0% found this document useful (0 votes)
41 views

Doe Handbook: Primer On Spontaneous Heating and Pyrophoricity

Uploaded by

Sarah Trawinski
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
41 views

Doe Handbook: Primer On Spontaneous Heating and Pyrophoricity

Uploaded by

Sarah Trawinski
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 75

 

  NOT MEASUREMENT 
SENSITIVE
DOE‐HDBK‐1081‐2014 
 
Supersedes 
DOE‐HDBK‐1081‐94 
 

DOE HANDBOOK 
 

PRIMER ON SPONTANEOUS HEATING AND 
PYROPHORICITY 
 

U.S. Department of Energy  FSC‐6910 
Washington, D.C. 20585 
DISTRIBUTION STATEMENT:  Approved for public release; distribution is unlimited. 

 
 

This document is available on the Department of Energy Technical Standards Program Web 
page at: 
http://www.hss.doe.gov/nuclearsafety/ns/techstds/ 
 

Key words:  Alkali Metals , Aluminum, Arsine, Calcium, Class D Extinguishing Agents, Coal Storage, 
Combustible Metals, Diborane,  Fire, Hafnium,  Heating, Hydrazine, Hydrocarbons, Hypergolic, Hypergolic 
Reaction, Iron, Lithium, Magnesium, Metals, Microbial Heating, NaK, Organic, Oxidizer, Phosphine, 
Phosphorus, Plutonium, Potassium, Pyrophoric, Pyrophoricity, Pyrophoric Gases, Pyrophoric Reagents, 
Silane Specific Area, Sodium, Sodium‐Potassium, Specific Surface Area, Spontaneous, Spontaneous 
Combustion, Steel, Super Oxides, Thorium, Titanium, Uranium, Water Reactive Metals, Zinc, Zirconium

 
FOREWORD
 

The Primer on Spontaneous Heating and Pyrophoricity is approved for use by all DOE Components.  It 
was developed to help Department of Energy (DOE) facility contractors prevent fires caused by 
spontaneous ignition.  Spontaneously ignitable materials include those that ignite because of a slow 
buildup of heat (spontaneous heating) and those that ignite in air (pyrophoricity).  The scientific 
principles of combustion and how they affect materials known to be spontaneously combustible are 
explained.  The fire hazards of specific spontaneously heating and pyrophoric materials are discussed as 
well as techniques to prevent their ignition.  Suitable fire extinguishing agents are included for most 
materials as well as safety precautions for storage and handling. 

The DOE Primers are fundamental handbooks on safety‐related topics of interest in the DOE Complex 
and are intended as an educational aid for operations and maintenance personnel and others who may 
have an interest in this topic.  The Primers attempt to supply information in an easily understandable 
form which will help workers perform their duties in a safe and reliable manner.  Persons trained in other 
technical areas may also find the Primers useful as a guide or as a reference source for further 
investigation. 

Beneficial comments (recommendations, additions, deletions) and any pertinent data that may improve 
this document should be sent to: 

U.S. Department of Energy 
Office of Nuclear Safety (HS‐30) 
1000 Independence Avenue SW 
Washington, D.C. 20585 

   


 
ACKNOWLEDGEMENTS
 
This DOE Primer was prepared under the sponsorship of the DOE Office of Environment, Health, Safety 
and Security (AU).  The sponsor is responsible for coordinating the development and/or review of the 
FAQS by subject matter experts to ensure that the technical content of the Standard is accurate and 
adequate for Department‐wide application.  The sponsor would like to acknowledge the following 
individuals who participated in the development and/or review of this document:  

Writing Team Coordinators:  
 Jim Bisker, DOE Office of Environment, Health, Safety & Security (AU‐32) 
 Tom Christman, Independent Consultant  

Writing Team Members:  
 Tom Allison, Savannah River Nuclear Solutions 
 Harvey Goranson, Oak Ridge National Laboratory 
 Jim Landmesser Sr., DOE Office of Environmental Management (EM‐41) 
 Andrew Minister, Battelle Memorial Institute ‐ Pacific Northwest National Laboratory 
 Rob Plonski, Los Alamos National Laboratory 
 
 
 
 

ii 
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
TABLE OF CONTENTS
 

OVERVIEW.........................................................................................................................................................
   1
 
INTRODUCTION ................................................................................................................................................. 2
 
DEFINITIONS......................................................................................................................................................
   3
 
PRINCIPLES OF COMBUSTION ...........................................................................................................................  4
 
Combustion ................................................................................................................................................... 4
 
The Fire Tetrahedron .................................................................................................................................... 4
 
Oxidizing Agent..........................................................................................................................................
   4
 
Fuel............................................................................................................................................................
   5
 
Heat Source ............................................................................................................................................... 6
 
Uninhibited Chain Reaction ......................................................................................................................  6
 
Spontaneous Ignition .................................................................................................................................... 7
 
Hypergolic and Pyrophoric Reactions .......................................................................................................  7
 
Spontaneous Heating ................................................................................................................................ 7
 
SPONTANEOUS HEATING/IGNITION OF HYDROCARBONS AND ORGANICS ..................................................... 8
 
Spontaneous Heating/Ignition of Hydrocarbons ..........................................................................................  8
 
Spontaneous Oxidation and Heating of Coal ..............................................................................................  10
 
Coal Storage ................................................................................................................................................ 11
 
PYROPHORIC GASES AND LIQUIDS..................................................................................................................
   13
 
Pyrophoric Gases.........................................................................................................................................
   13
 
Arsine ...................................................................................................................................................... 13
 
Diborane..................................................................................................................................................
   13
 
Phosphine................................................................................................................................................
   14
 
Silane ....................................................................................................................................................... 14
 
Extinguishing Pyrophoric Gas Fires .........................................................................................................  14
 
Pyrophoric Gas Storage and Dispensing Areas .......................................................................................  14
 
Pyrophoric NonmetallicLiquids......................................................................................................................
   15
 
Hydrazine ................................................................................................................................................ 15
 
PYROPHORIC  NONMETALLIC  SOLIDS ............................................................................................................  16
 
Phosphorus ................................................................................................................................................. 16
 
COMBUSTIBLE AND PYROPHORIC METALS.....................................................................................................
   16
 
 
Magnesium..................................................................................................................................................  18
 

iii 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
 
Properties................................................................................................................................................  18
 
Storage and Handling ..............................................................................................................................  18
 
Process Hazards ...................................................................................................................................... 19
 
Extinguishing Magnesium Fires...............................................................................................................
   20
 
Titanium ...................................................................................................................................................... 21
 
 
Properties................................................................................................................................................  21
 
Storage and Handling ..............................................................................................................................  21
 
Process Hazards.......................................................................................................................................
   21
 
Extinguishing Titanium Fires....................................................................................................................
   22
 
Alkali Metals: Sodium, Potassium, Sodium‐Potassium (NaK), and Lithium ................................................. 22
 
 
Properties................................................................................................................................................  22
 
Storage and Handling ..............................................................................................................................  23
 
Process Hazards.......................................................................................................................................
   24
 
Extinguishing Fires in Sodium, Lithium, NaK, and Potassium................................................................... 24
 
Zirconium and Hafnium ...............................................................................................................................  25
 
 
Properties................................................................................................................................................ 25
 
Storage and Handling ..............................................................................................................................  25
 
Process Hazards.......................................................................................................................................
   26
 
Extinguishing Fires in Zirconium and Hafnium.........................................................................................
   26
 
Calcium and Zinc..........................................................................................................................................
   26
 
 
Properties................................................................................................................................................ 26
 
Storage, Processing, and Extinguishing Fires in Calcium and Zinc ........................................................... 27
 
 
Aluminum.................................................................................................................................................... 27
 
Iron and Steel .............................................................................................................................................. 27
 
 
Plutonium.................................................................................................................................................... 28
 
 
Properties................................................................................................................................................ 28
 
Storage and Handling ..............................................................................................................................  30
 
Extinguishing Plutonium Fires  .................................................................................................................  30
 
Uranium ...................................................................................................................................................... 31
 
 
Properties................................................................................................................................................ 31
 
Storage and Handling ..............................................................................................................................  32
 
Extinguishing Uranium Fires ....................................................................................................................  32
 

iv 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Combustible Metal Extinguishing Agents and Application Techniques.........................................................
   32
 
Combustible Metal Fire Extinguishing Agents .........................................................................................  33
 
Other Combustible Metal Extinguishing Agents ......................................................................................  35
 
Water ...................................................................................................................................................... 39
 
LABORATORY SCALE OPERATIONS..................................................................................................................
   41
 
INCIDENT CASE  STUDIES.................................................................................................................................
   43
 
Current Edition (2014) Case Studies ...........................................................................................................  43
 
Previous Edition (1994) Case studies ..........................................................................................................  46
 
BIBLIOGRAPHY ................................................................................................................................................ 52
 
Appendix  A ‐ Materials  Subject  to  Spontaneous  Heating.............................................................................
   54
 
Appendix B – Pyrophoric and Combustible Elements and Compounds Commonly Found Within the DOE
 
Complex .......................................................................................................................................................... 61
 


DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
OVERVIEW
 

The Department of Energy (DOE) Primer on Spontaneous Heating and Pyrophoricity was prepared as an 
information resource for DOE and contractor personnel who may have these types of materials at their site.   
An understanding of spontaneous heating and pyrophoricity hazards is necessary for DOE facility personnel 
to operate and maintain facilities and facility support systems in a safe manner. 

The Primer on Spontaneous Heating and Pyrophoricity contains an introduction and sections on the 
following topics: 

 Principles of Combustion; 

 Spontaneous Heating/Ignition of Hydrocarbons and Organics; 

 Pyrophoric Gases and Liquids; 

 Pyrophoric Nonmetallic Solids; 

 Combustible and Pyrophoric Metals; and 

 Accident Case Studies. 

The information contained in this Primer is by no means all encompassing.  However, enough information 
is presented to provide the reader with a fundamental knowledge level sufficient to recognize most 
spontaneous ignition hazards and how to prevent ignition and widespread fires.  Additional resource 
materials for this topic are listed in the bibliography section at the end of this Handbook.     

   

1
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
INTRODUCTION
 

Some materials, such as phosphorus, ignite spontaneously when exposed to air.  Other materials, such as 
coal, may take several weeks to ignite under similar conditions.  This ignition time difference is the defining 
point between pyrophoricity and spontaneous heating.  It is well known that fires caused by these 
phenomena do occur, sometimes resulting in personal injury and significant damage to facilities.   By its very 
nature, spontaneous heating and pyrophoricity are among the most insidious types of fire hazards because 
here is usually no outward evidence of the potential for fire.  Therefore, an understanding of the principles 
of spontaneous heating and pyrophoricity is necessary for instituting appropriate fire prevention measures.  
This Primer introduces DOE operations and maintenance personnel with basic information necessary to 
identify and prevent spontaneous ignition hazards.  

Upon completion of this Handbook, the reader should be able to: 

 Identify the four required elements of the Fire Tetrahedron necessary to support combustion. 

 Define the following terms: combustion, oxidation, spontaneous heating, pyrophoricity, hypergolic, 
and specific area. 

 Describe the effects that atmospheric oxygen, moisture, heat transfer, and specific area have on 
spontaneous heating and ignition. 

 Identify five metals and three gases known to be pyrophoric. 

 Identify acceptable methods for long‐term storage of spontaneously heating and pyrophoric 
materials. 

 Identify the appropriate measures for preventing fires caused by spontaneous heating and
 
pyrophoricity.
 

 Identify references for obtaining further information on oxidizers, pyrophoric materials, hypergolic 
substances, and fire extinguishing agents. 

 Identify proper emergency response, including extinguishing agents for various spontaneously 
igniting materials, and self‐extinguishing without interaction. 
 Describe the importance of good housekeeping in limiting fire damage. 

   

2
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
DEFINITIONS
 

Combustion:  A chemical process of oxidation that occurs at a rate fast enough to produce heat 
and usually light in the form of either a glow or flame. 
   
Hypergolic  Any substance that will spontaneously ignite or explode upon exposure to an 
oxidizer. 
   
Ignition Temperature:  Minimum temperature a substance should attain in order to ignite under specific 
  test conditions. 
 
   
Oxidization:  A reaction driven by the removal or transfer of electrons between atoms or 
molecules.   
   
Oxidizer:  Any solid or liquid that readily yields oxygen or other oxidizing gas; or that readily 
reacts to promote or initiate combustion of combustible materials.  Additionally 
an oxidizer, under certain circumstances, can undergo a vigorous self‐sustained 
decomposition due to contamination or heat exposure.1   
Oxidizing Agent:  Any material that readily yields oxygen or other oxidizing gas; or that reacts 
chemically to oxidize combustible materials. 
   
Pyrolysis  A process in which material is decomposed into simpler molecular compounds by 
the effects of heat alone; pyrolysis often precedes combustion. 
  A chemical property characterized by the ability of a material to undergo a 
spontaneous ignition in air. 
Pyrophoric   A material that, even in small quantities and without an external ignition source, 
can ignite at or below 54.4°C (130°F) in contact with air. 
   
Specific Area:  Amount of surface area per unit weight of a material, usually expressed in cm2/g 
(in2/lb). 
   
Specific Surface Area:  The ratio of reactive surface area to the mass of the material (typically a factor of 
3‐5 times higher than the Specific Area previously defined). 
   
Spontaneous Heating:  Process whereby a material’s temperature increases due to its exothermic 
reaction with oxidants without drawing heat from its surroundings. 
   
   

                                                            
1
 See NFPA 400‐2013, Hazardous Materials Code for more information on Oxidizer classifications, including a list of 
the most common oxidizers.  

3
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
PRINCIPLES OF COMBUSTION
 

Combustion 

NFPA defines combustion as a chemical process of oxidation that occurs at a rate fast enough to produce 
heat and usually light in the form of either a glow or flame.  

Many materials oxidize to some degree; however, the rates of oxidation differ between materials.  The 
difference between slow and rapid oxidation is that the latter occurs so rapidly that heat is generated 
faster than it is dissipated, causing the material (fuel) being oxidized to reach its ignition temperature.  
Once the ignition temperature is reached, the material will continue to burn until the fuel or oxygen is 
consumed.  A visible flame usually accompanies the heat release during combustion.  However, some 
materials, such as charcoal, smolder rather than produce a flame.  Other materials, such as uranium and 
plutonium, can burn without a visible flame.  

A familiar slowly occurring oxidation reaction is the rusting of iron.  Such a reaction releases heat so slowly 
that the temperature hardly increases more than a few degrees above ambient temperature.  These slow 
reactions do not cause fires and are not considered combustion. 

The Fire Tetrahedron 

Generally, there are four items necessary to support combustion: 

1. Oxidizing Agent; 

2. Fuel; 

3. Heat Source; and 

4. Uninhibited Chain Reaction. 

These are depicted pictorially in Figure 1, which is commonly called the Fire Tetrahedron.  This graphic 
shows that for combustion to occur, fuel, an oxidizing agent, a heat source and an uninhibited chain 
reaction all need to be present in the same place at the same time.   If any one of the legs of the 
tetrahedron is removed, the fire will be extinguished. 

Oxidizing Agent 

An oxidizing agent (or oxidizer) is a material that readily yields oxygen or other oxidizing gas ‐ or that reacts 
chemically to oxidize combustible materials.  By far the most common oxidizing agent is the oxygen in the 
earth’s atmosphere; however, there are many chemical compounds that also act as oxidizing agents.  Some 
of these agents react with fuels more readily and violently than oxygen.  Further information on the relative 
hazards and classifications of oxidizing agents may be found in Appendix G in NFPA 400, Hazardous Materials 
Code. 

4
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 

Heat Source

Uninhibited 
Chain 
Reaction

Oxidizing 
Fuel 
Agent

Heat Source

Uninhibited 
Chain 
Reaction

Oxidizing 
Fuel 
Agent

Figure 1.  Fire Tetrahedron 

Fuel 

A fuel is the substance that reacts with the oxidizing agent during combustion.  Fuels can be solids, liquids, 
gases, and even metals.  Familiar fuels are coal, firewood, and gasoline.  For the purpose of this document, 
the discussion of fuels will be limited to those that are known to combust spontaneously or that involve 
metals. 

5
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Heat Source 

Normally, a heat source such as a flame or spark is required to ignite a mixture of a fuel and oxidizing agent 
(heat needs to be added or the fuel and oxidizing agent will not react).  But sometimes the heat source may 
not always be external.  The reactions that are the subject of this document are special instances where no 
external heat source is required to ignite the fuel.  These fuels react so readily with an oxidizer that an 
external heat source is not required for ignition due to the highly exothermic nature of the reaction.  
Ignition for these fuels therefore occurs spontaneously. 

Uninhibited Chain Reaction 

Once the fire is started, this exothermic reaction feeds heat back to the fuel to produce the gaseous fuel 
used in the flame.  In other words, the chain reaction can provide the heat necessary to maintain the fire. 

   

6
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Spontaneous Ignition 

Spontaneous ignition is the ignition of a fuel caused by the accumulation of heat from either a hypergolic 
reaction or pyrophoric reaction. 

Hypergolic and Pyrophoric Reactions 

A hypergolic reaction describes a material's ability to immediately ignite or explode upon contact with an 
oxidizing agent (e.g., rocket fuel mixture – simply combining hydrazine (fuel) with nitrogen tetroxide 
(oxidizing agent) will cause spontaneous ignition with or without the presence of oxygen).  Pyrophoricity is 
a special case of a hypergolic reaction where a substance spontaneously ignites upon exposure to air 
(atmospheric oxygen).  A pyrophoric material may be a solid, liquid, or gas.  Pyrophoric materials are not 
compatible with air, moisture, oxygen/oxidizer, and protic solvents including water, acids, alcohols, 
amines, mercaptans, etc.  Although there are some pyrophoric liquids and gases, most pyrophoric 
materials prudent to safety practices are metals that will react rapidly under the condition of having a large 
specific surface area.  In practice, increasing the material mass and/or decreasing its surface area will 
decrease the material specific surface area that will suppress its pyrophoric characteristics. 

The remainder of this document will be concerned only with spontaneous heating and pyrophoricity.  

Spontaneous Heating 

Spontaneous heating is a phenomenon caused by an unstable (usually oxidizable) material and its 
decomposition compounds with exothermic reactions releasing heat.  The retention of the generated heat 
in the material by virtue of its poor thermal heat loss (i.e., conduction, convection or radiation) will cause 
the temperature of the material to rise.  Under some circumstances, this process can lead to flaming 
combustion and overt fire, in which case it is properly called spontaneous ignition, and is regarded as a 
special case of spontaneous combustion.   

Spontaneous heating can be the result of direct oxidation of hydrocarbons (for example, oils, coal, and 
solvents) or it may occur because of the action of microorganisms in organic materials (not included within 
the scope of this text).  A more detailed discussion on spontaneous heating is included in the next section.

7
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
SPONTANEOUS HEATING/IGNITION OF HYDROCARBONS AND ORGANICS
 

Spontaneous Heating/Ignition of Hydrocarbons 

Some hydrocarbons are capable of spontaneous heating and ignition under proper conditions.  This 
phenomenon usually involves a liquid hydrocarbon in contact with combustible materials.  Likewise some 
solid hydrocarbons, such as coal, can react directly with atmospheric oxygen to create a condition for 
combustion.  Whether spontaneous heating leads to ignition or not depends on several factors including: 

 The critical stacking temperature which is influenced by rate at which heat is generated and 
removed from the stacking material. 

 The critical ambient temperature of the combustible material (e.g., fibrous, particle, dust, shaving, 
chips, even large pieces), hydrocarbon, or any thermally generated gaseous products. 

 The specific area of the hydrocarbons exposed to the oxidizer. 

 The mass of the material being oxidized. 

For spontaneous ignition to occur, the rate of heat being generated by the chemical reaction needs to 
exceed the rate of heat removal by conduction, convection, and radiation (thermal).  As the temperature 
of the material begins to rise, the rate of heat generation will often increase.  The result is a "runaway" 
reaction, which ultimately causes ignition.  If the rate of heat removal equals the rate of generation 
however, the material will not increase in temperature and ignition will not occur. 

When a volume of material is undergoing a chemical reaction, the material located near the surface of the 
pile may be able to release adequate heat away from the material to prevent combustion.  However, the 
sub‐surface materials are somewhat insulated and can’t release heat at an adequate rate so the inner core 
of the material heats to the auto‐ignition temperature of the material being oxidized which results in 
combustion.   

The rate of heat removal may be increased through physical contact with a thermally conductive surface, by 
rotating piles of combustibles to cool hot spots, spreading out the material to create a thin layer, and by 
circulating inert gases through the piles to cool hot spots and displace the oxidizing agent. 

These principles are illustrated in Figure 2.  Although coal is used as the example, the principles depicted 
apply to all materials which are known to heat spontaneously (including pyrophoric liquids, gasses 
(unoxidized) metals and other solids). 

The ignition temperature of the material is obviously of concern and varies widely among materials.  Much 
more stringent controls should be placed on materials which have lower ignition temperatures and those 
which liberate explosive gases.  Although most materials with high ignition temperatures are of lesser 
concern, some are more explosive than those with lower ignition temperatures.  Safety Data Sheets (SDSs) 
are a source for information such as ignition temperature, vapor pressure, toxicity, and reactivity. 

The specific area of a combustible substance is a ratio of the surface area of the material exposed to an 
oxidizing atmosphere to the mass.  Materials that have a high specific area are more prone to heat 
generation and spontaneous ignition.  Flammable or combustible liquids on fibrous materials pose an 
8
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
increased spontaneous ignition fire hazard (i.e. oils soaked into rags or paintbrushes, absorbent pads in an 
oil catch pan).  The fibers of the material allow the liquid to spread out over a larger surface area, allowing 
more contact with oxygen.  Therefore, the thinly layered combustible liquids spread over fibrous materials 
are easily oxidized.  The process of oxidation generates heat and an exothermic reaction can occur.   

As the ambient temperature rises, the rate of spontaneous heat generation will also rise.   High ambient 
temperatures also reduce the rate of heat removal, bringing the hydrocarbon closer to its ignition 
temperature. 

With these facts in mind, the following housekeeping steps will help minimize the threat of spontaneous 
heating and ignition of hydrocarbon or organic compounds: 

 Keep potentially spontaneously heating materials in a cool environment.  The heat transfer resulting 
from a cooler atmosphere or circulating air will lower the temperature of the materials. 

 Know all of the chemicals in your inventory and their potential self‐heating hazards along with their 
ignition temperatures.  Consult the chemical manufacturer's SDSs and subject matter experts 
where available. 

 Reduce the amount of fibrous materials (e.g., rags) used with combustible liquid hydrocarbons. 

 Enact passivation techniques such as spreading the material out in a thin layer over a large surface 
area or slowly allowing the material to oxidize in a controlled environment.  This increases the 
dissipation of heat caused by oxidation.  If the materials cannot be spread out, consider storing the 
materials in an approved waste receptacle designed to contain any potential fire. 

 Keep appropriate fire extinguishing equipment near potential areas of ignition.  Type A 
extinguishing agents are appropriate for most nonhazardous, combustible materials (rags, wood, 
textiles), whereas a Type B agent is necessary in the presence of quantities of combustible liquids.   
Class D extinguishing agents for metal fires are discussed in a later section and require specific 
agents for particular materials. 

 Fire hazard planning is important for both fire prevention and fire protection activities.  It may be 
more appropriate to control or allow a fire to self‐extinguish rather than trying to attempt 
extinguishment manually or automatically.  For example, attempting to extinguish a fire within a 
processing area may have the potential to contaminate the processing line while allowing the small 
quantity of material to continue to burn would result in minor damage if other materials are not 
involved. 

 Keep combustible materials away from known materials with spontaneous heating hazards.  Many 
fires have been started as the result of a self‐heating material being exposed to a combustible with 
a low ignition temperature.  This practice is also important from a fire loss minimization aspect.  

 Place combustible metals on substantial metal surfaces that can act as a heat sink. 
Spontaneous ignition may occur in piles of moist organic material where heat is generated in the early 
stages by the respiration of bacteria, molds, and microorganisms.  High moisture content is required for 
vigorous activity, and heating is generally controlled by maintaining the moisture content below a 

9
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
predetermined level.  This type of heating can only raise the material to the temperature range of 50 to 
75°C (122 to 167°F), where the living organisms die.  Beyond this point, other oxidation reactions must 
take over if ignition is to occur.  The existence of biological heating requires careful control of moisture, air 
supply, and nearby combustible or flammable materials.  Heat generated by biological action may also act 
as a catalyst for other reactions that occur only at elevated temperatures.  In addition, if a "hot spot" in a 
pile of organic material is exposed to a highly flammable liquid or gas, a fire or explosion may occur. 

The likelihood of biological heating may be reduced by the following measures: 

 Provide adequate ventilation of the organic material to remove moisture, heat, and dust particles. 

 Limit the storage time of the organic material using a "first in, first out" rule of thumb. 

 Circulate large quantities of organic materials to disperse areas bof localized heating. 

Appendix A lists many organic materials known to heat spontaneously and measures to prevent their 
ignition. 

Spontaneous Oxidation and Heating of Coal 

Coal presents hazards between the time it is mined and its eventual consumption in boilers and furnaces.   
Below are listed some of the characteristics of spontaneous fires in coal.  These characteristics can be used 
to evaluate the potential for coal fires and as guidelines for minimizing the probability of a fire: 
1. The higher the inherent (equilibrium) moisture, the higher the heating tendency. 
2. The lower the ash free Btu, the higher the heating tendency. 
3. The higher the oxygen content in the coal, the higher the heating tendency. 
4. Sulfur is a factor in the spontaneous heating of coal, but the exact extent is unknown.    There are 
many very low‐sulfur western subbituminous and lignite coals that have very high oxidizing 
characteristics and there are high sulfur coals that exhibit relatively low oxidizing characteristics. 
5. The oxidation of coal is a solid/gas reaction, which happens initially when air (a gas) passes over a 
coal surface (a solid).  Oxygen from the air combines with the coal, raising the temperature of the 
coal.  As the reaction proceeds, the moisture in the coal is liberated as a vapor and then some of 
the volatile matter that normally has a distinct odor is released.  The amount of surface area of the 
coal that is exposed is a direct factor in its heating tendency.  The finer the size of the coal, the 
more surface is exposed per unit volume and the greater the oxidization rate (See Figure 2).  
6. Many times, segregation of the coal particle sizes is the major cause of heating.  The coarse sizes 
allow the air to enter the pile at one location and react with the high surface area fines at another 
location.  Coals with a large top size [e.g., 100 mm (>4 in.)], will segregate more in handling than 
those of smaller size [50 mm (>2 in.)]. 
7. It is generally believed that the rate of reaction doubles for every 8 to 11°C (15 to 20°F) increase in 
temperature. 

10
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
8. Freshly mined coal has the greatest oxidizing characteristic, but a hot spot in a pile may not appear 
for one or two months.  As the initial oxidization takes place, the temperature gradually increases 
and the rate of oxidization accelerates. 
9. There is a critical amount of airflow through a portion of a coal pile that maximizes the oxidation or 
heating tendencies of coal.  If there is no airflow through a pile, then there is a limited supply of 
oxygen to keep up with oxidation that can lead to ignition.  If there is a plentiful supply of air, any 
heat generated from oxidation will be carried off and the pile temperature will reach equilibrium 
with the air temperature; this is considered a ventilated pile.  When there is just sufficient airflow 
for the coal to absorb most of the oxygen from the air and an insufficient airflow to dissipate the 
heat generated, the reaction rate increases and the temperatures may eventually exceed 
acceptable limits. 

Coal Storage 

Coal should be stored in properly designed bunkers, silos, bins, or in outside piles.  The most important 
aspects of coal storage are minimizing the flow of air through the pile, using the "first‐in, first out" rule of 
thumb, and minimizing the amount of finely divided coal in the pile.  “Hot spots" should be removed or 
exposed to the atmosphere to allow cooling.  Coal should be compacted to minimize the amount of air in 
the pile.   

Caution should be used when determining if water will be applied to a hot spot.  The size and location of 
the hot spot are significant variables that need to be considered.  The application of water to large, sub‐
surface hot spots may result in a steam explosion. 

Outside coal piles should not be located over pressurized utility lines (water, gas, etc.). 

Coal that is stored in bunkers has a limited amount of time prior to the formation of hot spots.  Depending 
on the design and capacity of a specific bunker, coal should be rotated through the bunker on a periodic 
basis.  When maintenance activities occur that prevent the rotation of the coal through the bunker, 
consideration should be given to completely emptying the bunker prior to performing the maintenance 
activity.   

 
11
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
 

 
 
 
 
   
  Dry Coal 
 
  Air
  Smaller  
  (fines) are to
   
 
 
 
 
 
  Figure 2a. Dormant pile of dry containing Figure 2b. Addition of moisture and
  small oxygen causes spontaneous heating 
 
 
 
 
  Inadequate heat transfer from the
  causes the temperature of the coal
 
  increase until. . .  
 
 
  Convection
 
 
 
 
 
  Conduction
  
  Figure 2c. Conduction, convection, and Figure 2d. Coal reaches its ignition temperature
  radiation heat transfer mechanisms.  resulting in a fire. 
 
  
Figure 2.  The evolution of a coal fire caused by spontaneous heating. 

   

12
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
PYROPHORIC GASES AND LIQUIDS
 

Pyrophoric Gases 

There are several pyrophoric gases that should be included in any discussion of pyrophoricity.  Many of 
these are used in manufacturing of microelectronics.  All of the gases presented here have three things in 
common:  1) they may ignite immediately upon exposure to air at certain temperatures; 2) they are all 
nonmetallic hydrides; and 3) many other compounds that contain these gases in their molecular structure 
are also pyrophoric. 

Arsine 

Arsine (AsH3 ), also known as arsenic hydride, is a colorless, flammable, pyrophoric, and highly toxic gas that 
is one of the simplest compounds of arsenic with a distinctive garlic‐like odor.  It is heavier than air and is a 
blood and nerve poison.  Arsine will generally not ignite in air unless it is at an elevated temperature, but it 
can explode with a suitably powerful initiator (heat source, shock wave, electrostatic discharge).  Arsine 
may also exist in other compounds.  The ignition temperatures of many of these arsine containing 
compounds are lower than that of arsine, causing them to ignite in air even at low temperatures (below 
0°C, 32°F).  All arsine compounds should be considered pyrophoric until they are properly characterized 
and determined not to be pyrophoric. Do not use water to extinguish fires involving arsenic compounds 
(e.g. arsenic trichloride); dry chemical or carbon dioxide extinguishers should be used; the use of water 
should be avoided because of the possibility of highly toxic run‐off from the site.  Fire service personnel 
should be advised that self‐contained breathing apparatus and totally encapsulated protective clothing are 
necessary. 

Diborane 

Diborane (B2H6 ) is a highly toxic, colorless gas with a repulsive but sweet odor; it is highly reactive and 
flammable.  It forms flammable mixtures with air over a wide range (flammable limits, 0.9% and 98%).  The 
ignition temperature of diborane is between 38°C and 52°C (100°F and 125°F).  Diborane will ignite 
spontaneously in moist air at room temperature.  It reacts spontaneously with chlorine and forms hydrides 
with aluminum and lithium, which may ignite spontaneously in air.  It reacts with many oxidized surfaces as 
a strong reducing agent, and reacts violently with vaporizing liquid‐type extinguishing agents. 

Storage should be in a detached, refrigerated (less than 20°C, 68°F), and well‐ ventilated place.  Boranes 
should be separated from halogens and other oxidizing agents and checked periodically for decomposition.  
Protect against electrical spark, open flames, or any other heat source.  A dry nitrogen purge should be 
used in any transfer.  Waste material should be completely hydrolyzed with water before disposal.  
Combustible solutions should be burned as a means of disposal.  There are no special shipping requirements 
for diborane other than steel pressure cylinders. 

Firefighting should be done from an explosion‐resistant location.  Use water from unmanned monitors or 
hose holders to keep fire‐exposed containers cool.  If it is necessary to stop the flow of gas, use water spray 
to protect personnel effecting shut‐off.  Halon should not be used as an extinguishing agent on diborane 
fires. 

13
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Phosphine 

Phosphine (PH3) is a colorless, flammable and highly toxic, gas with a fishy or garlic‐like odor.  This chemical
 
is very dangerous, with an ignition temperature of 100°C (212°F), often igniting spontaneously.
   
Phosphine gas readily combines with nitrates, halogens, and metals to form very explosive and volatile
 
compounds.  Specifically, phosphine reacts violently with air, boron trichloride, (BCl3), bromine (Br2),
 
chlorine (Cl2),hypochlorite (ClO), Mercury(II) nitrate (Hg(NO3)2), nitric oxide  (NO), nitrous oxide (N2O),
 
nitrogen trichloride (NCl3), nitrate (NO3), Nitrous acid (HNO2), oxygen gas (O2),  potassium in anhydrous
 
ammonia (K+NH3), and silver nitrate (AgNO3).
 

At elevated temperatures, phosphine decomposes, emitting highly toxic fumes of POx, which react
 
vigorously with oxidizing materials.  It possesses the characteristic putrefying odor of a mixture of garlic
 
and decaying fish.  Prolonged exposure to very low concentrations will cause chronic poisoning,
 
characterized by anemia, bronchitis, gastro‐intestinal disturbances, and visual, speech, and motor
 
difficulties.
 

Silane 

Silane (SiH4), also known as silicon tetrahydride, is a colorless gas with a putrid odor.  It and its compounds 
(e.g., disilane Si2H8) can ignite in air and react violently with chlorine (Cl2).  The presence of other hydrides as 
impurities causes ignition always to occur in air.  However, 99.95% pure silane ignites in air unless emerging 
at very high gas velocities, whereas mixtures of up to 10% silane may not ignite.  Hydrogen liberated from 
its reaction with air (atmospheric oxygen) often ignites explosively.  Silanes react violently with chlorine and 
bromine.  All silanes should be considered pyrophoric until they are properly characterized.  Halon should 
not be used as an extinguishing agent on silane fires.  For additional information on the safe handling of 
silane see:  AIGA 052/08, Storage and Handling of Silane and Silane Mixtures. 

Extinguishing Pyrophoric Gas Fires 

Pyrophoric gases may spontaneously explode at high gas release rates.  For fires involving flammable gases, 
the best procedure is to stop the flow of the gas before attempting extinguishment of the fire.  To 
extinguish the fire while allowing continued flow of the gas is extremely dangerous; an explosive cloud of 
gas/air mixture may be created that, if ignited, may cause far more damage than the original fire.  
Extinguishing the flame using carbon dioxide or dry chemical may be desirable to allow immediate access to 
valves to shut off the flow of gas, but this needs to be done carefully.  In many cases, it will be preferable to 
allow continued burning, while protecting exposures with water spray, until the flow of gas can be stopped.  
Since many pyrophoric gases react violently with halogens, Halons should not be used as extinguishing 
agents. 

Pyrophoric Gas Storage and Dispensing Areas 

Pyrophoric gas cylinders in storage or dispensing areas should be provided with safeguards as described in 
NFPA 318,Standard
   for the Protection of Semiconductor Fabrication Facilities; NFPA 55, Compressed Gases 
and Cryogenic Fluids Code; and, the International Building Code.  Additionally, NFPA 70, National Electrical 
Code, should be consulted for hazard classification and protection techniques of electrical equipment near 

14
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
flammable gas storage areas.  It should also be noted that pyrophoric gases are not allowed to be used or 
stored in an unsprinklered building. 

Pyrophoric Nonmetallic Liquids 

Hydrazine 

Properties 
Hydrazine is a colorless oily liquid resembling water in appearance and possesses a weak, ammonia‐like 
odor.  Its chemical formula is N2H4.  Commercially it is available as an anhydrous (without water) liquid and 
in aqueous solutions.  Hydrazine is most well‐known for its use as a rocket fuel, but is also used in 
manufacturing agricultural chemicals, explosives, and plastics.   It fumes in air and reacts with all oxidizing 
agents.  Hydrazine is hypergolic, meaning that it reacts explosively upon contact with many oxidizing 
agents.  The flash point of hydrazine is 38° C (100°F).  Its ignition temperature is 270°C (518°F) on a glass 
surface but may be as low as 23°C (74°F) when in contact with a strong oxidizing agent.  Hydrazine forms 
flammable mixtures with air from 4% to 100% by volume and decomposes when heated.  Hydrazine ignites 
in air at room temperature when exposed to metal oxide surfaces and in a wide variety of porous 
materials. 

Storage and Handling 
Storage in a detached building is preferred.   Inside storage should be in a standard flammable liquids 
storage warehouse, room, or cabinet.  An emergency water supply and automatic sprinklers are also 
necessary for fire extinguishment.  Hydrazine should be stored separately from metal oxides, acids, and all 
oxidizing agents.  Hydrazine is highly toxic and may be fatal if inhaled or absorbed through the skin.  It is also 
corrosive and may cause severe eye and skin burns.  Protective clothing that prevents penetration of 
hydrazine and positive pressure self‐contained breathing apparatus are advisable when working with 
hydrazine. 

Extinguishing Hydrazine Fires 
Fires involving hydrazine may produce irritants and toxic gases such as nitrogen oxides.  Fires should not be 
approached without protective clothing and positive pressure respirators.  Hydrazine fires should be 
approached from upwind to avoid hazardous vapors and toxic decomposition products.  Flooding amounts 
of water should be applied as a fog or spray.  Water should be sprayed on fire‐exposed containers of 
hydrazine to keep them cool.  Fires should be fought from a protected location or at a maximum possible 
distance.  Flooding amounts of water may be necessary to prevent reignition. 

   

15
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
PYROPHORIC  NONMETALLIC  SOLIDS
 

Phosphorus 

There are three different allotropes of phosphorus (P4 ).  These are commonly known as white, yellow, and 
red phosphorous.  Red phosphorus is not considered pyrophoric.  However, red phosphorus ignites easily 
and produces phosphine (a pyrophoric gas) during combustion. 

Pyrophoric white phosphorus is a colorless to yellow, translucent, nonmetallic solid.  It ignites 
spontaneously on contact with air at or above 30°C (86°F).  Phosphorous is explosive when mixed with 
oxidizing agents.  Fumes from burning phosphorus are highly irritating but only slightly toxic except in very 
high concentrations.  Like red phosphorus, white phosphorus also produces phosphine during combustion. 

When storing, protect containers against physical damage.  Phosphorus should always be kept underwater, 
or under an inert atmosphere, separated from oxidizing agents and combustible materials.  When shipping, 
keep phosphorus under water in hermetically sealed cans inside wooden boxes, under water in drums, or in 
tank motor vehicles or tank cars under water or blanketed with an inert gas.  Refer to NFPA 484, 
Combustible Metals, 2015, for additional information on sprinkler protection guidance. 

Phosphorous fires should be deluged with water until the fire is extinguished and the phosphorus has 
solidified.  The solidified phosphorus should then be covered with wet sand, clay, or ground limestone. 

COMBUSTIBLE AND PYROPHORIC METALS 

This section covers the pyrophoricity of combustible metals.  Properties of various combustible metals are 
discussed as well as the conditions in which they become pyrophoric.  For additional information on the fire 
hazards of combustible and pyrophoric metals, see Chapter 14 of the Ignition Handbook. 

Nearly all metals will burn in air under certain conditions.  Some are oxidized rapidly in the presence of air or 
moisture, generating sufficient heat to reach their ignition temperatures.  Others oxidize so slowly that 
heat generated during oxidation is dissipated before the metal becomes hot enough to ignite.  Certain 
metals, notably magnesium, titanium, sodium, potassium, lithium, zirconium, hafnium, calcium, zinc, 
plutonium, uranium, and thorium, are referred to as combustible metals because of the ease of ignition 
when they reach a high specific surface area (thin sections, fine particles, or molten states).  However, the 
same metals in heavier pieces, such as ingots and thick wall castings (not thin sections or fine particles or 
molten states) are comparatively difficult to ignite. 

Some metals, such as iron and steel, which are not normally thought of as combustible, may ignite and burn 
when in finely divided form (powders and dusts).  Generally, iron and steel are not considered pyrophoric but 
may be in certain particle ranges and under very specific conditions.  For example, clean, fine steel wool may 
be ignited.  Particle size, shape, quantity, and alloy are important factors to be considered when evaluating 
metal combustibility.  Combustibility of metallic alloys may differ and vary widely from the combustibility 
characteristics of the alloys' constituent elements.  Metals tend to be most reactive when in finely divided 
form, and some may require shipment and storage using an inert gas or liquid to reduce fire risks.  
Combustible dusts dispersed in air can present a dust explosion hazard and appropriate controls need to be 
implemented to prevent aerosolizing or dispersing combustible dust; for additional information, please see 
16
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
NFPA 654, 2013, Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing, 
and Handling of Combustible Particulate Solids. 

Hot or burning metals may react violently upon contact with other materials, such as oxidizing agents and 
extinguishing agents used on fires involving ordinary combustibles or flammable liquids.  Temperatures 
produced by burning metals can be higher than temperatures generated by burning flammable liquids.   
Some metals can continue to burn in carbon dioxide, nitrogen, water, or steam atmospheres in which 
ordinary combustibles or flammable liquids would be incapable of burning. 

Properties of burning metal fires cover a wide range.  Burning titanium produces little smoke, while burning 
lithium produces a smoke that is dense and profuse.  Some water‐moistened metal powders, such as 
zirconium, burn with near explosive violence, while the same powder wet with oil burns quiescently.   
Sodium melts and flows while burning; calcium does not.  Some metals (e.g., uranium) acquire an increased 
tendency to burn after prolonged exposure to moist air, while prolonged exposure to dry air makes it more 
difficult to ignite. 

Water should never be applied to burning metals since the water can break down into its molecular 
structure (hydrogen and oxygen) which could result in a significantly increased fire and possibly a violent 
reaction.  If a combustible metal is also in the presence of a flammable or combustible liquid, both the Class 
B and Class D fires must be considered, typically by extinguishing the metal fire first and then the liquid fire 
to avoid re‐ignition. 

The toxicity of certain metals is also an important factor in fire suppression.  Some metals (especially heavy 
metals) can be toxic or fatal if they enter the bloodstream or their smoke fumes are inhaled.  Metal fires 
should never be approached without proper protective equipment (clothing and respirators). 

A few metals, such as thorium, uranium, and plutonium, emit ionizing radiation that can complicate 
firefighting and introduce a radioactive contamination problem.  Where possible, radioactive materials 
should not be processed or stored with other pyrophoric materials because of the likelihood of widespread 
radioactive contamination during a fire.  Where such combinations are essential to operations, appropriate 
engineering controls and emergency procedures should be in place to prevent fires or quickly suppress 
fires in the event the controls fail. 

Because extinguishing fires in combustible metals involves techniques not commonly encountered in 
conventional firefighting operations, it is necessary for those responsible for controlling combustible metal 
fires to be thoroughly trained prior to an actual fire emergency.  Refer to Combustible Metal Extinguishing 
Agents and Application Techniques on page 32 for information on extinguishing agents; refer to NFPA 484, 
Combustible Metals, 2015, for sprinkler protection guidance. 

The following material discusses the properties of various combustible metals, conditions in which they 
become pyrophoric, storage and handling practices, processing hazards, and methods of extinguishing fires 
involving these kinds of metals.  For more detailed information regarding fire reactive metals, please see 
NFPA 484 as well as Factory Mutual Datasheet 7‐85 (April 2013) Metals and Alloys. 

17
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Magnesium 

Properties 

The ignition temperature of pieces of magnesium is very close to its melting point of 650°C (1,200°F) (See 
Appendix B).   However, ignition of magnesium in certain forms may occur at temperatures well below 
650°C (1,200°F).   For example, magnesium ribbons and shavings can be ignited under certain conditions at 
about 510°C (950°F), and finely divided magnesium powder can ignite below 482°C (900°F). 

Metal marketed under different trade names and commonly referred to as magnesium may be one of a 
large number of different alloys containing magnesium, but also significant percentages of aluminum, 
manganese, and zinc.    Some of these alloys have ignition temperatures considerably lower than pure 
magnesium, and certain magnesium alloys will ignite at temperatures as low as 427°C (800°F).    Flame 
temperatures of magnesium and magnesium alloys can reach 1,371°C (2,500°F), although flame height 
above the burning metal is usually less than 305 mm (12 in). 

As is the case with all combustible metals, the ease of ignition of magnesium depends upon its size and 
shape.    As noted earlier, the specific area of a combustible substance is the surface area of the substance 
exposed to an oxidizing atmosphere per gram of the substance and is usually expressed in cm2/g.   A 
combustible substance that has a high specific area is more prone to oxidize, heat, and ignite 
spontaneously.    A match flame may ignite thin, small pieces, such as ribbons, chips, and shavings, 
whereas castings and other large pieces are difficult to ignite even with a torch because of the high thermal 
conductivity of the metal.    In order to ignite a large piece of magnesium, it is usually necessary to raise the 
entire piece to the ignition temperature.  

Scrap magnesium chips or other fines (finely divided particles) may burn as the result of ignition of waste 
rags or other contaminants.  Chips wet with water, water‐soluble oils, and oils containing more than 0.2% 
fatty acid may generate hydrogen gas.  Chips wet with animal or vegetable oils may burn if the oils ignite 
spontaneously.  Fines from grinding operations generate hydrogen when submerged in water, but they 
cannot be ignited in this condition.    Containers used with fines should be provided with ventilation holes 
to allow for the dissipation of hydrogen gas.  Grinding fines that are slightly wetted with water may 
generate sufficient heat to ignite spontaneously in air, burning violently as oxygen is extracted from the 
water with the release of hydrogen. 

Storage and Handling 

The larger a piece of magnesium, the more difficult it is to ignite, but once ignited, magnesium burns 
intensely and is difficult to extinguish.   The storage recommendations in NFPA 484 take these properties 
into consideration.    Recommended maximum quantities of various sizes and forms to be stored in specific 
locations are covered in this standard.    Storage buildings should be noncombustible, and the magnesium 
should be segregated from combustible material as a fire prevention measure. 

With easily ignited lightweight castings, segregation from combustible materials is especially important.    In 
the case of dry fines (fine magnesium scrap), storage in noncombustible covered containers in separate fire 
resistive storage buildings or rooms with explosion venting facilities is preferable.  The use of sprinklers in 

18
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
magnesium scrap storage buildings or area is prohibited.  However, in some facilities magnesium is 
contained inside a robust steel container (e.g., Mag‐Beds) with the container providing sufficient 
separation/confinement of the material that sprinklers will not be an issue.    For combustible buildings or 
buildings containing combustible contents, or where combustibles are located within 9.14 m (30 ft) of the 
magnesium, NFPA 484 recommends automatic sprinkler protection to assure prompt control of a fire 
before the magnesium becomes involved. 

Because of the possibility of hydrogen generation and of spontaneous heating of fines wet with coolants 
(other than neutral mineral oil), it is preferable to store wet scrap fines outdoors.    Covered 
noncombustible containers should be vented to allow for the dissipation of hydrogen gas. 

Process Hazards 

In machining operations involving magnesium alloys, sufficient frictional heat to ignite the chips or shavings 
may be created if the tools are dull or deformed.    If cutting fluids are used (machining of magnesium is 
normally performed dry), they should be of the mineral‐oil type that have a high flash point.    Water or 
water‐oil emulsions are hazardous, since wet magnesium shavings and dust liberate hydrogen gas and burn 
more violently than dry material when ignited.    Machines and the work area should be frequently cleaned 
and the waste magnesium kept in covered, clean, dry steel or other noncombustible drums which should be 
removed from the buildings at regular intervals.  Magnesium dust clouds are explosive if an ignition source 
is present.   Grinding equipment should be equipped with a water‐spray‐type dust precipitator.  NFPA 484 
requires these types of precipitators to be vented to prevent hydrogen buildup resulting from magnesium 
reacting with the water spray.  NFPA 484 also places restrictions on the mass flow rate of magnesium into 
the precipitator as well as the amount of magnesium sludge accumulated in the precipitator.    The 
equipment should be restricted to magnesium processing only. 

Molten magnesium in the foundry presents a serious fire problem if not properly handled.  Sulfur dioxide or 
melting fluxes are commonly used to prevent oxidation or ignition of magnesium during foundry operations.   
The action of sulfur dioxide is to exclude air from the surface of the molten magnesium; it is not an 
extinguishing agent.  Fluxes perform both functions. 

Pots, crucibles, and ladles that may contact molten magnesium need to be kept dry to prevent steam 
formation or a violent metal‐water reaction.    Containers should be checked regularly for any possibility of 
leakage or weak points.    Steel lined runoff pits or pits with tightly fitting steel pans should be provided, 
and the pans kept free of iron scale.    Leaking metal contacting hot iron scale results in a violent thermite 
reaction.  Use of stainless steel pans or linings will eliminate this possibility. 

Heat treating ovens or furnaces, where magnesium alloy parts are subjected to high temperatures to 
modify their properties, present another special problem.  Temperatures for heat‐treating needed to 
secure the desired physical properties are often close to the ignition temperatures of the alloys 
themselves, and careful control of temperatures in all parts of the oven is essential.    Hot spots leading to 
local overheating are a common cause of these fires.    Large castings do not ignite readily, but fins or 
projections on the castings, as well as chips or dust, are more readily subject to ignition.    For this reason, 
castings should be thoroughly cleaned before heat‐treating.    Magnesium castings in contact with 

19
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
aluminum in a heat‐treating oven will ignite at a lower temperature than when they are placed on a steel 
car or tray. 

Magnesium should not be heat treated in nitrate salt baths.    Certain commonly used molten mixtures of 
nitrates and nitrites can react explosively with magnesium alloys, particularly at temperatures over 538°C 
(1,000°F). 

Extinguishing Magnesium Fires 

Magnesium and its alloys present special problems in fire protection.  Extinguishment of a magnesium fire 
should NOT be attempted with the following agents:  water, any water‐based agent (foams), carbon 
dioxide, halon containing agents, or nitrogen. 

Considering the importance of prompt attack on magnesium fires, automatic sprinklers may be desirable 
because they provide automatic notification and control of fire.    While the water from the sprinklers may 
have the immediate effect of intensifying magnesium combustion, it will serve to protect the structure and 
prevent ignition of surrounding combustible material.    An excess of water applied to fires in solid 
magnesium (avoiding puddles of molten metal) cools the metal below the ignition temperature after some 
initial intensification, and the fire goes out rapidly.    By contrast, the fire may be intensified but not 
controlled with only a small, finely divided water spray. 

The method of extinguishing magnesium fires depends largely upon the form of the material.    Burning 
chips, shavings, and small parts need to be smothered and cooled with a suitable dry‐chemical 
extinguishing agent (e.g., graphite and dry sodium chloride).  Where magnesium dust is present, care 
should be taken to prevent a dust cloud from forming in the air during application of the agent because this 
may result in a dust explosion. 

Small fires may be controlled by flooding with helium or argon if the fire is located in an area where flooding 
would be effective.  Inert gases, other than the noble gases (argon, helium, etc.) are ineffective on 
magnesium fires and some can create dangerous byproducts (magnesium nitride). 

Fires in pieces of magnesium can be fought without difficulty if attacked in their early stages.  It may be 
possible to remove surrounding material, leaving the small quantity of magnesium to burn itself out 
harmlessly. 

Magnesium fires in heat‐treating ovens can best be controlled with powders and gases developed for use 
on such fires.    By using melting fluxes to exclude air from the burning metal, fires in heat treating furnaces 
have been successfully extinguished.  Boron trifluoride gas is an effective extinguishing agent for small fires 
in heat‐treating furnaces.  Cylinders of boron trifluoride can be permanently connected to the oven or 
mounted on a suitable cart for use as portable equipment.  Boron trifluoride is allowed to flow into the 
oven until the fire is extinguished, or, where large quantities of magnesium are well involved before 
discovery or where the furnace is not tight, the boron trifluoride will control the fire until flux can be 
applied to extinguish the fire. 

20
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Titanium 

Properties 

Titanium, like magnesium, is classified as a combustible metal, but again the size and shape of the metal 
determines largely whether it will ignite.    Castings and other pieces of titanium are not combustible under 
ordinary conditions.  Small chips, fine turnings, and dust ignite readily and, once ignited, burn with the 
release of large quantities of heat.    Tests have shown that very thin chips and fine turnings could be ignited 
by a match and heavier chips and turnings by a Bunsen burner.    Coarse chips and turnings 0.79 by 2.7 mm 
(1/32 by 3/28 in.) or larger may be considered as difficult to ignite, but unless it is known that smaller 
particles are not mixed with the coarser material in significant amounts, it is wise to assume easy ignition is 
possible.  The unusual conditions under which various shaped pieces of titanium will ignite spontaneously 
include contact with liquid oxygen, in which case it may explode. 

Finely divided titanium in the form of dust clouds or layers does not ignite spontaneously (differing in this 
respect from zirconium, plutonium, and certain other metals); however, in the presence of an ignition 
source such as static electricity, titanium fines are easily ignited in air, carbon dioxide, or nitrogen.   
Ignition temperatures of titanium dust clouds in air range from 332 to 588°C (630 to 1,090°F), and of 
titanium dust layers from 382 to 510°C (720 to 950°F).  Refer to NFPA 484 for additional information.   

Storage and Handling 

Titanium castings and ingots are so difficult to ignite and burn that special storage recommendations for 
large pieces are not included in NFPA 484.  Titanium sponge and scrap fines, on the other hand, do require 
special precautions, such as storage in covered metal containers and segregation of the container from 
combustible materials.  Because of the possibility of hydrogen generation in moist scrap and spontaneous 
heating of scrap wet with animal or vegetable oils, a yard storage area remote from buildings is 
recommended for scrap that is to be salvaged.  Alternate recommended storage locations are detached 
scrap storage buildings and fire resistive storage rooms. Buildings and rooms for storage of scrap fines 
should have explosion vents. 

Process Hazards 

Contact of molten metal with water is the principal hazard during titanium casting.  To minimize this 
hazard, molds are usually thoroughly predried and vacuumed, or inert gas protection is provided to retain 
accidental spills. 

The heat generated during machining, grinding, sawing, and drilling of titanium may be sufficient to ignite 
the small pieces formed by these operations or to ignite mineral oil base cutting lubricants.  Consequently, 
water‐based coolants should be used in ample quantity to remove heat, and cutting tools should be kept 
sharp.  Fines should be removed regularly from work areas and stored in covered metal containers.  To 
prevent titanium dust explosions, any operation that produces dust should be equipped with a dust 
collecting system discharging into a water‐type dust collector. 

21
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Descaling baths of mineral acids and molten alkali salts may cause violent reactions with titanium at 
abnormally high temperatures.  Titanium sheets have ignited upon removal from descaling baths.    This 
hazard can be controlled by careful regulation of bath temperatures. 

There have been several very severe explosions in titanium melting furnaces.  These utilize an electric arc to 
melt a consumable electrode inside a water‐cooled crucible maintained under a high vacuum.  Stray arcing 
between the consumable electrode and crucible, resulting in penetration of the crucible, permits water to 
enter and react explosively with the molten titanium.  Indications are that such explosions approach 
extreme velocities.  The design and operation of these furnaces require special attention in order to prevent 
explosions and to minimize damage when explosions do occur. 

Extinguishing Titanium Fires 

Carbon dioxide, foam, and dry chemical extinguishers are not effective on titanium fires, but good results 
have been obtained with dry powder extinguishing agents developed for use on magnesium fires.  The use 
of water or a water‐based agent will result in a violent exothermic reaction. 

The safest procedure to follow with a fire involving small quantities of titanium powder is to cover the 
burning material with an appropriate extinguishing media (e.g. dry sand, MET‐L‐X or other Na‐Cl based 
agents).  Great care should be taken to prevent formation of a titanium dust cloud during the application of 
the extinguishing agent. 

Large titanium fires are very difficult to control or extinguish.  Adequate quantities of Class D agent are not 
likely to be available and if they were, application of the agent to the fire would be a serious safety risk due 
to the very high burning temperatures of the titanium.  Large fires are usually controlled by segregating the 
fire area and allowing the fire to burn out.  Based on the available quantities of titanium, this may result in 
a fire that burns for several days. 

Alkali Metals: Sodium, Potassium, Sodium‐Potassium (NaK), and Lithium 

Properties 

Sodium 
At room temperature, sodium oxidizes rapidly in moist air, but spontaneous ignitions have not been 
reported except when the sodium is in a finely divided form.  When heated in dry air, sodium ignites near 
its boiling point of 880°C (1,616°F).  Sodium in normal room air and at a temperature only slightly above its 
melting point 98°C (208°F) has been ignited by placing sodium oxide particles on its surface.  This indicates 
the possibility of ignition at temperatures below the boiling point.  Once ignited, hot sodium burns 
vigorously and forms dense white clouds of caustic sodium oxide fumes.  During combustion, sodium 
generates about the same amount of heat as an equivalent weight of wood. 

The principal fire hazard associated with sodium is the rapid reaction with water.    It floats on water 
(specific gravity 0.97), reacting vigorously and melting.  The hydrogen liberated by this reaction may be 
ignited and explode from the heat of the reaction.  Sodium (like other burning, reactive metals) reacts 

22
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
violently with most chemicals that can oxidize, halogenated hydrocarbons, with halogens such as iodine, 
and with sulfuric acid. 

Potassium 
The fire hazard properties of potassium (K) are very similar to those of sodium with the difference that 
potassium is more reactive.  For example, the reaction between potassium and the halogens is more 
violent, and, in the case of bromine, a deflagration/detonation can occur.  There is an explosive reaction 
with sulfuric acid.  Unlike sodium, potassium forms some peroxides and superoxides during combustion.   
These peroxides may react violently with organic contaminants (oils, etc.).  Peroxides and superoxides may 
also react explosively with metallic potassium (see NaK below).  Superoxides of potassium can be shock 
sensitive. 

Sodium‐Potassium (NaK) 
NaK is the term used when referring to any of several sodium‐potassium alloys.  The various NaK alloys 
differ from each other in melting point, but all are liquids or melt near room temperature.  NaK alloys 
possess the same fire hazard properties as those of the component metals except that the reactions are 
more vigorous.  Under pressure, NaK leaks have ignited spontaneously. 

The potassium in NaK will react with atmospheric oxygen to form three different oxides, potassium oxide 
(K2O), potassium peroxide (K2O2), and potassium superoxide (KO2).  These oxides form a crust over the NaK 
surface.  If this crust is permeated and the superoxide (KO2) is allowed to mix with the potassium in the 
NaK, a very high temperature thermite‐type reaction can occur.  This reaction may take several minutes to 
develop if the NaK is stored under an inert atmosphere or it may occur instantly if stored under 
atmospheric oxygen. 

Lithium 
Lithium, like sodium and potassium, cesium, and rubidium is one of the alkali metals.  Lithium undergoes 
many of the same reactions as sodium.  For example, both sodium and lithium react with water to form 
hydrogen; but whereas the sodium‐water reaction can generate sufficient heat to ignite the hydrogen, the 
far less violent lithium‐water reaction does not.  Lithium ignites and burns vigorously at a temperature of 
180°C (356°F), which is near its melting point.  Unlike sodium and potassium, it will burn in nitrogen.  The 
caustic (oxide and nitride) fumes accompanying lithium combustion are more profuse and dense than 
those of other alkali metals burning under similar conditions.  Lithium is the lightest of all metals.  During 
combustion, it tends to melt and flow. 

Storage and Handling 

Because of their reactivity with water, alkali metals require special precautions to prevent contact with 
moisture.  Drums and cases containing alkali metals should be stored in a dry, fire‐resistive room or 
building used exclusively for alkali metal storage.  Storage rooms should be located on the first floor level 
without a basement below the storage room.  Since sprinkler protection would be undesirable, no 
combustible materials should be stored in the same area.  It is good practice to store empty as well as filled 
alkali metal containers in the same area, and all containers should be on skids.  There should be no water 
or steam pipes, but sufficient heat should be maintained to prevent moisture condensation caused by 
23
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
atmospheric changes.  Natural ventilation at a high spot in the room is desirable to vent any hydrogen that 
may be released by accidental contact of alkali metal with moisture. 

Small quantities (1 kg or less per container) of alkali metals should be stored in sealed containers inside of 
metal or approved hazardous material storage cabinets in a building with fire sprinkler protection.  
Combustible materials should not be stored adjacent to the storage cabinets 

Large quantities of alkali metal are often stored outdoors in aboveground tanks.  In such installations, 
weatherproof enclosures should cover tank manholes and the free space within the tank should contain a 
nitrogen atmosphere.  Argon or helium atmospheres should be substituted for nitrogen in the case of 
lithium. 

For small‐scale transfer of solid alkali metal from a storeroom to the use area, a metal container with a 
tight cover is recommended.  Alkali metal should be removed from storage in an area other than the 
designated storage rooms and in as small quantities as practicable.  When stored on workbenches, it 
should be kept under kerosene or oil in a closed container.  Alkali metal, with its great affinity for moisture, 
may react at the time it is sealed in a container with any atmospheric moisture.  Because of the possible 
presence of hydrogen, containers should not be opened by hammering on the lid. 

Process Hazards 

Liquid alkali metal is valuable as a high temperature heat transfer medium.  For example, it is used in 
hollow exhaust valve stems in some internal combustion engines and in the transfer of heat from one type 
of nuclear reactor to a steam generator.  In the latter process or other large‐scale use of molten alkali 
metal, any equipment leak may result in a fire.  Where molten alkali metal is used in process equipment, 
steel pans should be located underneath to prevent contact with concrete floors.  Contact of molten alkali 
metal with concrete will cause spalling of the concrete and spattering of the metal. 

Processing of alkali metal is essentially remelting it to form sticks or bricks or to add as a liquid to closed 
transfer systems.  During this handling, contact with moist air, water, halogens, halogenated hydrocarbons, 
and sulfuric acid needs to be avoided. 

Extinguishing Fires in Sodium, Lithium, NaK, and Potassium 

The common extinguishing agents, such as water, foam, and clean agents, should never be used because of 
the violent reactions upon application to alkali metals.  Class D dry powders developed for alkali metal 
fires, dry sand, dry sodium chloride, copper powder, and dry soda ash are effective, with graphite based 
Class D agents being the best.  These finely divided materials blanket the fire while the metal cools to 
below its ignition temperature.  Alkali metal burning in an apparatus can usually be extinguished by closing 
all openings.  Blanketing with nitrogen is also effective except for lithium.  In the case of lithium, argon or 
helium atmospheres should be used.  If the alkali metal is with a combustible liquid, the Class B agent must 
be compatible with the Class D agent being used on the fire. 

Lithium and lithium alloys used in products such as batteries that also use ordinary combustibles, present 
an unusual fire hazard as many of the suppressants used to extinguish ordinary combustibles are not 
compatible with combustible metals.  For more information, refer to NFPA 484. 
24
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Zirconium and Hafnium 

Properties 

Zirconium 
The combustibility of zirconium increases as the average particle size decreases, but other variables, such as 
moisture content, also affect its ease of ignition.  Pieces of zirconium can withstand extremely high 
temperatures without igniting, whereas clouds of dust in which the average particle size is 3 microns have 
ignited at room temperature.  Dust clouds of larger particle size can be readily ignited if an ignition source is 
present, and such explosions can occur in atmospheres of carbon dioxide or nitrogen as well as in air.   
Zirconium dust will ignite in carbon dioxide at approximately 621°C (1,150°F) and nitrogen at approximately 
788°C (1,450°F).  Tests have also indicated that layers of 3‐micron‐diameter dust are susceptible to 
spontaneous ignition.  The depth of the dust layer and its moisture content are important variables for 
ignition.  Spontaneous heating and ignition are also possibilities with scrap chips, borings, and turnings if 
fine dust is present.  Layers of 6‐micron‐diameter dust have ignited when heated to 190°C (374°F).  
Combustion of zirconium dust in air is stimulated by the presence of limited amounts of water (5 to 10%).  
When very finely divided zirconium powder is completely immersed in water, it is difficult to ignite, but once 
ignited it burns more violently than in air. 

Pieces of zirconium do not ignite spontaneously under ordinary conditions, but ignition will occur when an 
oxide‐free surface is exposed to sufficiently high oxygen concentrations and pressure.  The explanation for 
this reaction is the same as that cited for a similar titanium reaction.  Zirconium fires (like fires involving 
titanium and hafnium) attain very high temperatures, but generate very little smoke. 

Explosions have occurred while zirconium was being dissolved in a mixture of sulfuric acid and potassium 
acid sulfate.  Zirconium has exploded during and following pickling in nitric acid, and also during treatment 
with carbon tetrachloride or other halogen‐containing materials.  Spontaneous explosions have occurred 
during handling of moist, very finely divided, contaminated zirconium scrap. 

Hafnium 
Hafnium has similar fire properties to zirconium.  Hafnium burns with very little flame, but it releases large
 
quantities of heat.  Hafnium in sponge form may ignite spontaneously.
 

Hafnium is generally considered somewhat more reactive than titanium or zirconium of similar form.
   
Damp hafnium powder reacts with water to form hydrogen gas, but at ordinary temperatures, this reaction
 
is not sufficiently vigorous to cause the hydrogen to ignite.  At higher temperatures, however, ignition of
 
the hydrogen may be expected to proceed explosively.
 

Storage and Handling 

Special storage precautions are not required for zirconium castings because of the very high temperatures 
that the pieces can withstand without igniting.  Zirconium powder, on the other hand, is highly 
combustible; consequently, it is customarily stored and shipped in 3.78‐L (1‐gal) containers with at least 
25% water by volume.  For specific details, refer to NFPA 484. 

25
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Zirconium powder storerooms should be of fire‐resistive construction equipped with explosion vents.   
Containers should be separated from each other to minimize the possibility of a fire at one can involving 
others and to permit checking of the cans periodically for corrosion.  Consider disposing of cans containing 
zirconium powder that have been on the shelf for more than six months. 

Process Hazards 

In general, processing recommendations for zirconium and hafnium are the same.  Handling of zirconium 
powder, whenever possible, should be under an inert liquid or in an inert atmosphere.  If zirconium or 
hafnium powder is handled in air, extreme care needs to be used because the small static charges 
generated may cause ignition. 

To prevent dangerous heating during machining operations, a large flow of mineral oil or water‐base 
coolant is required.  In some machining operations, the cutting surface is completely immersed.  Turnings 
should be collected frequently and stored under water in cans.  Where zirconium dust is a byproduct, dust‐
collecting equipment that discharges into a water precipitation type of collector is a necessity. Ignition of 
hafnium can result in an explosion when moisture content is in the range of 5‐10%; it is therefore highly 
advantageous to ensure that water concentrations are 25% or greater at all times when water is used as 
part of the process.  

Extinguishing Fires in Zirconium and Hafnium 

Fires exposing pieces of zirconium can be extinguished with water.  Limited tests conducted by Industrial Risk 
Insurers have indicated that the discharge of water in spray form would have no adverse effect on burning 
zirconium turnings.  These tests showed that when a sprinkler opened directly above an open drum of 
burning zirconium scrap, there was a brief flare‐up, after which the fire continued to burn quietly in the 
drum.  When a straight stream of water at a high rate of flow was discharged into the drum, water 
overflowed and the fire went out.  Similarly, fires exposing pieces of hafnium can also be extinguished with 
water; however, water should never be used directly on a hafnium fire unless it is used in large quantities. 

Where small quantities of zirconium or hafnium powder or fines are burning, the fire can be ringed with a 
Class D extinguishing powder to prevent its spread, after which the fire can be allowed to burn out.  Special 
powders developed for metal fires have been effective in extinguishing zirconium or hafnium fires.  When 
zirconium or hafnium dust is present, the extinguishing agent should be applied so that a zirconium dust 
cloud will not form.  If the fire is in an enclosed space, it can be smothered by introducing argon or helium. 

Calcium and Zinc 

Properties 

Calcium 
The flammability of calcium depends considerably on the amount of moisture in the air.  If ignited in moist 
air, it burns without flowing at a somewhat lower rate than sodium.  It decomposes in water to yield 
calcium hydroxide and hydrogen, which may burn.  Finely divided calcium will ignite spontaneously in air.  It 
should be noted that barium and strontium are very similar to calcium in their fire properties. 

26
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Zinc 
Zinc does not introduce a serious fire hazard in sheets, castings, or other pieces because of the difficulty of 
ignition.  Once ignited, however, large pieces burn vigorously.  Moist zinc dust reacts slowly with the water 
to form hydrogen, and, if sufficient heat is released, ignition of the dust can occur.  Zinc dust clouds in air 
ignite at 599°C (1,110°F).  Burning zinc generates appreciable smoke that obscures visibility and could 
inhibit occupant egress and emergency response. 

Storage, Processing, and Extinguishing Fires in Calcium and Zinc 

The storage, handling, and processing recommendations for magnesium are generally applicable to calcium 
and zinc. 

Aluminum 

The usual forms of aluminum have a sufficiently high ignition temperature so that its burning is not a factor 
in most fires.  However, very fine chips and shavings are occasionally subject to somewhat the same type of 
combustion as described for magnesium.  Powdered or flaked aluminum in its pure form can ignite easily in 
air and can be explosive in air in the presence of an ignition source (e.g. static discharge).  The degree of 
explosively of aluminum powder or flakes increases as the particle size decreases.  Wet or dry dust collection 
systems may be subject to such fires and protection requirements are established in NFPA 484.  Such 
collection systems should be located outdoors. 

Aluminum in contact with magnesium burns readily, perhaps due to the formation of an alloy at the 
interface.  Aluminum pastes are subject to fires, especially when the paste is solvent‐wet and the solvent 
vapors have a low ignition temperature.  

Extinguishing agents for aluminum depend upon the form in which it is in.  Although a fire in ordinary 
combustible materials with large castings of aluminum can be suppressed with large quantities of water, fire 
involving aluminum fines or powder must be treated carefully to avoid dispersal that may result in an 
explosion.  Powder and fines fires are best handled by hand application of dry sand or Class D extinguishing 
agent appropriate for the metal.  Water, dry powder, carbon dioxide, or halogen containing agents should be 
avoided as they can increase the intensity of the fire or result in a violent reaction.  

Iron and Steel 

Iron and steel are not usually considered combustible; in pieces (as in structural steel, cast iron parts, etc.), 
they do not burn in ordinary fires.  Steel in the form of fine steel wool or dust may be ignited in the 
presence of heat from, for example, a torch, yielding a form of sparking rather than actual flaming in most 
instances.  Fires have been reported in piles of steel turnings and other fine scrap that presumably 
contained some oil and were perhaps contaminated by other materials that facilitated combustion.  
Spontaneous ignition of water‐wetted borings and turnings in closed areas, such as ship hulls, has also 
been reported.  Pure iron has a melting point of  1,535°C (2,795°F).  Ordinary structural steel has a melting 
point of 1,430°C (2,606°F). 

27
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Finely divided powders of iron and steel can be dangerous if they are allowed to form a dust cloud or 
disturbed due to poor housekeeping practices.  Iron/steel powder that is allowed to build up on flat 
surfaces has the potential to cause massive fire balls if the powder is disturbed and allowed to free fall to 
the floor below. 

Plutonium 

Plutonium is one of the most widely used pyrophoric materials in the DOE Complex.Some of the most 
serious fires occurring within the Complex are caused by the ignition of finely divided plutonium particles.  
Several plutonium compounds are pyrophoric.  The radioactive decay of plutonium creates additional 
concerns such as dispersal of particles in a fire, pressurization of storage containers, and the production of 
hydrogen gas during decomposition of adsorbed water. 

  Note: Plutonium‐238 can generate as much as 1‐Watt/gram due to radioactive decay 

Properties 

Metal, Oxides, and Oxidation 
Large pieces of plutonium metal react slowly with the oxygen in air at room temperature to form plutonium 
oxides.  The rate of oxidation is dependent on a number of factors.  These include:  (a) temperature; (b) 
surface area of the reacting metal; (c) oxygen concentration; (d) concentration of moisture and other 
vapors in the air; (e) the type and extent of alloying; and (f) the presence of a protective oxide layer on the 
metal surface.  The rate of oxidation increases with increases in the first four factors and decreases with 
the last.  Alloying can either increase or decrease the oxidation rate, depending on the alloying metal.  Of 
all these factors, moisture has a large effect on the oxidation rate and is especially significant in evaluating 
conditions for storing plutonium metal and oxide. 

Several plutonium oxides can be formed from oxidation of metal or decomposition of plutonium 
compounds.  Oxide phases corresponding to sesquioxide (Pu2O3) and dioxide (PuO2) compositions have 
been identified and are well characterized.   Pu2O3  is pyrophoric in air and rapidly forms plutonium dioxide 
while releasing heat.   The dioxide is unreactive in air, but reportedly, heats slowly with water vapor at 
elevated temperatures. 

Hydride 
Plutonium hydride (PuHx, 2 < x < 3) forms during corrosion of plutonium metal by hydrogen from water, 
organic materials, and other sources.   Hydride is rapidly oxidized by dry air at room temperature to 
produce PuO2 and H2 and reacts with nitrogen at 250°C (482°F) to form plutonium nitride (PuN).  The 
reactivity of plutonium hydride in air depends on factors such as particle size, presence/absence of 
protective oxide layer, and the hydrogen to plutonium atomic ratio.  Finely divided hydride is pyrophoric in 
air at room temperature.  Thus, the only safe practice is to handle and store hydride in a dry, oxygen‐free 
atmosphere. 

28
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Carbides and Nitride 
Plutonium carbides, oxycarbides, and nitride are reactive and potentially pyrophoric materials that could 
pose handling problems if exposed to air or oxygen‐containing atmospheres.  These compounds react 
readily with moisture to form gaseous products such as methane, acetylene, and ammonia.  Because 
plutonium compounds of this type have been prepared at several sites and may have been "temporarily" 
stored under special conditions (hermetically sealed within an inert atmosphere) without first oxidizing 
them, caution should be exercised in opening cans that might contain such materials. 

Reactions Involving Water 
Water vapor accelerates the oxidation of plutonium by oxygen and reacts directly with the metal.   
Oxidation is about ten times higher in humid air than in dry air at room temperature.  For this reason, 
plutonium metal has routinely been handled in a very dry atmosphere such as one with a ‐40°C (‐40°F) dew 
point.  Inerting of gloveboxes and enclosures for handling plutonium with nitrogen or argon is effective in 
reducing metal oxidation only if it also excludes water vapor.  Rapid oxidation does not occur if oxygen is 
present at a level of 5% in nitrogen or argon.  However, if 1.3% moisture (50% relative humidity) 
accompanies the oxygen, then rapid metal oxidation can be anticipated. 

Plutonium dioxide can adsorb water on the surface.  The quantity adsorbed is a direct function of the 
surface area of the oxide.  The principal hazard associated with adsorbed water is pressurization of a sealed 
oxide container through any of several separate processes including evaporation of water, radiolysis to 
form oxygen and hydrogen, or direct reaction with the oxide to form a higher oxide and hydrogen gas. 

Pressurization of oxide containers can be prevented by use of sealed containers fitted with durable, high‐
efficiency metal filters.  Although gases can escape without release of plutonium‐containing particles, air 
(possibly moist) is able to enter the container. 

Pyrophoricity 
When heated to its ignition temperature, plutonium reacts at an accelerated oxidation rate, which sustains 
continued oxidation.  The burning temperature depends on the rate of heat dissipation to the surroundings 
and the rate of heat generation, which is dependent on the surface area of oxidizing metal.  Temperatures 
of plutonium fires usually exceed the melting temperature of plutonium metal 640°C (1184°F) which causes 
the material to consolidate into a molten configuration.  As such, finely divided metal, turnings, and casting 
skulls tend to ignite readily and achieve a high initial temperature that lasts until melting occurs and the 
surface area is reduced. 

The oxide layer that forms during burning limits the oxidation rate of plutonium.  The burning process is 
similar to that of a charcoal briquette.  The ignition temperature of plutonium metal depends on the 
factors that increase the oxidation rate.  Finely divided plutonium, such as metal powder or fine machine 
turnings, ignites near 150°C (302°F).  This temperature is easily reached if a coexisting pyrophoric material 
such as a hydride spontaneously ignites at room temperature.  Pieces of plutonium characterized as having 
a minimum thickness greater than 1.0 mm (0.04 in) and a specific surface area greater than 1 cm2 /g (71 in2 
lb) requires temperatures in excess of 400°C (752°F) to ignite.  Many plutonium fires have occurred because 
samples containing finely divided metal have spontaneously ignited.  Fires have not occurred with well‐

29
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
characterized metal existing in large pieces that have higher ignition temperatures.  Thus, a piece of 
plutonium is not considered pyrophoric or capable of self‐ignition. 

An investigation of two instances in which kilogram‐sized plutonium pieces were observed to 
"spontaneously ignite" in air at room temperature showed that they had been exposed to unlimited 
sources of hydrogen for extended periods, and that the samples were thermally insulated when ignition 
occurred.  The amount of hydride present on these pieces apparently generated sufficient heat to cause 
ignition.  These observations emphasize the need for well‐characterized materials. 

Storage and Handling 

Plutonium should be stored as pure metal (Pu) or in its dioxide (PuO2) form in a dry, inert or slightly 
oxidizing atmosphere.  The formation of oxide from metal is accompanied by a large volume expansion (up 
to 70%) which may bulge or breach the primary container.  Case studies show that mechanical wedging 
resulting from this expansion can even breach a second metal container, resulting in localized 
contamination release and possible exposure of personnel.  Oxidation of the metal and rupture of the 
container by mechanical wedging are prevented if the storage container is hermetically sealed.  Plutonium 
radioactively decays producing alpha particles and helium molecules.  Over long‐term storage, helium 
buildup can contribute to the pressurization of containers. 

Plutonium sesquioxide and hydride should be converted to plutonium dioxide before storage.  Primary and 
secondary containers should be hermetically sealed and contain no plastics or other materials that 
decompose as a result of radiation exposure. 

For a more complete discussion of plutonium storage, refer to DOE‐STD‐3013‐2012, Stabilization, 
Packaging, and Storage of Plutonium‐Bearing Materials (March 2012). 

Where plutonium must be handled, placing larger pieces on a thick stainless steel slab will generally 
conduct heat away from the material fast enough that spontaneous ignition does not occur. 

Extinguishing Plutonium Fires 

Plutonium fires should not be approached without protective clothing and respirators unless the fire is 
enclosed in a glovebox.  The most effective agent for extinguishing plutonium fires has been found to be 
magnesium oxide sand.  Gloveboxes that contain pyrophoric forms of plutonium should also contain a 
supply of magnesium oxide sand that is adequate for manual extinguishment.  Magnesium oxide sand 
extinguishes a plutonium fire by providing a heat sink that cools the plutonium below its ignition temperature 
and by providing a barrier that limits the availability of oxygen.  Burning plutonium should be completely 
covered with the sand to as great a depth as possible.  Extinguishment ‐ studies have shown that covering 
plutonium with one to two inches of magnesium oxide sand, or using a mass of magnesium oxide sand 
roughly three times that of the plutonium has been effective at extinguishing a plutonium fire.  
Additionally, if a mass of plutonium is burning within a stainless steel glovebox, agents typically non‐
compatible with plutonium (Clean Agents, CO2, etc.) can be used on the exterior of the glovebox to cool 
the burring mass; in some cases, this is sufficient to extinguish a plutonium fire by reducing the 
temperature of the burning mass below its ignition temperature. 

30
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Argon is a very effective extinguishing agent, if the oxygen content in the atmosphere is maintained at 4% 
or less.  Above 4% oxygen, flooding with argon will not extinguish a plutonium fire.  This is an important 
point, since it is nearly impossible to reduce the oxygen content to 4% or less during argon flooding in most 
fume hoods.  Argon may be used effectively to cool the burning plutonium prior to application of the 
magnesium oxide sand. 

Other agents have been tested for use on plutonium fires; however, none has proven to be as effective as 
magnesium oxide.  Typical foam or dry chemical agents are not effective extinguishing agents.  Fusible salt 
agents have been shown to be effective on small‐scale plutonium fires.  However, the expansion that 
accompanies the oxidation of plutonium has caused the fusible salt coating to crack, allowing the 
plutonium to re‐ignite. 

As a last resort, water can be used as an extinguishing agent for fires of ordinary combustibles that are 
exposing plutonium.   Where criticality safety considerations preclude the introduction of moderators such 
as water, suitable alternative fire protection measures need to be identified within fire hazard plans to 
coordinate or incorporate such measures into emergency response activities.  Proper housekeeping, which 
includes removal of combustibles from pyrophoric forms of plutonium, is the most important aspect of fire 
loss minimization. 

Uranium 

Properties 

Uranium is a radioactive metal that is also combustible in finely divided forms.  Its radioactivity does not 
influence its combustibility, nor is the radioactivity influenced by burning the material.  Metallic uranium 
that is handled in pieces does not present a significant fire risk unless exposed to a severe and prolonged 
external fire.  Once ignited, pieces of metal burn very slowly. In the absence of strong drafts, uranium oxide 
smoke tends to deposit in the immediate area of the burning metal.  Unless covered with oil, pieces of 
uranium will burn with virtually no visible flame.  Burning uranium reacts violently with carbon tetrachloride, 
1,1,1‐trichloroethane, and the Halons.   

Uranium in finely divided form is readily ignitable, and uranium scrap from machining operations is subject to 
spontaneous ignition.  This reaction can usually be avoided by storage under dry (without moisture) oil.  
Grinding dust has been known to ignite even under water, and fires have occurred spontaneously in drums 
of coarser scrap after prolonged exposure to moist air.  Because of uranium's thermal conductivity, larger 
pieces generally have to be heated entirely to their ignition temperature before igniting.  Moist dust, 
turnings, and chips react with water to generate hydrogen gas.  Uranium surfaces treated with 
concentrated nitric acid are subject to explosion or spontaneous ignition in air. 

The pyrophoric characteristics of uranium are similar to those of plutonium except that uranium forms do 
not ignite as easily as those of plutonium do.  Both form pyrophoric oxides and hydrides.  Both react 
violently with water and are best stored in their oxide form (UO2, PuO2) in dry, inert atmospheres.  
Uranium metal (U) releases hydrogen gas (H2) when allowed to react with water.  The hydrogen may then 
react with the metal to form uranium hydride (UH3) which may in turn react with oxygen in the air to form 
stable uranium oxide (UO2) and hydrogen gas (H2).   

31
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
The heat generated from corrosion, if dissipated in a water storage environment, may not be sufficient 
enough to ignite the uranium if properly configured.  This is a dynamic process and an SME should be 
consulted for an appropriate hazard analysis.  

Storage and Handling 

The storage of the many forms of uranium is beyond the scope of this primer.  For a more complete 
discussion of uranium storage, refer to DOE‐STD‐3028‐2000, Criteria for Packaging and Storing Uranium‐
233‐Bearing Materials (July 2000). 

Extinguishing Uranium Fires 

Uranium fires should be extinguished with the same techniques and precautions as plutonium fires (see 
corresponding paragraph on plutonium). 

Combustible Metal Extinguishing Agents and Application Techniques 

A variety of metals burn, particularly those in finely divided form.  Some metals burn when heated to high 
temperatures by friction or exposure to external heat; others burn from contact with moisture or in 
reaction with other materials.  Because accidental fires may occur with these materials, it is important to 
understand the nature of the various fires and the hazards involved. 

The hazards involved in the control or complete extinguishing of metal fires include extremely high 
temperatures, steam explosions, hydrogen explosions, toxic products of combustion, explosive reaction 
with some common extinguishing agents, breakdowns of some extinguishing agents with the liberation of 
combustible gases or toxic products of combustion, and, in the case of certain nuclear materials, dangerous 
radiation.  Some agents displace oxygen, especially in confined spaces.  Therefore, extinguishing agents and 
methods for their specific application should be selected with care.  Metal fires should not be approached 
without suitable personal protective equipment, including but not limited to: self‐contained breathing 
apparatus and protective clothing, unless immediate application can be performed to suppress or control a 
small fire. 

The use of water on a combustible metal fire is hazardous and great care must be taken to ensure the 
application of water does not deleteriously affect the fire.  The application of water or a water‐based 
extinguishing agent may result in a violent reaction which has the potential to spread burning material to an 
adjacent area; this can cause significant safety risk to firefighting personnel or others that may be located 
near the fire incident. 

Numerous agents have been developed to extinguish combustible metal (Class D) fires, but a given agent 
does not necessarily control or extinguish all metal fires.  Although some agents are valuable in working 
with several metals, other agents are useful in combating only one type of metal fire.  Despite their use in 
industry, some of these agents provide only partial control and cannot be considered actual extinguishing 
agents.  Certain agents that are suitable for other classes of fires should be avoided for metal fires, because 
violent reactions may result (e.g. water on sodium; vaporizing liquids on magnesium fires). 

32
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Certain combustible metal extinguishing agents have been used for years, and their success in handling 
metal fires has led to the designations "approved extinguishing powder" and "dry powder."  These 
designations have appeared in codes and other publications where it was not possible to employ the 
proprietary names of the powders.  These terms have been accepted in describing extinguishing agents for 
metal fires and should not be confused with the name "dry chemical," which normally applies to an agent 
suitable for use on flammable liquid (Class B) and live electrical equipment (Class C) fires.  Class B 
extinguishing agents may not be safely applied to combustible metal (Class D) fires.  Other extinguishing 
agents discussed herein have been used only experimentally in limited areas or at specific installations, and 
require much judgment in application.  NFPA 10 should be used when placing fire extinguishers.  Where a 
hydrophilic (attracts moisture and can chemically bond with it) Class D agent is placed in a container other 
than a fire extinguisher, it must be in an air‐tight container to avoid attracting moisture from the air, which 
would reduce the effectiveness of the agent. 

For fires that occur in chemical processing areas, the use of chemicals involved in the processing can be used 
to control or extinguish the fire with little or no adverse effect on the chemical processing.  For example, 
Lithium metal is produced in a salt bath of lithium chloride and potassium chloride operating at 
approximately 450°C (842°F).  If a fire should occur in the salt bath, adding more lithium or potassium 
chloride to the salt bath will lower the temperature of the salt bath and control the “operational excursion.”  
If an operator was to try to control the fire with a commercial fire extinguisher, the agent could poison the 
salt bath that would have to be drained, relined, and brought back to operations, which is costly in both 
downtime and expense.  For this reason and others, it is important to ensure an adequate fire hazard plan is 
in place.   

The successful control or extinguishment of metal fires depends heavily upon the method of application, 
training, and experience.  Class D agents are not all effective on all Class D fires and selection must be based 
on the material being protected.  To avoid re‐ignition, do not move the remains of a metal fire until it has 
cooled sufficiently.  Personnel using a Class D fire extinguisher or a container containing the Class D agent 
must be properly trained since the methods differ from conventional Class A:B:C extinguishers.  Practice drills 
should be held on the particular combustible metals on which the agent is expected to be used.  Prior 
knowledge of the capabilities and limitations of agents and associated equipment is always useful in 
emergencies.  Fire control measures or extinguishing agents must be immediately available to ensure they 
are effective.  In industrial plant locations where work is performed with combustible metals, public fire 
departments and industrial fire brigades have the advantage of fire control drills conducted under the 
guidance of knowledgeable individuals. 

Combustible Metal Fire Extinguishing Agents 

A number of proprietary combustible metal extinguishing agents have been submitted to testing agencies 
for approval or listing.  Others have not, particularly those agents developed for special metals in rather 
limited commercial use.  Those extinguishing agents described as follows have been shown to be effective 
for use on fires involving magnesium, aluminum, sodium, potassium, and sodium‐potassium alloy.  NFPA 
484 offers guidance on the selection of the appropriate extinguishing agent for use on combustible and 
pyrophoric metals in the Table “Combustible Metal Fire‐Extinguishing Agents Quick Reference Chart” of 
Annex A.  

33
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Met‐L‐X and Super‐D Powder 

These hygroscopic (absorbs water) dry powders, with particle sizes controlled for optimum extinguishing 
effectiveness, are composed of a sodium chloride base with additives.  The additives include tricalcium 
phosphate to improve flow characteristics and metal stearates for water repellency.  A thermoplastic 
material is added to bind the sodium chloride particles into a solid mass under fire conditions. 

Met‐L‐X and Super‐D powder are noncombustible, and secondary fires do not result from its application to 
burning metal.  There are no known health hazards resulting from the use of these agents.  They are also 
nonabrasive and nonconductive. 

Stored in sealed containers or extinguishers, Met‐L‐X and Super‐D powder are not subject to 
decomposition or a change in properties.  Periodic replacement of extinguisher charges is unnecessary.  
Extinguishers range from pressurized portable hand units, pails, cans, wheeled units, and stationary or 
piped systems.  The wheeled units and piped systems employ nitrogen as the propellant.  If the agent is 
stored in pails or cans, other than a fire extinguisher, it is applied either by scooping the material onto the 
fire or by dumping the agent from the container directly.  This method is only appropriate where the 
combustible metal is found in small quantities.  With either extinguishing method, sufficient agent must be 
applied to completely cover the burning material. 

These powders are suitable for fires in solid pieces (such as castings) because of their ability to cling to hot 
vertical surfaces.  To control and then extinguish a metal fire, the nozzle of the extinguisher is fully opened 
from a safe distance and a layer is cautiously applied over the burning material.  Some extinguishers have a 
low flow application that can be applied to finely divided particles with less risk of dispersal of the dust.  
Once control is established, the nozzle valve is used to throttle the stream to produce a soft, heavy flow.  
The metal can then be completely and safely covered from close range with a heavy layer.  The heat of the 
fire causes the powder to cake, forming a crust that excludes air and results in extinguishment. 

Met‐L‐X and Super‐D extinguishers are available for fires involving magnesium, sodium, potassium, and NaK.  
In addition, they have been successfully used where zirconium, uranium, and titanium present serious 
hazards. 

Na‐X Powder 
This powder was developed to satisfy the need for a low chloride content agent that could be used on 
sodium Potassium and NaK metal fires.  Na‐X has a sodium carbonate base with various additives 
incorporated to render the agent nonhygroscopic (does not absorb moisture) and easily fluidized for use in 
pressurized extinguishers.  It also incorporates an additive which softens and crusts over an exposed 
surface of burning sodium metal.  Na‐X is noncombustible, and does not cause secondary fires when applied 
to burning sodium metal above temperatures ranging from 649 to 816°C (1,200 to 1,500°F).  No known 
health hazard results from the use of this agent on sodium fires, and it is nonabrasive and nonconductive. 

Stored in hand portables and wheeled and stationary extinguishers, Na‐X is listed by UL for fires involving 
sodium metal up to a temperatures of 649°C (1,200°F).  Na‐X has been tested on sodium metal (spills and in 
depth) at fuel temperatures as high as 816°C (1,500°F).  Stored in the supplier's sealed metal pails and 
extinguishers, Na‐X is not subject to decomposition, so periodic replacement of the agent is unnecessary. 
34
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Other Combustible Metal Extinguishing Agents 

Foundry Flux 
In magnesium foundry operations, molten magnesium is protected from contact with air by layers of either 
molten or crust‐type fluxes.  These fluxes, which are also used as molten metal cleaning agents, consist of 
various amounts of potassium chloride, barium chloride, magnesium chloride, sodium chloride, and 
calcium fluoride.  The fluxes are stored in covered steel drums.  When applied to burning magnesium, these 
fluxes melt on the surface of the solid or molten metal, excluding air.  The thin layer of protection can be 
provided by properly applying relatively small amounts of flux. 

Fluxes are valuable in extinguishing magnesium spill fires from broken molds or leaking pots and in 
controlling and extinguishing fires in heat‐treating furnaces.  In open fires, the flux is applied with a hand 
scoop or a shovel.  Areas of furnaces that are difficult to reach can be coated by means of a flux‐throwing 
device similar to those used to throw concrete onto building forms. 

While fluxes would rapidly extinguish chip fires in machine shops, such use is not recommended.  The fluxes 
are hygroscopic and the water picked up from the air, combined with the salt, causes severe rusting of 
equipment. 

Copper Powder 
Advances in the science of alternative propulsion systems have led to the development of copper powder 
as a viable extinguishing agent for combustible metals.  Work sponsored by the Naval Sea Systems 
Command was conducted to evaluate the adequacy of existing lithium fire suppression agents and to 
develop new agents should deficiencies exist. 

Copper powder was found to be superior to known lithium fire extinguishing agents in extinguishing 
capacity.  The dry powder is of uniform particle size and extinguishes a lithium fire more quickly and 
efficiently than existing agents.  The process of extinguishment is by formation of a copper‐lithium alloy, 
which is nonreactive and forms preferentially on the surface of the molten lithium.  The alloy becomes an 
exclusion boundary between air and the molten metal, preventing re‐ignition and promoting cooling of the 
unreacted lithium. 

Copper powder can be applied from portable, hand‐held extinguishers.  The nominal size a hand‐held 
extinguisher is 14 kg (30 lb); 68 and 160 kg (150 and 350 lbs) for wheeled units; and is available in fixed 
systems as well.  Argon is used as the propellant. The method of application is similar to that of other metal 
fire powders, in that the fuel surface is coated with the copper powder in an initial pass, with a throttled 
application following once control is achieved.  Typical application densities are 3.6 kg (8 lbs) of copper 
powder per pound of lithium for complete extinguishment of the lithium.  An 18‐kg (40‐lb) lithium fire can 
be fully controlled in 30 seconds and completely extinguished in 9 minutes.  Copper powder also has been 
used to extinguish magnesium and aluminum fires. 

Lith‐X/G‐Plus Dry Powder 
These dry powder agents are composed of a special graphite base with additives.  The additives render 
them free flowing so they can be discharged from an extinguisher.  The technique used to extinguish a 
35
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
metal fire with these agents is the same as that used with NaCl based agents.  These powders do not cake 
or crust over when applied to burning metal.  They exclude air and conduct heat away from the burning 
mass to effect extinguishment.  They do not cling to hot metal surfaces, so it is necessary to completely 
cover the burning metal with the agent. 

Both agents will successfully extinguish lithium fires and are suitable for the control and extinguishment of 
magnesium and zirconium chip fires.  Lith‐x is also suitable for magnesium, sodium, and potassium zirconium, 
titanium, and NaK fires. 

TMB Liquid 
TMB is the chemical abbreviation for trimethoxyboroxine.  The agent contains methanol to render it free 
flowing.  It is classed as a flammable liquid for shipping purposes.  The liquid is colorless and hydrolyzes 
readily to form boric acid and methanol.  Contact with moist air or other sources of water need to be 
avoided to prevent hydrolysis. 

This agent is applied with a specially adapted 9.5 L (2‐1/2 gal) stored pressure extinguisher which delivers 
either spray or a straight stream.  Typical application of TMB to a metal fire yields a heat flash because of 
the breakdown of the chemical compound and ignition of the methanol.  A molten boric oxide coating on 
the hot metal prevents contact with air.  A stream of water may be used to cool the mass as soon as metal 
flames are no longer visible; this should be done cautiously to avoid rupture of the coating.  Indoor 
application (such as in machine shops) is not recommended because of the large volume of boric oxide 
smoke produced. Boric oxide is only slightly toxic. 

While TMB has been used primarily on magnesium fires, it has shown value in application to fires in 
zirconium and titanium.  Although TMB applied as a spray has been used to control small sodium and 
sodium‐potassium alloy fires, it is not recommended for fires in sodium, sodium‐potassium alloy, and 
lithium.  TMB reacts violently with lithium and sodium‐potassium alloy.  It will extinguish sodium in‐depth, 
but the protective coating formed by the TMB absorbs moisture very rapidly and in time may penetrate 
through to the sodium, resulting in a violent reaction.  Field experience has been limited to aircraft fires. 

Pyromet Powder 
Pyromet powder is composed of specially processed sodium chloride, diammonium phosphate, protein, 
and a waterproofing and flow‐promoting agent.  The powder is discharged under pressure provided by a 
carbon dioxide gas cartridge.  The unit contains 11 kg (25 lb) of powder.  The applicator consists of a 
tubular extension from the control valve, terminating in a cone‐shaped nozzle.  A mechanism in the nozzle 
absorbs the discharge pressure by swirling the powder as it is expelled.  This enables the operator to let the 
powder fall gently on the burning metal rather than to scatter burning material under the blast of a jet of 
powder. 

Pyromet has proven effective in handling fires involving sodium, calcium, zirconium, and titanium, as well as 
magnesium and aluminum in the form of powder or chips. 

36
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
TEC Powder 
TEC (ternary eutectic chloride) powder is a mixture of potassium chloride, sodium chloride, and barium 
chloride that is effective in extinguishing fires in certain combustible metals.  The powder tends to seal the 
metal, excluding air.  On a hot magnesium chip fire its action is similar to that of foundry flux.  In tests 
reported in Fire Technology, TEC powder was the most effective salt for control of sodium, potassium, and 
sodium‐potassium alloy fires.  TEC should not be used on plutonium, uranium, and alkali metal fires because 
it is hygroscopic. 

Nonproprietary Combustible Metal Extinguishing Agents 
Specially formulated extinguishing powders are generally used to suppress fires involving metals.  Because 
of the reaction many metals have with water, sprinklers and the use of other water‐based agents are not 
appropriate and, in some cases, quite dangerous.  However, many of the special agents for metal fires are 
at times unsatisfactory because they are corrosive, applied manually rather than by an extinguishing 
system, capable of clogging extinguishing nozzles, and expensive.  When these specialized proprietary 
extinguishing agents are undesirable, the following nonproprietary agents may be used.  

Talc (Powder) 
Talc, which has been used industrially on magnesium fires, acts to control rather than extinguish fire.  Talc 
acts as an insulator to retain the heat of the fire, rather than as a coolant.  It does, however, react with 
burning magnesium to provide a source of oxygen.  The addition of organic matter (such as protein) to talc 
assists in the controlling action, but does not prevent the reaction which releases oxygen to the fire. 

Carbon Microspheres 
Studies have been undertaken to examine the effectiveness of carbon microspheres or microspheroids to 
extinguish fires involving alkali metals, such as sodium, sodium‐potassium, and lithium.  These microspheres 
are petroleum‐coke‐based particles with a diameter of approximately 100 to 500 microns.  The particles 
possess high thermal conductivity, chemical inertness, and excellent flow characteristics and are capable of 
being directed onto fires from dry‐chemical‐type extinguishers and conventional nozzles. 

Tests have shown that carbon microspheres compare favorably in performance to other metal extinguishing 
agents.  In particular, experiments with carbon microspheroids incorporating neutron absorbers have been 
effective in extinguishing fires involving nuclear fissionable materials, such as uranium metal powder.  The 
excellent flow characteristics and noncoking properties of these microspheres suggest an effective way to 
extinguish radioactive metal fires within the inert atmosphere glovebox enclosures used in the nuclear 
industry. 

Graphite Powder 
Graphite powder (plumbago, G‐Plus Dry Powder) has been used as an extinguishing agent for metal fires 
and acts as a coolant.  Unless the powder is finely divided and closely packed over the burning metal, some 
air does get through to the metal and extinguishment is not as rapid as with G‐1 powder. 

37
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Sand 
Dry sand has often been recommended as an agent for controlling and extinguishing metal fires.  At times 
it seems to be satisfactory, but usually hot metal (such as magnesium) obtains oxygen from the silicone 
dioxide in the sand and continues to burn under the pile.  Sand is seldom completely dry.  Burning metal 
reacting with the moisture in the sand produces steam and, under certain conditions, may produce an 
explosive metal‐water reaction.  By laying the sand around the perimeter of the fire, fine dry sand can be 
used to isolate incipient fires of aluminum dust. 

Cast Iron Borings 
Cast iron borings or turnings are frequently available in the same machine shop as the various combustible 
metals.  Clean iron borings applied over a magnesium chip fire cool the hot metal and help extinguish the 
fire.  This agent is used by some shops for handling small fires where, with normal good housekeeping, only 
a few combustible metal chips are involved.  Contamination of the metal chips with iron may be an 
economic problem.  Oxidized iron chips need to be avoided to prevent possible thermite reaction with the 
hot metal, and the iron chips need to be free from moisture. 

Sodium Chloride 
Alkali metal fires can be extinguished by sodium chloride, which forms a protective blanket that excludes air 
over the metal so that the metal cools below its burning temperature.  Sodium chloride is an agent that is 
used for extinguishing sodium and potassium fires.  It can also be used to extinguish magnesium fires. 

Soda Ash 
Sodium carbonate or soda ash (not dry chemical) is recommended for extinguishing sodium and potassium 
fires.  Its action is similar to that of sodium chloride. 

Lithium Chloride 
Lithium chloride is an effective extinguishing agent for lithium metal fires.  However, its use should be 
limited to specialized applications because the chemical is hygroscopic to a degree and may present 
problems because of the reaction between the moisture and the lithium. 

Dolomite 
If zirconium or titanium in the form of dry powder becomes ignited, neither can be extinguished easily.  
Control can be affected by spreading dolomite (a carbonate of calcium and magnesium) around the burning 
area and then adding more powder until the burning pile is completely covered. 

Boron Trifluoride and Boron Trichloride 
Boron trifluoride and boron trichloride have both been used to control fires in heat‐treating furnaces 
containing magnesium.  The fluoride is considerably more effective. In the case of small fires, the gases 
provide complete extinguishment.  In the case of large fires, the gases effect control over the flames and 
rapid burning, but reignition of the hot metal takes place on exposure to air.  A combined attack of boron 
trifluoride gas followed by application of foundry flux completely extinguishes the fire.  For details of gas 
application, see NFPA 484. 

38
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Inert Gases 
In some cases, inert gases (such as argon and helium) will control zirconium fires if they can be used under 
conditions that will exclude air.  Gas blanketing with argon has been effective in controlling lithium, 
sodium, and potassium fires.  Caution should be exercised when using the agent in confined spaces 
because of the danger of suffocation of personnel. 

Water 

When burning metals are spattered with limited amounts of water, the hot metal extracts oxygen from the 
water and promotes combustion.  At the same time, hydrogen is released in a free state and ignites readily.  
Since small amounts of water do accelerate combustible metal fires (particularly where chips or other fines 
are involved), use of common portable extinguishers containing water is not recommended except to 
control fires in adjacent Class A materials. 

Water, however, is a good coolant and can be used on some combustible metals under proper conditions 
and applications to reduce the temperature of the burning metals below the ignition point.  The following 
paragraphs discuss the advantages and limitations of using water on fires involving various combustible 
metals. 

Sodium, Potassium, Lithium, NaK, Barium, Calcium, and Strontium Fires – Water cannot be used on fires 
involving these metals.  Water applied to sodium, potassium, lithium, sodium‐potassium alloys (NaK), 
barium, calcium, and strontium will induce chemical reactions that can lead to fire or explosion even at 
room temperatures. 

Zirconium Fires – Powdered zirconium wet with water is more difficult to ignite than the dry powder.  
However, once ignition takes place, wet powder burns more violently than dry powder.  Powder containing 
about 5 to 10% water is considered to be the most dangerous.  Water should not be applied to burning 
zirconium since violent reactions may result. 

Plutonium, Uranium, and Thorium Fires – As a last resort, water can be used as an extinguishing agent for 
fires of ordinary combustibles that are exposing these metals.  Where criticality safety considerations 
preclude the introduction of moderators such as water, suitable alternative fire protection measures need 
to be identified within fire hazard plans to coordinate or incorporate such measures into emergency 
response activities.   

Magnesium Fires – Automatic sprinklers will extinguish a typical shop fire where the quantity of 
magnesium is limited.  However, water should not be used on any fire involving magnesium ‐ a few burning 
chips can be extinguished by dropping them into a bucket of water.   

Burning magnesium parts such as castings and fabricated structures can be cooled and extinguished with 
coarse streams of water applied with standard fire hoses.  A straight stream scatters the fire, but coarse 
drops (produced by a fixed nozzle operating at a distance or by use of an adjustable nozzle) flow over and 
cool the unburned metal. Some temporary acceleration normally takes place with this procedure, but rapid 
extinguishment follows if the technique is pursued.  Well‐advanced fires in several hundred pounds (100 lb 
equals 45 kg) of magnesium scrap have been extinguished in less than 1 minute with two 37.5 mm (1‐1/2 

39
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
in.) fire hoses.  Water fog, on the other hand, tends to accelerate rather than cool such a fire.  Application 
of water to magnesium fires needs to be avoided where quantities of molten metal are likely to be present; 
the steam formation and possible metal‐water reactions may be explosive. 

Titanium Fires – Water cannot be used on fires in titanium fines and should be used with caution on other 
titanium fires.  Small amounts of burning titanium (other than fines) can be extinguished and considerable 
salvage realized by quickly dumping the burning material into a large volume of water to completely 
submerge it.  Hose streams have been used effectively on fires in outside piles of scrap, but violent 
reactions have been reported in other cases where water was applied to hot or burning titanium, resulting 
in serious injury to personnel.  Additional information on the use of water on titanium fires can be found in 
NFPA 484.   

40
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
LABORATORY SCALE OPERATIONS
  

Laboratory operations routinely use small quantities ‐ less than 0.23 kg (1/2 lb) of reactive materials 
including spontaneously ignitable and pyrophoric chemicals (reagents).  Safe handling of these chemicals is 
critical to the prevention of fires within laboratories and the prevention of injuries to laboratory personnel.  

Types of pyrophoric reagents include: 

 Alkali metals – Some alkali earth metals and other pure metals that are finely divided (metal 
catalysts, small particulates and nanoparticles) react with water vapor to generate hydrogen and 
heat. 
 Metal hydrides – These react in the same manner as alkali metals, generating heat and hydrogen. 
 Organometallics – These are reagents with carbon metal bonds that generate a volatile organic 
compound and heat when they react with moisture.  The most common examples are alkyl lithium 
reagents, Gringards (C‐MgX), and phosphines.  Some compounds that have carbon transition metal 
bonds are also known as pyrophoric reagents. 

There have been several fire events in laboratories both within and outside the DOE Complex that have 
occurred over the last 20 years that could have been prevented if the pyrophoric reagents were handled 
properly.  The consequences of these events have ranged from minor to significant, including at least one 
fatality.  The 2015 edition of NFPA 45, Standard on Fire Protection for Laboratories Using Chemicals has 
requirements to address the safe handling of pyrophoric reagents to prevent fires and to minimize the risk 
of significant injury from accidents involving pyrophoric reagents.  The following information is intended to 
address safe handling of pyrophoric reagents. 

Operations involving solid reagents are typically performed in an inert atmosphere glovebox or glovebag.  
Argon is primarily used as the inerting gas in a glovebox/bag arrangement that usually includes an oxygen 
sensor to verify that oxygen is not present when pyrophoric reagents are in use.  Liquid reagents can be 
used in an inert atmosphere within a glovebox/bag.  Pyrophoric liquids that are used outside of an inert 
atmosphere glovebox/bag have to be handled in closed systems that have been inerted and include an 
appropriate transfer method.  

After operations with pyrophoric reagents have been completed, all laboratory equipment and waste 
materials that have been in contact with pyrophoric reagents need to be neutralized or passivated to 
prevent a fire.  Very small quantities (microscopic) of pyrophoric reagents will react with oxygen and/or 
moisture in air and the resulting heat of reaction can start a fire.  Most fires associated with laboratory 
operations with pyrophoric reagents has been caused by inadequate neutralization or passivation of test 
tubes, glass ware, spatulas, wipes, needles, tubing and other tools prior to exposing them to air.  Neutralize 
pyrophoric liquids in accordance with manufacturer’s recommendations, typically by wetting the surfaces 
of the test tubes, glassware, needles and tubing with a solvent and rinsing with a secondary solvent.  For 
pyrophoric solids, the passivation of wipes, spatulas and other tools can be performed by slowly exposing 
them to low concentrations of oxygen over a 24‐hour period.   

Laboratory incidents involving pyrophoric reagents are provided at the end of this Handbook.  Additionally, 
there have been three minor events described below that were caused by pyrophoric waste that was not 

41
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
properly neutralize/passivated prior to disposal at DOE labs:  

 Paper in a garbage can was smoldering in a lab and was extinguished with water.  The event was 
caused by an exothermic reaction that occurred when the residue of chemical slurry containing 
ethylhexylcarbazole and platinum‐loaded carbon in a pipette dried out and reacted with the air to 
create heat (PNNL Non ORPS‐reportable Event). 
 Research staff was investigating a burning odor when they found a smoldering chemical wipe in a 
trash receptacle inside the lab.  The smoldering chemical wipe was extinguished with water.  The 
smoldering chemical wipe was a result of a chemical reaction after the wipe was used to clean 
Raney nickel slurry from a metal spatula and the wipe was discarded in the trash.  An investigation 
uncovered the fact that Raney nickel is provided in slurry with water because, when it is dry, it is a 
pyrophoric reagent that undergoes an exothermic reaction upon contact with air (PNNL Non ORPS‐
reportable Event). 
 A researcher found a burned trash can in a lab and used water to quench the smoldering papers.  
The cause of the burned trash can was determined be the result of the disposal of several chemical 
wipes that were removed from an inert atmosphere glovebox without being passivated.  The 
glovebox was used to handle less than 10‐micron size metal powders.  The metal powder is 
pyrophoric when exposed to air and the heat of reaction ignited the chemical wipes (see ORPS 
report: SC‐PNSO‐PNNL‐PNNLBOPER‐2014‐0005). 

Recommendations for the safe handling of pyrophoric reagents includes but not limited to: 

 Personal protective equipment that should be worn when working with pyrophoric reagents 
outside of an inert atmosphere of a glovebox typically include fire retardant lab coats, fire 
retardant gloves, safety glasses, and a face shield. 
 Operations involving pyrophoric reagents are to be performed only by those with experience in 
their hazards and properties or under close supervision by those with experience in their hazards 
and properties.   
 Avoid working alone with pyrophoric reagents. 
 Handle pyrophoric reagents in systems or enclosures that prevent the chemicals from igniting in 
accordance with the Safety Data Sheet.  Use septum sealed bottles and sealed vessels when 
pyrophoric liquids are dispensed in a fume hood.  Use syringe or double tipped needles to transfer 
pyrophoric liquids between containers in accordance with manufacturer’s recommendations and 
established safety practices.  Glassware, reaction vessels, needles, and other lab equipment must 
be cleaned of residual moisture and contaminates, and purged with a high purity inert gas prior to 
use with pyrophoric reagents.   
 Use an inert atmosphere glovebox for open dispensing of pyrophoric liquids or handling of
 
pyrophoric solids.
 
 Passivate or neutralize test tubes, glass ware, spatulas, wipes, needles, tubing and other tools that 
have been in contact with pyrophoric reagents prior to removing them from an inert atmosphere 
or disposal in accordance with established safety practices and the recommendations in the 
chemical’s Safety Data Sheet. 

42
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
INCIDENT CASE  STUDIES
 

Current Edition (2014) Case Studies 

The following case studies are considered as an update to the previous handbook Edition and are not 
inclusive of all DOE spontaneous heating or pyrophoric events that have occurred within the DOE complex 
between updates.  For more information on these events, please access the applicable Occurrence 
Reporting and Processing System (ORPS) number through either the internet or the ORPS Administrator. 
For additional case studies, please refer to the NFPA web site listed the bibliography section of this 
Handbook. 

Laboratory (Reagent) Incident – National Renewable Energy Laboratory (2002) 

ORPS Report No.:  GO‐NREL‐‐NREL‐2002‐0001 

At approximately 1301 (MST) on December 27, 2002 a fire was discovered by facility maintenance 
personnel in a chemical fume hood located in Solar Energy Research Facility (SERF) Lab C‐221.  The building 
fire alarm system and the NREL Emergency Notification System were activated.  An orderly evacuation of 
the facility was completed.  Firefighters and equipment responded to the scene and assessed the situation.  
The assessment determined that the fire was contained within the chemical fume hood and that a variety 
of chemicals, albeit small amounts, was involved.  A small flow of liquid was observed coming from the 
hood and pooling on the floor of the lab.  The liquid was identified as de‐ionized water, which was leaking 
from plastic piping that was apparently damaged by the fire.  The single most likely cause appears to have 
been a delayed reaction involving unreacted pyrophoric material, tris (trimethylsilyl) phosphine (TTMSP), 
inside one or more of the pipettes that had been transferred from the glovebox to the chemical fume 
hood.  Pipettes are used to transfer pyrophoric materials during sample preparation inside the glovebox.  
The glovebox is maintained under an inert atmosphere (helium) to prevent the reaction of pyrophoric 
materials.  There is no fire detection or suppression system inside the hood.  The laboratory is equipped 
with a fire sprinkler system.  This system did not activate, as the fire did not escape the hood.  Passive fire 
protection features such as laboratory compartmentalization and ventilation configuration prevented the 
spread of smoke beyond the laboratory. 

Environmental Restoration Incident – Rocky Flats Environmental Technology Site (2004) 

ORPS Report No.: EM‐RFO‐‐KHLL‐371OPS‐2003‐0011 

On May 6, 2003, D&D activities were taking place in room 2325 in Building 371.  Specific actions included 
cutting sheet metal panels from glovebox 8 to provide an airflow path in an attempt to provide ventilation 
into the glovebox to reduce airborne levels of plutonium during subsequent clean out and size reduction of 
the glovebox.  Workers noted smoke and evidence of a fire inside the glovebox structure, and took actions 
in an attempt to control the situation.  The workers discharged a number of portable fire extinguishers into 
the glovebox, only to have the fire re‐ignite.  Concurrent with these actions, the job supervisor notified the 
facility Configuration Control Authority (CCA) of the event, who contacted the Fire Department, initiating 
their response.  Further attempts to control the situation were initiated by the workers until the Fire 
Department arrived on scene and, using water, extinguished the fire and stabilized the situation.  Actual 

43
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
damage to the glovebox and other equipment was minimal, however four of the fire fighters received skin 
contamination as a result of the firefighting efforts.  Because of the use of respirators, they did not receive 
any radioactive material uptake or significant dose (maximum of 20 mrem).  Bioassay analysis of other 
potentially affected building personnel did not show any significant personnel contamination or radioactive 
material uptakes. 

Environmental Restoration Incident – Idaho National Laboratory (2004) 

ORPS Report No.: EM‐ID‐‐CWI‐ICDF‐2005‐0004 

On September 20, 2005, at the Idaho National Laboratory CERCLA disposal facility, a worker was preparing 
to mix zinc powder with sulfamic acid in a 5‐gallon bucket to be used for treating mercury‐contaminated 
soil when flames erupted from the bucket.  A co‐worker extinguished the flames using MET‐L‐X, and all 
employees left the area.  The fire department verified that the fire was out, and no one was injured. 

Processing Maintenance Incident – Y‐12 (2005) 

ORPS Report No.: NA‐‐YSO‐BWXT‐Y12NUCLEAR‐2005‐0036 

On November 22, 2005, at Y‐12, workers were performing maintenance on a crusher‐grinder when finely 
divided material ignited unexpectedly.  Thirteen employees were evacuated from the facility.  An 
investigation team learned that several factors caused the fire:  the material had been exposed to air for six 
weeks; actuation of the crusher cylinders stirred up the material, exposing the unoxidated material 
beneath a layer of passivated material; and the material had been exposed to moisture.  One of the 
employees was transported to an offsite medical facility for observation; the rest were uninjured. 

Laboratory (Reagent) Incident – Los Alamos National Laboratory (2005) 

ORPS Report No: NA‐‐LASO‐LANLFIRNGHELAB‐2005‐0012 

On December 8, 2005, at Los Alamos National Laboratory, a worker in an explosives laboratory was 
handling a piece of fiberglass matting which was coated with 1 gram of a nanoaluminum‐fluoroelastomer 
mixture when it unexpectedly ignited, causing second‐degree burns on the worker’s right hand.  The mat 
that ignited was one of a group of mats to which the mixture had been applied, vacuum‐dried at 80°C, and 
cooled to near room temperature.  Although facility personnel had worked with this mixture before, they 
had never used it bonded to fiberglass matting.  The accident investigation team determined that the most 
likely ignition source was energetic buildup within the material and that the hazards of handling the 
nanoaluminum material had not been properly characterized.  

Laboratory (Reagent) Incident ‐ Savannah River National Laboratory (2006) 

ORPS Report No.: EM‐SR‐‐WSRC‐LTA‐2006‐0002 

On January 10, 2006, at Savannah River National Laboratory, a principal investigator and first‐line manager 
were cleaning an attritor mill vessel (shown in Figure 1‐1 on a lifting table) when a fire flashed and caused 
first‐ and second‐degree burns to the right side of the manager’s face and head and his left hand.  The 
manager was treated at a local hospital and released.  
44
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
The attritor mill had been used to blend and finely grind metal hydride into powder for use in hydrogen 
storage technologies.  Grinding the metal hydride into fine particles renders it pyrophoric (i.e., capable of 
spontaneously combusting in air) because its increased surface area oxidizes more readily. 

After preparing the necessary quantity of metal hydride powder, the principal investigator and manager 
wiped down the attritor mill several times in an argon‐inerted glovebox.  They then removed the vessel 
from the glovebox and began wiping it down with isopropyl alcohol.  When the vessel was taken out of the 
glovebox, residual particulate reacted and flashed.  The principal investigator extinguished the fire with 
MET‐L‐X® powder. 

Following its evaluation of the January 2006 fire, the Accident Investigation Board determined that it 
occurred when metal hydride powder in the vessel bolt holes reacted with air and isopropyl alcohol vapors.  
The root cause was the failure to fully analyze the hazards of working with metal hydrides, particularly 
cleanup activities after processing. 

Processing Incident – Y‐12 (2005) 

ORPS Report No.:  NA‐‐YSO‐BWXT‐Y12NUCLEAR‐2007‐0012 

On March 15, 2007, at about 9:15 a.m., a uranium machine turnings (chips) fire occurred during a dry chip 
transfer operation in Building 9204‐2E.  The fire was small (~210 g U), was self‐extinguished, and did not 
activate any fire alarms or automatic suppression systems.  The operation occurred just outside the linear 
glovebox laboratory hood.  Three assembly operators and their supervisor were involved in the activity, 
and a Radiological Control technician was in support.  The resulting smoke prompted evacuation by 
involved operators, support personnel, and building occupants. Smoke generated from the fire quickly 
dispersed.  Radiological exposure to the maximally exposed individual may have exceeded the company 
administrative control level, but is not expected to exceed any regulatory exposure limits. 

Laboratory (Reagent) Incident ‐ Pacific Northwest National Laboratory (2013) 

Researchers in the Applied Process and Engineering Laboratory were testing a method to decompose 
ammonia borane (AB) and release hydrogen for use in fuel cells.  They created an experimental apparatus 
that used a slurry of AB powder mixed in silicon oil and tried various methods of pumping the mixture 
through a metal tube (reactor) wrapped with heat tape to release the hydrogen.  Plugging was a problem 
and they took the apparatus apart and cleaned it after each test.  During the third test, at 150C, they 
noticed the syringe pump was skipping‐‐indicating that the tube was plugged.  They stopped the test 
according to operating procedure and noticed a foam‐like substance leaking from a Teflon coupling (circled 
at right).  As the foam bubbled and dripped to the floor of the hood, it was burning with a short, green‐
colored flame.  They shut down power to all heater equipment, put out the flame with a fire extinguisher, 
and called 375‐2400.  Lessons Learned:  When developing standard operating procedures (SOPs) and 
obtaining a chemical process permit (CPP), include planned procedures for emergency response for all 
potential byproducts and, especially any that may be hazardous, despite a low probability of occurrence.  
This should always include pulling the fire alarm before using a fire extinguisher to put out a small fire. 

45
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Laboratory (Reagent) Incident ‐ Argonne National Laboratory East (2014) 

ORPS Report No.: SC‐‐ASO‐ANLE‐ANLECSE‐2014‐0001 

On February 20, 2014 at Argonne National Laboratory East, a worker had finished quenching residual 
material from a reactive material synthesis in an atmosphere‐controlled glovebox. Believing that all the 
reactants were either removed or quenched, the worker moved the vials, pipettes and wipes to a hood to 
be rinsed out and disposed of.  When the worker opened the last vial, he did not notice any reaction 
occurring so he started to rinse out the vial with Isopropyl alcohol.  Upon contact, the isopropyl alcohol 
ignited with the fire traveling up the solvent stream and involving all other ignitables within the hood.  The 
fire set off smoke alarms in the lab, alerting the fire department and evacuating the facility.  Upon 
investigation it was theorized that stearic acid must have somehow not come in contact with the remaining 
reactive material.  One reactive by‐product that was believed to remain was iron diamide, which reacted 
with the Isopropyl alcohol causing enough heat to ignite the combustible materials within the hood.         

Previous Edition (1994) Case studies  

Silane Gas Cabinet Fire 

A 6.1 x 9.1 m (20 x 30 ft) room with concrete block walls was used for distribution of process gases to clean 
room areas.  Silane cylinders were located in 12‐gauge metal gas cabinets.  The ventilation system for the 
cabinets was in the process of being upgraded and automatic sprinklers protected the cabinets. 

The silane cylinder involved was installed about 30 minutes prior to the incident.  Employees in the area 
heard a loud "pop" from the process gas distribution room.  Upon investigation, they found the windows of 
the cabinet broken, the doors open, and fire coming from the cylinder valve.  The sprinkler activated 
properly and confined the fire to the cylinder head. 

The escaping silane was caused by an improper connection of the cylinder to the distribution piping.  There 
was evidence that the connection was cross‐threaded, allowing the leakage.  The flow of silane could not 
be shut off because of damage to the cylinder manifold connections.  The fire continued to burn for about 
8‐1/2 hours until all silane in the cylinder had been consumed. 

Coal Fire at a DOE Site 

In 1992, a DOE site experienced a coal fire initiated by spontaneous ignition. Because of the nature of the 
fire and initial ineffectiveness of the means used to fight it, the fire required more than 28 hours to 
completely extinguish from the time a hot spot was first detected in a coal bunker.  The initial strategy 
involved trying to remove coal from the bunker by feeding it more rapidly to the boiler and by using a drag 
chain to move more of it to the field.  The drag chain failed in 30 minutes, however.  Subsequent efforts to 
control the fire with carbon dioxide applied through inspection ports at the bottom of the bunker and from 
the tripper (switchgear) room high above the bunker were ineffective, and may have worsened the 
situation.  The drag chain emptying coal from the bunker worked intermittently after being repaired, and 
finally stopped.  Boiler plant personnel then began to remove burning coal by hand shovel. 

46
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Twenty‐one hours after the fire was discovered, it had involved a large amount of the bunker.  At one 
point, flames appeared at the tripper room windows, which were approximately 22.86 m (75 ft) above the 
seat of the hot spots.  A strong concern for a steam explosion delayed the application of water, but the 
decision was finally made to use water, which was applied without incident and eventually ended the fire. 

Zirconium Incidents (Smith, 1956) 

Up to May 1955, no serious fires had been encountered during storage of scrap zirconium turnings, chips, 
plates, rods, etc.  Such scrap had been stored (pending contemplated future recovery) in segregated open‐
top bins.  Several days after a heavy rain, a fire of unknown origin took place in one of the bins with flames 
extending 30.48 m (100 ft) into the air.  Shortly afterwards, contents of other (but not necessarily 
adjoining) bins suddenly and intermittently flared up.  Material in all bins soon became involved and 
72,121 kg (159,000 lb) of zirconium were consumed.  The heat was sufficiently intense to crack windows 
and ignite wood located over 45.72 m (150 ft) away.  Particles of burning zirconium were carried over one‐
quarter mile through the air. 

In 1951, some water‐wet scrap zirconium powder in wooden barrels was placed in outside storage pending 
development of scrap‐recovery processes.  During the next several years, a few minor spontaneous fires 
broke out in this material.  In January 1956, the material in several deteriorated wooden barrels was wet 
with water and repackaged in steel drums.  In May 1956, employees working in the area noted that one of 
the steel drums lying on its side contained a black material "similar to carbon dust."  What happened is 
uncertain, but a spontaneous explosion occurred accompanied by streaks of red fire with black smoke 
extending 30.48 m (100 ft) into the air.  A pronounced concussion wave was noted and the sound of the 
blast was heard several miles away.  Two employees were killed; one having been blown 24.38 m (80 ft) 
through the air, and a third lost an arm.  The drum contained zirconium, probably in the form of a fine 
powder.  Using extensive precautions, the remaining drums of scrap zirconium were subsequently burned.  
During this operation, one of the drums exploded. 

Two men died and two others were seriously injured in 1954 in a spontaneous explosion initiated during 
removal of the friction‐top lid from a polythene‐bag‐lined, 3.79 L (1 gal) metal can containing zirconium 
powder 16 percent wet with water.  A ball of flame enveloped the entire area, accompanied by a 
concussion wave. 

A .907 kg (2 lb) sample of carbon‐tetrachloride‐moistened powdered zirconium was placed in a glass flask, 
vacuum applied, and the flask very gently heated with a Bunsen burner.  The zirconium suddenly began to 
heat up and detonated with a blinding flash.  The explosion was attributed to a small amount of water. 

Uranium Incidents (Smith, 1956) 

In January 1955, an attempt was made to roll two 453.6 kg (1,000 lb) uranium slabs into 0.254 mm (0.01 in) 
thick strips.  After initial heating to 621°C1 (1,150°F) in a lithium‐carbonate‐potassium/carbonate salt bath, 
several 30 percent reductions were made by rolling. It was observed that heavy work passes had caused 
overheating.  The strip, then 19.05 mm (3/4 in) thick, was cooled to 648.89 °C (1,200 °F).  The strip again 
excessively heated during the next three reductions and became so ductile on entering the fourth that it 

47
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
pulled into two parts.  The strip at this stage was cherry red, but by the time it had been removed to the 
mill floor it was observed to increase in temperature to a white heat followed by melting and burning. 

In February 1956, a technician was attempting to roll a plate consisting of zirconium‐clad uranium, which, 
in turn, was clad in a low‐carbon‐steel jacket.  During preheating, the furnace temperature control [which 
had been set to 788°C (1,450°F)] failed, allowing the temperature to rise to 982°C (1,800°F). 

During subsequent rolling, molten iron ‐ zirconium eutectic alloy within the steel jacket was forced to one 
end of the strip where it burst into flames as it sprayed out over an area approximately 3.048 m (10 ft) 
wide, 3.048 m (10 ft) high, and 7.62 m (25 ft) long.  One employee was seriously injured. 

In the early program for the large‐scale manufacture of metallic uranium, fine powder was allowed to 
collect under roughly 7.62 m (25 ft) feet of water.  At approximately one‐month intervals, and without 
prior warning, a geyser about 9.14 m (30 ft) high would suddenly develop over the powder and then 
immediately subside. 

A series of cases is known in which pieces of metallic uranium, plutonium, and thorium have displayed 
unusual pyrophoricity, e.g., spontaneously igniting at room temperature.  Spontaneous fires in uranium 
chips are, however, much more common and in one case ignition occurred six months after the chips had 
been placed in storage.  One investigator of spontaneous fires in briquette uranium chips opened a drum 
filled with briquettes that had been in outside storage for several weeks.  After noting that the drum 
contents were normal and at approximately room temperature, he was warned by an operator to stand 
back.  A few seconds later, a flame shot to a height of about 7.62 m (25 ft) and then immediately subsided.  
Upon reinspecting the drum interior, he noted that all of the briquettes were at an incandescent 
temperature. 

A series of incidents have been experienced in which uranium and titanium alloys have displayed explosive 
surface films following acid treatment.  Studies at Argonne National Laboratory showed that such 
explosions could be averted through use of adequate fluoride ion concentrations in nitric acid etching 
baths.  Witnesses have described metal‐surface explosions of this type as involving a brilliant flash of white 
light, accompanied by a sound similar to that of a 22‐caliber rifle shot. 

Thorium Incidents (Smith, 1956) 

For several years scrap thorium powder had been disposed of by burning in successive small amounts.  In 
July 1956, employees were engaged in burning scrap thorium powder that had previously been washed 
with several aqueous solutions and vacuum‐dried 3 days earlier.  Some of the thorium was placed in a 
special hood and ignited without incident.  An employee took a "golf‐ball‐size" piece of thorium from a 
metal pail containing 13.61/18.14 kg (30/40 lbs), replaced the pail lid, and placed the piece on a small 
thorium fire.  An immediate sharp explosion blew the employee 6.096 m (20 ft) across the room.  Almost 
immediately, a second blast involving the thorium in the pail was accompanied by a jet of orange fire and 
big cloud of dust.  A third explosion occurred in a nearby vacuum dryer containing about 3.18 Kg (7 lbs) of 
moist thorium powder.  One employee suffered fatal burns, while three others suffered serious injuries. 

48
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
In preparing an experimental charge for making metallic thorium in a reduction bomb, a mixer was being 
used to blend metallic calcium, dry zinc chloride, and dry thorium fluoride.  After several revolutions of the 
mixer, the operator opened the mixer vent and, noting the dust and gas were escaping, decided to call his 
foreman.  A second operator closed the vent, started the mixer, and soon heard a rumbling noise, followed 
by a sudden burst of flame covering a 45 angle and extending parallel to the floor for 12.19 m (40 ft).  Of 
the eight persons injured by the blaze, two subsequently died.  Reason for initiation of the reduction 
reaction in the blender is uncertain and unprecedented.  It was subsequently found that the calcium used 
was particularly reactive. 

Miscellaneous Incidents (Smith, 1956) 

On June 16, 1954, employees of a high‐energy‐fuel laboratory were sampling 15 drums of "bag fines" 
magnesium powder, which were opened in a special room that had been purged with nitrogen until the 
oxygen content had dropped below 1 percent.  During sampling of the fifth drum, the powder ignited 
suddenly.  The flame shot out from the drum, immediately subsided, and the operators left the room after 
replacing the drum cover.  From an external observation window, the employees noticed a gradual 
darkening of the drum's exterior, moving down to within 50.8 to 101.6 mm (2 to 4 in) of the drum bottom.  
The following day the drum was opened and contained a definite yellow coloration, which was presumed 
due to formation of magnesium nitride. 

A massive block of metallic barium was cut into 19.05 mm (3/4 in) square pieces while submerged in 
kerosene.  During attempts to remove residual kerosene with carbon tetrachloride (an operation that had 
been performed many times before without incident), a violent reaction dispersed glass fragments and 
burning barium over the immediate area.  Similar explosions have also occurred when sodium, uranium, 
and zirconium were treated with carbon tetrachloride. 

Trouble had been experienced in getting a Kroll process reduction of zirconium chloride, with magnesium 
to go to completion.  When the furnace was opened up, a slate grey material was noted on the surface, 
which was thought to consist of zirconium, magnesium, and magnesium chloride.  A sample of this 
material, roughly 6.36 mm (1/4 in) thick and 203.2mm (8 in) square, was removed for test and was totally 
inert when scratched with a file or hit with a hammer.  A piece of the sample melted under an 
oxyacetylene flame but showed no pyrophoric properties.  Samples were then placed in water and a slight 
evolution of gas was noted.  The following day an attempt was made to further wash the samples in 
several changes of water.  While under 127 mm (5 in) of water and without any prior evidence of reaction, 
an explosion occurred that shattered the laboratory bench, threw the technician against the wall, and blew 
out a window 7.62 m (25 ft) away.  Portions of the water‐washed sample blown to the floor ignited and 
"spit" when stepped upon.  Small samples were subsequently tested and found to contain magnesium, 
zirconium, and 1 percent carbon. 

Rocky Flats Plant Fire, 1969 

On May 11, 1969, Rocky Flats Plant experienced the worst accident in plant history, a major fire in the 776‐
777 building, initially caused by pyrophoric plutonium scrap.  One of the costliest industrial fires of all 
time—damages were estimated at between $26 to $50 million dollars—this accident was intensified and 
confounded by a number of operational errors. 
49
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
The fire at 2:27 p.m. Sunday was reportedly caused by spontaneous ignition of a 1.5 kg (3.3 lb) briquette of 
plutonium alloy scrap contained in a metal can.  This scrap was believed to have been oily and coated with 
residual CCl4 (carbon tetrachloride).  Once ignited, the fire spread through several hundred interconnected 
gloveboxes in the two connected buildings. 

The fire started in the west end of the north line, progressed eastward, crossed over to the south line 
through the interconnecting boxes, and spread through the south line.  The fire spread through the 
machining boxes at the east end of 776 and into the inspection boxes in 777.  Damage was extensive.  Both 
Benelex, a combustible neutron shielding material added to the gloveboxes, and the combustible Plexiglas 
glovebox windows contributed to rapid spread of the fire. 

The main fire lasted about four hours, with minor flare‐ups occurring through the next night.  After futile 
attempts to control the fire with conventional procedures, the firemen finally resorted to the unorthodox 
procedure of applying water to bring the fire under control.  This was the first time in history that water 
had been used to fight a plutonium fire.  Despite attendant criticality dangers, the use of water was 
successful in controlling the fire. 

The interiors of the two extremely large, high‐bay buildings were grossly contaminated.  An extensive, 
long‐term cleanup effort was necessary for decontamination.  Limited production was restarted about six 
months later in a temporary production line constructed in an adjacent building. 

As damaging as the fire was, the water use prevented breaching of the outer walls and ceiling of 776 and 
777, thus preventing a major release of plutonium to the environment.  The small amount of plutonium 
released—almost entirely contained on plant site—was about 0.0002 curies.  Slightly contaminated 
external areas were subsequently cleaned up. 

Fortunately, the fire caused no direct deaths.  However, one fireman received significant plutonium lung 
burdens, and other firemen and personnel incurred smaller radiation inhalations and exposures while 
fighting the fire and later cleaning up heavily contaminated areas. 

Immediately prior to the fire, personnel levels were significantly cut with no real decrease in work load or 
production demands.  Strict attention to plutonium chip handling no longer seemed to have been a top 
priority. 

The many lessons learned from this 1969 fire include the following: 

 Plutonium pyrophoricity is unpredictable as to when it may occur. 
 Combustible materials such as Benelex and Plexiglas should be kept to a minimum in process 
buildings. 
 Uncleaned and uncanned briquettes cannot be left unprotected and unattended on off‐shifts. 
 Buildings 776‐777 were essentially one large room with interconnected glovebox trains with 
basically no fire breaks or fire walls.  This setup allowed for rapid, large‐ area spread of fire and 
radioactive contamination. 

These lessons learned from the 1969 fire led to a number of safety improvements including the following 
equipment modifications and procedural revisions prior to the decommissioning of the plant: 

50
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
 A central, computerized alarm system has been installed. 
 A sprinkler/water system has been put in place. 
 Gloveboxes with inert atmospheres, heat detectors, and minimal Benelex and Plexiglas shielding 
are used. 
 Water‐filled double walls have been constructed. 
 Firewater dams on doors are in place. 
 Removal of flammable material from gloveboxes is done regularly. 
 Briquettes are stored in metal containers with tight lids. 
 Containers are placed on metal racks with heat detectors. 
 Canning of briquettes is done in an inert atmosphere or vacuum for unattended (overnight or 
longer) storage. 

   

51
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
BIBLIOGRAPHY
 

AIGA 052/08 Storage and Handling of Silane and Silane Mixtures,  published by Asia Industrial Gases 
Association at: 
www.asiaiga.org/docs/AIGA%20052_08%20Storage%20_%20handling%20of%20silane%20_%20silane%20
mixtures.pdf 

Alnajjar, M. etal., 2011, Methods for the Safe Storage; Handling; and Disposal of Pyrophoric Liquids and 
Solids in the Laboratory, Journal of Chemical Health and Safety, Volume 18, Issue 1, January–February 
2011, Pages 5–10. 

Armstrong, B. and Foster C., 1991, The Spontaneous Heating of Stored Coal, British Coal Corporation, Coal 
Research Establishment, Cheltenham, Gloucestershire, GL52‐4RZ, United Kingdom.
 

Babrauskas, Vytenis, 2003, Ignition Handbook: Principles and Applications to Fire Safety Engineering, Fire
 
Investigation, Risk Management and Forensic Science, Fire Science Publishers.
 

Basic Pyrophoricity, 1992, Revision 1, Rocky Flats Reference Handbook.
 

Bretherick, L., 1990, Handbook of Reactive Chemical Hazards, 7th Edition, Butterworth and Company.
 

Compressed Gas Association, 1990, Handbook of Compressed Gases, 5th Edition, Van Nostrand Reinhold,
 
New York.
 

Cooper, T. D., 1984, Review of Zirconium‐Zircaloy Pyrophoricity, Rockwell International, RHO‐RE‐ST‐31P.
 

Cote, Arthur E., Editor‐in‐Chief, 2008, National Fire Protection Association (NFPA) Fire Protection
 
Handbook, 20th Edition.
 

Dahn, C. James, Explosivity and Pyrophoricity of Metal Powders, Metals Handbook, Ninth Edition, Volume 7,
 
Powder Metallurgy.
 

DOE‐STD‐3013‐2012, Stabilization, Packaging, and Storage of Plutonium‐Bearing Materials (March 2012).
 

DOE‐STD‐3028‐2000, Criteria for Packaging and storing Uranium‐233‐Bearing Materials (July 2000).
 

Drysdale, Dougal, An Introduction to Fire Dynamics, 3rd Edition.
 

Evarts, Ben, 2011 Fires Caused by Spontaneous Combustion or Chemical Reaction, NFPA Fire Analysis &
 
Research Division.
 

FM Global Property Loss Prevention Data Sheets 7‐85 (April 2013), Metals and Alloys.
 

Felt, R. E., 1967, Burning and Extinguishing Characteristics of Plutonium Metal Fires, ISOCHEM Inc., ISO‐
756.
 

Jacobson, M. et al., 1965, Explosibility of Metal Powders, Bureau of Mines, U.S. Department of the Interior.
 

Meyer, E., 1989, Chemistry of Hazardous Materials, Second Edition, Prentice‐Hall.
 

52
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
National Fire Protection Association (NFPA), Fire Protection Guide on Hazardous Materials, 14th Edition,
 
2010, National Fire Protection Association, Quincy, MA.
 

NFPA 30, 2012, Flammable and Combustible Liquids Code.
 

NFPA 55, 2013, Compressed Gases and Cryogenic Fluids Code.
 

NFPA 70, 2014, National Electrical Code.
 

NFPA 318, 2012, Standard for the Protection of Semiconductor Fabrication Facilities.
 

NFPA 400, 2013, Hazardous Materials Code.
 

NFPA 484, 2012, Standard for Combustible Metals.
 

Pyrophoricity, 1991, Rocky Flats Plant Student Guide, Revision 1, PYR‐01 SG.
 

Sax, N. I., 1979, Dangerous Properties of Industrial Materials, Fifth Edition, Van Nostrand Reinhold
 
Company.
 

Smith, R. B., 1956, Pyrophoricity—A Technical Mystery Under Vigorous Attack, Nucleonics Magazine, 
December. 

Society of Fire Protection Engineering Handbook, 4th edition.
 

Stakebake, J. L., 1971, The Storage Behavior of Plutonium Metal, Alloys, and Oxide, Journal of Nuclear
 
Materials 38, pp. 241‐259.
 

Stakebake, J. L., 1992, Plutonium Pyrophoricity, Rocky Flats Plant, RFP‐4517.
 

Vendor information: For air sensitive reagents see:
  

http://www.sigmaaldrich.com/content/dam/sigma‐aldrich/docs/Aldrich/Bulletin/al_techbull_al134.pdf
  

For pyrophoric reagents see: 

http://www.sigmaaldrich.com/content/dam/sigma‐aldrich/docs/Aldrich/Bulletin/al_techbull_al164.pdf  

Video: https://www.youtube.com/watch?v=21iC4YEgOAs  

   

53
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Appendix A ‐ Materials Subject to Spontaneous Heating
Materials subject to spontaneous heating (From NFPA Fire Protection Handbook, 20th Edition). 
 

Tendency of  Usual shipping 
Spontaneous  container or storage  Precautions against spontaneous 
Name  Heating  method  heating  Remarks 
Alfalfa meal  High  Bags, bulk  Avoid moisture extremes;  tight  Many fires attributed to 
cars for transportation are  spontaneous heating probably 
essential.  caused by sparks, burning 
embers, or particles of hot 
metal picked up by the meal 
during processing.    Test fires 
caused in this manner have 
smoldered for 72 hours before 
becoming noticeable. 
Burlap bags "used"  Possible  Bales  Keep cool and dry.  Tendency to heat is dependent 
on previous use of bags.    If oily
would be dangerous. 
Castor oil  Very slight  Metal barrels, metal  Avoid contact of leakage from  Possible heating of saturated 
cans in wooden boxes  containers with rags, cotton, or  fabrics in badly ventilated piles.
other fibrous combustible 
materials. 
Charcoal  High  Bulk, bags  Keep dry; supply ventilation.  Hardwood charcoal must be 
carefully prepared and aged.  
Avoid wetting and subsequent 
drying. 
Coal, bituminous  Moderate  Bulk  Store in small piles; avoid high  Tendency to heat depends 
temperatures.  upon origin and nature of coals.
Highly volatile coals are 
particularly  liable to heat. 
Cocoa bean shell  Moderate  Burlap bags, bulk  Extreme caution must be  This material is very 
tankage  observed to maintain safe  hygroscopic and is liable to 
moisture limits.  heating if moisture content is 
excessive.    Precaution should 
be observed to maintain dry 
storage, etc. 
Coconut oil  Very slight  Drums, cans, glass  Avoid contact of leakage from  Only dangerous if fabrics, etc., 
containers  with rags, cotton, or  are impregnated. 
other fibrous combustible 
materials. 
Cod liver oil  High  Drums, cans, glass  Avoid contact of leakage from  Impregnated organic materials 
containers  with rags, cotton, or  are extremely dangerous. 
other fibrous combustible 
materials. 
Colors in oil  High  Drums, cans, glass  Avoid contact of leakage from  May be very dangerous if 
containers with rags, cotton, or  fabrics, etc., are impregnated. 
other fibrous combustible 
materials. 
Copra  Slight  Bulk  Keep cool and dry.  Heating possible if wet and hot. 

54
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Tendency of  Usual shipping 
Spontaneous  container or storage  Precautions against spontaneous 
Name  Heating  method  heating  Remarks 
Corn‐meal feeds  High  Burlap bags, paper  Material should be processed  Usually contains an appreciable 
bags, bulk  carefully to maintain safe  quantity of oil, which has rather 
moisture content and to cure  severe tendency to heat. 
before storage. 
Corn oil  Moderate  Barrels, tank cars  Avoid contact of leakage from  Dangerous heating of meals, 
containers  with rags, cotton, or  etc., unlikely unless stored in 
other fibrous combustible  large piles while hot. 
materials. 
Cottonseed  Low  Bags, bulk  Keep cool and dry.  Heating possible if piled wet 
and hot. 
Cottonseed oil  Moderate  Barrels, tank cars  Avoid contact of leakage from  May cause heating of saturated 
containers  with rags, cotton, or  material in badly ventilated 
other fibrous combustible  piles. 
materials. 
Distillers' dried  Moderate
  Bulk  Maintain moisture 7 to 10%; cool  Very dangerous if moisture 
grains with oil
  below 100°F (38°C) before  content is 5% or lower. 
content (Brewers'
  storage. 
grains)
 
‐no oil content  Moderate
  Bulk  Maintain moisture 7 to 10%; cool  Very dangerous  if moisture 
below 100°F (38°C) before  content is 5% or lower. 
storage. 
Feeds, various  Moderate
  Bulk, bags  Avoid extremely low or high  Ground feeds must be carefully 
moisture content.  processed.    Avoid loading or 
storing unless cooled. 
Fertilizers organic,  Moderate
  Bulk, bags  Avoid extremely low or high  Organic fertilizers containing 
inorganic,
  moisture content.  nitrates must be carefully 
combination  of
  prepared to avoid combinations
both mixed
  that might initiate heating. 
Fertilizers  Moderate
  Bulk, bags  Avoid free acid in preparation.  Ensure ventilation in curing 
synthetic,
  process by small piles or 
containing nitrates
  artificial drafts.    If stored or 
and organic matter
  loaded in bags, provide 
ventilation space between bags.
Fish meal  High
  Bags, bulk  Keep moisture 6 to 12%  Avoid  Dangerous if over dried or 
exposure to heat.  packaged over 100°F (38°C). 
Fish oil  High
  Barrels, drums, tank  Avoid contact of leakage from  Impregnated  porous or fibrous 
cars  containers with rags, cotton, or  materials are extremely 
other fibrous combustible  dangerous.  Tendency of 
materials.  various fish oils to heat varies 
with origin. 
Fish scrap  High
  Bulk, bags  Avoid moisture extremes.  Scrap loaded or stored before 
cooling is extremely liable to 
heat. 

55
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Tendency of  Usual shipping 
Spontaneous  container or storage  Precautions against spontaneous 
Name  Heating  method  heating  Remarks 
Foam rubber in  Moderate    Where possible remove foam  Foam rubber may continue to 
consumer products  rubber pads, etc., from garments  heat spontaneously  after being 
to be dried in dryers or over  subjected to forced drying as in 
heaters.  If garments containing  home or commercial dryers and
foam rubber parts have been  after contact with heating pads 
artificially dried, they should be  and other heat sources.   
thoroughly cooled before being  Natural drying does not cause 
piled, bundled, or put away.  Keep spontaneous heating. 
heating pads, hair dryers, other 
heat sources from contact with 
foam rubber pillows, etc. 
Grain (various  Very slight  Bulk, bags  Avoid moisture extremes.  Ground grains may heat if wet 
kinds)   and warm. 
Hay  Moderate  Bulk, bales  Keep dry and cool.  Wet or improperly cured hay is 
almost certain to heat in hot 
weather.  Baled hay seldom 
heats dangerously. 
Hides  Very slight  Bales  Keep dry and cool.  Bacteria in untreated hides may 
initiate heating. 
Iron pyrites  Moderate  Bulk  Avoid large piles; keep dry and  Moisture accelerates oxidation 
cool.  of finely divided pyrites. 
Istle  Very slight  Bulk, bales  Keep cool and dry.  Heating possible in wet 
material; unlikely under 
ordinary conditions.  Partially 
burned or charred fiber is 
dangerous. 
Jute  Very slight  Bulk  Keep cool and dry.  Avoid storing or loading in hot 
wet piles.    Partially burned or 
charred material is dangerous. 
Lamp black  Very slight  Wooden cases  Keep cool and dry.  Fires most likely to result from 
sparks or included embers, etc., 
rather than spontaneous 
heating. 
Lanolin  Negligible  Glass, cans, metal  Avoid contact of leakage from  Heating possible on 
drums, barrels  containers  with rags, cotton, or  contaminated fibrous matter. 
other fibrous combustible 
materials. 
Lard oil  Slight  Wooden barrels  Avoid contact of leakage from  Dangerous on fibrous 
containers with rags, cotton, or  combustible substances. 
other fibrous combustible 
materials. 
Lime, unslaked  Moderate  Paper bags, wooden  Keep dry; avoid hot loading.  Wetted lime may heat 
(calcium oxide,  barrels, bulk  sufficiently to ignite wood 
pebble lime,  containers, etc. 
Quicklime) 
Linseed  Very slight  Bulk  Keep cool and dry.  Tendency to heat dependent on 
moisture and oil content. 

56
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Tendency of  Usual shipping 
Spontaneous  container or storage  Precautions against spontaneous 
Name  Heating  method  heating  Remarks 
Linseed oil  High   Tank cars, drums, cans, Avoid contact of leakage from   Rags or fabrics impregnated 
glass  containers  with rags, cotton, or  with this oil are extremely 
other fibrous combustible  dangerous.  Avoid piles, etc. 
materials.  Store in closed containers, 
preferably metal. 
Manure  Moderate   Bulk  Avoid extremes of low or high  Avoid storing or loading 
moisture contents;  ventilate the  uncooled manures. 
piles 
Menhaden oil  Moderate to high   Barrels, drums, tank  Avoid contact of leakage from  Dangerous on fibrous product. 
cars  containers with rags, cotton, or 
other fibrous combustible 
materials 
2
Metal powders   Moderate   Drums, etc.  Keep in closed containers.  Moisture accelerates oxidation 
of most metal powders. 
2
Metal turnings   Practically none   Bulk  Not likely to heat spontaneously. Avoid exposure to sparks. 
Mineral wool  None   Pasteboard boxes,  Noncombustible; if loaded hot  This material is mentioned in 
paper bags  may ignite containers and other  this table only because of 
combustible surroundings.  general impression that it 
heats spontaneously. 
Mustard oil, black  Low   Barrels  Avoid contact of leakage from  Avoid contamination of fibrous 
containers with rags, cotton, or  combustible materials. 
other fibrous combustible 
materials 
Oiled clothing  High   Fiber boxes  Dry thoroughly before packaging.  Dangerous if material is stored 
in piles without ventilation.  
Oiled fabrics  High   Rolls  Keep ventilated; dry thoroughly  Improperly dried fabrics 
before packing  extremely dangerous.  
Comparatively tight rolls are 
safe. 
Oiled rags  High   Bales  Avoid storing in bulk in open.  Dangerous if wet with drying 
oil. 
Oiled silk  High   Fiber boxes, rolls  Supply sufficient ventilation.  Improperly dried material is 
dangerous in form of piece 
goods.  Rolls relatively safe. 
Oleic acid  Very slight   Glass bottles, wooden  Avoid contact of leakage from  Impregnated fibrous materials 
barrels  containers with rags, cotton, or  may heat unless ventilated. 
other fibrous combustible 
materials. 
Oleo oil  Very slight   Wooden barrels  Avoid contact of leakage from  May heat on impregnated 
containers with rags, cotton, or  fibrous combustible matter. 
other fibrous combustible 
materials. 

                                                            
2
Refers  to iron,  steel,  brass,  aluminum  and  other  common  metals.  Metals  known  to heat  spontaneously  are 
covered  in a later  section. 

57
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Tendency of  Usual shipping 
Spontaneous  container or storage  Precautions against spontaneous 
Name  Heating  method  heating  Remarks 
Olive oil  Moderate to low  Tank, drums, cans,  Avoid contact of leakage from  Impregnated  fibrous materials 
glass  containers  with rags, cotton, or  may heat unless ventilated.   
other fibrous combustible  Tendency varies with origin of 
materials.  oil. 
Paint containing  Moderate  Drums, cans, glass  Avoid contact of leakage from  Fabrics, rags, etc., impregnated 
drying oil  containers  with rags, cotton, or  with paints that contain drying 
other fibrous combustible  oils and driers are extremely 
materials.  dangerous. 
Store in closed containers, 
preferably metal. 
Paint scrapings  Moderate  Barrels, drums  Avoid large unventilated piles.  Tendency to heat depends on 
state of dryness of the 
scrapings. 
Palm oil  Low  Wooden barrels  Avoid contact of leakage from  Impregnated fibrous materials 
containers  with rags, cotton, or  may heat unless ventilated.   
other fibrous combustible  Tendency varies with origin of 
materials.  oil. 
Peanut oil  Low  Wooden barrels, tin  Avoid contact of leakage from  Impregnated  fibrous materials 
cans  containers with rags, cotton, or  may heat unless ventilated.   
other fibrous combustible  Tendency varies with origin of 
materials.  oil. 
Peanuts, "Red  High  Paper bags, cans, fiber  Avoid badly ventilated storage.  This is the part of peanut 
Skin"  board boxes, burlap  between outer shell and 
bags  peanut itself.    Provide well‐
ventilated storage. 
Peanuts, shelled  Very slight or  Paper bags, cans, fiber  Keep cool and dry.  Avoid contamination  of rags, 
board boxes, burlap  etc., with oil. 
Negligible 
bags 
Perilla oil  Moderate to high  Tin cans, barrels  Avoid contact of leakage from  Impregnated fibrous materials 
containers with rags, cotton, or  may heat unless ventilated.   
other fibrous combustible  Tendency varies with origin of 
materials.  oil. 
Pine oil  Moderate  Galls, drums  Avoid contact of leakage from  Impregnated  fibrous materials 
containers  with rags, cotton, or  may heat unless ventilated.   
other fibrous combustible  Tendency varies with origin of 
materials.  oil. 
Powdered eggs  Very slight  Wooden barrels  Avoid conditions that promote  Possible heating of decaying 
bacterial growth; inhibit against  powder in storage. 
decay; keep cool. 
Powdered milk  Very slight  Wooden and fiber  Avoid conditions that promote  Possible heating by decay or 
boxes, metal cans  bacterial growth; inhibit against  fermentation. 
decay; keep cool. 
Rags  Variable  Bales  Avoid contamination with drying  Tendency depends on previous 
oils; avoid charring;  keep cool  use of rags.    Partially burned 
and dry.  or charred rags are dangerous.
Red oil  Moderate  Glass bottles, wooden  Avoid contact of leakage from  Impregnated porous or fibrous 
barrels  containers  with rags, cotton, or  materials are extremely 
other fibrous combustible  dangerous.  Tendency varies 
materials.  with origin of oil. 

58
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Tendency of  Usual shipping 
Spontaneous  container or storage  Precautions against spontaneous 
Name  Heating  method  heating  Remarks 
Roofing felts and  Moderate  Rolls, bales, crates   Avoid overdrying the material;  Felts, etc., should have 
papers  controlled moisture content.   
supply ventilation. 
Packaging  or rolling uncooled 
felts is dangerous. 
Sawdust  Possible  Bulk   Avoid contact with drying oils;  Partially burned or charred 
sawdust may be dangerous. 
avoid hot, humid storage. 
Scrap film (nitrate)  Very slight  Drums and lined boxes Film must be properly stabilized  Nitrocellulose film ignites at 
against decomposition.  low temperature.   External 
ignition more likely than 
spontaneous heating.  Avoid 
exposure to sparks, etc. 
Scrap leather  Very slight  Bales, bulk   Avoid contamination with drying  Oil‐treated leather scraps may 
oils.  heat. 
Scrap rubber or  Moderate  Bulk, drums   Buffings of high rubber content  Sheets, slabs, etc., are 
buffings  should be shipped and stored in  comparatively safe unless 
tight containers.  loaded or stored before cooling 
thoroughly. 
Sisal  Very slight  Bulk bales   Keep cool and dry.  Partially burned or charred 
material is particularly  liable to 
ignite spontaneously. 
Soybean oil  Moderate  Tin cans, barrels, tank  Avoid contact with rags, cotton,  Impregnated  fibrous materials 
cars  or fibrous materials.  may heat unless well 
ventilated. 
Sperm oil—see         
whale oil 
Tankage  Variable  Bulk   Avoid extremes of moisture  Very dry or moist tankages 
contents; avoid loading or storing often heat.    Tendency more 
while hot.  pronounced if loaded or stored 
before cooling. 
Tung nut meals  High  Paper bags, bulk   Material must be very carefully  These meals contain residual oil 
processed and cooled thoroughly  which has high tendency to 
before storage.  heat.  Material also susceptible 
to heating if over‐dried. 
Tung oil  Moderate  Tin cans, barrels, tank   Avoid contact of leakage from  Impregnated fibrous materials 
cars   containers  with rags, cotton, or  may heat unless ventilated.   
other fibrous combustible  Tendency varies with origin of 
materials.  oil. 
Turpentine  Low  Tin, glass, barrels   Avoid contact of leakage from  Has some tendency to heat but 
containers  with rags, cotton, or  less so than the drying oils.   
other fibrous combustible  Chemically active with chlorine 
materials.  compounds and may cause fire.
Varnished fabrics  High  Boxes   Process carefully; keep cool and  Thoroughly dried varnished 
ventilated.  fabrics are comparatively  safe. 
Wallboard  Slight  Wrapped bundles,  Maintain safe moisture content;  This material is entirely safe 
pasteboard boxes  from spontaneous  heating if 
cool thoroughly  before storage. 
properly processed. 
Waste paper  Moderate  Bales   Keep dry and ventilated.  Wet paper occasionally heats in 
storage in warm locations. 

59
 
DOE‐HDBK‐1081‐2014    Primer on Spontaneous 
Heating and Pyrophoricity 
 
Tendency of  Usual shipping 
Spontaneous  container or storage  Precautions against spontaneous 
Name  Heating  method  heating  Remarks 
Whale oil  Moderate  Barrels and tank cars  Avoid contact of leakage from  Impregnated fibrous materials 
containers  with rags, cotton, or  may heat unless ventilated.   
other fibrous combustible  Tendency varies with origin of 
materials.  oil. 
Wool wastes  Moderate  Bulk, bales, etc.  Keep cool and ventilated or store  Most wool wastes contain oil, 
in closed containers;  avoid high  etc., from the weaving and 
moisture.  spinning and are liable to heat 
in storage.    Wet wool wastes 
are very liable to spontaneous 
heating and possible ignition. 

60
 
DOE‐HDBK‐1081‐2014      Primer on Spontaneous 
    Heating and Pyrophoricity 
 
Appendix B – Pyrophoric and Combustible Elements and Compounds Commonly Found Within the DOE

Complex

 

Solubility
Flash
Specific Melting Boiling LFL/ UFL Autoignition Preferred Extinguishing
Element/Compound Formula Point State
Gravity Point (°C) Point (°C) Cold H20 (°C) Temp (°C) Agent/others in hierarchy
(°C)

Active Raney Metal  Preferred: Water spray, alcohol‐
Catalyst   AlNi  8.94  14554  27304  insoluble4  ND  ND  874  l  resistant foam, CO2 or dry chemical4 
(Raney‐Nickel)   
Preferred: NaCl based agent, dry flux, 
dry sand NaCl, argon, or allow to burn 
itself out by forming a ring around 
the fire with an approved 
extinguishing agent 
 
Aluminum  Al  2.7  660  245210  insoluble  ND  ND  ND  s  Other Effective Agents: Carbon 
microspheres or dry soda ash 
 
DO NOT USE: WATER, FOAM, 
GRAPHITE BASED AGENTS, LiCl, CO2, 
NITROGEN, HALOGENATED AGENTS, 
OR HYDROCARBON CLEAN AGENTS 
Preferred: Class D or other metal 
extinguishing agent 
Aluminum Hydride  AlH3  1.477  150   ND  Reactive  ND  ND  ND  s 
 
DO NOT USE: WATER 
Preferred: Gentle surface application 
of Class D extinguishing agent or dry, 
inert granular material (e.g. sand) to 
cover and ring the burning powder. 
Aluminum Silicon 
AlSi  1.13  5773  ND  insoluble3  40 mg/L3  ND  6503  s  Avoid mixing the extinguishing agent 
Powder 
with the burning powder. Do not 
disturb the powder until completely 
cool. If possible, isolate burning 
powder 

61
 
DOE‐HDBK‐1081‐2014      Primer on Spontaneous 
    Heating and Pyrophoricity 
 
Solubility
Flash
Specific Melting Boiling LFL/ UFL Autoignition Preferred Extinguishing
Element/Compound Formula Point State
Gravity Point (°C) Point (°C) Cold H20 (°C) Temp (°C) Agent/others in hierarchy
(°C)

DO NOT USE: WATER, FOAM, 
HALOGENATED AGENTS, OR ABC DRY 
CHEMICAL EXTINGUISHERS3 

Preferred: Stop the flow of gas 
 
20cc/  
Arsine  AsH3  2.699 1169 629  4.5/789 629  2859  g  Other Effective Agents: CO2 
100cc H209   
 ‐ NO NOT USE: WATER 
 ‐ Preferred: dry chemical/dolomite 
 ‐
(powdered limestone) or NaCl 
 
Barium, Finely Divided  Ba  3.59  72510  114010  Reactive9  ND  ND  ND  s 
DO NOT USE: WATER, FOAM, CO2, 
HALOGENATED AGENTS, OR 
HALOGENATED AGENTS9 
Preferred: NaCl based agent, dry flux, 
dry sand, NaCl, argon, or allow to 
burn itself out 
 
Other Effective Agents: Carbon 
Microspheres, dry soda ash, or boron 
decompose
Calcium  Ca  1.55  82410  144010  ND  ND  ND  s  triflouride 
s   
DO NOT USE: WATER, FOAM, 
GRAPHITE BASED AGENTS, COPPER 
POWDER, LiCl, CO2, NITROGEN, 
HALOGENATED AGENTS, OR 
HYDROCARBON CLEAN AGENTS 
Preferred: Class D or other metal 
decompose extinguishing agent 
Cerium (powder)  Ce  6.67  795  3257  ND  ND  ND  s 
s   
DO NOT USE: WATER 
1 1 1 1
Diborane  B2H6  0.21 156 92.5   Insoluble   0.9/98 148.15  51.85  g  Preferred: Stop the flow of gas 

 ‐
 ‐  ‐
62
 
DOE‐HDBK‐1081‐2014      Primer on Spontaneous 
    Heating and Pyrophoricity 
 
Solubility
Flash
Specific Melting Boiling LFL/ UFL Autoignition Preferred Extinguishing
Element/Compound Formula Point State
Gravity Point (°C) Point (°C) Cold H20 (°C) Temp (°C) Agent/others in hierarchy
(°C)

Other Effective Agents: WATER 
 
DO NOT USE: HALOGENATED AGENTS 
Preferred: NaCl based agent, argon, 
or helium. 
 
9 10 10 9 Other Effective Agents: Allow to burn 
Hafnium  Hf  13.31   2223   5399   insoluble   ND  ND  ND  s 
itself out 
 
DO NOT USE: WATER, FOAM, CO2, 
OR HALOGENATED AGENTS 
Preferred: SMALL FIRE: Use DRY 
chemical powder. LARGE FIRE: Use 
1.011 to 
Hydrazine  N2H4  1.4  113.5  infinity  ND  381  231  l  water spray, fog or foam. 
1.4 
 
DO NOT USE: WATER JET 
Preferred: SMALL FIRE: Use dry 
chemical powder. LARGE FIRE: 
Carefully use water spray, fog or 
foam. 
 
Other Effective Agents: Carbon 
microspheres, NaCl based agents, dry 
Iron  Fe  7.86  1535  3000  insoluble  ND  ND  ND  s 
sand, argon, or nitrogen 
 
DO NOT USE: WATER JET, GRAPHITE 
BASED AGENTS, COPPER POWDER, 
DRY FLUX, LiCl, DRY SODA ASH, NaCl, 
CO2, HALOGENATED AGENTS, OR 
HYDROCARBON CLEAN AGENT.  
Preferred: Graphite based agent or 
copper powder 
decompose
Lithium  Li  0.53  186  133610  ND  ND  ND  s   

Other Effective Agents: Carbon 
microspheres, dry flux, dry sand, LiCl, 

63
 
DOE‐HDBK‐1081‐2014      Primer on Spontaneous 
    Heating and Pyrophoricity 
 
Solubility
Flash
Specific Melting Boiling LFL/ UFL Autoignition Preferred Extinguishing
Element/Compound Formula Point State
Gravity Point (°C) Point (°C) Cold H20 (°C) Temp (°C) Agent/others in hierarchy
(°C)

dry soda ash, NaCl, argon, or helium. 
(AFF Foam has been shown to be 
effective if used in the incipient 
stage)  
 
DO NOT USE: WATER, CO2, NaCl 
BASED AGENTS, NITROGEN, 
HALOGENATED AGENTS, OR 
HYDROCARBON CLEAN AGENTS 
Preferred: NaCl based agent, dry flux, 
dry sand, NaCl, argon, or allow to 
burn itself out. 
 
Other Effective Agents: Carbon 
10 1 Microspheres, graphite based agents, 
Magnesium   Mg  1.74  650   1110  insoluble  ND  ND  473   s 
dry soda ash, or boron triflouride 
 
DO NOT USE: WATER, FOAM, 
COPPER POWDER, LiCl, CO2, 
NITROGEN, HALOGENATED AGENTS, 
OR HYDROCARBON CLEAN AGENTS 
Neodymium Iron 
NdFeB  7.4  1832  ND  insoluble  ND  ND  ND  s  Preferred: Dry chemicals or dry sand 
Boron Alloy Powder 
Preferred: Dry sand, dry dolomite, or 
dry graphite powder or other dry 
chemical extinguishing agent 
Nickel‐Aluminum 
Ni‐Al  7.47  ND  13507  insoluble7  ND  ND  7607  s  formulated for metal fires 
Alloy, Powder 
 
DO NOT USE: WATER OR 
HALOGENATED AGENTS 
Preferred: Stop the flow of gas 
26cc/ 
Phosphine  Ph3  0.75 132.5 85  1/98  ND  1001  g   
100cc H20 
DO NOT USE: HALOGENATED AGENTS 
Preferred: Foam, water, wet sand or 
White Phosphorus  P4  1.836 ‐  446   ‐ ND  soluble6  ND  ND  306  s  earth, argon, or helium 
 

64
 
DOE‐HDBK‐1081‐2014      Primer on Spontaneous 
    Heating and Pyrophoricity 
 
Solubility
Flash
Specific Melting Boiling LFL/ UFL Autoignition Preferred Extinguishing
Element/Compound Formula Point State
Gravity Point (°C) Point (°C) Cold H20 (°C) Temp (°C) Agent/others in hierarchy
(°C)

DO NOT USE: ALKALINE BASED 
AGENTS6 
Preferred: MgO11 
 
Other Effective Agents: Dry sand, 
graphite powder, NaCl based agent, 
PuO2, argon, water can be used if 
Plutonium  Pu  19.86  640  331510  insoluble  ND  ND  Self‐Heating  s  adequate ventilation is present for 
hydrogen production and there is no 
criticality concern11 
 
DO NOT USE: HALOGENATED 
AGENTS11 
Preferred: NaCl based agent 
 
Potassium  K  0.86  6210  760  reactive  ND  ND  ND  s  DO NOT USE: WATER, FOAM, CO2, 
HALOGENATED AGENTS, OR 
HYDROCARBON CLEAN AGENTS 2 
Preferred: Dry chemical, Class D 
Praseodymium  decompose extinguisher 
Pr  6.778  9358  31308  ND  ND  ND  s 
(Powder)  s8   
DO NOT USE: WATER8 
Preferred: Class D or other metal 
extinguishing agent 
Rubidium  Rb  1.53  38.5  700  insoluble  ND  ND  Self‐Heating  s 
 
DO NOT USE: WATER, FOAM, OR CO2 
Preferred: Stop the flow of gas 
Silane  SiH4  0.68 185 112  insoluble  0.8/98  ND  Any1  g   
DO NOT USE: HALOGENATED AGENTS 
Preferred: NaCl based agent, graphite 
 ‐  ‐ based agent, copper powder, argon, 
decompose
10 nitrogen, Class D or other metal 
Sodium  Na  0.97  98   880  s, forms  ND  ND  ND  s 
extinguishing agent 
NaOH 
 
Other Effective Agents: include 

65
 
DOE‐HDBK‐1081‐2014      Primer on Spontaneous 
    Heating and Pyrophoricity 
 
Solubility
Flash
Specific Melting Boiling LFL/ UFL Autoignition Preferred Extinguishing
Element/Compound Formula Point State
Gravity Point (°C) Point (°C) Cold H20 (°C) Temp (°C) Agent/others in hierarchy
(°C)

carbon microspheres, dry sand, dry 
soda ash, dry LiCl, or dry NaCl 
 
DO NOT USE: WATER, FOAM, CO2, 
HALOGENATED AGENTS, OR 
HYDROCARBON CLEAN AGENTS2 
Preferred: NaCl based agent, graphite 
based agent, copper powder, argon, 
nitrogen, Class D or other metal 
extinguishing agent 
 
Other Effective Agents: Include 
Sodium‐Potassium  NaK  0.86 12.6  785  Reactive  ND  ND  120  l 
carbon microspheres, dry sand, dry 
soda ash, dry LiCl, or dry NaCl 
 ‐  
DO NOT USE: WATER, FOAM, CO2, 
HALOGENATED AGENTS, OR 
HYDROCARBON CLEAN AGENTS 
Preferred: NaCl based agent, dry flux, 
dry sand, NaCl, argon, or allow to 
burn itself out 
 
Other Effective Agents: Carbon 
decompose Microspheres, dry soda ash, or boron 
Strontium  Sr  2.6  800  1150  s into  ND  ND  ND  s  triflouride 
Sr(OH)2   
DO NOT USE: WATER, FOAM, 
GRAPHITE BASED AGENTS, COPPER 
POWDER, LiCl, CO2, NITROGEN, 
HALOGENATED AGENTS, OR 
HYDROCARBON CLEAN AGENTS 
Preferred: NaCl based agent, dry 
MgO, or dry sand 
Thorium  Th  11.2  1845  450010  insoluble  ND  ND  ND  s   
Other Effective Agents: Water can be 
used if adequate ventilation is 

66
 
DOE‐HDBK‐1081‐2014      Primer on Spontaneous 
    Heating and Pyrophoricity 
 
Solubility
Flash
Specific Melting Boiling LFL/ UFL Autoignition Preferred Extinguishing
Element/Compound Formula Point State
Gravity Point (°C) Point (°C) Cold H20 (°C) Temp (°C) Agent/others in hierarchy
(°C)

present for hydrogen production and 
there is no criticality concern2 

Preferred: NaCl based agent, dry 
sand, NaCl, LiCl, argon, or allow to 
burn itself out 
 
Other Effective Agents: Carbon 
Microspheres, graphite, or dry soda 
1200 (Solid)/ 
Titanium  Ti  4.5  172710  326010  insoluble  ND  ND  s  ash 
250 (Powder)1   
DO NOT USE: WATER, FOAM, 
GRAPHITE BASED AGENTS, DRY FLUX, 
COPPER POWDER, CO2, NITROGEN, 
HALOGENATED AGENTS, OR 
HYDROCARBON CLEAN AGENTS 
Preferred: MgO 
 
Other Effective Agents: Dry sand, 
graphite powder, NaCl based agent, 
PuO2, argon, water can be used if 
Uranium  U  18.95  113210  381510  insoluble  ND  ND  100  s  adequate ventilation is present for 
hydrogen production and there is no 
criticality concern. 
 
DO NOT USE: HALOGENATED 
AGENTS2 
Preferred: NaCl based agent, dry flux, 
dry sand, NaCl, argon, or allow to 
burn itself out 
 
Zinc  Zn  7.14  419  907  insoluble  ND  ND  Self‐Heating  s  Other Effective Agents: Carbon 
Microspheres, dry soda ash, or boron 
triflouride 
 
DO NOT USE: WATER, FOAM, 

67
 
DOE‐HDBK‐1081‐2014      Primer on Spontaneous 
    Heating and Pyrophoricity 
 
Solubility
Flash
Specific Melting Boiling LFL/ UFL Autoignition Preferred Extinguishing
Element/Compound Formula Point State
Gravity Point (°C) Point (°C) Cold H20 (°C) Temp (°C) Agent/others in hierarchy
(°C)

GRAPHITE BASED AGENTS, COPPER 
POWDER, LiCl, CO2, NITROGEN, 
HALOGENATED AGENTS, OR 
HYDROCARBON CLEAN AGENTS 
Preferred: NaCl based agent, dry 
sand, NaCl, LiCl, argon, helium, or 
allow to burn itself out 
 
Other Effective Agents: Carbon 
10 10 Microspheres or dry soda ash 
Zirconium  Zr  6.4  1830   3577   insoluble  ND  ND  Self‐Heating  s   
DO NOT USE: WATER, FOAM, 
GRAPHITE BASED AGENTS, DRY FLUX, 
COPPER POWDER, CO2, NITROGEN, 
HALOGENATED AGENTS, OR 
HYDROCARBON CLEAN AGENTS 
ND stands for No Data 
*  The above table contains elements and compounds most commonly found within the DOE Complex and should not be considered an unabridged list. For 
additional materials/information, please refer to the most current edition of NFPA 484 and the applicable Safety Data Sheet.  
**  Unless otherwise noted, the above material properties are from Perry’s Chemical Engineers Handbook 8th Ed. 
 
1
 The U.S. National Library of Medicine, WISER (2014) 
2
 The Los Alamos National Laboratory Fire Department Training Manual, 2013 
3
 ALCOA Inc., MSDS ID# 126, Aluminum‐Silicon, 2007 
4
 SIGMA‐ALDRICH, MSDS for Raney‐Nickle, 2013 
5
 ESPI Metals, MSDS for Cerium, 2005 
6
 OXY Glenn Springs Holding, Inc., MSDS ID# M7588, White Phosphorus, 2008 
7
 AMETEK Specialty Metal Products Division, MSDS ID# 82, Nickle Aluminum Alloy Powder, 2006 
8
 ESPI Metals, MSDS for Praseodymium, 2005 
9
 HMEx Assistant V6.2.0 
10
 National Fire Protection Association, NFPA 484 (2015) 
11
 Burning and Extinguishing Characteristics of Plutonium Metal Fires, R.E. Felt, 1967 

68
 

You might also like