This series UPS is an intelligent, single phase in single phase out, high frequency online
UPS designed by our R&D team who is with years of designing experiences on UPS.
With excellent electrical performance, perfect intelligent monitoring and network functions,
smart appearance, complying with EMC and safety standards, The UPS meets the
world’s advanced level.
Read this manual carefully before installation
This manual provides technical support to the operator of the equipment.
Table of Contents
1. Important Safety Warning ..................................................................................................................... 2
1-1 Transportation .............................................................................................................................. 2
1-2 Preparation .................................................................................................................................... 2
1-3 Installation ..................................................................................................................................... 2
1-4 Operation ....................................................................................................................................... 3
1-5 Maintenance, service and faults .............................................................................................. 3
1-6 Symbols used in this guide ...................................................................................................... 3
2. Installation and setup ............................................................................................................................. 4
2-1 Unpack checking ......................................................................................................................... 4
2-2 Real panel view ............................................................................................................................ 4
2-3 LCD control panel........................................................................................................................ 6
2-4 Setup the UPS .............................................................................................................................. 6
3. Operations ................................................................................................................................................. 7
3-1 Button operation .......................................................................................................................... 7
3-2 LCD display ................................................................................................................................... 8
3-3 UPS setting ................................................................................................................................. 11
3-4 Operating Mode Description .................................................................................................. 13
3-5 Operational Status and Mode(s) ............................................................................................ 14
3-6 Alarm or Fault reference code ............................................................................................... 14
4. Troubleshooting..................................................................................................................................... 15
5. Storage and Maintenance.................................................................................................................... 15
6. Options ..................................................................................................................................................... 16
7. Specification ........................................................................................................................................... 18
1
1. Important Safety Warning
Important safety instructions – Save these instructions
Please comply with all warnings and operating instructions in this manual strictly. Save
this manual properly and read carefully the following instructions before installing the unit.
Do not operate this unit before reading through all safety information and operating
instructions carefully
There exists dangerous voltage and high temperature inside the UPS. During the
installation, operation and maintenance, please abide the local safety instructions and
relative laws, otherwise it will result in personnel injury or equipment damage. Safety
instructions in this manual act as a supplementary for the local safety instructions. Our
company will not assume the liability that caused by disobeyingsafety instructions.
1-1 Transportation
Please transport the UPS system only in the original package to protect against
shock and impact.
1-2 Preparation
Condensation may occur if the UPS system is moved directly from cold to warm
environment. The UPS system must be absolutely dry before being installed. Please
allow at least two hours for the UPS system to acclimate the environment.
Do not install the UPS system near water or in moist environments.
Do not install the UPS system where it would be exposed to direct sunlight or near
heater.
Do not block ventilation holes in the UPS housing.
1-3 Installation
Do not connect appliances or devices which would overload the UPS system (e.g.
laser printers) to the UPS output sockets.
Place cables in such a way that no one can step on or trip over them.
Do not connect domestic appliances such as hair dryers to UPS output sockets.
The UPS can be operated by any individuals with no previous experience.
Connect the UPS system only to an earthed shockproof outlet which must be easily
accessible and close to the UPS system.
Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your
computer) to connect the UPS system to the building wiring outlet (shockproof outlet).
Please use only VDE-tested, CE-marked power cables to connect the loads to the
UPS system.
When installing the equipment, it should ensure that the sum of the leakage current of
the UPS and the connected devices does not exceed 3.5mA.
2
1-4 Operation
Do not disconnect the mains cable on the UPS system or the building wiring outlet
(shockproof socket outlet) during operations since this would cancel the protective
earthing of the UPS system and of all connected loads.
The UPS system features its own, internal current source (batteries). The UPS output
sockets or output terminals block may be electrically live even if the UPS system is
not connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the OFF/Enter button to
disconnect the mains.
Prevent no fluids or other foreign objects from inside of the UPS system.
CAUTION!
Read this information to avoid equipment damage
3
2. Installation and setup
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the
package is damaged. Please keep the original package in a safe place for future use.
1KVA(H):
2KVA(S):
4
2KVA(H)/3KVA(H)
2KVA(S)-6batt /3KVA(S):
1. AC input
2. Network /Fax/Modem Surge Protection(option)
3. Input circuit breaker
4. EPO(option)
5. USB communication port(option)
6. RS-232 communication port
7. SNMP intelligent slot (option)
8. Output receptacles
9. Battery Terminal
10. Output Terminal
5
2-3 LCD control panel
To allow for unattended UPS shutdown/start-up and status monitoring, connect the
communication cable one end to the USB/RS-232 port and the other to the
communication port of your PC. With the monitoring software installed, you can
schedule UPS shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or Relay card. When
installing either SNMP or Relay card in the UPS, it will provide advanced
communication and monitoring options.
NOTE: USB port and RS-232 port can’t work at the same time.
6
Step 4: Turn on the UPS
Press the ON button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation. Do not
expect full battery run capability during this initial charge period.
Step 5: Install software
For optimal computer system protection, install UPS monitoring software to fully
configure UPS shutdown. You may insert provided CD into CD-ROM to install the
monitoring software.
Step 6: External battery connection
If your UPS is not including batteries. Please connect external batteries as below
chart.
3. Operations
3-1 Button operation
Button Function
Turn on the UPS: Press and hold ON button for at least
2 seconds to turn on the UPS.
Down key: Press this button to display next selection in
ON Button UPS setting mode.
Exit setting mode:Press this button to confirm seletion
and exit setting mode when LCD display the last
selection in UPS setting mode.
Turn off the UPS: Press and hold this button at least 2
seconds to turn off the UPS in battery mode. UPS will
be in standby mode under power normal or transfer to
Bypass mode if the Bypass enable setting by pressing
this button.
Switch to bypass mode: When the main power is
OFF Button
normal, press and hold this button for 2 seconds. Then
UPS will enter to bypass mode. This action will be
ineffective when the input voltage is out of acceptable
range.
Up key: Press this button to display previous selection
in UPS setting mode.
7
Switch LCD message: Press this button to change the
LCD message for input voltage, input frequency, battery
voltage, output voltage and output frequency etc.
Mute the alarm: When the UPS is on battery mode,
FUNC/Mute press and hold this button for at least 2 seconds to
Button disable or enable the alarm system. But it’s not applied
to the situations when warnings or errors occur.
Switch to UPS self-test mode: Press and hold this
button for 2 seconds to enter UPS self-testing while in
AC mode.
OFF + FUNC Setting mode: Press and hold this button for 5 seconds
Button to enter UPS setting mode.
01 Input voltage
02 Battery voltage
8
03 Output voltage
04 Load
Temperature
(EnvironmentTemperatu
05
re)
9
CODE
07 (Operational status and
mode)
Alarm Code(Warming
Message)
08 All alarm codes are
present when abnormal
behavior(s) occur(s)
Cc MODE
09
Cv MODE
10
3-3 UPS setting
The setting fuction is controled by 3 buttons (Func,Off/up ▲, On/down▼): Func +Off/up
▲---goes into the setting page, Func --- value adjustment; Off ▲ & On ▼---for choosing
different pages.
After the UPS turn ON, press buttons Func & ▲ for 5seconds and then goes into the
setting interface page.
Note: Figure at left corner is the page number of the setting pages.
Frequency setting
11
Battery capacity setting
12
Mute setting
Press Func button to change
thesetting(ON or OFF).
Press UP button ▲ to select the
previous setting.
08
Press DOWN ▼ button to save and
exit the setup.
Online mode When the input voltage is within Inverter led light
acceptable range, UPS will provide
pure and stable AC power to output.
The UPS will also charge the battery
at online mode.
ECO mode Energy saving mode: Bypass led light
When the input voltage is within
voltage regulation range, UPS will
bypass voltage to output for energy
saving.
Battery mode When the input voltage is beyond the Battery led light
acceptable range or power failure and
alarm is sounding every 4 second,
UPS will backup power from battery.
Standby mode UPS is powered off and no output All LEDs turn off
supply power, but still can charge
batteries.
Bypass mode When input voltage is within Bypass led light
acceptable range but UPS is overload,
UPS will enter bypass mode or
bypass mode can be set by front
panel.
13
3-5 Operational Status and Mode(s)
item Content Displayed
2 Standby Mode
3 No Output
4 Bypass Mode
5 Utility Mode
6 Battery Mode
7 Battery Self-diagnostics
8 Inverter is starting up
9 ECO Mode
10 EPO Mode
11 Maintenance Bypass Mode
12 Fault Mode
Alarm code is shown as “34” Battery voltage is too low or Contact your dealer.
and battery led blinking the charger is fault.
Alarm code is shown as A UPS internal fault has Contact your dealer.
“01,02, 15,16,17,18” occurred.
Charge the batteries for at
Batteries are not fully least 5 hours and then check
Battery backup time is charged capacity. If the problem still
shorter than nominal value persists, consult your dealer.
Contact your dealer to
Batteries defect
replace the battery.
6. Options
SNMP card: internal SNMP
◆Loosen the 2 torquescrews (on each side of thecard).
◆Carefully insert the SNMP card and lock the screws
The slot called SNMP supports the MEGAtec protocol.We advise that Net AgentII-3
port is also a tool to remotely monitorand manage any UPS system
Relaycard
Mini dry contact card is used foproviding the interface for UPS peripheral monitoring.
The contact signals canreflect UPS running status.The card is connected to peripheral
monitoring devices via terminal board to facilitate the effective monitoring of the
real-timestatus of UPS and timely feedback the statusto monitor when abnormal situation
occurs(suchas UPS failure, mains interruption,UPS bypassand ect.). It is installed in the
intelligent slotof the UPS.
The relay card includes 6 output ports and one input port.Please refer to thefollowing table
for detail.
16
Pins definition of connecting terminal on the board
Line Mode
(synchroni 47-53Hz or 57-63Hz
Frequency zed range)
19