LED indicators alarms and troubleshooting 2. Press set and enter the button sequence of the
password (see above).
Refrigeration system failure, see the Ct
on when the compressor is 3. Check the ems controller reboots.
compressor parameter for details.
running.
Press down to clear the alarm and wait ten test routine
on when the evaporator fan minutes then check that the cooler is
fan To test the relays, temperature sensors, and motion sensor:
is running. working.
1. Access the menu and press down once to tst.
Appliance sensor failure.
standby mode
on if the standby mode 2. Press set and check display shows 888.
temperature Plug and unplug the sensor to ensure
temperature is disabled.
disable sensor is connected properly. 3. Press set to enter the menu test check display shows
1.0. Then:
Plug in another sensor, if display changes to
motion on when motion detected. USE, replace sensor. If display shows PF1, a. press down and check display shows 2.0
change the ems controller. b. press up and check display shows 3.0
cooler If controller is in the operational mode, c. press defrost and check display shows 4.0.
buttons lights do
ensure that the light switch inside the
not switch 4. Press set and defrost at the same time to start the
on cooler is switched on. relay test rel. Then:
set up no power Ensure the 12VAC plug is connected. Then, a. press down to test the evaporator fan.
check that 120VAC is going into the primary b. press up to test the lights.
and for 12 to 13VAC from secondary is
c. press set to test the compressor
down connected to the ems controller.
defrost 5. Press set and defrost at the same time to test the
Recommended spare parts inventory: analogue inputs AnA.
Coke part no. description qty 6. Press up and then press set to view the appliance
power up sequence sensor temperature.
ems55advanced 2
121829
integrated motion sensor
Checks all the display 7. Press set and defrost at the same time to test the
1 sensor wire, 2-way molex, 2 or 3
elements are working. 123660 motion detector Pir.
1.5 metres
8. Press defrost and then wave hand in front of the
Displays the firmware Parts are available for purchase from Coca-Cola Parts.
2 motion sensor. Check that the displayed number
version.
Phone: 1-800-638-2653 increases.
Displays the appropriate Website: www.coca-colaparts.com 9. Press set and defrost at the same time to exit the test
3 checksum for the cooler mode. The controller then resets and displays USE or
model. the appliance sensor temperature.
EMS55A-WORKAID-PARAMETERS-Iss3
parameters Fan set point is the temperature that if Fan cycle off is the inactive period of the
exceeded results in the evaporator fan evaporator fan while the compressor is off.
To view the parameter settings:
running continuously even if the door is Range is 30 minutes.
1. Access the menu and check PS is displayed opened.
Display stability sets the rate of change of
2. Press set to scroll through the parameters. Set to 52ºF. the displayed temperature.
Condenser high temperature is the Set to 64.
Celsius (°C) or Fahrenheit (°F) is the maximum permitted temperature measured
High voltage protection. Not used.
controller temperature scale. in the refrigeration system. On reaching Ht,
the controller disables the compressor and Set to 250 (disabled).
Set to 01 (Fahrenheit).
activates an alarm. Low voltage protection. Not used.
Set Point temperature in Fahrenheit (SPF) Set to 32ºF (disabled). Set to 90 (disabled).
or Celsius (SPC) sets the lower operational
mode temperature. Compressor rest time is the minimum time Buzzer enable is the option to disable a
between compressor cycles. warning buzzer for alarm conditions. Does
Range is 37°F.
Set to 3 minutes. not affect door alarms.
Differential added to the set point
Set to 0 (disabled).
temperature that sets the upper operational Delay to standby is the delay in switching
mode temperature. to standby from the operational mode. Buzzer duration for open door alarm
Global default is 7°F. Set to 0 minutes (no delay). conditions. After the buzzer duration, the
controller switches off the compressor.
Calibrate adds an offset to temperatures Light delay is the delay to switch off the
cooler lights after switching to the standby Set to 30 seconds.
measured by the appliance sensor.
mode. Alarm delay is the maximum time a door
Set to 0°F.
Set to 30 minutes. can be open before sounding the alarm
Standby set point sets the lower standby
buzzer. If disabled, the door switch is also
mode temperature. Standby restart is the maximum time
disabled.
Range is 45°F. allocated to lower the product temperature
to the set point temperature from the Set to 0 (door switch is disabled).
Standby differential is the temperature standby mode. Activity frequency is the minimum number
added to SSP that sets the upper standby of door openings or motion counts to indicate
Range is 120 minutes.
mode temperature. an active 30 minute period in the self-
Range is 7°F Refrigeration system failure is the
learning matrix.
maximum continuous runtime of the
Uninterrupted pull down is the Set to 3 (automatic).
compressor without reaching the set point
temperature that if exceeded starts an
temperature. Standby temperature disable is the option
uninterrupted pull down until the set point
Set to 72 hours. to maintain the operational mode
(SP) temperature.
Defrost interval is the period between the temperature at all times.
Set to 55ºF.
end of a defrost cycle and beginning of the Set to 1 (standby temperature is disabled).
Freeze-up protection is the temperature to next defrost cycle. Learning period defines 1-day or 7-day
disable the compressor and enable the
Range is 6 hours. learning period.
evaporator fan to prevent freeze up due to
low temperature. Defrost duration is the maximum time of a Set to 1 (7 days).
EMS55A-WORKAID-PARAMETERS-Iss3