Amvic ICF US Design Guide
Amvic ICF US Design Guide
US DESIGN GUIDE
This guide makes use of only the Prescriptive Method and ACI 318.
2
PART 6.2 US DESIGN GUIDE
Foundations
Unbalanced Backfill Height 9 feet (2.7 m)
Equivalent Fluid Density of Soil 60 pcf (960 kg/m3)
Presumptive Soil Bearing Value 2,000 psf (96 kPa)
Walls
Unit Weight of Concrete 150 pcf (23.6 kN/m3)
Wall Height (unsupported) 10 feet (3 m)
Floors
Floor Dead Load 15 psf (0.72 kPa)
First-Floor Live Load 40 psf (1.9 kPa)
Second-Floor Live Load (sleeping rooms)30 psf (1.4 kPa)
Floor Clear Span (unsupported) 32 feet (9.8 m)
Roofs
Maximum Roof Slope 12:12
Roof and Ceiling Dead Load 15 psf (0.72 kPa)
Roof Live Load (ground snow load) 70 psf (3.4 kPa)
Attic Live Load 20 psf (0.96 kPa)
Roof Clear Span (unsupported) 40 feet (12 m)
For SI: 1 foot = 0.3048 m; 1 psf = 47.8804 Pa; 1 pcf = 157.0877 N/m3 = 16.0179 kg/m3; 1 mph = 1.6093 km/hr
2. An engineered design shall be required for houses built along the immediate, hurricane-prone coastline
subjected to storm surge (i.e., beach front property) or in near-fault seismic hazard conditions (i.e., Seismic
Design Category E).
3. The provisions of the Prescriptive Method shall not apply to irregular structures or portions of structures in
Seismic Design Categories C, D1, and D2.
3
PART 6.2 US DESIGN GUIDE
4
PART 6.2 US DESIGN GUIDE
One Storey 20 16 13 11 10
Two Storey 27 22 18 15 14
For SI: 1 foot = 0.3048 m; 1 inch = 25.4 mm; 1 psf = 47.8804 Pa
1
Minimum footing thickness shall be the greater of one-third of the footing width, 6 inches (152 mm), or 11 inches (279 mm) when a dowel is
required in accordance with Section 6.0.
2
Footings shall have a width that allows for a nominal 2-inch (51-mm) projection from either face of the concrete in the wall to the edge of the
footing.
3
Table values are based on 32 ft (9.8 m) building width (floor and roof clear span).
4
Basement walls shall not be considered as a storey in determining footing widths.
5
Actual thickness is shown for flat walls while nominal thickness is given for waffle- and screen-grid walls. Refer to Section 2.0 for actual waffle-
and screen-grid thickness and dimensions.
6
Applicable also for 7.5-inch (191-mm) thick or 9.5-inch (241-mm) thick flat ICF foundation wall supporting 3.5-inch (88.9-mm) thick flat ICF
stories.
7
Applicable also for 9.5-inch (241-mm) thick flat ICF foundation wall storey supporting 5.5-inch (140-mm) thick flat ICF stories.
2. Foundations erected on soils with a bearing value of less than 2,000 psf (96 kPa) shall be designed in
accordance with accepted engineering practice.
5
PART 6.2 US DESIGN GUIDE
6
PART 6.2 US DESIGN GUIDE
3. Vertical reinforcement shall be as per table 3.2. For crawlspace walls carrying ICF wall on top, vertical rein-
forcement shall be the greater of that required in table 3.2 or table 4.2 in the following section
1
Table values are based on reinforcing bars with a minimum yield strength of 40,000 psi (276 MPa) and concrete with a minimum specified
compressive strength of 2,500 psi (17.2 MPa).
2
N/R indicates no vertical wall reinforcement is required.
3
Spacing of rebar shall be permitted to be multiplied by 1.5 when reinforcing steel with a minimum yield strength of 60,000 psi (414 MPa) is
used. Reinforcement, when required, shall not be less than one #4 bar at 48 inches (1.2 m) on center.
4
Applicable only to crawlspace walls 5 feet (1.5 m) or less in height with a maximum unbalanced backfill height of 4 feet (1.2 m).
5
Interpolation shall not be permitted.
6
Walls shall be laterally supported at the top before backfilling.
7
Actual thickness is shown for flat walls while nominal thickness is given for waffle-and screen-grid walls. Refer to Section 2.0 for actual waffle-
and screen-grid thickness and dimensions.
8
Applicable only to one-storey construction with floor bearing on top of crawlspace wall.
7
PART 6.2 US DESIGN GUIDE
Basement Walls
[Prescriptive Method – 3.2.3]
1. Basement walls shall be laterally supported at the top and bottom of the wall in accordance with section 6.0.
2. Minimum horizontal reinforcement shall be as per table 3.3.
8 (2.4) One No.4 bar within 12 inches (305 mm) of the top of the wall storey and one No.4
bar near mid-height of the wall storey
9 (2.7) One No.4 bar within 12 inches (305 mm) of the top of the wall storey and one No.4
bar near third points in the wall storey
10 (3.0) One No.4 bar within 12 inches (305 mm) of the top of the wall storey and one No.4
bar near third points in the wall storey
For SI: 1 foot = 0.3048 m; 1 inch = 25.4 mm; 1 pcf = 16.0179 kg/m3
Horizontal reinforcement requirements are for reinforcing bars with a minimum yield strength from 40,000 psi (276 MPa) and concrete with a
minimum concrete compressive strength of 2,500 psi (17.2 Mpa)
8
PART 6.2 US DESIGN GUIDE
9
PART 6.2 US DESIGN GUIDE
10
PART 6.2 US DESIGN GUIDE
11
PART 6.2 US DESIGN GUIDE
1. Concrete foundation walls supporting above-grade ICF walls in Seismic Design Category C shall be reinforced
with minimum No. 5 rebar at 24 inches (610 mm) on center (both ways) or a lesser spacing if required by
Tables 3.2 through 3.6
2. Concrete foundation walls supporting above grade ICF walls in Seismic Design Categories D1 and D2 shall
be reinforced with minimum No. 5 rebar at a maximum spacing of 18 inches (457 mm) on center (both
ways) or a lesser spacing if required by Tables 3.2 through 3.6 and the minimum concrete compressive
strength shall be 3,000 psi (20.5 MPa). Vertical reinforcement shall be continuous with ICF above grade wall
vertical reinforcement. Alternatively, the reinforcement shall extend a minimum of 40db into the ICF above
grade wall, creating a lap-splice with the above-grade wall reinforcement or extend 24 inches (610 mm)
terminating with a minimum 90º bend of 6 inches in length.
12
PART 6.2 US DESIGN GUIDE
85 18 24 29 23 31 37
90 20 27 32 25 35 41
100 24 34 39 31 43 51
110 29 41 48 38 52 61
120 35 48 57 45 62 73
130 41 56 66 53 73 854
140 47 65 77 61 844 994
150 54 75 884 70 964 1144
For SI: 1 psf = 0.0479 kN/m2; 1 mph = 1.6093 km/hr
1
This table is based on ASCE 7-98 components and cladding wind pressures using a mean roof height of 35 ft (10.7 m) and a
tributary area of 10 ft2 (0.9 m2).
2
Enclosure Classifications are as defined in Section 1.5d. Buildings are classified as partially enclosed or enclosed as defined in
ASCE 754.
3
Exposure Categories (as defined by section 1.5): Reflects the effect of the ground surface roughness on wind loads in
accordance with ASCE 7 [4]. Exposure Category B includes urban and suburban areas, or other terrain with numerous closely
spaced obstructions having the size of single-family dwellings or larger. Exposure Category C includes open terrain with
scattered obstructions having heights generally less than 30 ft (9.1 m) and shorelines in hurricane prone regions. Exposure D
includes open exposure to large bodies of water in non-hurricane-prone regions.
4
For wind pressures greater than 80 psf (3.8 kN/m2), design is required in accordance with accepted practice and approved
manufacturer guidelines.
2. If relying on fastest mile speed maps or design provisions based on fastest wind speeds, the
designer should convert wind speeds to 3 second gust wind in accordance with Table C1.1 for
use with the given tables in this section.
13
PART 6.2 US DESIGN GUIDE
For SI: 1 foot = 0.3048 m; 1 inch = 25.4 mm; 1 mph = 1.6093 km/hr
1
This table is based on reinforcing bars with a minimum yield strength of 40,000 psi (276 Mpa) and concrete with a minimum specified
compression strength of 2,500 psi (17.2 Mpa)
2
Deflection criterion is L/240 where L is the height of the wall storey in inches.
3
Interpolation shall not be permitted.
4
Reinforcement spacing for 3.5 inch (88.9 mm) walls shall be permitted to be multiplied by 1.6 when reinforcing steel with a minimum yield
strength of 60,000 psi (414 Mpa) is used. Reinforcement shall not be less than one #4 bar at 48 inches (1.2m) on center.
5
Reinforcement spacing for 5.5 inch (139.7 mm) walls shall be permitted to be multiplied by 1.5 when reinforcing steel with a minimum yield
strength of 60,000 psi (414 Mpa) is used. Reinforcement shall not be less than one #4 bar at 48 inches (1.2m) on center.
6
A 3.5 inch wall shall not be permitted if wood ledgers are used to support floor or roof loads.
14
PART 6.2 US DESIGN GUIDE
15
PART 6.2 US DESIGN GUIDE
16
PART 6.2 US DESIGN GUIDE
For SI: 1 foot = 0.3048 m; 1 inch = 25.4 mm; 1 psf = 0.0479 kN/m2
1
Table values are based on reinforcing bars with a minimum yield strength of 40,000 psi (276 MPa) and concrete with a
minimum specified compressive strength of 2,500 psi (17.2 MPa).
2
Table values are based on a 3.5 in (88.9 mm) thick flat wall. For a 5.5 in (139.7 mm) thick flat wall, multiply the table values by
0.9. The adjusted values shall not result in solid wall lengths less than 4 ft.
3
Table values are based on a maximum unsupported wall height of 10 ft (3.0 m).
4
Values are based on a 30 foot (9.1 m) building end wall width. For a 45 ft (13.7 m) building end wall and roof pitches greater
than 7:12, multiply the table values by 1.2. For a 60 ft (18.3 m) building end wall and roof pitches greater than 7:12, multiply the
table values by 1.4.
5
Linear interpolation shall be permitted.
17
PART 6.2 US DESIGN GUIDE
Two-Storey ≤ 1:12 5.00 5.50 5.75 6.25 6.75 7.25 7.50 8.50
40
5:12 5.50 6.25 6.75 7.25 8.00 8.50 9.00 10.25
7:12 4
6.25 7.00 7.75 8.75 9.50 10.25 11.00 12.50
12:12 4
7.00 8.00 8.75 9.75 10.75 11.50 12.50 14.25
≤ 1:12 5.50 6.00 6.50 7.00 7.50 8.00 8.50 9.50
50
5:12 6.00 6.75 7.50 8.25 9.00 9.75 10.50 11.75
7:12 4
7.00 8.00 9.00 10.00 10.75 11.75 12.75 14.50
12:124 7.75 9.00 10.00 11.25 12.25 13.50 14.75 17.00
≤ 1:12 5.75 6.50 7.00 7.50 8.25 8.75 9.50 10.75
60
5:12 6.75 7.50 8.25 9.25 10.00 10.75 11.75 13.25
7:124 7.75 9.00 10.00 11.00 12.25 13.25 14.50 16.75
12:12 4
8.75 10.00 11.50 12.75 14.00 15.50 16.75 19.50
For SI: 1 foot = 0.3048 m; 1 inch = 25.4 mm; 1 psf = 0.0479 kN/m2
1
Table values are based on reinforcing bars with a minimum yield strength of 40,000 psi (276 MPa) and concrete with a minimum specified
compressive strength of 2,500 psi (17.2 MPa).
2
Table values are based on a 3.5 in (88.9 mm) thick flat wall. For a 5.5 in (139.7 mm) thick flat wall, multiply the table values by 0.9. The
adjusted values shall not result in solid wall lengths less than 4 ft.
3
Table values are based on a maximum unsupported wall height of 10 ft (3.0 m).
4
Values are based on a 30 foot (9.1 m) building end wall width. For a 45 ft (13.7 m) building end wall and roof pitches greater than 7:12,
multiply the table values by 1.2. For a 60 ft (18.3 m) building end wall and roof pitches greater than 7:12, multiply the table values by 1.4.
5
Linear interpolation shall be permitted.
18
PART 6.2 US DESIGN GUIDE
2. Minimum amount of solid wall length for Seismic Design Categories C, D1 and D2 shall be as per table 5.5.
19
PART 6.2 US DESIGN GUIDE
3. The larger amount of solid wall length as required by tables 5.2A, 5.2B, 5.2C and 5.5 shall be used.
20
PART 6.2 US DESIGN GUIDE
2. Please refer to Prescriptive Method Section 6 for additional requirements on floor, roof, and minimum wall
thickness requirements for high wind pressures and seismic design categories C, D1 and D2.
21
PART 6.2 US DESIGN GUIDE
Section 2.1- Reinforcing Steel for wall opening sides and Sill
Steel reinforcing bars are required for wall openings in reinforced concrete ICF walls around the sides and sill (bottom
of opening) for windows. Diagonal reinforcing steel is also required at the corners of the wall openings. The main
purpose of this reinforcing steel is to resist cracks in concrete due to shrinkage and temperature. Figures 1 and 2
below illustrates the placement of reinforcing steel accordingly;
22
PART 6.2 US DESIGN GUIDE
]
m
4m
91
"[
36
WALL OPENING
>=2ft (0.6m)
]
m
4m
DIAGONAL STEEL
91
REINFORCEMENT AT
"[
CORNERS 2#5 (2-15M)
36
TYPICAL AT EACH CORNER
Figure 2 – Diagonal reinforcing steel for wall openings
23
PART 6.2 US DESIGN GUIDE
3
3
4" [19mm] Min.
Lintel top and bottom reinforcement must extend the proper development length beyond the face of the opening
and is indicated as (W) on the figure. The minimum development length depends on many factors. As a rule of
thumb the minimum development length should be not less than 40 times the bar diameter and the minimum
required should not be less than 24 inches in order to use the Amvic lintel charts. Table 1 gives the minimum (W) for
the different reinforcing bars used in the charts.
If the wall opening is near the end of wall length and there is not enough space left for proper development length
then the lintel reinforcing bars should be bent around the corner at 90° into the adjacent perpendicular wall.
Table 1 - Minimum Development Length (W) For Lintel Top & Bottom reinforcing Bars
24
PART 6.2 US DESIGN GUIDE
Amvic has prepared lintel charts as a guideline for reinforcing steel requirements for different loading conditions
and spans. The following table 2 represents the limitations and assumptions that were used in developing the lintel
charts.
25
PART 6.2 US DESIGN GUIDE
26
PART 6.2 US DESIGN GUIDE
Tables for Lintels in Load Bearing Walls Carrying Second Storey Wood Frame + Light Frame Roof
ILL 4x10
ILL 4x12
ILL 4x16
ILL 4x20
ILL 4x24
ILL 6x10
ILL 6x12
ILL 6x16
ILL 6x20
ILL 6x24
ILL 8x10
ILL 8x12
ILL 8x16
ILL 8x20
ILL 8x24
ILL 10x10
ILL 10x12
ILL 10x16
ILL 10x20
ILL 10x24
Disclaimer
Amvic assumes no liability whatsoever with regards to the correct use of the lintel tables. It is the user’s responsibility to assess a specific
situation and determine if the limitations and assumptions given in sections 2.2 & 2.3 are satisfied in order to use the tables. It is also the user’s
responsibility to determine the correct table to use for the specific lintel being considered.
27
PART 6.2 US DESIGN GUIDE
70 psf 4969.2
1-#4 top
30 psf 4556.2 1-#4 bot.
#3 @ 3.75˝
70 psf 6201.2
30 psf 5023.0
70 psf 6849.0
30 psf 5700.3
70 psf 7773.0
4" [102mm]
Lintel Depth = 10˝ 1-#4 top = top rebar
Effective Depth = 7.8˝ 1-#4 bot.= bottom rebar
713
Fy = 60,000 psi
28
PART 6.2 US DESIGN GUIDE
70 psf 6859.4
1-#4 top
30 psf 5710.8 1-#4 bot.
#3 @ 4.5˝
70 psf 7783.4
Fy = 60,000 psi
29
PART 6.2 US DESIGN GUIDE
Fy = 60,000 psi
1316
30
PART 6.2 US DESIGN GUIDE
171
31
PART 6.2 US DESIGN GUIDE
70 psf 6253.8
30 psf 5075.7
70 psf 6901.6
30 psf 5752.9
70 psf 7825.6
Fy = 60,000 psi
20" [508mm]
171
32
PART 6.2 US DESIGN GUIDE
Fy = 60,000 psi
24" [610mm]
33
PART 6.2 US DESIGN GUIDE
70 psf 6922.2
1-#9 top
30 psf 5773.5 1-#9 bot.
#3 @ 8.5˝
70 psf 7846.2
4" [102mm]
Lintel Width = 4˝ Legend
Lintel Depth = 24˝ 1-#5 top = top rebar
Effective Depth = 21.5˝ 1-#5 bot.= bottom rebar
F’c @ 28 days = 3,000 psi #3 @ 8.5˝ = use #3 stirrup @ 8.5˝ O/C
2112" [546mm]
Fy = 60,000 psi
24" [610mm]
34
PART 6.2 US DESIGN GUIDE
70 psf 7819.1
6" [152mm]
Lintel Depth = 10˝ 1-#4 top = top rebar
Effective Depth = 7.75˝ 1-#4 bot.= bottom rebar
F’c @ 28 days = 3,000 psi #3 @ 3.75˝ = use #3 stirrup @ 3.5˝ O/C
73
10" [254mm]
Fy = 60,000 psi
35
PART 6.2 US DESIGN GUIDE
F’c @ 28 days = 3,000 psi 2-#3 @ 4.5˝ = use two #3 stirrups @ 4.5˝ O/C
12" [305mm]
Fy = 60,000 psi
93
36
PART 6.2 US DESIGN GUIDE
Fy = 60,000 psi
133
37
PART 6.2 US DESIGN GUIDE
70 psf 4170.9
30 psf 3747.1
70 psf 5063.1
30 psf 4650.1
70 psf 6295.1
30 psf 5117.0
70 psf 6942.9
30 psf 5794.2
70 psf 7866.9
Fy = 60,000 psi
133
38
PART 6.2 US DESIGN GUIDE
1712" [445mm]
Fy = 60,000 psi
20" [508mm]
20" [508mm]
39
PART 6.2 US DESIGN GUIDE
70 psf 6326.9
1-#9 top
30 psf 5148.8 1-#9 bot.
#3 @ 7˝
70 psf 6974.7
30 psf 5826.1
70 psf 7898.7
1712" [445mm]
Fy = 60,000 psi
20" [508mm]
20" [508mm]
40
PART 6.2 US DESIGN GUIDE
13" [554mm]
Fy = 60,000 psi
24" [610mm]
24" [610mm]
2116
2116
41
PART 6.2 US DESIGN GUIDE
13" [554mm]
Fy = 60,000 psi
24" [610mm]
24" [610mm]
2116
2116
42
PART 6.2 US DESIGN GUIDE
8" [203mm]
Lintel Depth = 10˝ 1-#5 top = top rebar
Effective Depth = 7.6˝ 1-#5 bot.= bottom rebar
F’c @ 28 days = 3,000 psi 2-#3 @ 3.75˝ = use two #3 stirrups @ 3.75˝ O/C
78
10" [254mm]
Fy = 60,000 psi
43
PART 6.2 US DESIGN GUIDE
912" [241mm]
12" [305mm]
Fy = 60,000 psi
44
PART 6.2 US DESIGN GUIDE
70 psf 3392.0
30 psf 3206.6
70 psf 4364.6
30 psf 3899.9
70 psf 5303.6
30 psf 4845.8
70 psf 6600.4
30 psf 5334.7
70 psf 7282.4
30 psf 6044.1
70 psf 8255.0
912" [241mm]
12" [305mm]
Fy = 60,000 psi
45
PART 6.2 US DESIGN GUIDE
1312" [343mm]
16" [406mm]
16" [406mm]
Fy = 60,000 psi
46
PART 6.2 US DESIGN GUIDE
70 psf 4405.4
30 psf 3940.7
70 psf 5344.4
30 psf 4886.5
70 psf 6641.1
30 psf 5375.5
70 psf 7323.1
30 psf 6084.9
70 psf 8295.7
1312" [343mm]
16" [406mm]
16" [406mm]
Fy = 60,000 psi
47
PART 6.2 US DESIGN GUIDE
1712" [445mm]
Fy = 60,000 psi
20" [508mm]
20" [508mm]
48
PART 6.2 US DESIGN GUIDE
1712" [445mm]
Fy = 60,000 psi
20" [508mm]
20" [508mm]
49
PART 6.2 US DESIGN GUIDE
1" [546mm]
Fy = 60,000 psi
24" [610mm]
24" [610mm]
212
212
50
PART 6.2 US DESIGN GUIDE
1" [546mm]
Fy = 60,000 psi
24" [610mm]
24" [610mm]
212
212
51
PART 6.2 US DESIGN GUIDE
785" [193mm]
10" [254mm]
Fy = 60,000 psi
52
PART 6.2 US DESIGN GUIDE
70 psf 3397.1
30 psf 3211.7
70 psf 4369.7
30 psf 3905.0
70 psf 5308.7
30 psf 4850.9
70 psf 6605.5
30 psf 5339.8
70 psf 7287.5
30 psf 6049.2
70 psf 8260.0
785" [193mm]
10" [254mm]
Fy = 60,000 psi
53
PART 6.2 US DESIGN GUIDE
2" [241mm]
10" [254mm] 10" [254mm] Lintel Depth = 12˝ 1-#5 top = top rebar
Effective Depth = 9.5˝ 1-#5 bot.= bottom rebar
F’c @ 28 days = 3,000 psi 2-#3 @ 4.5˝ = use two #3 stirrups @ 4.5˝ O/C
91
91
12" [305mm]
12" [305mm]
Fy = 60,000 ps
54
PART 6.2 US DESIGN GUIDE
70 psf 3422.6
1-#8+1-#6 top
30 psf 3237.1 1-#8+1-#6 bot.
2-#3 @ 4.5˝
70 psf 4395.2
30 psf 3930.5
70 psf 5334.2
30 psf 4876.3
70 psf 6631.0
30 psf 5365.3
70 psf 7312.9
30 psf 6074.7
70 psf 8285.5
2" [241mm]
10" [254mm] 10" [254mm] Lintel Depth = 12˝ 1-#5 top = top rebar
Effective Depth = 9.5˝ 1-#5 bot.= bottom rebar
F’c @ 28 days = 3,000 psi 2-#3 @ 4.5˝ = use two #3 stirrups @ 4.5˝ O/C
91
91
12" [305mm]
12" [305mm]
Fy = 60,000 psi
55
PART 6.2 US DESIGN GUIDE
1312" [343mm]
F’c @ 28 days = 3,000 psi 2-#3 @ 6.5˝ = use two #3 stirrups @ 6.5˝ O/C
16" [406mm]
16" [406mm]
Fy = 60,000 psi
56
PART 6.2 US DESIGN GUIDE
70 psf 5385.1
30 psf 4927.3
70 psf 6681.9
30 psf 5416.2
70 psf 7363.9
30 psf 6125.6
70 psf 8336.5
1312" [343mm]
F’c @ 28 days = 3,000 psi 2-#3 @ 6.5˝ = use two #3 stirrups @ 6.5˝ O/C
16" [406mm]
16" [406mm]
Fy = 60,000 psi
57
PART 6.2 US DESIGN GUIDE
1" [445mm]
20" [508mm]
20" [508mm]
Fy = 60,000 psi
172
172
58
PART 6.2 US DESIGN GUIDE
1" [445mm]
20" [508mm]
20" [508mm]
Fy = 60,000 psi
172
172
59
PART 6.2 US DESIGN GUIDE
2112" [546mm]
Fy = 60,000 psi
24" [610mm]
24" [610mm]
60
PART 6.2 US DESIGN GUIDE
2112" [546mm]
Fy = 60,000 psi
24" [610mm]
24" [610mm]
61
PART 6.2 US DESIGN GUIDE
Tables for Lintels in Load Bearing Walls Carrying Second Storey ICF + Light Frame Roof
ILH 4x10
ILH 4x12
ILH 4x16
ILH 4x20
ILH 4x24
ILH 6x10
ILH 6x12
ILH 6x16
ILH 6x20
ILH 6x24
ILH 8x10
ILH 8x12
ILH 8x16
ILH 8x20
ILH 8x24
ILH 10x10
ILH 10x12
ILH 10x16
ILH 10x20
ILH 10x24
Disclaimer
Amvic assumes no liability whatsoever with regards to the correct use of the lintel tables. It is the user’s responsibility to assess a specific
situation and determine if the limitations and assumptions given in sections 2.2 & 2.3 are satisfied in order to use the tables. It is also the user’s
* Check
responsibility to determine the correct table to use for the specific lintel being applicability limits table 3 to use this chart
considered.
62
PART 6.2 US DESIGN GUIDE
70 psf 5803.4
30 psf 5345.6
70 psf 7100.2
30 psf 5834.6
70 psf 7782.2
30 psf 6544.0
70 psf 8754.8
Fy = 60,000 psi
63
PART 6.2 US DESIGN GUIDE
70 psf 7110.3
1-#4 top
30 psf 5844.6 1-#4 bot.
#3 @ 4.5˝
70 psf 7792.3
1-#4 top
30 psf 6554.0 1-#4 bot.
#3 @ 4.5˝
70 psf 8764.9
Fy = 60,000 psi
64
PART 6.2 US DESIGN GUIDE
Fy = 60,000 psi
1316
65
PART 6.2 US DESIGN GUIDE
Fy = 60,000 psi
20" [508mm]
171
66
PART 6.2 US DESIGN GUIDE
70 psf 5854.0
30 psf 5396.1
70 psf 7150.8
30 psf 5885.1
70 psf 7832.7
30 psf 6594.5
70 psf 8805.3
Fy = 60,000 psi
20" [508mm]
171
67
PART 6.2 US DESIGN GUIDE
Fy = 60,000 psi
68
PART 6.2 US DESIGN GUIDE
70 psf 7170.5
1-#9 top
30 psf 5904.8 1-#9 bot.
#3 @ 8.5˝
70 psf 7852.5
30 psf 6614.2
70 psf 8825.1
4" [102mm]
Fy = 60,000 psi
69
PART 6.2 US DESIGN GUIDE
70 psf 7505.1
1-#4 top
30 psf 6239.4 1-#4 bot.
#3 @ 3.75˝
1-#5 top
(35 feet) 50 psf 7213.2 1-#5 bot.
#3 @ 3.75˝
70 psf 8187.0
1-#5 top
30 psf 6948.8 1-#5 bot.
#3 @ 3.75˝
70 psf 9159.6
6" [152mm]
Lintel Depth = 10˝ 1-#5 top = top rebar
Effective Depth = 7.8˝ 1-#5 bot.= bottom rebar
F’c @ 28 days = 3,000 psi #3 @ 3.75˝ = use one #3 stirrup @ 3.75˝ O/C
73
10" [254mm]
Fy = 60,000 psi
70
PART 6.2 US DESIGN GUIDE
F’c @ 28 days = 3,000 psi #3 @ 4.5˝ = use one #3 stirrup @ 4.5˝ O/C
12" [305mm]
Fy = 60,000 psi
93
71
PART 6.2 US DESIGN GUIDE
4" [349mm]
16" [406mm]
16" [406mm]
Fy = 60,000 psi
133
133
72
PART 6.2 US DESIGN GUIDE
1712" [445mm]
Fy = 60,000 psi
20" [508mm]
20" [508mm]
73
PART 6.2 US DESIGN GUIDE
70 psf 6284.7
30 psf 5826.9
70 psf 7581.5
30 psf 6315.8
(35
50 psf 7289.6
feet)
70 psf 8263.5
30 psf 7025.2
70 psf 9236.0
1712" [445mm]
Fy = 60,000 psi
20" [508mm]
20" [508mm]
74
PART 6.2 US DESIGN GUIDE
13" [554mm]
Fy = 60,000 psi
24" [610mm]
24" [610mm]
2116
2116
75
PART 6.2 US DESIGN GUIDE
70 psf 7612.0
2-#6 top
30 psf 6346.4 2-#6 bot.
2-#3 @ 8.5˝
1-#8+1-#5 top
(35 feet) 50 psf 7320.2 1-#8+1-#5 bot.
2-#3 @ 8.5˝
70 psf 8294.0
1-#8+1-#5 top
30 psf 7055.7 1-#8+1-#5 bot.
2-#3 @ 8.5˝
70 psf 9266.6
13" [554mm]
Fy = 60,000 psi
24" [610mm]
24" [610mm]
2116
2116
76
PART 6.2 US DESIGN GUIDE
8" [203mm]
Lintel Depth = 10˝ 1-#5 top = top rebar
Effective Depth = 7.75˝ 1-#5 bot.= bottom rebar
F’c @ 28 days = 3,000 psi 2-#3 @ 3.75˝ = use two #3 stirrups @ 3.75˝ O/C
78
10" [254mm]
Fy = 60,000 psi
77
PART 6.2 US DESIGN GUIDE
912" [241mm]
12" [305mm]
Fy = 60,000 psi
78
PART 6.2 US DESIGN GUIDE
1312" [343mm]
16" [406mm]
16" [406mm]
Fy = 60,000 psi
79
PART 6.2 US DESIGN GUIDE
1712" [445mm]
Fy = 60,000 psi
20" [508mm]
20" [508mm]
80
PART 6.2 US DESIGN GUIDE
1712" [445mm]
Fy = 60,000 psi
20" [508mm]
20" [508mm]
81
PART 6.2 US DESIGN GUIDE
1" [546mm]
24" [610mm]
24" [610mm]
Fy = 60,000 psi
212
212
82
PART 6.2 US DESIGN GUIDE
1" [546mm]
24" [610mm]
24" [610mm]
Fy = 60,000 psi
212
212
83
PART 6.2 US DESIGN GUIDE
785" [193mm]
10" [254mm]
Fy = 60,000 psi
84
PART 6.2 US DESIGN GUIDE
2" [241mm]
10" [254mm] 10" [254mm] Lintel Depth = 12˝ 1-#5 top = top rebar
Effective Depth = 9.6˝ 1-#5 bot.= bottom rebar
F’c @ 28 days = 3,000 psi 2-#3 @ 4.5˝ = use two #3 stirrups @ 4.5˝ O/C
91
91
12" [305mm]
12" [305mm]
Fy = 60,000 psi
85
PART 6.2 US DESIGN GUIDE
1312" [343mm]
F’c @ 28 days = 3,000 psi 2-#3 @ 6.5˝ = use two #3 stirrups @ 6.5˝ O/C
16" [406mm]
16" [406mm]
Fy = 60,000 psi
86
PART 6.2 US DESIGN GUIDE
70 psf 5158.1
30 psf 4972.6
70 psf 6130.7
30 psf 5666.0
70 psf 7069.7
30 psf 6611.8
70 psf 8366.5
30 psf 7100.8
70 psf 9048.4
30 psf 7810.2
70 psf 10021.0
1312" [343mm]
F’c @ 28 days = 3,000 psi 2-#3 @ 6.5˝ = use two #3 stirrups @ 6.5˝ O/C
16" [406mm]
16" [406mm]
Fy = 60,000 psi
87
PART 6.2 US DESIGN GUIDE
1" [445mm]
20" [508mm]
20" [508mm]
Fy = 60,000 psi
172
172
88
PART 6.2 US DESIGN GUIDE
Floor Clear Ground Total Factored Carrying Second Storey ICF + Light Frame Roof
snow Uniform Load Lintel Span - Feet
Spanfeet load psf lbs/ft
12 ft 13 ft 14 ft 15 ft 16 ft 17 ft 18 ft 19 ft 20 ft
1-#6+1-#5 top 1-#6+1-#5 top 2-#6 top 1-#8+1-#5 top 1-#8+1-#6 top 2-#8 top 1-#9+1-#8 top 1-#9+1-#8 top 2-#9 top
30 psf 3711.0 1-#6+1-#5 bot. 1-#6+1-#5 bot. 2-#6 bot. 1-#8+1-#5 bot. 1-#8+1-#6 bot. 2-#8 bot. 1-#9+1-#8 bot. 1-#9+1-#8 bot. 2-#9 bot.
2-#3 @ 8.5˝ 2-#3 @ 8.5˝ 2-#3 @ 8.5˝ 2-#3 @ 8.5˝ 2-#3 @ 8.5˝ 2-#3 @ 8.5˝ 2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝
1-#6+1-#5 top 2-#6 top 1-#8+1-#5 top 1-#8+1-#6 top 2-#8 top 2-#8 top 1-#9+1-#8 top 2-#9 top
(10 feet) 50 psf 4026.9 1-#6+1-#5 bot. 2-#6 bot. 1-#8+1-#5 bot. 1-#8+1-#6 bot. 2-#8 bot. 2-#8 bot. 1-#9+1-#8 bot. 2-#9 bot.
2-#3 @ 8.5˝ 2-#3 @ 8.5˝ 2-#3 @ 8.5˝ 2-#3 @ 8.5˝ 2-#3 @ 8.5˝ 2-#3 @ 8.5˝ 2-#3 @ 7˝ 2-#3 @ 7˝
1-#6+1-#5 top 2-#6 top 1-#8+1-#5 top 1-#8+1-#6 top 2-#8 top 1-#9+1-#8 top 2-#9 top 2-#9 top
70 psf 4342.7 1-#6+1-#5 bot. 2-#6 bot. 1-#8+1-#5 bot. 1-#8+1-#6 bot. 2-#8 bot. 1-#9+1-#8 bot. 2-#9 bot. 2-#9 bot.
2-#3 @ 8.5˝ 2-#3 @ 8.5˝ 2-#3 @ 8.5˝ 2-#3 @ 8.5˝ 2-#3 @ 8.5˝ 2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝
1-#6+1-#5 top 2-#6 top 1-#8+1-#5 top 1-#8+1-#6 top 2-#8 top 1-#9+1-#8 top 2-#9 top 2-#9 top
30 psf 4314.2 1-#6+1-#5 bot. 2-#6 bot. 1-#8+1-#5 bot. 1-#8+1-#6 bot. 2-#8 bot. 1-#9+1-#8 bot. 2-#9 bot. 2-#9 bot.
2-#3 @ 8.5˝ 2-#3 @ 8.5˝ 2-#3 @ 8.5˝ 2-#3 @ 8.5˝ 2-#3 @ 8.5˝ 2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝
2-#6 top 1-#8+1-#5 top 1-#8+1-#6 top 2-#8 top 1-#9+1-#8 top 1-#9+1-#8 top 2-#9 top
(15 feet) 50 psf 4761.6 2-#6 bot. 1-#8+1-#5 bot. 1-#8+1-#6 bot. 2-#8 bot. 1-#9+1-#8 bot. 1-#9+1-#8 bot. 2-#9 bot.
2-#3 @ 8.5˝ 2-#3 @ 8.5˝ 2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝
2-#6 top 1-#8+1-#5 top 2-#8 top 2-#8 top 1-#9+1-#8 top 2-#9 top
70 psf 5209.0 2-#6 bot. 1-#8+1-#5 bot. 2-#8 bot. 2-#8 bot. 1-#9+1-#8 bot. 2-#9 bot.
2-#3 @ 8.5˝ 2-#3 @ 8.5˝ 2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝
2-#6 top 1-#8+1-#5 top 1-#8+1-#6 top 2-#8 top 1-#9+1-#8 top 2-#9 top
30 psf 5023.6 2-#6 bot. 1-#8+1-#5 bot. 1-#8+1-#6 bot. 2-#8 bot. 1-#9+1-#8 bot. 2-#9 bot.
2-#3 @ 8.5˝ 2-#3 @ 8.5˝ 2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝
1-#8+1-#5 top 1-#8+1-#6 top 2-#8 top 1-#9+1-#8 top 2-#9 top
(20 feet) 50 psf 5602.6 1-#8+1-#5 bot. 1-#8+1-#6 bot. 2-#8 bot. 1-#9+1-#8 bot. 2-#9 bot.
2-#3 @ 8.5˝ 2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝
1-#8+1-#5 top 2-#8 top 2-#8 top 1-#9+1-#8 top 2-#9 top
70 psf 6181.6 1-#8+1-#5 bot. 2-#8 bot. 2-#8 bot. 1-#9+1-#8 bot. 2-#9 bot.
2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝
1-#8+1-#5 top 1-#8+1-#6 top 2-#8 top 1-#9+1-#8 top 2-#9 top
30 psf 5716.9 1-#8+1-#5 bot. 1-#8+1-#6 bot. 2-#8 bot. 1-#9+1-#8 bot. 2-#9 bot.
2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝
1-#8+1-#6 top 2-#8 top 1-#9+1-#8 top 2-#9 top
(25 feet) 50 psf 6418.8 1-#8+1-#6 bot. 2-#8 bot. 1-#9+1-#8 bot. 2-#9 bot.
2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝
2-#8 top 2-#8 top 1-#9+1-#8 top
70 psf 7120.6 2-#8 bot. 2-#8 bot. 1-#9+1-#8 bot.
2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝
1-#8+1-#6 top 2-#8 top 1-#9+1-#8 top 2-#9 top
30 psf 6662.8 1-#8+1-#6 bot. 2-#8 bot. 1-#9+1-#8 bot. 2-#9 bot.
2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝
2-#8 top 1-#9+1-#8 top 2-#9 top
(30 feet) 50 psf 7540.1 2-#8 bot. 1-#9+1-#8 bot. 2-#9 bot.
2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝
2-#8 top 2-#9 top
70 psf 8417.4 2-#8 bot. 2-#9 bot.
2-#3 @ 7˝ 2-#3 @ 7˝
2-#8 top 2-#8 top 1-#9+1-#8 top
30 psf 7151.7 2-#8 bot. 2-#8 bot. 1-#9+1-#8 bot.
2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝
2-#8 top 1-#9+1-#8 top 2-#9 top
(35 feet) 50 psf 8125.5 2-#8 bot. 1-#9+1-#8 bot. 2-#9 bot.
2-#3 @ 7˝ 2-#3 @ 7˝ 2-#3 @ 7˝
1-#9+1-#8 top 2-#9 top
70 psf 9099.4 1-#9+1-#8 bot. 2-#9 bot.
2-#3 @ 7˝ 2-#3 @ 7˝
2-#8 top 1-#9+1-#8 top
30 psf 7861.1 2-#8 bot. 1-#9+1-#8 bot.
2-#3 @ 7˝ 2-#3 @ 7˝
1-#9+1-#8 top 2-#9 top
(40 feet) 50 psf 8966.5 1-#9+1-#8 bot. 2-#9 bot.
2-#3 @ 7˝ 2-#3 @ 7˝
2-#9 top
70 psf 10072.0 2-#9 bot.
2-#3 @ 7˝
1" [445mm]
20" [508mm]
20" [508mm]
Fy = 60,000 psi
172
172
89
PART 6.2 US DESIGN GUIDE
2112" [546mm]
Fy = 60,000 psi
24" [610mm]
24" [610mm]
90
PART 6.2 US DESIGN GUIDE
2112" [546mm]
Fy = 60,000 psi
24" [610mm]
24" [610mm]
91
ICF US DESIGN GUIDE
Amvic ICF is a high quality, innovative construction system designed for both residential and
commercial applications. Competitive pricing, extensive product distribution and excellent
technical support are combined to provide our clients with a simplified approach to a
superior finished product. If any questions or concerns are not completely addressed in this
guide, please contact us and our staff will be happy to answer any question. At Amvic, we
pride ourselves in offering our customers an exceptional level of customer service.
Disclaimer
Information contained in this document is provided as a guideline only, without any warranty
of any kind, either expressed or implied, including, but not limited to, the implied warranties
of merchantability, fitness for a particular purpose, and freedom of infringement.
This document provides basic reinforcement design guidelines for Amvic ICF and is intended
to supplement, rather than replace, the basic construction knowledge of a professional
engineer. All installations of Amvic ICF must be in accordance with all applicable building
codes and/or under the guidance of a licensed professional engineer. In all cases, applicable
building code regulations take precedence over this manual.
Technical Support
Please contact us for any inquiries pertaining to information included in this guide, or if you
require any other technical assistance.
Email [email protected]
The Amvic website is updated regularly with the most current news, including testing
reports, technical bulletins and evaluation reports. This document is available both in print
and as a downloadable file from www.amvicsystem.com
PRO0295
www.amvicsystem.com
BUILD TO A HIGHER STANDARD