4010ES Fire Alarm: Operator's Manual
4010ES Fire Alarm: Operator's Manual
Fire Alarm
Operator’s
Manual
579-969
Rev. C
Cautions, Warnings and Copyrights
Cautions READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation manual. These instructions must be
and followed to avoid damage to this product and associated equipment. Product operation and reliability depend upon proper Warnings
installation.
DO NOT INSTALL ANY SIMPLEX® PRODUCT THAT APPEARS DAMAGED - Upon unpacking your Simplex product,
inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify an
authorized Simplex product supplier.
ELECTRICAL HAZARD - Disconnect electrical field power when making any internal adjustments or repairs. All repairs should
be performed by a representative or authorized agent of your local Simplex product supplier.
EYE SAFETY HAZARD - Under certain fiber optic application conditions, the optical output of this device may exceed eye safety
limits. Do not use magnification (such as a microscope or other focusing equipment) when viewing the output of this device.
FCC RULES AND REGULATIONS – PART 15 - This equipment has been tested and found to comply with the limits for a Class A digital device
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in
accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is
likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES - To ensure proper system operation, this product must be tested in
accordance with NFPA-72, after any programming operation or change in site-specific software. Reacceptance testing is required after any change,
addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that
other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50
devices, must also be tested and proper system operation verified.
Copyright © 2011-2016 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown
were current as of document revision date and are subject to change without notice.
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks.
Unauthorized use is strictly prohibited.
ii
Table of Contents
In this Chapter Refer to the page number listed in this table for information on a specific topic.
1-1
Basic System Description
Overview The Simplex 4010ES Fire Alarm Control Panel (FACP) has three general functions.
• It monitors fire alarm initiating points (for example, smoke detectors, heat detectors, and pull
stations).
• It activates fire alarm notification appliances (horns, strobes, audio evacuation messages) when
an initiating point activates.
• It monitors and controls auxiliary building equipment (fan dampers, relays, security devices).
Note: The term “point” is used extensively throughout this manual. It is a generic term used to refer
to an individual component of the system, such as a single smoke detector, a single pull
station, etc.). Some devices may take up multiple points in a system.
The 4010ES operator interface, shown in Figure 1-1, allows a system operator to control and monitor
the facility-specific components connected to the 4010ES FACP.
1-2
Basic System Description, Continued
Overview
1-3
Normal Appearance of Operator Interface Panel
Description The 4010ES operator interface panel shows the following under normal conditions.
SYSTEM IS NORMAL
08:23:45 MON 14-NOV-10
Note: If the appearance of the operator interface panel is not as shown above, refer to the information
in Chapters 2, 3, and 4 for instructions on managing the alarm, supervisory, or trouble
condition.
1-4
Chapter 2 Alarm Conditions
Introduction An alarm condition occurs when an initiating device (such as a manual pull station, smoke detector, etc.)
activates. The 4010ES indicates the presence of the alarm condition through messages it displays on
the alphanumeric display, by flashing the ALARM indicator, and by activating the building’s
notification appliances (horns and strobes).
Note: An alarm condition is a serious event, indicating the possibility of fire danger.In addition to using
the 4010ES operator interface panel to investigate and manage alarm conditions as
described in this chapter, you should also be aware of any facility-specific procedures that
you may be required to follow.
In this Chapter Refer to the page number listed in this table for information on a specific topic.
Acknowledging an Alarm
How the 4010ES When an alarm condition is detected by the 4010ES, the panel does the following to indicate the
Indicates that an presence of the alarm.
Alarm has • Red LED, labeled Fire Alarm flashes. Tone-
Occurred • alert (piezo buzzer) pulses.
• LEDs on remote annunciators may illuminate.
• The alphanumeric display on the interface panel indicates an alarm condition. The exact
manner in which the alphanumeric display reports information for the alarm condition depends
on whether the system’s Display First Alarm Option is enabled.
- If Display 1st Alarm Option is Enabled. The display alternates between two screens
similar to Screen 1 and Screen 2 shown below. Screen 1 is a tally screen indicating the total
number of fire alarms, priority 2 alarms, supervisory conditions, and trouble conditions
present on the panel. Screen 2 is a detailed description of the first alarm received by the
panel.
2-1
- If Display 1st Alarm Option is not enabled. Only a screen similar to Screen 1
appears, indicating the total number of alarm conditions present on the system.
Overview - The first step in managing an alarm condition is to acknowledge the alarm. Acknowledging an
Acknowledging alarm does two important things:
Alarms • It records the time and date at which you observed the presence of an alarm, trouble, or
supervisory condition on the operator interface panel and stores that information in the system’s
historical log.
• When you press the acknowledge key, the system displays specific data on the location of the
alarm.
It is important to understand that the 4010ES can be configured with either Global or Individual
Acknowledge. Global or Individual Acknowledge is selected in the System Options sub-tab of the
Panel Tab in the ES Panel Programmer. Global Acknowledge is the default. These options function
as follows:
• Global Acknowledge. When global acknowledge is enabled, one press of the FIRE ALARM
ACK (or the PRIORITY 2 ACK) key acknowledges every abnormal point currently reporting an
alarm status. This is helpful when a series of devices enter an alarm state (for example, all of
the smoke detectors in an area of the building) and you want to acknowledge all of them at the
same time.
• Individual Acknowledge. If individual acknowledge is enabled, the FIRE ALARM ACK (or
PRIORITY 2 ACK) key must be pressed to individually acknowledge each alarm. Individual
acknowledge must be selected if the panel is providing proprietary receiving service in
accordance with NFPA72.
The FIRE ALARM ACK (or the PRIORITY 2 ACK) key, which is used to acknowledge alarms
(either globally or individually), is located just beneath the ALARMS LEDs.
Globally Use the following procedure if the Global Acknowledge option is enabled on your 4010ES
Acknowledging system.
Alarms 1. Unlock and open the enclosure door. Read the alphanumeric display on the interface panel. It
reports the number of alarm conditions as shown below.
2. Press the FIRE ALARM ACK key. Read and follow the instructions on the alphanumeric display.
After you press the FIRE ALARM ACK key, the system responds as follows:
• The tone-alert silences and the alphanumeric display reports pertinent information about the
alarm, such as the following:
2-2
• The ALARMS LED changes from flashing to steady ON, and all alarm conditions are
acknowledged.
• Pressing the FIRE ALARM ACK key again displays information on the next alarm.
Continue to do this to review all alarms in the system.
Individually Use the following procedure if the Individual Acknowledge option is enabled on your 4010ES
Acknowledging system.
Alarms
1. Unlock and open the enclosure door. Read the alphanumeric display on the interface panel. It
reports the number of alarm conditions as shown below.
2. Press the FIRE ALARM ACK key. A report similar to the one shown below appears. Read and
follow the instructions on the alphanumeric display.
Individually 3. Press the FIRE ALARM ACK key again. Read the report data. Repeat this procedure to review
Acknowledging all reports. Reports are displayed in chronological order. Alarms
• Tone-alert silences when the last unacknowledged alarm is acknowledged.
• System Alarm LED is ON, but is no longer flashing.
2-3
Silencing an Alarm
Overview When an alarm condition exists, various signals (horns and strobes), auxiliary relays, the city connection (which
is the link to the local fire department or central station monitoring service), and the tone-alert may
activate. The ALARM SILENCE key turns OFF all devices that are programmed to turn off when it
is pressed. Typically, this will be the audible notification appliances (horns).
Note: Depending on the programming of the system, some devices may not turn off when the ALARM
SILENCE key is pressed.
• Turns OFF signal circuits (which usually connect to the Notification Appliances).
• Turns ON the ALARM SILENCED LED.
• Displays “Alarm Silence In Progress”.
You should be aware that the following functions affect the operation of the ALARM SILENCE
function.
• If a Coded Input Device (typically a pull station) activates, the <ALARM SILENCE> key may
be ignored until this function has completed coding. Notification appliances (horns) cannot be
silenced when a coded station is in alarm, but silence upon coding completion.
• If the Alarm Silence Inhibit Option -- which is a timer that inhibits the operation of the
ALARM SILENCE function – is enabled, pressing the <ALARM SILENCE> key is ignored
until the timer expires. The message “ALARM SILENCE INHIBITED” displays for a short
time to indicate the action was not taken. The message “ALARM SILENCE NO LONGER
INHIBITED” displays when the timer expires.
• If Waterflow Sprinkler Devices are activated, Notification Appliances may or may not be
silenced (depending on local code requirements). Usually, a dedicated bell will continue to
sound to indicate water flow.
• Some visual notification appliances may continue to flash until the system is reset.
Using the Alarm Press the ALARM SILENCE key and read the display. The alphanumeric display shows signal
Silence Key status and the ALARM SILENCED LED turns ON steady.
ALARM SILENCE IN PROGRESS
Overview The function of the SYSTEM RESET key depends on whether active alarms are present at the time the key is
pressed.
• Active Alarms Present. Pressing the SYSTEM RESET key when alarms are present
attempts to return the system to its normal state. This includes resetting initiating devices (pull
stations and smoke detectors, for example), relays (including city relay and door holder relays),
notification appliances (horns and strobes), and all LEDs and indicators that have been
2-4
programmed to be reset with the SYSTEM RESET key. See “Resetting a System with Active
Alarms” below for more information.
• No Active Alarms Present. Pressing the SYSTEM RESET key when no alarms are present
causes the system to perform a hardware reset. See “Performing a Hardware Reset” below for
more information.
Resetting a System Activated devices (i.e, devices in alarm) can be reset, using the SYSTEM RESET key. Doing this
with Active Alarms allows the system to return to a normal state following alarm activation. Follow these steps to
perform a System Reset when alarms are present.
2. One of the following occurs, depending on whether the activated devices reset or not.
• If all zones or devices in alarm reset, the ALARMS LEDs flash. Press either the FIRE
ALARM ACK or the PRIORITY 2 ACK key or both, and the following message appears.
SYSTEM IS NORMAL
8:37:13 WED 17-NOV-10
• If a zone or device remains in alarm and fails to reset, the “SYSTEM RESET IN
PROGRESS” message is followed by the message shown below.
When this message appears, the system remains in an alarm state. The display indicates the total
number of alarms present in the system along with a prompt to use the FIRE ALARM ACK (or
PRIORITY 2 ACK) key to review the points. (These points do not require acknowledgment.) The
ALARMS LED remains ON to indicate that a fire alarm device is still in the alarm condition. Read
the display to determine the type and location of the device. Follow local procedures to investigate
the area of the building in alarm. Look for devices that are in an alarm state, for example, pull
stations with the handle down or smoke detectors with their LED lit.
Performing a A hardware reset reinitializes the state of certain hardware components and is typically used to reset a
2-5
Hardware Reset Class A Trouble (for example, on an IDNet or RUI channel) after the problem causing the trouble is
resolved. If you attempt to perform a hardware reset without first fixing the problem causing the
trouble, the hardware reset fails and the trouble reappears.
2-6
Disabling a Point that Remains in Alarm
Overview If a device remains in alarm and no alarm condition (i.e., smoke or an activated pull station) exists, the 4010ES
provides a way to inhibit alarm reporting for the malfunctioning point. Disabling a point causes a
trouble condition for the point or zone that you disable.
The DISABLE key, which is used to disable points, may be passcode protected. If it is, you need to
first log in to the system using the passcode that enables the key. Refer to “Logging In and Out of
the System” in Chapter 6 for information on doing this.
• Disabling a point causes the point to NOT report alarm conditions or other status changes. A
point should not be disabled unless it is clearly understood that fire detection or security for the
area of the building covered by that point will be lost. Appropriate steps must be taken to
provide alternate means of protecting the area of the building covered by the disabled point.
• If the Service Reset option is enabled, an operator can clear an alarm condition (i.e., successfully
perform a system reset) even though the device that caused the alarm remains in a trouble state.
The typical application for this would be the case where a malfunctioning initiating device such
as a smoke detector (consisting of a base and removable sensor) causes an alarm and activates
the city circuit. With this option enabled, the sensor can be removed and the system (including
the city circuit) can be reset. Without this option enabled, removing the sensor would cause a
trouble, which would prevent the city circuit from being reset.
Important Note: Service Reset is not a UL-Approved option and enabling this option on the panel
invalidates the panel’s UL certification.
3. Press the DISABLE key. The alphanumeric display shows the following message.
2-7
Disabling a Point that Remains in Alarm, Continued
Procedure 4. Press the ENTER key. The alphanumeric display shows the action taken.
Note: The system indicates a trouble condition each time a point is disabled. It is important to repair
the disabled point as soon as possible. Once repaired, the disabled point should be enabled
as soon as possible. See the procedure in “Enabling and Disabling Points” in Chapter 6 of
this manual.
2-8
Chapter 3 Trouble Conditions
Introduction A Trouble message is used to indicate that the FACP is impaired, for example, due to an open
circuit, short circuit, ground fault, etc.
This chapter describes using the Operator Interface Panel keys to investigate the details of the trouble
condition.
In this Chapter Refer to the page number listed in this table for information on a specific topic.
Overview 3-2
Acknowledging Troubles 3-4
3-1
Overview
How the 4010ES When a trouble condition is detected by the 4010ES, the panel does the following to indicate the
Indicates the presence of the trouble condition.
Presence of a
Trouble • In the Warnings group, the yellow TROUBLE LED flashes.
• Tone-alert (piezo buzzer) sounds steady.
• Trouble LEDs on remote annunciators may illuminate.
• The alphanumeric display on the interface panel indicates trouble condition, as shown below:
What Acknowledge The first step in managing a trouble condition is to acknowledge the trouble. Acknowledging a
Does trouble does two important things:
• It records the time and date at which you observed the presence of the trouble and stores that
information in the system’s historical log.
• When you press the acknowledge key, the system displays specific data on the location of the
trouble.
It is important to understand that the 4010ES can be configured with either Global or Individual
Acknowledge. These options function as follows:
Global Versus • Global Acknowledge. When global acknowledge is enabled, one press of the TROUBLE
Individual ACK key acknowledges every point currently reporting a trouble.
Acknowledge
• Individual Acknowledge. If individual acknowledge is enabled, the TROUBLE ACK key
must be pressed to individually acknowledge each trouble. Individual acknowledge must be
selected if the panel is providing proprietary receiving service in accordance with NFPA72.
The TROUBLE ACK key, which is used to acknowledge troubles (either globally or individually), is
located just beneath the TROUBLE LED. Refer to Figure 3-1. If the TROUBLE ACK key is
passcode protected (by default, it is not), you cannot use this key to acknowledge troubles unless you
have the required passcode. Refer to “Logging In and Out of the System” in Chapter 6 for
information on how to do this.
3-2
Continued on next page
Overview,
Continued
Trouble Indications TrueAlarm devices are considered sensors instead of detectors because these devices do not for
TrueAlarm determine alarm conditions. Instead, the TrueAlarm smoke sensor is a measuring device that sends Sensors
data regarding smoke density to the 4010ES FACP. The TrueAlarm heat sensor operates in a similar
What to do when reported any time the average value of an individual sensor reaches a slightly higher threshold
TrueAlarm level.
Troubles Occur
fashion, but it sends • Expired Trouble. An “Expired Trouble” condition is reported anytime a CO sensor has
temperature data to reached the end of its useful lifetime.
the control panel
instead of smoke In addition to the three automatic trouble conditions, the 4010ES software includes three
density data. Also, preprogrammed digital pseudo points: P132, P463 and P464. The pseudo point P132 (Sensor Almost
CO heat/smoke Dirty Log Enable) can be turned ON through the front display, logged on at level 4 to allow a
sensors operate just TrueAlarm sensor that is close to being dirty to report as if it were dirty. This is useful when
like the TrueAlarm maintenance is being scheduled for dirty sensors, as it provides a means of seeing which sensors are
heat/smoke sensors. approaching a dirty state. The pseudo points P463 and P464 are used to log all the CO sensors that
The 4010ES uses will expire in 6 and 12 months respectively.
this data to
determine whether a
trouble has System Operators should do the following when these troubles occur.
occurred.
• Almost Dirty Trouble. This feature is visible only when enabled from the front display or
The TrueAlarm and through the ES Panel Programmer. In this case, a SimplexGrinnell Technical Representative has
CO sensors have programmed the system to allow almost dirty sensors to report as dirty. Contact your facilities
three automatic management personnel to report the trouble and schedule maintenance (cleaning) for the
trouble indications. sensors. • Dirty. This trouble means the sensor is holding its sensitivity, that maintenance
should be scheduled for the sensor. Contact your facilities management personnel to report the
• Dirty. A trouble and schedule maintenance (cleaning) for the sensors.
“Smoke • Excessively Dirty. This trouble means the sensor is no longer compensating for dirt and dust.
Detector Dirty” False alarms are possible in this condition and sensors should be cleaned as soon as possible.
condition is Contact your facilities management personnel to report the trouble and immediately schedule
reported any maintenance (cleaning) for the sensors.
time the • Expired. This trouble means that the CORC (CO Replacement Cartridge) needs to be replaced.
average value
• Almost Expired. This trouble means that the CORC is almost at the end of its lifetime and
on an
would need to be replaced within 6 or 12 months, depending on the system configuration.
individual
sensor reaches
a set threshold
value.
• Excessively
Dirty. A
“Smoke
Detector
Excessively
Dirty” trouble
condition is
3-3
Acknowledging Troubles
Globally If global acknowledge is enabled on the 4010ES, the system automatically clears after the source of
Acknowledging the trouble clears. Approximately 30 seconds after the source of the trouble clears, the alphanumeric
Troubles display should indicate a normal system.
Unlock and open the enclosure door. The alphanumeric display shows the trouble condition. For
example:
Globally Acknowledging Troubles
2. Press the TROUBLE ACK key under the flashing yellow LED. The alphanumeric display shows the area
and type of trouble. The tone-alert silences and the yellow LED glows steady.
3. Read the alphanumeric display and investigate the area to determine the cause of the trouble.
a. Restore or replace the defective device (switch, wire, notification appliance, etc.) in
accordance with the device’s instructions.
b. The trouble condition automatically clears when the problem has been corrected.
c. After a delay, the alphanumeric display reads:
3-4
Continued on next page
Individually 2. Press the TROUBLE ACK key. Repeat this step and read the reports. You need to do this for
Acknowledging each trouble event. The following occurs:
Troubles
• The tone-alert silences and the LED glows steady.
• The alphanumeric display shows the area and type of problem, as shown below.
FIRST FLOOR EAST WING ROOM31
Press ACK key to acknowledge
FIRE MONITOR ZONE OPEN CIRCUIT TROUBLE
3. Read the alphanumeric display. Investigate the trouble to determine its cause. Restore or
replace defective device (switch, wire, notification appliance, etc.) in accordance with the
manufacturer’s instructions.
When the trouble clears, the TROUBLE LED flashes and the tone-alert sounds steadily.
4. Press the TROUBLE ACK key. The display shows the system status. Press the TROUBLE
ACK key again. After a delay, the display shows that the system status is normal.
3-5
If the Trouble Doesn’t Clear
Overview Normally, trouble points do not require acknowledgment of the cleared condition. If the system does not clear,
read the display. If the source of the trouble cannot be located, call a SimplexGrinnell branch office
to repair the system.
System Reset Key Some troubles latch until they are reset manually, or are reset by pressing the SYSTEM RESET key.
Try pressing the SYSTEM RESET key if the trouble is any one of the following:
If pressing the SYSTEM RESET key does not clear the trouble, or if the trouble toggles (clears and
then reappears), you may choose to either disconnect the device or to disable the point, using the
procedure outlined in the next section.
1. Press the TROUBLE ACK key to display the point’s information on the alphanumeric display.
For example:
2. Press the Disable key. The alphanumeric display shows the following message.
Note: The system indicates a trouble condition each time a point is disabled. It is important to repair
the disabled point as soon as possible. Once repaired, the disabled point should be enabled
as soon as possible. See the procedure in “Enabling and Disabling Points” in Chapter 6 of
this manual.
3-6
Chapter 4 Supervisory Conditions
Introduction A Supervisory condition indicates that
• some part of the building’s fire protection system is disabled. An example of this is a sprinkler
tamper switch being activated due to a fire sprinkler control valve being closed.
• a lower priority initiating device (such as a duct smoke detector) has been triggered. Depending
on the system design, a Supervisory point can be:
• Latching. The panel must be reset to clear the Supervisory condition.
• Non-latching. The indicators (LED, buzzer, etc.) turn off automatically when the condition
clears.
This chapter describes using the Operator Interface Panel keys to investigate the details of the
supervisory condition.
In this Chapter Refer to the page number listed in this table for information on a specific topic.
Overview 4-2
Acknowledging Supervisory Conditions 4-3
Overview
How the 4010ES When a supervisory condition is detected by the 4010ES, the panel does the following to indicate the
Indicates the presence of the condition.
Presence of a
Supervisory • Yellow LED, labeled “SUPERVISORY” flashes.
Condition • Tone-alert (piezo buzzer) sounds steady.
• The alphanumeric display on the interface panel indicates supervisory condition, as shown
below:
4-1
Figure 4-1. Interface Panel Showing Supervisory Condition
What Acknowledge The first step in managing a supervisory condition is to acknowledge the condition. Acknowledging a
Does supervisory does two important things:
• It records the time and date at which you observed the presence of the condition and stores that
information in the system’s historical log.
• When you press the acknowledge key, the system displays specific data on the location of the
supervisory condition.
It is important to understand that the 4010ES can be configured with either Global or Individual
Acknowledge. These options function as follows:
• Global Acknowledge. When global acknowledge is enabled, one press of the SUPV ACK
key acknowledges every point currently reporting a supervisory condition.
• Individual Acknowledge. If individual acknowledge is enabled, the SUPV ACK key must
be pressed to individually acknowledge each supervisory condition. Individual acknowledge
must be selected if the panel is providing proprietary receiving service in accordance with
NFPA72.
4-2
The SUPV ACK key, which is used to acknowledge supervisory conditions (either globally or
individually), is located just beneath the SUPERVISORY LED. Refer to Figure 4-1. If the SUPV
ACK key is passcode protected (by default, it is not), you cannot use this key to acknowledge
supervisory conditions unless you have the required passcode.
Globally Pressing the SUPV ACK key once globally acknowledges all supervisory conditions that exist
Acknowledging within the fire alarm system. In addition, the SUPERVISORY LED changes from flashing to steady
Supervisory ON and the tone-alert silences.
Conditions
If global acknowledge is enabled on your system, use the following procedure to acknowledge the
supervisory conditions.
1. Unlock and open the enclosure door. The alphanumeric display shows the supervisory condition,
similar to the following example.
2. Press the SUPV ACK key under the flashing yellow LED. The alphanumeric display shows the
area and type of condition. The tone-alert silences and the yellow LED glows steady.
Read the alphanumeric display. Investigate the problem to determine its cause. Restore or replace
the defective device (switch, wire, notification appliance) in accordance with the manufacturer’s
instructions, or call SimplexGrinnell to repair the system. When the problem causing the
supervisory is corrected, the supervisory automatically clears and, after a delay, the alphanumeric
display indicates that the system status is normal.
Individually If individual acknowledge is enabled on your system, you need to separately acknowledge each
Acknowledging supervisory condition. Use the following procedure to do this.
Supervisory
Conditions 1. Unlock and open the enclosure door. The alphanumeric display shows the supervisory condition,
similar to the following example.
4-3
Acknowledging Supervisory Conditions, Continued
Individually 2. Press the SUPV ACK key. Repeat this step and read the display. The alphanumeric display shows
Acknowledging the area and type of condition.
Supervisory
a. The tone-alert silences and the LED glows steady. Conditions
3. Read the alphanumeric display. Investigate the problem to determine its cause. Restore or
replace the defective device (switch, wire, notification appliance) in accordance with the
manufacturer’s instructions, or call SimplexGrinnell to repair the system.
When the problem causing the condition is corrected, the SUPERVISORY LED flashes and the
tone-alert sounds steady.
4. Press the SUPV ACK key. The display shows the system status.
5. Press the SUPV ACK key again. After a short delay, the display indicates that the system is
normal.
4-4
Chapter 5 Selecting Points for Status and
Control
Introduction Many of the advanced operations that can be accomplished from the operator interface first require you to
select the point on which you want to perform the operation. Points can be selected in one of three
ways.
• Alarm, Trouble, Supervisory List. Points that are reporting an alarm, trouble, or
supervisory condition can be selected from the active alarm, trouble, or supervisory list.
• Using the Menu. The menu system includes an option that allows you to scroll through each
category (monitor, signal, etc.) of point, and then after selecting a category, you can scroll
through the points for the category.
• Using the Entry Keys. The Entry keys, located on the far right of the operator interface,
contain abbreviated labels for each category of point. (For example, the key in the upper left
corner of the Entry keys is labeled “ZONE” and the key to its right is labeled “SIG.” Pressing
one of these keys causes the system to prompt you to select a specific point within the selected
category.
In this Chapter Refer to the page number listed in this table for information on a specific topic.
Procedure When a point experiences an abnormal condition, such as an alarm, trouble, or supervisory, it is added to the
appropriate list (alarm list, supervisory list, or trouble list). Points within these lists can be selected
as follows:
1. Press the appropriate acknowledge key to enter the list. (For example, press the FIRE ALARM
ACK key to enter the list of current fire alarms; press the TROUBLE ACK key to enter the list
of current troubles).
2. Use the Next and Previous keys to scroll through the entries in this list. Stop scrolling when the
point you are interested in is displayed.
5-1
Selecting Points from the Menu
Procedure 1. Press the Menu key to enter the panels’s menu system.
2. Press the Next key until the alphanumeric display reads as follows:
4. Press the Next key to scroll through the categories of points until the appropriate category is
shown. Press the ENTER key. The first point in the selected category appears. In the example
below, the point shown is the first one in the monitor zone category.
5. Press the Next key to scroll through the list of points in the category. When the point that you
want to select is displayed, press ENTER.
Overview The Entry Keypad, shown below, allows you to quickly select a category of points. For example, pressing the
ZONE key on the upper left side of the keypad selects the monitor zone category. After selecting a
category, messages on the display prompt you for the specific point in the category.
5-2
AUX, followed by ENTER, where AUX represents an
AUX - allows you to auxiliary relay and is a number from 3 to n. (n
select an Auxiliary Relay. represents the number of the last auxiliary relay in your
system.)
You can use the keypad to select either a local point or a network point. A local point is one that is
physically connected to the panel you are currently at, and a network point is one that is located on a
different panel but has been programmed so that it can be selected and controlled from another
panel.
Selecting Points Refer to the following table for information on using the keypad to select local points on this panel.
Selecting Points
Table 5-1. Keypad Use (continued)
5-3
C-D, followed by ENTER, where C represents the
IDNet, or VESDA channel and D represents the
device number. You must insert the dash between
channel and device. Use the NET key to insert the
dash.
5-4
Chapter 6 Advanced Functions
Introduction This chapter describes advanced functions that you can perform from the operator interface panel.
In this Chapter Refer to the page number listed in this table for information on a specific topic.
Introduction The 4010ES system uses four access levels, referred to by the numbers one through four, to control what
system operators can do with the system. The system typically operates at access level one, which
allows an operator to accomplish basic tasks (for example, acknowledge alarm, trouble, and
supervisory conditions) without logging in to the system.
Other functions – for example, the use of the user-defined function keys – are passcode protected to
prevent access by unauthorized personnel.
Log In Procedure Follow these steps to log in to the system at access level two, three, or four. The keypad used to enter
the passcode is located behind the interface panel access door.
1. Obtain the passcode for the access level at which you want to operate.
2. Press the Menu key. The alphanumeric display shows the following message.
3. Press the ENTER key on the Entry keypad. The following message displays:
6-1
4. Press the 1 key on the Entry keypad. The display shows the following message.
5. Enter the passcode for the access level. The passcode can be up to 10 numbers in length. Press
the ENTER key on the Entry keypad when you have finished entering the code. An X is
displayed for each digit of your passcode, as shown below.
Log In Procedure If the passcode entered in Step 5 is correct, the following message is
shown.
After a brief pause, the system displays the granted access level, such as the level 2 message shown
below.
Press the C/EXIT key twice. The display shows the system status.
Log Out Procedure Failure to log out allows unauthorized personnel access to the various passcode protected functions. If
no keypad activity is detected for ten minutes, the system returns to Level 1 access.
Perform the following procedure to log out and return the operator access level to Level 1.
6-2
Log Out Procedure
3. Press the 2 key. After a brief pause, the display shows a message similar to the one below.
4. Press the DEL key to exit. The display shows the system status.
Procedure Follow these steps to set the time and date used by the 4010ES FACP. Ensuring that the current time and date
are correct on the system is important. In particular, the accuracy of historical logs and reports
depends on the system time.
1. Press the Menu key. Press the Next or Previous key until the display shows the option for
setting time and date.
3. Press the More Info key. The display shows the time and date and places an underline character
under the hour, meaning it is the part of the time and date that can be changed.
6-3
• Time. Use the < and > keys to move the underline character between hours and minutes.
Use the Next and Previous keys to increment or decrement the value. For example, to
change the minutes, first use the < and > keys to move the highlight under the minutes field.
Then use the Next and Previous keys to change the value of the minutes field.
• Date. Use the < and > keys to move the underline character between the components of the
date field. Use the Next and Previous keys to increment or decrement the value of the field
until it is correct.
5. When the date and time are correct, press the ENTER key.
Overview The system records the time at which each alarm, trouble, and supervisory event occurs. You can view this
information in one of two ways:
• By displaying or printing the historical alarm or trouble log. Refer to “Displaying Historical
Logs” later in this chapter for information on doing this.
• By scrolling through the list of active alarm, trouble, or supervisory conditions, selecting a
specific event, and using the Event Time key. Refer to the procedure below for information on
doing this.
Procedure Select the alarm, trouble, or supervisory event whose event time you want to display. To do this, follow these
steps:
1. Press the FIRE ALARM ACK, PRIORITY 2 ACK, TROUBLE ACK, or SUPV. ACK key to
enter the appropriate list of events. (For example, press the FIRE ALARM ACK key to enter the
list of active fire alarms.)
2. Use the Next and Previous keys to scroll through the list until the alarm in which you are
interested is displayed.
3. Press the Event Time key. The time at which the alarm, priority 2 alarm, trouble, or supervisory
occurred appears in the display.
6-4
Enabling and Disabling Points
Overview Enabling and disabling points is sometimes necessary when performing maintenance on the system. When using
this function, it is critical that you understand whether Custom Control (either the system’s default
Custom Control or any user Custom Control) makes reference to the point or not. Actions driven by
custom control are suspended for the duration of time the point is disabled, but execute immediately
after the point is enabled.
Example. Suppose you disable a signal point and during the time the point is disabled, a Custom
Control equation executes that turns the point ON. This action is suspended for the duration of time
the point is disabled. However, when the point is subsequently enabled, the point’s state updates and
the Custom Control equation turning the point ON executes, turning the signal ON.
The system generates a “Disable Trouble” to remind you that the point is disabled. When you enable
the point again, the trouble clears.
6-5
Forcing Points On and Off
Overview Forcing a control point ON assigns a priority of 1 to the point, preventing system control until the point is
returned to automatic control. For example, you can force a relay or signal point ON to test or
execute its function. Unlike Enable/Disable (see description in previous section), a point that you
force OFF does not refresh its state when the point is turned back ON.
Example. Suppose you turn a signal point OFF and during the time the point is disabled, a Custom
Control equation executes that turns the point ON. When the point is subsequently returned to
automatic operation, the point’s state does not update and the Custom Control equation turning the
point ON does not execute. Points that have been returned to automatic operation will update the
next time an equation that outputs to that point is evaluated.
The system generates a “Manual Override Trouble” for the point to remind you that the point has
been forced ON or OFF.
Returning a Point Automatic operation is the normal operation of the point. For example, if the point is a signal point,
to Automatic a setting of AUTOMATIC indicates that the point is back under system control.
Operation
To return the state of a point that is currently ON or OFF to AUTOMATIC, follow these steps.
Overview Historical logs provide a record of both the events that have occurred on the system and the actions taken by an
operator to manage those events. The system contains the following logs.
• Historical Alarm Log. Provides detailed information on each alarm, including time and date
stamp, that has occurred since the last time the logs were cleared.
• Historical Trouble Log. Provides detailed information on each trouble, including time and date
stamp, that has occurred since the last time the logs were cleared.
Displaying/Clearing 1. Press the Menu key. Use the Next and Previous keys to scroll through the choices until the
Historical Logs “DISPLAY HISTORICAL ALARM LOG” or “DISPLAY HISTORICAL TROUBLE LOG”
6-6
choice is displayed.
3. Use the Next and Previous keys to scroll through the entries in the selected log. Press ENTER at
any time while in the log to clear all events.
6-7
Printing Reports
Report Description
6-8
Continued on next page
Printing
Reports, Continued
Overview
Table 6-1. Reports (continued)
Report Description
• Point ID.
• Custom Label.
• Pass/Fail.
TrueAlert Status Report
Report the following information for each SLC
Procedure 1. Press the Menu key. Use the Next and Previous keys to scroll through the choices until the “PRINT
REPORTS?” choice is displayed.
2. Use the Next and Previous keys to scroll through the categories of report (Alarm History,
Trouble History, etc.).
3. When the category of report you want to print is displayed, press ENTER. The system prompts
you to confirm that you want to generate the report. Press ENTER again.
6-9
Chapter 7 System Test Procedures
Introduction This section describes performing the system tests that can be performed from the front panel of the
4010ES.
In this Chapter Refer to the page number listed in this table for information on a specific topic.
Overview The Lamp Test key on the operator interface panel is used to determine local lamp failures within the system.
Lamps on the 4010ES operator interface panel illuminate along with the five function and
acknowledge LEDs.
The tone-alert (buzzer) can also be tested with the Lamp Test.
2. If you find defective lamps/LEDs, contact your local SimplexGrinnell branch office.
Testing the Tone- Holding the Lamp Test key for more than 3 seconds tests the tone-alert.
Alert
7-1
WalkTest Overview
Overview WalkTest allows the function of the system’s initiating devices and signals to be tested by a single person.
Conducting a WalkTest requires you to perform the following steps.
• Step 1. Create WalkTest Groups. The 4010ES supports up to eight WalkTest groups.
This allows the building to be divided into small portions for the WalkTest, and allows the
rest of the building to be protected by the fire alarm panel. Each group has a list of monitor
points (initiating devices) and a list of the 4010ES signal circuits that activate when one of
the group’s control points activates.
Refer to Chapter 9 of the ES Panel Programmer’s Manual (574-849) for information on adding
monitor points (initiating devices) and signals/relays to a WalkTest group.
• Step 2. Enable WalkTest Options from Front Panel. These options include the
following. Refer to the “Setting WalkTest Options” later in this section for information on
setting these options.
Step 3. Manually Activate Initiating Devices in Each Group and Interpret Signals.
Individually activate each initiating device in the group, using a magnet or canned smoke. Make
sure to proceed in a logical manner (i.e., start with the lowest IDNet address and work toward the
highest). Each time you activate an initiating device, the system’s signals pulse a code that allows
you to verify exactly which initiating device triggered the signals. For hardwired monitor zones, the
signal code corresponds to the number of the zone. (For example, if the zone number is eight, the
signals pulse eight times to indicate zone eight.) For IDNet devices, the first set of pulses from the
signals corresponds to the channel. The signals then pause momentarily and the second set of pulses
corresponds to the number of the device on the channel. For example, if you activate an IDNet
smoke detector with an address of M1-25, the signals sound once to indicate channel one, pause for a
short duration, and then sound 2 times, pause, and then sound 5 times to indicate device 25.
In some cases, immediately after verifying the function of an initiating device, you may also want to
verify its ability to generate a trouble condition. To do this, cause a trouble on the device (i.e.,
remove the sensor from a TrueAlarm device), and then listen to the signals. The signals sound
steady for 4 seconds to indicate trouble conditions, then reset.
Important Notes Signals and initiating devices (with the exception of pull stations) automatically acknowledge and
automatically reset, allowing for one-man testing without the need for someone at the main control
panel to acknowledge and reset the system each time an initiating device and its associated signals
activate.
A silent Walk Test may be performed (no signals will sound) and logging of events may be selected.
Refer to “Setting WalkTest Options” below for additional information.
If an alarm condition is detected from a zone that is not in the present active Walk Test group, the
system will operate as a fire alarm panel and the active Walk Test groups are aborted.
7-2
Setting
WalkTest Options
Enabling WalkTest 1. Press the Menu key and then use the Next and Previous keys until “ENABLE WALKTEST?” is
for a Group displayed. Press ENTER.
2. Use the Next and Previous keys to scroll through the WalkTest groups until the group that you
want to test is displayed. Press ENTER. A screen similar to the following appears.
Setting Options Each of the options shown in the example above is associated with a number from one to four. Pressing
the associated number on the keypad toggles the setting of the option. The arrow points to choice
currently enabled for the option.
Example. The first option shown above( 1 = on --> OFF )allows you to turn WalkTest on and off
for the group you selected in Step 2 above. In the example, the arrow points to OFF, indicating that
WalkTest is not currently on for the selected group. To turn it on, you would press the number 1 on
the keypad. When you do this, the arrow turns around to indicate that ON is selected and the option
reads 1 = ON <-- off.
Option Description
7-3
Allows you to configure a silent WalkTest (i.e., no
signals are used). Make sure to enable the logging of
WalkTest events, which allows each zone with an
4 = no --> SIG abnormal condition to be time tagged and added to the
log. See previous option above. When SIG is selected,
signals sound during the WalkTest. When NO is
selected, no signals are used during the WalkTest.
TrueNAC Voltage Drop Test
Overview The TrueNAC Voltage Drop Test is used in conjunction with the TrueNAC Circuit Design tool. A job is first
designed using the TrueNAC Circuit Design tool. The tool provides a report with job layout and
device voltages. After the job is installed, the TrueNAC Voltage Drop Test is run to verify proper
installation of the 4906 devices.
The TrueNAC Voltage Drop Test determines the line voltage for notification appliances that are
connected to a TrueAlert Power Supply’s (TPS) Signaling Line Circuit (SLC) channels, under worst
case panel operating conditions. It differs from simply checking with a meter, in that the voltage
output of the panel under nominal operating conditions is typically higher than the voltage output
under worst case conditions (e.g. on end-of-life batteries). Prior to the start of the test, the horn
volume is selected to be either “ON” (horns set to high volume) or “OFF” (silent testing of the
system).
The TrueNAC Voltage Drop Test is compatible only with the 4906 series TrueAlert devices
connected to a TrueAlert Power Supply (TPS). It is not compatible with the Extended System
Supply or TrueAlert ES appliances. The test can be run on a single TrueAlert SLC, or on all the
TPS’s in the system.
• If older "fixed” candela devices are present, the tool will indicate incompatible devices and will
not run. This will also be indicated in the report.
• TPS PCAs Revision E and older may be updated with the latest slave code to run the TrueNAC
Voltage Drop Test. The results will be less accurate than with Revision F or later TPSs. The
reports will also indicate the use of an older TPS and caution that results are less accurate.
• If older TPS slave code (1.04 and earlier) is installed on a newer TPS PCA (Revision F or later),
a "HW CONFIG/SW REV MISMATCH TROUBLE" trouble will be indicated on the panel.
The TrueNAC Voltage Drop Test performs the following diagnostic verification:
• Devices are polled and report terminal voltage, candela rating, and device type to the 4010ES.
• The line impedance of the SLC channel is determined through the TrueNAC algorithm.
• Notification Appliances that fall below the device threshold are reported as failed devices to the
4010ES, and the panel indicates TrueNAC Voltage Drop Test failed trouble.
Devices that have failed the TrueNAC Voltage Drop Test require the following actions:
• Fix the device with the lowest voltage as indicated in the TrueNAC status report.
• Repeat the TrueNAC Voltage Drop Test.
The 4010ES keeps track of the devices that failed the TrueNAC Voltage Drop test. A trouble alarm
is indicated on the panel for devices that failed the test. This trouble is cleared after hardware reset.
The TrueNAC Voltage Drop Test must be repeated to verify that all troubles are fixed.
Accessing the To gain access to the TrueNAC Voltage Drop diagnostic test, you must login with an access level
TrueNAC Voltage higher than level one (Refer to Chapter 6 for access level discussion).
7-4
Drop Test
1. Press the Menu key on the Display/Action keypad, located on the right side of the interface panel.
The alphanumeric display shows the following message.
7-5
TrueNAC Voltage Drop Test, Continued
Accessing the 2. Press the Next key on the Display/Action keypad. Use the Next and Previous keys to scroll to
TrueNAC Voltage the Diagnostic Functions. The following message displays:
Drop Test
3. Press the ENTER key on the Entry keypad. Scroll to the TrueNAC Voltage Drop Test using the
Next and Previous keys on the Display/Action keypad. The following message displays:
4. Press the ENTER key on the Entry keypad. The following message displays.
Testing all Use the following procedure to test all the TrueAlert Power Supply’s SLC lines at once. Before you
TrueAlert Power start this test, make sure you have already completed the procedure Accessing the TrueNac Voltage
Supply’s SLCs Drop Test.
1. Press the ENTER key on the Entry keypad. The following message displays:
2. To turn the horn on or off before performing the TrueNAC Voltage Drop Test, use the Next and
Previous keys to set the horn state.
Note: The horn can be turned off to prevent any disturbance during the TrueNAC Voltage Drop Test.
Horns that are turned on are set to high volume. If Horns are on, the panel will perform two
passes one with horns on and one with horns off. This is done to enhance measurement
accuracy with A/Vs.
7-6
TrueNAC Voltage Drop Test, Continued
Testing each Use the following procedure to test separately each of the TrueAlert Power Supply’s SLC lines.
TrueAlert Power Before you start this test, make sure you have already completed the procedure Accessing the
Supply’s SLC TrueNAC Voltage Drop Test.
1. Press the Next key on the Display/Action keypad. The following message displays.
2. Press the ENTER key on the Entry keypad. The following message displays:
3. Use the Next and Previous keys on the Display/Action keypad to change the SLC channel.
4. Press the ENTER key on the Entry keypad. The following message displays:
5. To turn the horn on or off before performing the TrueNAC Voltage Drop Test, use the Next and
Previous keys to set the horn state.
Note: The horn can be turned off to prevent any disturbance during the TrueNAC Voltage Drop Test.
Horns that are turned on are set to high volume. If Horns are on, the panel will perform two
passes one with horns on and one with horns off. This is done to enhance measurement
accuracy with A/Vs.
7-7
TrueNAC Voltage Drop Test, Continued
The TrueNAC A TrueNAC status report can be generated and displayed by the panel with the completion of the
Report TrueNAC Voltage Drop Test.
7-8
TrueNAC Voltage Drop Test, Continued
Samples
7-9
TrueNAC Voltage Drop Test, Continued
7-10
Disable IDNET CO Algorithms
Overview The Disable IDNET CO Algorithms is one of the options available under the Diagnostics menu, at the front panel
of the 4010ES. When choosing this option, the technician ensures that the CO sensors will get a
testing threshold downloaded and the CO over time is disabled. With the Disable IDNET CO
Algorithms option on, the technician can then proceed to test the devices with the WalkTest option
Enabled or Disabled. When the Disable IDNET CO Algorithms is entered, a trouble will be
generated. The trouble screen that will appear will look as follows:
Since all three possible sensors (photo, heat and CO) could be tested simultaneously, the LED on the
base will be used to give the technician an indication of the test result. The LED states and their
meanings are as follows:
• LED OFF - No sensors have passed the test.
• LED ON - At least one sensor has passed the test (If testing only one sensor this is the LED state
you'd expect if the test passed).
• LED FLASHING - All sensors for this device have passed the test (Note: This could be 2 or 3
sensors depending on what type of CO combination device is configured. This state will not be
seen if only a single sensor is being tested).
Because the sensors can either be tested one at a time or by combining multiple technologies into a
single test, one can follow two similar approaches to complete the tests. and show the two flowcharts
denoting those approaches.
7-11
Continued on next page
7-12
Disable IDNET CO Algorithms, Continued
Overview
Figure 7-2. Simultaneous Testing of Multiple Sensor Technologies
Disable IDNET CO With the WalkTest option disabled, the devices will bring in actual alarms at the panel unless
specific Algorithms without custom control is written to prevent this.
WalkTest Enabled
Disable IDNET CO With the WalkTest option enabled, the devices won't go into alarm at the panel. Instead the device
Algorithms with that went over threshold will be coded out and a print message will be generated to show that it
WalkTest Enabled passed a functional test.
7-13
579-969
Rev. C
© 2011-2016 SimplexGrinnell LP. All rights reserved. Specifications and other information were current as of publication and are subject to change without notice.