Rules To Estimate The Zero Sequence Parameters For Three Limb Transformers
Rules To Estimate The Zero Sequence Parameters For Three Limb Transformers
A R T I C LE I N FO A B S T R A C T
Keyword: Simple rules to estimate the expected values of zero-sequence impedance measurements for 3-phase core-type
Transformer zero-sequence impedances transformers are shown. The proposed rules are based on the analysis of magnetic circuits. Due to this fact, a
conceptual description about zero-sequence impedances of these transformers is included. The rules were ver-
ified with measurements on fifteen transformers, and these measurements were used for refining the rules. In
case of magnetizing zero-sequence impedances, the presence or not of magnetic shunts on tank walls defines the
details of these rules. In case of short-circuit zero-sequence impedances, only the positive-sequence transformer
impedances are necessary to apply the proposed rules. These rules are important in order to reduce the prob-
ability of errors during the tests. Some rules related to the resistive part of the impedances are also presented.
1. Introduction Most of available values for this article were taken from measure-
ments on YNynd transformers. The analysis of YNynd transformers re-
Three-phase core-type transformers are also known in the literature quires the study of YNyn and Dyn connections. For 3-phase core-type
as 3-phase 3-limb transformers, or 3-phase 3-leg transformers. Zero- YNynd transformers: (a) Z0M are measured with the other wye side in
sequence impedances (Z0) of 3-phase core-type transformers have been open-circuit and the tertiary in open-delta condition; (b) all the other
studied for years [1–20]. There are standardized procedures for Z0 possible measurements are Z0SC, and they can be obtained with one
measurements [11–13], which are based on feeding a wye side of the transformer side without current or with all the windings with currents.
transformer with zero-sequence currents. Induced zero-sequence cur- These differences between the Z0 values are not evident in some
rents could be or not circulating in other transformer sides, depending literature about this topic. There are references with a clear difference
on the specific test. Only the standardized procedures for Z0 measure- between the diverse Z0 values [1–13], but some documents only present
ments are considered in this paper. a wide range of “reactor-type” values [14–16]. The relative position
Z0 values of transformers depend on their design. Measured values (inner/outer) of the winding connected to the source during the test
of Z0 for transformers may be classified as [1]: “no-load type” (very determines the values of the measurements in core-type transformers,
high value), “reactor type” (Z0 is in the order of 1 pu), and “short-circuit and only few references [6–11] consider this key point, but useful ways
type” (Z0 values are relatively low, in the same order of positive-se- to estimate the measurements are only available in a subset of them
quence short-circuit impedances). “No-load type” and “reactor type” [10,11]. Fortunately, an IEC standard [11] has some rules for esti-
values are measured with current only in the winding connected to the mating the values of Z0 measurements, but without any explanation
source (under these conditions, 3-phase core-type units have “reactor about the origin of such rules. Some concepts related to the nature of
type” values, whereas 3-phase units with closed ferromagnetic path for these Z0 values were previously analyzed (in papers about their de-
zero-sequence fluxes have “no-load type” values). For 3-phase core-type termination, with the help of computing magnetic fields in transformer
transformers, “reactor type” values can be also called zero sequence geometry [21–23]), but an integral description about them is still ne-
magnetizing impedances (Z0M) because there is not circulating current cessary, and this paper is a contribution for it.
in the other windings (but there is induced zero-sequence current in the Unavailability of expected values for Z0 has an influence in some
tank). Zero-sequence short-circuit impedances (Z0SC) are measured with human errors during the tests (and such errors could be easily corrected
induced zero-sequence currents in other wye side or in delta windings. during the tests if the persons know the expected values for Z0). For
⁎
Corresponding author at: Dpto. de Conversión y Transporte de Energía, Universidad Simón Bolívar, Apdo. Postal 89.000, Caracas 1080, Venezuela.
E-mail address: [email protected] (E. Sorrentino).
https://doi.org/10.1016/j.epsr.2018.08.020
Received 20 May 2018; Received in revised form 10 August 2018; Accepted 29 August 2018
0378-7796/ © 2018 Elsevier B.V. All rights reserved.
E. Sorrentino, J.C. Burgos Electric Power Systems Research 165 (2018) 94–101
95
E. Sorrentino, J.C. Burgos Electric Power Systems Research 165 (2018) 94–101
the same current in per-unit (if both values are taken at the same zero-
sequence voltage in per-unit, the approximation error is slightly greater
[21]). Results of Fig. 2 are useful to confirm that ΔZ0M tends to be
approximately constant if the difference is taken at the same current in
per-unit or at the same zero-sequence voltage in per-unit (i.e., obtained
curves are practically parallel).
On the other hand, the second rule related to Z0M is: the expected
values of Z1-O and Z2-O should be greater for units with magnetic shunts
on tanks walls than for units without magnetic shunts on tanks walls.
This rule is based on the fact that magnetic shunts on tank walls are
ferromagnetic paths which facilitate the ZSMF by the space between the
winding connected to the source and the tank (i.e., the aforementioned
values of Z0M are greater since the net reluctances are lower).
Furthermore, the use of magnetic shunts on tanks walls decreases the
ZSMF by the tank; consequently, tank losses during ZOM tests in theses
cases should be lower than in cases of units without magnetic shunts on
tank walls. Therefore, the third rule related to Z0M is: the expected
angles of Z0M should be greater for units with magnetic shunts on tanks
walls than for units without magnetic shunts on tanks walls (since va-
lues of Z0M are greater, and tank losses during ZOM tests are lower, in
cases of units with magnetic shunts on tanks walls).
Table 2 shows the available Z0M data for the analyzed transformers.
A subset of these data was analyzed in Ref. [21] to show that ΔZ0M is
approximately Z12 for units without magnetic shunts on tank walls but
not for units with magnetic shunts on tank walls (i.e., this fact is con-
Fig. 2. Example of nonlinearity of zero-sequence magnetizing impedances in firmed here). Two additional points can be highlighted from Table 2:
core-type transformers (the markers in the graph are the measured values in (a) Z1-0 is approximately in the range of 50%–90% for units without
unit 5).
magnetic shunts on tank walls, and in the range of 110%–150% for
units with magnetic shunts on tank walls; (b) K0 ≈ 1 for units without
transformers with magnetic shunts on tank walls. However, ΔZ0M is magnetic shunts on tank walls, and K0 is approximately in the range of
approximately Z12 for units without magnetic shunts on tank walls 0.55–0.75 for units with magnetic shunts on tank walls. Both points are
[21], and this fact is taken to formulate the first rule related to Z0M. On in accordance with the rules derived from the conceptual analysis
the other hand, for cases of transformers with magnetic shunts on tank shown in Section 3.1. These numerical ranges of values can be im-
walls, an additional analysis of measured and computed values of Z0M proved in the future, from the analysis of additional test data from other
in Ref. [21] indicates that ΔZ0M is lower than Z12 for this type of core-type transformers (especially in case of transformers with mag-
transformers; this point had not been previously highlighted and it is netic shunts on tank walls, because the number of analyzed units is very
also taken to formulate the first rule related to Z0M. Thus, the first rule low in this case, and the data of Z0M for unit 14 were not taken exactly
related to Z0M is: at the same per-unit value of IN).
ΔZ0M = Z2-O − Z1-O ≈ K0 Z12 (1)
3.3. Angle of Z0M
K0 = 1 for units without magnetic shunts on tank walls, otherwise
K0 < 1. Table 3 shows the available data for analyzing the angle of Z0M (and
Magnetizing Z0 values are dependent of nonlinearity of tank steel the resistive part of Z0M). A recommendation about using an estimated
[2–5,10,22]. An example of this nonlinearity is shown in Fig. 2. value near to 69° for the angle of Z0M is mentioned in Ref. [22], for
Therefore, the application of this rule should be performed under some transformers without magnetic shunts on tank walls. This angle is close
specific conditions. The recommendation from Ref. [21] is the appli- to 72.5°, which is an approximate value mentioned in Ref. [4] (without
cation of this approximation when both values (Z1-O, Z2-O) are taken at taking into account the presence or not of magnetic shunts). Results
Table 2
Available data of Z0M for the transformers taken as examples, and computed quotients (ΔZ0M/Z12).
Unit MVA Z1-O (%) Z2-O (%) ΔZ0M (%) Z12 (%) ΔZ0M/Z12 (pu) IN or V0 (pu) MS
96
E. Sorrentino, J.C. Burgos Electric Power Systems Research 165 (2018) 94–101
Table 3 Table 4
Data of transformers to analyze the resistive part of Z0M. Estimation for Z1-0 using K1 values from Ref. [8].
Unit 1 3 14 Unit MVA MS K1 Z12 (%) Z1-0 (%) Z1-0 (%)
MVA 15 25 40 Estimated Measureda
Some authors have indicated that Z1-O could be estimated by mul- 4. Zero-sequence short-circuit impedances
tiplying Z12 by an empirical factor (K1) [7–9]:
4.1. Analysis of magnetic circuits
Z1-O ≈ K1 Z12 (2)
Proposed value of K1 [8,9] decreases as transformer capacity is The equilibrium of magnetomotive forces during Z0SC tests is dif-
larger (e.g., K1 ≈ 10 for 10 MVA, and K1 ≈ 5 for 80 MVA, as shown in ferent than in case of positive-sequence short-circuit tests. For positive-
Fig. 3). Table 4 shows the result of applying this estimation to the sequence short-circuit tests, N1I1 = N2I2 if there are currents only in
transformers taken as examples. This comparison shows that this rule two windings, and N1I1 = N2I2 + N3I3 if there are currents in the three
should not be applied for transformers with magnetic shunts on the windings (N1, N2, N3 are the numbers of turns; I1, I2, I3 are the winding
tank walls. This rule of thumb can be applied for units without mag- currents). Nevertheless, these equations are invalid for zero-sequence
netic shunts on tank walls, considering that differences between mea- tests since zero-sequence currents can circulate in the tank.
sured and estimated values can be in the order of 20%. a) Zero-sequence currents in only two windings
On the other hand, Table 1 of IEC Std. 60076-8 [11] simply in- In these cases, the zero-sequence magnetic fluxes (ZSMF) pass
dicates two “approximate” values for Z0M (Z2-0 ≈ 60% and Z1- through the zone between the winding connected to the source and the
0 ≈ 50%), which are not very near to the values shown in Table 2. short-circuited winding (the closed-delta is considered a short-circuited
Fortunately, Section 4.3 of this standard properly indicates that these winding for zero-sequence currents). This fact establishes the following
impedances are nonlinear. Measured values of Table 2 show that the similarities with positive-sequence impedance values: Z1-S and Z2-S are
mean value of Z1-0 is nearer to 70% than to 50%, for units without similar to Z12, Z2-O-D is similar to Z23, and Z1-O-D is similar to Z13.
magnetic shunts on tank walls, and the mean value of Z1-0 is near to Main return paths for ZSMF are imposed by the relative position of
130% for units with magnetic shunts on tank walls (variations in results short-circuited winding since the net flux linkages should be almost
are in the order of 20% in both cases). zero inside it (voltage drop in winding resistance can be considered
negligible). The main ZSMF paths for the different tests are shown in
Figs. 4 and 5. There are main return paths through the magnetic core if
the short-circuited winding is outer than the winding connected to the
power source (Figs. 4 a, 5 a, c, and d), otherwise there are main return
paths through the tank (Figs. 4 b–d, and 5 b).
When the main return paths are through the core, the Z0SC value is
very similar to the sequence-positive value:
When the main return paths are through the tank, the Z0SC value is
Fig. 3. Values of K1 (figure reproduced from Ref. [8]). lower than the sequence-positive value (and the stray losses are greater
97
E. Sorrentino, J.C. Burgos Electric Power Systems Research 165 (2018) 94–101
Fig. 4. Schematic view of main paths for ZSMF during Z0SC tests, with zero-sequence currents in only two windings. Case: T21.
Z1-S-D < Z123 for case T21 (13) Fig. 7. Schematic view of main paths for ZSMF during Z0SC tests, with zero-
sequence currents in the three windings. Case: 21T.
Table 5 shows the data for the 15 transformers taken as examples, as Z1-S ≈ 0.91 Z12 (14)
well as computed quotients of Z0SC divided by the correspondent po-
Z2-O-D ≈ 0.95 Z23 for case T21 (15)
sitive-sequence impedances. These quotients show that approximations
from Eqs. (3) to (13) are very good. Z1-O-D ≈ 0.87 Z13 for case T21 (16)
The computed quotients allow the following refinement for the
Fig. 5. Schematic view of main paths for ZSMF during Z0SC tests, with zero-sequence currents in only two windings. Case: 21T.
98
E. Sorrentino, J.C. Burgos Electric Power Systems Research 165 (2018) 94–101
Table 5
Data of Z0SC for fifteen transformers taken as examples, and computed quotients for Z0SC.
Connection YNynd (T21) YNynd (21T) YNyn
Unit 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
MVA 15 15 25 25 25 30 30 75 100 120 120 150 5 40 100
Z12 10.91 10.64 10.76 10.90 10.68 10.90 14.06 14.00 8.87 14.45 13.78 14.11 6.92 13.90 12.80
Z13 18.25 17.55 20.03 19.11 18.10 17.10 21.39 20.79 14.58 21.69 22.47 17.65 – – –
Z23 5.26 4.98 6.34 5.55 4.75 4.26 5.04 4.92 4.58 40.17 40.53 35.57 – – –
Z2-S/Z12 – 0.98 1.00 1.01 1.03 1.01 1.00 0.97 – 1.01 – 1.00 0.99 – –
Z1-S/Z12 0.93 0.86 0.90 0.90 0.90 0.94 0.93 0.96 – 0.90 0.94 0.90 0.90 0.95 0.95
Z2-O-D/Z23 1.01 – 0.89 – 0.99 – – 0.98 0.97 0.97 – – – – –
Z1-O-D/Z13 0.89 – 0.82 – 0.84 – – 0.93 0.93 0.96 0.98 – – – –
Z2-S-D/Z213 1.10 1.08 1.00 1.02 1.10 1.00 1.01 1.01 – 1.01 – 1.01 – – –
Z1-S-D/Z123 0.93 0.84 0.91 0.91 0.89 0.95 0.93 0.96 0.96 0.99 0.99 1.02 – – –
These rules were also applied to an example (T21) from the litera- R1-S > R12 (21)
ture. The measured positive-sequence impedances are [24,25]: R2-O-D > R23 for case T21 (22)
Z12 = 13.78%, Z13 = 33.3%, Z23 = 18%. Table 7 shows the compar-
ison between estimated and measured values. These results also con- R1-O-D > R13 for case T21 (23)
firm the validity of these rules.
b) Zero-sequence currents in the three windings
Figs. 6 and 7 show the main path for ZSMF. Thus:
4.4. Resistive part of Z0SC
R2-S-D ≈ R213 (24)
Section 4.1 indicates that stray losses are greater when main return
R1-S-D ≈ R123 for case 21T (25)
paths for ZSMF are through the tank because there are more losses in
Table 6
Errors in computed quotients for Z0SC, in comparison with the factors of Eqs. (3), (7)–(12), and (14)–(17).
Connection YNynd (T21) YNynd (21T) YNyn
Unit 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
MVA 15 15 25 25 25 30 30 75 100 120 120 150 5 40 100
Z2-S/Z12 – −0.02 0.00 0.01 0.03 0.01 0.00 −0.03 – 0.01 – – −0.01 – –
Z1-S/Z12 0.02 −0.05 −0.01 −0.01 −0.01 0.03 0.02 0.05 – −0.01 0.03 0.03 −0.01 0.04 0.04
Z2-O-D/Z23 0.06 – −0.06 – 0.04 – 0.03 0.02 −0.03 – – – – –
Z1-O-D/Z13 0.02 – −0.05 – −0.03 – 0.04 0.04 −0.04 −0.02 −0.02 – – –
Z2-S-D/Z213 0.10 0.08 0.00 0.02 0.10 0.00 0.01 0.01 – 0.01 – – – – –
Z1-S-D/Z123 0.03 −0.06 0.01 0.01 −0.01 0.05 0.03 0.06 0.06 −0.01 −0.01 −0.01 – – –
99
E. Sorrentino, J.C. Burgos Electric Power Systems Research 165 (2018) 94–101
Table 8
Data of transformers for analyzing the resistive part of Z0SC.
Unit 1 3 9 14
Connection YNynd (T21) YNynd (T21) YNynd (T21) YNyn
MVA 15 25 100 40
100
E. Sorrentino, J.C. Burgos Electric Power Systems Research 165 (2018) 94–101
part or the angle of zero-sequence impedances, were included here; (d) [10] S. Kulkarni, S. Khaparde, Transformer Engineering: Design and Practice, Marcel
a rule to estimate the difference between the two magnetizing im- Dekker Inc., 2004.
[11] IEC Std. 60076-8, Power Transformers. Part 8: Application Guide, 1997.
pedances is included here; (e) the presence of magnetic shunts on tank [12] IEC Std. 60076-1, Power Transformers. Part 1: General, 2011.
walls has an effect on results and this effect has been considered here. [13] IEEE Std. C57.12.90, IEEE Standard Test Code for Liquid-immersed Distribution,
Power, and Regulating Transformers, 2010.
[14] R. Del Vecchio, B. Poulin, P. Feghali, D. Shah, R. Ahuja, Transformer Design
Acknowledgements Principles, CRC Press, 2010.
[15] M. Heathcote, The J&P Transformer Book, Reed Educational and Professional
Authors are grateful to Gas Natural Fenosa (Spain), Siemens Publishing Ltd., 1998.
[16] C. Wagner, R. Evans, Symmetrical Components, McGraw-Hill, 1933.
(Colombia and Venezuela) and CAIVET (Venezuela) for their valuable [17] J. Winders, Power Transformers: Principles and Applications, Marcel Dekker, 2002.
help, by providing the test data of transformers. [18] R. Bean, N. Chackan, H. Moore, E. Wentz, Transformers for the Electric Power
Industry, McGraw-Hill, 1959.
[19] A. Blume, G. Boyajian, T. Camilli, S. Lennox, V. Minneci, Transformers Engineering,
References
John Wiley & Sons, 1951.
[20] Westinghouse Electric Corporation, Electrical Transmission and Distribution
[1] A. Carlson, J. Fuhr, G. Schemel, F. Wegscheider, Testing of Power Transformers, Reference Book, Westinghouse Electric Corporation, 1950.
ABB AG, 2003. [21] E. Sorrentino, J. Burgos, About the difference between zero-sequence magnetizing
[2] P. Anderson, Analysis of Faulted Power Systems, IEEE Press, 1995. impedances of a 3-phase core-type transformer, Electr. Power Syst. Res. 116
[3] E. Clarke, Circuit Analysis of AC Power Systems vol. 2, John Wiley & Sons, 1950. (November) (2014) 439–443.
[4] A. Garin, Zero-phase-sequence characteristics of transformers. Part II, Gen. Electr. [22] E. Sorrentino, J. Burgos, Application of 2D linear models for computing zero-se-
Rev. 43 (April (4)) (1940) 174–179. quence magnetizing impedances of 3-phase core-type transformers, Electr. Power
[5] A. Garin, Zero-phase-sequence characteristics of transformers. Part I, Gen. Electr. Syst. Res. 117 (December) (2014) 123–133.
Rev. 43 (March (3)) (1940) 131–136. [23] E. Sorrentino, J. Burgos, Application of 2D linear modeling for computing zero-
[6] M. Christoffel, Nullreaktanzen von transformatoren und drosselspulen, Brown sequence short-circuit impedances of 3-phase core-type YNynd transformers, Electr.
Bovery Mitteilungen 52 (November/December (11/12)) (1965) 837–842 (in Power Syst. Res. 122 (2015) 1–9.
German). [24] A. Narang, R. Brierley, Topology based magnetic model for steady-state and tran-
[7] C. Arturi, Comportamento omopolare dei trasformatori trifasi con nucleo a tre co- sient studies for three-phase core type transformers, IEEE Trans. Power Deliv. 9
lonne e due avvolgimenti, L’Energia Elettrica (1) (1987) (in Italian). (August (3)) (1994) 1337–1349.
[8] F. Coppadoro, L’impedenza alla sequenza zero dei trasformatori, Elettrificazione (2) [25] X. Chen, S. Venkata, A three-phase three-winding core-type transformer model for
(1970) (in Italian). low-frequency transient studies, IEEE Trans. Power Deliv. 12 (April (2)) (1997)
[9] V. Oels, Ersatszchaltungen des transformators für das nullsystem, Elektrotechnische 775–782.
Zeitschrift Ausgabe 89 (1968) 59–62 (in German).
101