Datasheet For Distribution Boards
Datasheet For Distribution Boards
System at T2-II
NOTES:
1) Test and Certificates: Submit complete certified manufacturer's type test and routine test records in accordance with standard applicable.
All equipment should be ASTA or KEMA certfied.
2) Interior of Distribution board shall be pan assenmbly consisting of galvanised sheet steel chassis mimimum 2mm thick, folded, flanged and
reinforced, with bus bars vertically arranged and mounted on moulded insulators with insulation grade 25kV for 1 minute.
3) Moulded insulators shall be minimum temperature rating of 130 deg.C and insulation grade of 3.5kV for one minute.
4) Circuit Breaker shall be mounted in twin arrangement (except for larger circuit breakers) and bilted rigidly to copper cross and centre bus
connectors.
5) Manufacturer shall provide all special tools required for Distribution Board installation, commissioning and maintenance
6) Panel space heater rating to be confirmed by Manufacturer.