TECHNICAL BRIEF: North America 60Hz

Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable

Overview
This technical brief presents voltage rise guidelines for dedicated PV branch circuits and methods for
calculating the AC line voltage rise when using the Enphase IQ Microinverters™ and the Enphase Q
Cable™.
Applying proper voltage rise calculations in your system design helps prevent nuisance voltage out-of-range
trip issues due to high line voltage conditions. Less resistance in conductors also results in less power loss,
less heat at the terminals, and improves performance of the PV system.
When designing circuits for electrical loads, these calculations are commonly called voltage drop (VDrop).
Since PV systems with inverters generate electricity instead of consuming it, voltage rises at the AC
terminals of each inverter. Therefore, this brief refers to these calculations as voltage rise (VRise).

Recommendations
To minimize voltage rise, Enphase recommends that you apply these guidelines when planning your system:
• The total VRise in the AC wiring should stay below 2% in all wire sections from the point of common
coupling (PCC) to the last microinverter on each branch or sub-branch circuit (as described in
“Voltage Rise by Wire Section” on page 3). A good practice is to maintain less than 1% VRise in the
Q Cable.
• Center-feed the branch circuit to minimize voltage rise in a fully-populated branch. Since the VRise is
nonlinear, reducing the number of microinverters on a Q Cable from the junction box to the last
inverter by center feeding and creating sub-branch circuits greatly reduces the voltage measured at
the last microinverter in each sub-branch. To center-feed a branch, divide the circuit into two sub-
branch circuits protected by a single overcurrent protection device (OCPD). Find out more in
“Advantages of Center-Feeding the AC Branch Circuits” on page 6.
• Use the correct wire size in each wire section. Using undersized conductors can result in nuisance
tripping of the microinverter anti-islanding function when an AC voltage out-of-range condition
occurs. “What Contributes to Voltage Rise?” on page 2 provides more information.
• Use the calculation methods in “Calculating Total Voltage Rise” on page 7 to determine voltage rise
values for your project.

Background
The IEEE 1547 standard requires that grid-tied or utility-interactive inverters cease power production if
voltage measured at the inverter terminal exceeds +10% or -12% of nominal. Enphase Microinverters, like all
utility-interactive inverters, sense voltage and frequency from the AC grid and cease exporting power when
voltage or frequency from the grid is too high or too low.
If the voltage measured is outside of the limit, the Enphase Microinverter enters an AC Voltage Out-Of-
Range (ACVOOR) condition and ceases to export power until this condition clears. Besides voltage
variations from the AC grid, voltage changes within the system wiring can also contribute to VRise and could
cause microinverters to sense an over-voltage condition and cease operation.

1 © 2018 Enphase Energy Inc. All rights reserved. November 2018


Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable – North America 60Hz

The Enphase Microinverter reference point for voltage measurement is at the microinverter AC output. Since
the microinverter is located at the array, and the point of common coupling (PCC) is generally at the site load
center, the distance from the microinverter AC output to the PCC could be substantial.
All components within system wiring contribute to resistance and must be considered when calculating the
total VRise. The main factors that determine voltage rise in an Enphase Microinverter system are: 1)
distance from the microinverters to the PCC, and 2) conductor size. “What Contributes to Voltage Rise?” on
page 2 provides details.
Typically, you can quantify the voltage rise of three distinct wire sections and several wire terminations, as
described in “Voltage Rise by Wire Section” on page 3. There is also some resistance associated with each
OCPD, typically a circuit breaker, but this is generally not taken into account.

What Contributes to Voltage Rise?


Enphase Microinverter systems are installed as dedicated branch circuits with each branch circuit protected
by a 20 A OCPD. The following points must be considered for each branch circuit when calculating VRise.
• Wire size: Improper wire size can result in nuisance tripping of the utility-protective functions in the
microinverter. Undersized conductors can cause the voltage measured at the microinverter to fall
outside of the IEEE limits, triggering an ACVOOR condition. This results in loss of energy harvest.
Although the National Electric Code recommends that branch circuit conductors be sized for a
maximum of 3% VRise (Article 210.19, FPN 4.), this value in practice is generally not low enough for
a utility-interactive inverter.

There is a tradeoff made between increased wire size and increased cost. You can often increase
wire size by one AWG trade size with minimal cost impact. At some point, increasing the wire size
necessitates increases in the conduit and/or terminal size, thus further increasing costs. However,
the increased wiring and conduit costs can be offset by the increase in energy production over the
lifetime of the system. These are important to invest in, especially for long wire runs.
• Circuit current: Circuit current varies depending on which “wire section” is being considered in the
installation. “Voltage Rise by Wire Section” on page 3 describes a typical installation containing three
wire sections where current is considered. With Q Cable, current increases with each inverter added
to the circuit.
• Circuit length: There is often little control over circuit length, but center-feeding the dedicated
branch circuit significantly reduces voltage rise within the branch, as described in “Advantages of
Center-Feeding the AC Branch Circuits” on page 6.
• Voltage margin: If service voltage is chronically high, the utility will sometimes perform a tap change
on the distribution transformer. This can provide a percent or two of additional voltage margin.
• Utility voltage: The utility should maintain voltage at the PCC within +/- 5% of nominal and in some
states within +/- 3% of nominal. The protective functions of the microinverters are set to +10% / -12%
by default. The high voltage end of the tolerance is of most concern because the inverters are a
source and not a load. If the utility is consistently 5% high, that leaves less than 5% for all wiring and
interconnection losses as well as inverter measurement accuracy. If you are concerned about the
utility voltage, you may request that your utility place a data logger at the PCC and make a record of
the voltages available to you at the site.

2 © 2018 Enphase Energy Inc. All rights reserved. November 2018


Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable – North America 60Hz

Voltage Rise by Wire Section


In this section, two typical system configurations are discussed: 1) IQ Microinverter system using the Branch
Aggregator, 2) IQ Microinverter system using an Enphase IQ Combiner (or IQ Combiner+) or PV subpanel.

1) IQ Microinverter system using the Branch Aggregator

IQ Microinverter system using the Branch Aggregator

Section Description

1 Internal voltage rise within the Q Cables to rooftop junction box. See internal VRise values
for IQ Micros in Tables 1.1 through 1.15. Only the Q Cable with microinverter connectors is
addressed in this section.

2 Q Extension voltage rise from Q Cable to the Q Aggregator. The #12 AWG row in
“Conductor Lengths by Wire Section” on page 18 lists maximum distances that maintain a
1% voltage rise for this wire section.

3 Voltage rise from the Q Aggregator to the Main Panel. The tables in “Conductor Lengths by
Wire Section” on page 18 list maximum distances that maintain a 1% voltage rise for this
wire section.

3 © 2018 Enphase Energy Inc. All rights reserved. November 2018


Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable – North America 60Hz

2) IQ Microinverter system using an Enphase IQ Combiner or PV subpanel

IQ Microinverter system using an Enphase IQ Combiner or PV subpanel

Section Description

1 Internal voltage rise within the Q Cables to rooftop junction box. See internal VRise values
for IQ Micros in Tables 1.1 through 1.15. Only the Q Cable with microinverter connectors is
addressed in this section.

2 Voltage rise from the array-mounted AC junction box, along the AC branch circuits, to the
load center containing the dedicated microinverter OCPDs (circuit breakers). The tables in
“Conductor Lengths by Wire Section” on page 18 list maximum distances that maintain a 1%
voltage rise for this wire section.
Enphase AC Combiner or PV subpanel to the PCC. Voltage rise from the load center to the
3
PCC. The tables in “Conductor Lengths by Wire Section” on page 18 list maximum distances
that maintain a 1% voltage rise for this wire section.

Calculate each component individually and verify that the total voltage rise is less than 2%. “Calculating Total
Voltage Rise” lists formulas to determine voltage rise. Additional losses exist at the terminals, connectors,
and in circuit breakers; however, if you design for a 2% total voltage rise, these other factors may be ignored.

4 © 2018 Enphase Energy Inc. All rights reserved. November 2018


Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable – North America 60Hz

Q Cable and Internal Voltage Rise


The Q Cable is a continuous length of 12 AWG stranded copper, outdoor-rated cable, with integrated
connectors for IQ-Series Microinverters. The following table lists the Q Cable types for single phase projects.

Voltage type and conductor count Model Connector spacing PV module orientation
240 VAC, 2 conductor Q-12-10-240 1.3 m (51”) Portrait
240 VAC, 2 conductor Q-12-17-240 2 m (79”) 60-cell Landscape
240 VAC, 2 conductor Q-12-20-200 2.3 m (91”) 72-cell Landscape

Regardless of the application, Enphase recommends that the total percentage of voltage rise in the AC
wiring be less than 2%, with (an inclusive) less than 1% voltage rise in the Q Cable. Although the Q Cable is
optimized for minimal VRise, it is still important to calculate total VRise for the entire system for the array
from the last microinverter on each branch of sub-branch to the PCC.

Determining VRise Within a Microinverter Branch Circuit


It is not difficult to determine VRise within the microinverter branch circuit. Tables 1.1 through 1.15 provide
VRise values for the available IQ Micros and Q Cable types. Use these values to help calculate total VRise
for your project. The following diagram represents a 240 VAC system with a fully populated end-fed branch
circuit of IQ 6+ Micros. It illustrates how voltage measured at an individual microinverter increases by
position in the branch circuit. As the number of microinverters in a branch circuit increase, the voltage at
each microinverter rises in a non-linear manner.

The top row of numbers is the incremental voltage rise from one microinverter to the next, and the bottom
row is the cumulative line-to-line voltage overall.
The following graph illustrates how the number of microinverters connected to a portrait-oriented Q Cable
causes a non-linear voltage rise when operating at 240 VAC.

5 © 2018 Enphase Energy Inc. All rights reserved. November 2018


Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable – North America 60Hz

Advantages of Center-Feeding the AC Branch Circuits


Since voltage rise is non-linear, reducing the number of microinverters in the branch circuit greatly reduces
the voltage measured at the last microinverter in the branch. One way to minimize this voltage rise is to
center-feed the branch, that is, divide the circuit into two sub-branch circuits protected by a single OCPD.
The following diagram illustrates the center-fed method.

A fully populated IQ 6+ branch circuit has 13 microinverters. If center-fed, there will be seven microinverters
on one sub-branch circuit and six on the other sub-branch circuit. All microinverters are parallel connected to
a single circuit, either at a junction box or Q Aggregator connector, and run back to the circuit breaker panel.
As an example, a fully populated branch circuit with 13 IQ 6+ microinverters and 72-cell landscape cabling
would measure 1.32% voltage rise to the last inverter if the circuit was end-fed. If this same circuit was
center-fed, the voltage rise within the Q Cable would be reduced to 0.52%. This analysis assumes that the
circuit was equally center-fed, however, since the AC connections in this case will be parallel connected,
equal sub-circuits are not a requirement, and center-feeding can be used in a way that is more convenient at
the site. When calculating the VRise of the total circuit, the larger of the sub-branches should be used when
determining internal Q Cable VRise.

6 © 2018 Enphase Energy Inc. All rights reserved. November 2018


Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable – North America 60Hz

Q Extension Cable Lengths


When using the Q Extension Cable (P/N: Q-RAW-300), use Tables 2.1 through 2.5 to determine the voltage
rise for this section of cable. Reference the number of IQ Micros and the length of cable to find the voltage
rise for this section.

Conductor Lengths for Wire Sections


Use the calculations in Tables 3.1 through 3.5 to determine the proper conductor size for a given section of
wire. These tables list the maximum conductor lengths from the roof back to the main service panel for
maintaining a 1% voltage rise. With the IQ system there is the option to locate a Q Aggregator on the roof to
combine up to three 20A microinverter branch circuits, or each microinverter branch circuit can be kept
separate if using a PV Subpanel or Enphase AC Combiner. Use these tables as a quick reference to
determine the appropriate conductor size for a single circuit of IQ Microinverter or up to three circuits if
installing with the Q Aggregator or AC Combiner. Keep in mind that a single wire section may only represent
a single section of the overall system, and that all sections should maintain a total voltage rise of 2%.

Calculating Total Voltage Rise

Voltage Rise Formulas


All resistances of the system components are in series and are cumulative. Since the same current is flowing
through each resistance, the total VRise is simply the total current times the total resistance.
The VRise percentage for an Enphase Microinverter system is:
% of Total VRise = % VRise Section 1 + % VRise Section 2 + % VRise Section 3
Where,
% VRise Section 1 = % by number of microinverters in Internal VRise of Q Cable with IQ-Series
Microinverters
% VRise Section 2 = VRise Section 2 ÷ System Voltage (either 240 or 208)
% VRise Section 3 = VRise Section 3 ÷ System Voltage (either 240 or 208)

VRise Formula for a 240 VAC, Single-Phase Installation


In a 240 VAC single-phase system, the total resistance is equal to two times the one-way resistance.
VRise of Section = (amps/inverter x number of inverters) x (Ω/ft x 2-way wire length of
Section 2 (or 3))

7 © 2018 Enphase Energy Inc. All rights reserved. November 2018


Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable – North America 60Hz

Sample Calculations for Single-Phase 240 VAC Installations


As part of this analysis, we calculate VRise for a sample scenario of a fully populated Q Aggregator with 48
IQ 6 Microinverters. Each 20 A circuit has 16 IQ 6 microinverters. Each branch circuit has been center-fed
into two sub-branch circuits of eight microinverters each.

Section 1: IQ 6 Internal VRise for 240 VAC Q Cable


Refer to the following table to find the Q Cable VRise appropriate for your project.

Table 1.1: Internal Q Cable VRise (IQ 6 – 240V / Portrait Cable, Q-12-10-240)
IQ 6 Microinverters per branch (Portrait)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Current (A) 0.96 1.92 2.88 3.83 4.79 5.75 6.71 7.67 8.63 9.58 10.54 11.50 12.46 13.42 14.38 15.33
VRise (V) 0.02 0.05 0.10 0.16 0.24 0.34 0.45 0.58 0.73 0.89 1.07 1.26 1.47 1.70 1.94 2.20
VRise (%) 0.01 0.02 0.04 0.07 0.10 0.14 0.19 0.24 0.30 0.37 0.45 0.53 0.61 0.71 0.81 0.92

For a sub-branch circuit of eight IQ 6 Micros, the voltage rise on the 240 VAC Q Cable is 0.24%.

Section 2: Voltage Rise from Q Cable to Q Aggregator


In some cases, it may not be possible to connect the Q Cable directly to the Q Aggregator. For instance,
when an array is located some distance from the Q Aggregator. In this case, use the Q Extension cable and
male and female Field-Wireable Connectors to make this configuration possible. Use Tables 2.1 through 2.4
to determine the maximum length of Q extension cable to maintain 1% voltage rise for this section. To further
reduce voltage rise, you may increase the conductor size and use the following calculation. Here we
calculate the voltage rise from an array of 16 IQ 6 Microinverters back to the location of the Q Aggregator.
This run uses 20 feet of Q extension cabling.

VRise = (amps/inverter × number of inverters) × (resistance in Ω/ft) × (2-way wire length in ft)
The following example is for a fully populated circuit of 16 IQ 6 Microinverters.
• IQ 6 full load AC current = 0.96 amp
• Wire gauge for Q Extension cable = #12 AWG THWN-2 CU
• #12 AWG THWN-2 CU resistance = 0. 00198 /ft (from NEC 2008, Chapter 9, Table 8)
• Length of individual branch circuit = 20 feet, with two-way wire length = 40 feet
VRise = (0.96 amp × 16) × (0. 00198 Ω/ft) × (20 ft × 2)
= 15.36 amps × 0.00198 Ω/ft × 40 ft
= 1.22 volts
%VRise = 1.22 volts ÷ 240 volts = 0.51%
The voltage rise from the array to the Q Aggregator is 0.51%.

8 © 2018 Enphase Energy Inc. All rights reserved. November 2018


Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable – North America 60Hz

Section 3: Voltage Rise from the Q Aggregator to Main Panel


Use Tables 3.1 through 3.5 as a quick reference to determine an adequate wire size. To calculate the
voltage rise in this portion of the circuit, multiply the combined current of the microinverters in the branch by
the total resistance of the wire run.
VRise = (amps/inverter × number of inverters) × (resistance in Ω/ft) × (2-way wire length in ft)
The following example is for a fully populated Q Aggregator of 48 IQ 6 Microinverters.
• IQ 6 full load AC current = 0.96 amp
• Wire gauge for individual branch circuit = #10 AWG THWN-2 CU
• #6 AWG THWN-2 CU resistance = 0. 000491 /ft (from NEC 2008, Chapter 9, Table 8)
• Length of individual branch circuit = 40 feet, with two-way wire length = 80 feet
VRise = (0.96 amp × 48) × (0. 000491 Ω/ft) × (40 ft × 2)
= 46 amps × 0.000491 Ω/ft × 80 ft
= 2.86 volts
%VRise = 1.81 volts ÷ 240 volts = 0.75%
The voltage rise from the Q Aggregator to the Main Panel is 0.75%.

Summary of Wire Section Calculations for Single-Phase 240 VAC Applications


With the utility operating at the upper limit of their allowable tolerance (+5%) and the microinverters having a
measurement accuracy of 2.5%, we are left with a voltage rise budget of 5.4 volts (2.25%) for all wiring to the
PCC. The calculated VRise for all three portions of the system must be 5.4 volts or less. For systems with
very long branch circuit runs and/or very long runs from the PV load center to the PCC, it is best to make the
VRise in the Q Cable as small as possible. As we have already determined, 5.4 volts is equal to 2.25% of the
nominal voltage. After accounting for additional losses within connections, terminals, circuit breakers, and
unexpected increases in wire length, we recommend implementation of a total system voltage rise of less
than 2%.
Section 1: Voltage rise in Q Cable from the microinverters to the AC junction box = 0.24%
Section 2: Voltage rise from the AC junction box to the microinverter subpanel = 0.51%
Section 3: Voltage rise from the microinverter subpanel to the main service panel (PCC) = 0.75%
Total system voltage rise for all three wire sections = 1.5%

Conclusion
Center-feeding is a great way to decrease home run conductor costs, improve production, and increase
system reliability. Follow the guidelines and calculations in this document to help minimize voltage rise
issues with your installation and increase system production. Use the tables in the following Appendix to
determine voltage rise and conductor size for your installations.

9 © 2018 Enphase Energy Inc. All rights reserved. November 2018


Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable – North America 60Hz

Appendix: VRise and Conductor Length Tables

Internal VRise of Q Cables with IQ Series Microinverters 240V


Use the following tables to determine the voltage rise attributed to the Q Cable when the IQ Micros are
connected to 240 Volts. Reference the IQ Micro and Q Cable type (model numbers provided) to find the
appropriate table. For end fed circuits reference the number of microinverters in the circuit to find the voltage
rise attributed to the Q Cable. For center-fed circuits, reference the number of microinverters in the longer of
the two sub-branches.

Table Key Explained

Q Cable Type
(P=Portrait,
Micro model L-L service voltage L-60= Landscape 60-cell
L-72=Landscape 72-cell)

IQ 6+ 240V L-72

10 © 2018 Enphase Energy Inc. All rights reserved. November 2018


Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable – North America 60Hz

IQ 6 – IQ6-60-*-US

Table 1.1: Internal Q Cable VRise (Portrait Cable, Q-12-10-240) IQ 6 240V P

IQ 6 Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Current (A) 0.96 1.92 2.88 3.83 4.79 5.75 6.71 7.67 8.63 9.58 10.54 11.50 12.46 13.42 14.38 15.33

VRise (V) 0.02 0.05 0.10 0.16 0.24 0.34 0.45 0.58 0.79 0.89 1.07 1.26 1.47 1.70 1.94 2.20

VRise (%) 0.01 0.02 0.04 0.07 0.10 0.14 0.19 0.24 0.30 0.37 0.45 0.53 0.61 0.71 0.81 0.92

Table 1.2: Internal Q Cable VRise (Landscape 60-Cell Cable, Q-12-17-240) IQ 6 240V L-60

IQ 6 Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Current (A) 0.96 1.92 2.88 3.83 4.79 5.75 6.71 7.67 8.63 9.58 10.54 11.50 12.46 13.42 14.38 15.33

VRise (V) 0.02 0.07 0.15 0.25 0.37 0.52 0.70 0.90 1.12 1.37 1.64 1.94 2.27 2.61 2.99 3.37

VRise (%) 0.01 0.03 0.06 0.10 0.16 0.22 0.29 0.37 0.47 0.57 0.68 0.81 0.94 1.09 1.25 1.41

Table 1.3: Internal Q Cable VRise (Landscape 72-Cell Cable*, Q-12-20-200) IQ 6 240V L-72

IQ 6 Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Current (A) 0.96 1.92 2.88 3.83 4.79 5.75 6.71 7.67 8.63 9.58 10.54 11.50 12.46 13.42 14.38 15.33

VRise (V) 0.03 0.09 0.17 0.29 0.43 0.60 0.80 1.03 1.29 1.58 1.89 2.23 2.61 3.10 3.44 3.89

VRise (%) 0.01 0.04 0.07 0.12 0.18 0.25 0.33 0.43 0.54 0.66 0.79 0.93 1.09 1.25 1.43 1.62

*Note that IQ 6 Micros are compatible with 60-cell PV modules only but can be used with Q-12-20-200 cable.

11 © 2018 Enphase Energy Inc. All rights reserved. November 2018


Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable – North America 60Hz

IQ 6+ - IQ6PLUS-72-*-US

Table 1.4: Internal Q Cable VRise (Portrait Cable, Q-12-10-240) IQ 6+ 240V P

IQ 6+ Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11 12 13

Current (A) 1.17 2.33 3.50 4.67 5.83 7.00 8.17 9.33 10.50 11.67 12.83 14.00 15.17

VRise (V) 0.02 0.06 0.12 0.20 0.30 0.41 0.55 0.71 0.89 1.08 1.30 1.54 1.79

VRise (%) 0.01 0.02 0.05 0.08 0.12 0.17 0.23 0.30 0.37 0.45 0.54 0.64 0.75

Table 1.5: Internal Q Cable VRise (Landscape 60-Cell Cable, Q-12-17-240) IQ 6+ 240V L-60

IQ 6+ Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11 12 13

Current (A) 1.17 2.33 3.50 4.67 5.83 7.00 8.17 9.33 10.50 11.67 12.83 14.00 15.17

VRise (V) 0.03 0.09 0.18 0.30 0.45 0.64 0.85 1.09 1.36 1.67 2.00 2.36 2.76

VRise (%) 0.01 0.04 0.08 0.13 0.19 0.27 0.35 0.45 0.57 0.69 0.83 0.99 1.15

Table 1.6: Internal Q Cable VRise (Landscape 72-Cell Cable, Q-12-20-200) IQ 6+ 240V L-72

IQ 6+ Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11 12 13

Current (A) 1.17 2.33 3.50 4.67 5.83 7.00 8.17 9.33 10.50 11.67 12.83 14.00 15.17

VRise (V) 0.03 0.10 0.21 0.35 0.52 0.73 0.98 1.26 1.57 1.92 2.30 2.72 3.17

VRise (%) 0.01 0.04 0.09 0.15 0.22 0.31 0.41 0.52 0.65 0.80 0.96 1.13 1.32

12 © 2018 Enphase Energy Inc. All rights reserved. November 2018


Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable – North America 60Hz

IQ 7 - IQ7-60-*-US

Table 1.7: Internal Q Cable VRise (Portrait Cable, Q-12-10-240) IQ 7 240V P

IQ 7 Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Current (A) 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0 15.0 16.0

VRise (V) 0.02 0.05 0.10 0.17 0.25 0.35 0.47 0.61 0.76 0.93 1.11 1.32 1.54 1.77 2.03 2.30

VRise (%) 0.01 0.02 0.04 0.07 0.11 0.15 0.20 0.25 0.32 0.39 0.46 0.55 0.64 0.74 0.84 0.96

Table 1.8: Internal Q Cable VRise (Landscape 60-Cell Cable, Q-12-17-240) IQ 7 240V L-60

IQ 7 Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Current (A) 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0 15.0 16.0

VRise (V) 0.03 0.08 0.16 0.26 0.39 0.55 0.73 0.94 1.17 1.43 1.71 2.03 2.36 2.73 3.12 3.53

VRise (%) 0.01 0.03 0.06 0.11 0.16 0.23 0.30 0.39 0.49 0.60 0.71 0.84 0.99 1.14 1.30 1.47

Table 1.9: Internal Q Cable VRise (Landscape 72-Cell Cable*, Q-12-20-200) IQ 7 240V L-72

IQ 7 Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Current (A) 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0 15.0 16.0

VRise (V) 0.03 0.09 0.18 0.30 0.45 0.63 0.84 1.08 1.34 1.64 1.97 2.33 2.72 3.14 3.59 4.06

VRise (%) 0.01 0.04 0.07 0.12 0.19 0.26 0.35 0.45 0.56 0.68 0.82 0.97 1.13 1.31 1.49 1.69

*Note that IQ 7 Micros are compatible with 60-cell PV modules only but can be used with Q-12-20-200 cable.

13 © 2018 Enphase Energy Inc. All rights reserved. November 2018


Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable – North America 60Hz

IQ 7+ - IQ7PLUS-72-*-US

Table 1.10: Internal Q Cable VRise (Portrait Cable, Q-12-10-240) IQ 7+ 240V P

IQ 7+ Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11 12 13

Current (A) 1.2 2.4 3.6 4.8 6.0 7.3 8.5 9.7 10.9 12.1 13.3 14.5 15.7

VRise (V) 0.02 0.06 0.12 0.20 0.31 0.43 0.57 0.73 0.92 1.12 1.35 1.59 1.86

VRise (%) 0.01 0.03 0.05 0.09 0.13 0.18 0.24 0.31 0.38 0.47 0.56 0.66 0.77

Table 1.11: Internal Q Cable VRise (Landscape 60-Cell Cable, Q-12-17-240) IQ 7+ 240V L-60

IQ 7+ Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11 12 13

Current (A) 1.2 2.4 3.6 4.8 6.0 7.3 8.5 9.7 10.9 12.1 13.3 14.5 15.7

VRise (V) 0.03 0.09 0.19 0.31 0.47 0.66 0.88 1.13 1.41 1.73 2.07 2.45 2.86

VRise (%) 0.01 0.04 0.08 0.13 0.20 0.27 0.37 0.47 0.59 0.72 0.86 1.02 1.19

Table 1.12: Internal Q Cable VRise (Landscape 72-Cell Cable, Q-12-20-200) IQ 7+ 240V L-72

IQ 7+ Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11 12 13

Current (A) 1.2 2.4 3.6 4.8 6.0 7.3 8.5 9.7 10.9 12.1 13.3 14.5 15.7

VRise (V) 0.04 0.11 0.22 0.36 0.54 0.76 1.01 1.30 1.62 1.99 2.38 2.82 3.29

VRise (%) 0.02 0.05 0.09 0.15 0.23 0.32 0.42 0.54 0.68 0.83 0.99 1.17 1.37

14 © 2018 Enphase Energy Inc. All rights reserved. November 2018


Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable – North America 60Hz

IQ 7X - IQ7X-96-*-US

Table 1.13: Internal Q Cable VRise (Portrait Cable, Q-12-10-240) IQ 7X 240V P

IQ 7X Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11 12

Current (A) 1.3 2.6 3.9 5.3 6.6 7.9 9.2 10.5 11.8 13.1 14.4 15.8

VRise (V) 0.02 0.07 0.13 0.22 0.33 0.47 0.62 0.80 1.00 1.22 1.46 1.73

VRise (%) 0.01 0.03 0.06 0.09 0.14 0.19 0.26 0.33 0.42 0.51 0.61 0.72

Table 1.14: Internal Q Cable VRise (Landscape 60-Cell Cable, Q-12-17-240) IQ 7X 240V L-60

IQ 7X Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11 12

Current (A) 1.3 2.6 3.9 5.3 6.6 7.9 9.2 10.5 11.8 13.1 14.4 15.8

VRise (V) 0.03 0.10 0.20 0.34 0.51 0.72 0.95 1.23 1.53 1.88 2.25 2.66

VRise (%) 0.01 0.04 0.09 0.14 0.21 0.30 0.40 0.51 0.64 0.78 0.94 1.11

Table 1.15: Internal Q Cable VRise (Landscape 72-Cell Cable, Q-12-20-200) IQ 7X 240V L-72

IQ 7X Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11 12

Current (A) 1.3 2.6 3.9 5.3 6.6 7.9 9.2 10.5 11.8 13.1 14.4 15.8

VRise (V) 0.04 0.12 0.24 0.39 0.59 0.82 1.10 1.41 1.76 2.16 2.59 3.06

VRise (%) 0.02 0.05 0.10 0.16 0.25 0.34 0.46 0.59 0.74 0.90 1.08 1.27

15 © 2018 Enphase Energy Inc. All rights reserved. November 2018


Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable – North America 60Hz

Q Extension Cable Lengths


When using the Q Extension Cable (Model: Q-RAW-300), use the following tables to determine the voltage
rise for this section of cable. Reference the number of IQ Micros and the length of cable to find the voltage
rise for this section.
Table 2.1: Q Extension Cable (IQ 6)
Feet IQ 6 Microinverters per branch 240V

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

10 0.02% 0.03% 0.05% 0.06% 0.08% 0.09% 0.11% 0.13% 0.14% 0.16% 0.17% 0.19% 0.21% 0.22% 0.24% 0.25%

15 0.02% 0.05% 0.07% 0.09% 0.12% 0.14% 0.17% 0.19% 0.21% 0.24% 0.26% 0.28% 0.31% 0.33% 0.36% 0.38%

20 0.03% 0.06% 0.09% 0.13% 0.16% 0.19% 0.22% 0.25% 0.28% 0.32% 0.35% 0.38% 0.41% 0.44% 0.47% 0.51%

25 0.04% 0.08% 0.12% 0.16% 0.20% 0.24% 0.28% 0.32% 0.36% 0.40% 0.43% 0.47% 0.51% 0.55% 0.59% 0.63%

30 0.05% 0.09% 0.14% 0.19% 0.24% 0.28% 0.33% 0.38% 0.43% 0.47% 0.52% 0.57% 0.62% 0.66% 0.71% 0.76%

40 0.06% 0.13% 0.19% 0.25% 0.32% 0.38% 0.44% 0.51% 0.57% 0.63% 0.70% 0.76% 0.82% 0.89% 0.95% 1.01%

50 0.08% 0.16% 0.24% 0.32% 0.40% 0.47% 0.55% 0.63% 0.71% 0.79% 0.87% 0.95% 1.03% 1.11% 1.19% 1.27%

60 0.09% 0.19% 0.28% 0.38% 0.47% 0.57% 0.66% 0.76% 0.85% 0.95% 1.04% 1.14% 1.23% 1.33% 1.42% 1.52%

70 0.11% 0.22% 0.33% 0.44% 0.55% 0.66% 0.77% 0.89% 1.00% 1.11% 1.22% 1.33% 1.44% 1.55% 1.66% 1.77%

80 0.13% 0.25% 0.38% 0.51% 0.63% 0.76% 0.89% 1.01% 1.14% 1.27% 1.39% 1.52% 1.64% 1.77% 1.90% 2.02%

90 0.14% 0.28% 0.43% 0.57% 0.71% 0.85% 1.00% 1.14% 1.28% 1.42% 1.57% 1.71% 1.85% 1.99% 2.13% 2.28%

100 0.16% 0.32% 0.47% 0.63% 0.79% 0.95% 1.11% 1.27% 1.42% 1.58% 1.74% 1.90% 2.06% 2.21% 2.37% 2.53%

Table 2.2: Q Extension Cable (IQ 6+)


Feet IQ 6+ Microinverters per branch 240V

1 2 3 4 5 6 7 8 9 10 11 12 13
10 0.02% 0.04% 0.06% 0.08% 0.10% 0.12% 0.13% 0.15% 0.17% 0.19% 0.21% 0.23% 0.25%

15 0.03% 0.06% 0.09% 0.12% 0.14% 0.17% 0.20% 0.23% 0.26% 0.29% 0.32% 0.35% 0.38%

20 0.04% 0.08% 0.12% 0.15% 0.19% 0.23% 0.27% 0.31% 0.35% 0.39% 0.24% 0.46% 0.50%

25 0.05% 0.10% 0.14% 0.19% 0.24% 0.29% 0.34% 0.39% 0.43% 0.48% 0.53% 0.58% 0.63%

30 0.06% 0.12% 0.17% 0.23% 0.29% 0.35% 0.40% 0.46% 0.52% 0.58% 0.64% 0.69% 0.75%

40 0.08% 0.15% 0.23% 0.31% 0.39% 0.46% 0.54% 0.62% 0.69% 0.77% 0.85% 0.92% 1.00%

50 0.10% 0.19% 0.29% 0.39% 0.48% 0.58% 0.67% 0.77% 0.87% 0.96% 1.06% 1.16% 1.25%

60 0.12% 0.23% 0.35% 0.46% 0.58% 0.69% 0.81% 0.92% 1.04% 1.16% 1.27% 1.39% 1.50%

70 0.13% 0.27% 0.40% 0.54% 0.67% 0.81% 0.94% 1.08% 1.21% 1.35% 1.48% 1.62% 1.75%

80 0.15% 0.31% 0.46% 0.62% 0.77% 0.92% 1.08% 1.23% 1.39% 1.54% 1.69% 1.85% 2.00%

90 0.17% 0.35% 0.52% 0.69% 0.87% 1.04% 1.21% 1.39% 1.56% 1.73% 1.91% 2.08% 2.25%

100 0.19% 0.39% 0.58% 0.77% 0.96% 1.16% 1.35% 1.54% 1.73% 1.93% 2.12% 2.31% 2.50%

16 © 2018 Enphase Energy Inc. All rights reserved. November 2018


Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable – North America 60Hz

Table 2.3: Q Extension Cable (IQ 7)

Feet IQ 7 Microinverters per branch 240V

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

10 0.02% 0.03% 0.05% 0.07% 0.08% 0.10% 0.12% 0.13% 0.15% 0.17% 0.18% 0.20% 0.21% 0.23% 0.25% 0.26%

15 0.02% 0.05% 0.07% 0.10% 0.12% 0.15% 0.17% 0.20% 0.22% 0.25% 0.27% 0.30% 0.32% 0.35% 0.37% 0.40%

20 0.03% 0.07% 0.10% 0.13% 0.17% 0.20% 0.23% 0.26% 0.30% 0.33% 0.36% 0.40% 0.43% 0.46% 0.50% 0.53%

25 0.04% 0.08% 0.12% 0.17% 0.21% 0.25% 0.29% 0.33% 0.37% 0.41% 0.45% 0.50% 0.54% 0.58% 0.62% 0.66%

30 0.05% 0.10% 0.15% 0.20% 0.25% 0.30% 0.35% 0.40% 0.45% 0.50% 0.54% 0.59% 0.64% 0.69% 0.74% 0.79%

40 0.07% 0.13% 0.20% 0.26% 0.33% 0.40% 0.46% 0.53% 0.59% 0.66% 0.73% 0.79% 0.86% 0.92% 0.99% 1.06%

50 0.08% 0.17% 0.25% 0.33% 0.41% 0.50% 0.58% 0.66% 0.74% 0.83% 0.91% 0.99% 1.07% 1.16% 1.24% 1.32%

60 0.10% 0.20% 0.30% 0.40% 0.50% 0.59% 0.69% 0.79% 0.89% 0.99% 1.09% 1.19% 1.29% 1.39% 1.49% 1.58%

70 0.12% 0.23% 0.35% 0.46% 0.58% 0.69% 0.81% 0.92% 1.04% 1.16% 1.27% 1.39% 1.50% 1.62% 1.73% 1.85%

80 0.13% 0.26% 0.40% 0.53% 0.66% 0.79% 0.92% 1.06% 1.19% 1.32% 1.45% 1.58% 1.72% 1.85% 1.98% 2.11%

90 0.15% 0.30% 0.45% 0.59% 0.74% 0.89% 1.04% 1.19% 1.34% 1.49% 1.63% 1.78% 1.93% 2.08% 2.23% 2.38%

100 0.17% 0.33% 0.50% 0.66% 0.83% 0.99% 1.16% 1.32% 1.49% 1.65% 1.82% 1.98% 2.15% 2.31% 2.48% 2.64%

Table 2.4: Q Extension Cable (IQ 7+)


Feet IQ 7+ Microinverters per branch 240V
1 2 3 4 5 6 7 8 9 10 11 12 13

10 0.02% 0.04% 0.06% 0.08% 0.10% 0.12% 0.14% 0.16% 0.18% 0.20% 0.22% 0.24% 0.26%

15 0.03% 0.06% 0.09% 0.12% 0.15% 0.18% 0.21% 0.24% 0.27% 0.30% 0.33% 0.36% 0.39%

20 0.04% 0.08% 0.12% 0.16% 0.20% 0.24% 0.28% 0.32% 0.36% 0.40% 0.44% 0.48% 0.52%

25 0.05% 0.10% 0.15% 0.20% 0.25% 0.30% 0.35% 0.40% 0.45% 0.50% 0.55% 0.60% 0.65%

30 0.06% 0.12% 0.18% 0.24% 0.30% 0.36% 0.42% 0.48% 0.54% 0.60% 0.66% 0.72% 0.78%

40 0.08% 0.16% 0.24% 0.32% 0.40% 0.48% 0.56% 0.64% 0.72% 0.80% 0.88% 0.96% 1.04%

50 0.10% 0.20% 0.30% 0.40% 0.50% 0.60% 0.70% 0.80% 0.90% 1.00% 1.10% 1.20% 1.30%

60 0.12% 0.24% 0.36% 0.48% 0.60% 0.72% 0.84% 0.96% 1.08% 1.20% 1.32% 1.44% 1.56%

70 0.14% 0.28% 0.42% 0.56% 0.70% 0.84% 0.98% 1.12% 1.26% 1.40% 1.54% 1.67% 1.81%

80 0.16% 0.32% 0.48% 0.64% 0.80% 0.96% 1.12% 1.28% 1.44% 1.60% 1.75% 1.91% 2.07%

90 0.18% 0.36% 0.54% 0.72% 0.90% 1.08% 1.26% 1.44% 1.61% 1.79% 1.97% 2.15% 2.33%

100 0.20% 0.40% 0.60% 0.80% 1.00% 1.20% 1.40% 1.60% 1.79% 1.99% 2.19% 2.39% 2.59%

17 © 2018 Enphase Energy Inc. All rights reserved. November 2018


Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable – North America 60Hz

Table 2.5: Q Extension Cable (IQ 7X)


Feet IQ 7X Microinverters per branch 240V
1 2 3 4 5 6 7 8 9 10 11 12

10 0.02% 0.04% 0.06% 0.09% 0.11% 0.13% 0.15% 0.17% 0.19% 0.22% 0.24% 0.26%

15 0.03% 0.06% 0.10% 0.13% 0.16% 0.19% 0.23% 0.26% 0.29% 0.32% 0.36% 0.39%

20 0.04% 0.09% 0.13% 0.17% 0.22% 0.26% 0.30% 0.35% 0.39% 0.43% 0.48% 0.52%

25 0.05% 0.11% 0.16% 0.22% 0.27% 0.32% 0.38% 0.43% 0.49% 0.54% 0.60% 0.65%

30 0.06% 0.13% 0.19% 0.26% 0.32% 0.39% 0.45% 0.52% 0.58% 0.65% 0.71% 0.78%

40 0.09% 0.17% 0.26% 0.35% 0.43% 0.52% 0.61% 0.69% 0.78% 0.87% 0.95% 1.04%

50 0.11% 0.22% 0.32% 0.43% 0.54% 0.65% 0.76% 0.87% 0.97% 1.08% 1.19% 1.30%

60 0.13% 0.26% 0.39% 0.52% 0.65% 0.78% 0.91% 1.04% 1.17% 1.30% 1.43% 1.56%

70 0.15% 0.30% 0.45% 0.61% 0.76% 0.91% 1.06% 1.21% 1.36% 1.52% 1.67% 1.82%

80 0.17% 0.35% 0.52% 0.69% 0.87% 1.04% 1.21% 1.39% 1.56% 1.73% 1.91% 2.08%

90 0.19% 0.39% 0.58% 0.78% 0.97% 1.17% 1.36% 1.56% 1.75% 1.95% 2.14% 2.34%

100 0.22% 0.43% 0.65% 0.87% 1.08% 1.30% 1.52% 1.73% 1.95% 2.17% 2.38% 2.60%

Conductor Lengths by Wire Section


Use the following tables to help determine the proper wire size based on the number of microinverters in the
circuit and the length of the wire section. Use these tables for either individual microinverter branch circuits or
combined branch circuits that use the Q Aggregator. The tables list the maximum length a particular
conductor can be run to maintain 1% voltage rise for this section of wire. Keep in mind that if multiple
sections are combined, then the conductor size should be increased appropriately.

Table 3.1: Maximum Distance (in feet) to Maintain 1% VRise for 240 VAC (IQ 6)
AWG Number of IQ 6 Micros
3 6 9 12 15 16 18 21 24 27 30 33 36 39 42 45 48
#12 211 105 70 53 42 40 35 30 26 23 21 19 18 16 15 14 13
#10 337 168 112 84 67 63 56 48 42 37 34 31 28 26 24 22 21
#8 536 268 179 134 107 101 89 77 67 60 54 49 45 41 38 36 34
#6 850 425 283 213 170 159 142 121 106 94 85 77 71 65 61 57 53
#4 1355 678 452 339 271 254 226 194 169 151 136 123 113 104 97 90 85
Single Branch Circuit Q Aggregator Combined Quantity of IQ 6

Table 3.2: Maximum Distance (in feet) to Maintain 1% VRise for 240 VAC (IQ 6+)
AWG Number of IQ 6+ Micros
3 6 9 12 13 15 18 21 24 27 30 33 36 39
#12 173 87 58 43 40 35 29 25 22 19 17 16 14 13
#10 276 138 92 69 64 55 46 39 35 31 28 25 23 21
#8 441 220 147 110 102 88 73 63 55 49 44 40 37 34
#6 698 349 233 175 161 140 116 100 87 78 70 63 58 54
#4 1113 557 371 278 257 223 186 159 139 124 111 101 93 86
Single Branch Circuit Q Aggregator Combined Quantity of IQ 6+

18 © 2018 Enphase Energy Inc. All rights reserved. November 2018


Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable – North America 60Hz

Table 3.3: Maximum Distance (in feet) to Maintain 1% VRise for 240 VAC (IQ 7)
AWG Number of IQ 7 Micros
3 6 9 12 15 16 18 21 24 27 30 33 36 39 42 45 48
#12 202 101 67 51 40 38 34 29 25 22 20 18 17 16 14 13 13
#10 323 161 108 81 65 60 54 46 40 36 32 29 27 25 23 22 20
#8 514 257 171 129 103 96 86 73 64 57 51 47 43 40 37 34 32
#6 815 407 272 204 163 153 136 116 102 91 81 74 68 63 58 54 51
#4 1299 649 433 325 260 244 216 186 162 144 130 118 108 100 93 87 81
Single Branch Circuit Q Aggregator combined quantity of IQ 7

Table 3.4: Maximum Distance (in feet) to Maintain 1% VRise for 240 VAC (IQ 7+)
AWG Number of IQ 7+ Micros
3 6 9 12 13 15 18 21 24 27 30 33 36 39
#12 167 84 56 42 39 33 28 24 21 19 17 15 14 13
#10 267 133 89 67 62 53 44 38 33 30 27 24 22 21
#8 425 213 142 106 98 85 71 61 53 47 43 39 35 33
#6 674 337 225 169 156 135 112 96 84 75 67 61 56 52
#4 1075 537 358 269 248 215 179 154 134 119 107 98 90 83
Single Branch Circuit Q Aggregator combined quantity of IQ 7+

Table 3.5: Maximum Distance (in feet) to Maintain 1% VRise for 240 VAC (IQ 7X)
AWG Number of IQ 7X Micros
3 6 9 12 15 18 21 24 27 30 33 36
#12 154 77 51 38 31 26 22 19 17 15 14 13
#10 246 123 82 61 49 41 35 31 27 25 22 20
#8 392 196 131 98 78 65 56 49 44 39 36 33
#6 621 310 207 155 124 103 89 78 69 62 56 52
#4 989 495 330 247 198 165 141 124 110 99 90 82
Single Branch Circuit Q Aggregator combined quantity of IQ 7X

Internal VRise of Q Cables with IQ Series Microinverters 208V


Use the following tables to determine the voltage rise attributed to the Q Cable when the IQ Micros are
connected to 208/120V services. Reference the IQ Micro and Q Cable type (model numbers provided) to find
the appropriate table. For end fed circuits reference the number of microinverters in the circuit to find the
voltage rise attributed to the Q Cable. For center-fed circuits, reference the number of microinverters in the
longer of the two sub-branches.

Table Key Explained

Q Cable Type
(P=Portrait,
Micro model L-L service voltage L-60= Landscape 60-cell
L-72=Landscape 72-cell)

IQ 7 208V L-60

19 © 2018 Enphase Energy Inc. All rights reserved. November 2018


Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable – North America 60Hz

IQ 6 – IQ6-60-*-US

Table 4.1: Internal Q Cable VRise (Portrait Cable, Q-12-10-240) IQ 6 208V P

IQ 6 Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11 12 13 14

Current (A) 1.11 2.21 3.32 4.42 5.53 6.63 7.74 8.85 9.95 11.06 12.16 13.27 14.38 15.48

VRise (V) 0.02 0.06 0.11 0.19 0.28 0.39 0.52 0.67 0.84 1.03 1.23 1.46 1.70 1.96

VRise (%) 0.01 0.03 0.05 0.09 0.13 0.19 0.25 0.32 0.40 0.49 0.59 0.70 0.82 0.94

Table 4.2: Internal Q Cable VRise (Landscape 60-Cell Cable, Q-12-17-240) IQ 6 208V L-60

IQ 6 Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11 12 13 14

Current (A) 1.11 2.21 3.32 4.42 5.53 6.63 7.74 8.85 9.95 11.06 12.16 13.27 14.38 15.48

VRise (V) 0.03 0.09 0.17 0.29 0.43 0.60 0.81 1.04 1.29 1.58 1.90 2.24 2.62 3.02

VRise (%) 0.01 0.04 0.08 0.14 0.21 0.29 0.39 0.50 0.62 0.76 0.91 1.08 1.26 1.45

Table 4.3: Internal Q Cable VRise (Landscape 72-Cell Cable*, Q-12-20-200) IQ 6 208V L-72

IQ 6 Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11 12 13 14

Current (A) 1.11 2.21 3.32 4.42 5.53 6.63 7.74 8.85 9.95 11.06 12.16 13.27 14.38 15.48

VRise (V) 0.03 0.10 0.20 0.33 0.50 0.69 0.93 1.19 1.49 1.82 2.18 2.58 3.01 3.47

VRise (%) 0.02 0.05 0.10 0.16 0.24 0.33 0.45 0.57 0.72 0.87 1.05 1.24 1.45 1.67

*Note that IQ 6 Micros are compatible with 60-cell PV modules only but can be used with Q-12-20-200 cable.

20 © 2018 Enphase Energy Inc. All rights reserved. November 2018


Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable – North America 60Hz

IQ 6+ - IQ6PLUS-72-*-US

Table 4.4: Internal Q Cable VRise (Portrait Cable, Q-12-10-240) IQ 6+ 208V P

IQ 6+ Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11

Current (A) 1.35 2.69 4.04 5.38 6.73 8.08 9.42 10.77 12.12 13.46 14.81

VRise (V) 0.02 0.07 0.14 0.23 0.34 0.48 0.64 0.82 1.02 1.25 1.50

VRise (%) 0.01 0.03 0.07 0.11 0.16 0.23 0.31 0.39 0.49 0.60 0.72

Table 4.5: Internal Q Cable VRise (Landscape 60-Cell Cable, Q-12-17-240) IQ 6+ 208V L-60

IQ 6+ Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11

Current (A) 1.35 2.69 4.04 5.38 6.73 8.08 9.42 10.77 12.12 13.46 14.81

VRise (V) 0.04 0.11 0.21 0.35 0.53 0.74 0.98 1.26 1.58 1.93 2.31

VRise (%) 0.02 0.05 0.10 0.17 0.25 0.35 0.47 0.61 0.76 0.93 1.11

Table 4.6: Internal Q Cable VRise (Landscape 72-Cell Cable, Q-12-20-200) IQ 6+ 208V L-72

IQ 6+ Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11

Current (A) 1.35 2.69 4.04 5.38 6.73 8.08 9.42 10.77 12.12 13.46 14.81

VRise (V) 0.04 0.12 0.24 0.40 0.60 0.85 1.13 1.45 1.81 2.21 2.66

VRise (%) 0.02 0.06 0.12 0.19 0.29 0.41 0.54 0.70 0.87 1.06 1.28

21 © 2018 Enphase Energy Inc. All rights reserved. November 2018


Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable – North America 60Hz

IQ 7 - IQ7-60-*-US

Table 4.7: Internal Q Cable VRise (Portrait Cable, Q-12-10-240) IQ 7 208V P

IQ 7 Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11 12 13

Current (A) 1.15 2.31 3.46 4.62 5.77 6.92 8.08 9.23 10.38 11.54 12.69 13.85 15.00

VRise (V) 0.02 0.06 0.12 0.20 0.29 0.41 0.55 0.70 0.88 1.07 1.29 1.52 1.77

VRise (%) 0.01 0.03 0.06 0.09 0.14 0.20 0.26 0.34 0.42 0.52 0.62 0.73 0.85

Table 4.8: Internal Q Cable VRise (Landscape 60-Cell Cable, Q-12-17-240) IQ 7 208V L-60

IQ 7 Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11 12 13

Current (A) 1.15 2.31 3.46 4.62 5.77 6.92 8.08 9.23 10.38 11.54 12.69 13.85 15.00

VRise (V) 0.03 0.09 0.18 0.30 0.45 0.63 0.84 1.08 1.35 1.65 1.98 2.34 2.73

VRise (%) 0.01 0.04 0.09 0.14 0.22 0.30 0.40 0.52 0.65 0.79 0.95 1.13 1.31

Table 4.9: Internal Q Cable VRise (Landscape 72-Cell Cable*, Q-12-20-200) IQ 7 208V L-72

IQ 7 Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11 12 13

Current (A) 1.15 2.31 3.46 4.62 5.77 6.92 8.08 9.23 10.38 11.54 12.69 13.85 15.00

VRise (V) 0.03 0.10 0.21 0.35 0.52 0.72 0.97 1.24 1.55 1.90 2.28 2.69 3.14

VRise (%) 0.02 0.05 0.10 0.17 0.25 0.35 0.46 0.60 0.75 0.91 1.09 1.29 1.51

*Note that IQ 7 Micros are compatible with 60-cell PV modules only but can be used with Q-
12-20-200 cable.

22 © 2018 Enphase Energy Inc. All rights reserved. November 2018


Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable – North America 60Hz

IQ 7+ - IQ7PLUS-72-*-US

Table 4.10: Internal Q Cable VRise (Portrait Cable, Q-12-10-240) IQ 7+ 208V P

IQ 7+ Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11

Current (A) 1.39 2.79 4.18 5.58 6.97 8.37 9.76 11.15 12.55 13.94 15.34

VRise (V) 0.02 0.07 0.14 0.24 0.35 0.49 0.66 0.85 1.06 1.30 1.56

VRise (%) 0.01 0.03 0.07 0.11 0.17 0.24 0.32 0.41 0.51 0.62 0.75

Table 4.11: Internal Q Cable VRise (Landscape 60-Cell Cable, Q-12-17-240) IQ 7+ 208V L-60

IQ 7+ Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11

Current (A) 1.39 2.79 4.18 5.58 6.97 8.37 9.76 11.15 12.55 13.94 15.34

VRise (V) 0.04 0.11 0.22 0.36 0.54 0.76 1.02 1.31 1.63 1.99 2.39

VRise (%) 0.02 0.05 0.10 0.17 0.26 0.37 0.49 0.63 0.78 0.96 1.15

Table 4.12: Internal Q Cable VRise (Landscape 72-Cell Cable, Q-12-20-200) IQ 7+ 208V L-72

IQ 7+ Microinverters per branch

1 2 3 4 5 6 7 8 9 10 11

Current (A) 1.39 2.79 4.18 5.58 6.97 8.37 9.76 11.15 12.55 13.94 15.34

VRise (V) 0.04 0.13 0.25 0.42 0.63 0.88 1.17 1.50 1.88 2.29 2.75

VRise (%) 0.02 0.06 0.12 0.20 0.30 0.42 0.56 0.72 0.90 1.10 1.32

23 © 2018 Enphase Energy Inc. All rights reserved. November 2018


Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable – North America 60Hz

IQ 7X - IQ7X-96-*-US

Table 4.13: Internal Q Cable VRise (Portrait Cable, Q-12-10-240) IQ 7X 208V P

IQ 7X Microinverters per branch

1 2 3 4 5 6 7 8 9 10

Current (A) 1.51 3.03 4.54 6.06 7.57 9.09 10.60 12.12 13.63 15.14

VRise (V) 0.03 0.08 0.15 0.26 0.38 0.54 0.72 0.92 1.15 1.41

VRise (%) 0.01 0.04 0.07 0.12 0.18 0.26 0.34 0.44 0.55 0.68

Table 4.14: Internal Q Cable VRise (Landscape 60-Cell Cable, Q-12-17-240) IQ 7X 208V L-60

IQ 7X Microinverters per branch

1 2 3 4 5 6 7 8 9 10

Current (A) 1.51 3.03 4.54 6.06 7.57 9.09 10.60 12.12 13.63 15.14

VRise (V) 0.04 0.12 0.24 0.39 0.59 0.83 1.10 1.42 1.77 2.17

VRise (%) 0.02 0.06 0.11 0.19 0.28 0.40 0.53 0.68 0.85 1.04

Table 4.15: Internal Q Cable VRise (Landscape 72-Cell Cable, Q-12-20-200) IQ 7X 208V L-72

IQ 7X Microinverters per branch

1 2 3 4 5 6 7 8 9 10

Current (A) 1.51 3.03 4.54 6.06 7.57 9.09 10.60 12.12 13.63 15.14

VRise (V) 0.05 0.14 0.27 0.45 0.68 0.95 1.27 1.63 2.04 2.49

VRise (%) 0.02 0.07 0.13 0.22 0.33 0.46 0.61 0.78 0.98 1.20

24 © 2018 Enphase Energy Inc. All rights reserved. November 2018