C400N5C - A042j404 Cummins Gta38
C400N5C - A042j404 Cummins Gta38
Gaseous Fuel
Generator Set
GTA38 Engine Series
400 kW 50 Hz
500 kW - 690 kW 60 Hz
Non-regulated
Description Control System - The PowerCommand®
This Cummins Inc. commercial Generator electronic control is standard equipment
Set (GenSet) is a fully integrated power and provides total GenSet system
generation system providing optimum integration, including automatic remote
performance, reliability, and versatility for starting/stopping, precise voltage
stationary standby and continuous power regulation, alarm and status message
applications. display, AmpSentry™ protective relay,
output metering, and auto-shutdown at
fault detection.
Features
Cummins Heavy-Duty Engine - Rugged
4-cycle industrial spark-ignited engine Warranty and Service - Backed by a
delivers reliable power, low emissions, and one-year warranty and worldwide
quick response to load changes. distributor network.
Engine Specifications
Base Engine Cummins Model GTA38
Displacement 37.7 L (2301 in3)
Overspeed Limit 2100 rpm
Regenerative Power 19.7 kW (C500N6B model)
Cylinder Block Configuration 550 kW (C580N6, C635N6, C690N6 models)
Cranking Current Cast iron with replaceable wet cylinder liners
Battery Charging Alternator 1400 CCA (cold soak at -18 °C (0 °F) or above)
Battery Type 43 amps
Starting Voltage 8D (x2)
Standard Cooling System 24-volt, negative ground
Lube Oil Filter Types See derates on Engine Data Sheet
Total System Back Pressure Allowed 51 mm Hg (2 in. Hg)
Silencer Back Pressure (Factory Enclosed Units Only) 5.6 mm Hg (.22 in. Hg)
Alternator Specifications
Design Brushless, 4-pole, drip-proof revolving field
Stator 2/3 pitch
Rotor Direct-coupled by flexible disc
Insulation System Class H per NEMA MG1-1.65 or better
Standard Temperature Rise * 125 °C
Exciter Type Permanent Magnet Generator (PMG)
Phase Rotation A (U), B (V), C (W)
Alternator Cooling Direct-drive centrifugal blower
* For UL 1004 ratings, refer to temperature rise at 120 °C or below, and ambient temperature up to 40 °C
C400N5C/C580N6 Cont. Amps N/A 1735 1640 1504 950 867 820 752 601
C580N6 Standby Amps N/A 2012 1903 1744 1102 1006 951 872 698
C635N6 Standby Amps N/A 2203 2083 1910 1206 1102 1042 955 764
C690N6 Standby Amps N/A 2394 2264 2075 1310 1197 1132 1037 830
Fuel Consumption
Rated Load Fuel Consumption in Standard Cubic Feet per Hour (CFH)
Model Fuel Type 1/4 1/2 3/4 Full
Fuel inlet pressure at GenSet connection: 381 to 508 mm WC (15 to 20 in. WC)
Exhaust System
• GenSet mounted muffler (enclosure models, only)
• Catalyst available upon request
Generator Set
• Batteries and battery charger
• Main line circuit breaker and spring isolators This outline drawing is for reference only.
• PowerCommand® Network Aux 101, 102 module Do not use for installation design.
• Modbus® to BACnet™ Module
Dim “A” Dim “B” Dim “C”
• Weather protective enclosure (F001) with silencer
mm (in.) mm (in.) mm (in.)
• Level I and Level II enclosure w/silencer
• Audible alarm, remote drains, and remote annunciator All Models 4756 (187) 2330 (92) 2721 (107)
panel
• 2-year standby and 5-year basic power warranty NOTE: Consult drawings for applicable weights. Contact the factory for additional
information. See enclosure Specification Sheet for enclosure dimensions.
(model-specific)
Warning: Backfeed to a utility system can cause electrocution and/or property damage. Do not connect GenSets to
any building electrical system except through an approved device or after the building main disconnect is open. Neutral
connection must be bonded in accordance with National Electrical Code.
www.power.cummins.com