SDM630MV CT
Din Rail Smart Energy Meter for Single and Three Phase Electrical Systems
USER MANUAL
2016 V3.5
JIAXING EASTRON ELECTRONIC INSTRUMENTS CO.,LTD.
TEL:0086-573-83698881/83698882 FAX: 0086-573-83698883
Web: www.eastrongroup.com Email: [email protected]
Add: No.1369. Chengnan Road, Nanhu District, Jiaxing City, Zhejiang, China 314001. -1-
EASTRON SDM630MV CT User Manual
1. Introduction
This document provides operating, maintenance and installation instructions. The unit measures
and displays the characteristics of three phase four wires(3p4w) supplies, including voltage,
frequency, current, power ,active and reactive energy, imported or exported. Energy is measured
in terms of kWh, kVArh. Maximum demand current can be measured over preset periods of up to
60minutes. In order to measure energy, the unit requires voltage and current inputs in addition to
the supply required to power the product. The requisite current input(s) are obtained via current
transformers(CT).
This meter can be configured to work with a wide range of CTs with 0.33V output, giving the unit
a wide range of operation. Built-in interfaces provides pulse and RS485 Modbus RTU outputs.
Configuration is password protected.
This unit can be powered from a separate auxiliary(AC or DC)supply. Alternatively it can be
powered from the monitored supply, where appropriate.
Two pulse output indicates real-time energy measurement. An RS485 output allows remote
monitoring from another display or a computer.
2. Start Up Screens
The first screen lights up all display segments and
can be used as a display check.
After a short delay, the screen will display active energy measurements.
3. Measurements
The buttons operate as follows:
Selects the Voltage and Current display screens
In Set-up Mode, this is the “Left” or “Back” button.
3.3 Power
4. Setting Up
To enter set-up mode, pressing the button for 3 seconds, until the password screen
appears.
Setting up is password-protected so you must enter the correct password (default ‘1000’) before
processing. If an incorrect password is entered, the display will show: PASS Err
To exit setting-up mode, press repeatedly until the measurement screen is restored.
1) Use the and buttons to select the required item from the menu. selection
does not roll over between bottom and top of list
3) If an item flashes, then it can be adjusted by the and buttons. If not, there
maybe a further layer.
4) Having selected an option from the current layer, press to confirm your selection.
The SET indicator will appear.
5) Having completed a parameter setting, press to return to a higher menu level. The
SET indicator will be removed and you will be able to use the and buttons for
further menu selection.
1) The current digit to be set flashes and is set using the and buttons
2) Press to confirm each digit setting. The SET indicator appears after the last digit has
JIAXING EASTRON ELECTRONIC INSTRUMENTS CO.,LTD.
TEL:0086-573-83698881/83698882 FAX: 0086-573-83698883
Web: www.eastrongroup.com Email: [email protected]
Add: No.1369. Chengnan Road, Nanhu District, Jiaxing City, Zhejiang, China 314001. -8-
EASTRON SDM630MV CT User Manual
been set.
3) After setting the last digit, press to exit the number setting routine. The SET indicator
will be removed.
Press to exit the number setting routine and return to the Set-up menu.
Press to exit the DIT selection routine and return to the menu.
4.4 CT
The CT option sets the primary current(CT2 fixed 0.333V) of the current transformer (CT) that
wires to the meter.
Secondary CT(CT2)
It’s fixed 0.333V, and can not be set.
4.5 PT
The PT option sets the secondary voltage (PT2 100 to 500V) of the Voltage transformer (PT) that
wires to the meter.
Secondary PT setting
For example, if set the ratio to be 100,it means the primary voltage equals secondary voltage
x100
Use this section to set up the relay pulse output—Units: kWh, kVArh
On completion of the entry procedure, press to confirm the setting and press
Use and buttons to choose pulse rate. On Completion of the entry procedure,
press to confirm the setting and press to return to the main set up menu.
Use and buttons to choose pulse width. On Completion of the entry procedure,
press to confirm the setting and press to return to the main set up menu.
4.7 Communication
There is a RS485 port can be used for communication using Modbus RTU protocol. For Modbus
RTU, parameters are selected from Front panel.
On completion of the entry procedure, press button to confirm the setting and press
On Completion of the entry procedure, press to confirm the setting and press
4.7.3 Parity
On completion of the entry procedure, press to confirm the setting and press
On completion of the entry procedure, press to confirm the setting and press
4.8 CLR
The meter provides a function to reset the maximum demand value of current and power.
Press to confirm the setting and press to return to the main set up menu.
5 Specifications
5.1 Measured Parameters
The unit can monitor and display the following parameters of four phase four wire(3p4w) supply.
5.3 Accuracy
Voltage 0·5% of range maximum
Current 0·5% of nominal
Frequency 0·2% of mid-frequency
Power factor 1% of unity (0.01)
Active power (W) ±1% of range maximum
Reactive power (VAr) ±2% of range maximum
Apparent power (VA) ±1% of range maximum
Active energy (Wh) Class 1 IEC 62053-21
Reactive energy (VARh) ±2% of range maximum
Total harmonic distortion 1% up to 31st harmonic
5.7 Environment
Operating temperature -25°C to +55°C*
Storage temperature -40°C to +70°C*
Relative humidity 0 to 90%, non-condensing
Altitude Up to 2000m
Warm up time 1 minute
5.8 Mechanics
DIN rail dimensions 72 x 94.5 mm (WxH) per DIN 43880
Mounting DIN rail (DIN 43880)
Sealing IP20 (minimum)
Material Self-extinguishing UL94 V_0
6 Dimensions
7 Installation