0% found this document useful (0 votes)
112 views

Water Distribution: Cross Connection Control Water Conservation

The document discusses water distribution systems, which transport heated or cooled water from central plants to air handlers or terminal units throughout buildings. Key components include pumps, which move water through the system, and valves, which regulate water pressure and flow. Systems can be either closed-loop, where water does not contact outside air, or open-loop, where condenser water is exposed to air in cooling towers. Proper maintenance of pumps and valves through preventive maintenance plans helps maintain efficient system operation, saves energy costs, and extends equipment lifespan.

Uploaded by

Owolabi Ruth
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
112 views

Water Distribution: Cross Connection Control Water Conservation

The document discusses water distribution systems, which transport heated or cooled water from central plants to air handlers or terminal units throughout buildings. Key components include pumps, which move water through the system, and valves, which regulate water pressure and flow. Systems can be either closed-loop, where water does not contact outside air, or open-loop, where condenser water is exposed to air in cooling towers. Proper maintenance of pumps and valves through preventive maintenance plans helps maintain efficient system operation, saves energy costs, and extends equipment lifespan.

Uploaded by

Owolabi Ruth
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 10

Water Distribution

Topics:

 Introduction
 Types of Water-Distribution Systems
 Key Components of Water-Distribution Systems
 Safety Issues
 Best Practices for Efficient Operation
 Best Practices for Maintenance
o Maintenance Schedule for Water-Distribution Systems
 References

Introduction

Many large buildings and campuses have HVAC water-distribution systems, also called hydronic
systems. Water is heated or cooled in a central plant, then pumped to air handlers, where
ventilation air is conditioned as needed.

Maintaining and optimizing the performance of pumps and valves-the key mechanical
components of water-distribution systems-can be challenging. These systems often have hidden
performance problems that waste energy and cause excessive wear on equipment.

As with other mechanical components of the HVAC system, a preventive and predictive
maintenance plan is an excellent way to maintain an efficient system, save energy dollars,
prevent costly breakdowns, and extend equipment life.

Learn more about establishing a Best Practice Operation-and-Maintenance Program

.  The water distribution system is the essential link between the water supply source and
the consumer. It is not just the main that runs down your street, quite the contrary. It is an
elaborate conveyance system that allows water to be moved through miles of piping before
reaching your tap. Pumps allow water to move through the system; valves allow water
pressure and flow direction to be regulated along the way.

    The Water Distribution Division is responsible for the maintenance of water mains, water
services, fire hydrants, water valves and backflow devices located within the City's service
area. In short, the Distribution Division ensures that treated water is delivered to your tap.
The Water Utility Supervisor - Distribution supervises five field crews as part of day to day
operations. In addition, a Water System Specialist is responsible for the management and
implementation of the Cross Connection Control Program as required by the 1986 Safe
Drinking Water Act and a Water Conservation Specialist administers the City's Water
Conservation Program.

    540 miles of water mains deliver approximately 24,000 acre feet of water per year to
more than 27,700 residential and commercial customers within our service area. Water
mains vary in size from 1 inch to 48 inches in diameter. Approximately 4,187 hydrants,
7,000 valves and 400 cross connection control devices complete the distribution network.
Employee knowledge of the distribution system and expertise in maintenance and repair
helps ensure the City delivers safe, high-quality water to our customers.

    The current focus of our Distribution crews is the repair and replacement of the more
than 3,000 polybutylene services which remain in our system. Polybutylene service
connections have been leaking due to premature pipe failure and our crews have replaced
approximately 3,200 polybutylene services with copper services. This is an expensive and
time-consuming process; however, maintaining the integrity of the distribution system is
our top priority.

Types of Water Distribution Systems

Water-distribution systems are either closed-loop (cooling- or heating-system water does not
come in contact with outside air) or open-loop (condenser water is exposed to outside air, usually
in the cooling tower). Water in a closed loop requires less treatment than water in an open
system.

Distribution systems for chilled water and heating water

Hydronic System Types


Chilled water: Chilled-water distribution systems transport water used for air conditioning from
the chiller to the air handlers, where the chilled water flows through coils in the ventilation air
stream. Chilled water can also flow directly to terminal units located in the occupied space.
Another variation is radiant cooling or chilled beams where chilled water flows through a radiant
cooling device. Passive chilled beams provide cooling separate from the ventilation-air system.
Active chilled beams are integrated into a ventilation-delivery system.

Learn more about Operation and Maintenance of Chillers.

Heating water: Heating-water systems move water from the boiler, typically located in a central
plant, to air handlers or perimeter terminal units. Heating-water systems are closed loops.

Learn more about Operation and Maintenance of Boilers.

Condenser water: Condenser water loop moves water between the chiller's condenser and the
cooling tower. These systems are usually open loops.

Learn more about Operation and Maintenance of Cooling Towers.

Water-loop heat pump: This hydronic system circulates water to individual water-to-air heat
pumps throughout the building. Most heating and cooling is done by individual heat pumps
serving the zones in which they're located. These heat pumps either take heat from the water loop
or reject heat to the loop. In moderate weather, the water loop self-balances within a controlled
range, usually 65-90°F. In hot weather, if the temperature of the loop exceeds 90°F, water in the
loop will be diverted to a cooling tower. In cold weather, if the loop temperature drops below
65°F, the water will be diverted through a boiler to increase the water temperature in the loop.
Hydronic heat pumps are typically closed-loop systems.

Ground-source water-loop heat pumps: This is a water-loop heat-pump system (as described
above) with the addition of an extensive piping loop buried in the ground which acts as a heat
sink. Heat is absorbed from the ground by the water in the piping loop in heating season, and
rejected into the ground in cooling season.

Constant- and Variable-Flow Pumping Systems

All hydronic systems are either constant-flow or variable-flow. Generally, older buildings have
constant-flow systems and buildings or systems built after about 1990 use some form of variable-
flow control for pumping chilled and heating water.

Constant flow: A constant flow rate is maintained throughout the hydronic loop whenever the
system is operating. Flow rates are established for a peak design condition, which represents a
small fraction of total operating hours.

Variable flow: Variable-flow pumping can be accomplished in several ways:


 Mechanical or magnetic clutch: This type of device controls the torque to the pump
from the motor in response to an external input from the DDC system, typically the
differential pressure between the supply and return piping.
 Variable-speed drive: A VSD alters the frequency of the electrical input to the motor,
allowing the motor to speed up or slow down as required to maintain a setpoint.

Modulating control valves: There are two valve types, two-way and three-way. Either type can
be used for both constant-flow and variable-flow pumping.

 Two-way valves: These can be used in a constant-flow pumping system in conjunction


with a bypass valve that controls pressure. They allow unused water to return to the
central plant if the supply pressure gets too high due to a number of the valves closing.
They can also be used in variable-flow pumping systems where the pump output is
controlled directly by the differential pressure.
 Three-way valves: These are traditionally used in constant-flow pumping systems,
where the unused water is bypassed at the coil. They are also used in variable-flow
pumping systems. In special cases, several may be installed at the end of the longest
piping runs. The sum of their flows equals the minimum flow the pump can produce in
stably. This also allows the piping system to stay at the temperature setpoint in case
another air handler requires immediate chilled or heating water.

Pumping System Arrangements

There are several ways to combine the above system of pumps and valves to provide energy
savings as compared to a single-loop constant-flow system.

Primary-secondary variable-flow systems: Water flows through the chiller or boiler primary
loop at a constant rate, and water flows through the secondary loop, which serves air handlers or
fan coils, at a variable rate. The decoupled section (shown as common piping in the diagram
below) isolates the two systems hydraulically. Primary-secondary variable-flow systems are
more energy efficient than constant-flow systems, because they allow the secondary variable-
speed pump to use only as much energy as necessary to meet the system demand.
Schematic of primary-secondary loop system

Primary-loop variable-flow systems: These are chilled-water or heating-water systems with a


single variable-flow loop. A two-way bypass valve is typically used to maintain a minimum
specified flow rate through the chiller or boiler. Primary-loop variable-flow systems are more
efficient than primary-secondary variable-flow systems.

Key Components of Water Distribution Systems

Pumps: HVAC water-distribution systems use centrifugal pumps. Centrifugal pumps have a
rotating and a stationary component. The rotating section consists of an impeller and shaft; and
the stationary section is the housing, which includes a casing, casing cover, and bearings. A
motor spins the shaft and impeller, creating centrifugal force to increase the velocity of the water
and push it through the volute (the curved funnel increasing in area) to the pump outlet.
Centrifugal pump

Valves: Manual or automatic valves regulate the flow of water throughout the piping system.
Valves perform four basic functions: 1) starting, stopping, and directing flow; 2) regulating or
throttling flow; 3) preventing backflow; and 4) relieving or regulating pressure.

Balance valves, also called circuit setters, are a special type of regulating valve that limit flow at
design conditions. This allows the system to be balanced so that every coil in the system has
adequate flow. Excessive pressure drop across these valves can waste a considerable amount of
energy.

Valve bodies are available in many configurations according to type of service. Regardless of
function, the basic valve components are the body, seat, stem, and packing or gasket. Valve
actuators control water flow through automatic valves in response to electronic or pneumatic
control signals.

Either two-way or three-way valves control the flow of heating or cooling water. Two-way
valves reduce flow and are commonly found in variable-flow systems. Three-way valves
maintain a single flow rate by diverting the water around the coil (or other equipment such as a
chiller or boiler) when necessary. Three-way valves are typically used in constant-flow systems.
Valve components

Pipe and other system components: Pipes connect all components and, with the possible
exception of hydronic-heat-pump loops, should be insulated per local codes. Other system
components that need to be operated and maintained properly are expansion tanks, strainers, and
gauges for pressure and temperature.

Safety Issues

Working near rotating pump shafts and couplings can be dangerous. Control panels for electrical
motors and electrical connections on pump motors present a shock hazard. Heating-water
systems are dangerous if not fully insulated, so be careful not to touch uninsulated piping without
first checking its temperature.

Always observe lock-out and tag-out procedures during maintenance.

Best Practices for Efficient Operation

These best practices will help improve the performance of your water-distribution system and
reduce operating costs:
Monitor the make-up water meter: A quick way to spot a leak in a closed-loop hydronic
system is to monitor the meter on the system make-up water inlet. Reading the meter daily or
weekly and comparing the readings to historical averages can help identify problems.

Investigate valve chatter: Valve chatter or water hammer coming from control valves may
indicate overpressurization at the valve. High pump pressure or system imbalance can exceed the
valve's actuator shut-off rating and cause water to pass through the "closed" valve and thereby
cause the chatter. Water passing through a "closed" valve causes overcooling or overheating,
thereby destabilizing control and wasting energy. Generally, the shut-off pressure limit for 2-way
valves with vertical actuators should be 25% greater than maximum pump head. Two-way valves
with rotating actuators use a much lower torque. Three-way valves do not need as high a limit as
vertical 2-way valves since they simply divert flow. Rebalancing or, as a last resort, replacing the
valve actuator with one with a suitable higher pressure limit may fix the problem. Confirm the
correct operating parameters of the valves in your system before making any changes.

Confirm correct control setpoints: Pumps in a variable-flow system are controlled to maintain
a minimum differential pressure across the coil for a critical zone or for the coil farthest from the
central plant. Make sure the differential pressure setpoint for this coil (there could be more than
one) is at the proper design value. Occasionally these setpoints are raised in an attempt to fix an
unrelated problem and then forgotten, wasting pump energy.

Investigate parallel pumping: Most variable-flow systems have one on-line (or lead) pump and
one standby (or lag) pump. At higher flow rates, it can be more energy efficient to operate both
pumps in parallel. A typical control sequence is for the lead pump to operate alone until twice its
minimum flow rate is reached, then the lag pump cycles on and the two pumps operate together
in parallel on the same speed-control signal. An engineering professional should determine the
best strategy for your particular system.

Best Practices for Maintenance

Pumps are a vital part of HVAC and process-load applications. Pump efficiency directly affects
the efficiency of other system components.

Inspect system weekly: At least once a week, a building engineer should walk the entire system
and check piping, valves, and pumps for leaks and unusual noise. Noise often indicates hidden
valve or pump problems. Sources of noise include turbulence, cavitation, release of entrained air,
and water hammer.

Ensure adequate water treatment: Scale and sludge deposits reduce flow and impair heat
transfer. An ongoing water-treatment program is critical to efficient equipment operation
throughout the distribution system.

Inspect insulation: System efficiency is compromised if the distribution piping has inadequate,
damaged, or wet insulation. Proper insulation can reduce radiant energy loss by as much as 90 to
95%. Removable lagging pads or snap-on insulation are available for parts such as valves that
need periodic maintenance.
Test valve stroke: Test each automatic valve annually. Conduct a test where the valve actuator
moves the valve stem through the entire range of the stroke. Failure to move smoothly through
the entire range indicates a problem.

Maintain optimal condenser water flow: Most condenser-water systems include a strainer to
remove larger material picked up in the open cooling tower. In areas with high particulate counts
in the air, a side-stream mechanical filtration system is recommended to constantly filter the
water and remove contaminants.

Test pump efficiency annually: Testing the efficiency of large pumps and comparing it to
previous benchmarking data will help spot developing problems.

Balance or recommission the system: If temperature-control problems are found in multiple air
handlers and can't be otherwise resolved, or if the hydronic system has been expanded or
modified, a test-and-balance specialist or commissioning engineer should test and recommission
the system.

The table below provides a checklist for maintenance tasks.

Download this table as a Word Document

Maintenance Schedule for Water-Distribution Systems


Maintenance
Description Comments
Frequency
Check pump
Turn off/sequence unnecessary pumps. Daily
use/sequencing
Visually inspect pumps,Visually inspect components to ensure that all
valves, and all equipment is operating, safety systems are in place, Weekly
mechanical joints and no unusual leaks exist.
Test for proper concentrations of dissolved solids and
Test water Monthly
chemistry. Adjust chemicals as necessary.
Ensure that all bearings are lubricated according to
Check lubrication Monthly
manufacturer's recommendations.
Check packing for wear and repack as necessary.
Check packing Monthly
Consider replacing packing with mechanical seals.
Check for leakage that exceeds the manufacturer's
Check mechanical seals Monthly
specifications. Replace if necessary.
Align the pump/motor coupling to ensure efficient
Motor/pump alignment Annually
torque transfer to the pump.
Check mountings Check and secure all pump mountings. Annually
Inspect bearings and drive belts for wear. Adjust,
Check bearings Annually
repair, or replace as necessary.
Check strainers Clean strainers. Annually
Inspect these tanks to make sure that the acceptance
Check expansion tanks Annually
capacity is adequate and that they function properly.
Temperature differences may indicate air binding,
Inspect heating and
clogged strainers, or excessive scale. Determine the Annually
cooling heat exchangers.
cause and correct.
Observe the valves moving through their full range
from closed to 100% open. Back off one-half turn
Cycle valves Annually
from 100% open to prevent the valve from "freezing"
in the full open position.
Check the condition of the motor through temperature Annually
Motor condition
or vibration analysis.

References

ASHRAE Handbook, HVAC Systems and Equipment, 2000

US Department of Energy, Improving Pumping System Performance, Second Edition, May 2006
www1.eere.energy.gov/industry/bestpractices/pdfs/pump.pdf

Harold R. Colen, PE, HVAC Systems Evaluation, 1990

FEMP O&M Best Practices Guide 2.0, July 2004

For additional information on pumps, visit these sites sponsored by the Hydraulic Institute:
www.pumplearning.org, www.pumps.org, and www.pumpsystemsmatter.org.

You might also like