HSCB 6000A Breaker

The document provides specifications for high speed DC switchgear ratings, including: 1. It lists the nominal voltage as 750V DC, rated voltage as 900V DC, and maximum operational voltage as 1000V DC. 2. The rated continuous current at 40°C is listed for various components between 4000A and 6000A. 3. The switchgear has an inherent tripping time of opening within 40ms and total break time within 20ms, and a mechanical life time of over 20,000 cycles.

Uploaded by

rajesh kannan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
68 views

HSCB 6000A Breaker

The document provides specifications for high speed DC switchgear ratings, including: 1. It lists the nominal voltage as 750V DC, rated voltage as 900V DC, and maximum operational voltage as 1000V DC. 2. The rated continuous current at 40°C is listed for various components between 4000A and 6000A. 3. The switchgear has an inherent tripping time of opening within 40ms and total break time within 20ms, and a mechanical life time of over 20,000 cycles.

Uploaded by

rajesh kannan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Tender No.

ELP_46R_NOA_BB_Dt12-01-21

Table 2.5.1. : DC High Speed Switchgear Rating

SN Description High Speed DC Switchgear Rating


Indoor horizontal type suitable for floor /
1 Type pedestal mounting

2 Voltage

a. Nominal voltage (Un) 750 V DC

b. Rated Voltage (Une) 900 V DC

c. Maximum Operational Voltage 1000V DC

c. Rated insulation voltage (Unm) 1800 V DC


d. 10 kV to earth and between phases
Rated Impulse Voltage 12 kV -across the isolating distance, if
applicable
e.
Power frequency withstand voltage 4.6 kV -to earth and between phase
rms 50 Hz 1 min to earth and 5.5 kV -across the isolating distance, if
between phases applicable
Rated continuous current at
3 temperature +40 °C
a.
Incomer Feeder 6000 A
Line Feeder 4600 A
Bypass 4600 A
Bridging HSCB 4600 A

b. Busbar Rating 10000A (as per IEC 61992 part I, table 7).
4 Inherent tripping time Opening time not more than 40 ms and
total break time not more than 20 ms
5 Mechanical life time More than 20000 cycle
6 Short circuit rating 125 kA for 100 ms
IP 41
7 Degree of protection
8 Class H
9300 A for 1 min.
Short time current (+40 °C) for 1
9 min. ( For 4600 A Breaker) 7200 A for 5 min
14500 A for 10 sec.
15000 A for 1 min.
10 Short time current (+40 °C) for 1
min. ( For 6000 A Breaker) 12500 A for 5 min
18000 A for 10 sec.
11 Breaking and Making capacity According to ANSI C37-14/ IEC 61992-2, Ip-
200 kA & Is = 120 kA
12 Current interruption Bi-directional.
13 Mechanical endurance 20000 operating cycle.

Page 74 of 356