Eaton Emergency Lighting CPS Catalog 2020 SM Part3
Eaton Emergency Lighting CPS Catalog 2020 SM Part3
Installation example
Country-specific regulations and guidelines must be observed when planning and designing the installation.
SOU
ESF- CG-S UVA
RVS30-1
SOU
ESF-
RVS30-1 CG-S UVA
9
SOU
ESF- CG-S
RVS30-1 UVA
ACU
D G Bus
Et
Ethernet
A
Anschluss
DualG
uard-S
12C
3 3 3
General lighting
3-PM-IO TLS
to general lighting
switches (230 V)
LAN
RJ45 connection
ACU DG Bus
VisionGuard
Monitoring and
programming equipment
3
7 3
F3 remote indicator
Sub distribution board 1 general lighting Sub distribution board 2 general lighting
3 3 1 3 3
LAN
3
ACU DG BUS
to other substations
3 3
3 3
DualGuard-S 28 or DualGuard-S 20
for operation with a maximum of 28 or 20 SKU.1.1 CG-S circuit
modules with 88 circuit terminals. Up to 6 sub-stations can be
supplied with battery power or main power (up to 6 sub-stations
1-phase, up to 2 sub-stations 3-phase).
DualGuard-S 28 DualGuard-S 20
Order details
Model Included with delivery Order no.
DualGuard-S 28 Free-standing cabinet with optimized wiring system for central battery system CEAG 40071362511
DualGuard-S 28, equipped with battery control module (BCM.1), advanced control unit
(ACU DG-S) and power supply unit (PSU). For installing a 4.3" or 7" TFT touch display.
With extra space for adding a maximum of 88 final circuits, or a maximum of 28
variable circuit boards. Please note! The CM charging modules and the TFT touch
display are not part of the cabinet module.
DualGuard-S 20 Free-standing cabinet with optimized wiring system for central battery system CEAG 40071362510
DualGuard-S 20, equipped with battery control module (BCM.1), advanced control unit
(ACU DG-S) and power supply unit (PSU). For installing a 4.3" or 7" TFT touch display.
With extra space for adding a maximum of 88 final circuits, or a maximum of 20
variable circuit boards. Please note! The CM charging modules and the TFT touch
display are not part of the cabinet module.
Order details
Model Included with delivery Order no.
DualGuard-S LAD 100 Free-standing cabinet for central battery system CEAG DualGuard-S LAD 100A, 40071362540
equipped with battery control module (BCM.1), advanced control unit (ACU DG-S) and
power supply unit (PSU). For installing a 4.3" or 7" TFT touch display. With extra space
for adding a maximum of 16 final circuits, or a maximum of 4 variable circuit boards.
Please note! The CM charging modules and the TFT touch display are not part of the
cabinet module.
Order details
Model Included with delivery Order no.
DualGuard-S 12C Compact cabinet for central battery system CEAG DualGuard-S 12C, equipped with 40071362520
battery control module (BCM.1), advanced control unit (ACU DG-S) and power supply
unit (PSU). For installing a 4.3" or 7" TFT touch display. With extra space for adding a
maximum of 48 final circuits, or a maximum of 12 variable circuit boards. Please note!
The CM charging modules and the TFT touch display are not part of the cabinet
module.
DualGuard-S12C6 Compact cabinet for central battery system CEAG DualGuard-S 12C6, equipped with 40071362523
battery control module (BCM.1), advanced control unit (ACU DG-S) and power supply
unit (PSU). For installing a 4.3" or 7" TFT touch display. With extra space for adding a
maximum of 48 final circuits, or a maximum of 12 variable circuit boards. Please note!
The CM charging modules and the TFT touch display are not part of the cabinet
module.
DualGuard-S20C6 Compact cabinet for central battery system CEAG DualGuard-S 20C6, equipped with 40071362524
battery control module (BCM.1), advanced control unit (ACU DG-S) and power supply
unit (PSU). For installing a 4.3" or 7" TFT touch display. With extra space for adding a
maximum of 68 final circuits, or a maximum of 20 variable circuit boards. Please note!
The CM charging modules and the TFT touch display are not part of the cabinet
module.
DualGuard-S12C4 Compact cabinet for central battery system CEAG DualGuard-S 12C4, equipped with 40071362521
battery control module (BCM.1), advanced control unit (ACU DG-S) and power supply
unit (PSU). For installing a 4.3" or 7" TFT touch display. With extra space for adding a
maximum of 48 final circuits, or a maximum of 12 variable circuit boards. Please note!
The CM charging modules and the TFT touch display are not part of the cabinet
module.
DualGuard-S4C3 Compact cabinet for central battery system CEAG DualGuard-S 4C3, equipped with 40071362525
battery control module (BCM.1), advanced control unit (ACU DG-S) and power supply
unit (PSU). For installing a 4.3" or 7" TFT touch display. With extra space for adding a
maximum of 20 final circuits, or a maximum of 4 variable circuit boards. Please note!
The CM charging modules and the TFT touch display are not part of the cabinet
module.
Order details
Model Included with delivery Order no.
DualGuard-S US 38 Free-standing cabinet for sub-stations CEAG DualGuard-S US-S 38, equipped with 40071362513
advanced control unit (ACU DG-S) and power supply unit (PSU). For installing a 4.3" or
7" TFT touch display. With extra space for adding a maximum of 88 final circuits, or a
maximum of 38 variable circuit boards. Please note! The TFT touch display is not part of
the cabinet module.
DualGuard-S US 30 Free-standing cabinet for sub-stations CEAG DualGuard-S US-S 30, equipped with 40071362512
advanced control unit (ACU DG-S) and power supply unit (PSU). For installing a 4.3" or
7" TFT touch display. With extra space for adding a maximum of 88 final circuits, or a
maximum of 30 variable circuit boards. Please note! The TFT touch display is not part of
the cabinet module.
DualGuard-S US 23 Wall cabinet for CEAG DualGuard-S US-S 23 sub-stations, equipped with advanced 40071362532
control unit (ACU DG-S) and power supply unit (PSU). For installing a 4.3" or 7" TFT
touch display. With extra space for adding a maximum of 52 final circuits, or a
maximum of 23 variable circuit boards. Please note! The TFT touch display is not part of
the cabinet module.
DualGuard-S US 15 Wall cabinet for CEAG DualGuard-S US-S 15 sub-stations, equipped with advanced 40071362531
control unit (ACU DG-S) and power supply unit (PSU). For installing a 4.3" or 7" TFT
touch display. With extra space for adding a maximum of 32 final circuits, or a
maximum of 15 variable circuit boards. Please note! The TFT touch display is not part of
the cabinet module.
DualGuard-S US 7 Wall cabinet for CEAG DualGuard-S/US-S 7 sub-stations, equipped with advanced 40071362530
control unit (ACU DG-S) and power supply unit (PSU). For installing a 4.3" or 7" TFT
touch display. With extra space for adding a maximum of 28 final circuits, or a
maximum of 7 variable circuit boards. Please note! The TFT touch display is not part of
the cabinet module
Order details
Model Included with delivery Order no.
DualGuard-S US SOU2 Small distribution board for DualGuard-S/US-S SOU2 sub-stations, 40071362519
equipped with two SOU CG-S 2x4A circuit modules
DualGuard-S US SOU1 Small distribution board for DualGuard-S/US-S SOU1 sub-stations, 40071362518
equipped with one SOU CG-S 2x4A circuit module
DualGuard-S ESF30 15-P Wall cabinet for sub-stations with 30 minutes of functional integrity during fire from 40071362516
outside CEAG DualGuard-S ESF30 15-P, equipped with 4.3" TFT touch display,
advanced control unit (ACU DG-S) and power supply unit (PSU). With extra space for
adding a maximum of 40 final circuits, or a maximum of 15 variable circuit boards.
DualGuard-S ESF30 30-P Free-standing cabinet for sub-stations with 30 minutes of functional integrity during fire 40071362517
from outside CEAG DualGuard-S ESF30 30-P, equipped with 4.3" TFT touch display,
advanced control unit (ACU DG-S) and power supply unit (PSU). With extra space for
adding a maximum of 58 final circuits, or a maximum of 30 variable circuit boards.
685
1135
535
3
230
230
230
230
396
396 396
Order details
Model Included with delivery Order no.
DualGuard-S ESF30 SOU5 Wall cabinet for sub-stations with 30 minutes of functional integrity during fire from the 40071362538
outside DualGuard-S ESF30 SOU5, equipped with five SOU CG-S 2x4A circuit modules
DualGuard-S ESF30 SOU3 Wall cabinet for sub-stations with 30 minutes of functional integrity during fire from 40071362537
outside DualGuard-S ESF30 SOU3, equipped with three SOU CG-S 2x4A circuit
modules
DualGuard-S ESF30 SOU2 Wall cabinet for sub-stations with 30 minutes of functional integrity during fire from the 40071362536
outside DualGuard-S ESF30 SOU2, equipped with two SOU CG-S 2x4A circuit modules
DualGuard-S ESF30 SOU1 Wall cabinet for sub-stations with 30 minutes of functional integrity during fire from the 40071362535
outside DualGuard-S ESF30 SOU1, equipped with one SOU CG-S 2x4A circuit module
TFT touch display 4.3" and 7" TFT touch display 4.3" and 7"
• Dimmable TFT touch display with 64k colors and 250 cd/m2light density
• Touch function across the entire operating surface
• Multi-color icons for status displays, operation and programming
• High performance 32-bit processor, 512MB Ram, 4GB Flash
• Start screen with all essential system information for servicing,
technical acceptance, initial operation and maintenance at a glance
• Intuitive menu navigation through operating levels for initial operation,
configuration, programming and servicing
• EATON's cyber security for password protection, web access and connectivity
• All operating texts and status information in 19 different languages
• Customer-specific texts can be entered on-site
• USB 2.0 host for use in transmitting data during start-up, configuration modifications,
9
log book and software updates
• Web connection available as standard equipment
• IP65 – Meets the highest standards in terms of quality and service life
• Meets all EMV requirements for industrial and commercial use
• DEKRA system certification documents product quality and
compliance with standards for the entire system
• Functionality for 30 minutes in the event of fire verified in a fire test conducted by an independent
materials testing institute
• Conforms to RoHS and REACH
Order details
Model Included with delivery Order no.
HMI module 4.3" SP 4.3" TFT touch display for door installation 40071361644
HMI module 7" SP 7" TFT touch display for door installation 40071361654
Order details
Model Included with delivery Order no.
ACU DG-S module Control module for top-hat rail installation 40071361600
ACU Modul
Cable type such as IY(ST)Y 4x2x0.8 mm
Maximum cable length 900 m
Terminating resistor Switchable via DIL switch on ACU DG-S.
Maximum number of DualGuard-S systems 32
Order details
Model Included with delivery Order no.
AC trafo AC trafo
• For mains supply to internal modules
• DEKRA system certification documents product quality
and compliance with standards for the entire system
• Functionality for 30 minutes in the event of fire verified in a
fire test conducted by an independent materials testing institute
• Conforms to with RoHS and REACH
PSU Modul
Pollution level 2
Order details
Model Included with delivery Order no.
H
P
Strang 1
© 2017 Eaton. All Rights Reserved.. 4
Strang 2
HMI
Strang 3
Strang 4
ACU BCM.1
Order details
Model Included with delivery Order no.
CM.1 1.7A 1.7A charging module for component rack installa- 40071361580
tion
Order details
Model Included with delivery Order no.
Inputs
Nominal AC voltage 220-240V
Nominal DC voltage 184-275V
Rated frequency 50 or 60 Hz
Maximum head dissipation capacity: 8W
Outputs
Rated current 1.5A
short-circuit current 1500A
Inrush current 60A per circuit/240A per module
Order details
Model Included with delivery Order no.
SKU.1 CG-S 4 x 1.5A Circuit switching 4 x 1.5A for component rack instal- 40071361550
lation
Order details
Model Included with delivery Order no.
Inputs
Nominal AC voltage 220-240V
Nominal DC voltage 184-275V
Rated frequency 50 or 60 Hz
Maximum head dissipation capacity: 4W
Output nominal current 6A
short-circuit current 1500A
Inrush current 250A
Order details
Model Included with delivery Order no.
Inputs
Nominal AC voltage 220-240V
Nominal DC voltage 184-275V
Rated frequency 50/60 Hz
Maximum head dissipation capacity: 9W
Short-circuit current per circuit 1500A
Inrush current 250A per circuit
Order details
Model Included with delivery Order no.
Inputs
Nominal AC voltage 220-240V
Nominal DC voltage 184-275V
Rated frequency 50 Hz
Outputs
9 Rated current/voltage 0.65A/24V
Order details
Model Included with delivery Order no.
Inputs
Nominal AC voltage 220-240V
Nominal DC voltage 184-275V
Rated frequency 50 Hz
Outputs
Rated current/voltage 0.65A/24V 9
Order details
Model Included with delivery Order no.
Ordering details
Type Scope of supply Order No.
Order details
Model Included with delivery Order no.
CEAG 3-PM module with test button Circuit monitor module for top-hat rail installation 40071361660
CEAG 3-PM-IO module External CEAG 3-PM-IO and CEAG 3-PM-IO-INV module
To avoid hazards from mains power outages, the functionality of the light distributors for the general
lighting must be continuously monitored in order to turn on safety lighting in the event of a disruption.
Consequently, the CEAG 3-PM-IO and CEAG 3-PM-IO-INV modules are an important element of the
safety system.
• Test button for mains emergency light fault, so there is no need to interrupt
mains voltage and, therefore, no disruptions to operations in progress
• 3-PM-IO module: Eight measurement inputs for monitoring up to three phases
and up to five * light switches
• 3-PM-IO-INV module: Eight inverted measurement inputs for monitoring
CEAG 3-PM-IO-INV module up to three phases and up to five* light switches
• Programmable allocation of CEAG 3-PM-IO and CEAG 3-PM-IO-INV modules
• Meets the requirements of future standards. Reduces the risk of cost incurred from retrofitting
• No E30 wiring by virtue of short circuit/interruption-tolerant communication. This results in signifi-
9
cantly simpler installation and cost savings.
• Does not require that mains power to general lighting be shut off during weekly function testing by
virtue of simple manual testing of the circuit monitoring function via the test button. This avoids the
disruption of operations in progress and the resulting costs thereof
• Automatic record keeping in inspection log. The documentation requirements for safety equipment
are thus satisfied
• Meets all EMV requirements for industrial and commercial use
• DEKRA system certification documents product quality and
compliance with standards for the entire system
• Functionality for 30 minutes during fire verified in a
fire test conducted by an independent materials testing institute
* If the phase monitoring function is not required, all eight measuring
inputs can be used for the light switch query
Order details
Model Included with delivery Order no.
CEAG 3-PM-IO module Module for DIN support rail installation 40071361670
with test button
CEAG 3-PM-IO-INV module Module for DIN support rail installation 40071361680
with test button with inverted input logic
DIN support rails 4 DIN support rails for mounting 40071347125
external modules in the switch cabinet
including mounting material
Order details
Model Included with delivery Order no.
TLS.1 module Stairwell light switch module for top-hat rail installa- 40071361720
tion
9 An automated configuration routine using soft addressing and menu navigation of the TFT touch dis-
play via user icons makes it very easy to manage the system sensor reports and provides a complete
overview.
Order details
Model Included with delivery Order no.
BDM module Battery data bus module for top-hat rail installation 40071361780
Order details
Model Included with delivery Order no.
12V/M6 BBS sensor Battery block sensor for 12V battery blocks 40071362190
with an M6 connection.
14Ah, 23.3Ah, 32Ah, 39.8Ah, 50.4Ah, 53.7Ah,
66.2Ah, 85.7Ah, 89.4Ah
6V/M8 BBS sensor Battery block sensor for 6V battery blocks 40071362202
with an M8 connection.
118Ah
Recommended procedure:
Example:
With respect to the safety lighting requirements for one assembly Depending on the rated operating period required (1, 3 and 8 h),
point (3 h rated operating period and 12 h recharging period), the the battery capacity (C10; 1.8V/cell; +20°C) relative to the maximum
following number of luminaires was determined. discharge current – determined via the battery power consumption
of all consumers – can be determined using the battery discharge
tables. Pursuant to EN 50171, batteries with a duration of at least 10
Quan- Model Current consump- Total years at 20°C shall be used. In this example, with a required rated
tity tion per light operating period of 3 h, a battery capacity of 39.80 Ah (C10: 1.8V/cell;
+20°C) should be selected from the table. The maximum discharge
100 GuideLed 11011 0.011A 1.10A
current for 3 hours of discharge is 11.00A.
250 GuideLed SL 13021.1 0.02A 5.00A
100 V-CG-SLI 350 0.043A 4.30A
Total: 10.40A
Example:
Battery current uptake
= 11.00A for 3 h discharge
Required number of charging modules:
1 x 3.4A according to the charging module table
Example:
Battery current uptake
10.40A + 25%
Aging reserve = 13.00A
Battery Urated = 216V
90% Urated battery
(108 cells) = 194.4V = 1.8V per cell
Example:
100 units GuideLed 11011 @ 8VA = 0.80kVA
250 units GuideLed SL 13021.1 @ 8VA = 2.00kVA
100 units V-CG-SLI 350
11.6VA = 1.16kVA
= 3.96kVA
Order details
Model Included with delivery Order no.
Order details
Model Included with delivery Order no.
DualGuard-S 20C6 DualGuard-S 12C6 DualGuard-S 12C DualGuard-S 12C4 DualGuard-S 4C3
1 1 1 1 1
1 1 1 1 1
1 1 1 1 1
0-20 0-12 0-12 0-12 0-5
0-1 0-1 0-1 0-2 1
0-2 0-2 0-1 – –
-5°C to +35°C -5°C to +35°C -5°C to +35°C -5°C to +35°C -5°C to +35°C
1 1 1 1 1
IP21 IP21 IP21 IP21 IP21
50 50 35 25 12
14.5 14.5 13.8 5.8 3.5
50 50 35 25 12
13.6 13.6 7.6 5.4 2.6
– – – – –
35 mm 2
16 mm 2
16 mm 2
16 mm 2
16 mm2
2 outlets 1 outlet 1 outlet 1 outlet –
2070 x 800 x 605 2040 x 800 x 605 2040 x 800 x 405 1800 x 600 x 405 1000 x 600 x 305
Compact cabinet Compact cabinet Compact cabinet Compact cabinet Compact cabinet
– – – – –
5.5-89.4 Ah 5.5-89.4 Ah 23.3-53.7 Ah 5.5-23.3 Ah 5.5-14 Ah
– – – – –
DualGuard-S US sub-stations
Modules:
Control section: ACU DG-S & HMI 1 1 1 1 1
PSU 1 1 1 1 1
SKU.1 CG-S circuit module 0-38 0-30 0–23*1 0-15 0-7
Cabinet design, electric:
Rated voltage 400/230V 400/230V 230V 230V 230V
Rated frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
9 Cable placement and grounding system TN-C-S/IT TN-C-S/IT TN-C-S/IT TN-C-S/IT TN-C-S/IT
in mains/battery mode
Max. ambient temperature range -5°C to +35°C -5°C to +35°C -5°C to +35°C -5°C to +35°C -5°C to +35°C
Protection class 1 1 1 1 1
Degree of protection IP21 IP21 IP54 IP54 IP54
Max. rated current (mains) 80 80 50 50 25
[∑ L1, L2, L3] [A]
Max. rated output 18.4 18.4 11.5 11.5 6.9
(mains) [KW]
Max. rated current (battery) [A] 80 80 50 50 25
Max. rated output 17.3 17.3 10.8 10.8 6.5
(battery) [KW]
Three-phase split Yes Yes No No No
Connection diameter 35 mm2 35 mm2 35 mm2 16 mm2 16 mm2
for mains and battery feed
Terminal capacity – – – – –
Max. connection diameter of 4 mm2 4 mm2 4 mm2 4 mm2 4 mm2
final circuit
Max. number 88 88 52 32 28
of final circuit connections
Cabinet design, mechanical:
Dimensions H x W x D (mm) 2070 x 800 x 405 2070 x 800 x 405 1200 x 600 x 305 800 x 600 x 305 750 x 400 x 305
Material/design Sheet steel/ Sheet steel/ Sheet steel/wall Sheet steel/wall Sheet steel/wall
free-standing cabi- free-standing cabi- cabinet cabinet cabinet
net net
Hinge position Right Right Right Right Right
Outer finish Powder coating Powder coating Powder coating Powder coating Powder coating
Color RAL 7035 RAL 7035 RAL 7035 RAL 7035 RAL 7035
Partial glazed door Yes Yes No No No
Lock mechanism 3 mm 3 mm 3 mm 3 mm 3 mm
double ward key double ward key double ward key double ward key double ward key
Cable inlets on top Yes Yes Yes Yes Yes
Cable inlets on bottom Yes Yes No No No
Base (optional) 100/200 100/200 - – –
Weight (w/o battery) approx. 170 kg approx. 165 kg approx. 110 kg approx. 75 kg approx. 42 kg
Modules:
Control section: ACU DG-S & HMI 1 1
PSU 1 1
SKU.1 CG-S 1 x 6A circuit module 0-15 0-30
SKU.1 CG-S 2 x 3A circuit module 0-15 0-30
SKU.1 CG-S 4 x 1.5A circuit module 0-15 0-30
DLS/TLS interface module 1 2
Cabinet design, electric:
9
Rated voltage 230V 400/230V
Rated frequency 50/60 Hz 50/60 Hz
Ventilation, decibel level (dB) 55 55
Cable placement and grounding system in TN-C-S/IT TN-C-S/IT
mains/battery mode
Max. ambient temperature range -5°C to +35°C -5°C to +30°C
Protection class I I
Degree of protection IP42 IP42
Max. total rated current [A] relative to ambient temperature
+25°C
+30°C 33 48
+35°C 33 48
33 48
Max. total rated output [A] relative to
ambient temperature
+25°C 7 10.3
+30°C 7 10.3
+35°C 7 10.3
Three-phase split No Yes
Connection diameter for mains and 35 mm² 35 mm²
battery feed
Max. connection diameter of final circuit 4 mm2 4 mm2
Max. number of final circuit connections 40 58
Cabinet design, mechanical:
Dimensions H x W x D (mm) 1278x918x496 2278x918x604
Material/design Coated gypsum fiber- Coated gypsum fiber-
board/wall cabinet board/free-standing
cabinet
Hinge position Right Right
Color RAL 7035 RAL 7035
Cable entry From above From above
Base (optional) – – only with base
Weight 210 kg approx. 330 kg
Licenses/certifications
ABZ housing including components Z-86.3 ... requested requested
ABZ empty housing Z-86.1 ... Yes Yes
Summary report for functional integrity fire test MPA NRW Yes Yes
VDE certificate – –
Specialized company declaration Yes Yes
Modules:
SOU CG-S 2 x 4 A circuit switching module 5 3 2 1
DLS/TLS interface module 2 1 1 –
Cabinet design, electric:
Rated voltage 230V 230V 230V 230V
Rated frequency 50 or 60 Hz 50 or 60 Hz 50 or 60 Hz 50 or 60 Hz
Ventilation, decibel level (dB) – – – –
Cable placement and grounding system in TN-C-S/IT TN-C-S/IT TN-C-S/IT TN-C-S/IT
mains/battery mode 9
Max. ambient temperature range -5°C to +35°C -5°C to +35°C -5°C to +35°C -5°C to +35°C
Protection class I I I I
Degree of protection IP65 IP65 IP65 IP65
Maximum installed heat dissipation performance [W]
Max. total rated current [A] relative to ambient temperature
+25°C
+30°C 33 20 15 8
+35°C 28 17 12 6
16 10 9 5
Max. total rated output [A] relative to
ambient temperature
+25°C 7.1 4.3 3.2 1.7
+30°C 6.0 3.6 2.5 1.2
+35°C 3.4 2.1 1.3 1.0
Three-phase split No No No No
Connection diameter for mains and 10 mm² 10 mm² 10 mm² 10 mm²
battery feed
Max. connection diameter final circuit 4 mm2 4 mm2 4 mm2 4 mm2
Max. number of final circuit connections 10 6 4 2
Cabinet design, mechanical:
Dimensions H x W x D (mm) 1135 x 396 x 230 835 x 396 x 230 685 x 396 x 230 535 x 396 x 230
Material/design Coated Coated Coated
gypsum fiberboard/ gypsum fiberboard/ gypsum fiberboard/
wall cabinet wall cabinet wall cabinet
Hinge position Left Left Left Left
Color RAL 7035 RAL 7035 RAL 7035 RAL 7035
Cable entry From above From above From above From above
Weight (w/o battery) approx. 81 kg approx. 61 kg approx. 51 kg approx. 34 kg
Licenses/certifications
ABZ housing including components Z-86.3 ... – – – –
ABZ empty housing Z-86.1 ... – – – –
Summary report for functional integrity fire test MPA NRW Yes Yes Yes Yes
VDE certificate Yes Yes Yes Yes
Specialized company declaration – – – –
Table 1
Determining the required battery capacity from maintenance-free AGiV block batteries as per EN 50171 (larger battery capacities on request).
C10 battery capacity Ah 5.5 8.5 14.0 23.3 32.0 39.8 50.4 53.7 66.2 85.7 89.4 106.0 118.0 143.1 155.6 178.8 195.4 245.0 268.2 308.0 357.6
at 1.8V/cell and +20°C
1 x 39.8
1 x 66.2
1 x 89.4
1 x 53.7
1 x 89.4
1 x 66.2
2 x 89.4
1 x 89.4
1 x 66.2
1 x 39.8
2 x 89.4
1 x 66.2
3 x 89.4
3 x 89.4
1 x 39.8
4 x 89.4
Max. discharge cur- 1.0 3.2 4.5 9.3 15.4 20.2 24.1 30.7 37.9 49.2 52.6 63.8 73.3 85.1 101.7 113.0 127.6 137.1 176.8 191.4 215.5 255.2
rent [A] at rated op- 1.5 2.5 3.4 6.9 11.9 15.0 19.0 22.7 27.6 34.5 38.3 46.1 53.5 60.0 73.7 80.6 92.2 99.6 126.7 138.3 157.3 194.7
erating period [h],
2.0 2.1 2.9 5.7 9.2 12.3 14.6 18.5 21.5 26.3 31.0 36.0 40.9 46.9 57.5 62.3 72.0 76.9 98.3 108.0 122.6 144.0
1.8V per cell and
+20°C ambient 3.0 1.5 2.1 4.1 6.9 9.1 11.0 13.6 15.8 18.2 23.1 26.5 29.2 33.3 42.3 44.7 53.0 55.7 71.2 79.5 90.5 106.0
temperature 8.0 0.7 1.0 1.7 2.8 3.7 4.8 5.9 6.6 7.9 10.3 11.0 12.7 14.2 17.6 18.9 22.0 23.7 29.9 33.0 37.8 44.0
Special note: The aging allowance of 25% for the batteries is not included in the discharge current figures.
Table 2
9
Number of 1.7A and 3.4A charging modules given a recharging time as per DIN EN 50171 of:
C10 battery capacity h A 5.5 8.5 14.0 23.3 32.0 39.8 50.4 53.7 66.2 85.7 89.4 106.0 118.0 143.1 155.6 178.8 195.4 245.0 268.2 308.0 357.6
at 1.8 V/cell and +20°C
1.7 1 1 1 1 1 0 0 0 1 1 1 0 0 1 0 0 1 1 1 1 0
1.0
3.4 0 0 0 0 0 1 1 1 1 1 1 2 2 2 3 3 3 4 4 5 6
1.7 1 1 1 1 0 0 0 0 1 1 0 0 1 0 0 1 1 1 0 0 1
1.5
3.4 0 0 0 0 1 1 1 1 1 1 2 2 2 3 3 3 3 4 5 6 6
1.7 1 1 1 1 0 0 0 0 1 1 0 0 1 0 0 1 0 0 1 0 0
12 hours/80% 2.0
3.4 0 0 0 0 1 1 1 1 1 1 2 2 2 3 3 3 4 5 5 6 7
1.7 1 1 1 1 0 0 0 1 1 1 0 1 1 0 1 0 0 0 0 1 1
3.0
3.4 0 0 0 0 1 1 1 1 1 1 2 2 2 3 3 4 4 5 6 6 7
1.7 1 1 1 0 0 0 1 1 1 0 0 1 0 1 0 1 1 0 1 1 1
8.0
3.4 0 0 0 1 1 1 1 1 1 2 2 2 3 3 4 4 4 6 6 7 8
Table 3
Number of battery cabinets; battery weight
C10 battery capacity 5.5 8.5 14.0 23.3 32.0 39.8 50.4 53.7 66.2 85.7 89.4 106.0 118.0 143.1 155.6 178.8 195.4 245.0 268.2 308.0 357.6
at 1.8 V/cell and +20°C
Table 4
Determination of air supply and ventilation in electrical operating rooms according to DIN EN 50272-2 (calculated for boost charge):
216V battery 5.5 8.5 14.0 23.3 32.0 39.8 50.4 53.7 66.2 85.7 89.4 106.0 118.0 143.1 155.6 178.8 195.4 245.0 268.2 308.0 357.6
Ventilation cross-section
of the inlet and outlet openings 6.65 10.28 16.93 28.18 38.71 48.14 60.96 64.96 80.08 103.66 108.14 128.22 142.73 173.09 188.21 216.28 236.36 296.35 324.41 372.56 432.55
of the installation space [cm2]
Table 5
Determination of air supply and ventilation in electrical operating rooms according to DIN EN 50272-2 (calculated for boost charge*):
216V battery 5.5 8.5 14.0 23.3 32.0 39.8 50.4 53.7 66.2 85.7 89.4 106.0 118.0 143.1 155.6 178.8 195.4 245.0 268.2 308.0 357.6
Ventilation cross-section
of the inlet and outlet openings 0.83 1.29 2.12 3.52 4.84 6.02 7.62 8.12 10.01 12.96 13.52 16.03 17.84 21.64 23.53 27.03 29.54 37.04 40.55 46.57 54.07
of the installation space [cm2]
DualGuard-S 12C
Final circuit
AE-CU
Scenario: connection via
potential-free signaling contacts
Note:
Fault and scenario
active
Final circuit
DualGuard-S 12C4
Please note the country-specific regulations and guidelines for planning and realisation.
SOU
ESF- CG-S UVA
RVS30-1
SOU
ESF-
RVS30-1 CG-S UVA
SOU
ESF- CG-S
RVS30-1 UVA
RS48
5 Bus
CG-S
ESF- SOU Bus
RVS30-1 CG-S UVA
ZB-S/1
8 C3
US-S/ SOU1
Distribution board for area by area installation
allows electricity costs allocation per rental area
An integral search function automatically detects all system- • Energy-saving and increased service life via alternating switching
dependent luminaires and modules that are assigned an of the charging modules and optimised efficiency
address during installation. A central monitoring device can
be connected via an interface.
four 24 V-inputs,
freely allocated
Terminals for data bus
External 3-PM-IO Module for common switching of safety- and general lighting
Freely programmable
assignment of independent
inputs
(2.5 mm2) per emergency light-
ing circuit or per light
8 inputs with
LED display
Installation example Emergency lighting system ZB-S with distribution board US-S/ SOU1.
Please note the country-specific regulations and guidelines for planning and realisation.
3rd floor
1 2 3 20
SDB
2nd floor
1 2 3 20
SDB
löschen?
ESF-RVS30-1 US-S/ SOU1
3-PM-IO
1st floor
1 2 3 20
SDB
Cellar
1 2 3 20
Power supply
3-PM-IO
E30
ZB-S
RS485
Safe operation
under the most
extreme environ-
mental conditions
There are different types of sub-distributors available for
9 compliance with the requirements on functional integrity of
MLAR 11/2005.
ESF30 SOU2
Small distributor
In accordance with the model guideline on fire protection require-
ments pertaining to wire systems (MLAR specimen guideline on
wire systems), version 11/2005, verified by a National Material
Testing Office.
Tested by a Material Testing Office (MPA) as an empty fire protec-
tion enclosure with a fire resistance rating of minimum 30 minutes
in case of an external fire exposure, with fire test number:
No. 210006480-01.
Functional integrity exceeding 30 minutes is certified by a VDE
certificate, together with an expert opinion relating to the electrical
equipment based on a fire test.
Please note the country-specific regulations and guidelines for planning and realisation.
ESF E3
0/13-S
230 V AC
Data li
ne
220 V DC
ZB--S/1
8 C3
7 control keys • C
onnection for analog inputs:
for user-friendly navigation 4 of freely assignable 24 V analog inputs, can
be programmed negated and non-negated,
e.g. for start / cancel function test, start / cancel
LED indicators for:
operating duration test, disable / enable
• Ready
system, manual reset, maintained light on / off,
• Electrical Source for Safety Services
power on safety lighting as continuity lighting.
• Failure
Graphic display:
128 x 64 pixel, backlit, program
adjustable contrast and brightness.
Mains operation X
Charging fault X
Circuit fault X
Luminaire fault X
Common system fault X
Total discharge protection X
ISO fault X
Function test X
Continuous operation test X
Device fault
Ordering details
Type Model Order No.
SD Card Secure-Digital-Card
Flexible data storage for system and log book configuration, e.g. of the mandatory archiving of log
book information for a minimum of 4 years.
The system can also be programmed at any PC using optional SD-card reader and CEAG software.
Texts can also be entered on the control module in the switch cabinet.
Storage of:
• 360,000 log book entries
• Location texts for the luminaires (20 characters per luminaire)
SD card reader • Location texts of external modules such as phase monitor, TLS, 3-PM-IO (20 characters per module)
• Circuit names (20 characters per circuit)
• System name (20 characters)
Ordering details
Type Model Order No. 9
SD card SD card formatted for ZB-S 40071347911
SD card reader SD card reader for USB-Port 40064070561
Software Software for external programming 40071347152
of the ZB-S via PC
Programming
• Easy system programming
with an office PC according
Removable configuration to installation plans
and log book storage SD • System configuration can be
stored in the PC
PC with CEAG software
for SD programming and
analysis
Ordering details
Type Order No.
AC-Module AC-Module
Together with the DC/DC converter.2, the optional AC module supplies the internal system voltage
when the battery supply is isolated, e. g. for maintenance.
Ordering details
Type Scope of supply Order No.
Ordering details
Type Scope of supply Order No.
Fusing 5 AT / 6.3 x 32
Continuous current rating 3 A per circuit
Max. inrush current 250 A per circuit
Typical switch over time AC/DC approx. 450 ms
Own consumption 3.85 W
Ordering details
Type Scope of supply Order No.
Fusing 10 AT / 6.3 x 32
9 Continuous current rating 6 A per circuit
Max. inrush current 250 A per circuit
Typical switch over time AC/DC approx. 450 ms
Own consumption 3.85 W
Ordering details
Type Scope of supply Order No.
Fusing 8 AT / 6.3 x 32
Continuous current rating 4 A per circuit
Max. inrush current 250 A per circuit
Typical switch over time AC/DC approx. 450 ms
Own consumption ≤ 9 W (for 2 x 4 A)
Dimensions 178 x 108 x 60
Ordering details
Type Scope of supply Order No.
SKU CG 2 x 3 A SKU CG 2 x 3 A
Change-over module SKU, module without STAR Function
• Up to 20 luminaires can be monitored individually
• AC/DC switching per each circuit
• Separate fusing for mains and battery operation
• Easy access to fuses
• LED indicates fault and Run/ON for each circuit
• Supplies electronic ballast and LED-luminaires
• Service-friendly modular units are wired up and ready to connect to 3-tier 4 mm2 disconnect
neutral terminals (optional)
• Gear tray mounting
Fusing 5 AT / 6.3 x 32
9
Continuous current rating 3 A per circuit
Max. inrush current 120 A per circuit
Typical switch over time AC/DC approx. 450 ms
Own consumption 3.85 W
Ordering details
Type Scope of supply Order No.
SKU CG 1 x 6 A SKU CG 1 x 6 A
Change-over module SKU, module without STAR Function
• Up to 20 luminaires can be monitored individually
• Separate fusing for mains and battery operation
• Easy access to fuses
• LED indicates fault and Run/ON
• Supplies electronic ballast and LED luminaires
• Service-friendly modular units are wired up and ready to connect to 4 mm2 3-tier disconnect
neutral terminals (optional)
• Gear tray mounting
Fusing 10 AT / 6.3 x 32
Continuous current rating 6 A per circuit
Max. inrush current 180 A per circuit
Typical switch over time AC/DC approx. 450 ms
Own consumption 3.85 W
Ordering details
Type Scope of supply Order No.
Slots 1
Fusing G-Fuse 5 x 20 1.6 AT
Max. rated current AC 0.65 A
Max. rated current DC 1.00 A
9 Max. connection terminals 150 VA
for luminaire KVG
Rated power DC/DC-converter 2.3 W
Distortion factor <5%
Ordering details
Type Scope of supply Order No.
SWR 150 Indicate light source and luminous flux ratio 40071347960
General
lighting
Safety lighting in
switched maintained
mode
Attention:
Parallel switching of various
lamp wattages on one circuit
is not possible.
Backplane N
Backplane L
Table 1. Battery current consumption values (A) dependent upon number of luminaires and luminous flux ratio (LV%)
at 20 °C ambient temperature at the luminaire.
T5
International description
Base G5
Lamp power (W) 8W-VVG
Luminous flux ratio (%) 100 51 35
Switch setting 0 4 9
Number of luminaires /
Current consumption from the battery / [A] [VA] [A] [VA] [A] [VA]
Apparent power
1 0.175 / 36 0.123 / 19 0.118 / 12
2 0.258 / 72 0.150 / 37 0.090 / 24
3 – 0.213 / 56 0.120 / 36
4 – 0.246 / 74 0.157 / 48 9
5 – 0.276 / 92 0.192 / 60
6 – 0.322 / 110 0.220 / 71
7 – – 0.240 / 83
8 – – 0.260 / 94
9 – – 0.280 / 105
Table 2. Battery current consumption values (A) dependent upon number of luminaires and luminous flux ratio (LV%)
at 20 °C ambient temperature at the luminaire.
T26
International description
Base G13
Lamp power (W) 58 58 58 36 36 36 36 18 18 18 18
Luminous flux ratio (%) 100 48 32 100 75 54 32 100 87 54 36
Switch setting 0 5 9 0 2 4 8 0 1 5 9
Number of luminaires /
Current consumption from the battery / [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA]
Apparent power
1 0.62 147 0.37 84 0.35 81 0.47 107 0.34 80 0.31 71 0.30 70 0.37 85 0.31 72 0.26 60 0.26 60
2 – – – – – – – – 0.59 137 0.47 109 0.36 83 – – 0.56 121 0.33 75 0.29 67
3 – – – – – – – – – – – – – – – – – – 0.47 108 0.35 82
Table 3. Battery current consumption values (A) dependent upon number of luminaires and luminous flux ratio (LV%)
at 20 °C ambient temperature at the luminaire.
TC-L
International description
Base 2G11
Lamp power (W) 36 36 36 24 24 24 24 18 18 18 18
Luminous fluxverhältnis (%) 100 59 43 100 73 57 46 100 71 52 47
Switch setting 0 5 9 0 3 6 9 0 3 7 9
Number of luminaires /
Current consumption from the battery / [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA]
Apparent power
1 0.47 108 0.30 70 0.29 68 0.38 89 0.28 64 0.27 62 0.27 65 0.39 90 0.26 60 0.26 60 0.25 60
2 – – 0.43 96 0.33 76 – – 0.42 99 0.34 79 0.32 74 – – 0.42 98 0.31 70 0.28 65
3 – – 0.58 135 0.44 103 – – 0.61 136 0.44 103 0.37 86 – – 0.57 135 0.40 94 0.34 80
9
4 – – – – – – – – – – 0.56 130 0.47 105 – – – – 0.50 117 0.46 104
Table 4. Battery current consumption values (A) dependent upon number of luminaires and luminous flux ratio (LV%)
at 20 °C ambient temperature at the luminaire.
TC-D
International description
Base G24Q1. G24Q2
Lamp power (W) 26 26 26 26 18 18 18 18 13 13 13 13 10 10 10
Luminous flux ratio (%) 100 71 61 47 100 79 63 48 100 77 63 42 100 68 52
Switch setting 0 3 5 9 0 2 5 9 0 2 4 9 0 4 9
Number of luminaires /
Current consumption from the battery / [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA] [A] [VA]
Apparent power
1 0.36 85 0.28 63 0.27 61 0.27 64 0.30 51 0.26 37 0.24 29 0.23 24 0.26 60 0.26 49 0.21 49 0.21 49 0.25 58 0.21 49 0.20 44
2 – – 0.39 93 0.35 80 0.33 76 0.47 87 0.35 64 0.29 47 0.28 37 0.39 90 0.30 68 0.28 63 0.29 66 0.39 90 0.26 58 0.26 62
3 – – 0.54 126 0.45 104 0.36 80 0.65 114 0.48 86 0.36 65 0.32 48 0.53 121 0.41 91 0.32 73 0.30 71 0.54 125 0.31 74 0.30 70
4 – – – – 0.57 132 0.43 97 – – 0.60 106 0.44 81 0.34 62 – – 0.53 110 0.38 87 0.32 74 – – 0.38 88 0.32 72
5 – – – – – – – – – – 0.71 125 0.53 94 0.40 73 – – 0.57 130 0.48 103 0.33 76 – – 0.47 104 0.36 75
6 – – – – – – – – – – – – 0.60 108 0.44 83 – – – – 0.52 120 0.38 87 – – 0.54 121 0.40 81
7 – – – – – – – – – – – – – – – – – – – – 0.59 136 0.42 94 – – 0.59 137 0.45 94
PD 3 printer PD 3 printer
The printer logs and memorizes all function tests and mains failures of a ZB-S cover or a substation.
After the performance of an automatic function test, the results are printed out in plain text stating
also the time and date. The printing is automatic with each entry into the log book of the control
module. A mains failure is also logged with time and date. The printer documents the operational
state of emergency luminaires of a emergency lighting supply system. By means of the printer,
the information on possible failures of the luminaires (e. g. defective lamp) can be printed out in detail.
• Gear tray mounting
Ordering details
Type Scope of supply Order No.
Ordering details
Type Scope of supply Order No.
Ordering details
Type Scope of supply Order No.
Mains distribution module incl. 3 pcs. screw caps E18 and 40071347160
for track mounting 3 pcs. D02-fuse inserts 25 A
1 2 3
Current rating 63 A
Battery distribution module D02-E18 Rated operating voltage 400 V
Box terminal for circulator conductor to 16 mm2
Material Polyamide (PA 6.6), 30 % glass-fibre-reinforced
Scope of supply incl. 2 pcs. screw caps E18 and
2 pcs. D02-fuse inserts 25 A
Ordering details
Type Scope of supply Order No.
Battery distribution module incl. 2 pcs. screw caps E18 and 40071347161
for track mounting 2 pcs. D02-fuse inserts 25 A
Cover strip
Busbar guard: Cover strip for clip-mounting to the trunking section. Ready-cut to module width.
Material: Hard PVC.
Ordering details
Type Scope of supply Order No.
Busbar cover strip Cover strip in module width for clip mounting 40071347192
at the trunking section
Charging characteristics IU
Terminals 2.5 mm2 rigid and flexible
End-of-charge voltage boost charge 259 V DC
(factory setting for +20°C) trickle charge 248 V DC
Deep discharge protection 183.6 V DC
9 Potential-free signal contacts 0.5 A/24 V AC/DC
Ordering details
Type Scope of supply Order No.
Ordering details
Charging module CM 3.4 A Type Scope of supply Order No.
Charging module rack 4-way Unit accommodates 4 charging modules CM 3.4 A 40071347043
for ZB-S/26 and ZB-S/18 9
Charging module rack 2-way Unit accommodates 2 additional 40071347130
charging modules CM 3.4 A for ZB-S/26 and ZB-S/18
(only in conjunction with 40071347043)
Ordering details
Typ Lieferumfang Bestell-Nr.
Charging module rack 1-way Unit accommodates 1 charging module CM 3.4 A 40071347167
compact for ZB-S/10 C
Charging module rack 2-way Unit accommodates 2 charging modules CM 3.4 A 40071347130
compact for ZB-S/10 C6
Ordering details
Type Scope of supply Order No.
Remote switch
Control loop for blocking the installation during factory shutdowns with differential loop monitoring
for short-circuit and open circuit detection.
F3 remote indication
Ready
12
Source for Safety Services 22
Failure 32
S1
1k
S2
Remote switch
+
S1 S2 C0 12 14 21 22 24 31 32 34 + –
LAN
with HTTP via TCP
IP: 192.168.100.6
CEAG 3-PM Voltage monitoring module CEAG 3-PM Voltage monitoring module
To avoid risks from mains failures, it is necessary to permanently monitor the function of the mains
lighting light distributors in order to switch on the safety lighting in the event of a fault. Thus the CEAG
3-PM modules are an important part of the safety system.
If one phase fails, the CEAG 3-PM module switches a relay contact and interrupts the 24 V current
loop to the emergency lighting units. All emergency luminaires in stand-by circuit are switched to con-
tinuous light. A second relay contact is used to signal the power failure.
• No E30 wiring due to short circuit and interruption tolerant 24 V current loop technology.
• Test button for mains/emergency light failure thus no interruption of the mains voltage necessary
and thus no failures of the operational processes.
Ordering details
Type Scope of supply Order No.
CEAG 3-PM Modul with Test-Taster Module ready for mounting 40071361660
Current loop
24 V current loop for emergency lighting request using differential loop monitoring for short-circuit
and open circuit detection.
ZB-S /
LP-STAR /
AT-S+
CEAG 3-PM-IO Modul External CEAG 3-PM-IO and CEAG 3-PM-IO-INV module
To avoid risks from mains failures, it is necessary to permanently monitor the function of the general
lighting light distributors in order to switch on the safety lighting in the event of a fault.
Thus, the CEAG 3-PM-IO and CEAG 3-PM-IO-INV modules are an important part of the safety system.
• Permanent function monitoring of the entire system by bus technology
• Automatic logging of all test results in the test log book
• Test button for mains / emergency light failure thus no interruption of the
mains voltage necessary and thus no malfunctions of the operational processes
• 3-PM-IO Modul: Eight measurement inputs for monitoring up to three phases
CEAG 3-PM-IO-INV Modul
and up to five * light switches
• 3-PM-IO-INV Modul: Eight inverted measurement inputs for monitoring up to
three phases and up to five* light switches
• Freely configurable assignment of the measuring inputs to the emergency lighting
• No E30 wiring of bus illumination due to Fail Save Bus technology 9
* If the phase monitor function is not required, all eight measurement
inputs can be used for light switch enquiry.
Ordering details
Type Scope of supply Order No.
General General
lighting lighting
Emergency Emergency
CEAG 3-PM-IO-Modul CEAG 3-PM-IO-INV
lighting lighting
RS 485 RS 485
max. length of bus 1200 m max. length of bus 1200 m
9 SOU SOU
TLS TLS
3-PM-IO 3-PM-IO
CG-
US-S1 Controller
CG-S Bus
ZB-S
max. length
of bus 900 m
US-S2 ZB-S US-S3
terminal with JY(ST)Y terminal
CG-S bus for communication 4 x 2 x 0.8 mm
by ZB-S or US-S systems with a resistant resistant
CG controller ZB-S. 105 105
Notes:
i
Bus topology: linear, double terminated (no spur lines allowed)
The absolutely essential terminating resistors are supplied in a plastic pack in the control cabinet.
Cable type (minimum requirement): JY(ST)Y 4 x 2 x 0.8 mm (twisted pair, screened).
The conductor size required for the 24 V bus voltage will depend on the line length and the number
of bus modules (Umin = 19 V DC).
3-PM-IO = external maintained light switching module (3-PM-IO bus module)
TLS = external stairwell light switching module
BMS = Building Management System
Detailed print of the programmed electrical circuits (line diagram) with the following details per
electrical circuit:
• electrical circuit / SKU number and type
• individual electrical circuit name
• type of monitoring
• switching mode of the electrical circuit
• number of luminaires
• address and individual name per luminaire
• switching mode of each luminaire
Ordering details
Type Scope of supply Order No.
Ordering details
Type Scope of supply Order No.
Central battery system ZB-S/26 Central battery system type ZB-S/26 incl. CU CG-S, 40071362905
BCM and DC/DC.2, 26 free module slots*1
Central battery system ZB-S/18 Central battery system type ZB-S/18 incl. CU CG-S, 40071362906
BCM and DC/DC.2, 18 free module slots*1
Central battery system ZB-S/LAD Central battery system type ZB-S/LAD incl. CU CG- 40071347099
S, BCM and DC/DC.2, (2 free module slots possible)
Central battery system ZB-S/10 C Central battery system type ZB-S/10 C, incl. CU 40071362900
CG-S, BCM and DC/DC.2, 10 free module slots*1
Central battery system ZB-S/26 C6 Central battery system type ZB-S/26 C6 incl. CU 40071689064
CG-S, BCM and DC/DC.2, 26 free module slots*1
Central battery system ZB-S/18 C6 Central battery system type ZB-S/18 C6 incl. CU 40071362904
CG-S, BCM and DC/DC.2, 18 free module slots*1
Central battery system ZB-S/10 C6 Central battery system type ZB-S/10 C6 incl. CU 40071362903
9 CG-S, BCM and DC/DC.2, 10 free module slots*1
Central battery system ZB-S/18 C3 Central battery system type ZB-S/18 C3, incl. CU 40071362902
CG-S, BCM and DC/DC.2, 19 free module slots
Central battery system ZB-S/10 C3 Central battery system type ZB-S/10 C3, incl. CU 40071362901
CG-S, BCM and DC/DC.2, 11 free module slots
Central battery system ZB-S/2 C3 Central battery system type ZB-S/2 C3, incl. CU 40071360201
CG-S, BCM and DC/DC.2, 3 free module slots
Substation US-S/36 Substation type US-S/36 incl. CU CG-S and 40071362907
DC/DC.2, 36 free module slots
Substation US-S/28 Substation type US-S/28 incl. CU CG-S and 40071362908
DC/DC.2, 28 free module slots
Substation US-S/21 Substation type US-S/21 incl. CU CG-S and 40071347088
DC/DC.2, 21 free module slots
Substation US-S/13 Substation type US-S/13 incl. CU CG-S and 40071347089
DC/DC.2, 13 free module slots
Substation US-S/5 Substation type US-S/5 incl. CU CG-S and 40071347090
DC/DC.2, 5 free module slots
Substation US-S/ SOU2 Substation type US-S/ SOU2 40071360510
incl. 2 x SOU CG-S 2 x 4 A
Substation US-S/ SOU1 Substation type US-S/ SOU1 40071360511
incl. 1 x SOU CG-S 2 x 4 A
E30 junction box ESF-RVS30-1 For small cabinets type US-S/SOU with 2 NEOZED 40036071032
fuses inside
Substation ESF-E30/13-S Substation type ESF-E30/13-S, equipped with 40071362912
control module CU CG-S, DC/DC 2-converter,
with space reserve for expansion to max. 40 final
circuits, but max. 13 variable circuit modules
Substation ESF-E30/28-S Substation type ESF-E30/28-S, equipped with 40071362913
control module CU CG-S, DC/DC 2-converter,
with space reserve for expansion to max. 60 final
circuits, but max. 28 variable circuit modules
Substation US-S ESF30 28-P Substation type US-S ESF30 28-P incl. control 40071360738
module CU CG-S and DC/DC.2, with space reserve
for final assembly up to max. 60 final circuits, how-
ever accepts max. 28 variable change-over modules
Substation US-S ESF30 13-P Substation type US-S ESF30 13-P incl. control 40071360737
module CU CG-S and DC/DC.2, with space reserve
for final assembly up to max. 40 final circuits, how-
ever accepts max. 13 variable change-over modules
*1 Plus max. two additional slots in correlation of CM 1.7 A and CM 3.4 A placement.
Ordering details
Type Scope of supply Order No.
Substation US-S ESF30 SOU5 Small distribution board US-S ESF30 SOU5, incl. 40071360734
5 switching over units SOU CG-S 2 x 4 A
Substation US-S ESF30 SOU3 Small distribution board US-S ESF30 SOU3, incl. 40071360732
3 switching over units SOU CG-S 2 x 4 A
Substation US-S ESF30 SOU2 Small distribution board US-S ESF30 SOU2, incl. 40071360729
2 switching over units SOU CG-S 2 x 4 A
Substation US-S ESF30 SOU1 Small distribution board US-S ESF30 SOU1, incl. 40071360726
1 switching over unit SOU CG-S 2 x 4 A
ESF-RVS30 E30 junktion box ESF-RVS30 for ESF-E30 40071347920
with 4 Neozed fuse inside
Reduction Reduction M32 to M20 cable glands 40071071033
for E30 junction boxes incl. M20 cable gland
4 pcs. DIN-mounting rail incl. mounting accessories 40071347125
3 pcs. C-section rail incl. mounting accessories 40071347126
9
Modules:
Control module: CU CG-S 1 1 1 1
DC/DC.2-converter (DCM) *5
1 1 1 1
BCM 1 1 1 1
Circuit module SKU CG-S*5 0-26*8 0-18*8 0-2*2 0-10*8
Maximum number of SWR 150 7 7 2 7
due to 100% luminous flux and
max. rated power
Charging module 1,7 A 0-2 0-2 0-2 0-2
Charging module 3,4 A 0-6*1 0-6*1 0-8 0-1*3
Electrical cabinet construction:
Rated voltage 400/230 V 400/230 V 400/230 V 230 V
9 Rated frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Conductor order and system of earthing in mains TN-C-S / IT TN-C-S / IT TN-C-S / IT TN-C-S / IT
power operation/battery operation
Max. ambient temperature*9 -5 °C to +35 °C -5 °C to +35 °C -5 °C to +35 °C -5 °C to +35 °C
Insulation class 1 1 1 1
Degree of protection IP20 IP20 IP20 IP20
Max. current rating mains [∑ L1, L2, L3] [A] 80 80 100 35
Max. rated power mains [KW] 18.4 18.4 23 13.8
Max. current rating battery [A] 80 80 100 35
Max. rated power battery [KW] 17.3 17.3 21.6 7.6
Three-phase distribution yes yes yes no
Conductor size for 50 mm2 50 mm2 50 mm2 16 mm2
mains and battery supply
Outgoing circuits 0 - 6 Feeders 0 -6 Feeders 0 - 15 Feeders 1 Feeder
Conductor size 16 mm2 16 mm2 16 mm2 35 mm2
Max. conductor size final circuits 4 mm2 4 mm2 4 mm2 4 mm2
Max. number of final circuit terminals 80 68 8 40
Mechanical cabinet construction:
Dimensions H x W x D (mm) 2050 x 800 x 400 2050 x 800 x 400 2050 x 800 x 400 2050 x 800 x 400
Material / Design Sheet steel / Sheet steel / Sheet steel / Sheet steel /
Cabinet Cabinet Cabinet Compact cabinet
Door stop right right right right
Outer coating Textured powder paint Textured powder paint Textured powder paint Textured powder paint
Colour RAL 7035 RAL 7035 RAL 7035 RAL 7035
Partial viewing door Yes Yes No Yes
Lock 3 mm 3 mm 3 mm 3 mm
Two-way Two-way Two-way Two-way
Cable entry from above yes yes yes*7 yes
Cable entry from below yes yes yes*7 no
Base (optional) 100/200 100/200 100/200 200
Weight (without batteries) approx. 180 kg approx. 170 kg approx. 170 kg approx. 155 kg
Battery capacity, installed in:
Compact cabinet – – – 23.3-53.7 Ah
Battery cabinet 23.3-195.4 Ah 23.3-195.4 Ah 23.3-308 Ah –
Battery rack 23.3-195.4 Ah 23.3-195.4 Ah 23.3-308 Ah –
1 1 1 1 1 1
2 2 1 1 1 1
1 1 1 1 1 1
0-26*8 0-18*8 0-10*8 0-19 0-11 0-3
7 7 7 7 7 2
2250 x 800 x 600 2050 x 800 x 600 2050 x 800 x 600 1800 x 600 x 350 1800 x 600 x 350 1000 x 600 x 300
Sheet steel / Sheet steel / Sheet steel / Sheet steel / Sheet steel / Sheet steel /
Compact cabinet Compact cabinet Compact cabinet Compact cabinet Compact cabinet Compact cabinet
right right right right right right
Textured powder paint Textured powder paint Textured powder paint Textured powder paint Textured powder paint Textured powder paint
RAL 7035 RAL 7035 RAL 7035 RAL 7035 RAL 7035 RAL 7035
Yes Yes Yes Yes Yes No
3 mm 3 mm 3 mm 3 mm 3 mm 3 mm
Two-way Two-way Two-way Two-way Two-way Two-way
yes yes yes yes yes yes
no no no no no no
– – – 200 200 –
approx. 250 kg approx. 205 kg approx. 206 kg approx. 120 kg approx. 115 kg approx. 50 kg
*6 Higher battery capacities =>118 Ah are achieved by connecting several battery sets in parallel.
*7 Please indicate the cable entry when planning the system.
*8 Plus max. two additional slots in correlation of CM 1.7 A and CM 3.4 A placement.
*9 Optimal ambient battery temperature +20 °C.
Modules:
Control module: CU CG-S 1 1 1 1
DC/DC.2-converter (DCM) *1
1 1 1 1
Circuit module SKU CG-S*1 0-36 0-28 0-21 0-13
1 – –
1 – –
0-5 inkl. 2 x incl. 1 x
SOU CG-S 2 x 4 A SOU CG-S 2 x 4 A
– – –
– – –
230 V 230 V 230 V
50/60 Hz 50/60 Hz 50/60 Hz
TN-C-S / IT TN-C-S / IT TN-C-S / IT
9
25 16 8
6.5 3.4 1.7
no no no
16 mm2 10 mm2 10 mm2
– – –
4 mm2 4 mm2 4 mm2
20 4 2
Modules:
Control module: CU CG-S 1 1
DC/DC.2-converter (DCM)*1 1 1
Circuit module SKU CG-S 1 x 6 A 0-13 0-28
Circuit module SKU CG-S 2 x 3 A 0-13 0-28
Circuit module SKU CG-S 4 x 1.5 A 0-13*3 0-28*4
Switching over unit SOU CG-S 2 x 4 A – –
Maximum number of SWR 150 due to 100% – –
luminous flux and max. rated power
Interface module DLS/TLS 2 2
Web module 1 1
Electrical cabinet construction:
9 Rated voltage 230 V 400/230 V
Rated frequency 50/60 Hz 50/60 Hz
Artificial ventilation, sound pressure level (dB) 55 55
Conductor order and system of earthing in mains TN-C-S / IT TN-C-S / IT
power operation/battery operation
Max. ambient temperature -5 °C to +35 °C -5 °C to +30 °C
Insulation class I I
Degree of protecton IP42 IP42
Maximal permitted heating power loss [W] 45 90
Maximal rated power [A] depending on the
ambient temperature
+25 °C 35 (30)*6 40 (45)*6
+30 °C 17.3 (30)*6 20 (45)*6
+35 °C 11 (30)*6 – (45)*6
Maximal rated power [kW] depending on the
ambient temperature
+25 °C 7.5 (6.4)*6 8.6 (9.7)*6
+30 °C 3.7 (6.4)*6 4.3 (9.7)*6
+35 °C 2.3 (6.4)*6 – (9.7)*6
Three-phase distribution no yes
Conductor size for 35 mm² 35 mm²
mains and battery supply
Max. conductor size final circuits 4 mm2 4 mm2
Max. number of final circuit terminals 40 60
Mechanical cabinet construction:
Dimensions H x W x D (mm) 1278 x 918 x 496 2278 x 918 x 604
Material / Design Coated plaster Coated plaster
board / Wall board / Wall
cabinet cabinet
Door stop right right
Colour RAL 7035 RAL 7035
Cable entry from above from above*7
Base (optional) – – only with base
Weight (without batteries) approx. 169 kg approx. 330 kg
Certification / Verification
ABZ housing including modules - -
ABZ housing without modules yes yes
Fire test fire protection test report short form MPA NRW yes yes
VDE certificate – –
Declaration of expert yes yes
*1: After more than 13 SKU CG-S 4 x 1.5 A or 26 SKU CG-S 2 x 3 A / 1 x 6 A a second DC/DC converter is needed.
Please observe that all DC/DC-converters are operated on the same module assembly frame next to each other.
*2: Protective isolated acc. to VDE 0106
*3: Max. 40 circuits. Attention: Please note the maximum rated power!
*4: Max. 60 circuits. Attention: Please note the maximum rated power!
*5: Please note: Each DLS module reduces the possible number of SOU modules.
*6: (...) = Plannings with SKU CG-S 2 x 3 A and SKU CG-S 1 x 6 A modules.
*7: Cable entry from below on request
US-S ESF30 SOU5 US-S ESF30 SOU3 US-S ESF30 SOU2 US-S ESF30 SOU1
– – – –
– – – –
– – – –
– – – –
– – – –
5 3 2 1
– – – –
2*5 1*5 1 –
– – – –
33 20 15 8
28 17 12 6
16 10 9 5
1135 x 396 x 230 835 x 396 x 230 685 x 396 x 230 535 x 396 x 230
Coated plaster Coated plaster Coated plaster Coated plaster
board / Wall board / Wall board / Wall board / Wall
cabinet cabinet cabinet cabinet
left left left left
RAL 7035 RAL 7035 RAL 7035 RAL 7035
from above from above from above from above
– – – –
approx. 81 kg approx. 61 kg approx. 51 kg approx. 34 kg
- - - -
- - - -
yes yes yes yes
yes yes yes yes
yes yes yes yes
3 3 3
Browser LAN
General lighting
to general lighting
switches (230 V)
CG-S BU S 2)
CG-S BU S 2)
3
löschen?
Control and
1)
programming unit
3
3
CG Controller
ZB-S
1)
7 3
F3 remote indicator
Sub distribution board 1 general lighting Sub distribution board 2 general lighting
3 3 1 3 3
2)
2)
RS485 BUS to other
RS485 BUS to other external modules
external modules
3-PM-IO TLS 3-PM-IO
3 3
3 3
1 2 3 4 5 6 7 8 1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 16 9 17 10 11 12 13 14 15 16 17
J J J
I I
I
H
H H
G G
G
F
F F
E
E E
D
D D
9 C
C
C
B
B B
1 2 3 4 6 7
und Rissen. Abweichungen müssen über Grenzmuster gesondert vereinbart werden.
Free of dirt
8 and unfamiliar materials, sink marks, voids, burrs, flow marks and cracks.
9 10 11 12 13 14
SBG ZB-S LSC 40071361280 Benennung/ designation
ZB-S 18 LSC
A0 D 1 1
5 Deviations have to be agreed upon boundary samples.
CEAG-Sachnummer/ CEAG-part number
1 2 3 4 6 7 8 9 10 11 12 13 14
SBG ZB-S LSC 40071361281 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
5
Erstellt/ Gep
issued 3.3.16 Blüggel che
Entstanden aus/ Ersa
developed from repl
Län
Rad
A Win
Wer
ZB-S/10C3 ZB-S/2C3
Deviations have to be agreed upon boundary samples.
1 2 3 4 5 6 7 8 9 10 11 12 13 14
SBG ZB-S LSC
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
1 2 3 4 6 7 8 9 10 11 12 13 14
SBG ZB-S LSC 40071361230
5
Substations
2068
2068 81,42
918
918 36,14
496
496 19,53
918
918 36,14
596
596 23,46
US-S ESF30 SOU5 US-S ESF30 SOU3 US-S ESF30 SOU2 US-S ESF30 SOU1
535
685
835
396
1135
230
230
396
230
396
230
396
LP-
STAR
Ethernet
LP-
STAR
Ethernet
9
Ethernet
LP-
STAR
Ethernet
Building 1
IP router Central battery LP-STAR Automatic Test LP-STAR
system ZB-S System AT-S+
Ethernet
TCP/IP
Building 3
CGVision PC
CG-S bus
Simple installation
and reliable power
supply 9
LP-STAR is especially recommended in case of the separate supply Features • Optional webmodule for
of emergency lighting systems of individual fire areas to save on • No special requirements the automatic monitoring of
installation costs incurred by installing E30 cabling to cover concerning the housing on LP-STAR according to EN
different fire areas. functionality in case of 62034
The LP-STAR System supplies reliable power to the escape installation in separate fire • Optional CG-S interface for
luminaires and exit sign luminaires (230V AC/220 V DC) according areas connecting to the CG-S bus
to EN 50171. It is suitable for emergency lighting systems • Cost savings as E30 wiring is for CGVision or master/slave
according to DIN VDE 0100-560, EN 50172 and V DIN V VDE 0108- not required because devices operation for connecting
100. are installed in separate fire several LP-STAR devices
The system performs an automatic self-check and monitors all areas • Shorter inspection time using
CG-S luminaires connected (up to 20 luminaires per circuit) simply • Natural ventilation is generally the CEWA GUARD
through a feed line. The circuit type of each connected CG-S sufficient due to the closed technology, automatic
luminaire can be programmed freely in the 50 Hz or 60 Hz supply form and low capacity of function monitoring of up to
network with the control module based on the STAR technology. batteries 20 luminaires per circuit
This means that the same power circuit is used for mixed operation • Reduced installation costs
• Additional safety even in
including maintained light, switched maintained light and non- due to the STAR technology,
case of fire due to the
maintained light, all this without an additional data cable! freely programmable mixed
decentralised arrangement
The control module including a non-volatile program memory as of systems operation of switching modes
well as a big graphical display that monitors and controls the LP- per luminaire in a single
• Simple operation and
STAR device and checks all functions of the connected emergency circuit without an additional
commissioning based on a
luminaires according to EN 62034 and it reports the operating data cable
smart programming and
states of the entire system. The integrated search function detects • Automatic luminaire search
operating plan
all luminaires addressed during installation automatically. A central function
monitoring system can be connected using the optional bus • 230V AC / 220V DC supply
interface. voltage selectable to power • Plain text display at the
the escape luminaires and control module for all
The main scope for the protection of electrical rooms is the luminaires
exit sign luminaires to comply
protection of the environment against the hazards involved with
with architectural issues • Flexible data memory for the
technical devices, transformer stations and switching stations of
over 1 kV. At the same time, for example in case of fire, the • Standard integrated phase test log and device
operation of safety-relevant systems, central battery systems and monitor for monitoring configuration using the
fixed power generators must be maintained for a specific period of general power supply Secure Digital card
time. conditions • Absence of retroactive effect
The LP-STAR System was designed to meet the requirements • Additional phase monitor of different circuits in case of
concerning batteries and these have been verified according to EN input including line a short-circuit due to the
60950 and EN 50272-2. monitoring for an external automatic, selective shut-off
phase monitor function
• Standard eight digital 230 V • EoL shut-off, programmable
input channels for switching as standard
each luminaire separately, for
example, freely
programmable
S = Switching
T = Technology
A = Advanced
R = Revision
9
Switch to safety!
The continuing development of the CEWA GUARD monitoring system has led to the creation of the
Switching
Technology
Advanced
Revision,
or STAR for short. This CG-STAR-technology allows different switching modes to be implemented
in the same circuit, and the switching mode of each individual luminaire can be re-programmed at any
time.
As a result, this technology offers not just the proven CEWA Guard safety when it comes to operating
a safety lighting system, it also gives planners the confidence and flexibility of knowing that the system
can respond and adapt at any time to any changes that are made to a building and its use.
L1/L2/L3/N/PE
4 x 2,5 AT
220 V
DC
24 V
DC
12 V 12 V
Your Advantages:
The number of outgoing circuits needed can be sharply reduced, since continuously operating,
stand-by and switchable permanent lighting can be realised in one common circuit.
This allows the use of shorter cable distances, reduces installation costs and minimises the effects
of burning materials. Any mode of operation can be assigned at a later date – without
encroachment in the lighting installation. This enables simple project planning without having to
take all possible types of operation into account.
As with CEWA GUARD technology, the patented STAR technology requires no additional data
cable to the luminaires.
Conventional Installation:
Maintained light 1 (DS)
Non-maintained light 1 (BS)
Non-maintained light 2 (BS) 9
Maintained light 2 (DS)
Switched maintained light 1
(3-PM-IO)
Switched maintained light
(3-PM-IO)
• Each type of switching mode
requires two circuits
DS 3-PM-IO
• Only one type of switching
BS 3-PM-IO mode is possible per circuit
• Any later modifications in-
BS
volve a large amount of work
and expense
DS
DS
7 control keys
for a user-friendly navigation
Graphic display:
14:15:00 31.01.15
ČČČČČČČČČČČČČČČČČČČČ 128 x 64 pixels, back-lit, program adjustable
Operation contrast and brightness.
U= 27,8V ĀāI=+ 0,2A
Mains operation X
Mains failure X X
UV mains failure X
Charge fault X
Circuit fault X
Luminaire fault X
Common system fault X
Total discharge protection X
ISO fault X
Function test X
Duration test X
Device fault
Note:
NO = Normal Open
(normally open)
NC = Normal Closed (normally
closed)
11 12 14 21 22 24 31 32 34 41 42 44 The device is fitted with
4 potential-free signal contacts
(relay outputs) and an integrated
buzzer.
Signal contacts freely
programmable including: 1 x
Rel 1 Rel 2 Rel 3 Rel 4 changeover contact 1 x 24 V;
0.5 A capacity
Programming
• Simple device programming
with a PC at the office
based on the installation
Removable SD card with designs
configuration and inspection • Device configuration can be
log book data saved on the PC
PC with CEAG software
for programming and
evaluating the SD card data
Input
Output
LP-STAR 4-48
LP-STAR 4-12 LP-STAR 4-24 LP-STAR-4-36 LP-STAR-4-48
Circuits 4 4 4 4
Max. battery size
2 x 12 V / 12 Ah 4 x 12 V / 12 Ah 6 x 12 V / 12 Ah 8 x 12 V / 12 Ah
(C10; 1.8 V/Z, +20 °C)
Dimensions (W x H x D) 260 x 550 x 260 mm 260 x 730 x 260 mm
Max. ambient temperature For storage: -20 °C to + 40 °C,
For operation*: -5 °C to + 35 °C
Sound pressure level at mains 0 dB / 50 dB
operation / emergency mode
(converter operation)
Housing colour RAL 7035
Degree of protection / insulation class IP20 / I
Weight (approx.) without battery 17 kg 21 kg
Battery
Rated capacity Dimensions Number of batteries Total weight
AhK10, 1.8 V/Z, +20 °C of one battery UB = 12 V pieces of all batteries
L x W x H (mm) (kg)
1 = 4 x M25
2 = 18 x M20
3 = 6 x M16
Ordering details
Type Model Order No. Selection
Input
Output
Circuits 4 4 4 4
max. battery size
2 x 12 V / 12 Ah 4 x 12 V / 12 Ah 6 x 12 V / 12 Ah 8 x 12 V / 12 Ah
(C10; 1,8 V/Z, +20 °C)
Dimensions (W x H x D) 815 x 600 x 300 mm
Max. ambient temperature For storage: -20 °C to + 40 °C,
For operation*: -5 °C to + 35 °C
Sound pressure level at mains 0 dB / 30 dB
operation / emergency mode
(converter operation)
24 x M16 1 x M50/32 Housing colour RAL 7035
13 x M20 4 x M32/20
Degree of protection electronic area IP54
8 x M25/16
Degree of protection battery box IP21
2 x M20
Degree of protection / insulation class I
Weight (approx.) without battery 17,5 kg
Battery
Rated capacity Dimensions Number of batteries Total weight
AhK10, 1.8 V/Z, +20 °C of one battery UB = 12 V of all batteries
L x W x H (mm) (kg)
Ordering details
Type Model Order No. Selection
6 5
LP-STAR
1
3 4-24 / ESF30 2
4 3 LP-STAR ESF30
5 4 5
6 6
7 7
8 8 9
9 10
10
688
J Input
Output
1238
Circuits 4 4 4 4
335
E String 1
String 2
max. battery size 36Ah
2 x 12 V / 12 Ah 4 x 12 V / 12 Ah 6 x 12 V / 12 Ah 8 x 12 V / 12 Ah
(C10; 1,8 V/Z, +20 °C)
String 3
Dimensions
A (2 : 5)
(W x H x D) 1238 x 688 x 335 mm
Max. ambient temperature For storage: -20 °C to + 40 °C,
40
18
D
For operation*: -5 °C to + 35 °C
Sound pressure level at mains 0 dB / 30 dB
operation / emergency mode
(converter operation)
String 1
C String 2
Housing colour 36Ah Light grey
String 1
String 2
Degree of protection 48Ah IP54
String 3
A (2 : 5) Degree of protection / insulation calss I
String 3
Weight (approx.) without battery String 4
170 kg
B
Number of cable entries:
2 x 40 mm * Maximum Design Life Time at +20 °C: 10 years Erstellt/
issued 21.6.18 Blüggel Geprüft/
checked
Entstanden aus/ Ersatz für/
developed from replacemen
32 x 18 mm Battery
CTQ
Längen/ len
Radius/ rad
Winkel/ ang
ASMD LP-STAR ES
Deviations have to be agreed upon boundary samples.
LP-STAR
1 2 3 10 J: 12 Ah
4 5 152 x 98 x 1026 max.
7 8 pieces 8 4 pieces:9 15,25
String 1 8 pieces: 30,50
String 2
48Ah
String 3
String 4
Erstellt/
issued 21.6.18 B
Entstanden aus/
developed from
ASMD LP
3 4 5 6 7 8 9 LP-STAR
Ordering details
Type Model Order No. Selection
5
6
Schematic diagram
3/N/PE
PE
N-DLS2
N-DLS3
N-DLS4
N-DLS5
N-DLS6
N-DLS7
N-DLS8
L-DLS1
L-DLS2
L-DLS3
L-DLS4
L-DLS5
L-DLS6
L-DLS7
L-DLS8
U1
U2
U3
U4
01
02
03
04
S1
S2
S3
S4
11
12
14
21
22
24
31
32
34
41
42
44
PE
L3
L2
L1
N
CSU
3/N/PE
Controller
CGVision
CM4-24 + CNV -
N L
U 220V DC
24V DC
B+ t B- B+ B-
+ - + - + - + - PE
N-DLS2
N-DLS3
N-DLS4
N-DLS5
N-DLS6
N-DLS7
N-DLS8
CG-S-A
CG-S-A
CG-S-B
CG-S-B
L-DLS1
L-DLS2
L-DLS3
L-DLS4
L-DLS5
L-DLS6
L-DLS7
L-DLS8
UH+
UH+
UH-
UH-
U1
U2
U3
U4
01
02
03
04
S1
S2
S3
S4
11
12
14
21
22
24
31
32
34
41
42
44
PE
L3
L2
L1
N
CSU
Controller CM4-24 + CNV -
N L
U 220V DC
24V DC
B+ t B- B+ B-
+ - + - + - + -
CEAG 3-PM Voltage monitoring module CEAG 3-PM Voltage monitoring module
To avoid risks from mains failures, it is necessary to permanently monitor the function of the mains
lighting light distributors in order to switch on the safety lighting in the event of a fault. Thus the CEAG
3-PM modules are an important part of the safety system.
If one phase fails, the CEAG 3-PM module switches a relay contact and interrupts the 24 V current
loop to the emergency lighting units. All emergency luminaires in stand-by circuit are switched to con-
tinuous light. A second relay contact is used to signal the power failure.
• No E30 wiring due to short circuit and interruption tolerant 24 V current loop technology.
• Test button for mains/emergency light failure thus no interruption of the mains voltage necessary
and thus no failures of the operational processes.
Ordering details
Type Scope of supply Order No.
CEAG 3-PM Modul with Test-Taster Module ready for mounting 40071361660
Current loop
24 V current loop for emergency lighting request using differential loop monitoring for short-circuit
and open circuit detection.
ZB-S /
LP-STAR /
AT-S+
Ordering details
Type Scope of supply Order No.
Remote switch
Control loop for blocking LP-STAR during operating downtimes with differential loop monitoring for
short circuit and wire breakage detection.
F3 module
Ready
Soures for 12
Safety Services 22
Failure 32
S1
Remote switch S2
+
+ S2 S1 - 11 12 14 21 22 24 31 32 34
CG-S bus
CG-S/USB
Interface
Ethernet
TCP/IP
Ethernet
CGVision PC
To connect a LP-STAR to a CGVision visualization software,
(See ordering details on
CGVision product page)
following CG-S Bus Interface for LP-STAR is required:
Ordering details
Type Scope of supply Order No.
*A
ttention: The CG-S Bus Interface must be installed by the manufacturer. The module can be installed later on site only with the
replacement of the entire CSU module.
Detailed print of the programmed circuits (wiring diagrams) with the following information for each
circuit:
• Circuit/ SKU number and type
• Individual circuit name
• Monitoring type for circuit
• Switch type for circuit
• Number of luminaires
• Address and individual name of each luminaire
• Circuit type for each luminaire
Ordering details
Type Scope of supply Order No.
12 V 12 V
Max. inrush current transformer output 250 A
Luminaire series Luminaire type Power consumption Power consumption Inrush current [A]
battery operation [W]* mains operation [VA]*
N-EVG 54 W V-CG-S Rated value N-EVG ... V-CG-S in case of mains and battery operation
Term T5 T5 T5 T5 T5 T5
Lamp cap G5 G5 G5 G5 G5 G5
Type N-EVG ... V-CG-S 14 / 21 / 28 / 14 / 21 / 28 / 14 / 21 / 28 / 14 / 21 / 28 / 24/39 W 24/39 W
35 W 35 W 35 W 35 W
Lamp load [W] 14 21 28 35 24 39
Battery operation, incl. converter efficiency
[W] in switch position (luminous flux
�E/�Rated in %)
100 % 18 24 33 40 29 42
90 % 15 22 29 35 26 37
80 % 14 20 26 31 22 33
70 % 13 18 24 29 20 29
60 % 11 15 22 24 18 26
50 % 10 14 20 22 15 24
40 % 9 12 18 20 15 22
30 % 8 11 15 18 13 20
Power consumption [VA] 18 25 32 39 28 41
Inrush current [A] 10 10 10 10 10 10
System power lamp + EVG 16 23 30 37 25 41
acc. EN 50294 [W]
N-EVG 58 W V-CG-S
Term T5 T5 T5 T8 T8
Lamp cap G5 G5 G5 G13 G13
Type N-EVG ... V-CG-S 49W 54W 80W 36W 58W
Lamp load [W] 49 54 80 36 58
Power consumption [A] at 220 V battery
operation in switch position (luminous
flux �E/�Rated in %)
100 % 53 57 84 37 55
90 % 46 51 75 33 48
80 % 42 46 66 31 44
70 % 37 40 59 26 40
60 % 33 35 53 24 35
50 % 31 33 46 22 31
9
40 % 26 29 42 20 29
30 % 24 26 37 18 24
Power consumption [VA] 55 58 85 37 55
Inrush current [A] 10 10 12 10 10
System power lamp + EVG acc. 52 57 84 34 53
EN 50294 [W]
The required battery current is determined based on luminous flux conditions (30% ... 100%).
Dim mode 30% only down to 10°C, 60% only down to 0°C allowed.
When used outdoors, the 100% setting should only be used.
Calculation example
The following luminaires should be connected to one power circuit:
8 pieces of GuideLed 10011 CG-S RZ
4 pieces of V-CG-SLI 350
2 pieces of GuideLed SL 13021.1
There are the following conditions:
Battery operation: Mains operation:
max. cont. output: 330 W max. 345 VA apparent power
max. inrush current 250 A
max. output:
10011 CG-S: 8 x 1.9 W = 15.2 W
V-CG-S-SLI 350: 4 x 10.7W = 42.8 W
13021.1 CG-S: 2 x 3.9W = 7.8 W
Total = 65.8 W < 330 W --> OK 9
Attention!
The connected load of all circuits in total may not exceed 540 W and 1080 VA per LP-STAR device.
When conecting external modules to the 24 V auxiliary supply, consider power consumption with
battery sizing.
U
I
CM 4-24
2,4 V/cell
The completely sealed lead batteries are charged gradually based on an IU0U charging curve in
2,23 V/cell U
function of temperature. Boost charge is activated in function of the battery charge level to ensure
1,7 V/cell deep discharge protection
that the batteries are charged without exceeding the gassings voltage.
The charge monitoring procedure verifies the charging process continuously and it reports any faults
I
immediately, including interruption of the battery circuit, faulty charging unit or a high impedance
battery cell.
O2
Evaluation of aeration and deaeration of electrical service rooms according to DIN EN 50272-2
PbO2
Pb
– H2O + Capacity 12 24 36 48
Air volume flow required for the aeration of the 57.6 115.2 172.8 230.4
The extremely low gas emission absorption location room [l/h], calculated for boost charge*
cells are designed to ensure that the Vent cross-section of the air inlets and outlets of 1.6 3.2 4.8 6.5
positive plate is charged completely before the place of installation [cm2], calculated for boost
the negative plate and consequently the charge*
released oxygen diffuses to the negative
plate. On the negative plate it reacts Air volume flow required for the aeration of the 7.2 14.4 21.6 28.8
with the lead to form lead-oxide which location room [l/h], calculated for trickle charge*
in turn reacts with the sulphuric acid Vent cross-section of the air inlets and outlets of 0.2 0.4 0.6 0.81
electrolyte and forms lead-sulphate and the place of installation room [cm2], calculated for
water to prevent any loss of water.
trickle charge*
* If boost charge is not frequently used (for example once a month), the air flow rate can be calculated
based on the trickle charge current.
General lighting
Browser LAN
CG-S BUS
3
7 3
F3 remote indication
LP-STAR light cannot be selected at the Status and error messages can • individual buttons for device
monitoring module or EVG/LED be retrieved for each individual test, function test and
supply module using slide luminaire. duration test.
switches, coding switches or Communication with system- • 3 freely programmable
jumpers respectively. The oriented luminaires takes place function keys for example:
additional costs incurred due to only through the connected Lock/unlock device, manual
the use of parts made by other power line. reset, turn on/off maintained
manufacturers or additional light, display fault list, turn on/
components on the installation Using the search function, the
luminaires connected to the off continuity lighting,
lines cannot be claimed. simulation mains failure UV.
system addressed during
Simple connection technology installation are automatically • 7 control buttons for user-
using plug-in, back of hand detected. friendly navigation in query
proof clamp connections. and programming mode.
Control module Programming options:
Bus technologies
9 A freely programmable control Individual luminaire monitoring,
CG-S bus technology based on module with a non-volatile circuit monitoring, individual
LONWorks® technology program memory and name (20 characters) per
For data communication a alphanumeric graphic display device, circuit, luminaire, device
2-pole, bidirectional CG-S data monitors and controls the LP- address, selective manual
bus, is integrated optimally in STAR system. All functions reset, delayed emergency light
the control module of LP-STAR. such as loading, mains/ (1-15 min.), LON switch, timer
Using the optionally available emergency switch-over and function, automatic function
CG-S Bus Interface, any deep discharge protection of and duration test, selection of
LP-STAR emergency lighting devices and the connected menu language, automatic
building control systems based
power supply in a compact emergency luminaires are daylight savings time setting,
on the LONWorks® technology
design automatically inspected. Errors password protection.
can communicate with the
Low Power System according system on the CG-S bus. arising will be reported Connection for disable switch:
to EN 50171 for the power immediately. Control loop for disabling the
supply of escape luminaires and Alternatively, any OPC
compatible building control An interface provides a system during operating
exit sign luminaires 230V / 216V connection to a central downtimes with differential
AC/DC. It is suitable for system can be connected to
the optionally available OPC monitoring device. loop monitoring for short circuit
emergency lighting systems and wire breakage detection.
according to DIN VDE 0100-560, server and the Interface-Box In case of a short circuit or
EN 50172 and V DIN V VDE using the CG-S bus. interruption of control current Differential monitoring: Short
0108-100. With an automatic Thus extensive status loops, differential monitoring circuit or interruption lead to the
test device and monitoring and messages and commands can leads to the system system going into standby.
displaying the state and name be queried through the CG-S immediately switching on Connection for phase monitor:
of individual luminaires bus. (maintained light) or to the 24V current loop for emergency
connected to system-specific system being put in standby. light requirement with
The following data can thus be
EVG/LED supply module Graphical display: differential loop monitoring for
directly communicated:
including a monitoring 128 x 64 pixels, back-lit, short circuit and wire breakage
component without an • Status messages such as program-adjustable contrast detection.
additional data cable. device disabled, deep and brightness.
discharge protection, battery Differential monitoring: Short
The switching operation of each Display values: circuit or interruption lead to the
interruption, battery voltage,
escape luminaire and exit sign battery voltage, battery charge system switching on
current and temperature,
luminaire with system-specific current (+), battery charge (maintained light) immediately.
insulation error, charging unit
EVG/LED supply module or current in test mode or in case
fault, bus communication Connection for potential-free
monitoring component is of fault (–), charge fault,
error, mains failure, circuit indicator contacts, buzzer:
programmed freely in the luminaire fault with location
faults etc. 4 potential-free indicator
control module without an information in plain text, deep
• Input commands such as contacts with a separate root.
additional control cable to the discharge protection, manual
Start function test, Start and Every potential-free contact can
luminaires. reset, delayed emergency light
cancel duration test, Manual have one or more of the 11
The CEAG STAR technology (remaining time in minutes), different alerts assigned to it.
reset, Disable and release test mode, date/time, insulation
results in a severe reduction of Freely programmable, DIN VDE
system. fault, UV-AV fault, fault
end circuits, because the mixed specification retrievable at any
operation including maintained 16 virtual switching inputs can information, programming time as default setting.
light, switched maintained light be used to directly and information, test log book.
independently switch circuits or Connection for 230 V digital
and non-maintained light is LED displays:
even individual luminaires via inputs without phase monitor
implemented in a single circuit. System readiness, supply from
external LON sensors. function: 8 freely assignable
The control module assigns the the source for safety services, inputs 230V, programmable as
different operating modes Interconnection of all LP-STAR failure. inverted and non-inverted for
without any modification of the distribution boards also possible Sealed keypad: example for start/stop function
luminaire installation. The via various media such as fibre test, start/stop duration test,
operating modes: non- optic cables, Ethernet and LAN manual reset, turn on/off
maintained light or maintained using optional components.
maintained light, turn on checks the operation of the • Integrated email program for materials are recovered and
emergency lighting as connected luminaires. a convenient error notification reused for new products.
continuity lighting. • Monitoring of up to 20 via email Specifications have been
Memory card: luminaires per circuit with • Adjustable email dispatch quoted based on CEAG
Memory card for archiving the individual status display acc. to type of error or products. Specifications can be
device configuration and the • Mixed operation of function test compared based on this
mandatory inspection log book continuous lighting, switched • Up to 5 email recipients product. The tenderer can
information over a minimum of maintained light and non- programmable submit a tender based on a
4 years. maintained light within a variant solution including an
• Adjustable update cycle for equivalent product (proof by the
Storing: single circuit. (an additional web browser via the
data line to the luminaires is tenderer). Detailed product
• 360.000 inspection log book webmodule descriptions must be attached
entries not required)
• Authenticated access via to the offer for the evaluation of
• Luminaire target location • Output voltage in battery administrator account with equivalence:
texts (20 characters per operation: 220 V DC password protection
luminaire) • Typical switch-over time References 9
• Configurable guest account
• Circuit names (20 characters mains/battery: 450 ms for restricted access with CEAG Notlichtsysteme GmbH
per circuit) • freely programmable for password protection Senator-Schwartz-Ring 26
maintained light, switched D-59494 Soest/Germany
• Device name • Static or dynamic (DHCP) IP Telephone +49 (0) 2921/69-870
(20 characters) maintained light or addressing possible
maintained mode Fax +49 (0) 2921/69-617
Using The device can be • Any number of webmodules Internet www.ceag.de
programmed offline on a PC • fuses easily accessible on the operable in parallel Email [email protected]
using the optional CEAG front part of the component
• Overview of all active web- A ISO 9001 certification must
software. • permanent monitoring of modules on the Intranet with be further provided as proof.
fuses status display and hyperlink Manufacturers without the
Charging technology • automatic luminaire search function ISO 9001 certification are
The sealed maintenance-free function Supply voltage: 24V DC not permitted.
lead batteries are charged power consumption: < 1.5W
gradually based on an LONWorks®: Registered
Webmodule Connection: RJ45
microprocessor-controlled IU trademark of the Echelon
Webmodule for visualising and Housing made of polycarbonate Corporation
charging curve in function of monitoring a LP-STAR device on
temperature. Force charge is for installation on DIN rail, 2TE
the local Ethernet (LAN) or
activated in function of the Internet (WWW) with a regular Dimensions (L x W x H): 90 mm
battery charge level to ensure WEB browser. Access to the x 35 mm x 58 mm Weight: ca.
that the batteries are charged webmodule via internet 100 g Protection rating: IP20
without exceeding the gas (WWW) must be appropriately
development voltage. The administered and set up on site 24V OGiV block battery
charge monitoring procedure by a competent IT department. Only closed and non-spillable
verifies the charging process
Integrated email program for OGiV batteries are used. Rated
continuously and it reports any
convenient, event-related error operating time 1, 3 and 8 hours
faults immediately, including
notification via email, for up to 5 respectively
interruption of the battery
circuit, faulty charging unit or a email recipients. • extremely low gas emissions
high impedance battery cell. • Simple menu navigation • Period of use: 10 years at
• with ISO test device • Complete visualisation and 20°C
according to DIN VDE0100 monitoring of an LP-STAR • low self-discharge
Part 410 through the local Ethernet
• Design according to
• LED displays for charging unit (LAN) with a regular WEB
IEC60896-21/-22
on, boost charge on, browser
insulation fault, charge fault, • electrolyte and air oxygen
• Retrieving and indicating all
mains available sealed terminals
current operating states
• potential-free contacts charge CEAG is a member of the
• Localised fault indicators for
fault, boost charge, insulation “Stiftung Gemeinsames
every emergency luminaire
fault Rücknahmesystem Batterien
circuit and luminaires with
[joint battery recycling
• Temperature sensor built into target location information
programme] (GRS)“.
the battery compartment in plain text connected to a
function test In this manner batteries
undergo a controlled and
Circuit components • Continuous up-to-date
complete recycling cycle. This
The circuit switch-over supplies information on charging
means that possible polluting
and monitors emergency device and battery
luminaires with electronic • Parallel access from various
ballasts for DC operation. The PC workstations to a web-
CEWA GUARD monitoring module possible (max. 8)
Loadstar
System Design - Loadstar..................................................................................................................... 410
Loadstar AC/AC Systems...................................................................................................................... 418
Compact AC/AC.................................................................................................................................... 426
Easicheck
EasiCheck 1.5 Slave.............................................................................................................................. 431
EasiCheck EC125.................................................................................................................................. 431
EasiCheck EC140 – Module with control input.................................................................................... 431
EasiCheck EC141 – Monitoring module with control input.................................................................. 431
ACM1 - Changeover module................................................................................................................. 431
EasiCheck 1.5 Slave..............................................................................................................................432
10
EasiCheck EC125..................................................................................................................................434
EasiCheck EC140 – Module with control input....................................................................................436
EasiCheck EC141 – Monitoring module with control input..................................................................437
ACM1 - Changeover module.................................................................................................................439
AT-S+
Automatic Test System AT-S+ with STAR+ Technology......................................................................440
Features................................................................................................................................................443
What is STAR+?.....................................................................................................................................444
Easy planning........................................................................................................................................445
Strong in detail......................................................................................................................................446
Distribution box SU1 and SOU1............................................................................................................448
Distribution box ESF30 SU2 and ESF30 SOU2....................................................................................449
Substations with functional integrity of 30 minutes.............................................................................450
Across fire compartments-specific installation example.....................................................................452
Components and options...................................................................................................................... 453
Technical data........................................................................................................................................464
Installation example..............................................................................................................................468
Specifications........................................................................................................................................ 470
Technical drawings................................................................................................................................ 472
10.1 Loadstar
• •
10
10.2 Easicheck
•1*
10.3 AT-S+
•2*
monitoring in AC
Single luminaire
single luminaire
operation (DC)
operation
CEWA GUARD STAR Technology STAR+ Technology EasiCheack (EC) AE-CU
Circuit Monitoring
Technology (CG) (S) (S+) Technology Technology
10
•1*
• • •
1* Optional luminaire test system for Loadstar
2* Luminaire test and controll system for
external AC safety power supply systems
10
Central battery system based emergency lighting is ideal for Eaton manufactures a wide range of central battery emergency
medium to large installations. For projects where central control lighting systems. Standard products include AC/AC static inverter
and testing is desirable, a central battery system is a viable and systems, with the addition of a new compact, competitively priced
cost effective alternative to self-contained emergency lighting unit for smaller installations. Bespoke systems to suit the exact
products. The main advantages of central battery systems over requirements of the specifier are also available.
self-contained systems are:
To complement the range of central battery systems, Eaton also
offers a wide selection of slave luminaires and conversion modules
• Testing and maintenance is much easier to carry out
for mains fluorescent and LED luminaires. EasiCheck automatic
• Battery replacement is much quicker and less disruptive
self-testing can be readily incorporated into central systems.
• Battery life is generally 10 years or more
• Luminaires can be centrally controlled
• High light levels can easily be achieved
• The emergency lighting system can be completely unobtrusive
Emergency
Lighting
distribution
Board
data loop
Neutral
Live IN
EC125
Live OUT
SAVEL Ballast
410 EATON - EMERGENCY LIGHTING CPS – Global Catalogue 2020
Interface
Central Battery Systems AC/AC
System Design - Loadstar
Normal mains healthy condition Failure of normal lighting final circuit Total mains failure
KEY
- LIVE
- DEAD
Normal mains healthy condition Failure of normal lighting final circuit Total mains failure
10
KEY
- LIVE
- DEAD
Normal mains healthy condition Failure of normal lighting final circuit Total mains failure
KEY
- LIVE
- DEAD
Normal mains healthy condition Failure of normal lighting final circuit Total mains failure
10
OR
KEY
- LIVE
- DEAD
Battery Type
Eaton offers a choice of five different battery types: Each battery type has specific characteristics. The table below (fig.
• Valve regulated lead acid (10 year design life) 2) provides a comparative guide to these characteristics.
• Valve regulated lead acid (3-5 year design life) The most popular battery type is valve regulated lead acid with a
• Vented nickel-cadmium 10 year design life. This type of battery is used on approximately
90% of projects due to its competitive cost, good life
• High performance plante lead acid characteristics, ease of maintenance and compact size.
• Flat plate lead acid
Valve Regulated Lead Valve Regulated Lead Vented Nickel High Performance Flat Plate
Characteristics Acid (10 year life) Acid (3-5 year life) Cadmium Plante Lead Acid Lead Acid
Expected life √√√ √ √√√ √√√ √
Capital cost √√ √√√ √ √ √
10 Maintenance √√√ √√√ √√ √√ √√
Resistance to damage and abuse √ √ √ √ √
Through life costs √√ √ √√ √√ √√
A = 0.045 x N x I
V
Where:
N = Number of cells in the battery
V = Volume of room in cubic metres
I = Charge rate in Amperes
This formula will give the number of air changes per hour required
during boost charge conditions. On float charge (systems are
on float charge for most of their service life), the amount of gas
emitted is approximately 1.5% of that liberated whilst on boost
charge and under most circumstances this will be dissipated by
natural ventilation, and will not present a hazard. However, we
recommend that the boost charge condition is allowed for at the
design stage to ensure the appropriate decision on ventilation
requirements is made.
Although Valve Regulated Lead-Acid Batteries require little
ventilation under normal operating conditions, it is good practice to
apply the formula to calculate the number of air changes required
to achieve minimum risk under battery fault or failure conditions.
Please refer to: EN IEC 62485-2: 2018.
Installation Notes
• Warning notices should be displayed on entry doors to battery
rooms: BATTERY ROOM. EXTINGUISH ALL NAKED LIGHTS
BEFORE ENTERING. NO SMOKING
System Sizing considered in addition to lamp wattage and control gear losses.
When sizing the system, it is important to allow for the full input High frequency control gear circuits have excellent PFC ratings,
requirement of the light fittings rather than the lamp wattages. usually of around 0.96 to 0.98. This compares with 0.85 to 0.9 for
equivalent lamp magnetic control gear circuits. Care should be
taken when low wattage compact fluorescent lamps are used,
AC/AC systems utilising high frequency gear or high PFC versions where possible.
When utilising a static inverter system, the fitting operates at full Low power factor versions can have PFC ratings of only 0.45 to
output during both mains healthy and mains failure conditions. 0.5, thereby greatly increasing the inverter rating required for the
When sizing a suitable static inverter to power a particular load, system. If utilising low voltage lighting powered via step-down
it is important to consider the input VA and the input (not lamp) transformers, it is essential to allow for the efficiency and power
wattage of the emergency luminaires. The total VA requirement factor of the step-down transformers. Table (fig. 3) and graph (fig.
defines the inverter module size, and the total input wattage 4) illustrate the relationship between wattage and VA rating for a
defines the battery size. typical system.
Therefore, to establish the correct inverter module size, the Note: EN 60598-2-22 prohibits the use of glow starters in
power factor correction (PFC) rating of the luminaires must be fluorescent luminaires used for emergency lighting.
10
Fig 3. Typical system. VA rating with and without power factor correction
Qty of VA Rating (Compact lamps VA Rating (Compact
Luminaires Description Total Circuit Watts without PFC) lamps with PFC)
25 1 x 58W T8 (wire wound ballasts) 1725 1925 1925
40 1 x 28W 2D (wire wound ballasts) 1360 2960 1560
15 1 x 16W 2D (wire wound ballasts) 315 690 375
15 1 x 13W TC-D (wire wound ballasts) 270 600 315
5 1 x 40W GLS incandescent 200 200 200
Inverter Rating = 3870 6375 4375
Note: Use of compact fluorescent luminaires with power factor correction (PFC) leads to a reduced inverter module size and therefore savings in
space and capital costs
Fig 4. Typical system. VA rating with and without power factor correction
Additional Considerations
Spare capacity
With any central battery system it is important to bear in mind that
it is difficult to extend the system at a later date unless capacity
has been allowed for at the design stage. For this reason, we
would strongly recommend that some spare capacity is included
when selecting the central battery system rating. Our technical
department is available to provide assistance.
VDT = I x VDM x D
The problems of volt drop can be overcome by:
Where: • Using higher system voltages (= lower currents and therefore lower
10 VDT = volts drop total volt drop)
I = maximum load current • Using larger cables (= lower resistance and therefore lower volt drop)
VDM = volts drop per ampere per metre (obtained from fig. 5)
• Using multiple outgoing circuits (= less current per circuit and
D = cable run in metres therefore lower volt drop)
Example:
Fig. 6 and 7 show an example comparison for a central battery
system with a total connected load of 1500W and a 50m run of
16mm2 cable supplying the luminaires.
This example shows that for this configuration, a 230 V system
would be most suitable to meet the requirements of max. 4 %
voltage drop. The low current value combined with greater
allowable volt drop would enable much smaller cables to be used.
Fig 6. Fig 7.
The use of larger cables or multiple outgoing circuits may permit the
use of 24, 50 or 110V systems in the above example.
Additional Considerations
Fire protection of cables
Cables should be routed through areas of low fire risk.
The following cables and wiring systems should be used.
a) Cables with inherently high resistance to attack by fire
b) Wiring systems with additional fire protection.
Systems should be installed in accordance to the national
Regulations. Additional fire protection may apply. For example, if
cables are buried in the structure of the building.
Loadstar
The Loadstar range of AC/AC static inverter units offer the opportunity to create a discreet emergency
lighting system, utilising suitable standard mains luminaires without modification. Small or decorative
compact luminaires can also be easily incorporated. Loadstar AC/AC systems offer many benefits,
including higher light levels in emergency mode, as all lamps in the luminaire are usually energised by
the emergency supply. Mains voltage and lower currents enable cables of smaller cross sectional area
to be used with low voltage AC/DC systems, without unacceptable levels of voltage drop. The proven
and reliable modular design ensures a cost effective emergency lighting.
Dimensions
System Standard
Operation Specification
• In mains healthy condition, the system charges the batteries • Cubicles
and stores power, ready for emergency operation - 1.6mm zinc coated steel panels with powder coat RAL7032 light
• In mains healthy condition, the power to luminaires designated pebble grey finish
for emergency use is supplied from the normal mains, via a by- - Plinth base feature to prevent build up of moisture/corrosive
pass contactor inside the cubicle. This may be switched, using materials and aid mechanical handling by fork or pallet truck
a “maintained lights” switch (optional extra) or by use of a
- 3 standard size cubicles, for combined charger/inverter/battery,
remote switch connected to terminals provided
charger/inverter only or battery only
• Local change-over switching can be achieved using an ACM1
- Small systems require only one cubicle. Larger systems housed
module, controlling single or multiple luminaires (if fed from
in multiple sets (see selection tables)
common switched mains supply - max load 750VA). The system
10 will then supply normal mains power or emergency power via - Electrical control gear and battery compartments are segregated,
the inverter, dependant on status of mains supply at the static with lockable access door(s)
inverter - Battery compartments supplied, where appropriate with separate
• In the event of a mains failure, the system provides emergency tiered sections, to enable ease of electrolyte level inspection
power to dedicated mains slave or designated standard mains - Separate fixed facia panel for mounting control/display panel
luminaires, until mains power is restored (or for the rated - Option of open battery racks on larger systems
duration of the system in the event of extended mains failure)
• Output voltage, from the system via the inverter, is 230V AC
nominal • Battery Charger
• Standard mains luminaires require no modification to operate - Solid state, constant voltage charge control module
with the static inverter (unless ACM1 change-over module is - Fully automatic
fitted integrally). All lamps in multi-lamp luminaires will be lit - Full recharge within 24 hours of a rated discharge
during mains failure, unless separate control gear is provided for
- Recharge to 80% capacity within 12 hours, complying with EN
individual lamps
50171
• Sub-circuit monitoring and hold off relays can be added to the
- Manual boost switch on systems with vented battery cells
system to energise the emergency luminaires in the event of a
localised mains circuit failure, if the ACM1 module is not used - Current limit facility, preventing overcharging or damage to the
system in the event of battery failure or fault
- Outputs have low AC ripple currents for maximum battery life and
in compliance with EN 50171
- Input protection by MCB to BS 3871 Part 1 or BS 4752 Part 1
Energy Efficient Standby Operation
The Loadstar range of AC/AC static inverter systems are designed
• Battery
specifically for long term sustainability, reduced carbon footprint
and reduced running cost without compromising on the products - Systems can be specified with:
performance criteria. Due to the passive stand-by operation of • Valve regulated lead acid
the inverter only operating when required, the quiescent running • Vented nickel cadmium
power is minimised while maximising equipment lifetime and
reduced running cost. • High performance plante
- See selection tables/guides for battery characteristics
• Fusegear
- Removable industrial HRC fuses
• Input Circuits
- Cable entry via removable gland plate on top of cubicle
-Single phase 230V ± 10% AC 50Hz supply. Other input voltages
on request
- Input terminals and MCB DIN-rail mounted and easily accessible
• Load Circuits
- Substantial DIN rail mounted output terminals
- Option of integral distribution board (MCB or HRC fuses)
• Inverter
- Extensively proven and reliable modular design
- Systems with ratings up to 4 kVA incorporate a single module
rated at 1.25 kVA, 2.5 kVA or 4 kVA
- Larger systems utilise multiple modules in parallel to provide a
single common output, equal to sum of individual ratings
- Complies fully with EN50171
- Modules can be quickly and easily removed/replaced, aiding
installation and maintenance
- See table for detailed technical specification
• Frequency
- 50 Hz +/- 0.01% (60 Hz option)
Inverter Inverter
• To ensure a suitably rated system is selected, list the luminaires to be used, with their
characteristics, to determine the wattage and VA power rating of the required inverter
• Where possible, utilise luminaires with high frequency control gear, compact fluorescent luminaires
with high power factor correction, or dedicated 230V AC mains slave luminaires, to minimise the
required VA rating of the inverter
• Using uncorrected compact fluorescent luminaires with poor power factor, will increase the size of
inverter module required, leading to increased capital cost and space requirements
• For details of static inverter systems with ratings above those listed, please contact our central
systems technical sales department
• It should be noted that multiple smaller units can often be more cost effective than a single large
system. Distribution costs can be substantially reduced by locating units throughout a large building
• Note - systems specified for emergency lighting use should not have other services connected to
them
L1
L2
L3
L4
N
S1019
N
N
L
L
N/0
N/0
COM
COM
LOOP OUT
LOOP IN
LOOP OUT
LOOP IN
TO NEXT MONITOR
OR CENTRAL BATTERY
SYSTEM
SCM and HOR units are designed to accept a single common neutral per enclosure, all monitored circuits connected to an individual unit must
share a common neutral.
Ordering details
Type: Number of ways monitored Order No. of Sub Circuit Monitor Order No. of Hold Off Relay Monitor
4 1SCM4 1HOR4
8 1SCM8 1HOR8
12 1SCM12 1HOR12
AC26KVA/22100/SLR*/ 26 22100 934FC + 934I + 2 x 932B3 934FC + 934I + 2 x 934FC + 934I + 2 x 934B3
TPN4W 934B3 + 2 x 932B3
AC28KVA/23800/SLR*/ 28 23800 934FC + 934I + 934B3 + 934FC + 934I + 2 x 934FC + 934I + 3 x 934B3
TPN4W 932B1 934B3 + 932B3
AC30KVA/25500/SLR*/ 30 25500 934FC + 934I + 2 x 932B3 934FC + 934I + 2 x 934FC + 934I + 4 x 934B3
TPN4W 934B3 + 932B2
AC32KVA/27200/SLR*/ 32 27200 934FC + 934I + 934B3 + 934FC + 934I + 2 x 934FC + 934I + 4 x 934B3
TPN4W 932B3 934B3 + 932B2
AC34KVA/28900/SLR*/ 34 28900 934FC + 934I + 934B3 + 934FC + 934I + 2 x 934FC + 934I + 4 x 934B3
TPN4W 932B3 934B3 + 932B3 + 934B1
AC36KVA/30600/SLR*/ 36 30600 934FC + 934I + 934B3 + 934FC + 934I + 2 x 934FC + 934I + 4 x 934B3
TPN4W 932B3 934B3 + 932B3 + 934B1
AC38KVA/32300/SLR*/ 38 32300 934FC + 2 x 932I + 934B3 + 934FC + 2 x 932I + 3 x 934FC + 2 x 932I + 4 x
TPN4W 932B3 934B3 934B3 + 934B1
10
AC40KVA/34000/SLR*/ 40 34000 934FC + 2 x 932I + 2 x 934FC + 2 x 932I + 3 x 934FC + 2 x 932I + 5 x
TPN4W 934B3 934B3 934B3
AC42KVA/35700/SLR*/ 42 35700 934FC + 2 x 932I + 3 x 934FC + 2 x 932I + 4 x 934FC + 2 x 932I + 3 x
TPN4W 932B3 934B3 934B3 + 3 x 932B3
AC44KVA/37400/SLR*/ 44 37400 934FC + 2 x 932I + 3 x 934FC + 2 x 932I + 4 x 934FC + 2 x 932I + 5 x
TPN4W 932B3 934B3 934B3
AC46KVA/39100/SLR*/ 46 39100 934FC + 2 x 932I + 3 x 934FC + 2 x 932I + 4 x 934FC + 2 x 932I + 3 x
TPN4W 932B3 934B3 + 934B1 934B3 + 3 x 932B3
AC48KVA/40800/SLR*/ 48 40800 934FC + 2 x 932I + 2 x 934FC + 2 x 932I + 4 x 934FC + 2 x 932I + 6 x
TPN4W 934B3 + 932B3 934B3 + 934B1 934B3
AC50KVA/42500/SLR*/ 50 42500 934FC + 934I + 932I + 2 x 934FC + 934I + 932I + 4 934FC + 934I + 932I + 6 x
TPN4W 934B3 + 932B3 x 934B3 + 934B1 934B3
AC52KVA/44200/SLR*/ 52 44200 934FC + 934I + 932I + 2 x 934FC + 934I + 932I + 4 934FC + 934I + 932I + 4 x
TPN4W 934B3 + 932B3 x 934B3 + 934B1 934B3 + 4 x 932B3
AC54KVA/45900/SLR*/ 54 45900 934FC + 934I + 932I + 2 x 934FC + 934I + 932I + 4 934FC + 934I + 932I + 4 x
TPN4W 934B3 + 932B2 x 934B3 + 934B1 934B3 + 4 x 932B3
AC56KVA/47600/SLR*/ 56 47600 934FC + 934I + 932I + 2 x 934FC + 934I + 932I + 5 934FC + 934I + 932I + 4 x
TPN4W 934B3 + 932B2 x 934B3 934B3 + 4 x 932B3
AC58KVA/49300/SLR*/ 58 49300 934FC + 934I + 932I + 2 x 934FC + 934I + 932I + 4 934FC + 934I + 932I + 4 x
TPN4W 934B3 + 932B2 x 934B3 + 934B1 934B3 + 4 x 932B3
AC60KVA/51000/SLR*/ 60 51000 934FC + 934I + 932I + 2 x 934FC + 934I + 932I + 4 934FC + 934I + 932I + 4 x
TPN4W 934B3 + 932B3 x 934B3 + 934B1 934B3 + 4 x 932B3
AC/NC Range
AC/HP Range
System Reference Inverter Power Rating (kVA) Inverter Wattage
AC/HP Series 1.0 - 25.0 500 - 21250
Compact AC/AC
10
Compact AC/AC
• 500 VA or 600 VA static inverter system
• Compact - ideal for smaller installations
• Fully complies with EN 50171
• Four separately fused outputs
• Digital display to clearly indicate system status
• EasiCheck compatible version available
Dimensions in mm Inverter
Output voltage Pre-settable in the range 220-240V AC. Default setting is 230V AC. Voltage
tolerance is 2% on loads of 0-100% of system rating
Frequency 50Hz. ±0.1%. Waveform: Sinusoidal
Voltage regulation Static 2%, dynamic 6%
Isolation 1kv rms between input and output terminals
Total harmonic distortion Typically 3% or better. Max. 10%
Power factor Will supply loads in the 0.7 lag - 0.7 lead range
Overload 200% for 10 seconds, 125% for 20 minutes without reduction in output voltage
Start-up time Standard 300mS. Soft start
10 Noise level Effectively silent on both charge and discharge
Efficiency 83% nominal. Typically 82-85%
H x W x D: 970 x 530 x 400 Protection DC input protection. AC output fuses
DC input reverse polarity protection
Short circuit protection
Pre-charge protection fuse
Low voltage shut down Inverter module automatically shuts down when battery discharges to a pre-set
level. Re-set is automatic following the restoration of the mains supply
Inhibit An inhibit switch to control the inverter is fitted on the main PCB in the cubicle
Technology Pulse width modulation with high frequency switching
Ordering details
Type Inverter Output Order No. of Hold Off
Rating (VA) Relay Monitor
Easicheck
EasiCheck 1.5 Slave.............................................................................................................................. 431
EasiCheck EC125.................................................................................................................................. 431
EasiCheck EC140 – Module with control input.................................................................................... 431
EasiCheck EC141 – Monitoring module with control input.................................................................. 431
ACM1 - Changeover module................................................................................................................. 431
EasiCheck 1.5 Slave..............................................................................................................................432
EasiCheck EC125..................................................................................................................................434
EasiCheck EC140 – Module with control input....................................................................................436
EasiCheck EC141 – Monitoring module with control input..................................................................437
ACM1 - Changeover module.................................................................................................................439
10
10
Dimensions An EasiCheck interface module is fitted into all suitable dedicated emergency luminaires and mains
D2
luminaires converted for emergency operation.
W
• Each module shall be addressed using a hand held programmer during installation with a unique
address number in the range
0-250
• Every luminaire is connected to a 2 core data BUS cable in a loop configuration, which is linked back
to the control panel. A single panel can accommodate up to 250 luminaires
H
• It is important to maintain accurate ‘as fitted’ drawings to identify the respective luminaire and its
assigned address/location
• Text information can be allocated to each system component
• The panel can then be programmed to carry out automatic test sequences according to EN 50172
or any regional testing regime. Testing can also be initiated manually. All test data is sent back and
stored at the control panel. Additionally, the system carries out continuous real time monitoring of all
D1 connected devices
H: 375 mm
• In the event of a fault, the precise location of the device is displayed at the control panel along with
W: 357 mm accurate details of the nature of the fault, time/date stamp and an alarm is raised
D1: 50 mm
• The system can be enhanced by networking up to 63 panels. Central PC monitoring can also be
D2: 45 mm incorporated
Ordering details
Type Order No.
Ordering details
Scope of supply Order No.
Emergency
Lighting
distribution
Board
data loop
Loop OUT
Loop IN
Neutral
Live IN
EC125
Live OUT
SAVEL Ballast
Interface
Mains
Lighting To Mains
distribution Lighting
Board Circuits
Emergency
Lighting
distribution
Board
data loop
Non-maintained emergency
EC125 SAVEL Interface luminaires operating only when power
mounted within luminaire failure or emergency test initiated
Loop OUT
Loop IN
Neutral
Live IN
EC125
Live OUT
SAVEL Ballast
Interface