VG+ Series 2 Software 14911
VG+ Series 2 Software 14911
All rights reserved. This notice applies to all copyrighted materials included with this product,
including, but not limited to, this manual and software embodied within the product. This manual is
intended for the sole use of the persons to whom it was provided, and any unauthorized distribution
of the manual or dispersal of its contents is strictly forbidden. This manual may not be reproduced in
whole or in part by any means whatsoever without the expressed written permission of
ELECTROMOTIVE SYSTEMS by MagneTek.
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result in
death or serious injury. This signal word is to be limited to the most extreme situations.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, could result in
death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, could result in
minor or moderate injury. It may also be used to alert against unsafe practices.
WARNING
Chapter 1: Introduction
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Assessing the System Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Assessing the Drive Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Chapter 2: Installation
IMPULSE•VG+ Series 2 System Components And External Devices . . . . . . . . . . . . . . . . . 2-4
Long Time Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Chapter 3: Wiring
IMPULSE•VG+ Series 2 Wiring Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
IMPULSE•VG+ Series 2 Standard Connection Diagram . . . . . . . . . . . . . . . . . . . . . . . 3-5
Suggested Circuit Protection Specifications and Wire Size . . . . . . . . . . . . . . . . . . . . . 3-6
Power Circuit Wiring Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Auto-Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-15
Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-55
DC Injection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-55
Automatic Slip Compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-57
Automatic Speed Regulator (ASR) Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-57
Torque Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-58
Speed/Torque Control Switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-60
Droop Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-61
Dwell Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-62
S-Curve Acceleration/Deceleration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-63
Carrier Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-65
Factory Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-66
Here’s a sample of IMPULSE•VG+ Series 2’s special features and how they can help you improve
your overhead material handling performance:
• Distinct speed control (up to nine speeds) as well as infinitely variable speed control are
provided; you can use pendant pushbutton stations, infrared or radio controls, or joysticks.
• An English, plain-language liquid crystal display (2 lines, 16 characters per line) makes
programming, troubleshooting, and operating the drive easy.
• Built-in Serial Communication (9600-baud modbus) provides reliable digital linkage among the
various crane system peripherals, including our line of PulseStar™ Remote Crane Controls.
• Micro-Positioning Control™ is used to place loads with a high degree of precision, eliminating
the need to jog or plug your motors.
• A compact circuit design gives the drive a small footprint.
• Ultra-Lift™ capabilities enhance productivity by allowing the overspeeding of any load less than
full load.
• Safe Operating Windows™ prevents you from programming the drive with unsafe parameters.
• Automatic Keypad Lockout™ and a snap-in, removable keypad helps you limit programming
access and reduce the possibility of programming errors.
• Load Check™ prevents you from overstressing equipment by attempting to lift a load beyond
the capacity of the crane or hoist.
• Weight Measurement enables you to weigh a load with an accuracy of ±5 percent of full load.
• Phase Loss Detection causes the drive to fault and commands the electric brake to set if an input
or output phase loss occurs.
• Quick Stop™ ensures a rapid deceleration to stop once a drive RUN command is removed,
reducing the possibility of a crane collision.
• Reverse Plug Simulation™ allows you to change the direction of travel (motor’s phase
sequence) very rapidly before the electric brake can be set.
• Flash ROM stores the drive system’s last four fault occurrences in the drive’s memory—even
after power-down—for diagnostic purposes.
This nameplate is located on the side of the drive nearest to the keypad.
Introduction
This page intentionally left blank.
WARNING
• Do not touch any circuitry components while the main AC power is on. In addition, you
must wait until the red “CHARGE” LED is out before performing any service on that unit.
(As you look at the face of the circuitry, the “CHARGE” LED is located in the lower right
corner of the board.) It may take as long as 10 minutes for the charge on the main DC bus
capacitors to drop to a safe level.
• Do not check signals during operation.
• Do not connect the main output terminals (T1, T2, T3) to the incoming, three-phase AC
source.
• Do not connect the control board terminals, which are the 27 two-tiered terminals,
directly to the 120VAC user input device.
• Before executing Built-In Auto-Tuning, ensure that the motor is disconnected from the drive
train and the electric brake is released. If the electric brake cannot be released, you must
ensure that the brake is disengaged for the entire tuning process.
The instructions in the next three chapters apply to most IMPULSE•VG+ Series 2 crane, hoist, and
monorail applications. However, you need to carefully evaluate your specific situation and ensure
that you follow NEC codes and your local wiring practices.
These chapters tell you how to install IMPULSE•VG+ Series 2 and, to some extent, the components
that it interconnects. It explains how to: assess the drive’s environment, mount the drive, and wire
the drive circuits. It’s important to develop a “plan of attack” for both the mounting and wiring since
each task has an effect on the other one. To assist you, “IMPULSE•VG+ Series 2 Wiring Practices”
is included.
NOTE: If your IMPULSE•VG+ Series 2 is part of an Electromotive Systems, pre-engineered
TCONTROLS® motor control panel, disregard this chapter and turn to Chapter 4.
2006
2008
2011
2017
2025
2033
2054
2068
2080
2130
2160
2224
2300
Rated current (A) 6 8 11 17.5 25 33 54 68 80 130 160 224 300
Capacity (kVA) 2.3 3.0 4.2 6.7 9.5 13 19 24 30 50 61 85 110
460V Class
Specifi-
cation Specification Values and Information for Each 460V-Class Model (####-FVG+)
4001
4003
4005
4008
4011
4014
4021
4028
4034
4041
4052
4065
4080
4096
4128
4165
4224
4302
4450
4605
Rated 1.9 3.6 5.1 8.5 11.7 14.8 21 28.6 34 41 52 65 80 96 128 165 224 302 450 605
current (A)
Capacity 1.4 2.6 3.7 6.1 8.4 11 16 21 26 31 40 50 61 73 98 130 170 230 340 460
(kVA)
575V Class
Specifi-
cation Specification Values and Information for Each 460V-Class Model (####-FVG+)
5003
5004
5006
5009
5012
5017
5022
5027
5032
5041
5052
5062
5077
5099
5130
5172
5200
Rated current 3.5 4.41 6.3 9.8 12.5 17 22 27 32 41 52 62 77 99 130 172 200
(A)
Capacity 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200
(kVA)
The CDBM/CDBR, and its associated dynamic braking resistor, are used to help the inverter
decelerate AC motors (dynamic braking) and to provide a path for motor regenerative energy under
over hauling conditions, such as on a hoist.
CDBM-4045
0.24
CDBM-4090 8.50 14.50 5.94 7.09 13.98 (6)
(216) (368) (151) (180) (355)
CDBM-4220 10.63 14.50 7.25 8.27 13.98
(270) (368) (184) (210) (355)
CDBM-5037 5.53 11.0 5.91 3.94 10.24
(140.5) (279.5) (150) (100) (260)
WARNING
120 VAC is not needed for the control circuit to operate. If 120 VAC is applied to
terminals 1, 2, 5 or 6, DAMAGE TO THE UNIT WILL RESULT.
NOTE: • Some Braking units have only a symbol labeling the terminal.
• Most resistors do not have P 0 (r0 ) and B ( s0 ) designators.
• Polarity does not matter on the resistor.
5. CDBR model #4220 has an internal fan. It requires terminals r and s to be wired to one phase of
the 460V line voltage in order to power the fan.
6. Terminals 3 and 4 are the Cooling Fin Overheat Contact.
Thermoswitch contact rating: 250VAC, 1A max
30VDC, 1A max
7. Terminals 1, 2 , 5 and 6 are used for MASTER/SLAVE Operation. Use twisted-pair wires of 14
AWG or smaller for connection between 5, 6, and 1, 2 on the braking units. Parallel connection
is possible up to a maximum of 10 units. Refer to Figure 1-4 (page 1-14) for parallel connection
of braking units.
8. Set the Voltage Selection Jumper to match the voltage of the incoming power source.
9. Set the Master/Slave Jumper to Master for single unit operation.
10. For further information, refer to CDBR/CDBM manual.
The following guidelines may help determine input and output reactor requirements:
• Install an input reactor if the power source is greater than
500kVA.
• Install an output reactor if the distance between the drive and the motor exceeds 150 feet.
• Install an output reactor if a device, such as a power limit switch, is used to disconnect the motor
from the drive.
• Install one output reactor per drive for a multiple-drive arrangement requiring reactor protection.
• For a multiple drive arrangement, an input reactor for each drive is recommended for optimal
protection. However, if the drives are within two drive sizes of each other, a single input reactor
can be used. The reactor must be rated at an amperage equal to or greater than the sum of the
amperage for all the drives.
230V Class
Model Number 230V Part Number Maximum Amps of Reactor
2006-FVG+ REA230-2 8
2008-FVG+ REA230-2 8
2011-FVG+ REA230-3 12
2017-FVG+ REA230-5 18
2025-FVG- REA230-7.5 25
2033-FVG+ REA230-10 35
2054-FVG+ REA230-20 55
2068-FVG+ REA230-25 80
2080-FVG+ REA230-30 80
2130-FVG+ REA230-50 130
2160-FVG+ REA230-60 160
2224-FVG+ REA230-100 250
2300-FVG+ REA230-125 320
575V Class
Model Number 575V Part Number Maximum Amps of Reactor
5003-FVG+ REA575-2 & 3 4
5004-FVG+ REA575-2 & 3 4
5006-FVG+ REA575-5 8
5009-FVG+ REA575-10 12
5012-FVG+ REA575-10 12
5017-FVG+ REA575-15 18
5022-FVG+ REA575-20 & 25 25
5032-FVG+ REA575-30 35
5041-FVG+ REA575-40 45
5052-FVG+ REA575-50 55
5062-FVG+ REA575-60 & 75 80
5077-FVG+ REA575-60 & 75 80
5099-FVG+ REA575-100 100
5130-FVG+ REA575-150 160
5172-FVG+ REA575-200 200
5200-FVG+ REA575-200 200
G5IF has eight optically isolated drive terminals which can be used to connect with the user input
device. The Terminal 1 and 2 are always used for the directional run commands (Forward and
Reverse, Up and Down). The rest of six terminals are multi-function terminals, and are used for
speed control and other characteristics. With multi-function terminals you can assign various
functions and performance characteristics without having to rewire the drive.
G5OUT has two 240VAC, 1.5 Amp solid state relays for output indication devices. It includes two
programmable multi-function output terminals.
G5IN4 card has four additional input terminals, which can have a total of 14 sets of input selections.
The individual terminals can be enabled/disabled within a set. For program information refer to
Chapter 5, Programming Advanced Features.
Installation
This page intentionally left blank.
WARNING
• When preparing to mount the IMPULSE•VG+ Series 2 drive, lift it by its base. Never lift
it by the front cover.
• Mount the drive on nonflammable material.
• The IMPULSE•VG+ Series 2 drive generates heat. For the most effective cooling
possible, mount it vertically. For more details, refer to the “IMPULSE•VG+ Series 2
Dimensions/Heat Loss—Open Chassis” pages 2-9 through 2-11.
• When mounting units in an enclosure, install a fan or other cooling device to keep the
enclosure temperature below 113°F (45°C).
In addition, this section will cover information on the components that interconnect with
IMPULSE•VG+ Series 2.
Choosing a Location
Be sure that the drive is mounted in a location protected against the following conditions:
• Extreme cold and heat. Use only within the ambient temperature range:
Open Chassis: +14 to 113°F (-10 to 45°C)
• Direct sunlight (not for use outdoors)
• Rain, moisture
• High humidity
• Oil sprays, splashes
• Salt spray
• Dust or metallic particles in the air
• Corrosive gases (e.g. sulfurized gas or liquids)
• Radioactive substances
• Combustibles (e.g. thinner, solvents, etc.)
• Physical shock, vibration
• Magnetic noise (e.g. welding machines, power devices, etc.)
Figure 2-3
NOTE:
• The required clearances at the top, bottom, and both sides of the inverter are the same for
both open chassis and NEMA 1 enclosures.
• Allowable intake air temperature: 14°F to 104 °F (-10°C to +40°C)
• If necessary, a heater or air conditioner must be used to maintain the temperature range
listed above.
Figure 2-4
12. Remove the drive cover. For Models 2003-FVG+ through 2033-FVG+ and 4001-FVG+ through
4014-FVG+ and 5003-FVG+ through 5022-FVG+. See Figure 2-5. On larger size drives, the
cover is attached with screws.
Figure 2-5
13. Remove the G5OUT Card (if used).
14. Remove the G5IF Card.
15. Follow the wiring practices outlined in Chapter 3.
230V Class
Wiring
This page intentionally left blank.
IMPULSE•VG+ Series 2 Wiring Practices
WARNING
Before you wire the drive, review the following practices to help ensure that your system is
wired properly.
• Do not connect the main output terminals (T1, T2, and T3) to the incoming, three-phase AC
source. This will damage the unit!
• Except for Terminals 18, 19, and 20, do not connect the control board terminals directly to the
120VAC user input device. This will damage the unit!
• Ensure that the drive-to-motor wiring distance is less than 150 ft unless appropriate reactors and/
or filters are used.
• If a device that can interrupt power is installed between the drive and the motor, install a reactor
on the output side of the drive.
• On external user input devices, use hard contact inputs rather than solid-state inputs.
• If the power source is 500 kVA or greater, or more than 10 times the inverter kVA rating, ensure
that there is at least 3 percent impedance between the power source and the drive input. To
accomplish this, you can install a DC reactor between inverter terminals ⊕1 and ⊕2, or use an
AC line reactor on the input of the drive. If you don’t provide enough impedance, excessive
peak currents could damage the input power supply circuit.
• If the user input device is a PLC TRIAC output, use a 5-K Ω, 10-W resistor between the signal
and L2 (X2).
• Comply with “Suggested Circuit Protection Specifications” on page 3-6.
• Use time delay fuses, which are sized at 150% of drive's continuous-rated current, for drive input
protection.
• Use appropriate R-C or MOV type surge absorbers across the coil of all contactors and relays in
the system. Failure to do so could result in noise-related, nuisance fault incidents.
• Use external dynamic braking resistors for all applications.
• Do not ground the drive with any large-current machines.
• Before you use any welding or high-current machines near the crane, disconnect all line and
ground wiring.
• Do not use output contactors between the drive and the motor.
• Do not let the wiring leads come in contact with the drive enclosure.
• Do not connect power factor correction capacitors to the drive input or output.
• Hard-wire the drive and motor (e.g., festoon cable). Do not use sliding collector bars.
• If you have a user input device or interface board that is remote, use shielded cable between the
drive input terminals and the interface output terminals or user input device(s).
• Before turning on the drive, check the output circuit (T1, T2 and T3) for possible short circuits
and ground faults.
CAUTION:
The following guidelines are only suggested values. Always conform to local electrical
codes and wiring practices.
L1
Main circuit input power supply
L2
L3
T1
Inverter output
T2
T3
Te r m i n a l
B1
Braking resistor n/a
B2
s
DC reactor ( ⊕1–⊕2) DC power supply (⊕1–s )
⊕1 DC reactor (⊕1– ⊕2)
DC power supply (⊕1– ⊕) Braking unit (⊕ 3–s)
DC Power supply (⊕1– s)
⊕2 Braking unit (⊕3–s ) (⊕ 1 and ⊕ 2 terminals not provided)
⊕3
r
n/a Cooling fan power supply
s
L1
L2 Main circuit input power supply
L3
T1
T2 Inverter output
T3
B1
T e r m i n a l
s
DC reactor (⊕1– ⊕2)
⊕1 DC power supply (⊕– s) DC power supply (⊕1– s) Braking unit (⊕ 3–s)
Braking unit (⊕3–s) (⊕ 1 and ⊕ 2 terminals not provided)
⊕2
⊕3 n/a
s Cooling fan
n/a
power supply
r Cooling fan power supply
n/a
(Control power supply)
s200 r–s200: 200 to 230VAC input
n/a r–s400: 380 to 460VAC input
s400
L1 (R)
L2 (S) Main circuit input power supply
L3 (T)
T1 (u)
T2 (V) Inverter output
T e r m i n a l
T3 (W)
B1
Braking resistor n/a
B2
.
IMPULSE•VG+ Series 2 (14908-14911) Instruction Manual – 6/23/00
3-11
Wiring the Control Circuit
Control Input
IMPULSE•VG+ Series 2 is designed to interface directly with a 120VAC user input device. User
input devices include: pendant controls (pushbutton station), remote control transmitters (infrared
and radio), master switches, programmable logic controls (PLC), and personal computers. This
design feature eliminates the need for interface relays or isolation circuitry. The user interface
device is connected to the G5IF 120V Control Interface Card, which includes Terminals 1, 2, 3, 4, 5,
6, 7, and 8. Four more terminals can be added with the optional G5IN4 120V Control Input Card.
NOTE: Terminal X2 is also on both control input cards, and should always be connected to X2 of
the user input device.
For the G5IF, Terminals 1 and 2 are always used for the directional run commands (FORWARD,
REVERSE, UP, DOWN, LEFT, RIGHT). The other terminals are multi-function terminals, and are
used for speed control and other characteristics. With multi-function terminals you can assign
entirely different functions and performance characteristics without having to rewire the drive.
Control Output
The table below summarizes the control output terminal functions:
NOTE: If the drive is being applied in a no-load brake hoist application, Electromotive
Systems recommends the use of an external warning device wired to terminal 2 of the
G5OUT card. Reference No-Load Brake Start/Stop and Digital Outputs – Fault
Annunciate in Chapter 5 on page 5-32 for more details.
Before you wire the encoder circuit, refer to the specification tables in this section and to “Wiring
Specifications.”
Encoder Specifications
Power supply +12VDC; if current demand is greater than 200 mA, an auxiliary power supply must provided
Output Type Quadrature (A and B channels; Z is not necessary)
Type of output circuit High-speed, differential line drive
Resolution 1024 PPR
Mounting method Encoder must be direct-coupled to motor shaft, using a zero-backlash-type coupling.
To wire the encoder circuit for IMPULSE•VG+ Series 2 (assuming the cover and keypad are
detached):
1. Direct-couple the encoder to the motor shaft, using a zero-backlash-type coupling.
NOTE: Do not connect the encoder to the motor with roller chain or gear drive. If unable to
direct-couple the encoder, use a timing belt to drive the encoder. (Contact
Electromotive Systems for encoder kits.) Also, do not connect the encoder to the low-
speed shaft of a speed reducer.
2. Connect the encoder to the PG-X2 Encoder Interface Card. Refer to Figure 3-9: “Generic
Encoder” and Figure 3-10: “PG-X2 Interface Card Terminal Functions” on page 3-20.
NOTE: Use twisted-pair, shielded cable (Electromotive R-20/6, Belden 9730, or Brand Rex T-
11651). Strip the encoder wires .25 in. (5.5 mm). Keep the wiring length less than
300 feet. (For cable lengths greater than 300 feet, contact Electromotive Systems for
information on available fiber optic cable systems.)
3. Ground the shielded cable to Terminal TA-3 of the PG-X2 Encoder Interface Card. (Ground only
one end of the shielded cable.)
NOTE: For LakeShore encoders, the shield connection is not considered “Ground.” The
shield should be grounded at TA-3 and connected to the shield at the encoder.
4. Whenever possible, the encoder cable should be wired in a continuous run between the motor
and drive. If it cannot be a direct run, the splice should be in its own junction box and isolated
from the power wires.
The following drawing and table shows you how to connect a LakeShore Model 8500 encoder to the
PG-X2 Encoder Interface Card.
CAUTION:
The following guidelines are only suggested values. Always conform to local electrical
codes and wiring practices.
WARNING
Precautions
• Only start the motor if motor shaft rotation is stopped.
• Even with small loading, never use a motor whose nameplate amperage exceeds the inverter
rated current.
DANGER
Braking method selection as shipped from Electromotive Systems is set for Decelerate to Stop
command. Extreme caution should be used. If deceleration time is too long, equipment could
run into endstop device, causing damage to equipment or injury to personnel.
WARNING
Because of the additional potential hazards that are introduced when any drive is operated
locally, we advise you to avoid operating it this way. If you do operate the drive locally, be
aware that the crane or hoist will move when you press the RUN button. If you have questions,
contact Electromotive Systems.
FWD
This LED lights when the FORWARD command is given.
REV
This LED lights when the REVERSE command is given.
REMOTE
• The SEQ LED lights when selecting the RUN command from the control
SEQ REF circuit terminals or serial communication.
• The REF LED lights when the Speed Reference is input through control
circuit terminals or serial communication.
• Pressing this key toggles between the mode set-up display and the phone
number for Electromotive Systems Service Department.
• Also toggles between REMOTE and LOCAL (Digital operator from
keypad) operation when 02-1 is set to 1.
ESC
Backs up to the previous display (before the DATA/ENTER key is depressed).
JOG
Jog run is enabled when local operation is selected.
• Pressing this key initiates run command when LOCAL operation is selected.
RUN
STOP
• Pressing this key initiates Base Block stop command.
• The red LED lights steadily when drive is at stop; blinks when Run command
is active but output frequency reference is zero, off when drive output is
controlling motor speed.
Parameters
There are hundreds of parameters that determine how the drive functions. These parameters are
programmed in the drive’s software as measurable values or options—both of which will be referred
to in this manual as settings. While some of these parameters are associated with one setting, others
are tied to a number of possible settings.
NOTE: The terms “constant” and “parameter” have the same meaning.
Before shipping the drive to you, we programmed initial settings in the drive’s software so that most,
if not all, of your crane system requirements are supported. However, if you do find it necessary to
change the initial settings, we recommend that you only allow qualified crane system technicians to
program the drive. This can be accomplished by using the Password Barrier and Access Level
features. For more information on these security features, see Initialization Set-up on page 4-9.
You also have the option of allowing personnel with limited crane system knowledge to program
only certain parameters— User Parameters—that you select. To select these parameters, see “User
Parameters (A2-XX)” on page 4-14.
Two other features to be aware of are Initialize Parameters (A1-05) and User Defaults (O2-03). Both
these features are related and allow you to revert back to parameter settings that you save. This is
especially helpful when you have made a number of programming changes, but want to get back to
the settings you had before you made any changes. To program these features, see “Initilize
Parameters (A1-05)” and “User Defaults (02-03)” on page 4-14.
Operation Mode
Drive operation is enabled. Drive status LED lights.
Initialize Mode
Parameter access levels, control method, motion, speed control mode, and passwords are selected.
Programming Mode
Parameters are set/read. Items to be set/read vary depending on the access level setting.
Auto-Tuning Mode
Motor parameters are automatically set by entering tuning data (motor nameplate values) when using
open loop vector control method.
Setting Description
0 Operation Only
1 User Program - Accesses parameters selected by OEM (A2-01 to A2-32).
2 Advanced Level - For advanced programming in special applications.
Refer to the parameter code table in Chapter 5 for available parameters at each level.
Setting Description
3 Flux Vector
NOTE: An auto-tune must be performed for all flux vector applications. Refer to the Auto-Tuning
section on page 4-15.
Setting Description
0 Traverse - Decelerate to stop upon removal of RUN command.
2 No-Load Brake Hoist
Setting Description
0 5-SPD Multi-step (default) — Defines Terminals 3-6 as speeds 2-5.
1 2-Step infinitely variable — Terminals 1 and 2 = b1-01 (Reference 1) and speed
hold. Terminal 3 = Accelerate.
2 3-Step infinitely variable — Terminals 1 and 2 = b1-01 (Reference 1).
Terminal 3 = Speed Hold. Terminal 4 =Accelerate.
3 Uni-polar analog — Terminals 1 and 2 = A directional input. Terminal 13 = 0-
10V. Terminal 14 = 4-20mA.
4 Bi-polar analog — Terminal 13 = -10 to +10V. An input on Terminal 1 is
required, but direction is determined by the reference given on Terminal 13.
5 2-SPD Multi-step — Defines Terminal 3 = 2nd speed.
6 3-SPD multi-step — Defines Terminals 3 and 4 as speeds 2 and 3 respectively.
7 Not Used–Defines Terminals 3-8 as not used. Use this setting if using the
G5IN4 option card for inputting speed references.
Jog Reference
Parameter Description Speed 1 Speed 2 Speed 3 Speed 4 Speed 5 Speed 6 Speed 7 Speed 8 Reference Priority
A1-04 5-Speed Multi-Step 6.00 15.00 30.00 45.00 60.00 9999 9999 9999 6.00 0
A1-04 2-Step Infinitely Variable 6.00 9999 9999 9999 60.00 9999 9999 9999 6.00 0
A1-04 3-Step Infinitely Variable 6.00 9999 9999 9999 60.00 9999 9999 9999 6.00 0
A1-04 Uni-Polar Analog 9999 9999 9999 9999 9999 9999 9999 9999 6.00 1
A1-04
A1-04 Bi-Polar Analog 9999 9999 9999 9999 9999 9999 9999 9999 6.00 1
A1-04 2-Speed Multi-Step 20.00 60.00 9999 9999 9999 9999 9999 9999 6.00 0
A1-04 3-Speed Muti-Step 15.00 30.00 60.00 9999 9999 9999 9999 9999 6.00 0
A1-04 Not Used 15.00 30.00 60.00 9999 9999 9999 9999 9999 6.00 0
*Applies only for software versions 14910 and 14911.
Note: Data 9999 denotes no change from previously programmed value.
A1-04 Uni-Polar Analog 100.00 2.0 0 10.0 10.0 0 1.50 1.50 1.50 0 00
A1-04 Bi-Polar Analog 100.00 2.0 0 10.0 10.0 0 1.50 1.50 1.50 0 00
A1-04 2-Speed Multi-Step 100.00 2.0 0 10.0 10.0 0 1.50 1.50 1.50 0 00
A1-04 3-Speed Muti-Step 100.00 2.0 0 10.0 10.0 0 1.50 1.50 1.50 0 00
A1-04 Not Used 100.00 2.0 0 10.0 10.0 0 1.50 1.50 1.50 0 00
* Applies only for software versions 14910 and 14911.
Terminal Terminal Terminal Terminal Terminal Terminal Terminal Terminal Terminal Terminal
Parameter Description 3 Select 4 Select 5 Select 6 Select 7 Select 8 Select 9 Select 25 Select 26 Select 13 Signal
A1-04 5-Speed Multi-Step 00 01 02 03 24 0E 00 00 7F 0
A1-04 2-Step Infinitely 05 07 09 13 24 0E 00 00 7F 0
Variable
A1-04 3-Step Infinitely 04 05 07 09 24 0E 00 00 7F 0
Variable
A1-04
Jog Reference
Parameter Description Speed 1 Speed 2 Speed 3 Speed 4 Speed 5 Speed 6 Speed 7 Speed 8 Reference Priority
A1-04 5-Speed Multi-Step 6.00 15.00 30.00 45.00 60.00 9999 9999 9999 6.00 0
A1-04 2-Step Infinitely Variable 6.00 9999 9999 9999 60.00 9999 9999 9999 6.00 0
A1-04 3-Step Infinitely Variable 6.00 9999 9999 9999 60.00 9999 9999 9999 6.00 0
A1-04
A1-04 Uni-Polar Analog 9999 9999 9999 9999 9999 9999 9999 9999 6.00 1
A1-04 Bi-Polar Analog 9999 9999 9999 9999 9999 9999 9999 9999 6.00 1
A1-04 2-Speed Multi-Step 20.00 60.00 9999 9999 9999 9999 9999 9999 6.00 0
A1-04 3-Speed Muti-Step 15.00 30.00 60.00 9999 9999 9999 9999 9999 6.00 0
A1-04 Not Used 15.00 30.00 60.00 9999 9999 9999 9999 9999 6.00 0
* Applies only for software versions 14910 and 14911.
NOTE: Data 9999 denotes no change from previously programmed value.
A1-04 Uni-Polar Analog 100.00 2.0 1 5.0 3.0 0 .50 .50 .50 0 04
A1-04 Bi-Polar Analog 100.00 2.0 1 5.0 3.0 0 .50 .50 .50 0 04
A1-04 2-Speed Multi-Step 100.00 2.0 1 5.0 3.0 0 .50 .50 .50 0 04
A1-04 3-Speed Muti-Step 100.00 2.0 1 5.0 3.0 0 .50 .50 .50 0 04
A1-04 Not Used 100.00 2.0 1 5.0 3.0 0 .50 .50 .50 0 04
* Applies only for software versions 14910 and 14911.
Terminal Terminal Terminal Terminal Terminal Terminal Terminal Terminal Terminal Terminal
Parameter Description 3 Select 4 Select 5 Select 6 Select 7 Select 8 Select 9 Select 25 Select 26 Select 13 Signal
A1-04 5-Speed Multi-Step 00 01 02 03 24 0E 00 00 7F 0
A1-04 2-Step Infinitely 05 07 09 13 24 0E 00 00 7F 0
Variable
A1-04 3-Step Infinitely 04 05 07 09 24 0E 00 00 7F 0
Variable
A1-04
Setting Description
0 No Initialization (factory default)
1110 User Initialization - resets the inverter to user-specified initial values. To set
user-specified initial values, make all required changes to parameter settings,
then set 02-03 to “1”. The inverter will memorize all current settings as the
user-specified initial values. Up to 50 changed parameters can be stored.
CAUTION
The brake output is not energized during auto-tune. The brake must be manually released and
unreleased when Auto-Tuning is complete.
WARNING
The IMPULSE•VG+ can adapt to all motors manufactured worldwide with its automatic tuning
function. The inverter asks the user for minimal motor information, then guides the user through a
quick simple tuning process. Refer to the Structure of Parameters on page 4-7 and the table below
for the motor data required for automatic tuning.
NOTE: Contact Electromotive Systems service department if an auto-tune can not be performed.
After scrolling through the tuning parameters using the Up Arrow key, depress the RUN key to begin
auto-tuning. During tuning, “Tuning Proceeding” flashes on the digital operator display. When
complete, “Tune Successful”, is displayed. Depress the Menu key to exit auto-tuning mode. Please
refer to the “Fault Display and Corrective Actions at Auto-Tuning” section on page 6-18 if “Tune
Successful” is not displayed.
NOTE: If the STOP key is depressed during tuning, auto-tuning is interrrupted and the motor
coasts to a stop. The data changed during tuning returns to its original values.
NOTE: If an auto-tune is unsuccessful, temporarily change D12-30=1 and D10-01 to at least
5.0KHz.
Programming Advanced
Features
This page intentionally left blank.
Application
• B1 Preset References
• B2 Reference Limits
• B3 Sequence/Reference Source
• B4 Trim Control Level
• B5 Acceleration/Deceleration
• B6 Phase Loss Detection
• B8 Jump Frequencies
Preset Reference
Open
Loop
Parmtr Initial V/F Vector
Code Display Function Range Value Access Access
B1-01* Reference 1 Sets the frequency of 0.00–150.00 Hz 15 Adv Adv
Minimum Speed/Speed 1.
B1-02* Reference 2 Sets the Speed 2 frequency. 0.00–150.00 Hz 30 Adv Adv
B1-03* Reference 3 Sets the Speed 3 frequency. 0.00–150.00 Hz 60 Adv Adv
B1-04* Reference 4 Sets the Speed 4 frequency. 0.00–150.00 Hz 45 Adv Adv
B1-05* Reference 5 Sets the Speed 5 frequency. 0.00–150.00 Hz 60 Adv Adv
B1-06** *Reference 6 Sets the Speed 6 frequency. 0.00–150.00 Hz 0.0 Adv Adv
B1-07** *Reference 7 Sets the Speed 7 frequency. 0.00–150.00 Hz 0.0 Adv Adv
B1-08** *Reference 8 Sets the Speed 8 frequency. 0.00–150.00 Hz 0.0 Adv Adv
B1-09* Jog Reference Jog Control and Inching 0.00–150.00 Hz 6 Adv Adv
Control frequency
reference.
B1-10* Ref Priority Determines whether the 0 Adv Adv
digital or analog frequency
reference is used.
0 Digital Ref Only
1 Analog Ref Only
2 Higher Ref Sel
* Initial value is determined by X-Press Programming (Table 4.1-4.6)
** Applies only for software versions 14910 and 14911.
An alternate upper limit frequency can be used during operation when a Multi-Function Input (MFI)
is set to 43 (Alt S-Ref UpLimit) and the MFI is on. Alternate Upper Limit Frequency = (B2-03)% x
(E1-04).
Open
Loop
Parmtr Initial V/F Vector
Code Display Function Range Value Access Access
B2-01 Ref Upper Limit Sets as a percentage of the 0.0–110% 100 Adv Adv
maximum output frequency
(E1-04), which determines
the maximum frequency at
which the drive is able to
run.
B2-02 Ref Lower Limit Sets as a percentage of the 0.0–109% 2 Adv Adv
maximum output frequency
(E1-04), which determines
the minimum frequency at
which the drive is able to
run.
B2-03 Upper Lim Gain A multiplier, sets an 0–255% 100 Adv Adv
alternate upper limit
frequency by a multi-
function input = 43
Braking torque: without braking resistor, approximately 20% of motor rated torque; with braking
option, approximately 150% of motor rated torque.
This parameter sets the speed reference level at which Zero Speed mode operation will activate, in
accordance with the selection programmed B3-05 (see the figures below).
Parmtr Access
Code Display Function Range Initial Value Level
B3-05 Zero-Speed Oper Operation Selection at Zero 0 Adv
Speed.
0 RUN at Freq Ref Operate according to the
Frequency Reference
1 Stop Coast when the Frequency
Reference is below E1-09
2 RUN at Min. Freq (E1- Output the Frequency set in
09) E1-09
3 RUN at Zero RPM Zero reference value when the
frequency reference is below
E1-09
B3-05: 1 STOP
Open
Loop
Parmtr Initial V/F Vector
Code Display Function Range Value Access Access
B3-06 # of Input Scans Selects the microprocessor 1 Adv Adv
scan time
0 2ms–2 scans
1 5ms–2 scans
Open
Loop
Parmtr Initial V/F Vector
Code Display Function Range Value Access Access
B3-07 LOC/REM Run Sel Determines action after 0 Adv Adv
switching Run/Speed
reference source.
0 Cycle Extrn Run If the run command is
present at the time when
the Run/Speed reference
source is switched, it
requires the run command
to be removed and then
reapply the run command
from the new source to
resume the normal
operation.
1 Accep Extrn Run If the run command is
present at the time when
the Run/Speed reference
source is switched, it does
not require the run
command from the new
source to be removed. The
normal operation will
continue.
If the trim control increase command is ON when a frequency reference is input on the analog input,
the trim control level will be added to the analog frequency reference and then that sum will be
output as the output frequency. If the trim control decrease command is ON, the frequency reference
will be decreased by the trim control level.
Set the trim control level as a percentage of the maximum output frequency.
If the frequency reference minus the trim control level is less than zero, the output frequency will be
zero.
Parmtr Access
Code Display Function Range Initial Value Level
B5-05 Accel Time N Chg Sets acceleration time at 0.0–25.5 sec 1.0 Adv
Speed Switch frequency.
B5-06 Dec Time N Chg Sets deceleration time at 0.0–25.5 sec 1.0 Adv
Speed Switch frequency.
B5-07 Hoist 2 Stop Sets deceleration time for 0.0–25.5 sec 0.3 Adv
DOWN/REVERSE direction,
when B3-03=5 (Hoist 2-
Stop).
B5-08 Fault Stop Time Sets deceleration time for 0.0–25.5 sec 0.3 Adv
complete stop at external
fault. See External Response
Selection page 5-82.
B5-09 Acc/Dec Units Determines acceleration and 1 Adv
deceleration time interval and
range.
0 0.01sec for 0.00–2.55
sec
1 0.1sec for 0.0–25.5
B5-10 Acc/Dec SW Freq Determines acceleration/ 0.0–150.0Hz 120.0 Adv
deceleration switching level
B5-11 SW Freq Compare Determines when 1 Adv
Acceleration Time and
Deceleration Time at Speed
Switch Hz is enabled;
0 lower SW Freq 0: B5-05/06 is enabled, N-out≤B5-10
1 upper SW Freq 1: B5-05/06 is enabled, N-out≥B5-10
Parmtr Access
Code Display Function Range Initial Value Level
B5-12 For T Lim Accel Determines acceleration time 0.0–25.5 sec 0 Adv
at FORWARD when Torque
Limit Acc/Dec is multi-
function input = 14.
B5-13 For T Lim Decel Determines deceleration time 0.0–25.5 sec 0 Adv
at FORWARD when Torque
Limit Acc/Dec is multi-
function input = 14.
B5-14 Rev T Lim Accel Determines acceleration time 0.0–25.5 sec 0.5 Adv
at REVERSE when Torque
Limit Acc/Dec is multi-
function input = 14.
B5-15 Rev T Lim Decel Determines deceleration time 0.0–25.5 sec 0 Adv
at REVERSE when Torque
Limit Acc/Dec is multi-
function input = 14.
Phase Loss Detection compares the output current of each of the three phases to a preset level. If the
output current of any of the phases falls below the preset level, a “LF” fault will appear on the
display. The drive will immediately set the brake, thus retaining control of the load.
Motion (A1-03)
Special Function Traverse (A1-03=0) No-Load Brake (A1-03=2)
C1: Quick Stop/Reverse Plug Simulation Yes Yes
C2: Micro Positioning Yes Yes
C3: End of Travel Limits Yes Yes
C4: Zero Servo Yes Yes
C5: Load Check No Yes
C6: Ultra Lift No Yes
C7: Torque Limit Yes Yes
C8: No-Load Brake Hoist No Yes
C9: G5IN4 Setup Yes Yes
C10: Weight Measurement No Yes
C11: Slack Cable Detection No Yes
C12: Delay Timers Yes No
Parmtr Access
Code Display Function Range Initial Value Level
C2-01 MS Gain 1 For Micro-Positioning 0.00–2.55 1.00 Adv
Control–the number
multiplied by the Analog or
Digital Speed Reference to
achieve slow-speed
operation.
C2-02 MS Gain 2 For Micro-Positioning 0.00–2.55 1.00 Adv
Control–an alternate
number multiplied by the
Analog or Digital Speed
Reference to achieve slow-
speed operation.
Parmtr Access
Code Display Function Range Initial Value Level
C3-01 Up Limit 1 Speed Speed at Upper Limit input.. 0–150 Hz 6 Adv
C3-02 UL 1 Decel Time Decel time to Upper Limit 0.0–25.5 sec 1.0 Adv
Speed.
C3-03 UL 2 Stop Time Decel time to STOP when 0.0–25.5 sec 0.5 Adv
Upper Limit is Input..
C3-04 Low Limit 1 Speed Speed at Lower Limit input.. 0–150 Hz 6 Adv
C3-05 LL 1 Decel Time Decel time to Lower Limit 0.0–25.5 sec 1.0 Adv
Speed
C3-06 LL 2 Stop Time Decel time to STOP when 0.0–25.5 sec 0.5 Adv
Lower Limit is input.
C3-07* Upper Action Determine the stop method at 0 Adv
Upper Limit 2 and Lower
Limit 2 Input.
0 Decel to Stop
1 BB to Stop Base Block
* Initial value is determined by X-Press Programming (Table 4.1 to 4.6).
Parmtr Access
Code Display Function Range Initial Value Level
C4-01 Zero Servo Timer Maximum duration of Zero 0–255 sec 10 Adv
Servo action at multi-function
input.
C4-02 Zero Servo Gain Zero Servo multiplier. 0–100 * Adv
C4-03 Zero Servo Count Zero Servo completion width. 0–16383 10 Adv
* For drive model #s 2006-2080, 4003-4041 and 5003-5032 the Initial Value is 25. For drive model #s 2130-2300,
4052-4605 and 5041-5200 the Initial Value is 50.
Parmtr Access
Code Display Function Range Initial Value Level
C5-01 Load Check 0/1 Determines whether Load 0 Adv
Check is enabled.
0 Disabled
1 Enabled
C5-02 LC Alarm Action Action at Load Check alarm 2 Adv
or fault. “BB to Stop” is
Immediate Stop at STOP.
0 Alarm Only
1 Decel to Stop
2 Coast to Stop
3 Fault Stop
C5-03 Min Torque Ref Minimum current/torque 0–100% 60 Adv
reference during acceleration
that triggers Load Check.
C5-04 Look Speed 1 First Load Check frequency 0–150 Hz 6 Adv
reference.
C5-06 Vec Torque Ref Torque reference at LS1, 2 0–300% 125 Adv
and 3.
C5-07 Look Speed 2 Second Load Check 0–150 Hz 20 Adv
frequency reference.
C5-09 Look Speed 3 Third Load Check frequency 0–150 Hz 60 Adv
reference.
C5-11 1 Ref for > LS 3 Load Check Current when 30–200% 160 Adv
Output Frequency > Look
Speed 3.
C5-12 LC Setting Time Time for holding Output 0–2.55 sec 0.20 Adv
Frequency to stabilize Output
Current.
C5-13 LC Test Time Time (after the LC Setting 0–2.55 sec 0.10 Adv
Time) for comparing Output
Current with Reference
Current
C5-14 LC Fault Speed Maximum lowering speed 0–150 Hz 6 Adv
after Load Check fault
Open
Loop
Parmtr Initial V/F Vector
Code Display Function Range Value Access Access
C6-01 Ultra Lift 0/1 Determines whether Ultra 0 Adv Adv
Lift is enabled.
0 Disabled
1 Enabled Automatic
2 Enabled by MFI
C6-02 Ultra Lift ForSpd Maximum Output 0–150 Hz 60 Adv Adv
Frequency during Ultra
Lift—FORWARD.
C6-03 Ultra Lift RevSpd Maximum Output 0–150 Hz 60 Adv Adv
Frequency during Ultra
Lift—REVERSE.
C6-04 Ultra Lift For T Maximum output torque 0–100% 50 Adv Adv
below which Ultra Lift—
FORWARD is enabled.
C6-05 Ultra Lift Rev T Maximum output torque 0–255% 30 Adv Adv
below which Ultra Lift
REVERSE is enabled.
C6-06 UL Enabling Spd Threshold frequency at 0–150 Hz 60 Adv Adv
which Ultra Lift is enabled.
C6-07 UL Delay Time Delay time at enabling 0.0–30.0 sec 2.0 Adv Adv
speed prior to torque-
compare function.
C6-08 SFS Acc Gain Speed feedback 0.1–9.9 1.0 Adv Adv
acceleration multiplier.
WARNING
Motors and drive machinery must be capable of operating above motor base speed. Consult
the motor/gearbox/hoist manufacturer before enabling Swift Lift function. Failure to observe
this warning may result in damage to equipment and possible injury or death to personnel.
Parmtr Access
Code Display Function Range Initial Value Level
C7-01 Torque Limit Fwd FORWARD torque limit 0–300% 150 Adv
C7-02 Torque Limit Rev REVERSE torque limit 0–300% 150 Adv
C7-03 Torq Lmt Rgn Regenerative torque limit at 0–300% 180 Adv
FORWARD
C7-04 Torq Limit Rev Rgn Regenerative torque limit at 0–300% 180 Adv
REVERSE
C7-07 T-Lim Gain MFI Used when H1-01~H1-06 = 0–2.55 1.25 Adv
15 and MFI is on
The NLB Sequence is comprised of a series of Timers and Counters that monitor certain feedback
devices. The sequence is divided into two parts, NLB Start and NLB Stop.
The NLB Start Sequence begins by building up torque in the motor to a predefined level within the
C8-01 (Torque Compensation Time) timer. This level is determined by several factors which are
defined below. During the C8-01 time, the drive is monitoring current to motor. The internal
current feedback equation must be satisfied within the time set in C8-02 (IFB OK Time). If it is not,
a BE2 (No-Current) alarm will be displayed on the keypad and the drive will stop outputting voltage
to the motor. The brake will remain closed.
Factor 1: On the first run command after power up, or after any major fault which causes the NLB
Stop sequence to be skipped, the NLB Start sequence by default looks at the value programmed in
C8-16, the Initial Brake Release torque.
Factor 2: Once the system has completed a successful NLB Start and NLB Stop, a new value is used.
This value is one that has been memorized and stored into memory during the NLB Stop Sequence.
It is equivalent to the amount of torque required for the motor to hold the load that is on the hook in
Zero Servo (otherwise known as Load Float) with the brake released. Some benefits of memorized
Load Float torque for the next brake release are:
• Faster response to run commands when drive is in Base Block Status.
• Upon brake release, shaft rotation begins in the direction of the run command.
Once the brake has been commanded to release, the output remains in Zero Servo for the amount of
time programmed into C8-04. During C8-04, the drive waits for the brake to completely open and
watches encoder feedback. If the amount of feedback is less than the setting in C8-05 (Roll Back
Count), then the drive proceeds to the BE3 check. If it is not, a BE1 alarm is displayed on the
keypad and the sequence stops. For the BE3 check, if the brake opened mechanically, then the
encoder feedback must be greater than or equal to the value programmed in C8-07 (BE3 Detect
Count) within the time set in C8-06 (BE3/Alternate Torque Time). If it is not, then BE3 is displayed.
By the time the drive has completed the BE3 check, there should be a significant amount of motor
shaft movement and the NLB start sequence is complete.
The NLB Stop Sequence begins when the run command has been removed and the output frequency
has decelerated to zero. Once at zero speed, the motor maintains a Zero Servo position or more
commonly referred to as Load Float for the duration of C8-10 (Load Float Time). During the Load
Float time, run commands in either direction are accepted and will begin accelerating immediately in
the commanded direction thereby skipping the NLB Start Sequence entirely. The Load Float Timer
is reset after each new run command. Once the Load Float Timer expires, the brake output
command is removed (thereby closing the brake) and Zero Servo is maintained for the time set in
C8-11 (Brake Delay Time) to allow the brake to fully close. Once the Brake Delay Time has
expired, the BE6 check is executed. The BE6 check monitors encoder feedback and compares it to
C8-13 (BE6 Max count). The encoder feedback must not exceed the number of counts in C8-13
within the C8-12 (BE6 Detect Timer) time. If it does (meaning the load slipped through the brake),
a BE6 alarm is displayed on the keypad and the drive will reset its zero servo position and maintain
its new position. Run commands will still be accepted with the exception of a reduced speed in the
up direction set by C8-17 (BE6 Up speed) and the NLB stop sequence will begin again once the run
command had been removed.
NOTE: All of the above faults are annunciated by a digital output which is preprogramed by
Electromotive Systems to output to terminal 2 on the G5OUT card. A customer supplied
warning device should be connected to this output to notify operators of potentially hazardous
brake conditions. BE6 detection is disabled (C8-12=0) when the inverter leaves the factory.
Electromotive Systems does not recommend enabling BE6 detection without the use of an
audible or visual alarm to signal an operator of a hazardous condition. If BE6 detection is
desired, a warning device should be installed and wired to terminal 2 of the G5OUT card (see
Fig. 3-24 for wiring details). If the alarm activates upon removing the run command and the
stopping sequence is intitiated, DO NOT turn off power. This fault means the brake has failed
and the motor/drive combination is holding the load. In this situation, move the crane to a safe
location and remove the load from the hook. Corrective action should then be taken. See page
6-5.
WARNING
DO NOT turn off power to the drive during a BE6 fault. This may result in loss of control of the
load if the brake has failed in the open position or is unable to hold the load.
To enable BE6 detection, C8-12 must be greater than 0. C8-12=2.0 seconds is the recommended
BE6 detect time. For more information on BE6 detection, reference Fig. 5-30, No Load Brake BE6
timing diagram.
Parmtr Access
Code Display Function Range Initial Value Level
C8-18 Load Float PG Moni Enables encoder monitoring 0 to 1 Enabled Adv
during Load Float.
Parmtr Access
Code Display Function Range Initial Value Level
C8-19 PG Moni Count Sets the desired movement 0 to 99 PPR 20 Adv
length in terms of motor shaft
rotation.
For this function, 1 motor revolution would be undesirable so the range of the parameter setting has
been limited. The motor shaft will rotate forward for the C8-19 counts and then rotate back to its
start position and repeat for the duration of the Load Float Time (C8-10). The speed reference at
which the drive commands the motor shaft to move at is partly derived by the distance at which it
needs to travel. Increasing the distance, increases the frequency reference.
Parmtr Access
Code Display Function Range Initial Value Level
C8-20 Shaft Osc. Gain Adjusts the frequency which 0 to 60 15 Adv
the oscillations occur.
C8-21 PG Moni Flt Time Sets the amount of time 0 to 8.00 1.00 Adv
allowed for the oscillation to
occur without a fault.
Parmtr Access
Code Display Function Range Initial Value Level
C9-01 G5IN4 0/1 Determines whether the 0 Adv
G5IN4 Digital Multi-
Function Inputs are enabled.
0 Disabled
1 Enabled
C9-02 G5IN4 Setup Determines the four settings 0000–FFFF 0 Adv
for G5IN4 Digital Multi-
Function Inputs.
The optional G5IN4 board accepts four additional multi-function inputs. The G5IN4 board has four
terminals, each of which can be programmed to one of the fourteen sets of inputs. Each input in the
set can be enabled or disabled.
1. Set C9-01 to 1.
2. Determine the parameter C9-02 setting by specifying the first digit (from left) and the fourth
digit (from left) using tables 5.4 and 5.5. The second and third digit should always be “0”.
3. Set parameter C9-02.
Table 5.3
MONITOR TERMINAL
U1-25 1 2 3 4
1 1 0 0 0
2 0 1 0 0
3 1 1 0 0
4 0 0 1 0
5 1 0 1 0
6 0 1 1 0
Table 5.4: G5IN4 Digital Multi-Function Input Sets (1 through E) (Software 14906, 14908, 14909)
Multi-Function Input Assigned to Each Terminal
First Digit (From
Left) You Enter Terminal 1 Terminal 2 Terminal 3 Terminal 4
1 Upper Limit—SLOW Upper Limit STOP; Lower Limit SLOW; Lower Limit STOP;
DOWN; Normally Closed Normally Closed Normally Closed Normally Closed
2 Upper Limit—SLOW Upper Limit STOP; Lower Limit SLOW; Lower Limit STOP;
DOWN; Normally Open Normally Open Normally Open Normally Open
3 Upper Limit STOP; Lower Limit STOP; Micro-Positioning Control Micro-Positioning Control
Normally Closed Normally Closed Multiplier 1 Multiplier 2
4 Upper Limit STOP; Lower Limit STOP; Micro-Positioning Control Micro-Positioning Control
Normally Open Normally Open Multiplier 1 Multiplier 2
5 Upper Limit STOP; Lower Limit STOP; Micro-Positioning Control Swift-Lift Enable
Normally Closed Normally Closed Multiplier 1
6 Upper Limit STOP; Lower Limit STOP; Micro-Positioning Control Swift-Lift Enable
Normally Open Normally Open Multiplier 1
7 Upper Limit STOP; Lower Limit STOP; Micro-Positioning Control Torque Limit Acceleration/
Normally Closed Normally Closed Multiplier 1 Deceleration
8 Upper Limit STOP; Lower Limit STOP; Micro-Positioning Control Torque Limit Acceleration/
Normally Closed Normally Closed Multiplier 1 Deceleration
9 Upper Limit STOP; Lower Limit STOP; Micro-Positioning Control Zero Servo Command
Normally Closed Normally Closed Multiplier 1
A Upper Limit STOP; Lower Limit STOP; Micro-Positioning Control Weight Measurement
Normally Closed Normally Closed Multiplier 1 Command
B Swift-Lift Enable Torque Limit Acceleration/ Micro-Positioning Control Micro-Positioning Control
Deceleration Multiplier 1 Multiplier 2
C Alternate Torque Limit Torque Limit Micro-Positioning Control Upper Limit SLOW;
Acceleration/Deceleration Multiplier 1 Normally Closed
D Zero Servo Command Load Float Time Extension Micro-Positioning Control Micro-Positioning Control
Multiplier 1 Multiplier 2
E Alternate Speed Reference Serial/Inverter Command Micro-Positioning Control Alternate Torque Limit
Upper Limit Changeover Multiplier 1
Parmtr Access
Code Display Function Range Initial Value Level
C10-01 Load Weight 0/1 Determines whether Load 0 Adv
Weight is enabled.
0 Disabled
1 Enabled at C5-04
2 Enabled at MFI
3 Both Auto & MFI
C10-02 TRO Pri Delay Torque Output Calculation 0–1000 msec 200 Adv
primary delay time.
C10-03 LW Display Hold 0 Adv
0 Hold Display Until next run command is on
1 Hold Disp 3 sec
C10-04* LW Conversion Multiplier of torque output 00000–39999 0 Adv
calculation for display. Data
is n0000, so multiplier is
10000; “n” is decimal point.
C10-05 Full Load TRO Precentage of Torque Output 0.0–200.0% 100 Adv
that is defined as Full-Load
Torque Output.
C10-06 No Load TRO Percentage of Torque Output 0.0–200.0% 0 Adv
that is defined as No-Load
Torque Output.
C10-07 Line 2 Display Determines “weight” 0 Adv
measurement units in which
0 tons the parameter settings will be
1 pounds expressed. The unit
abbreviations appear on line 2
2 kilograms of the display
3 metric tons
4 percent load
H1-01~06 Terminal 3~8 = 44 Weight Measurement enable Adv
by Multi-Function Input.
*For an example, please refer to Table 5.19 on page 5-104.
NOTE: The Weight Measurement Function only works during the forward motion (lifting).
System Tare:
Attach all of the under hook attachments that are required during normal lifting, i.e. chains. Run the
hoist motor at 30 Hz. Record the Torque reference value by monitoring U1-09 during at constant
speed. For better accuracy, repeat the above operation several times and calculate the average torque
reference value. Enter the average value at C10-06 (no load torque reference).
K: C10-04 multiplier of torque output calculation for display. The display data is Nxxxx.
“N” is the decimal points. xxxx four digits are multiplier.
System Calibration
The following is a example of system calibration.
Set
C10-01=2 Enabled at MFI
C10-02=700ms TRO Calculation primary Delay Time
C10-03=1 Hold Display for 3 seconds
C10-04=K1 Multiplier of TRO Calculation for Display
C10-05=100% Full Load Torque Output
C10-06=U1-09 No Load Torque Output obtained for system tare
C10-07=0 Display Units; tons
H1-06=44 Weight measurement enabled by MFI
WRL
K1= x100
100-(C10-06)
3. Place a known weight that is equal or less than the rated load, to the hoist.
4. Run the hoist at 6Hz and take a reading value of W1 (U1-29). Repeat above step serveral times
to obtain an average of W1 (U1-29).
5. Compare W1 to WRL. If the difference between W and WRL is greater than 5%, calculate K2 as
indicated below.
WRL
K 2= x Ki
W 1 (U1-29)
7. Repeat steps 4 and 5 until the difference between W 1 (U1-29) and WRL is less than 5%.
K = Multiplier (C10-04).
The Slack Cable Detection is not executed, unless both of the following conditions are true:
• The output frequency is between C11-04 and C11-06.
• The Slack Cable Detection delay time is between C11-05 and C11-07.
Setup Procedure:
• To set the Slack Cable Detection torque level (C11-03), by lowering the hoist without load
at a constant speed that the hoist would normally run during the operation. Monitor and
record the torque reference (U1-09). Repeat above operation several times to ensure an
accurate reading.
• Then Set C11-03 = [(U1-09)-2].
• Enable Slack Cable Detection by setting the C11-01 to 1.
• Select output action when Slack Cable is detected by defining C11-02.
Parmtr Access
Code Display Function Range Initial Value Level
C11-01 Slack Cable 0/1 (For Hoist Application) 0 Adv
Determines whether Slack
Cable Detection is enabled.
0 Disabled
1 Enabled
C11-02 Action at SLC Multi-function output that 2 Adv
occurs at Slack Cable
Detection. For all Selections,
RAISE command is
permitted.
0 No Action Alarm Only
1 No Act/C3-04 Next LOWER command is at
Lower Limit 1 speed (C3-04).
2 Decel/C3-04 Decelerate to Lower Limit 1
Speed C3-04. Continued
LOWER commands allowed,
but at C3-04.
3 Decel/No Opr Decelerate to Lower Limit 1
Speed C3-04. Continued
LOWER commands are not
allowed.
4 Dec Stop/C3-04 Decel (by C3-05) to Lower
Limit 1 Speed C3-04.
Continued LOWER
commands allowed, but at
C3-04.
5 Dec Stop/No Opr Decel (by C3-06) to stop.
Continued LOWER
commands are not allowed.
NOTE: The Jog control input is a multi-function input. It is enabled by programming data 16 or
17 in H1-01~06.
DC Injection
DC Injection can be used to stop a motor whose rotational direction is uncertain at start-up.
With ramp to stop enabled (B3-03=0), upon removal of the run command the IMPULSE•VG+
Series 2 drive controls motor deceleration according to the Decel Time setting, until output
frequency reaches the DC Injection Braking Start Frequency (D1-01 setting). Then the
IMPULSE•VG+ Series 2 drive output is turned off and DC injection current is applied to the motor.
The effective DC injection time and current should be set to provide adequate stopping without
excessive motor heating. The DC injection voltage is determined by the DC injection braking
current and motor impedance.
Parmtr Access
Code Display Function Range Initial Value Level
D1-01 DCInj Start Freq DC Injection braking 0.0–10 Hz 1.5 Adv
frequency start.
D1-03 DCInj@Start DC Injection braking time. 0.00–10.00 sec 0.00 Adv
D1-04 DCInj Time@Stop DC Injection braking time at 0.00–10.00 sec 0.05 Adv
stop.
D1-05 DC Injection P Gain 0.00–1.00 0.05 Factory
D1-06 DC Injection Integral Time 0–1000 msec 100 Factory
D1-07 DC Injection Limit 0.0–30% 15.0 Factory
Parmtr Access
Code Display Function Range Initial Value Level
D2-01 Slip Comp Gain Slip compensation multiplier. 0.0–2.5 1 Adv
Parmtr Access
Code Display Function Range Initial Value Level
D4-01 ASR P Gain 1 ASR Proportional Gain 1. 1.00–300.00 30 Adv
D4-02 ASR 1 Time 1 ASR Integral Time 1. 0.00–10.000 sec. 0.500 Adv
Parameters D4-01 and D4-02 provide adjustments to enable the optimum performance during load
disturbances. The proportional gain (D4-01) adjusts the amount of instantaneous droop as a function
of loss, and provides dampening from load disturbances such as speed reference change, or a change
in load. The integral time (D4-02) adjusts the response time of the IMPULSE•VG+ Series 2 to the
load disturbances.
NOTE: Speed control response is increased by increasing the proportional gain setting and
decreasing the integral time. However, instability or hunting may occur between the
IMPULSE•VG+ Series 2 and the load if D4-01 (ASR Proportional Gain) is set too high, or
D4-02 (ASR Integral Time) is set too low.
Parameter D4-03 is used as an additional proportional gain adjustment, and parameter D4-04
determines the response time for Proportional Gain 2 (D4-03).
Torque Control
Parmtr Access
Code Display Function Range Initial Value Level
D5-01 Torque Control Determines whether Speed or 0 Adv
Torque Control is selected.
0 Speed Control Speed Control enabled with
torque limit
1 Torque Control Torque control enabled with
speed limit.
Speed/torque control selection can also be made by using a multi-function input select (H1-XX=39 speed-
torque control changeover).
D5-02 Torque Ref Filter Primary delay time for 0–1000msec 0 Adv
Torque Reference Input.
1 Torque
Torque Reference
(from Terminal 16) 1+sT Reference
d5-02
Parmtr Access
Code Display Function Range Initial Value Level
D5-03 Speed Limit Sel Speed Limit Selection (See 1 Adv
figure below)
1 Analog Input
2 Program Setting
D5-04 Speed Lmt Value Speed Limit Value (% of -120–120% 0 Adv
E1-04)
D5-05 Speed Lmt Bias Speed Limit Bias (% of 0–120% 10 Adv
E1-04)
D5-06 Ref Hold Time Speed/Torque Switching 0–120% 0 Adv
Timer
*1: When speed limit selection (D5-03) is set to “1”, the master frequency reference input from
terminal 13, 14 or 16 becomes the speed limit selection (D5-03) is set to “2”, the set value
of D5-04 becomes the speed limit.
*2: When terminal 14 or 16 function selection is set to torque compensation (H3-09= “14”),
terminal 14 or 16 set value can be used as the torque compensation value.
Terminal Parameter
Number Number Setting Descrption
8 H1-06 39 Speed/torque control selection
13 B3-01 1 Frequency reference selection (terminals 13, 14, or
D5-03 1 16)
Speed limit selection (terminals 13, 14, or 16)
16/14 H3-05/H3-09 13 Torque reference/torque limit
1. When the speed/torque control selection contact is OFF, speed control is activated.
• Speed reference during speed control depends on the frequency reference selection (B3-01)
setting. To use terminal 13, 14 or 16 as the master frequency reference, set B3-01 to “1.”
• Torque limit during speed control is the smaller of the absolute value of terminal 14 or 16
torque limit, or the values set in the torque limit parameters (C7-01 to C7-04) is used as the
torque limit.
• When a stop command is given during speed control, speed control is maintained as the
motor decelerates to stop and the smaller of the absolute value of the terminal 16 torque
limit, or the values set in the torque limit parameters (C7-01 to C7-04) is used as the torque
limit.
2. When the speed/torque control selection is ON, torque control is activated.
• Speed limit during torque control is the master frequency reference at terminal 13, 14 or 16
when speed limit selection (D5-03) is set to “1”, and is the speed limit value (D5-04) when
Droop Control
The Drooping function reduces the motor speed based on the load torque of the motor. The actual
amount of motor speed reduction is based on the ratio of the amount of motor torque and maximum
output frequency (E1-04).
The Droop Delay Time D6-02 sets the response time for the drooping function. Decreasing the
Droop Delay Time will cause the response to become quicker, however, instability may occur.
Parmtr Access
Code Display Function Range Initial Value Level
D6-01 Droop Quantity Sets the motor speed 0.0 - 100.0 0 Adv
reduction when torque
output equals 100%
D6-02 Droop Delay Sets the response time for 0.03 - 2.0 sec 0.05 Adv
Time the drooping function
Parmtr Access
Code Display Function Range Initial Value Level
D8-01 Dwell Ref @ Start Sets Dwell frequency 0.0–150.0 Hz 0 Adv
reference at start.
D8-02 Dwell Time @ Start Sets the time duration for the 0.0–10.0 sec 0 Adv
Dwell function at start.
D8-03 Dwell Ref @ Stop Sets dwell frequency 0.0–150.0 Hz 0 Adv
Reference at stop.
D8-04 Dwell Time @ Stop Sets the time duration for the 0.0–10.0 sec 0 Adv
Dwell function at stop.
Parmtr Access
Code Display Function Range Initial Value Level
D9-01* S-Crv Acc @ Start Sets S-Curve time at Accel 0.00–2.50 sec 0.50 Adv
start
D9-02* S-Crv Acc @ End Sets S-Curve time at Accel 0.00-2.50 sec 0.50 Adv
end
D9-03* S-Crv Dec @ Start Sets S-Curve time Decel start 0.00–2.50 sec 0.50 Adv
D9-04 S-Crv Dec @ End Sets S-Curve time at Decel 0.00–2.50 sec 0 Adv
end
*Initial value is determined by X-Press Programming (Table 4.1 to 4.6).
CAUTION
Voltage/Frequency Pattern
Table 5.7:
Overvoltage Trip Braking Transistor
Inverter E1-01
Voltage Setting Trip Reset On Off Stall Level
230 150-255 400V 380V 380V 375V 380V
460 ≥400 800V 760V 760V 750V 760V
460 <400 720V 680V 660V 650V 670V
575 >500V 1040V 990V 990V 970V 960V
575 <500V 990V 940V 860V 840V 830V
Parameter E1-01 performs the above mentioned function in all three control modes.
E1-13 (2) Base Voltage Motor Base Voltage 0.0–510.0 V 0.0 User
If auto-tuning cannot be performed, some E2 constants can be calculated using the motor’s
nameplate information.
Motor rated slip frequency (E2-02) can be calculated by using the following equation:
Motor terminal resistance E2-05 can be calculated by using the following equation:
WARNING
Do not switch between motors when the drive’s output is on as it will damage the unit!
NOTE: *Fast-stop is selected, the stopping time is set by B5-08 (Fault stop time)
When the 3CH individual input is used, parameter B3-01 is automatically set to “1” (frequency
reference from control circuit terminal). The option/inverter reference selection, which is selected
by a multi-function contact input (H1-XX= “1E”), is disabled when using the AI-14B option.
Setting Function CH1 (TC1 to TC4 CH2 (TC2 to TC4) CH3 (TC3 to TC4)
0 3-channel individual input Substitute for terminals Substitute for terminals Substitute for
(factory default) 13 & 17 14 & 17 terminals 16 & 17
1 3-channel additonal input Sum of CH1 to CH3 input values is used as the frequency reference value
When the 3CH individual input is used, parameter B3-01 is automatically set to “1” (frequency
reference from control circuit terminal). The option/inverter reference selection, which is selected
by a multi-function contact input (H1-XX= “IE”), is disabled when using the AI-14B option.
Table 5.8:
Setting Terminal No. Description
TD5/TD11 Overcurrent (SC, OC, GF)
TD6/TD11 Overvoltage (OV)
0 TD7/TD11 Inverter overload (OL2)
8-Channel
TD8/TD11 Fuse blown (FU)
individual
TD9/TD11 Not used
(factory Default)
TD10/TD11 Inverter overheat (OH)
TD1/TD2 During zero-speed detection
TD3/TD4 During speed agree
TD5/TD11
TD6/TD11
Binary output*
TD7/TD11
1
TD8/TD11
binary output
TD9/TD11 During zero-speed detection
TD10/TD11 During speed agree
TD1/TD2 During run
TD3/TD4 Minor fault
* When F6-01 is set to binary output (setting = “1”), use the table on the following page to read the DO-08 output.
PO-36F Set-up
Digital Inputs
The IMPULSE•VG+ Series 2 has six multi-function contact inputs for the set-up of numerous
functions. The following table lists the function selections for the multi-function contact inputs
(terminals 3 to 8) and indicates the control modes during which each function can be enabled. An
OPEO3 error will occur if a function is programmed in more than one terminal at the same time.
.
Parmtr Ref Page Initial Access
Code Display Function Number Range Value Level
H1-01* Terminal 3 Sel Selects the multi-function 0 Adv
inputs.
(parameter)
H1-02* Terminal 4 Sel Same as H1-01 0–45 1 Adv
(parameter)
H1-03* Terminal 5 Sel Same as H1-01 0–45 7 Adv
(parameter)
H1-04* Terminal 6 Sel Same as H1-01 0–45 9 Adv
(parameter)
H1-05* Terminal 7 Sel Same as H1-01 0–45 24 Adv
(parameter
H1-06* Terminal 8 Sel Same as H1-01 0–45 E Adv
(parameter)
0 Multi-Step Ref 2 Multi-Step Speed 2. 5-3
1 Multi-Step Ref 3 Multi-Step Speed 3. 5-3
2 Multi-Step Ref 4 Multi-Step Speed 4. 5-3
3 Multi-Step Ref 5 Multi-Step Speed 5. 5-3
4 Speed Hold 2 Hold function (2nd step of 4-10
Three-Step Infinitely
Variable).
5 Accel Command Acceleration function (2nd 4-10
step of Two-Step Infinitely
Variable or 3rd step of Three-
Step Infinitely Variable).
Reference
Parmtr Page Initial Access
Code Display Function Number Range Value Level
H2-01 Terminal 9 Sel Assigns one of the following --- 0–40 0 Adv
48 multi-function digital
output parameters to
Terminal 9, 25, or 26.
H2-02 Terminal 25 Sel Terminal 1 on the G5OUT --- 0–40 0 Adv
Option Card
H2-03 Terminal 26 Sel Terminal 2 on the G5OUT --- 0–40 7F Adv
Option Card
0 Brake Output Closed when voltage or n/a
frequency is output
1 Zero Speed Closed when below B2-02 or 5-95
D1-01
2 Fref/Fout Agree 1 Output when Frequency 5-95
Reference and Frequency
Output agree
3 Fref/Set Agree 1 Output when Output 5-95
Frequency Reference equals
L4-01.
4 Freq Detect 1 Closed when output 5-96
frequency is < L4-01.
5 Freq Detect 2 Closed when output 5-96
frequency is > L4-01.
6 Inverter Ready Closed when an inverter is n/a
not in a fault state
7 DC Bus Undervolt Closed when DC Bus voltage n/a
drops belowUV trip point.
8 BaseBlk 1 Closed when the inverter is n/a
not outputting voltage.
9 Option Reference Closed when the frequency 5-107
reference is input from the
digital operator.
A Remote Operation Closed when the RUN 5-107
command is input from the
digital operator.
B Trq Det 1 N.O. Output when torque > L6-02 5-97
C Loss of Ref Closed when inverter has 5-96
detected a loss of frequency
reference
D DB Overheat Closed when inverter n/a
displays “RH” or “RR” fault.
E Fault Closed during a major fault. 6-3
F Not Used No function
10 Minor Fault Closed during minor fault or 6-3
alarm.
Before you start to program this feature, you may find it convenient to first photocopy the “Binary-
to-Hexadecimal Conversion Worksheet” in this section. By being able to write in the worksheet’s
boxes, you will find it easier to program the feature.
Programming Digital Outputs—Fault Annunciate requires that you determine two 4-digit binary
numbers and then convert these numbers to two 1-digit hexadecimal numbers. You enter the
hexadecimal numbers when you program the drive.
For example, if you selected Set 2, you would enter “1 0” in the first two columns from the left,
which would represent the first two digits of the first binary number that you would convert later.
First digit from the left Second digit from the left
1 or 0 1 or 0 1 or 0 1 or 0 1 or 0 1 or 0 1 or 0 1 or 0
10. Determine which fault outputs should be enabled. To enable a fault output, enter 1 in the box
above the fault output; otherwise, enter 0. Do this for each fault output in the set.
For example, if Set 2 is selected and LL1 and UL1=1, “1 0 0 0” and “1 0 1 0 “ would be the
two 4-digit binary numbers.
11. Using the conversion table below, determine the 1-digit hexadecimal number for both
4-digit binary numbers.
Table 5.11
Hexadecimal
Binary Number Number
0000 0
0001 1
0010 2
0011 3
0100 4
0101 5
0110 6
0111 7
1000 8
1001 9
1010 A
1011 B
1100 C
1101 D
1110 E
1111 F
Table 5.12
External Fault Selection
Input Level MFI Setting
Selection Dectection Method External Fault Action Result
During Ramp to Alarm
N.O. N.C. Always Run Stop Coast to Stop Fast-stop* Only
√ √ √ 20
√ √ √ 24
√ √ √ 28
√ √ √ 2C
√ √ √ 22
√ √ √ 26
√ √ √ 2A
√ √ √ 2E
√ √ √ 21
√ √ √ 25
√ √ √ 29
√ √ √ 2D
√ √ √ 23
√ √ √ 27
√ √ √ 2B
√ √ √ 2F
NOTE: (1) N.O. = normally open contact; N.C. = normally closed contact
(2) Setting 24 is the factory default
NOTE: After changing any H5 parameter, power to the inverter must be cycled.
NOTE: After initial communication, if the inverter is not communicated with for 2 seconds, a
communication fault will occur (CE Memobus ERR).
Motor Overload
The IMPULSE•VG+ Series 2 protects against motor overload with a UL-recognized, built-in
electronic thermal overload function.
The electronic thermal overload function estimates motor temperature, based on inverter output
current, frequency and time to protect the motor from overheating. When the thermal overload fault
is activated, an “OL1” trip occurs, shutting OFF the inverter output and preventing excessive
overheating in the motor. As long as the inverter is powered up, it continues to calculate the motor
temperature.
When operating with one inverter connected to one motor, an external thermal relay is not needed.
When operating several motors with one inverter, use the internal thermal protection from the motor
or install an external thermal overload relay on each motor. In this case, set parameter L1-01 to “0.”
CAUTION
This function automatically adjusts the output frequency, acceleration and/or deceleration rates
in order to continue operation without tripping or “stalling” the inverter.
If deceleration times are set too short for load conditions, the inverter automatically extends the
deceleration time according to the main circuit DC bus voltage level. When using an optional
braking resistor for the IMPULSE•VG+ Series 2, set parameter L3-04 to “0.” See the figure on next
page.
Table 5.13
Setting Description
0 Stall prevention during deceleration is disabled (factory default). An excessively
(Disabled) short deceleration time will generate an overvoltage fault (OV), and the inverter
will stop.
1 Stall prevention during deceleration is enabled.
(General Purpose) The DC bus voltage level is monitored, and the deceleration rate is automatically
extended to prevent an overvoltage condition. This deceleration rate may be
longer than the set value (B5-02).
Sets the detection level for the desired frequency agree 1 and frequency detection 1 and 2 functions.
The set detection level is effective during both FWD and REV operation.
Sets the detection width for frequency and desired frequency agree 1 and frequency detection 1 and
2 functions.
Sets the detection level for the desired frequency agree 2 and frequency detection 3 and 4 functions.
The set detection level is effective during either FWD or REV operation, depending on the set
detection level (positive value for FWD operation, negative value for REV operation).
Sets the dectection width for frequency and desired frequency agree 2 and frequency detection 3
and 4 functions.
Table 5.14
Setting Description
0 Overtorque detection is disabled (factory default).
1 Overtorque detection is enabled whenever at the speed agree level (when inverter
is not accelerating or decelerating). Continue running after detection (OL3
alarm).
2 Overtorque detection is enabled always. Continue running after detection (OL3
alarm).
3 Overtorque detection is enabled whenever at the speed agree level. Coast to a
stop after detection (OL3 fault).
4 Overtorque detection is enabled always. Coast to a stop after detection (OL3
fault).
Table 5.15:
Setting Description
0 Overtorque detection is disabled (factory default).
1 Overtorque detection is enabled whenever at the speed agree level (when inverter
is not accelerating or decelerating). Continue running after detection (OL4
alarm).
2 Overtorque detection is enabled always. Continue running after detection (OL4
alarm).
3 Overtorque detection is enabled whenever at the speed agree level. Coast to a stop
after detection (OL4 fault).
4 Overtorque detection is enabled always. Coast to a stop after detection (OL4
fault).
Overtorque detection 2 functions the same as overtorque detection 1 (L6-01), except that “OL4” is
displayed on the digital operator instead. This function is used when two types of detection are
output to the multi-function output terminals.
* To program constant L9-04 and L9-05, refer to the example on the following page and follow
steps 1 through 4:
1. Sign 1 to each fault code that you wish to enable the auto reset.
2. Sign 0 to each fault code that you wish to disable the auto reset.
3. Convert all Digits (1 to 4) from binary to hex.
4. Program L9-04 and L9-05 by entering the hex number obtained from step 3.
Table 5.16
Digit 4 Digit 3 Digit 2 Digit 1
HEX 2 0 0 1
Binary 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 1
L9-04 D P O R L P O O O S O G O U U U
E G S H F F L L H C V F C V V V
V O 2 1 3 2 1
HEX 0 0 8 0
Binary 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0
L9-05 S C C E E E E E E
– – – – – – – V E A F F F F F F
E L 8 7 6 5 4 3
L
Table 5.17
L9-04 Binary HEX
Digit 4 0010 2
Digit 3 0000 0
Digit 2 0000 0
Digit 1 0001 1
Table 5.18
Hexadecimal
Binary Number Number
0000 0
0001 1
0010 2
0011 3
0100 4
0101 5
0110 6
0111 7
1000 8
1001 9
1010 A
1011 B
1100 C
1101 D
1110 E
1111 F
Monitor Selection
The top level in the operation mode allows the viewing of four monitor variables. They are Fref,
Fout, Iout, and User-Selected monitor. This user-selected monitor can be selected from the
following table. See Monitor Parameters table on page 5-109 for available monitors by control
method.
Table 5.19
Setting (O1-03) Description
00000 Unit: 0.01Hz (factory default)
00001 Unit: 0.01%
00002 to 00039 Unit: rpm (set O1-03 equal to the number of motor poles)
00040 to 39999 Digits: 5th 4th 3rd 2nd 1st
(user-selected units) 0 0 0 0 0
The first through fourth digits determine the set value at 100% output frequency.
Decimal point position is set by the fifth digit as follows:
5th digit = 0: displayed as 0000
5th digit = 1: displayed as 000.0
5th digit = 2: displayed as 00.00
5th digit = 3: displayed as 0.000
Example 1
If 100% output frequency is equal to 200.0 units: Set O1-03=”12000”; 100% of
this reference is displayed as 200.0 and 60% of this reference is displayed as
120.0.
Example 2
If 100% output frequency is equal to 65.00: Set O1-03=”26500”; 60% of this
reference is displayed as 39.00.
Parmtr
Code Display Function Units Access Level
Monitor
U1-01 Frequency Ref Frequency Reference Hz Operation
U1-02 Output Frequency Inverter Output Frequency Hz User Program
U1-03 Output Current Inverter Output Current A User Program
U1-04 Control Method Displays the value of A1-02 n/a User Program
U1-05 Motor Speed Motor Speed Hz User Program
U1-06 Output Voltage Inverter Output Voltage V User Program
(Reference)
U1-07 DC Bus Voltage DC Bus Voltage (Measured) V User Program
U1-08 Output kWatts Inverter Output Power kW User Program
(Calculated)
U1-09 Torque Reference Torque Reference (Internal) % User Program
U1-10 Input Term Sts Input Terminal Status (See page n/a User Program
5-111 for a detailed description.)
U1-11 Output Term Sts Output Terminal Status (See n/a User Program
page 5-112 for a detailed
description.)
U1-12 Int Ctl Sts 1 Operation Status (See page 5-113 n/a User Program
for a detailed description.)
U1-13 Elapsed Time Elapsed Time. See O2-07 and hours User Program
O2-08.
U1-14 Flash ID Flash ROM software ID number n/a User Program
U1-15 Terminal 13 Level External Terminal 13 input level V Advanced
U1-16 Terminal 14 Level External Terminal 14 input level V/mA Advanced
U1-17 Terminal 16 Level External Terminal 16 input level V Advanced
U1-18 Mot SEC Current Motor secondary current (lq). A Advanced
U1-19 Mot EXC Current Motor excitation current (ld). A Advanced
U1-20 SFS Output Primary freq. after the SFS Hz Advanced
U1-21 ASR Input Monitors the input to the speed % Advanced
regulator.
100%=FMAX
U1-22 ASR Output Monitors the output from the % Advanced
speed regulator.
The motor’s secondary current
corresponds to 100%.
U1-23 Speed Deviation Monitors the speed deviation % Advanced
within the speed regulator.
FMAX=100%
U1-24 PID Feedback PID feedback signal level % Advanced
U1-25 G5IN4 Reference See page 5-45. Hex Advanced
U1-26 Voltage Reference (Vq) Motor secondary voltage V Advanced
reference
U1-27 Voltage Reference (Vd) Motor excitation voltage V Advanced
reference
U1-28 CPU ID CPU software ID number n/a Advanced
Fault Trace
U2-01 Current Fault Displays current fault User Program
U2-02 Last Fault Displays last fault detected User Program
U2-03 Frequency Reference Freq ref when fault was detected Hz User Program
U2-04 Output Frequency Output freq when fault was Hz User Program
detected
U2-05 Output Current Output current when fault was A User Program
detected
U2-06 Motor Speed Motor Speed when the “Last User Program
Fault” occurred
U2-07 Output Voltage Output voltage when fault was V User Program
detected
U2-08 DC Bus Voltage DC Bus voltage when fault was V User Program
detected
U2-09 Output kWatts Output power when fault was kW User Program
detected
U2-10 Torque Reference Torque Reference when the User Program
“Last Fault” occurred
U2-11 Input Terminal Sts Input terminal status when fault n/a User Program
was detected
U2-12 Output Terminal Sts Output terminal status when fault n/a User Program
was detected
U2-13 Inverter Status Inverter status before fault was n/a User Program
detected
U2-14 Elapsed Time Elapsed time when fault was hours User Program
detected
Fault History
U3-01 Last Fault Most recent fault User Program
U3-02 Fault Message 2 2nd most recent fault User Program
U3-03 Fault Message 3 3rd most recent fault User Program
U3-04 Fault Message 4 4th most recent fault User Program
U3-05 Elapsed Time 1 Elapsed time of most recent fault User Program
U3-06 Elapsed Time 2 Elapsed time of 2nd most recent User Program
fault
U3-07 Elapsed Time 3 Elapsed time of 3rd most recent User Program
fault
U3-08 Elapsed Time 4 Elapsed time of 4th most recent User Program
fault
U3-09 AC Operations Total number of RUN commands User Program
received since the AC counter
was last cleared (03-02)
Troubleshooting
IMPULSE•VG+ Series 2
This page intentionally left blank.
Troubleshooting the Drive
In this troubleshooting section, “check,” means investigating whether an item is functioning and in
an acceptable physical condition, and then taking corrective action (adjusting, fixing, replacing,
etc.) as necessary. In the Corrective Action column, you may not have to perform all of the steps to
correct the problem.
BE0 Brake answer back signal is lost during run. 1. Check brake answer back circuit.
Brake Ans Lost While running, the multi-function input brake
answer back is lost. 2. Check terminal status. (U1-10)
BE1 Torque Proving Minor Fault. The BE1 fault 1. Please reference troubleshooting
Rollback detect indicates that the drive has released the brake, but encoder related faults on page 6-16.
not started to accelerate the motor when it detects
more than the expected encoder feedback. A BE1
fault will occur if the pulses received during the BE1
detection time (C8-04) are greater then the expected
number of pulses (C8-05).
CALL Serial Communication SI-B Transmission Fault. 1. Check serial device connections.
Serial Com Call Control data is not received correctly after power 2. Ensure drive is properly programmed
supply is turned ON for 2 sec. for serial communication.
CE Communication Error. Serial communications 1. Check serial connections (6 CN).
disruption.
Memobus Com Err 2. Check H5-01 through H5-05 for
proper programming.
CPF00 Control Circuit Fault 1— Keypad Transmission. 1. Check the keypad connection.
Com-Err (OP&INV) Because of external noise, excessive vibration or 2. Replace keypad.
shock, or component failure (including RAM and
PROM), one or both of the following occurs: 3. Replace Control board.
• Transmission between the inverter and keypad
cannot be established 5 sec after power-up.
• MPU peripheral element check fault (on-line).
EF3 External fault occurs in the Terminal 3 external 1. Check constant H1-01 for proper
External control circuit. programming.
Fault 3 2. Check the condition of the input
terminal #3 on G5IF card.
EF4 External fault occurs in the Terminal 4 external 1. Check constant H1-02 for proper
External control circuit. programming.
Fault 4 2. Check the condition of the input
terminal #4 on G5IF card.
External fault occurs in the Terminal 5 external 1. Check constant H1-03 for proper
EF5 control circuit. programming.
External
Fault 5 2. Check the condition of the input
terminal #5 on G5IF card.
EF6 External fault occurs in the Terminal 6 external 1. Check constant H1-04 for proper
External control circuit. programming.
Fault 6 2. Check the condition of the input
terminal #6 on G5IF card.
EF7 External fault occurs in the Terminal 7 external 1. Check constant H1-05 for proper
External control circuit. programming.
Fault 7 2. Check the condition of the input
terminal #7 on G5IF card.
EF8 External fault occurs in the Terminal 8 external 1. Check constant H1-06 for proper
External control circuit. programming.
Fault 8 2. Check the condition of the input
terminal #8 on G5IF card.
ERR EEPROM Read/Write Fault. EEPROM internal 1. Cycle Power.
EEPROM data did not match when initializing the parameter. 2. User initialize (A1-05=1110).
R/W Err
3. Replace Control board.
FAN Cooling fan fails while power is on. 1. Remove any debris from fan.
Fan Fault 2. Check fan wiring.
3. Replace fan (contact Electromotive
Systems).
GF During operation, the inverter sums the currents of 1. Disconnect motor from drive and
Ground Fault all three motor phases. Ideally, the sum should check it for shorts using a megger.
always equal zero. If the sum is greater than 50% of
the inverter rated output current, a GF occurs. 2. Ensure that R/C Surge Suppressors are
used across all brake contactor coils to
prevent disturbance by electrical
transients.
LCI Load Check Fault. Load is greater than specified 1. Reduce Load.
Load Check Err amount.
2. Check Load Check sequence set-up.
(C5-XX).
LF An open phase occurred at the inverter output. 1. Check for broken wires in output
Output Pha Loss cable.
2. Check for open winding in the motor.
3. Check for loose terminals
LL1 Lower Limit 1—SLOW DOWN 1. May not require corrective action.
Lower Limit 1 Err Indicator. Lower Limit 1—SLOW DOWN is input 2. Check the Limit Switches position.
(switch status is changed).
3. Check the Limit Switches condition.
OH1 Overheat Fault. There are two situations that result 1. Ensure that the heat sink cooling fans
Heatsink MaxTemp in an overheat fault. The first occurs when the are functioning.
measured heat sink exceeded 105°C. The second is a
result of a fault in the internal 24VDC cooling fan. 2. Ensure that the heat sink is free from
dirt and debris.
3. Ensure that the inverter’s ambient
temperature is within specification.
4. Replace the 24VDC fan
5. Replace the heat sink thermistor(s)
OL1 Motor Overload Fault. Inverter output exceeded 1. Ensure drive is programmed with
the motor overload level. proper motor full load Amp (E2-01).
Motor Overloaded
2. Reduce the load.
OL2 Inverter Overload Fault. Inverter output exceeded 1. Reduce the load.
the inverter overload level.
INV Overloaded 2. Extend the acceleration time.
OL3 Overtorque Detection Level 1 Fault. Defined by 1. Check for proper programming for
L6-02. Alarm defined by L6-01. L6-XX constant.
Overtorque
Det 1
OL4 Overtorque Detection Level 2 Fault. Defined by 1. .Check for proper programming for
Overtorque L6-05. Alarm defined by L6-04. L6-XX constant.
Det 2
OP Keypad Digital Monitor Fault. Digital monitor 1. Remove power and remount keypad.
unit in keypad fails, or the keypad is mounted when
in the program mode or during operation by the
operator.
OP3 Optional Card Fault. Optional card is 1. Replace optional card.
incompatible or has failed.
OPE01 kVA Setting Fault. Inverter kVA setting range is 1. Check 02-04 constant for proper kVA.
kVA Selection incorrect.
OPE06 Missing PG Card. A closed loop control method 1. Install the required option card.
PG Opt Missing was selected, and the required PG feedback card is 2. Remove power and reset the option
not installed. card.
3. Check the A1-02, control method,
program setting
OPE07 Multi-Function Analog Input Setting Fault. H3- 1. Check the function selections.
Analog Selection 05 and H3-09 multi-Function analog input settings
are set to the same value.
OPR Keypad Disconnected. The keypad is removed 1. Secure the keypad.
Oper Disconnect while the inverter is running, and the run command 2. Verify O2-06 setting.
was initiated via the keypad RUN key.
OS Overspeed Fault. The motor has exceeded the 1. Check the Automatic Speed Regulator
Over Speed programmed detection level and time. This is settings, D4 sub group.
typically caused by a overshoot condition due to an
over-responsive ASR loop. If the drive is 2. Check for rapid load changes
programmed to flux vector “torque control” mode, 3. Verify proper encoder PPR setting,
and no load is present, an overspeed fault will F1-01.
typically occur.
OV Overvoltage Fault. The main circuit direct current 1. Extend the deceleration time.
voltage exceeded the overvoltage level. Detection
DC Bus Overvolt 2. Check for proper DBU operation.
level:
230V class—approx. 400V 3. Check the resistor.
460V class—approx. 800V 4. Check the line voltage.
575V class—approx. 1000V
Overvoltage Fault. Overvoltage occurs during 1. Check the line voltage.
OV (blinks) stop. Main circuit DC voltage rises above the
DC Bus Overvolt detection level while the drive output is off.
Detection level: 410V or more for 230V, 820V or
more for 460V and 1040V or more for 575V.
PF Input Phase Loss Fault. Inverter input power 1. Check the line voltage.
supply has open phase.
Input Pha Loss 2. Remove power.
3. Retighten the input terminal screws.
PGO Pulse Generator Signal Missing Fault. The 1. Check for proper direction of encoder
PG Open inverter detected a loss of encoder feedback. feedback.
2. Please reference troubleshooting
encoder related faults on page 6-13.
PGO2 Pulse Generator Signal Monitor Fault. This fault 1. Check for proper direction of encoder
is set by either the encoder monitor or encoder feedback.
backup function.
2. Please reference troubleshooting
encoder related faults on page 6-14.
Definition
Speed deviation faults mean that the drive output is not following the commanded speed reference.
This is possible if there is not enough torque available to follow the internal speed reference.
Therefore, speed deviations will typically occur when the drive is at its programmed torque limit. In
addition, if the drive receives erratic, or missing, encoder pulses, speed deviations are also possible.
If the initial drive tuning and start-up of the system was successfully completed and the crane has
been in operation without any faults, then the occurrence of this fault most likely indicates that
something mechanical with the system has changed or drive parameters were changed (i.e., failed
encoder, load snag, crane overload, change in acceleration or deceleration times, etc.).
Corrective Action
1. Do NOT continue to operate the hoist.
NOTE: Continued attempts to operate the hoist with speed deviation faults occurring can
result in loss of control of the load under certain circumstances.
2. As a precaution the load float time, parameter C8-10, should be set to zero until the source of the
speed deviation fault has been determined and corrected.
3. Verify if the load has snagged or if there is a load on the hook that exceeds capacity.
4. Check the alignment of the encoder pulse wheel with the sensor head, or the encoder shaft
coupling (depending on the type of encoder used). If the pulse wheel is misaligned or the shaft
coupling is loose the drive will get erratic pulse signals or no signals at all causing a speed
deviation fault or PGO (Pulse Generator Open) fault. Repairs to the encoder wheel or shaft
coupling should be made immediately before again attempting to operate the hoist.
5. If the encoder appears to have no mechanical problems, the encoder cable should be checked for
damage and replaced if a problem is found.
5.1 Each of the encoder wires should be checked for continuity.
5.2 The wires should be checked for shorts between any two wires.
5.3 The wires should be checked for shorts to the shield or ground.
5.4 Visually inspect the cable for damage that may be causing intermittent problems.
6. If the encoder feedback system checks out mechanically and electrically, then the last physical
check to make is for something in the mechanical system that might be resisting normal
operation. One example may be the brake is not opening fully and is causing enough drag to
prevent the system from operating at commanded speed.
Definition
The pulse generator signal missing fault indicates that the drive has detected a loss of encoder
feedback. This fault will typically occur if the drive doesn’t receive any encoder feedback
pulses while it is commanded to run.
Corrective Action
1. Do NOT continue to operate the hoist.
NOTE: Continued attempts to operate the hoist with PGO faults occurring can result in
loss of control of the load under certain circumstances.
2. As a precaution, the load float time, parameter C8-10, should be set to zero until the source
of the PGO Fault has been determined and corrected.
3. Check the alignment of the encoder pulse wheel with the sensor head, the encoder shaft
coupling (depending on the type of encoder used), or check for a failed encoder sensor
head. If one of these conditions exist the drive will get erratic pulse signals or no signal at
all causing a speed deviation fault or PGO fault. Repairs to the encoder wheel or shaft
coupling should be made immediately before again attempting to operate the hoist.
4. If the encoder appears to have no mechanical problems, the encoder cable should be
checked for damage and replaced if a problem is found.
4.1 Each of the encoder wires should be check for continuity.
4.2 The wires should be checked for shorts between any two wires.
4.3 The wires should be checked for shorts to the shield or ground.
4.4 Visually inspect the cable for damage that may be causing intermittent problems.
5. If the encoder feedback system checks out, then check for physical obstruction to motor
rotation such as brake failing to open.
Definition
The Pulse Generator signal monitor fault indicates that the drive has detected a problem with the
encoder. This fault may be generated by the encoder monitor function or the encoder backup
function. In the encoder monitor function, if the motor shaft is told to move forward a number of
pulses at a calculated frequency, the drive expects to see those counts forward in C8-21 time or less.
If it does not, the drive sets a PGO2 Fault indicating a problem with the PG Circuit. In the encoder
backup function, this fault is generated when the multi-function input has changed state and the
encoder position has remained constant. Additionally this fault condition needs to be present for
multiple consecutive changes in state of the multi-function input. The number of times required is set
in F1-18.
Corrective Action
1. Do NOT continue to operate the hoist.
NOTE: Continued attempts to operate the hoist with PGO2 faults occurring can result in loss
of control of the load under certain circumstances.
2. As a precaution, the load float time, parameter C8-10, should be set to zero until the source of
the PGO fault has been determined and corrected.
3. Check the alignment of the encoder pulse wheel with the sensor head, the encoder shaft coupling
(depending on the type of encoder used), or check for a failed encoder sensor head. If one of
these conditions exist the drive will get erratic pulse signals or no signals at all causing a speed
deviation fault or PGO fault. Repairs to the encoder wheel or shaft coupling should be made
immediately before again attempting to operate the hoist.
4. If the encoder appears to have no mechanical problems, the encoder cable should be checked for
damage and replaced if a problem is found.
4.1 Each of the encoder wires should be checked for continuity.
4.2 The wires should be checked for shorts between any two wires.
4.3 The wires should be checked for shorts to the shield or ground.
4.4 Visually inspect the cable for damage that may be causing intermittent problems.
5. If the encoder feedback system checks out, then check for a physical obstruction to motor
rotation such as a brake failing to open.
6. If there is no physical problem detected, then adjust the parameters for the encoder monitor (C8-
18–C8-21) or encoder backup function (F1-16–F1-18) as necessary.
7. After the corrective action has been taken and the fault no longer occurs then the load float time,
C8-10, can be set back to its initial value.
Definition
Noisy encoder faults indicate that the drive has detected erratic encoder feedback. The drive
continuously monitors the quality of the encoder feedback. If the encoder feedback exhibits erratic
feedback for a period of time (set in B7-01) then this fault will be displayed.
Corrective Action
1. Do NOT Continue to operate the hoist.
NOTE: Continued attempts to operate the hoist with SVR faults occurring can result in loss of
control of the load under certain circumstances.
2. As a precaution, the load float time, parameter C8-10, should be set to zero until the source of
the SVR fault has been determined and corrected.
3. Check the alignment of the encoder pulse wheel with the sensor head, or the encoder shaft
coupling (depending on the type of encoder used). If the pulse wheel is misaligned or the shaft
coupling is loose the drive will get erratic pulse signals or no signals at all possibly causing an
SVR fault. Repairs to the encoder wheel or shaft coupling should be made immediately before
again attempting to operate the hoist.
4. If the encoder appears to have no mechanical problems, the encoder cable should be checked for
damage and replaced if a problem is found.
4.1 Each of the encoder wires should be checked for continuity.
4.2 The wires should be checked for shorts between any two wires.
4.3 The shield should be checked for proper grounding.
4.4 The wires should be checked for shorts to the shield or ground.
4.5 Visually inspect the cable for damage that may be causing intermittent problems.
5. If none of the above steps has identified a valid problem(s), only then should the SVR delay
timer setting be adjusted.
NOTE: It is desirable to have as fast a fault no longer occurs then the load float time, C8-10,
can be set back to its initial value.
6. After the corrective action has been taken and the fault no longer occurs then the load float time,
C8-10, can be set back to its initial value.
Definition
The BE1 fault indicates that the drive has released the brake, but has not started to accelerate the
motor when it detects more than the expected encoder feedback. A BE1 fault will occur if the pulses
received during the BE1 detection time (C8-04) are greater than the expected number of pulses (C8-
05). This is typically caused by the drive/motor have insufficient torque to suspend the load.
Correction Action
1. For reference, see timing diagram on page 5-40.
2. Check the encoder cable for damage and proper grounding. Replace it if a problem is found.
2.1 Each of the encoder signals should be checked for excessive noise.
2.2 The shielded encoder cable should be properly grounded.
2.3 Visually inspect the cable for damage that may be causing intermittent problems.
3. Check the alignment of the encoder pulse wheel with the sensor head, or the encoder shaft
coupling (Depending on the type of encoder used). If the pulse wheel is misaligned or the shaft
coupling is loose the drive may get erratic pulse signals possibly causing a BE1 fault. Repairs to
the encoder wheel or shaft coupling should be made immediately before again attempting to
operate the hoist.
4. If none of the above steps has identified a valid problem(s), only then should the BE1 detection
parameters be adjusted.
NOTE: It is desirable to have as fast a fault reaction time as possible without causing
nuisance trips.
5. Increase C8-05 to no more than 800.
Definition
The BE3 fault indicates that the drive has released the brake and commanded the drive to run, but
has not detected the expected encoder feedback. A BE3 fault will occur if the pulses received during
the BE3 detection time (C8-06) are less than the expected number of pulses (C8-07).
NOTE: Depending on the condition of the crane and control system, the load may drift during the
BE3 detection time until the brake is again set. If giving a run command, the BE3 fault
should be detected before a PGO fault would be detected.
Corrective Action
1. For reference, see timing diagram on page 5-41.
2. Check the brake for proper operation. If the brake does not open the drive will not see the proper
number of encoder pulses returned and will post this fault.
3. Check the alignment of the encoder pulse wheel with the sensor head, or the encoder shaft
coupling (depending on the type of encoder used). If the pulse wheel is misaligned or the shaft
coupling is loose the drive will get erratic pulse signals or no signals at all possibly causing a
BE3 fault. Repairs to the encoder wheel or shaft coupling should be made immediately before
again attempting to operate the hoist.
Definition
The BE6 alarm indicates that the drive has commanded the brake to set but it has detected more than
the expected encoder feedback. A BE6 alarm will occur if the number of pulses received during the
BE6 detection time (C8-12) is greater than the expected number of pulses (C8-13).
NOTE: This fault typically indicates a failed brake. Power should NOT be removed while this
fault is active and the load should be moved to a safe location and lowered before
proceeding with any corrective action.
Corrective Action
1. For reference, see timing diagram on page 5-43.
2. Check the brake for proper operation and adjustment. If the brake does not set, is improperly
adjusted or is excessively worn, it may not be able to hold the load. This will allow the encoder
pulses received during the detection time to exceed the set point.
3. Check the encoder cable for damage and proper grounding. Replace it if a problem is found.
3.1 Each of the encoder signals should be checked for excessive noise.
3.2 The shielded encoder cable should be properly grounded.
3.3 Visually inspect the cable for damage that may be causing intermittent problems.
4. Check the alignment of the encoder pulse wheel with the sensor head, or the encoder shaft
coupling (Depending on the type of encoder used). If the pulse wheel is misaligned or the shaft
coupling is loose the drive may get erratic pulse signals possibly causing a BE6 fault. Repairs to
the encoder wheel or shaft coupling should be made immediately before again attempting to
operate the hoist.
5. If none of the above steps has identified a valid problem(s), only then should the BE6 detection
parameters be adjusted.
NOTE: It is desirable to have as fast a fault reaction time as possible without causing
nuisance trips.
Definition
An over current fault is caused if the output current exceeds 200% of the inverter rated output
current. This fault can be caused by short circuits in the wiring or in the motor, and it can also be
caused by parameters that are not adjusted properly. One other cause of this alarm could be erratic or
no encoder feedback. In the last instance, the drive is trying to command the motor to hold a position
but due to the encoder problem, is unable to find the correct position. This would cause the drive to
increase current output to the motor in an attempt to correct the position until an over current fault
occurs.
Corrective Action
1. Check the motor wiring and the motor itself for a short between phases.
2. Check the alignment of the encoder pulse wheel with the sensor head, or the encoder shaft
coupling (depending on the type of encoder used). If the pulse wheel is misaligned or the shaft
coupling is loose the drive will get erratic pulse signals or no signals at all possibly causing an
OC fault. Repairs to the encoder wheel or shaft coupling should be made immediately before
again attempting to operate the hoist.
3. If the encoder appears to have no mechanical problems, the encoder cable should be checked for
damage and replaced if a problem is found.
3.1 Each of the encoder wires should be check for continuity.
3.2 The wires should be checked for shorts between any two wires.
3.3 The shield should be check for proper grounding.
3.4 The wires should be checked for shorts to the shield or ground.
3.5 Visually inspect the cable for damage that may be causing intermittent problems.
4. If none of the above steps has identified a valid problem(s), check if any of the torque limit
parameters (C7-01 to C7-04) have been changed. If these parameters have been changed to
allow a higher torque value, it could cause over current trips.
NOTE: Changing these parameters could also induce speed deviation or overload faults.
Only a trained technician should modify these parameters. It is desirable to have as
fast a fault reaction time as possible without causing nuisance trips.
WARNING
Do NOT touch any circuit components while AC main power is on or immediately after the
main AC power is disconnected from the unit. You must wait until the red “CHARGE” lamp
is extinguished. It may take as long as 10 minutes for the charge on the main DC bus
capacitors to drop to a safe level. Failure to adhere to this warning could result in serious
injury.
Figure 6-1
Servicing
IMPULSE•VG+ Series 2
This page intentionally left blank.
Service
This chapter includes information pertaining to on-call service, drive identification, troubleshooting,
and warranty. Before you install, troubleshoot, or service the drive, we highly recommend that you
read this entire chapter. Doing this will help assure quick service response, minimize your on-site
repair costs, and reduce crane downtime.
Your IMPULSE•VG+ Series 2 drive includes a two-year warranty from date of shipment. The
warranty is described in detail later in this chapter.
On-Call Service
If you ever require our assistance, contact us at (800) 288-8178; our fax number is (800) 298-3508.
Technical support is available 24 hours a day, seven days a week, and 365 days a year. If necessary,
we can arrange to have a Service Technician visit your site to evaluate the situation.
MODEL NO.:
Figure 6.1
This nameplate is normally located on the side of the drive nearest to the keypad.
Service Policy For Small Drives, DBUs, and Other Electrical Components
This section explains Electromotive Systems’ service policy for the small drives (2006-FVG+
through 2224-FVG+ and 4001-FVG+ through 4165-FVG+ and 5003-FVG+ through 5099-FVG+),
dynamic braking units (DBUs), and other electrical components.
Should your IMPULSE product fail during the warranty period, Electromotive Systems will repair or
replace your unit within 72 hours (3 working days). In most cases, we can supply a replacement unit
within 24 hours (1 working day). If the problem is not covered under warranty, you are responsible
for the cost of the repairs and the shipping charges.
To return a failed unit (or part):
1. Request a Return Authorization (RA) from Electromotive Systems’ Service Department, as a
condition for us to repair or replace the unit. Return the failed unit to Electromotive Systems via
pre-paid freight. When you call, please have the serial number of the drive available and be
prepared to provide the information requested on the Return Authorization Information Sheet
found on page A-5.
2. A purchase order or credit card is required to cover the cost of the replacement unit or repairs to
a returned unit.
Company’s sole liability shall be to repair at its factory, or replace any item returned to it within two
years from date of shipment, which Company finds to contain defective material or workmanship.
All items to be repaired or replaced shall be shipped to Company (Note: return authorization by
Company is required) within said two year period, freight prepaid, as a condition to repair or replace
defective material or workmanship. Company’s herein assumed responsibility does not cover
defects resulting from improper installation, maintenance, or improper use. Any corrective
maintenance performed by anyone other than the Company during the warranty period shall void the
warranty. Company shall not be liable for damages of any kind from any cause whatsoever beyond
the price of the defective Company supplied items involved. Company shall not be liable for
economic loss, property damage, or other consequential damages or physical injury sustained by the
purchaser or by any third party as a result of the use of any Company supplied items or material.
Company neither assumes nor authorizes any other person to assume for Company any other
liability in connection with the sale or use of items sold by Company.
Materials or items may not be returned for credit, without the prior written consent of the Company.
Any authorized return of materials or items shall be subject to a restocking charge equal to 25% of
the net invoiced amount ($100 minimum charge for all control products) after Company determines
that the material or item is in resalable condition. If upon receipt of the material or items returned,
the Company determines that said material or items cannot be resold without alteration or service,
the Company reserves the right to reject the returned materials or items and to send the same back to
said purchaser at purchaser’s expense.
Any claim for errors in shipment or for material or time shortages must be received by Company
within 30 days of shipment and must be accompanied by copies of the bill of lading and packing slip.
Factory Ref
No. Parameter Name Default Page#
A1-01 Access Level 2 4-9
A1-02 Control Method 3 4-9
A1-03 Motion 0 or 2 4-10
A1-04 Speed Ref 6 4-10
A1-05 Init Parameters 0 4-14
A1-06 Password 1 0 4-14
A1-07 Select Password 1 0 4-14
A2-01 to A2-30 User Parameters --- 4-14
B1-01 Reference 1 15 5-3
B1-02 Reference 2 30 5-3
B1-03 Reference 3 60 5-3
B1-04 Reference 4 45 5-3
B1-05 Reference 5 60 5-3
B1-06 Reference 6 0.0 5-3
B1-07 Reference 7 0.0 5-3
B1-08 Reference 8 0.0 5-3
B1-09 Jog Reference 6 5-3
B1-10 Ref Priority 0 5-3
B2-01 Ref Upper Limit 100.0 5-5
B2-02 Ref Lower Limit 2 5-5
B2-03 Upper Limit Gain 100 5-5
B3-01 Reference Source 1 5-6
B3-02 Run Source 1 5-6
B3-03 Stopping Method * 5-7
B3-05 Zero-Speed Operation 0 5-9
B3-06 Control Input Scans 1 5-13
B3-07 Local/Remote Run Select 0 5-13
B4-02 Trim Control Level 10 5-13
B5-01 Acceleration Time 1 5.0 5-14
B5-02 Deceleration Time 1 3.0 5-15
B5-03 Acceleration Time 2 1.0 5-15
B5-04 Deceleration Time 2 1.0 5-15
B5-05 Acceleration Time N Change 1.0 5-16
B5-06 Deceleration Time N Change 1.0 5-16
B5-07 Hoist 2 Stop Decel 0.3 5-16
B5-08 Fault Stop Time 0.3 5-16
B5-09 Accel/Decel Units 1 5-16
B5-10 Accel/Decel Switch Freq 120.0 5-16
B5-11 Switch Freq Compare 1 5-16
Differences in
Software Versions
This page intentionally left blank.
Important Product Upgrade Information
Changes in Software from 14906 to 14908/14909
Table 1
Control Method (A1-02) Motion (A1-03) Stopping Method (B3-03)
0–Ramp to Stop
Appropriate Software Upgrades for 14911 would utilize Impulse Link 3.053, Data Pulse 2.001
and Data Logger v1.23.