Foundation Chapter 4
Foundation Chapter 4
4.1 INTRODUCTION
The principles of design of centrally loaded footings have been already explained in Chapter 3.
In this chapter, we will deal with a few examples to illustrate these principles.
36
Design of Centrally Loaded Isolated Footings and Column Pedestals 37
Service load
Area, A = -
Allowable bearing capacity
Step 2: Soil reaction for limit state design.
_ Factored load _ P
Area L2 I
Step 3: Find the depth for one-way shear. By considering one-way shear, the depth d is
obtained from the shear at section at X\X{ at d from the face of the column for
a square footing (L x L). As seen in Sec. 3.6.2, it can be evaluated from the
following formula.
38 Design of Reinforced Concrete Foundations
(4J)
700 + 2q
[Note: The actual value of Tc will depend on the percentage of main steel present
at the section continued for a distance d on both sides of the section. Some
recommend adopting the lowest value of Tc (namely, the one corresponding to
a percentage of steel equal to 0.15%) for routine calculations, others recommend
that the minimum main steel in all foundations should be 0.2 to 0.25% as it is
difficult to repair once foundations are built. Distribution steel may be only
0.12% for Fe 415 steel.]
Step 4: Find the depth for resistance in the building. The depth from bending moment
consideration is obtained by taking moments at the face of the column XX.
L(L - a)2
= ÿ-(L-a)2
oL
(4.2)
M = KfckLd2 (as single reinforced beam). [Note the whole length L is assumed
to resist bending.]
Hence,
M.. n>/2
d= [For Fe 415, K = 0.138 or « 0.14] (4.3)
KfckL
Step 5: The depth should satisfy two-way shear or punching shear at section dl2 from
the column face.
Critical parameter = 4{a + d). Considering equilibrium of forces, we get
(P/L2) LL2 - (a + d)2J = 4(a + d) dxp
Hence
q{L2 - (a + d)2) < 4{a + d) dfp
where rp =0.25ÿ//ÿÿ It is easier to check for the value of rp in this expression
for the value of d obtained from Eqs. (4.1) and (4.3) than to solve the equation
for d. Alternately, if the R.H.S is equal to or greater than P, then the design is
safe against punching shear.
Step 6: Take the larger of the depths as obtained from steps 3 to 5. Provide the cover.
Step 7: Find the area of steel required from the value of M/Ld2 and percentage of steel
p using Table B.l or by M = A/Jd using Figure 2.2.
(Use M/Ld2 SP 16 for easy determination of the area of steel.)
Also, check for minimum steel percentage and steel spacing as given in
Sec. 22.7.
Design of Centrally Loaded Isolated Footings and Column Pedestals 39
Step 8: Check the development length. Select the size of the bar whose development
length is less than II2(L - a); otherwise, provide the development length by 90°
bend at the end.
Step 9: Detail steel as discussed in Sec. 3.7.
(One of the methods to decrease steel in footings is to adopt a liberal depth for
the footing.)
B-H
\ 1
Mxx /
\T>"/
\ibJ<
!IN_7 r
~tu \
/
/
/
The procedure for the design of sloped footings varies among designers. This is due to
the fact that there have not been many large-scale tests on sloped footings, and an accepted
yield line pattern at the failure of centrally loaded and eccentrically loaded sloped footings is
not yet available. As also stated in Sec. 22.7, the minimum steel needs to be checked at the mid-
depth of sloped footings after it is designed as an ordinary footing.
(4.4)
8B
Similarly,
P
Myy = — if' - a)2 (for steel in the y-direction) resisted by length b (4.4a)
8L
Method (b): A less conservative method, which will give a lesser depth of footing
is to assume that the moment to be resisted by column faces is that due to the loads
in the trapezoidal area only, as shown in Figure 4.1. Accordingly,
Mxx = (Pressure) x (CG of the area)
Myy = -
7 L + aÿ ( B-bX X r 2L + aÿ 1 r B-b>
LB LI 2 j to {L -Fa j 3 I 2 j
P
Mxx = 2MB (2L + a)(B - by (for steel in the X-direction) (4.5)
Similarly,