Aplicacion Uk Casa Best-Practice-Guide-3
Aplicacion Uk Casa Best-Practice-Guide-3
Connecting a
microgeneration
system to a
domestic or
similar electrical
installation
(in parallel with the
mains supply)
This is one of a series of Best Practice Guides produced by
Electrical Safety First1 in association with leading industry
bodies for the benefit of electrical contractors and installers,
and their customers.
BEAMA Installation
www.beamainstallation.org.uk
In electronic format, this Guide is intended to be made available free of
British Gas charge to all interested parties. Further copies may be downloaded from
www.britishgas.co.uk the websites of some of the contributing organisations.
City & Guilds
www.cityandguilds.com The version of this Guide on the Electrical Safety First website
(www.electricalsafetyfirst.org.uk) will always be the latest. Feedback on
ELECSA any of the Best Practice Guides is always welcome – email
www.elecsa.co.uk [email protected]
Electrical Contractors’ Association
www.eca.co.uk Electrical Safety First is supported by all sectors of the electrical industry,
approvals and research bodies, consumer interest organisations, the
Energy Networks Association electrical distribution industry, professional institutes and institutions,
www.energynetworks.org regulatory bodies, trade and industry associations and federations, trade
Gemserv unions, and local and central government.
www.gemserv.co.uk
*Electrical Safety First (formerly the National Inspection Council for
Health and Safety Executive
Electrical Installation Contracting) is a charitable non-profit making
www.hse.gov.uk
organisation set up in 1956 to protect users of electricity against the
Institution of Engineering & Technology hazards of unsafe and unsound electrical installations.
www.theiet.org
Local Authority Building Control
www.labc.uk.com
Published by:
MOCOPA
www.mocopa.org.uk
Electrical Safety First
Micropower Council Unit 331
www.micropower.co.uk Metal Box Factory
30 Great Guildford Street
NAPIT
London SE1 0HS
www.napit.org.uk
NICEIC
Tel: 0203 463 5100
www.niceic.com
Email: [email protected]
Renewable Energy Association Website: www.electricalsafetyfirst.org.uk
www.r-e-a.net
Electrical Safety First and other contributors believe that the guidance
SELECT (Electrical Contractors’ and information contained in this Best Practice Guide is correct, but all
Association of Scotland) parties must rely on their own skill and judgement when making use of
www.select.org.uk it. Neither Electrical Safety First nor any contributor assumes any liability
to anyone for any loss or damage caused by any error or omission in this
Sundog Energy Guide, whether such error or omission is the result of negligence or any
www.sundog-energy.co.uk other cause. Where reference is made to legislation, it is not to be
considered as legal advice. Any and all such liability is disclaimed.
The Guide takes into account the publication of The Guide does not provide installation guidance
Amendment 1 to BS 7671: 2008. where it is intended to install more than one
microgenerator. In such cases it is necessary to
The Guide does not provide installation guidance
consider the possibility of interaction between the
specific to any particular types of microgeneration.
protection and control equipment of the
BS 7671: 2008 Section 712 contains particular
microgenerators, and the specific advice of the
requirements for photovoltaic installations, as does
manufacturers or suppliers of each of the
DTI Publication URN 06/1972*, Photovoltaics in
microgenerators should be obtained and followed.
Buildings, Guide to the installation of PV systems
(2nd Edition), dated 2006. For any microgenerator Where multiple microgeneration installations are to
installation, the instructions of the manufacturer or be installed in a close geographical region (such as in
supplier should be followed. a housing development), it is also necessary to
obtain the permission of the DNO in advance.
* URN 06/1972 is expected to be superseded in Autumn 2011 by a revised version, called Guide to the Installation of Photovoltaic
Systems, containing material changes. Further information may be obtained from www.microgenerationcertification.org
† G83/1-1 is expected to be superseded by a revised version (G83/2), containing material changes, during late 2011 or early 2012.
* URN 06/1972 is expected to be superseded in Autumn 2011 by a revised version, called Guide to the Installation of Photovoltaic
Systems, containing material changes. Further information may be obtained from www.microgenerationcertification.org
A)
B)
This option is technically simpler and creates least (iii) Means must also be provided to prevent the
impact on existing use and hence on the user of the connection of the microgenerator to the mains
installation. The cost implication may not be supply in the event of loss of that supply or
significant when compared to the cost of the deviation of the voltage or frequency at the
generator itself, and in some cases it may be less supply terminals from the declared values
expensive in view of the need to meet the technical (Regulation 551.7.5 of BS 7671 refers).
requirements detailed below for connecting into an Note. The requirements are given in G83 and in
BS EN 50438. Amongst other things, it is required that
existing final circuit.
feeding power to the distribution network will only
commence after the voltage and frequency on the
Whichever of the two options is chosen, it is
distribution network have been within the limits of the
imperative that the safety of the electrical interface protection settings for a minimum of 3 minutes
installation is not impaired by the installation of the for mechanical a.c. generation or 20 s for inverter based
microgenerator. systems.
(viii)Where a microgenerator is connected on the protective device and Ig is the rated output
same side of an RCD as final circuits protected current of the microgenerator (Regulation
by that RCD, the RCD must disconnect the line 551.7.2(i) of BS 7671 refers). This may
and neutral conductors (Regulation 551.4.2 require the protective device to be replaced
refers). For example, this applies to an with one having a lower rated current.
A microgenerator is a source of supply to the Isolation and switching devices in any d.c. circuits,
electrical installation. A main linked switch or linked such as on the d.c. side of a PV installation, must be
circuit-breaker for this source must therefore be of types suitable for d.c use. Switchgear intended for
provided in a readily accessible position as near as a.c. circuits is often not suitable for d.c. or may need
practicable to the origin of the installation, such as to be derated for such use. The manufacturer’s
adjacent to the consumer unit, as a means of specific advice in this respect should be obtained
switching off the supply on load and as a means of and followed.
isolation (Regulations 132.15.1, 537.1.4 and 551.2.4
To comply with the labelling requirements of
refer). The switch or circuit-breaker must disconnect
Regulation 514.15.1 relating to alternative or
the line and neutral conductors (Regulation
additional sources of supply, and those of clause 6.2
537.2.1.1 refers).
of G83/1-1† and clause 6.4 of BS EN 50438: 2007,
Means must also be provided to isolate the warning labels must be provided as a minimum at:
microgenerator from the public mains supply, as
• the DNO’s fused cutout
required by Regulation 551.7.6. This must be located
at an accessible position within the installation, as • the DNO’s meter position
required by clause 5.3 of G83/1-1†. Clause 4.2.1.3 of • the consumer unit(s)
BS EN 50438: 2007 states that ‘Where this means • the output terminals of the microgenerator
of isolation is not accessible for the DNO at all times
it is acceptable to provide two means of automatic
• the points of isolation for the mains supply and
the microgenerator supply.
disconnection, with a single control. At least one of
the means of disconnection must be afforded by the In the case of a renewable source, such as PV cells or
separation of mechanical contacts.’ a wind turbine, a notice must be placed at the
microgenerator isolator to warn that the conductors
The same means of isolation could be used for the on the microgenerator side may remain live when
purposes of both the previous two paragraphs, if it the isolator is open.
meets all the requirements referred to in those
paragraphs. The Health and Safety (Safety Signs and Signals)
Regulations 1996 stipulate that the labels should
If the microgenerator is not in the same room as the display the prescribed triangular shape and font size
main linked switch or linked circuit-breaker (as may using black on yellow colouring. A typical label is
be the case with the inverter of a PV system), a local shown below.
isolator should also be installed adjacent to the
microgenerator (Regulation 537.2.1.1 refers).
† G83/1-1 is expected to be superseded by a revised version (G83/2), containing material changes, during late 2011 or early 2012.
British Standards
BS 7671
Requirements for electrical installations. IET Wiring
Regulations. Seventeenth edition
BS EN 50438
Requirements for the connection of micro-generators
in parallel with public low-voltage distribution
networks
BS EN 61008
Residual current operated circuit-breakers without
integral overcurrent protection for household and
similar uses (RCCBs). General rules
BS EN 61009
Residual current operated circuit-breakers with
integral overcurrent protection for household and
similar uses (RCBOs). General rules
Other standards
IEC 62423
Type F and type B residual current operated circuit-
breakers with and without integral overcurrent
protection for household and similar uses