Power System Protection: Week-01
Power System Protection: Week-01
Week-01
Shoaib Ahmed Shaikh
Lecturer (EE)
Sukkur IBA University
Books:
1. Protective Relaying: Principles and Applications,
Fourth Edition By J. Lewis Blackburn, Thomas J.
Domin
▪ Transformer Protection
▪ Generator Protection
▪ Motor Protection
• The opening of one or two of the three phases makes the system
unbalanced. Unbalanced currents flowing in rotating machines set up
harmonics, thereby heating the machines in short periods of time. In
the case of cables, transformers, generators and other equipment, the
causes of faults are failure of solid insulation due to aging, heat,
moisture or overvoltage, mechanical damage, accidental contact with
earth.
• Sometime circuit breakers may trip due to errors in the switching
operation, testing or maintenance work, wrong connections, defects
in protective devices.
• The fault impedance being low, the fault current are relatively high.
During the fault, the power flow is diverted towards the fault and
supply to the neighboring zones is affected.
• Protection is needed not only against short circuits but also against
any other abnormal conditions which may arise on a power system.
• A few examples of other abnormal conditions are:
✓ Over speed of generators and motors,
✓ Over/Under voltage / frequency/current,
✓ Loss of excitation,
✓ Overheating of stator and rotor of an alternator,
✓ Reversal of power,
✓ Temperature rise,
✓ Power swings,
✓ Instability.
Faults Analysis and Calculation:
• The purpose of fault analysis is to determine the values of voltages
and currents at different points of the system during the fault. Such
an analysis enables us to select appropriate protective schemes,
relays, and circuit breakers in order to save the system from the
abnormal condition within minimum time.
• On the other hand, an overload means that loads greater than the designed values
have been imposed on the system. Under such conditions, the voltage at the
overload point may be low, but not zero. The undervoltage conditions may
extend for some distance beyond the overload point into the remainder of the
system. The currents in the overloaded equipment are high but are substantially
lower than that in the case of a short-circuit.
• Earth fault is the unintentional fault between the live conductor and the earth.
It also occurs, because of the insulation breakdown. When the fault occurs, the
short-circuit currents flow through the system, and this current is returned
through the earth or any electrical equipment. This fault current damaged the
equipment of the power system and also interrupted the continuity of the supply.
• A short-circuit current is differentiated from an overload by the
fact that the current is flowing outside of the normal path. These
currents are much larger than overload and can cause significant
damage in the form of thermal, magnetic, and arcing. Time is
critical in the interruption of short circuits from the system.
Causes of short-circuit
A short circuit in the power system is the result of some kind of
abnormal conditions in the system. It may be caused due to
internal and/or external effects.
(ii) The magnitude of short-circuit current determines the setting and sometimes the
types and location of protective system.
❖They are generally installed along with the circuit breaker in order
that repairs, and replacement of circuit breakers can be made without
any danger
Fuse :
❖A fuse is a short piece of wire which melts when excessive current
flows through it for sufficient time.
❖It is inserted in series with the circuit to be protected.
❖Under normal operating conditions, the fuse element is at a
temperature below its melting point. Therefore, it carries the normal
load current without overheating. However, when a short circuit or
overload occurs, the current through the fuse element increases
beyond its rated capacity.
❖This raises the temperature, and the fuse element melts (or blows
out), disconnecting the circuit protected by it. In this way, a fuse
protects the machines and equipment from damage due to
excessive currents.
❖In some types the sensing device and the interrupting device are
completely separated, interconnected only through external control
wiring.
❖In other types the sensing and interrupting functions are combined
in the same device.
Fuse and Circuit breaker difference:
❖A fuse is both a sensing and interrupting device. It is connected in
series with the circuit and responds to thermal effects produced by
current flow through it. Its fusible element is designed to open at a
predetermined time depending on the amount of current that flows.
❖A relay is a device which detects the fault and supplies information to the breaker
for circuit interruption.
(i) The primary winding of a current transformer (C.T.) (The circuit to be protected
carries a large current (normal or fault current) and is reduced to a suitable value for
relay operation with the help of a current transformer.) which is connected in series
with the circuit to be protected. The primary winding often consists of the main
conductor itself.
(ii) The second circuit is the secondary winding of C.T. connected to the relay
operating coil.
Relay Trip Circuit:
(iii) The third circuit is the tripping circuit which is a part of circuit breaker that
will react to action of relay coil during fault condition. which included a battery,
trip coil and relay contacts. It will react according to relay coil or relay contacts.
❖Consequently, the contacts of the circuit breaker remain closed. When a fault
occurs, a large current flows through the primary of C.T. This increases the
secondary e.m.f. and hence the current through the relay operating coil. The relay
contacts are closed resulting in the energization of the trip coil of the circuit
breaker. Due to this, current starts flowing from battery and activates the circuit
breaker opening mechanism in order to isolate the faulty part from rest of the
healthy system.
Instrument Transformers:
❖Instrument transformers are used in AC system for measurement of electrical
quantities such as voltage, current, and power. These devices are also used with
protective relay for protection of power system.
❖If we want to measure extremely high values of current and voltage then there are
two ways of measuring it.
❖One is to use high-capacity instruments which would be obviously costly.
❖Second way is to use the transformation property of current and voltage.
❖Current and voltage can be stepped down by using a transformer whose turn’s
ratio is known and then measuring the stepped down current and voltage by a
normal ammeter or voltmeter.
❖The original magnitude can be determined by multiplying the stepped down
magnitude with the turn’s ratio. Such specially constructed transformer with
accurate turn’s ratio are called as instrument transformer.
❖If this ammeter is disconnected with the secondary left unconnected, then, the
secondary voltage of the transformer is 100 times the primary voltage.
❖In many applications such as 220 V AC power circuits, this amounts to a secondary voltage
will be 220,00 V AC. This is high enough to generate dramatic sparking and arcing or, at the
least, voltage breakdown in the current transformer itself.
❖By increasing the number of secondary windings, Ns, the secondary current can be made
much smaller than the current in the primary circuit. In other words, the number of turns
and the current in the primary and secondary windings are related by an inverse
proportion.
❖A current transformer, like any other transformer, must satisfy the amp-turn equation as
below:
Example-01:
❖A bar-type current transformer which has 1 turn on its primary and 160 turns
on its secondary is to be used with a standard range of ammeters that have an
internal resistance of 0.2Ω. The ammeter is required to give a full-scale
deflection when the primary current is 800 Amps. Calculate the maximum
secondary current and secondary voltage across the ammeter.
Secondary Current:
❖It can be noticed that since the secondary of the current transformer is
connected across the ammeter, which has a very small resistance, the voltage
drop across the secondary winding is only 1.0 volts at full primary current.
Potential Transformer (PT):
• The voltage transformer (VT) or potential transformer (PT) is an instrument transformer
used for metering and protection purpose.
• Potential transformers are basically step-down transformers used to step down the
voltage of high magnitude to a lower voltage which can be measured with standard
measuring instrument.
• These transformers have large number of primary turns and smaller number of
secondary turns.
• The construction of PT/VT is same as that of power transformer except for insulation
level, cooling, sealing etc.
❖If due to any reason, the primary relay fails to operate, there is a
back-up protective scheme to clear the fault as a second line of
defense as shown in Figure.
❖The backup protection provides the backup to the main protection
whenever it fails in operation, and it is essential for the proper
working of the electrical system.
References:
Notes by Dr. J.A Laghari
Principles of Power System Book by V.K Mehta
H.W
What happens if secondary of CT is open circuited?
Why secondary of CT should not be opened?
Why secondary of PT should not be short circuited?
What is difference between Fuse and Circuit Breaker?
What is difference between Short circuit and Overload and Earth fault?
Discuss types of back-up protection? (Remote back-up, Relay back-up and
Breaker back-up)
Thank You