Manual Control
Manual Control
, Ltd
Microcomputer temperature controller
{JY-260 Product Manual}
Thank you for choosing our JY280 microcomputer temperature controller. Please read this
product manual carefully before installing and using the product. Please keep this product
manual in Anshan for future use.
This product adopts the latest microelectronics technology, brings together the advantages and
experience of domestic and foreign stand-alone thermostats, and provides the most lively
solution while meeting the needs of users. The product has the advantages of small size LED
digital tube red display, simple operation, accurate temperature control and strong anti-drying
ability. It is a small integrated intelligent controller with stable performance. This product is
suitable for all kinds of occasions such as heating, breeding, incubation, etc. It has the function of
long-term memory of the parameters set by Lu.
It has the function of long-term memory of the set parameters when the power is off.
1. Technical Participation:
11. Working voltage: 230 VAC, power consumption of the whole machine <2w;
1.2. Temperature measurement range: -50C-260°C, measurement error: ±0.5°C;
1.3. Temperature inspection range: -50C-20C; Temperature control accuracy: 1℃ Resolution:
0.1℃; Hysteresis: adjustable between 1-100℃;
1.4. Temperature probe: NTC B4537 soil 1% (standard with 1.5 meters of Teflon cable, regardless
of positive or negative);
1.5. Load output: 1 relay, normally open contact 40A/250VAC;
1.6.Working environment: temperature: 40C -85C; humidity: 90%RH without condensation;
1.7. Overall dimensions: 75 (width) X35 (height) X82 (depth) mm;
1.8. Hole size: 71 (width) x29 (height) mm;
2. Indicator status description:
Indicator light The indicator light is Light does not shine Light flashes
always on
please press the Ser key, press the △ key or the ▽key to modify the parameters in the code.
After the modification is completed, press the Set key to save and exit; (If you do not press
any-key within 5 seconds during the operation, it will return to normal temperature
measurement State)
Note: 1A minimum lower limit and HA maximum upper limit are non-control temperature
parameter adjustments. If changed, the control temperature adjustment range will be reduced.
User function parameter setting:
6.1. Master temperature setting:
After power-on, when the current ambient temperature status is displayed, press the set key
once to flash and display the factory default control temperature. Press the △ key to change
the required value and then press the Set key to save and exit. (Press and hold the △ key or ▽
key for 2 seconds when adjusting the main control temperature to quickly adjust the value);
6.2. Heating control:
For example, set the control temperature value to 80°C, and the temperature return difference
is 2°C. When the ambient temperature value >= the set temperature value (80℃), the relay will
open and close the output load; when the ambient temperature value <= the set temperature
value (8℃)-the differential temperature (2℃) and set " After "delayed start", the relay pulls in
and starts the output load: (if the delay function is not required, the delayed start (code PU) can
be read as 0);
6.3Restore factory values: Keep pressing the RST button for 5 seconds and wait for the display to
flicker and then let go. At this time, after the screen display flickers 6 times, all the parameters set
by the user will be restored to the factory default values;
6.4On/off function: When the host displays the ambient temperature and normal temperature,
keep pressing the △ key for five seconds without letting go to turn off the thermostat. When
the thermostat is off and in the standby state, keep pressing the key for five seconds without
letting go Turn on the thermostat;
6.5. User parameter lock: Press the ▽ key for 5 seconds and the display flashes "OFF" for 6
times, indicating that the user has said that the parameter is locked. According to the same
operation, the display flashes "ON" for 6 times, indicating that the user has set the parameter
The lock is released. (After the parameters are locked, the user can only view but not modify, but
the control temperature adjustment is still effective)
7. Installation method:
7.1 The newly purchased host first press the center point of the yellow movable buckle on both
sides and slide it down and then open the hole according to the hole size;
7.2Then align the mainframe with the wiring terminal at the window that has been opened and
push it in;
7.3Then push the yellow movable buckle from the wiring terminal to the slide rails on both sides
of the shell to the position where the host is not loose at the front and back;
9.Fault prompt:
9.1. When the sensor is short-circuited or the current ambient temperature is away from 260
degrees, the flashing HHH prompt will be displayed and the load output will be turned off;
9.2When the sensor has an open circuit or the current ambient temperature value is lower than
-50 degrees, the flashing LLL prompt will be displayed and the load output will be turned off;
10. Installation wiring diagram: