Chapter 6 Pump Station
Chapter 6 Pump Station
Pump Station
Use of Pumps
Water pumps must not be used as they are not designed to cope
with matters that may be found in sewage and the variability and
quantity of sewage flow.
1. Structural Requirements
2. Ventilation Requirements
3. Odor Control Requirements
4. Wet Wells Requirements
5. Lighting Requirements
6. Level Controls
7. Pump Hydraulic Design
Types of Pumping Station
2. Dry-well type
2. Reciprocating pumps
❑ Capacity
The volume of fluid pumped per unit of time (m3/s)
❑ Head
1. Static head
The actual vertical distance the liquid must be lifted.
2. Friction head
The equivalent distance of the energy that must be supplied to overcome friction.
3. Velocity head
The equivalent distance of the energy consumed in achieving and maintaining the
desired velocity in the system.
❑ Pump efficiency
Pump efficiency is defined as the ratio of water horsepower output from the pump to the
shaft horsepower input for the pump.
❑ Power input
The mechanical power taken by the pump shaft or coupling from the drive.
Pump Stations Design
Assuming 2.5 peaking factor, design a pumping station for a daily average flow of
sewage equal to 15 MLD while 30% of the average flow is considered as minimum
flow, It is required that sewage is to be pumped against a head of 8 m and will be
conveyed by a rising main (pipe) to a treatment site located 200 m away from the
sump well. Assume the efficiency of the pump as 65% and the motor efficiency as
75%. Retention time of sewage in the wet well is 20 minutes.
(a) Compute the maximum and minimum sewage flow, assumed the min flow
as 30% of average flow
(b) Design the rising main, given that vh = 0.75 m/s in the rising main pipe
(c) Design the sump well (wet well), given that the depth of sump well = 4 m
(d) Design the pumps, assumed the losses in bends = 0.5 m
(e) Design the suction pipes, given that vh = 1 m/s in the pipe
(f) Design the dry wells
Example: Design of Pumping Station
1 m3
Qavg = 15 MLD = 15 10 L/d
6
= 15,000 m3 / d
1000 L
Maximum sewage flow reaching the pumping station,
Qmax = peaking factor Qavg
= 2.5 15 MLD
= 37.5 MLD
1d
= 37,500 m3 /d = 0.435 m3 /s
86400 s
Solution: (b) Design of rising main, given that vh = 0.75 m/s in the rising main.
Assuming 0.75 m/s as the flow through velocity in Example of rising main:
the rising main, the cross-sectional area of the
rising main, at peak flow is
Qpeak 0.435 m3 / s
Ax = = = 0.58 m2
vh 0.75 m / s
The diameter of the rising main, dR isdet er mined
by the equation,
4 Ax 4 0.58 m2
dR = = = 0.859 m 0.9 m
Provide a rising main of 900 mm diameter.
Construction of Rising main, Valves and Fittings
Example: Design of Pumping Station
Assuming that the sump well retains the flow of wastewater for 20 minutes,
The quantity of sewage in a rising main of 200 m length is = Volume of sewage in rising main
(0.9 m)2 200 m = 127.23 m3
4
The total capacity of the sump required = Quantity of sewage in the sump +
Quantity of sewage in the rising main
= 522 m3 + 127.23 m3
= 649.23 m3 650 m3
Example: Design of Pumping Station
Assuming a maximum of 4 m depth of the sump well, the surface area of the sump well,
Capacity (or volume) 650 m3
As = = = 162.5 m2
Depth 4m
Pr oviding 3 wet wells such that 2 wells will always remain in operation when
one of the wells is taken under repair or maintenance, the surface area of one wet well is
162.5 m2
A s for 1 wet well = = 54.16 m2
3 units
Now, as the diameter of each sump is 8.5 m, the area of the wet well is
A s = d2 = (8.5 m)2 = 56.72 m2
4 4
Therefore, the minimum liquid depth in each well is
V 190 m3
Dmin = = 2
= 3.35 m 3.4 m
As 56.72 m
Considering all the three (3) pumps to be in operation, the maximum flow that each
pump has to lift,
0.435 m3
Qpump = = 0.145 m3 / s 0.15 m3 / s
3 units
Example: Design of Pumping Station
fLV 2
(i) Compute frictional losses in pipes, hf by the equation, hf =
2gd
where
hf = headloss due to friction, m
f = coefficient of friction = 0.01
L = length of the pipe, m = 200 m
v = velocity of flow in the pipe (rising main), m/s = 0.75 m/s
g = gravitation acceleration, m2 / s = 9.81 m2 / s
d = diameter of the pipe (rising main), m = 0.9 m
Solution: (d) Design of pumps (Con’t) Friction loss in pipe + loss in bends
The maximum flow in the pipe for each wet well is 0.15 m3 / s.
A dry well is designed on the basis of the space required for housing the working well
as well as standby pumps. Normally, one can assume the same dimensions as that
for a wet well. Additional space is provided for ladder (rugs) and working area for
maintenance, etc.
The figure shows a typical plan view of the designed pump house (not to scale).
20 m
10 m 10 m
8.5 m
Wet well 1
Pumps
30 m
Influent
and Wet well 2
pipe
working
space
Wet well 3
Dry well
Operations and Maintenance of Pumps