AC Power

For Business-Critical Continuity™

Liebert ® GXT3™, 500VA -3000VA Models


Reliable On-Line UPS Protection In A Compact 2U Package

One of the most affordable UPS systems in


its class, Liebert GXT3 leads the industry in
combining small size, high capacity and high
reliability features:
On-line design means zero transfer time
from external to internal power. When
utility power fails, your critical load remains
supported by a seamless flow of power.
Liebert GXT3 rated output power factor
of 0.9 better matches up with switch-
mode power supplies used in today’s IT
equipment. A higher output power factor
allows for a more efficient utilization of
the UPS.
The UPS provides easy serviceability with
user replaceable hot-swappable batteries.

Liebert GXT3 is a true on-line UPS that delivers continuous, high-quality For maximum control, Liebert GXT3 is
custom configurable to your needs
AC power to IT equipment with no break when transferring to battery. It protects using a specially designed Windows
equipment from virtually all power disturbances due to blackouts, brownouts, software package.

sags, surges or noise interference. The UPS is available in rack/tower and ENERGY STAR® qualified models available.

mini-tower configurations. Trade Compliance: Public sector customers


may select from four capacities (1000,
1500, 2000 and 3000 VA, 120V) to provide
TAA compliance.Refer to Liebert GXT3-
GVG3 models.

Ideally suited for:


PCs
Network workstations
Servers
Network closets
Large network peripherals
VoIP
Liebert GXT3
Standard Features
Flexibility:
Up To Six Battery-Backed Outlets
A generous quantity of battery-backed

The Proven Reliability Of True On-Line outlets allows more equipment to be


protected by the UPS.
Operation Plus The Features You Need Most Rotatable Display Panel
The LED display panel rotates 90° to make
the readout of the LED display easy to see in
Although Liebert® GXT3™ requires just a slim 2U of rack space, it rack or tower position.

provides the capabilities of a physically larger system. Get up to 3kVA Automatic Frequency Sensing
of capacity and battery backup, in 120V or 230V systems. External The UPS automatically adjusts to the input
frequency, 50Hz or 60Hz.
battery cabinets may be added for extended run time.
Mounting Flexibility
On-Line UPS Protection for Essential and Critical Applications Optional telescoping rack rails mount to the
sides of the UPS for easy installation into a
rack enclosure. A standard tower support
Dynamic base ships with the UPS.
Bypass

Surge Power Factor


Utility Suppression Correction/Rectifier Inverter Load
Charger

Battery

Liebert GXT3 is a true on-line power source, so whatever the quality of


power coming in, the pure sinewave output meets the exacting standards of
your equipment.

Liebert GXT3 includes:


Power factor correction
Internal batteries
Frequency conversion
Internal automatic bypass to utility in case of adverse UPS conditions
Manual bypass capability
Support for up to four external battery cabinets (rack/tower models)

Liebert GXT3 handles all these potential power problems:


Liebert GXT3 is easily configured for either
Power spikes and transients rackmount or tower applications. The LED display
EMI/RFI noise rotates for easy viewing in either orientation.

Voltage sags and brownout conditions


Harmonics ENERGY STAR®
qualified UPS models
Power-factor corrected loads
- UPS products
Outages meeting the EPA’s
Frequency variations requirements use
an average of 35%
less energy than
their standard
counterparts.
2
Liebert® GXT3™ contains internal batteries,
and is also able to support up to four
external battery cabinets – also 2U size.

Multiple Choices For


Communication, Shutdown
Higher Availability: And Reporting:
Advance Early Warning Power-Factor Correction SNMP And Web-Based
of UPS System Status Prevents noise, harmonics and Communication Options
Multiple audible and visual alarms distortion from being passed on to Liebert IntelliSlot® Web Card provides
immediately alert you to an output connected loads or from being fed SNMP (including SNMPv3) and IPv.6 and
overload, low battery, bypass, battery back to the utility. web-based management to your Liebert
discharge, battery loss or replace GXT3. Provides SNMP MIB to monitor
battery condition. Internal Automatic and Manual and control your UPS from your network
Bypass Capability management station or any PC running
4-8 minutes of Battery Assures continuity of power to critical Microsoft Internet Explorer.
Backup Time at Full load loads during system problems or

Network shutdown
Provides ample time for an orderly maintenance.
shutdown of connected equipment 
Sends both SNMP traps and emails for
when utility power fails. Optional Intelligent Battery Management event notification, and automatically
matching external battery cabinets Includes efficient three-stage emails a daily UPS history
offer additional backup time. charging technique and 
Auto-senses 10M/100M Ethernet
comprehensive discharging

Compatible with shutdown software
Overload Capability protection that extends battery life
to ensure graceful computer shutdown
Designed to handle output for greater availability.
overload conditions. The Liebert GXT3 is also fully
Input Circuit Breaker
compatible with:
Full Sequenced Battery Testing Provides increased protection to ease
Provides automatic and manual recovery from overloads. 
Liebert MultiLink™ shutdown software
self-diagnostic battery testing –included with the Liebert GXT3 UPS
capabilities. This provides a Lightning and Surge Protection 
Liebert Nform™ monitoring software
comprehensive analysis of the The transient voltage surge 
Liebert Multiport multiplexing unit
condition of the batteries within the suppression (TVSS) circuitry inside

Liebert Intellislot Relay Interface Card
UPS and will notify you when the Liebert GXT3 provides additional
internal batteries need to be replaced. protection for the connected USB Communications
equipment from incoming spikes, Windows (98 and later) built-in
User Replaceable surges, and other power anomalies power management functions provide
Hot Swappable Batteries present on the incoming monitoring of UPS status and manage
Easy to replace batteries increase utility power source. the automatic orderly shutdown of the
product life and provide prolonged Liebert MicroPOD
computer if a power outage ever exceeds
UPS reliability. Batteries are
the battery capacity of the UPS. Liebert
conveniently located behind the front
MultiLink shutdown software can also be
bezel of the unit.
used via USB connection.
Lowest Total Cost Of Ownership: Optional Liebert MicroPOD
0.9 Output Power Factor Output Distribution And
Liebert GXT3 rated output power factor of 0.9 better matches up with switch- Maintenance Bypass Module
mode power supplies used in today’s IT equipment. A higher output power factor When your computer system can’t be
allows for a more efficient utilization of the UPS. without power, even for scheduled UPS
maintenance, the Liebert MicroPOD
Wide Input Voltage Window Maintenance Bypass and Output
Prolongs battery life by allowing the UPS to maximize the use of utility power Distribution Unit ensures continuous
before transferring to battery when input voltage exceeds specified limits. uptime. It allows you to manually transfer
connected equipment to utility power via
Intelligent Fan Operation a maintenance bypass switch, permitting
Automatically changes rotation speed depending on system requirements to scheduled service or UPS replacement
decrease power consumption and noise. without the need to shut down
connected equipment. Features include:
Efficient Operation
≥ 88% AC-AC, minimum. 
2U height minimizes rack space Liebert GXT3 mini-
requirements tower model provides
Warranty Protection 1000VA capacity in a

Installs with plug-and-play ease
The industry’s best warranty – No-hassle two-year warranty with UPS compact design.

Two-year, no-hassle
replacement in the event of problems. Shipping is free for both original
replacement warranty
UPS return and the replacement unit. Optional one-year and three-year
extensions also available.
3
Specifications
Model Number GXT3-500RT120 GXT3-700RT120 GXT3-1000RT120 GXT3-1000MT120 Emerson Network Power
TAA Compliant Liebert Corporation World Headquarters
N/A N/A GVG3-1000RT120 N/A
Part Number 1050 Dearborn Drive
Model Rating VA/W 500/450 700/630 1000/900 1000/900 P.O. Box 29186
Dimensions: in. (mm) 19.7 x 16.9 x 3.4 15.4 x 6.9 x 8.9 Columbus, Ohio 43229
DxWxH (497 x 430 x 85) (390 x 175 x 225) United States Of America
Weight: lbs. (kg) 44 (20) 800 877 9222 Phone (U.S. & Canada Only)
614 888 0246 Phone (Outside U.S.)
Input AC Parameter
614 841 6022 FAX
Voltage Range 120VAC nominal; variable based on output load [email protected]
Frequency 40Hz ~ 70Hz; Auto Sensing Emerson Network Power
Input Power Cord 10 ft. attached w/ NEMA 5-15P plug Caribbean and Latin America
Output AC Parameter Office – United States of America
+1-954-984-3452 Phone
Output Receptacles 5-15R x 6
[email protected]
Voltage 110/115/120/127VAC (user-configurable); ±3%
liebert.com
Waveform Sine wave 24 x 7 Tech Support
Battery 800 222 5877 Phone
614 841 6755 (outside U.S.)
Full Load 17 minutes 11 minutes 7 minutes 7 minutes

Half Load 34 minutes 27 minutes 17 minutes 17 minutes


Emerson Network Power.
Recharge Time 6 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown The global leader in enabling
Agency Business-Critical Continuity™.
Safety UL 1778, cUL Listed

RFI/EMI FCC Part 15, Class A=CISPR22 Class B While every precaution has been taken to ensure accuracy and
completeness in this literature, Liebert Corporation assumes no
Surge Immunity IEC 62040-2 2nd Ed responsibility, and disclaims all liability for damages resulting
from use of this information or for any errors or omissions.
Transportation ISTA Procedure 1A
© 2013 Liebert Corporation. All rights reserved throughout
ENERGY STAR® qualifed No Yes Yes No the world. Specifications subject to change without notice.

All names referred to are trademarks or registered trademarks


of their respective owners.
Model Number GXT3-1500RT120 GXT3-2000RT120 GXT3-3000RT120 GXT3-3000RT208 ® Liebert is a registered trademark of the Liebert Corporation.

TAA Compliant SL-23182 (R03/13) Printed in USA


GVG3-1500RT120 GVG3-2000RT120 GVG3-3000RT120 N/A
Part Number

Model Rating VA/W 1500/1350 2000/1800 3000/2700 3000/2700 Business-Critical Continuity, Emerson Network Power and the
Emerson Network Power logo are trademarks and service marks of
Emerson Electric Co.
Dimensions: in. (mm) 19.7 x 16.9 x 3.4 23.7 x 16.9 x 3.4 ©2013 Emerson Electric Co.
DxWxH (497 x 430 x 85) (602 x 430 x 85)

Weight: lbs. (kg) 48.5 (22) 52.9 (24) 61.7 (28) 61.7 (28)

Input AC Parameter
Emerson Network Power.
208VAC nominal;
The global leader in enabling
Voltage Range 120VAC nominal; variable based on output load variable based on Business-Critical Continuity™.
output load

Frequency 40Hz ~ 70Hz; Auto Sensing AC Power


10 ft. attached w/ 10 ft. attached w/ 10 ft. attached w/ 10 ft. attached w/ Connectivity
Input Power Cord
NEMA 5-15P plug NEMA 5-20P plug NEMA L5-30P plug NEMA L6-20P plug
DC Power
Output AC Parameter
Embedded Computing
Output Receptacles 5-15R x 6 5-20R x 6 L5-30R x 1+5-20R x 6 L6-20R x 1+L6-15R x 2
Embedded Power
110/115/120/127VAC 208/220/230/240 VAC
Voltage
(user-configurable); ±3% (user-configurable); ±3% Industrial Power
Waveform Sine wave Infrastructure Management
Battery & Monitoring
Full Load 4 minutes 3 minutes 3 minutes 3 minutes Outside Plant
Half Load 11 minutes 11 minutes 11 minutes 11 minutes Power Switching & Controls
Recharge Time 6 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown Precision Cooling
Agency Racks & Integrated Cabinets
Safety UL 1778, cUL Listed Services
RFI/EMI FCC Part 15, Class A=CISPR22 Class B

Surge Immunity IEC 62040-2 2nd Ed

Transportation ISTA Procedure 1A

ENERGY STAR® qualifed Yes Yes Yes Yes