Pvsyst - Simulation Report: Grid-Connected System
Pvsyst - Simulation Report: Grid-Connected System
Author
Project: 3 MW PV Solar Plant in ASWAN
Variant: New simulation variant
PVsyst V7.1.7
VC0, Simulation date:
21/06/21 12:35
with v7.1.7
Project summary
Geographical Site Situation Project settings
Idfū Latitude 24.98 °N Albedo 0.20
Egypt Longitude 32.88 °E
Altitude 84 m
Time zone UTC+2
Meteo data
Idfū
Meteonorm 7.3 (1980-2009), Sat=100% - Synthetic
System summary
Grid-Connected System No 3D scene defined, no shadings
System information
PV Array Inverters
Nb. of modules 6669 units Nb. of units 21 units
Pnom total 3001 kWp Pnom total 2310 kWac
Pnom ratio 1.299
Results summary
Produced Energy 5942 MWh/year Specific production 1980 kWh/kWp/year Perf. Ratio PR 79.07 %
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Main results 4
Loss diagram 5
Special graphs 6
PVsyst V7.1.7
VC0, Simulation date:
21/06/21 12:35
with v7.1.7
General parameters
Grid-Connected System No 3D scene defined, no shadings
PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 28 / 0 ° Diffuse Perez, Meteonorm
Circumsolar separate
PV Array Characteristics
PV module Inverter
Manufacturer Ulica Solar Manufacturer Ginlong Technologies
Model UL-450M-144 Model Solis-110K-5G
(Custom parameters definition) (Custom parameters definition)
Unit Nom. Power 450 Wp Unit Nom. Power 110 kWac
Number of PV modules 6669 units Number of inverters 21 units
Nominal (STC) 3001 kWp Total power 2310 kWac
Modules 351 Strings x 19 In series Operating voltage 180-1000 V
At operating cond. (50°C) Max. power (=>35°C) 121 kWac
Pmpp 2708 kWp Pnom ratio (DC:AC) 1.30
U mpp 702 V
I mpp 3857 A
Array losses
Array Soiling Losses Thermal Loss factor DC wiring losses
Loss Fraction 3.0 % Module temperature according to irradiance Global array res. 3.0 mΩ
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC
Uv (wind) 0.0 W/m²K/m/s
PVsyst V7.1.7
VC0, Simulation date:
21/06/21 12:35
with v7.1.7
Main results
System Production
Produced Energy 5942 MWh/year Specific production 1980 kWh/kWp/year
Performance Ratio PR 79.07 %
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
PVsyst V7.1.7
VC0, Simulation date:
21/06/21 12:35
with v7.1.7
Loss diagram
2290 kWh/m² Global horizontal irradiation
+9.4% Global incident in coll. plane
PVsyst V7.1.7
VC0, Simulation date:
21/06/21 12:35
with v7.1.7
Special graphs
Daily Input/Output diagram