 195 340 325 2 2 220 ... 230, 50 Hz B 3TK12 42-0AP0 1 1 unit 41B
230 ... 240, 50 Hz D 3TK12 42-0AU0 1 1 unit 41B
110/120, 50/60 Hz D 3TK12 42-0AF0 1 1 unit 41B
24, 50 Hz D 3TK12 42-0AB0 1 1 unit 41B
350 130 230 395 370 2 2 220 ... 230, 50 Hz B 3TK13 42-0AP0 1 1 unit 41B
230 ... 240, 50 Hz D 3TK13 42-0AU0 1 1 unit 41B
110/120, 50/60 Hz D 3TK13 42-0AF0 1 1 unit 41B
24, 50 Hz D 3TK13 42-0AB0 1 1 unit 41B
550 205 360 620 510 2 2 220 ... 230, 50 Hz1) B 3TK14 42-0AP0 1 1 unit 41B
230 ... 240, 50 Hz D 3TK14 42-0AU0 1 1 unit 41B
110/120, 50/60 Hz D 3TK14 42-0AF0 1 1 unit 41B
800 300 525 905 575 2 2 220 ... 230, 50 Hz1) B 3TK15 42-0AP0 1 1 unit 41B
230 ... 240, 50 Hz D 3TK15 42-0AU0 1 1 unit 41B
110/120, 50/60 Hz D 3TK15 42-0AF0 1 1 unit 41B
1000 375 655 1135 -- 2 2 220 ... 230, 50 Hz1) B 3TK17 42-0AP0 1 1 unit 41B
230 ... 240, 50 Hz D 3TK17 42-0AU0 1 1 unit 41B
110/120, 50/60 Hz D 3TK17 42-0AF0 1 1 unit 41B
1)
At 60 Hz: 240 V.
■ Accessories
For contactors Version Rated control supply DT Order No. Price PU PS* PG
voltage Us per PU (UNIT,
Type V AC SET, M)
Surge suppressors
3TK10 ... 3TK13 RC elements 24 ... 48 D 3TK19 30-0A 1 1 unit 41B
110 ... 415 B 3TK19 30-0B 1 1 unit 41B
3TK14 ... 3TK17 48 ... 110 C 3TK19 34-0C 1 1 unit 41B
220 ... 600 B 3TK19 34-0D 1 1 unit 41B
Terminal covers
3TK10, 3TK11 For mounting onto contactors B 3TK19 40-0A 1 2 units 41B
3TK12, 3TK13 B 3TK19 42-0A 1 2 units 41B
3TK14, 3TK15 B 3TK19 44-0A 1 2 units 41B
4
3TK17 B 3TK19 46-0A 1 2 units 41B
Mechanical interlocking of two identical contactors
3TK10, 3TK11 Locking devices, auxiliary contacts 2 NC B 3TK19 20-0A 1 1 unit 41B
3TK12, 3TK13 B 3TK19 22-0A 1 1 unit 41B
3TK14 ... 3TK17 Mechanical interlock B 3TK19 24-0A 1 1 unit 41B
including mounting plate
Spare parts
For contactors Version Auxiliary contacts DT Order No. Price PU PS* PG
Connections per PU (UNIT,
Type SET, M)
14 22 32 44
2. block 1 NO + 1 NC 53 61 71 83 B 3TK19 10-3B 1 1 unit 41B
54 62 72 84
Contacts with fixing parts
3TK10 4 moving and 8 fixed contacts D 3TK19 60-0A 1 1 unit 41B
3TK11 D 3TK19 61-0A 1 1 unit 41B
3TK12 D 3TK19 62-0A 1 1 unit 41B
3TK13 D 3TK19 63-0A 1 1 unit 41B
3TK14 D 3TK19 64-0A 1 1 unit 41B
3TK15 D 3TK19 65-0A 1 1 unit 41B
3TK17 D 3TK19 67-0A 1 1 unit 41B
Arc chutes
3TK10 1 arc chute, 4-pole D 3TK19 50-0A 1 1 unit 41B
3TK11 D 3TK19 51-0A 1 1 unit 41B
3TK12 D 3TK19 52-0A 1 1 unit 41B
3TK13 D 3TK19 53-0A 1 1 unit 41B
3TK14 D 3TK19 54-0A 1 1 unit 41B
3TK15 D 3TK19 55-0A 1 1 unit 41B
3TK17 D 3TK19 57-0A 1 1 unit 41B
Solenoid coils
AC operation1)
3TK10, 3TK11 3TK19 70-0A..
3TK12, 3TK13 3TK19 72-0A..
3TK14 ... 3TK17 3TK19 74-0A..
1)
Rated control supply voltages: The 10th and 11th digit of the Order No.
must be supplemented according to the table.
AC operation
50 Hz 60 Hz
24 V -- B0 --
110 V 120 V F0 F0
220 ... 230 V 240 V P0 P0
230 ... 240 V -- U0 U0
■ Overview ■ Application
Standards Contactors with plug-in terminals
IEC 60947-1, EN 60947-1, The main area of application for the 3TK2 contactors with flat
IEC 60947-4-1, EN 60947-4-1 connectors is in household equipment. These contactors are
also suitable for simple electric controllers.
The contactors are suitable for use in any climate. The contac-
tors with screw terminals are finger-safe according to EN 50274. No auxiliary switch blocks can be retrofitted.
Connection methods
The contactors are available in versions with screw terminals,
6.3 mm plug-in terminals and solder pin connections for solder-
ing in printed circuit boards.
The contactors 3TK2 with 6.3 mm x 0.8 mm flat connectors are
4
coded and can be used in the plug-in base with solder pin con-
nections for printed circuit boards (see "Accessories").
■ Technical specifications
3TK20
Endurance of the main contacts
The characteristic curves show the con-
tact endurance of the contactors when
switching inductive AC loads (AC-3) de- Contactor type 3TK20
pending on the breaking current and rated
operational voltage. It is assumed that the 107
107 8 6 8 NSB0_01629
operating mechanisms are switched ran- 8 6
4 6
domly, i.e. not synchronized with the 6 4 4
Operating cycles at 500 V
Type 3TK20
Size 00
H
Dimensions (W x H x D) mm 45 x 48 x 63
D
W
4
• Flat connectors 6.3 mm x 0.8 mm V 500
• Solder pin connections V 500
Rated impulse withstand voltage Uimp
(pollution degree 3)
• Screw terminals kV 6
• Flat connectors 6.3 mm x 0.8 mm kV 6
• Solder pin connections kV 6
Protective separation between coil and main contacts V Up to 300
according to IEC 60947-1, Appendix N
Permissible ambient temperature1)
• During operation °C -25 ... +55
• During storage °C -55 ... +80
Degree of protection acc. to IEC 60947-1, Appendix C IP00 open
IP20 for screw terminals
IP40 coil assembly
Touch protection acc. to EN 50274 Finger-safe for screw terminals
Shock resistance
• Rectangular pulse
- AC operation g/ms 8.3/5 and 5.2/10
- DC operation g/ms 11.3/5 and 9.2/10
• Sine pulse
- AC operation g/ms 13/5 and 8/10
- DC operation g/ms 17.4/5 and 12.9/10
2)
Conductor cross-sections
Short-circuit protection for contactors without overload relays
Main circuit3)
• Fuse links, operational class gG:
LV HRC, type 3NA; DIAZED, type 5SB; NEOZED, type 5SE
according to IEC 60947-4-1/EN 60947-4-1
- Type of coordination "1" A 25
- Type of coordination "2"4) A 10
- Weld-free A 10
• Miniature circuit breaker with C characteristic A 10
Auxiliary circuit
• Short-circuit test with fuse links of gG operational class: A 6
DIAZED, type 5SB; NEOZED, type 5SE
with short-circuit current Ik = 1 kA acc. to IEC 60947-5-1
1) Applies to 50/60 Hz coil:
At 50 Hz, 1.1 x Us, side-by-side mounting and 100 % ON period the max.
ambient temperature is +40 °C.
2)
See page 4/26.
3)
According to excerpt from IEC 60947-4-1
Type of coordination "1":
Destruction of the contactor and the overload relay is permissible. The
contactor and/or overload relay can be replaced if necessary.
Type of coordination "2":
The overload relay must not suffer any damage. Contact welding on the
contactor is permissible, however, if the contacts can be easily separated.
4) A short-circuit current of I ≤ 6 kA applies to type of coordination "2".
q
- Closed VA 6.1
- P.f. 0.46
• AC operation, 50/60 Hz1)
- Closing VA 16.5/13.2
- P.f. 0.43/0.38
- Closed VA 8.0/5.4
- P.f. 0.48/0.42
For USA and Canada:
• AC operation, 50 Hz
- Closing VA 14.6
- P.f. 0.38
- Closed VA 6.5
- P.f. 0.40
• AC operation, 60 Hz
- Closing VA 14.4
- P.f. 0.30
- Closed VA 6.0
- P.f. 0.44
• DC operation (closing = closed) W 3
Permissible residual current of the electronic circuit2) (with 0 signal)
• AC operation mA ≤ 3 x (230 V/Us)
• DC operation mA ≤ 1 x (230 V/Us)
Operating times for 0.8 ... 1.1 x Us3)
Total break time = Opening delay + Arcing time
Values apply with coil in cold state and at operating temperature
for operating range
• AC operation
- Closing delay ms 5 ... 19
- Opening delay ms 2 ... 22
- Dead interval To use the 3TK20 AC-operated contactor in reversing an additional dead
interval of 50 ms is required along with an NC contact interlock.
• DC operation
- Closing delay ms 16 ... 65
- Opening delay ms 2 ... 5
• Arcing time ms 10 ... 15
Operating times for 1.0 x Us3)
• AC operation
- Closing delay ms 5 ... 18
- Opening delay ms 3 ... 21
- Dead interval To use the 3TK20 AC-operated contactor in reversing an additional dead
interval of 50 ms is required along with an NC contact interlock.
• DC operation
- Closing delay ms 19 ... 31
- Opening delay ms 3 ... 4
• Arcing time ms 10 ... 15
1)
Applies to 50/60 Hz coil:
At 50 Hz, 1.1 x Us, side-by-side mounting and 100 % ON period the max.
ambient temperature is +40 °C.
2)
The 3TX4 490-1J additional load module is recommended
for higher residual currents (see "Accessories for 3TF2 Contactors",
Chapter 3).
3) The OFF-delay of the NO contact and the ON-delay of the NC contact are
increased if the contactor coils are attenuated against voltage peaks
(noise suppression diode 6 to 10 times; diode assembly 2 to 6 times,
varistor +2 to 5 ms).
4
690/660 V kW 17 --
• Minimum conductor cross-section for loads with Ie mm2 2.5 2.5
Utilization categories AC-2 and AC-3
• Rated operational current Ie Up to 220 V A 9.0 9.0
230 V A 9.0 9.0
380 V A 9.0 9.0
400 V A 8.4 8.4
500 V A 6.5 6.5
660 V A 5.2 --
690 V A 5.2 --
• Rated power for motors At 110 V kW 1.2 1.2
with slipring or squirrel cage 115 V kW 1.2 1.2
at 50 and 60 Hz 120 V kW 1.3 1.3
127 V kW 1.4 1.4
200 V kW 2.2 2.2
220 V kW 2.4 2.4
230 V kW 2.5 2.5
240 V kW 2.6 2.6
380 V kW 4.0 4.0
400 V kW 4.0 4.0
415 V kW 4.0 4.0
440 V kW 4.0 4.0
460 V kW 4.0 4.0
500 V kW 4.0 4.0
575 V kW 4.0 --
660 V kW 4.0 --
690 V kW 4.0 --
Utilization category AC-4
(contact endurance approx. 200 000 operating cycles at Ia = 6 x Ie)
• Rated operational current Ie Up to 400 V A 2.6 2.6
690 V A 1.8 --
• Rated power for motors with squirrel cage At 110 V kW 0.32 0.32
at 50 and 60 Hz 115 V kW 0.33 0.33
120 V kW 0.35 0.35
• Max. permissible rated operational current 127 V kW 0.37 0.37
Ie/AC-4 r Ie/AC-3 up to 500 V, for reduced contact 200 V kW 0.58 0.58
endurance and reduced switching frequency 220 V kW 0.64 0.64
230 V kW 0.67 0.67
240 V kW 0.70 0.70
380 V kW 1.10 1.10
400 V kW 1.15 1.15
415 V kW 1.20 1.20
440 V kW 1.27 1.27
460 V kW 1.33 1.33
500 V kW 1.45 1.45
575 V kW 1.30 --
660 V kW 1.10 --
690 V kW 1.15 --
Switching frequency
Switching frequency z in operating cycles/hour
• Contactors without overload relays No-load switching h-1 10000
frequency
Dependence of the switching frequency z' AC-1 h-1 1000
on the operational current I' and operational voltage U': AC-2 h-1 500
z' = z ⋅(Ie/I ') ⋅(400 V/U ')1.5 ⋅1/h AC-3 h-1 1000
• Contactors with overload relays (mean value) h-1 15
Flat connectors
2
• When using a plug-in sleeve 6.3 – 1 mm 0.5 ... 1
• Finely stranded with 6.3 – 2.5 mm2 1 ... 2.5
Solder pin connections
(only for printed circuit boards)
• Solder pin cross-section (does not apply mm2 0.8 x 1.2
to plug-in bases)
4
- 3-phase At 115 V hp -- --
200 V hp 3 3 (1 for 3TK20. .-6)
230 V hp 3 3 (1 for 3TK20. .-6)
460/575 V hp 5 --
Overload relays Type 3UA7
• Setting range A 8 ... 10
s, u and U rated data of the auxiliary contacts
Rated voltage, max. V AC 600
Auxiliary switch blocks, max. V AC 300
Switching capacity A 600, Q 300
Uninterrupted current at 240 V AC A 10
AC operation
Solenoid coils for AC 50 and 60 Hz
50 Hz 60 Hz
24 V AC 29 V AC B0
110 V AC 132 V AC F0
230/220 V AC 276 V AC P01)
DC operation
24 V DC B4
1) Operating range at 220 V:
0.85 to 1.15 x Us; lower operating range limit according to IEC 60947.
Please inquire about further voltages.
■ Overview ■ Application
Standards The contactors are suitable for:
IEC 60947-1, EN 60947-1, • For changing the polarity of hoisting gear motors
IEC 60947-4-1, EN 60947-4-1 • For switching of two separate loads
The contactors are suitable for use in any climate. They are fin- Note:
ger-safe according to EN 50274.
Single device for pole reversal; not suitable for reversing duty.
The accessories for the 3-pole SIRIUS 3RT20 contactors can 3RT25 contactors are not suitable for switching a load between
also be used for the 4-pole versions. 2 current sources.
Size S0 contactors have 2 auxiliary contacts 1 NO and 1 NC in- General descriptions of the sizes S00 and S0 see Chapter 3,
tegrated in the basic unit. "Power contactors for switching motors" ➞ "SIRIUS 3RT20
contactors, 3-pole, 3 to 18.5 kW".
Mountable auxiliary contacts
4
Size S00 and S0
4 additional auxiliary contacts, including no more than 2 NC.
■ Technical specifications
Type 3RT25 16 3RT25 17 3RT25 18 3RT25 26
Size S00 S00 S00 S0
Dimensions (W x H x D)1)
H
mm 45 x 57.5 x 73 / 60 x 85 x 97 /
45 x 70 x 73 60 x 101.5 x 97
D
W
• With mounted auxiliary switch block mm 45 x 57.5 x 116 / 60 x 85 x 141 /
45 x 70 x 121 60 x 101.5 x 144
General technical specifications
Permissible mounting positions
The contactors are designed for operation on a vertical
NSB0_00478c
360° 22,5° 22,5°
mounting surface.
NSB0_00477a
(at 60 °C)
• Rated power for At 230 V kW 3 3 4 5.5
slipring or squirrel-cage motors NO contacts at 400 V kW 4 5.5 7.5 11
at 50 and 60 Hz NC contacts at 400 V kW 4 4 4 11
Load rating with DC
Utilization category DC-1, switching resistive loads (L/R ≤ 1 ms)
• Rated operational currents Ie (at 60 °C)
- 1 conducting path Up to 24 V A 16 20 35
60 V A 16 20 20
110 V A 2.1 2.1 4.5
220 V A 0.8 0.8 1
440 V A 0.6 0.6 0.4
- 2 conducting paths in series Up to 24 V A 16 20 35
60 V A 16 20 35
110 V A 12 12 35
220 V A 1.6 1.6 5
440 V A 0.8 0.8 1
Utilization category DC-3/DC-52),
shunt-wound and series-wound motors (L/R ≤ 15 ms)
• Rated operational currents Ie (at 60 °C)
- 1 conducting path Up to 24 V A 16 20 20
60 V A 0.5 0.5 5
110 V A 0.15 0.15 2.5
220 V A 0.75 0.75 1
440 V A -- -- 0.09
- 2 conducting paths in series Up to 24 V A 16 20 35
60 V A 5 5 35
110 V A 0.35 0.35 15
220 V A -- -- 3
440 V A -- -- 0.27
1)
For AC operation: 25 A; for DC operation: 20 A.
2)
For Us >24 V the rated operational currents Ie for the NC contact conduct-
ing paths are 50 % of the values for the NO contact conducting paths.
4
3RT25 1.-1A . 00 3RT25 1.-2A.00 3RT25 2.-1A. 00 3RT25 2.-2A .00
Rated data Auxiliary contacts Rated control DT Screw terminals DT Spring-type
AC-2/AC-3, AC-1, Ident. No. Version supply voltage terminals
Tu: up to 60 °C Tu: 40/60 °C Us
Opera- Ratings of Opera- Order No. Price Order No. Price
tional induction motors tional per PU per PU
current Ie at 50 Hz and current Ie
At 400 V 400 V
A kW A NO NC V AC
For screw fixing and snap-on mounting onto TH 35 standard mounting rail
Size S002)
1 R1 R3 3
A1(+)
A2(–)
2 R2 R4 4
A2(–)
2 R2 R4 4 14 22
A2(–)
2 R2 R4 4
A2(–)
2 R2 R4 4 14 22
■ Overview
Standards The accessories for the 3-pole SIRIUS 3RT10 contactors can
also be used for the 4-pole versions.
IEC 60947-1, EN 60947-1,
IEC 60947-4-1, EN 60947-4-1 Mountable auxiliary contacts
The contactors are suitable for use in any climate. They are fin- Maximum 4 auxiliary contacts can be either laterally mounted or
ger-safe according to EN 50274. snapped onto the top (auxiliary switch blocks acc. to EN 50012
Note: or EN 50005).
Single device for pole reversal; not suitable for reversing duty.
3RT15 contactors are not suitable for switching a load between
2 current sources.
4
■ Technical specifications
Type 3RT15 35
Size S2
H
3RT15 35-1. . . .
Rated data Rated control supply DT Screw terminals DT Spring-type
AC-2/AC-3, AC-1, voltage Us terminals
Tu: Up to 60 °C Tu: 40/60 °C
Operational Ratings of Operational Order No. Price Order No. Price
current Ie induction motors current Ie per PU per PU
at 50 Hz and
At 400 V 400 V
A kW A V
For screw fixing and snap-on mounting onto TH 35 standard mounting rail
AC operation
Size S2
A1(+) 1 R1 R3 3
A2(−) 2 R2 R4 4
40 18.5 55 / 50 24, 50 Hz B 3RT15 35-1AB00 --
110, 50 Hz B 3RT15 35-1AF00 --
230, 50 Hz } 3RT15 35-1AP00 --
DC operation · DC solenoid system
Size S2
A1(+) 1 R1 R3 3
A2(−) 2 R2 R4 4
40 18.5 55 / 50 24 DC } 3RT15 35-1BB40 --
220 DC B 3RT15 35-1BM40 --
1)
Single device for pole reversal; not suitable for reversing duty.
Other voltages according to page 4/38 on request.
Accessories and spare parts see "3RT10 Contactors",
Chapter 3.
■ Overview
Standards Only discharged capacitors are permitted to be switched on
with capacitor contactors.
IEC 60947-1, EN 60947-1,
IEC 60947-4-1, EN 60947-4-1, For the capacitor switching capacity of the basic 3RT10 contac-
IEC 60947-5-1, EN 60947-5-1 (auxiliary switches) tor version.
The contactors are suitable for use in any climate. They are fin- Auxiliary switches
ger-safe according to EN 50274.
The auxiliary switch block which is snapped onto the capacitor
Function contactor contains the three leading NO contacts and in the
The 3RT16 capacitor contactors are special versions of the case of S00 one standard NC contact and in the case of S0 and
3RT10 contactors size S00 to S3. The capacitors are precharged S3 one standard NO contact, which is unassigned. Size S00 also
by means of the mounted leading NO contacts and resistors; contains another unassigned NO contact in the basic unit.
4
only then do the main contacts close. In addition, a 2-pole auxiliary switch block can be mounted lat-
This prevents disturbances in the network and welding of the erally on the 3RT16 47 capacitor contactors (2 NO, 2 NC or
contactors. 1 NO + 1 NC versions); type 3RH19 21-1EA. .. The fitting of aux-
iliary switches for 3RT16 17 and 3RT16 27 is not expandable.
■ Technical specifications
All technical specifications not mentioned in the table below are those of the 3RT10 26 contactors for size S0 and to those of the
identical to those of the 3RT10 17 contactors for size S00, to 3RT10 45 contactors for size S3 (see Chapter 3).
Type 3RT16 17-.A. .3 3RT16 27-.A. .1 3RT16 47-.A. .1
Size S00 S0 S3
H
Rear clamping point • Finely stranded with end sleeve mm² -- 2.5 ... 50
connected • Finely stranded without end sleeve mm² -- 10 ... 50
• Solid mm² -- 2.5 ... 16
NSB0_00480
Both clamping points • Finely stranded with end sleeve mm² -- max. 2 x 35
connected • Finely stranded without end sleeve mm² -- max. 2 x 35
• Solid mm² -- max. 2 x 16
• Stranded mm² -- max. 2 x 50
NSB0_00481
L1 L2 L3 L1 L2 L3
F0 F0
13 51 43
1/L1
5/L3
3/L2
1/L1
5/L3
3/L2
A1 A1
2/T1
4/T2
6/T3
2/T1
4/T2
6/T3
A2 A2
14 52 44
4
NSB0_00558b
NSB0_01382c
C1 C1
■ Options
Rated control supply voltages, possible on request (the 10th and 11th position of the order number must be changed)
Rated control supply Contactor type 3RT23 1, 3RT23 2, 3RT13 3, 3RT14 4 3RT16 17,
voltage Us 3RT25 1 3RT25 2 3RT13 4, 3RT16 27,
3RT15 3 3RT16 47
Size S00 S0 S2, S3 S3 S00, S0, S3
Sizes S00 to S3
AC operation
Solenoid coils for 50 Hz (exception: Size S00: 50 and 60 Hz1))
24 V AC B0 B0 B0 B0 B0
42 V AC D0 D0 -- D0 --
48 V AC H0 H0 -- H0 --
4
110 V AC F0 F0 F0 F0 F0
230 V AC P0 P0 P0 P0 P0
240 V AC U0 U0 U0
400 V AC V0 V0 V0 V0 V0
Solenoid coils for 50 and 60 Hz1)
24 V AC B0 C2 C2 C2 C2
42 V AC D0 D2 D2 D2 --
48 V AC H0 H2 H2 H2 --
110 V AC F0 G2 G2 G2 G2
220 V AC N2 N2 N2 N2 N2
230 V AC P0 L2 L2 L2 L2
240 V AC P2 P2 P2 P2 P2
Solenoid coils (for USA and Canada2))
50 Hz 60 Hz
110 V AC 120 V AC K6 K6 K6 K6 K6
220 V AC 240 V AC P6 P6 P6 P6 P6
Solenoid coils (for Japan)
50/60 Hz3) 60 Hz4)
100 V AC 110 V AC G6 G6 G6 G6 G6
200 V AC 220 V AC N6 N6 N6 N6 N6
400 V AC 440 V AC R6 R6 R6 R6 R6
DC operation
12 V DC A4 -- -- -- --
24 V AC B4 B4 B4 B4 --
42 V AC D4 D4 D4 D4 --
48 V AC W4 -- W4 W4 --
60 V DC -- -- -- E4 --
110 V DC F4 F4 F4 F4 --
125 V DC G4 G4 G4 G4 --
220 V DC M4 M4 M4 M4 --
230 V DC P4 -- P4 P4 --
Examples
AC operation 3RT23 25-1AP00 Contactor with screw terminals; with solenoid coil for 50 Hz for rated control supply voltage 230 V AC.
3RT23 25-1AG20 Contactor with screw terminals; with solenoid coil for 50/60 Hz for rated control supply voltage 110 V AC.
DC operation 3RT25 26-2BB40 Contactor with spring-type terminals; for rated control supply voltage 24 V DC.
3RT25 26-2BG40 Contactor with spring-type terminals; for rated control supply voltage 125 V DC.
Rated control supply Contactor type 3RT14 56-6A..., Rated control supply Contactor type 3RT14 56-6N..., 3RT14 56-6P/Q ...,
voltage 3RT14 66-6A..., voltage 3RT14 66-6N..., 3RT14 66-6P/Q ...,
3RT14 76-6A... 3RT14 76-6N... 3RT14 76-6P/Q ...
Us min ... Us max5) Size S6, S10, S12 Us min ... Us max5) Size S6, S10, S12 S6, S10, S12
Size S6 to S12
UC operation (AC 50 to 60 Hz, DC)
23 ... 26 V AC/DC B3 21 ... 27.3 V AC/DC B3 --
42 ... 48 V AC/DC D3 96 ... 127 V AC/DC F3 F3
110 ... 127 V AC/DC F3 200 ... 277 V AC/DC P3 P3
200 ... 220 V AC/DC M3
220 ... 240 V AC/DC P3
240 ... 277 V AC/DC U3
380 ... 420 V AC/DC V3
440 ... 480 V AC/DC R3
500 ... 550 V AC/DC S3
575 ... 600 V AC/DC T3
1) Coil operating range 3) Coil operating range
at 50 Hz: 0.8 ... 1.1 x Us Size S00: at 50/60 Hz: 0.85 ... 1.1 x Us
at 60 Hz: 0.85 ... 1.1 x Us Size S0 to S3: at 50 Hz: 0.8 ... 1.1 x Us
2)
Coil operating range at 60 Hz: 0.85 ... 1.1 x Us
4)
Size S00: at 50 Hz: 0.85.... 1.1 x Us Coil operating range
at 60 Hz: 0.8 ... 1.1 x Us at 60 Hz: 0.8 ... 1.1 x Us
Size S0 to S3: at 50 Hz and 60 Hz: 0.8 ... 1.1 x Us 5)
Coil operating range: 0.7 x Us min ... 1.3 x Us max
■ Overview L+
L-
Standards
S1
IEC 60947-4-1, EN 60947-4-1,
for requirements acc. to IEC 60077-1 and IEC 60077-2
The contactors are finger-safe according to EN 50274. These E1
size S00 and S0 contactors have spring-type connections for all Rv +
Q1
terminals.
Ambient temperature
Q1 1/L1 3/L2 5/L3
The permissible ambient temperature for operation of the con-
NSB0_02178
tactors (across the full coil operating range) is -40 to +70 °C. A2- 2/T1 4/T2 6/T3
Uninterrupted duty at temperatures > +60 °C reduces the me-
4
chanical endurance, the current carrying capacity of the con-
ducting paths and the switching frequency. Circuit diagram (version with suppressor diode)
Control and auxiliary circuits The size S00 contactors are supplied prewired with a plug-on
module containing the series resistor. The suppressor diode is
The solenoid coils of the contactors have an extended coil oper- integrated. A 4-pole auxiliary switch block (according to
ating range from 0.7 to 1.25 x Us and are fitted as standard with EN 50005) can be fitted additionally.
surge suppressors. The opening delay is consequently 2 to 5 ms
longer than for standard contactors. A circuit diagram showing the terminals is stuck onto each con-
tactor. One NC of the auxiliary contacts is required for the series
resistor function. The selection and ordering data shows the
■ Application number of additional, unassigned auxiliary contacts. With size
For operation in installations which are subject both to consider- S00 it is possible to extend the number of auxiliary contacts.
able variations in the control voltage and to high ambient tem- Side-by-side mounting
peratures, e.g. railway applications under extreme climatic con-
ditions, rolling mills, etc. At ambient temperatures up to 70 °C, the size S00 contactors
are allowed to be mounted side by side.
Also for control supply voltages with battery buffering to extend
the operating time in the event of battery charge failure. 3RT20 2. contactors with solid-state operating mechanism,
extended operating range
Contactors with conventional coil
Control and auxiliary circuits
Control and auxiliary circuits
The solenoid coils of the contactors have an extended coil oper-
These contactors have an extended operating range from 0.7 to ating range from 0.7 to 1.25 x Us and are fitted as standard with
1.25 x Us; on size S00 the coils are fitted with suppressor diodes, varistors to provide protection against overvoltage.
on size S0 with varistors. An additional series resistor is not re-
quired. The contactors are energized via upstream control electronics
which ensure the coil operating range of 0.7 to 1.25 x Us at an
Note: ambient temperature of 70 °C. They are supplied as complete
An additional auxiliary switch block cannot be mounted. units with integrated coil electronics. A varistor is integrated for
damping opening surges in the coil.
Side-by-side mounting
The possibility of mounting auxiliary switches is the same as that
A clearance of 10 mm is required for side-by-side mounting at for equivalent standard contactors for switching motors in the
ambient temperatures > 60 °C ≤ 70 °C. matching size (see exploded drawings of the 3RT2 contactors in
Chapter 3).
3RT20 1. contactors with coil with series resistor
Side-by-side mounting
Control and auxiliary circuits
At ambient temperatures up to 70 °C, size S0 of these contactor
The solenoid coils of the contactors have an extended coil oper-
versions are allowed to be mounted side by side.
ating range from 0.7 to 1.25 x Us and are fitted as standard with
a surge suppressor (suppressor diode or varistor as preferred).
A surge suppressor (a suppressor diode or varistor as preferred)
is integrated.
The DC solenoid systems of the contactors are modified
(to holding excitation) by means of a series resistor.
■ Technical specifications
Contactors Type 3RT20 17 3RT20 2. 3RT20 2.-2XB40- 3RT20 2.-2XF40-
0LA2 0LA2
General technical specifications
Upright mounting position
• Contactors with coil with series resistor Special version (on request)
• Contactors with conventional coil Special version (on request)
Ambient temperature
• During operation °C -40 ... +70
• During storage °C -55 ... +80
Control circuits
Coil operating range DC 0.7 ... 1.25 x Us 0.7 ... 1.3 x Us
4
Power consumption of the solenoid coils For cold coil and 1.0 x Us
• Contactors with series resistor - Closing W 13 -- -- --
- Closed W 4 -- -- --
• Contactors with conventional operating - Closing W 2.8 4.5 -- --
mechanism
- Closed W 2.8 4.5 -- --
• Contactors with solid-state operating - Closing W -- -- 6.7 13.2
mechanism
- Closed W -- -- 0.8 1.56
4
3RT20 1.-2K.4. 3RT20 1.-2K.42-0LA0
Rated data Auxiliary contacts Rated control DT Spring-type terminals PU PS* PG
AC-2 and AC-3 supply voltage (UNIT,
Tu: 70 °C Us Configurator SET, M)
Operational Ratings of Ident. No. Version
current Ie induction motors Order No. Price
at at per PU
400 V 230 V 400 V 500 V 690 V
A kW kW kW kW NO NC V DC
3RT20 contactors for switching motors
Size S00
With conventional coil, fitted with suppressor diode
• 1 NO, Ident. No. 10 • 1 NC, Ident. No. 01
A1(+) 1/L1 3/L2 5/L3 13 A1(+) 1/L1 3/L2 5/L3 21
A2(–) A2(–)
2/T1 4/T2 6/T3 14 2/T1 4/T2 6/T3 22
12 3 5.5 5.5 5.5 101) 1 -- 24 } 3RT20 17-2KB41 1 1 unit 41B
110 B 3RT20 17-2KF41 1 1 unit 41B
12 3 5.5 5.5 5.5 011) -- 1 24 } 3RT20 17-2KB42 1 1 unit 41B
110 B 3RT20 17-2KF42 1 1 unit 41B
With conventional coil, fitted with varistor
• 1 NO, Ident. No. 10 • 1 NC, Ident. No. 01
A1(+) 1/L1 3/L2 5/L3 13 A1(+) 1/L1 3/L2 5/L3 21
A2(–) A2(–)
2/T1 4/T2 6/T3 14 2/T1 4/T2 6/T3 22
1)
12 3 5.5 5.5 5.5 10 1 -- 24 B 3RT20 17-2LB41 1 1 unit 41B
110 B 3RT20 17-2LF41 1 1 unit 41B
12 3 5.5 5.5 5.5 011) -- 1 24 B 3RT20 17-2LB42 1 1 unit 41B
110 B 3RT20 17-2LF42 1 1 unit 41B
With coil with series resistor, fitted with suppressor diode
E1(+) 1/L1 3/L2 5/L3
A2(–)
2/T1 4/T2 6/T3
A2(–)
2/T1 4/T2 6/T3
12 3 5.5 5.5 5.5 --2) -- 13) 24 B 3RT20 17-2LB42-0LA0 1 1 unit 41B
110 B 3RT20 17-2LF42-0LA0 1 1 unit 41B
16 4 7.5 10 11 --2) -- 13) 24 B 3RT20 18-2LB42-0LA0 1 1 unit 41B
110 B 3RT20 18-2LF42-0LA0 1 1 unit 41B
For online configurator see www.siemens.com/sirius/configurators. Accessories see "3RT20 Contactors", Chapter 3.
1)
It is not possible to mount an auxiliary switch block. A clearance of 10 mm
is required for side-by-side mounting at ambient temperatures > 60 °C.
2)
One 4-pole auxiliary switch block according to EN 50005 can be mounted;
no distance required up to 70 °C.
3) NC contact cannot be used because it is used for switching of the series
resistor.
A2(–)
2/T1 4/T2 6/T3 14 22
A2(–)
2/T1 4/T2 6/T3 14 22
4
• Coils with solid-state control unit Control and auxiliary circuits
The solenoid coils of the contactors have an extended coil oper- The contactors are energized via upstream control electronics
ating range from 0.7 to 1.25 x Us and are fitted as standard with which ensure the coil operating range of 0.7 to 1.25 x Us at an
varistors to provide protection against overvoltage. The opening ambient temperature of 70 °C.
delay is consequently 2 to 5 ms longer than for standard contac-
tors. A varistor is integrated for damping opening surges in the coil.
The opening delay is consequently 2 to 5 ms longer than for
Ambient temperature standard contactors.
The permissible ambient temperature for operation of the con- The possibility of mounting auxiliary switches is the same as that
tactors (across the full coil operating range) is -40 °C to +70 °C. for equivalent standard contactors.
Uninterrupted duty at temperatures > +60 °C reduces the me- Mounting
chanical endurance, the current carrying capacity of the con-
At ambient temperatures up to 70 °C, sizes S2 and S3 of these
ducting paths and the switching frequency.
contactor versions are allowed to be mounted side by side.
■ Application Dimensions
Because of the built-on contactor control unit, the height of the
For operation in installations which are subject both to consider-
size S2 and S3 contactors increases by up to 34 mm.
able variations in the control voltage and to high ambient tem-
peratures, e.g. railway applications under extreme climatic con-
ditions, rolling mills, etc.
3RT10 contactors with series resistor
The DC solenoid systems of the contactors are modified
to holding excitation by means of a series resistor.
NSB0_00562c
(-)
A1
A2
Rv
A1
21 A2
22
(+) (-)
■ Technical specifications
Contactors Type 3RT10 3. 3RT10 4.
3RT10 contactors with series resistor
General technical specifications
Ambient temperature
• During operation °C -40 ... +70
Control circuits
Coil operating range AC/DC 0.7 ... 1.25 x Us
Power consumption of the solenoid coils For cold coil and 1.0 x Us
• Closing W 46 78
• Closed W 14 23
Upright mounting position -- --
4
3RT10 3.-3K.44-0LA0
Rated data Auxiliary Rated control supply DT Spring-type terminals PU PS* PG
AC-2 and AC-3 contacts voltage Us (UNIT,
Tu: 70 °C SET, M)
Operational Ratings of Version Order No. Price
current Ie induction motors at per PU
at
400 V 230 V 400 V 500 V 690 V
A kW kW kW kW NO NC V DC
For screw fixing and snap-on mounting onto TH 35 standard mounting rail
Size S2
With series resistor
1/L1 3/L2 5/L3 13 21 31 43
A1(+)
A2(–)
2/T1 4/T2 6/T3 14 22 32 44
A2(–)
2/T1 4/T2 6/T3 14 22 32 44
4
3RT10 . .-3X.40-0LA2
Rated data Auxiliary Rated control DT Screw terminals DT Spring-type terminals
AC-2 and AC-3 contacts1) supply volt- for coil terminals
Tu: up to 70 °C age Us
Rated opera- Ratings of Version Order No. Price Order No. Price
tional current Ie induction motors per PU per PU
up to at 50 Hz
400 V 400 V
A kW NO NC V DC
For screw fixing and snap-on mounting onto TH 35 standard
mounting rail
Size S2
A1(+) 1/L1 3/L2 5/L3
U
A2(-) 2/T1 4/T2 6/T3
L L+
Standards L L-
IEC 60947-4-1, EN 60947-4-1 S1 S1
21
For requirements according to IEC 60077-1 and IEC 60077-2 1 3
K2 K2 K1 22
31 2 4
The contactors are finger-safe according to EN 50274. Terminal Rv K1 Rv 5 7
covers may have to be fitted onto the connecting bars, depend- 32 K2 K2
6 8
ing on the configuration with other devices. K1 A1 K2 A1
K1 A1
All specifications and technical specifications not mentioned
here are identical to those of the standard 3TB contactors.
NSB0_00715
Ambient temperature
A2 NSB0_01357b A2 A2
4
■ Technical specifications
Contactors Type 3TB50 3TB52 3TB54 3TB56
Size 6 8 10 12
General technical specifications
Ambient temperature
• During operation °C -40 ... +70
Control circuits
Coil operating range 0.7 ... 1.25 x Us
Power consumption of the solenoid coils For cold coil and 1.0 x Us
• Closing W 38 40 190 295
• Closed W 20 21 43 59
4
Contactors for switching AC voltage
DC operation · DC solenoid system
Terminal designations acc. to EN 50012 or EN 50005
1/L1 3/L2 5/L3 13 21 31 43
A1
A2
2/T1 4/T2 6/T3 14 22 32 44
■ Accessories
Spare parts
For contactors Remarks Rated control supply DT Order No. Price PU PS* PG
voltage Us per PU (UNIT,
SET,
M)
Size Type V DC
Solenoid coils
For contactors with extended operating range
6 3TB50 With series resistor, 24 C 3TY6 503-0LB4 1 1 unit 41B
without varistor 110 D 3TY6 503-0LF4 1 1 unit 41B
8 3TB52 and 3TC52 24 D 3TY6 523-0LB4 1 1 unit 41B
110 D 3TY6 523-0LF4 1 1 unit 41B
10 3TB54 24 C 3TY6 543-0LB4 1 1 unit 41B
110 C 3TY6 543-0LF4 1 1 unit 41B
12 3TB56 and 3TC56 24 C 3TY6 563-0LB4 1 1 unit 41B
110 C 3TY6 563-0LF4 1 1 unit 41B
All spare parts not mentioned here are identical to those of the
basic versions of the 3TB5 contactors; see Chapter 3.
L L+
Standards L L-
IEC 60947-4-1, EN 60947-4-1 S1 S1
21
For requirements according to IEC 60077-1 and IEC 60077-2 1 3
K2 K2 K1 22
31 2 4
The contactors are finger-safe according to EN 50274 (excep- Rv K1 Rv 5 7
tion: series resistor). Terminal covers may have to be fitted onto 32 K2 K2
6 8
the connecting bars, depending on the configuration with other K1 A1 K2 A1
K1 A1
devices.
All specifications and technical specifications not mentioned
NSB0_00715
here are identical to those of the standard 3TC contactors.
A2 NSB0_01357b A2 A2
Ambient temperature
4
The permissible ambient temperature for operation of the con- Circuit diagrams with series resistor
tactors (across the full coil operating range) is -50 to +70 °C. Un-
interrupted duty at temperatures < -25 °C and > +55 °C reduces Reversing contactors
the mechanical endurance, the current-carrying capacity of the With the 3TC52 and 3TC56 contactors, the series resistor must
conducting paths and the switching frequency. be connected using an additional K2 reversing contactor
At ambient temperatures > 55 °C, a clearance of 10 mm is re- (3RT13 17-1F.40). This contactor is automatically included in the
quired for side-by-side mounting of size 2 contactors. There is scope of supply in the same packaging as the contactor.
no need to reduce the technical specifications.
Dimensions
Series resistor Attaching resistors and varistors increases the width of the con-
The DC solenoid systems of the 3TC contactors must be modi- tactors.
fied (to hold-in coil) by means of a series resistor. This series re-
sistor is supplied separately packed with the contactors. ■ Application
With types 3TC48, the series resistor must be attached onto the For operation in plants which are subject both to considerable
right-hand side of the auxiliary switch block by means of the en- variations in the control voltage and to high ambient tempera-
closed mounting parts and sets of links provided, while in the tures, e.g. in railway applications.
case of the 3TC44 it must be mounted and wired between the
contactor poles. With types 3TC52 and 3TC56, the series resis- Control and auxiliary circuits
tor must be attached separately next to the contactors.
The solenoid coils of the contactors have an extended coil oper-
One NC of the auxiliary contacts is required for the series resistor ating range from 0.7 to 1.25 x Us and are fitted as standard with
function. The selection and ordering data show the number of varistors to provide protection against overvoltage. The opening
additional, unassigned auxiliary contacts. It is not possible to ex- delay is consequently 2 to 5 ms longer than for standard contac-
tend the number of auxiliary contacts. tors.
■ Technical specifications
Contactors Type 3TC44 3TC48 3TC52 3TC56
Size 2 4 8 12
General technical specifications
Ambient temperature
• During operation °C -40 ... +70
Control circuits
Coil operating range 0.7 ... 1.25 x Us
Power consumption of the solenoid coils For cold coil and 1.0 x Us
• Closing W 48 26 40 295
• Closed W 13 14 21 59
4
3TC48
Size Utilization Rated Rated power Auxiliary Rated control DT Screw terminals PU PS* PG
categories operational of loads contacts1) supply voltage (UNIT,
current Ie at Us SET, M)
at Version Order No. Price
750 V 220 V 440 V 600 V 750 V per PU
A kW kW kW kW NO NC V DC
Contactors for switching DC voltage
DC operation · DC solenoid system
Terminal designations according to EN 50012 and EN 50005
1/L1 3/L2 13 21 31 43
A1
A2
2/T1 4/T2 14 22 32 44
2 DC-1 32 7 14 19.2 24 2 12) 24 B 3TC44 17-0LB4 1 1 unit 41B
DC-3/DC-5 7.5 5 9 9 4 110 C 3TC44 17-0LF4 1 1 unit 41B
4 DC-1 75 16.5 33 45 56 2 12) 24 C 3TC48 17-0LB4 1 1 unit 41B
DC-3/DC-5 75 13 27 38 45 110 C 3TC48 17-0LF4 1 1 unit 41B
8 DC-1 170 48 97 132 165 2 12) 24 C 3TC52 17-0LB4 1 1 unit 41B
DC-3/DC-5 170 41 82 110 110 110 C 3TC52 17-0LF4 1 1 unit 41B
12 DC-1 400 88 176 240 300 2 12) 24 C 3TC56 17-0LB4 1 1 unit 41B
DC-3/DC-5 400 70 140 200 250 110 D 3TC56 17-0LF4 1 1 unit 41B
1) The number of auxiliary contacts cannot be increased.
2)
One NC contact used for series resistor.
■ Accessories
Spare parts
For contactors Remarks Rated control DT Order No. Price PU PS* PG
supply voltage per PU (UNIT,
Us SET, M)
Size Type V DC
Arc chutes
For contactors with extended operating range
2 3TC44 17-0L. . With cutout for resistor B 3TY2 442-0B 1 1 unit 41B
mounting
Solenoid coils
For contactors with extended operating range
2 3TC44 With series resistor, 24 C 3TY6 443-0LB4 1 1 unit 41B
without varistor 110 C 3TY6 443-0LF4 1 1 unit 41B
4 3TC48 24 C 3TY6 483-0LB4 1 1 unit 41B
110 C 3TY6 483-0LF4 1 1 unit 41B
All spare parts not mentioned here are identical to those of the
basic versions of the 3TC contactors; see Chapter 3.
■ Overview ■ Application
3TC4 and 3TC5 The contactors are suitable for switching and controlling DC mo-
tors as well as all other DC circuits.
IEC 60947-1, EN 60947-1,
IEC 60947-4-1, EN 60947-4-1 A version with an especially large coil operating range is avail-
able for operation in electrically driven vehicles and in switch-
The contactors are finger-safe according to EN 50274. Terminal gears with significant fluctuations in the actuating voltage (see
covers may have to be fitted onto the connecting bars, depend- page 4/49).
ing on the configuration with other devices.
The DC motor ratings given in the tables are applicable to the
DC-3 and DC-5 utilization categories with two-pole switching
of the load or with the two conducting paths of the contactor con-
nected in series.
4
■ Technical specifications
Contactors Type 3TC4 and 3TC7 3TC5
Rated data of the auxiliary contacts
Rated insulation voltage Ui V 690
(pollution degree 3)
Conventional thermal current Ith = A 10 10
Rated operational current Ie/AC-12
AC load
Rated operational current Ie/AC-15/AC-14
• For rated operational voltage Ue
24 V A 10 10
110 V A 10 10
125 V A 10 10
220 V A 6 6
230 V A 5.6 5.6
380 V A 4 4
400 V A 3.6 3.6
500 V A 2.5 2.5
660 V A 2.5 2.5
690 V A -- --
DC load
Rated operational current Ie/DC-12
• For rated operational voltage Ue
24 V A 10 10
60 V A 10 10
110 V A 3.2 8
125 V A 2.5 6
220 V A 0.9 2
440 V A 0.33 0.6
600 V A 0.22 0.4
Rated operational current Ie/DC-13
• For rated operational voltage Ue
24 V A 10 10
60 V A 5 5
110 V A 1.14 2.4
125 V A 0.98 2.1
220 V A 0.48 1.1
440 V A 0.13 0.32
600 V A 0.07 0.21
10 7 20 NSB0_00656
8 NSB0_00655
6 Mill.
4
16
10 6
8
6 14
4
12
2
5
10 10
8
6
4 8
2
6
10 4
8
6 4
4
2
2
0,5
10 3
200 400 50 100 150 200 250 300 a (A) 400
10 20 40 100 600 1000 a (A)
H
Dimensions (W x H x D)
• DC operation mm 70 x 85 x 141 100 x 183 x 180 135 x 238 x 232 160 x 279 x 310
D
• AC operation W mm 70 x 85 x 100 100 x 183 x 154 135 x 238 x 200 160 x 279 x 251
Control circuits
Coil operating range 0.8 ... 1.1 x Us
Power consumption of the solenoid coils
(for cold coil and 1.0 x Us)
• DC operation - Closing = Closed W 10 19 30 86
• AC operation, 50 Hz coil - Closing VA/p.f. 68/0.86 300/0.5 640/0.48 1780/0.3
- Closed VA/p.f. 10/0.29 26/0.24 46/0.23 121/0.22
• AC operation, 60 Hz coil - Closing VA/p.f. 95/0.79 365/0.45 730/0.38 2140/0.3
4
H
Dimensions mm 78 x 352 x 276 160 x 366 x 290
D
W
NSB0_00650c
22,5° 22,5° 22,5° 22,5°
The contactors are designed for operation on a
vertical mounting surface.
4
Rated impulse withstand voltage Uimp kV 8
Protective separation between the coil and the main contacts V 630
acc. to IEC 60947-1, Appendix N
Permissible ambient temperature °C -25 ... +55
Degree of protection acc. to IEC 60947-1, Appendix C IP00/open
Short-circuit protection
Main circuit
Fuse links, operational class gG:
LV HRC, type 3NA
• Type of coordination "1" A 630
• Type of coordination "2" A 500
Auxiliary circuits
• Short-circuit test with fuse links of gG operational class: A 16
DIAZED, type 5SB; NEOZED, type 5SE
with short-circuit current Ik = 1 kA acc. to IEC 60947-5-1
• Test with miniature circuit breaker up to 230 V with C characteristic: A 10
Short-circuit current Ik = 400 A acc. to IEC 60947-5-1
Control circuits
Coil operating range
• DC operation At Uc = 24 V 0.8 ... 1.2 x Us
At Uc > 24 V 0.7 ... 1.2 x Us
• AC operation At Uc = 24 V 0.7 ... 1.15 x Us
At Uc > 24 V 0.7 ... 1.14 x Us
Power consumption of the solenoid coils (when coil is cold and 1.0 x Us)
• DC operation Closing = Closed W 46 92
• AC operation, 50 Hz Closing, VA 80 160
Closed 0.95 0.95
Operating times (The values apply up to and including 15 % undervoltage,
(Total break time = Opening delay + Arcing time) 10 % overvoltage, as well as when the coil is cold and warm)
• AC and DC operation - Closing delay ms 60 ... 100
- Opening delay ms 20 ... 35
• Arcing time at 0.06 ... 4 x Ie ms 40 ... 70
Main circuit
Load rating with DC
Utilization category DC-1, switching resistive loads (L/R ≤ 1 ms)
• Rated operational current Ie/DC-1 (at 55 °C) A 500 500
• Minimum conductor cross-section mm2 2 x 150 2 x 150
• Rated power At 220 V kW 110 110
440 V kW 220 220
600 V kW 300 300
750 V kW 375 375
1200 V kW -- 600
1500 V kW -- 750
• Critical currents, without arc extinction At 440 V A ≤7 --
600 V A ≤ 13 --
750 V A ≤ 15 --
≤ 800 V A -- ≤7
1200 V A -- ≤ 13
1500 V A -- ≤ 15
Utilization categories DC-3 and DC-5, switching DC motors 2)
3TC44 3TC48
Size Utilization Opera- Ratings of Auxiliary Rated control DT Screw terminals PU PS* PG
category1) tional cur- DC motors at contacts2) supply volt- (UNIT,
rent Ie3) 110 V 220 V 440 V 600 V 750 V Version age Us SET, M)
Order No. Price
per PU
A kW kW kW kW kW NO NC V
3TC44 to 3TC56 two-pole contactors
Terminal designations acc. to EN 50012
1/L1 3/L2 13 21 31 43
A1
A2
2/T1 4/T2 14 22 32 44
DC operation
Screw fixing and snap-on mounting onto TH 35 standard mounting rail
2 DC-3, DC-5 32 2.5 5 9 9 4 2 2 24 DC } 3TC44 17-0AB4 1 1 unit 41B
110 DC } 3TC44 17-0AF4 1 1 unit 41B
220 DC } 3TC44 17-0AM4 1 1 unit 41B
Screw fixing
4 DC-3, DC-5 75 6.5 13 27 38 45 2 2 24 DC A 3TC48 17-0AB4 1 1 unit 41B
110 DC A 3TC48 17-0AF4 1 1 unit 41B
220 DC A 3TC48 17-0AM4 1 1 unit 41B
8 DC-3, DC-5 2204) 20 41 82 110 110 2 2 24 DC C 3TC52 17-0AB4 1 1 unit 41B
110 DC C 3TC52 17-0AF4 1 1 unit 41B
220 DC C 3TC52 17-0AM4 1 1 unit 41B
12 DC-3, DC-5 400 35 70 140 200 250 2 2 24 DC C 3TC56 17-0AB4 1 1 unit 41B
110 DC C 3TC56 17-0AF4 1 1 unit 41B
220 DC C 3TC56 17-0AM4 1 1 unit 41B
AC operation, 50 Hz
Screw fixing and snap-on mounting onto TH 35 standard mounting rail
2 DC-3, DC-5 32 2.5 5 9 9 4 2 2 220/230 AC5) } 3TC44 17-0BP0 1 1 unit 41B
110 / 110 AC } 3TC44 17-0BF0 1 1 unit 41B
Screw fixing
4 DC-3, DC-5 75 6.5 13 27 38 45 2 2 220/230 AC5) A 3TC48 17-0BP0 1 1 unit 41B
110 AC C 3TC48 17-0BF0 1 1 unit 41B
4) 5)
8 DC-3, DC-5 220 20 41 82 110 110 2 2 220/230 AC A 3TC52 17-0BP0 1 1 unit 41B
110 AC C 3TC52 17-0BF0 1 1 unit 41B
12 DC-3, DC-5 400 35 70 140 200 250 2 2 220/230 AC5) C 3TC56 17-0BP0 1 1 unit 41B
110 AC C 3TC56 17-0BF0 1 1 unit 41B
3)
Other rated control supply voltages according to page 4/56 on The following rated operational currents are permitted for reversing duty
request. with 3TC44 to 3TC56 contactors:
1) Permissible load for DC-1 utilization category see detailed technical speci- Contactor Rated operational voltage
fications in the reference manual "Contactors and Contactor Assemblies". Type 110 V, 220 V 440 V
2)
The fitting of auxiliary switches cannot be altered on DC-operated contac- 3TC44 32 A 7A
tors. 3TC48 75 A 75 A
3TC52 170 A 170 A
3TC56 400 A 400 A
4)
At > 600 V: Ie = 170 A.
5)
Operating range at 220 V: 0.85 to 1.15 x Us
3TC74 3TC78
Size Utilization Opera- Ratings of Auxiliary Rated control DT Screw PU PS* PG
category1) tional DC motors at contacts2) supply terminals (UNIT,
current Version voltage Us SET,
Ie 110 V 220 V 440 V 600 V 750 V 1200 V 1500 V M)
4
Order No. Price
per PU
A kW kW kW kW kW kW kW NO NC V
3TC74 1-pole contactors · Operational voltage up to 750 V
DC operation
Terminal designations acc. to EN 50005
A1 1/L1 13 21 31 43 53 61 71 83
2/T1 14 22 32 44 54 62 72 84
A2
12 DC-3, 400 35 70 140 200 250 -- -- 4 4 230/220 AC3) C 3TC74 14-1CM 1 1 unit 41B
DC-5
3TC78 2-pole contactors · Operational voltage up to 1500 V
DC operation
Terminal designations acc. to EN 50005
A1 1/L1 3/L2 13 21 31 43 53 61 71 83
2/T1 4/T4 14 22 32 44 54 62 72 84
A2
12 DC-3, 400 35 70 140 200 250 400 500 4 4 24 DC C 3TC78 14-0EB 1 1 unit 41B
DC-5 110 DC C 3TC78 14-0EF 1 1 unit 41B
AC operation, 50 Hz
Terminal designations acc. to EN 50005
Z
1/L1 3/L2 13 21 31 43 53 61 71 83
~A2
~A1
2/T1 4/T2 14 22 32 44 54 62 72 84
12 DC-3, 400 35 70 140 200 250 400 500 4 4 230/220 AC3) C 3TC78 14-1CM 1 1 unit 41B
DC-5
1) Permissible load for DC-1 utilization category see detailed technical speci- Other rated control supply voltages according to page 4/56 on
fications in the reference manual "Contactors and Contactor Assemblies". request.
2)
The fitting of auxiliary switches cannot be altered on DC-operated contac-
tors. Spare parts see page 4/58.
3)
Upper operating range limit at 230 V: 1.14 x Us.
■ Options
Rated control supply voltages (the 10th and 11th position of the order number must be changed)
Contactor type 3TC44 3TC48 3TC52/56 3TC74/78
Rated control supply voltage
Us
AC operation
Solenoid coils for 50 Hz
24 V AC B0 B0 -- --
110 V AC F0 F0 F0 --
230/220 V AC P01) P01) P01) M2)
240 V AC U0 U0 -- --
AC operation
4
■ Accessories
For contactors Version DT Screw terminals PU PS* PG
(UNIT,
SET,
M)
Size Type Order No. Price
per PU
Solid-state compatible auxiliary switch blocks with screw terminals
For operation in dusty atmospheres and in solid-state
circuits with rated operational currents
Ie AC-14 and DC-13 of 1 ... 300 mA at 3 ... 60 V
2 and 4 3TC44, For lateral mounting onto contactors. } 3TY7 561-1UA00 1 1 unit 41B
3TC48 With 1 changeover contact.
2nd auxiliary switch block, left or right
(replacement for 3TY6 561-1U, 3TY6 561-1V)
Mounting on the left Mounting on the right
5TY7 561-1. 51 61
52 54 62 64
Terminal covers
6 3TC48 For protection against inadvertent contact with M6 B 3TX6 506-3B 1 1 unit 41B
8 and 12 3TC52, exposed busbar connections M10 B 3TX6 546-3B 1 1 unit 41B
3TC56 Can be screwed on free screw end.
Covers one busbar connection
(1 set = 6 units).
3TX6 526-3B
For contactors Version Rated control supply DT Order No. Price PU PS* PG
voltage Us per PU (UNIT,
SET,
M)
Size Type V AC V DC
Surge suppressors · Varistors
2 3TC441) Varistors2) 24 ... 48 24 ... 70 A 3TX7 402-3G 1 1 unit 41B
with line spacer, for mount- 48 ... 127 70 ... 150 A 3TX7 402-3H 1 1 unit 41B
ing onto the coil terminal 127 ... 240 150 ... 250 A 3TX7 402-3J 1 1 unit 41B
240 ... 400 -- C 3TX7 402-3K 1 1 unit 41B
400 ... 600 -- C 3TX7 402-3L 1 1 unit 41B
4 3TC48 Varistors2) 24 ... 48 24 ... 70 D 3TX7 462-3G 1 1 unit 41B
for sticking onto the contac- 48 ... 127 70 ... 150 C 3TX7 462-3H 1 1 unit 41B
3TX7 402-3. tor base or for mounting 127 ... 240 150 ... 250 B 3TX7 462-3J 1 1 unit 41B
separately 240 ... 400 -- A 3TX7 462-3K 1 1 unit 41B
4
400 ... 600 -- C 3TX7 462-3L 1 1 unit 41B
8 and 3TC52, Varistor 24 ... 48 -- D 3TX7 462-3G 1 1 unit 41B
12 3TC56 for sticking onto the contac- 48 ... 127 -- C 3TX7 462-3H 1 1 unit 41B
tor base or for mounting 127 ... 240 -- B 3TX7 462-3J 1 1 unit 41B
separately 240 ... 400 -- A 3TX7 462-3K 1 1 unit 41B
400 ... 600 -- C 3TX7 462-3L 1 1 unit 41B
8 and 3TC52, Varistors2) -- 24 ... 70 B 3TX7 522-3G 1 1 unit 41B
3TX7 462-3. 12 3TC56 for separate screw connec- -- 70 ... 150 B 3TX7 522-3H 1 1 unit 41B
tion or snapping onto TH 35 -- 150 ... 250 B 3TX7 522-3J 1 1 unit 41B
standard mounting rail
3TX7 522-3.
Surge suppressors · RC elements
4 3TC48 RC elements 24 ... 48 -- C 3TX7 462-3R 1 1 unit 41B
For lateral snapping onto -- 24 ... 70 B 3TX7 522-3R 1 1 unit 41B
auxiliary switch or TH 35 48 ... 127 -- A 3TX7 462-3S 1 1 unit 41B
standard mounting rail -- 70 ... 150 B 3TX7 522-3S 1 1 unit 41B
127 ... 240 -- A 3TX7 462-3T 1 1 unit 41B
-- 150 ... 250 B 3TX7 522-3T 1 1 unit 41B
240 ... 400 -- A 3TX7 462-3U 1 1 unit 41B
400 ... 600 -- C 3TX7 462-3V 1 1 unit 41B
3TX7 462-3., 8 and 3TC52, RC elements 24 ... 48 -- B 3TX7 522-3R 1 1 unit 41B
3TX7 522-3. 12 3TC56 For lateral snapping onto 48 ... 127 -- B 3TX7 522-3S 1 1 unit 41B
auxiliary switch or TH 35 127 ... 240 -- B 3TX7 522-3T 1 1 unit 41B
standard mounting rail 240 ... 400 -- B 3TX7 522-3U 1 1 unit 41B
400 ... 600 -- B 3TX7 522-3V 1 1 unit 41B
Surge suppressors · Diodes
4 to 12 3TC48, Diode assemblies3) -- 24 ... 250 D 3TX7 462-3D 1 1 unit 41B
3TC52, . (diode and Zener diode) for
3TC56 DC solenoid system, for
sticking onto the contactor
base or for mounting sepa-
rately
3TX7 462-3.
1)
The connection piece for mounting the surge suppressor must be bent
slightly.
2)
Includes the peak value of the alternating voltage on the DC side.
3) Not for DC economy circuit.
Size Type NO NC
Auxiliary switch blocks
For mounting on the side Left Right
2 and 4 3TC44, Auxiliary switch block } 3TY6 501-1AA00 1 1 unit 41B
3TC48 (replacement for 3TY6 501-1A/-1B)
1 1 13 21 31 43
4
14 22 32 44
4 3TC48 2nd auxiliary switch block, left1) } 3TY6 501-1K 1 1 unit 41B
1 1
2nd auxiliary switch block, right1) D 3TY6 501-1L 1 1 unit 41B
1 1
3TY6 561-1A 8 and 12 3TC52, Auxiliary switch block, left } 3TY6 561-1A 1 1 unit 41B
3TC56 1 1 13 21
14 22
Auxiliary switch block, right } 3TY6 561-1B 1 1 unit 41B
1 1 31 43
32 44
2nd auxiliary switch block, left1) C 3TY6 561-1K 1 1 unit 41B
1 1 13 21
14 22
2nd auxiliary switch block, right1) C 3TY6 561-1L 1 1 unit 41B
1 1 31 43
32 44
1) Can only be mounted on AC-operated contactors.
3TY2 482-0A
Solenoid coils
DC operation1)
2 3TC44 3TY6 443-0B..
4 3TC48 3TY6 483-0B..
8 3TC52 3TY6 523-0B..
12 3TC56 3TY6 563-0B..
AC operation1)
2 3TC44 3TY7 403-0A..
4 3TC48 3TY6 483-0A..
8 3TC52 3TY6 523-0A..
12 3TC56 3TY6 566-0A..
1) Rated control supply voltages see table, page 4/56. The 10th and 11th
digit of the Order No. must be supplemented accordingly.
4
For Version Rated control DT Order No. Price PU PS* PG
contactors supply voltage Us per PU (UNIT,
SET,
M)
Type V AC/DC
Surge suppressors ⋅ Varistors
3TC7 For sticking onto the contactor base 24 C 3TX2 746-2F 1 1 unit 41B
110 C 3TX2 746-2G 1 1 unit 41B
Contacts with fixing parts
3TC7 Main contacts (1 set) -- C 3TY2 740-0E 1 1 unit 41B
2 units required per contactor
Arc chutes
3TC7 For 3TC78: 2 units required -- C 3TY2 742-0C 1 1 unit 41B
per contactor
■ Overview ■ Application
Version Because they are hum-free they are suitable for use in house-
hold appliances and distribution boards in office and residential
The 3TG10 power relays/miniature contactors with 4 main con- areas. They can also be used for applications where there is little
tacts are available with screw terminals or 6.3 mm × 0.8 mm flat space such as air conditioners, heating systems, pumps and
connectors. The versions with screw terminals are climate-proof fans, i.e. for simple electrical controls.
and finger-safe according to IEC 61140.
Standards
The 3TG10 miniature contactors are characterized by their width
of only 36 mm. IEC 60947-1, IEC 60947-4-1, IEC 60947-5-1
Surge suppression Overload and short-circuit protection
The 3TG10 power relays/miniature contactors have an inte- The 3UA7 overload relay can be used for overload protection.
grated protective circuit against opening surges. This applies to mounting onto contactors and to stand-alone in-
4
stallation.
■ Technical specifications
Type 3TG10
Dimensions (W x H x D) mm 36 x 56 x 56
H
D
W
Type 3TG10
AC capacity
Switching gas discharge lamps with correction, ECG
Per main current path 230 V, 50 Hz
Rated power per lamp/capacitance/
rated operational current per lamp
• Shunt compensation L18 W 4.5 µF 0.11 A Unit(s) 15
L36 W 4.5 µF 0.21 A Unit(s) 15
L58 W 7 µF 0.32 A Unit(s) 10
• With ECG (single lamp) L18 W 6.8 µF 0.10 A Unit(s) 39
L36 W 6.8 µF 0.18 A Unit(s) 39
L58 W 10 µF 0.27 A Unit(s) 26
• With ECG (two lamps) L18 W 10 µF 0.18 A Unit(s) 2 x 26
L36 W 10 µF 0.35 A Unit(s) 2 x 26
L58 W 22 µF 0.52 A Unit(s) 2 x 12
4
Utilization category AC-5b, switching incandescent lamps kW 1.6
Per main current path at 230 V, 50 Hz
Load rating with DC
Utilization category DC-1, switching resistive loads (L/R ≤ 15 ms)
• Rated operational currents Ie
- 1 conducting path Up to 24 V A 16
60 V A 6
110 V A 2
220 V / 240 V A 0.8
- 2 conducting paths in series Up to 24 V A 16
60 V A 16
110 V A 6
220 V / 240 V A 1.6
- 3 conducting paths in series Up to 24 V A 18
60 V A 18
110 V A 16
220 V / 240 V A 6
- 4 conducting paths in series Up to 24 V A 20
60 V A 20
110 V A 20
220 V / 240 V A 20
Utilization category DC-3 and DC-5
Shunt-wound and series-wound motors (L/R ≤ 15 ms)
• Rated operational currents Ie
- 1 conducting path Up to 24 V A 10
60 V A 0.5
110 V A 0.15
220 V / 240 V A 0
- 2 conducting paths in series Up to 24 V A 16
60 V A 5
110 V A 0.35
220 V / 240 V A 0
- 3 conducting paths in series Up to 24 V A 16
60 V A 16
110 V A 10
220 V / 240 V A 1.75
- 4 conducting paths in series Up to 24 V A 18
60 V A 16
110 V A 10
220 V / 240 V A 2
Conductor cross-sections
Screw terminals
Terminal screws M3
• Finely stranded with end sleeve (DIN 46228 Form A/D/C) mm2 2 x (0.75 ... 2.5)
• Solid mm2 2 x (1 ... 2.5), 1 x 4
Permissible opening tool (screwdriver) 3.0 mm x 0.5 mm (3RA29 08-1A) or Pozidriv 2
Flat connectors
A2(–) A2(–)
2/T1 4/T2 6/T3 14 2/T1 4/T2 6/T3 22
A2(–) A2(–)
2/T1 4/T2 6/T3 14 2/T1 4/T2 6/T3 22
■ Accessories
Max. rated operational currents Ie/AC-1 Max. conductor DT Order No. Price PU PS* PG
(at 55 °C) of the contactors cross-sections per PU (UNIT,
SET,
M)
Type mm2
Links for paralleling (star jumpers)
3-pole, without connection terminals1)2)
16 -- } 3RT19 16-4BA31 1 1 unit 41B
3-pole, with connection terminals1)3)
40 25 } 3RT19 16-4BB31 1 1 unit 41B
4-pole, with connection terminals1)4)
40 25 C 3RT19 16-4BB41 1 1 unit 41B
1) The links for paralleling can be reduced by one pole. 2) Replacement for 3TX4 490-2C.
The rated operational currents apply to each pole. 3)
Replacement for 3TX4 490-2A.
The links for paralleling are insulated. 4)
Replacement for 3TX4 490-2B.