100% found this document useful (1 vote)
598 views

InteliSCADA 2 1 0 Global Guide

scada of comap manual
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
598 views

InteliSCADA 2 1 0 Global Guide

scada of comap manual
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 130

InteliSCADA

Monitoring tool
for ComAp devices

SW version 2.1.0
1 Document information 6
2 Getting started 9
3 Designer 22
4 Runtime 50
5 Security 60
6 Instruments 61
7 Automatically generated screen 110
8 Troubleshooting 122

Copyright © 2021 ComAp a.s.


Written by ComAp
Prague, Czech Republic
ComAp a.s., U Uranie 1612/14a,
170 00 Prague 7, Czech Republic
Tel: +420 246 012 111
E-mail: [email protected], www.comap-control.com Global Guide
Table of contents
1 Document information 6
1.1 Clarification of Notation 6
1.2 About this guide 6
1.3 Legal notice 6
1.4 Document history 8

2 Getting started 9
2.1 Welcome 9
2.2 Requirements 9
2.3 Installation 10
2.3.1 Installation 10
2.3.2 Start Runtime or Designer 10
2.3.3 Custom branding 10
2.3.3.1 Custom global guide 11
2.3.3.2 Custom company logo 11
2.3.4 InteliSCADA as service 11
2.4 Licenses 12
2.4.1 License activation 15
2.4.2 Clients limitation 16
2.4.3 Site limitation 16
2.5 Supported ComAp devices 17
2.5.1 Controllers 17
2.5.2 Communication modules 18
2.6 Backup & restore 19
2.6.1 How to back up the data 19
2.6.2 How to restore the backed up data 19
2.6.3 Automatic site backup 20
2.7 Uninstallation 21

3 Designer 22
3.1 Sites 25
3.1.1 Add site 26
3.1.2 Edit site 27
3.1.3 Import site 28
3.2 Devices 28
3.2.1 Add device 29
3.2.2 Setting up controller username and password 31

InteliSCADA 2.1.0 Global Guide 2


3.2.3 Connection status 33
3.3 Editor 34
3.3.1 Data points 34
3.3.2 Importing data points 34
3.3.3 Navigation in Editor 35
3.3.4 Toolbar 36
3.3.5 Sidebar 37
3.3.6 Screens panel 37
3.3.7 Instruments panel 38
3.3.8 Screen Content panel 39
3.3.9 Properties panel 40
3.3.10 Image gallery panel 41
3.3.11 Screen canvas 42
3.3.12 How to add instrument on the screen 42
3.3.13 Editing instruments 46
3.3.14 Shortcuts in Editor 47
3.3.14.1 Shortcuts in screen canvas 47
3.3.14.2 Shortcuts in Screen Content panel 47
3.4 Preview 47
3.4.1 Preview restriction 48
3.4.2 Screens overview 49

4 Runtime 50
4.1 Navigation in Runtime 50
4.1.1 Runtime toolbar 50
4.2 Sites 52
4.3 Setpoints 52
4.3.1 Edit setpoint 53
4.4 Values 55
4.5 History 55
4.5.1 History filters 58
4.5.2 History columns 58
4.5.3 Exporting history 59
4.6 In-progress indication 59

5 Security 60

6 Instruments 61
6.1 Instruments specific properties 62
6.1.1 Warning limits 62

InteliSCADA 2.1.0 Global Guide 3


6.1.2 Scale 62
6.1.3 Data point selection 63
6.1.4 Color picker 65
6.2 Alarm List 66
6.3 Analog Meter 69
6.4 Bar Graph 72
6.5 Breaker 76
6.6 Breaker Button 77
6.7 Bus 78
6.8 Busbar 79
6.9 Control Button 80
6.10 Data Row 82
6.11 Engine 84
6.12 Fault Reset 85
6.13 Generator 86
6.14 Horn Reset 87
6.15 IFrame 87
6.16 Image 90
6.16.1 Image source dialog 92
6.16.2 Dynamic Image 93
6.17 LED 93
6.18 Line 95
6.19 Load 95
6.20 Mains 96
6.21 Markdown Text 97
6.22 Mode Selector 100
6.23 Multi Alarm List 101
6.24 Rectangle 103
6.25 Start Engine 104
6.26 Stop Engine 105
6.27 Trend 106
6.28 Wire Junction 108

7 Automatically generated screen 110


Device templates 111
Controllers 111
Communication modules 120

8 Troubleshooting 122
8.1 Connection to server 122

InteliSCADA 2.1.0 Global Guide 4


8.2 Instrument non-standard states 124
8.3 Device column template states 124
8.4 Database compatibility 127
8.5 Error and warning notifications 128
8.5.1 Data point import notifications: 128
8.5.2 Communication error notifications: 129
8.5.3 License error notifications: 130
8.5.4 Disk space notifications: 130
8.6 Reporting an issue 130

InteliSCADA 2.1.0 Global Guide 5


1 Document information
1.1 Clarification of Notation 6
1.2 About this guide 6
1.3 Legal notice 6
1.4 Document history 8

1.1 Clarification of Notation


Note: This type of paragraph calls the reader’s attention to a notice or related theme.

IMPORTANT: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.

Example: This type of paragraph contains information that is used to illustrate how a specific function
works.

1.2 About this guide


This Global Guide describes how to use InteliSCADA monitoring tool and contains general information about:
How to install and uninstall InteliSCADA
Application structure (Runtime and Designer)
Site management and monitoring
Device management
Screen management
Editor features
Preview functionality

1.3 Legal notice


This End User's Guide/Manual as part of the Documentation is an inseparable part of ComAp’s Product
and may be used exclusively according to the conditions defined in the “END USER or Distributor LICENSE
AGREEMENT CONDITIONS – COMAP CONTROL SYSTEMS SOFTWARE” (License Agreement) and/or in
the “ComAp a.s. Global terms and conditions for sale of Products and provision of Services” (Terms) and/or in
the “Standardní podmínky projektů komplexního řešení ke smlouvě o dílo, Standard Conditions for Supply of
Complete Solutions” (Conditions) as applicable.
ComAp’s License Agreement is governed by the Czech Civil Code 89/2012 Col., by the Authorship Act
121/2000 Col., by international treaties and by other relevant legal documents regulating protection of the
intellectual properties (TRIPS).
The End User and/or ComAp’s Distributor shall only be permitted to use this End User's Guide/Manual with
ComAp Control System Registered Products. The Documentation is not intended and applicable for any
other purpose.

InteliSCADA 2.1.0 Global Guide 6


Official version of the ComAp’s End User's Guide/Manual is the version published in English. ComAp
reserves the right to update this End User's Guide/Manual at any time. ComAp does not assume any
responsibility for its use outside of the scope of the Terms or the Conditions and the License Agreement.
Licensed End User is entitled to make only necessary number of copies of the End User's Guide/Manual. Any
translation of this End User's Guide/Manual without the prior written consent of ComAp is expressly
prohibited!
Even if the prior written consent from ComAp is acquired, ComAp does not take any responsibility for the
content, trustworthiness and quality of any such translation. ComAp will deem a translation equal to this End
User's Guide/Manual only if it agrees to verify such translation. The terms and conditions of such verification
must be agreed in the written form and in advance.
For more details relating to the Ownership, Extent of Permitted Reproductions Term of Use of the
Documentation and to the Confidentiality rules please review and comply with the ComAp’s License
Agreement, Terms and Conditions available on www.comap-control.com.
Security Risk Disclaimer
Pay attention to the following recommendations and measures to increase the level of security of ComAp
products and services.
Please note that possible cyber-attacks cannot be fully avoided by the below mentioned recommendations
and set of measures already performed by ComAp, but by following them the cyber-attacks can be
considerably reduced and thereby to reduce the risk of damage. ComAp does not take any responsibility for
the actions of persons responsible for cyber-attacks, nor for any damage caused by the cyber-attack.
However, ComAp is prepared to provide technical support to resolve problems arising from such actions,
including but not limited to restoring settings prior to the cyber-attacks, backing up data, recommending other
preventive measures against any further attacks.
Warning: Some forms of technical support may be provided against payment. There is no legal or factual
entitlement for technical services provided in connection to resolving problems arising from cyber-attack or
other unauthorized accesses to ComAp's Products or Services.
General security recommendations and set of measures
1. AccessCode
• Change the AccessCode BEFORE the device is connected to a network.
• Use a secure AccessCode – ideally a random string of 8 characters containing lowercase, uppercase letters
and digits.
• For each device use a different AccessCode.
2. Password
• Change the password BEFORE the device enters a regular operation.
• Do not leave displays or PC tools unattended if an user, especially administrator, is logged in.
3. Controller Web interface
• The controller web interface at port TCP/80 is based on http, not https, and thus it is intended to be used only
in closed private network infrastructures.
• Avoid exposing the port TCP/80 to the public Internet.
4. MODBUS/TCP
• The MODBUS/TCP protocol (port TCP/502) is an instrumentation protocol designed to exchange data
between locally connected devices like sensors, I/O modules, controllers etc. From it’s nature it does not
contain any kind of security – neither encryption nor authentication. Thus it is intended to be used only in
closed private network infrastructures.

InteliSCADA 2.1.0 Global Guide 7


• Avoid exposing the port TCP/502 to the public Internet.
5. SNMP
• The SNMP protocol (port UDP/161) version 1,2 is not encrypted. Thus it is intended to be used only in
closed private network infrastructures.
• Avoid exposing the port UDP/161 to the public Internet.

1.4 Document history


Revision number Related sw. version Date Author
6 2.1.0 8.10.2021 Vlastimil Petrucha
5 2.0.0 17.6.2021 Vlastimil Petrucha
4 1.4.0 29.3.2021 Vlastimil Petrucha
3 1.2.6 27.10.2020 Vojtěch Skopal
2 1.1.0 26.6.2020 Vojtěch Skopal
1 1.0.48 9.4.2020 David Čermák

InteliSCADA 2.1.0 Global Guide 8


2 Getting started
2.1 Welcome 9
2.2 Requirements 9
2.3 Installation 10
2.4 Licenses 12
2.5 Supported ComAp devices 17
2.6 Backup & restore 19
2.7 Uninstallation 21

6 back to Table of contents

2.1 Welcome
Welcome to ComAp's InteliSCADA global guide. InteliSCADA is a monitoring tool for ComAp devices (see
Supported ComAp devices on page 17) and runs on Microsoft Windows operating system (see
Installation on page 10 for details). It supports both online and offline device connections. Devices can be
connected either via the Ethernet connection, AirGate connection, direct connection (using USB or RS232) or
offline connection (device connected to the offline archive only). Devices are managed in sites. There are two
applications accessible via pre-installed Windows Desktop shortcuts:
Designer (page 22) - Used to manage sites, devices and custom screens
Sites (page 25) tab - Add, edit or delete a site
Devices (page 28) tab - Add, edit or delete a device of the particular site
Editor (page 34) tab - Add, edit, delete or design a screen of the particular site
Preview (page 47) tab - Preview the automatically generated screen or the custom screen, for long-
term monitoring use the Runtime (page 50) instead
Runtime (page 50) - used for long-term site monitoring:
Sites (page 52) tab - Lists all sites available on the server
Opens particular site for monitoring (the site password is required)
Is used to monitor and control all devices of the particular site

2.2 Requirements
Microsoft Windows 10 64-bit or Windows 10 IoT 64-bit. Keep your SW updated (e.g. Windows operation
system, drivers, ...)
Web browser Google Chrome or Mozilla Firefox if running InteliSCADA in the browser
The latest firmware versions for all ComAp devices and other modules (e.g. CM-Ethernet, IB-COM etc.)
which will be connected to InteliSCADA.

InteliSCADA 2.1.0 Global Guide 9


Minimal hardware requirements:
Intel® Celeron® quad core processor J1900, 32 GB SSD (5 GB available space), 4GB RAM used for
example in ComAp industrial panel InteliVision 18Touch.
Installed InteliSCADA takes up 2 GB of disk space.
Performance recommendations:
The performance depends on the number and type of instruments on the screen and on the amount of
communicated data (number of connected devices and data points). A high-performance site configuration
for InteliVision 18Touch contains about 16 devices and 400 instruments per screen.

2.3 Installation
2.3.1 Installation
1. Get the latest InteliSCADA installation package
2. Run it and follow the on-screen instructions
3. Read and accept terms in the license agreement to continue installation
4. Select components to install. It is recommended to use the default installation
5. Enter the port number used by InteliSCADA server to listen on, except for the reserved ports from the TCP
and UDP list (Default = 8801)
6. If InteliSCADA is already installed on the computer, backup of user data is created automatically (see
Backup & restore (page 19))
7. Once the installation is finished, InteliSCADA service is started and following desktop shortcuts are
created:
a. InteliSCADA Designer
b. InteliSCADA Runtime

2.3.2 Start Runtime or Designer


To start Runtime or Designer use desktop shortcuts that were created during the installation process.
InteliSCADA Designer
InteliSCADA Runtime
To toggle between the fullscreen and windowed mode, press the key F11 on the keyboard. Press the key F5,
to manually refresh the active window.

2.3.3 Custom branding


There is a possibility to customize InteliSCADA application.
If a custom logo or custom global guide is required, it has to be provided together with the installation package
executable (InteliSCADA-Product-Suite-M.N.P.B.exe). If there is no requirement for customization, the
default ComAp branding is applied.
The custom logo and global guide must be added properly following these procedures:

InteliSCADA 2.1.0 Global Guide 10


2.3.3.1 Custom global guide
Name of the document must be GlobalGuide.pdf
The document location must be as follows (path relative to the installation package):
.\branding\docs\GlobalGuide.pdf

2.3.3.2 Custom company logo


the name of the logo must be company-logo.svg and the logo must in SVG format
The logo location must be as follows (path relative to the installation package): 
.\branding\images\company-logo.svg
See the branding folder for reference:

2.3.4 InteliSCADA as service


In Microsoft Windows operating system InteliSCADA server starts as ComApInteliSCADAService service.
The service is started automatically after each MS Windows restart. In case the service stops working, it is
recommended to restart MS Windows.
The service can be started, stopped and restarted manually in Task manager:
1. Open Windows Start menu
2. Type "Task manager"
3. Click on "Task manager" application shortcut
4. Go to "Services" tab in Task manager
5. Right-click on "ComApInteliSCADAService" to display context menu

InteliSCADA 2.1.0 Global Guide 11


Image 2.1 InteliSCADA as service – task manager

2.4 Licenses
Runtime (page 50) supports 3 license types according to your data requirements (Designer (page 22)
doesn't require any license activation). Currently available license types and their limits are listed in the table
below.

License Type
Maximum number per site
Lite Pro Pro+
Data Points 100 400 10000
Devices 32 32 32
Communication Gateway Unsupported Supported Supported

Note: One data point from one device used on multiple instruments and/or screens counts as one data point.

To see information about licenses go to Designer and open the License Details dialog from the Settings
section available in the Device tab, Editor tab or Preview tab.

InteliSCADA 2.1.0 Global Guide 12


If any license limit is exceeded for a particular site, it is not possible to open it in Runtime until the "Required
License" type is activated. However, it is still possible to work with the site in the Designer. The information
about the required license for the particular site is displayed in the License Details dialog in the Designer and
also in the Sites tab in the Runtime (see Navigation in Runtime on page 50).
In Runtime, there are symbols that indicate whether the site complies with the current license.
The site complies with the current license (no limit exceeded)

The site doesn't comply with the current license (any limit of currently used license exceeded)

InteliSCADA 2.1.0 Global Guide 13


To see the required license for a particular site or current license simple click on the red dollar button
in Runtime. It is possible to either activate higher license (see License activation (page 15)) or modify the
site in Designer to comply with the current license limits

If the number of data points exceeds the limits of Pro+ license, the required license will be of type
'Unavailable' and the site will not be possible to open in Runtime. To open it in Runtime, please modify the site
in Designer to meet the requirements of available licenses.

InteliSCADA 2.1.0 Global Guide 14


2.4.1 License activation
A license can be activated only from Runtime
either using License Activation dialog, which can be opened from Settings section

or using extended License Activation dialog, which can be opened from Sites of Runtime by clicking on
the red dollar button of particular site

To activate a license follow this procedure:

Copy the Hardware ID( ) and send it, including required type of license, to your distributor (e.g. by
email)

Distributor will send back the activation code. Copy and paste it to the Activation Code input field
Click on the Activate License button to activate the license
There will be a notification in the dialog about the activation result and the Current License field will
change accordingly
IMPORTANT: Activation Code is generated based on the Hardware ID, i.e. for the specified PC
hardware, where InteliSCADA is installed. If any part of the hardware is changed, a new license
activation code might be required.

InteliSCADA 2.1.0 Global Guide 15


2.4.2 Clients limitation
Only one Designer and one Runtime can be opened at the same time. Any additional clients are rejected by
the server and the information page is returned:

2.4.3 Site limitation


Up to 32 devices can be added into a site. If the user tries adding another device by clicking on the "Add
Device" button and there are already 32 devices in the site, a message is displayed, see the picture
below.

InteliSCADA 2.1.0 Global Guide 16


2.5 Supported ComAp devices
Supported ComAp devices and related applications are listed in the tables below. Each device application
displays predefined template on Automatically generated screen (page 110).

2.5.1 Controllers
ComAp controller Application
SPtM
InteliGen NT/NTC BaseBox MINT
SPI
SPtM
InteliGen NT/NTC BaseBox GeCon Marine MINT
SPI
SPtM
InteliGen NT/NTC BaseBox GeCon LandBased MINT
SPI
SPtM
InteliGen NT/NTC MINT
SPI
SPtM
InteliGen GSC/GSC-C MINT
SPI
SPtM
InteliSys NTC BaseBox MINT
SPI
SPtM
InteliSys NTC BaseBox GeCon Marine MINT
SPI
SPtM
InteliSys NTC BaseBox GeCon LandBased MINT
SPI
SPtM
InteliSys GSC-C MINT
SPI
SPtM
InteliSys Gas MINT
SPI
InteliSys NTC Hybrid MCB

InteliSCADA 2.1.0 Global Guide 17


ComAp controller Application
MGCB
MINT
MCB
InteliMains NT/NTC BaseBox MGCB
BTB
MCB
InteliMains NT MGCB
BTB
SPtM
InteliGen 200
MINT
SPtM
InteliGen 500
MINT
InteliLite AMF20 AMF
InteliLite AMF25 AMF
InteliMains 210 BTB BTB
MCB
InteliMains 210
MGCB
InteliLite 9 AMF
InteliLite 4 AMF 8 AMF
InteliLite 4 AMF 9 AMF
InteliLite 4 AMF 20 AMF
InteliLite 4 AMF 25 AMF
InteliLite 4 AMF 25 LT AMF
AS
InteliDrive DCU Industrial
SS
AUX
CMB
InteliDrive DCU Marine
EME
PRP

2.5.2 Communication modules


ComAp communication module Notes
Provided data points are limited to values and setpoints.
Other types like Alarm List or LEDs are not supported,
InteliGateway therefore they are not available in the Editor (page 34).
InteliFieldbus Gateway Although more devices can be connected to
InteliFieldbus Gateway, the gateway itself is considered
as one device in InteliSCADA.

InteliSCADA 2.1.0 Global Guide 18


2.6 Backup & restore
IMPORTANT: Every time you uninstall, re-install, upgrade or downgrade InteliSCADA a backup
folder with your data is automatically created.

A size of backup files depends on the sites configuration. Consider available free disk space for the new
backup. It is also possible to back up the data manually, see the chapter How to back up the data (page
19).

2.6.1 How to back up the data


To create a backup of data manually, make a spare copy of the complete directory
C:\ProgramData\ComAp PC Suite\InteliSCADA\.
IMPORTANT: We strongly recommend that you back up the data regularly to prevent potential
data loss. Most important is to back up data.db file that contains created sites and images.

Files cs-data.db and cs-archives.db can be deleted to save disk space - these files contain cache for faster
loading and will be generated again automatically.
It is also possible to backup automatically exported sites stored in C:\ProgramData\ComAp PC
Suite\InteliSCADA-Backup\Sites\. For more information see Automatic site backup on page 20.

2.6.2 How to restore the backed up data


Before backup restoration make sure that InteliSCADA service is not running (see InteliSCADA as service
(page 11)). If the service is running, stop it.
1. To find automatically backed up data, open Windows explorer and go to the specific backup folder:
C:\ProgramData\ComAp PC Suite\InteliSCADA-Backup\specific backup folder
contains today date & actual version of InteliSCADA (Backup[YYYYMMDDHHMMSS]-
[Version])
If the backup was made manually as described in chapter How to back up the data (page 19) you can
use the repository from manual backup.
2. Select all files and folders to be restored (data.db, License folder) and select Copy function

InteliSCADA 2.1.0 Global Guide 19


3. Paste copied files and folders to destination folder at C:\ProgramData\ComAp PC
Suite\InteliSCADA\

4. If there are any data in the destination folder, consider to make a backup before overwriting
5. Run InteliSCADA service again (see InteliSCADA as service (page 11))

2.6.3 Automatic site backup


Each site edited in Designer is automatically backed up to the specific folder after the site is closed. The
backup operation runs seamlessly in the background (temporary increase of the CPU and RAM usage may
occur).
In case of corruption or loss of the site it is possible to restore it using the "Import site" feature, see Import
site on page 28. Just select the site you want to recover from C:\ProgramData\ComAp PC
Suite\InteliSCADA-Backup\Sites\

InteliSCADA 2.1.0 Global Guide 20


2.7 Uninstallation
1. Open the Start menu
2. Select ComAp PC Suite
3. Select Uninstall InteliSCADA
Before uninstallation the backup of user data is automatically created, see Backup & restore (page 19)
During uninstallation you can remove the user data by checking the corresponding checkbox. If checked, the
following files are removed:
Sites
Log files
Activated license
Cached history

InteliSCADA 2.1.0 Global Guide 21


3 Designer
3.1 Sites 25
3.2 Devices 28
3.3 Editor 34
3.4 Preview 47

6 back to Table of contents


The first step in Designer is to create a site, see Sites on page 25. Once the site is created, devices can be
added into this site, see Devices on page 28. Afterward, the Automatically generated screen (page 110)
is updated and it is ready for monitoring. It is also possible to create custom screens in the Editor (page 34)
using these devices.

Image 3.1 Basic InteliSCADA Designer Workflow

Welcome screen of Designer is the Sites tab (list of sites):


Sites can be added, edited, deleted, imported and exported, see Sites on page 25

"Add Site" button – Creates a new site

"Import Site" button – Imports the site from the selected file (*.isx)

List of all sites available on the server


Site can be opened by:

Devices link – Opens the Devices tab for a particular site

Editor link – Opens the Editor tab for the site

Preview link – Opens the Preview tab with the default monitoring screen of the site

InteliSCADA 2.1.0 Global Guide 22


Designer toolbar:
Once the particular site is opened, the toolbar is divided in 3 main parts:

Toolbar sections Description


Tabs to navigate through Designer
Active tab is underlined (for reference see the Devices
tab in the picture above)
Sites tab – Opens the list of sites
Devices tab – Opens the list of a for the particular
Designer navigation
site
Editor tab – Opens the editor with the last selected
screen for the site
Preview tab – Opens the preview of the screen
opened in editor for the site
Buttons specific for the currently active tab
Devices tab:
"Add Device" button - Opens the dialog to add a
new device
Preview tab:
Setpoints button - Opens the dialog to monitor and
edit setpoints of any device in the particular site
Values button - Opens the dialog to monitor values
Tab specific buttons of any device in the particular site
History button - Opens the dialog with history
records from all devices in the site, see History
(page 55)
Screens button - Opens the screens overview
"Fit To Screen" button - Zooms the screen so the
whole screen is visible and fits the screen size
"Zoom 100%" button - Zooms the screen to the
screen's original size
Name of the open site
Name of the open screen (only if in the Editor tab or
Preview tab)
Connection Status button (only if in the Preview tab),
General
see Connection status (page 33)
Settings button
"Export All" (button is enabled only for open site) -
Exports all data of the specific site (site, devices

InteliSCADA 2.1.0 Global Guide 23


Toolbar sections Description
archives and logs are packed into a single ZIP file).
See also Reporting an issue (page 130)
"License Details" (button is enabled only for opened
site) - Opens the dialog with information about the
required license for particular site (enabled for open
site)
Manual - Opens the InteliSCADA global guide
About - Opens the dialog with information
aboutInteliSCADA

InteliSCADA 2.1.0 Global Guide 24


3.1 Sites
The Sites toolbar contains "Add Site" button (see Add site on page 26 for details) and "Import Site"
button (see Import site on page 28 for details)
The Sites tab contains following information:

Image 3.2 sites toolbar

# Site order in the list of sites

Site Name User defined site name

Last Update Date and time of the latest update

Devices link Link to the Devices tab for of the site

Editor link Link to the Editor tab with the default screen of the site

Preview link Link to the Preview tab with the default screen of the site

"Lock/Unlock Locks / unlocks the particular site. If the site is locked, it opens the dialog to
Site" button unlock it, otherwise it locks the site
"Site Runtime
Shows the Runtime URL link to the default screen for the site
Link" button

"Edit Site" button Opens the dialog for editing the site details (site name, password)

"Clone Site"
Creates a copy of the site with the same site password
button

InteliSCADA 2.1.0 Global Guide 25


Exports the site to a file (*.isx).
"Export Site"
Site, device archives and images are included. The exported site is
button
protected by the site password.
"Delete Site" Deletes the particular site.
button Important: Even the locked site can be deleted.
"Move Up/Down"
Drag & drop to change the site's order in the list of sites
button

3.1.1 Add site


Click on the "Add Site" button to add a new site

Required fields:

"Site Name" – User defined site name (supported up to 32 characters)

"Enter Password" – User defined password, see password requirements and its purpose in
Security (page 60)

"Retype Password" - Enter the password again

InteliSCADA 2.1.0 Global Guide 26


3.1.2 Edit site
Click on the "Edit Site" button to change the particular site details.

To change the site name only:

Keep the "Change connection details password" tick box unchecked

Enter Site Name


To change the site password:

It is necessary to check the "Change connection details password" tick box

Enter Current Password (required)

Enter New password (required)

Retype New Password (required)

InteliSCADA 2.1.0 Global Guide 27


3.1.3 Import site
Click on the "Import Site" button to import a site from the file (*.isx). The imported site will be locked and it is
necessary to know the password to unlock it. Usually, the site is prepared on the designer's laptop and then it
is imported to the client's laptop.

Required fields:

File Name – Click the Browse button to browse the file to be imported

Site Name – Enter the site name (up to 32 characters)


Validation errors can appear during the import process
Unsupported version of the file – Either the export file version or the export file content data version is
not supported
Bad format of the file – The file is corrupted or contains malformed data

3.2 Devices
List of devices for the particular site can be accessed by:

Clicking on the Devices link from the list of sites in Designer

InteliSCADA 2.1.0 Global Guide 28


Clicking on the Devices tab from Designer

The Devices tab contains following information:

Device order in the list of devices. It also defines device template order
# on Automatically generated screen (page 110) (template for device
# 1 is placed as first from the left side of the screen)

Device User defined device name entered when creating or updating device

Connection Communication type + detail (eg. IP: 10.72.0.205 or AirGate : xxxxxxx)

Device (Controller)
Device CAN bus address
Address

Data Points Count Total number of imported data points

Import Data Points


Tries to connect and re-import data points from the device
button

Edit Device button Opens a dialog for device details editing

Delete Device button Deletes the device

Move Up/Down button Drag & drop to change the device order in the list of devices

3.2.1 Add device


To add a new device click on the "Add Device" button

Fill in all required fields:

InteliSCADA 2.1.0 Global Guide 29


Device Name in
User defined device name in InteliSCADA
InteliSCADA
Necessary if a specific user/password access level should be applied
Username (Applies only for IGS NT, IM NT and InteliLite 4) (see Setting up
controller username and password on page 31 for details)
Device password (see Setting up controller username and
Password
password on page 31 for details)

Controller Address CAN address (for ComAp controllers 1 - 32)

Communication type options


Internet / Ethernet: Host/IP + port (default: 23)
AirGate: AirGate ID, AirGate Key, AirGate server (default:
airgate.comap.cz) + port (default: 44445)
Communication Type
Serial: COM number (eg. "COM8")
Archive: browse the offline archive you want to attach to
supported archive files are .ant, .aid, .ail3, .ail4, .aig3, .ail,
.accg.

Access Code Device access code

Import data points Once the device is added into the site it will try to connect to that device
from this device and import data points from it automatically (checked by default)

InteliSCADA 2.1.0 Global Guide 30


3.2.2 Setting up controller username and password
The process of logging in can vary depending on a controller type. Some types of controllers (e.g. IGS NT
family, IM NT family, InteliLite 4) require the username and password to log in, others (e.g. InteliLite, InteliGen
200, InteliGen 500, InteliMains 210, most of InteliDrive) require just the password.
Connecting to the controller is generally possible with or without logging in to the controller. By logging in
to the controller, its levels of access rights can be used.

The controller usernames are defined using InteliConfig (User management) or InteliMonitor (Admin
users) based on the controller type.

The list of usernames is also available in InteliMonitor in the Login (Enter password…) dialog for online
connection . List of usernames are not available for Archives .

The Username and Password are case sensitive.


The default administrator username also depends on the controller type and can be changed as well.
Therefore it is recommended to verify the current usernames in the controller before logging in
InteliSCADA.
The entered credentials are protected by the site password (see Security on page 60for details).
Most types of controllers can be also connected without logging in. This can be done by leaving Username
and Password fields empty. Access to data is restricted accordingly.
Logging in is mandatory for controllers with the new version of user management (e.g. InteliLite 4).
In InteliSCADA it is not possible to log in after establishing a connection (there is no Login button as in
other ComAp tools). The login data is defined in the Device form in Designer and it is used when
establishing a connection.

InteliSCADA 2.1.0 Global Guide 31


Here are some username and password setting examples for different ComAp controllers families
IGS NT family + IM NT family

Logged in Not logged in

Username required empty

Password required empty

IG 200, IG 500, IM 210, InteliLite, InteliLite NT and most of InteliDrive controllers

Logged in Not logged in

Username empty empty

Password required empty

InteliLite 4

InteliSCADA 2.1.0 Global Guide 32


Logged in Not logged in

Username required not supported

Password required not supported

3.2.3 Connection status


There is an overview of all devices, which are configured in the site with their current connection status. The
"Connection Status" dialog can be opened:
from the toolbar in Preview in Designer

from the toolbar in Runtime (see Runtime on page 50)

Connection Status button indicates overall status of devices

Disconnected – At least one device is disconnected

Connecting – At least one device is still connecting while others may be already
connected

Connected – All devices are connected

The "Connection Status" dialog provides this information:

All Devices – Total number of devices configured in the particular site

Disconnected – Total number of disconnected devices

Connecting – Total number of connecting devices

Connected – Total number of connected devices

# – Device order in the list of devices

Status – Device connection status

InteliSCADA 2.1.0 Global Guide 33


Disconnected – device is disconnected
Connecting – device is connecting
Connected – device is connected

Device Name – User defined device name used in InteliSCADA

Status Detail – Device detail connection status or connection error description, see also
Communication error notifications: (page 129)

Connection Type – Device communication type

3.3 Editor
Editor provides tools to:
Manage screens (by default every site contains one Automatically generated screen (page 110) and
one custom screen)
Place the instruments on the screen canvas, see How to add instrument on the screen (page 42)
Edit the properties of the screens and the instruments using the Properties panel (page 40)
To check how the edited screen looks and works online, see Preview (page 47)

3.3.1 Data points


InteliSCADA data point is a core component and represents data object, which refers to the single value or
setpoint of any device, but also represents more complex data objects like commands, alarm list data, LEDs,
etc. This concept allows to connect any instrument to any data point of any device.
To use data points in Editor the data points have to be imported first, see Importing data points (page 34)

3.3.2 Importing data points


IMPORTANT: if you want to connect an instrument to a device, it is necessary the device to be
defined and its data points imported:

There are two options how to import the data points


Manually for already existing device
Open the Devices tab
Click on the "Import Data Points" button for the particular device
It will try to connect to the device and import data points automatically
Automatically when a new device is added, see Add device (page 29)

IMPORTANT: If any error occurred during the data point import, the error notification is displayed
(see Error and warning notifications (page 128)

InteliSCADA 2.1.0 Global Guide 34


3.3.3 Navigation in Editor

Tab Description

Navigation Navigation tabs through Designer

Toolbar Editor specific buttons (see details below)

Buttons can open panels for:


Screens panel (page 37)
Sidebar
Instruments panel (page 38)
Image gallery panel (page 41)
Screen space to place instruments on (except for the
Canvas
Automatically generated screen (page 110))

Properties Properties panel for the selected screen or instrument

InteliSCADA 2.1.0 Global Guide 35


3.3.4 Toolbar
The toolbar can be useful especially when designing custom screens since the Automatically generated
screen (page 110) is read only.

Tab Description
Saves changes in the screen (changes are also automatically
Save
saved every 3 seconds)

Undo Takes back 1 step in the screen history

Redo Moves forward 1 step in the screen history

Copies the selected instrument to the clipboard (keyboard:


Copy
CTRL + C)
Cuts the selected instrument to the clipboard (keyboard: CTRL
Cut
+ X)
Opens the dialog with instructions (paste keyboard shortcut:
Paste
CTRL+V)

Delete Deletes the selected instrument

Moves the selected instrument to the end of the "Screen


Bring To Front
Content" list and to the foreground in the canvas
Moves the selected instrument to the top of the "Screen
Sent To Back
Content" list and to the background in the canvas
Allows to set the density of the grid or hide the grid completely.
Grid Density The color of the grid is set automatically to a color contrasting
to the Background Color of the screen.
Enables or disables the snap to grid feature. If the feature is
Snap To Grid enabled, instruments are automatically snapped to the grid
when they are being created, moved or resized.

Fit To Screen Sets the zoom value so the screen fits to canvas

Zoom Out Decreases the zoom value by 10 %

Zoom Sets the zoom value according to slider position

Zoom In Increases the zoom value by 10 %

Displays the current zoom value. It is also possible to set the


Zoom value
zoom value by entering the value into this input directly.

InteliSCADA 2.1.0 Global Guide 36


3.3.5 Sidebar

Tab Description

Screens button Opens Screens panel (page 37)

Instruments button Opens Instruments panel (page 38)

Image Gallery button Opens Image gallery panel (page 41)

3.3.6 Screens panel

Contains list of all screens available for the particular site

Auto-screen
It is always the first screen in the list
It is read only and cannot be deleted

InteliSCADA 2.1.0 Global Guide 37


By default it is marked as default screen
It is generated automatically, see Automatically generated screen (page 110)
Action buttons:

"Add Screen" button – Adds a new screen right below the active screen

"Clone Screen" button – Creates copy of the active screen below the active screen

"Delete Screen" button - Permanently deletes the active screen.

3.3.7 Instruments panel

Search field

Is used as a filter applied to the list of instruments


If empty, no filter is applied
Is case-insensitive

List of all supported instruments


Drag & drop the instrument on the custom screen canvas (be aware the Automatically generated
screen (page 110) is not editable, it is not possible to put any instrument on it)
See also Instruments (page 61) for more information about all supported instruments

InteliSCADA 2.1.0 Global Guide 38


3.3.8 Screen Content panel
The panel shows all instruments used in the screen. It also can be used either to select one or more
instruments or to change one or more instruments order.

Select the instrument


Instrument can be selected by the left mouse button
Multiple instruments can be selected
 by drawing rectangular selection area on the canvas

Only instruments that are fully in the area are selected

if the area starts on instrument, use SHIFT key while drawing

by selecting a list of instruments in the "Screen Content" panel

click on the first instrument by the left mouse button

press and hold the SHIFT key

click on the last instrument by the left mouse button

by the left mouse button on the instrument in the canvas or in the "Screen Content" list

Press and hold the CTRL key for multi-selection

by the key combination CTRL + A (selects all instruments)


Change the instrument order
when the instrument is visually placed over another one, then the order is shown
Default order of instruments represents the order in what they were added onto the canvas (new
instrument is placed at the end of the list, visually is on top of all instruments in the canvas)
Drag & Drop one or more instruments to change their order

InteliSCADA 2.1.0 Global Guide 39


Changing the order actually represents "Bring To Front" and "Send to Back" functionality described in
Toolbar (page 36)

3.3.9 Properties panel

Displays properties either for the selected screen or the selected instrument 
Screen properties:
General

Name – User defined screen name (fixed for "Auto-Screen")

Width – Screen width (up to 3840, fixed for "Auto-Screen")

Height – Screen height (up to 2160, fixed for "Auto-Screen")

Default Screen – Sets the screen as default for the particular site

Design

Background Color – Screen background color (not available for "Auto-Screen")


Instrument properties
E.g. position, size, device, scale limits, color, etc., see Instruments (page 61) for more information
Multiple instruments properties:
Device bulk change – Device that selected instruments are connected to (only if all selected
instruments support it)

InteliSCADA 2.1.0 Global Guide 40


3.3.10 Image gallery panel

Contains images, which can be placed on the canvas and used as a part of the scheme or as a
background of the screen. User images are also automatically added into this collection from any imported
site.
Predefined images can be filtered by the "Default" filter button
User images can be filtered by the "User" filter button
The panel provides following functionality:

"Add Image" button


Adds user image from the local storage
Supported image types: .gif, .jpg, .jpeg, .png, .svg, .bmp

"Filter" buttons
All - No filter applied
Default – Filters only predefined images
User – Filters only user images

Search by name or tags – Searches images with the name or tag containing the entered text. The
result is filtered by the Filter

Drag & drop the image from the panel onto the canvas

InteliSCADA 2.1.0 Global Guide 41


Click on the image to display more information

3.3.11 Screen canvas


Screen space to place instruments
New user screen is the same size as the current default screen
Size of the screen can be defined in the Properties panel (page 40)
Size of the canvas is reduced by the height of the top toolbar placeholder
Placeholder is the same height as the toolbar described in Navigation in Runtime (page 50)
It is not possible to place any instrument into the toolbar placeholder area

3.3.12 How to add instrument on the screen


1. Add "Device 1" to your site
2. Import data points for "Device 1", see Importing data points (page 34)

3. Go to the Editor tab, click on the Screens button in the Sidebar and select one of the available custom
screens

InteliSCADA 2.1.0 Global Guide 42


4. Go to the panel on the left, click on the "Instruments" button in the Sidebar and drag the instrument and
drop it on the canvas

Note: Enable Snap To Grid feature to arrange instruments easily, see Snap To Grid on page 36

InteliSCADA 2.1.0 Global Guide 43


5. The "Screen Content" panel shows all instruments used on the canvas

6. Select the instrument on the canvas (or in the "Screen Content" panel) and choose a device for this
instrument in the "Instrument Properties" panel (property Source / Device)

7. Open the "Data Point Selection" dialog (Properties / Data Source / Data Point)

8. Select the data point type in the "TYPES" column. Then select the data point group in the "GROUPS"
column. Finally select the specific data point in the "DATA POINTS" column.
The list of data points is filtered only to the data types supported by the selected instrument. If there are no
data points in the dialog, the import of the data points may not have been successful, see Importing data

InteliSCADA 2.1.0 Global Guide 44


points (page 34)

9. Click on the Preview tab to see the result. Check also Instrument non-standard states (page 124).

InteliSCADA 2.1.0 Global Guide 45


3.3.13 Editing instruments
It is possible to change properties of any instrument on the canvas. There is also possible to change some
properties when more instruments are selected.
Single instrument selection
Click the left mouse button to select the instrument on the canvas
Change the property
Use the Instrument Properties panel to change the property
Resize the instrument by mouse
Click on the grip point placed on the right bottom corner of the instrument selection. Hold the
mouse button down and move mouse to change the instrument's width or height
Some instruments have fixed aspect ratio, others support to switch it to off / on, see Instruments
(page 61)
Multiple instruments selection
Press and hold CTRL key and click the left mouse button to add / remove the instrument on the
canvas to / from selection
Or press CTRL + A for selection of all instruments on the canvas
Change the property
Use the Instruments' Properties Bulk Change panel to change the property

Only Device property is supported

Device property is available only if there is at least one instrument with Device property in the
selection
Moving the instrument
Activate Single instruments selection or Multiple instruments selection
Drag and drop the selection to move it to new position
Or use arrow keys to move selection to new position

Arrow key moves selection by 1 point

Arrow key + SHIFT key moves selection by 5 points


For single instrument selection there is a possibility to use the Instrument Properties panel to
change the property manually

InteliSCADA 2.1.0 Global Guide 46


3.3.14 Shortcuts in Editor
3.3.14.1 Shortcuts in screen canvas

Shortcut Action
Delete Deletes selected instruments
Confirms the opened dialog or the property value in the
Enter
Properties panel (page 40)l
Esc Cancels the opened dialog without any changes
Arrow key Moves selected instruments by 1 point in arrow direction
Shift + Arrow key Moves selected instruments by 5 points in arrow direction
Ctrl + Mouse down Selects / unselects the instrument clicked by the left mouse button
Ctrl + A Selects all instruments on the canvas
Ctrl + C Copies selected instruments
Saves all changes made on the current screen (changes are also
Ctrl + S
saved automatically every 3 seconds)
Ctrl + V Pastes instruments which were previously copied or cut
Ctrl + X Cuts selected instruments
Ctrl + Y Redoes changes on the current screen
Ctrl + Z Undoes changes on the current screen
To keep the instrument's current aspect ratio when resizing, press
the key SHIFT
Draw selection area
Mouse down -> Mouse move
after mouse up all instruments in the area will be selected
press and hold the SHIFT key to start drawing the selection
area over any instrument

3.3.14.2 Shortcuts in Screen Content panel

Shortcut Action
Selects / unselects the instrument clicked by the left mouse button
Ctrl + Mouse down

Selects all instruments from the currently selected one up to the


Shift + Mouse down
next clicked one

3.4 Preview
The Preview tab is used mainly for the custom screen content validation, i.e. to check how the edited custom
screen looks and works when online. It helps with designing complex screens and with instruments
configuration. The content of the Automatically generated screen (page 110) can be also checked in the
Preview tab even it is not editable. When in the Preview tab, any instrument on the screen can indicate
special states, see Instrument non-standard states (page 124)

InteliSCADA 2.1.0 Global Guide 47


Available buttons in the Preview tab:

Setpoints button – Opens the dialog to monitor and edit setpoints of any device in the particular site,
see Setpoints (page 52)

Values button – Opens the dialog to monitor values of any device in the particular site, see Values
(page 55)

History button – Opens the dialog with history records from all devices in the particular site, see
History (page 55)

Screens button – Opens the screens overview (not supported in Runtime)

"Fit To Screen" button – Zooms the screen so the whole screen is visible and fits the screen size
Fit to screen option is kept when screens are switching or when browser window is re-sized

"Zoom 100%" button – Zooms the screen to the original screen size

3.4.1 Preview restriction


The Preview tab in Designer is not intended for long-term monitoring as it is restricted for 1 minute every 15
minutes. For long-term monitoring, please use Runtime instead.
If the Preview tab is opened at the moment when the restriction starts, the user will be automatically
redirected to the Editor tab. While in restriction mode, the tab is disabled and there is a tooltip "Preview
temporarily restricted. Use Runtime instead.", see the image below. Once the restriction is over, the tab is
enabled again. Preview restriction does not apply for those sites, which have all devices configured to
communication type of Archive.

InteliSCADA 2.1.0 Global Guide 48


3.4.2 Screens overview
Contains list of all screens of the site
The default screen is indicated by the "home" icon
Click on the item to open a screen

6 back to Designer

InteliSCADA 2.1.0 Global Guide 49


4 Runtime
4.1 Navigation in Runtime 50
4.2 Sites 52
4.3 Setpoints 52
4.4 Values 55
4.5 History 55
4.6 In-progress indication 59

6 back to Table of contents


The InteliSCADA Runtime application is used to monitor a site prepared in the Designer (page 22). It
contains the Sites (page 25) tab and the Runtime screen for currently opened site:
a Runtime screen (i.e. custom screen or Automatically generated screen (page 110)) is used to
monitor and control the devices in the site
It is possible to switch to other screen using the Link property of an instrument, see Instruments
(page 61)
It is possible to monitor and edit setpoints in the Setpoints (page 52) dialog
It is possible to monitor values in the Values (page 55) dialog
It is possible to monitor the Site's history in the History (page 55) dialog
Sites can only be unlocked if the correct site password has been entered
Sites cannot be created, edited, deleted or imported (use Designer (page 22) instead)

4.1 Navigation in Runtime


The basic Runtime workflow looks like this:

Welcome screen to Runtime is theSites (page 25) tab. Alternatively it is possible to open the default screen
in Runtime directly using URL link in the browser, see "Site Runtime Link" button (page 25)

4.1.1 Runtime toolbar


Once the site is opened, the toolbar is divided in 4 main parts:

InteliSCADA 2.1.0 Global Guide 50


Tab Description
Tabs to navigate through the Runtime
Active tab is underlined (for reference see the
Runtime tab in the picture above)
Runtime navigation Available tabs
Sites tab – Opens the list of sites
Runtime tab – Opens the default screen of the
site
Buttons specific for active tab
Runtime tab:
Setpoints button - Opens the dialog to monitor
and edit setpoints of any device in the site
Tab specific buttons
Values button – Opens the dialog to monitor
values of any device in the site
History – Opens the dialog with the history
records from all devices in the site

Fit To Screen and Zoom 100% Sets the screen zoom

Currently open site name (only if in the Runtime tab)


Currently open screen name (only if in the Runtime
tab)
"Connection Status" button, see Connection status
(page 33)
Settings button
"Export All" (button is enabled for open sites
only) – Exports all data of the particular site (site,
General devices archives and logs are packed into a
single ZIP file). See also Reporting an issue
(page 130)
"License Activation" button – Opens the dialog
for license activation, see License activation
(page 15)
Manual – Opens the InteliSCADA global guide
About – Opens the dialog with information about
InteliSCADA

6 back to Runtime

InteliSCADA 2.1.0 Global Guide 51


4.2 Sites
It is not possible to modify or import sites in the Runtime (page 50), use the Designer (page 22) instead
The Sites tab contains the following information:

List of sites

Runtime link – Link to the default screen of a site. To use this link the particular site has to be
unlocked

Lock/Unlock Site button - If a site is locked, it opens the dialog to unlock it, otherwise it locks the
site

License Activation button – It is disabled if the site complies with the current license. Otherwise it
opens the "License Activation" dialog.

4.3 Setpoints
The dialog is used for monitoring and editing of any setpoint of any device configured in a site.
The dialog is divided into 3 columns:

Devices column
Lists all devices configured in a site
Click on the desired device to list its groups in the Groups column
A device, which is not connected, is disabled and cannot be selected
The first connected device is pre-selected by default, when the dialog is opened

Groups column
Lists all groups of the selected device
Click on the desired group to see its data points in the "Data Points" column

"Data Points" column


Lists all data points of a selected group
It shows live data points values

InteliSCADA 2.1.0 Global Guide 52


4.3.1 Edit setpoint
Setpoints are writable data points which can be edited using "Edit Value" dialog. The dialog can be opened for
a particular setpoint using Edit button placed to the right of the setpoint value.
The Edit button can have one of these states:

Enabled – the setpoint can be edited

Disabled – the setpoint cannot be edited because the currently logged in user doesn't have the
required permission or "Edit Value" dialog for this type of a setpoint is not supported yet

Hidden (Forcing icon visible) – the setpoint cannot be edited because it is actively forced

Edit Value dialog


The dialog is used to edit the value of a setpoint, There are several types of dialogs which are shown based
on a data type of the edited setpoint. All dialogs share the same structure.

InteliSCADA 2.1.0 Global Guide 53


Setpoint name and unit

Current value of the setpoint with the possibility to change the value

Range of values which are valid for the setpoint

Value of the setpoint at the time the dialog was opened

Default value of the setpoint (must be supported by the device)

Confirms and writes the new value to the device and closes the dialog

Cancel changes and closes the dialog

InteliSCADA 2.1.0 Global Guide 54


4.4 Values
The dialog is used for temporary monitoring of any value of any device configured in a site.
The dialog is divided into 3 columns. For a description of each column see Setpoints on page 52.

4.5 History
The dialog shows the overview of history records for multiple devices configured in a site.
It is possible to open the History dialog:
from the Preview tab in Designer, see Preview on page 47
from Runtime, see Runtime on page 50
Once the dialog is opened, the history is loaded in parts by infinite scroll.
History records are ordered chronologically by the date and time from the most recent history record to the
oldest one. Make sure to set the correct date & time setpoints in each ComAp controller to have records
ordered chronologically.
The history table is automatically updated when:
the most recent history record (with No. 0) is visible and a new record arrives
the History dialog is opened
the table is scrolled up to the most recent history record and the page is not yet loaded in the cache
the table is scrolled down to the oldest history record and the page is not yet loaded in the cache, new
records should be loaded by infinite scroll

InteliSCADA 2.1.0 Global Guide 55


No. - The number of the records

Date - Date when the record was generated in the device

Time - Time when the record was generated in the device

Device - User defined device name used in InteliSCADA

Reason - Reason of the record

Recorded values are divided into columns by values or grouped into one column in case of
the text record

InteliSCADA 2.1.0 Global Guide 56


Pre-mortem history records are visually distinguished.

Note: The number of history records is limited. The maximum number of records is 25.000 in total for all
sites. The oldest records beyond this limit will be automatically removed.

Click on any of the rows in the table to set focus. The row with focus is highlighted and when the history table
is updated (and the table still contains the focused row) the table is scrolled, so the focused row is always
visible. Sometimes it can happen that the focused row is not loaded on the table update. In that case all the
rows lose their focus and the table is not scrolled anywhere.
The history toolbar indicates connection status of used devices. History records that belong to disconnected
devices display indication on the Device column. Be aware that the history records from disconnected
devices are most likely not complete.

The total number of connected devices

The total number of disconnected devices

Indicates the history record belongs to a disconnected device

InteliSCADA 2.1.0 Global Guide 57


4.5.1 History filters
The filter functionality is provided by the Device column only. To open the filter options, click on the filter icon
in the column header. The icon highlights whether the filter is applied or not. The history records are loaded
only for selected devices. By default all devices are selected..

Filter icon - Opens the filter options. Green icon indicates an active filter.

Filter options

4.5.2 History columns


The order of the columns can be changed by drag and drop. The width of any column can be changed by
moving the column splitter. The No., Date, Time, Device and Reason are pinned to the left by default. Pinned
columns are protected from horizontal scrolling. Each column, except those that are pinned by default, can be
pinned or unpinned by dragging the column from the unpinned area and dropping into the pinned area. Every
time any change that affects one of these settings (order, width, pin) is done, the current settings are saved
and previous settings are lost. The most recent settings are loaded, when the history window is closed and
opened again and it is also preserved, when the application is closed and opened again.

InteliSCADA 2.1.0 Global Guide 58


4.5.3 Exporting history
The History dialog offers the possibility to export history to the CSV file (that can be opened e.g. in Excel). By
default, the file name is generated from the site name (e.g. Site1.csv). The history is exported only for the
selected devices specified by the filter, see History filters (page 58). Export might take a few minutes so it
runs in the background.

Export History - Exports history. It shows In-progress indication (page 59) while the
export is in progress in the background.

Once the history export is completed and ready to download, a notification message with the Download
button will be displayed. The file will be either downloaded automatically to the destination folder or the "Save
as" dialog will appear depending on your browser settings. The notification message can be manually closed
once downloaded, otherwise it will be closed automatically in 10 minutes.

4.6 In-progress indication


In-progress state is indicated by 3-white-dots (not flashing icon) and is used either
for operations, which take a long time (e.g. exporting history) or
for not initialized data (e.g. not initialized value in the "Data Row" instrument, see below)

Example: In-progress indication in the "Data Row" instrument:

InteliSCADA 2.1.0 Global Guide 59


5 Security
6 back to Table of contents
Every site has its own devices. To protect device connection details (sensitive device credentials) every site
requires the user-defined password. This password is mandatory and it is defined when creating a new site,
see Add site (page 26).
Password requirements
at least 6 characters length
white space characters are not allowed
Password can be also changed later, see Edit site (page 27)
It is possible to Unlock/Lock a site
in Designer, see "Lock/Unlock Site" button (page 25)
in Runtime, see "Lock/Unlock Site" button in Sites (page 52)
Site status is indicated by Key icon

Key icon Site status On click action

Site unlocked If clicked, it locks a site

Site locked If clicked, it opens the dialog to unlock a site

It is required to unlock a site to get access to anything related to this site

IMPORTANT: It is not possible to recover the site password, therefore it is recommended to take
precautions against the loss of the password.

InteliSCADA 2.1.0 Global Guide 60


6 Instruments
All supported instruments can be used on any custom screen or on Automatically generated screen (page
110).
Some instrument properties configurations(e.g. scale limits, warning limits, iframe content, alternative
images) are not reflected when the instrument is placed on the canvas in Editor, but they are reflected in
Runtime and Preview.
Some properties are interconnected, thus the content of one property may depend on the value of another
one, e.g. to select a data point, the device must be selected first.
There are non-standard state indications apply to any of the instruments, see Instrument non-standard
states (page 124)

6.1 Instruments specific properties 62


6.2 Alarm List 66
6.3 Analog Meter 69
6.4 Bar Graph 72
6.5 Breaker 76
6.6 Breaker Button 77
6.7 Bus 78
6.8 Busbar 79
6.9 Control Button 80
6.10 Data Row 82
6.11 Engine 84
6.12 Fault Reset 85
6.13 Generator 86
6.14 Horn Reset 87
6.15 IFrame 87
6.16 Image 90
6.17 LED 93
6.18 Line 95
6.19 Load 95
6.20 Mains 96
6.21 Markdown Text 97
6.22 Mode Selector 100
6.23 Multi Alarm List 101
6.24 Rectangle 103
6.25 Start Engine 104
6.26 Stop Engine 105
6.27 Trend 106
6.28 Wire Junction 108

6 back to Table of contents

InteliSCADA 2.1.0 Global Guide 61


6.1 Instruments specific properties
6.1.1 Warning limits
Settings of warning limits are supported for the following instruments:
Analog Meter
Bar Graph
There is possible to configure Type of source for Warning limit value as:
Constant
Data point

6.1.2 Scale
Settings of Scale are supported for instruments:
Analog Meter
Bar Graph
Trend
There is possible to configure Type of source for Warning limit value as:
Data point
Analog Meter and Bar Graph only
Constant
Default

InteliSCADA 2.1.0 Global Guide 62


6.1.3 Data point selection
Settings of Data point as value source are supported for instruments:
Analog Meter
Bar Graph
Busbar
Data Row
Image
LED
Trend
Wire Junction

InteliSCADA 2.1.0 Global Guide 63


For instruments which support internal data point types (e.g. LED) the dialog window shows also Internal
data points category, see the illustration picture below.
IMPORTANT: If not all of the expected Data points are present in Data Point Selection list,
reimport Data points for the Device (see Importing data points on page 34 for details).

These instruments support only predefined collection of Data points:


Alarm List
Breaker
Breaker Button
Bus

InteliSCADA 2.1.0 Global Guide 64


Control Button
Engine
Fault Reset
Generator
Horn Reset
Load
Mains
Mode Selector
Start Engine
Stop Engine

6.1.4 Color picker


Settings of custom Color are supported for instruments:
Busbar
Data Row
Line
LED
Rectangle
Text
Trend
Wire Junction

InteliSCADA 2.1.0 Global Guide 65


Color selector area Click to select a color at specific area
Color selector area
position.
Configure the color value in RGBA format.
Hex – configure RGB channels values in hexadecimal
format
Color configuration input R – configure Red channel value
fields
G – configure Green channel value
B – configure Blue channel value
A – configure Alpha channel value - transparency
Buttons for predefined
Click to load the configuration of the selected color.
colors

Default button Reset the color configuration values to the default values.

Close the configuration for the color parameters and saves the
Save button
configuration.
Close the configuration for the color parameters. The
Cancel button
configuration is not saved after being closed.

6.2 Alarm List

The Alarm list instrument is used to display alarms on a selected device. Alarm List contains following
information:

InteliSCADA 2.1.0 Global Guide 66


Red when an alarm record exists
Explanation mark icon Red & flashing when an unconfirmed alarm record exists
Grey when the alarm list is empty

Number of alarm records Active / unconfirmed (alarms marked with asterisk) / total

Level 1 (Warnings) highlighted in yellow


Level 2 (Shutdowns) highlighted in red
List of active alarms
Sensor Fail – black&white
ECU alarm – blue

Editor properties
Category Name Note Input type Range Default
1 .. 64
Name User name of the instrument Text UNICODE *)
chars
0 .. screen
width –
X Number
instrument
[X, Y] coordinates of top left width
corner 0 .. screen
height –
General Y Number
instrument
height
200 ..
Width Number 320
screen width
Width and height of the
100 ..
instrument
Height Number screen 320
height
Keep Aspect Keeps aspect ratio during
Checkbox Unchecked
Ratio resizing
Device that instrument is List of
Device Select
connected to devices
Alarm List source
Some devices have standard Standard
Source Data point
and ECU alarms in 2 separate alarm
Data Point selection
lists, others have just 1 alarm list list/ECU
(page 63)
(the Standard one), which alarm list
displays all alarm types together.
Background color of the header.
Color
Background The transparent color can be set
Header picker #3B415B
Color to make the background
(page 65)
invisible.
Design Border Color Border color of the instrument. Color #3B415B

InteliSCADA 2.1.0 Global Guide 67


Category Name Note Input type Range Default
Transparent color can be set to picker
make the border invisible. (page 65)
Background color of the
Color
Background instrument. The transparent
picker Transparent
Color color can be set to make the
(page 65)
background invisible.
Color
Text Text Color Color of the text picker #FFFFFF
(page 65)

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

InteliSCADA 2.1.0 Global Guide 68


6.3 Analog Meter

Image 6.1 Analog Meter

Name

Value

Unit

Scale low limit (Scale 0%)

Scale high limit (Scale 100%)

Warning (or shutdown) limit

Analog meter is a rounded meter with a pointer. It displays the current value of the selected data point
graphically. Warning / Shutdown limits can be indicated on the analog meter with yellow (warning) / red
(shutdown) scale color by setting up the warning limits.
In case the value (pointer) is out of the scale range the pointer stops 15 degrees below / above the scale
limit.
Upper scale limit (Scale 100%) can be expanded to 125% of its original value using the Expand Scale
option configured in the Scale dialog.

InteliSCADA 2.1.0 Global Guide 69


Editor properties
Category Name Note Input type Range Default
User name of the 1 .. 64 UNICODE
Name Text *)
instrument chars
0 .. screen width –
X Number
instrument width
[X, Y] coordinates of
0 .. screen height
top left corner
General Y Number – instrument
height
100 .. screen
Width Number 160
Width and height of the width
instrument 150 .. screen
Height Number 240
height
Device that instrument
Device Select List of devices
is connected to
Source A source for Analog Data point
Filter: numeric
Data Point meter data (e.g. Actual selection
data points
power) (page 63)
Background color of
the header. The
Background Color picker
Header transparent color can #272D43
Color (page 65)
be set to make the
background invisible.
One of the following
types can be used:
Constant –
numeric value
defined by user
Data Point –
Constant/Data
Scale 0% Type usually a Select Default
Point/Default
setpoint
Default – low
limit of the
Design Source data
point

Based on Scale 0%
type:
Enter a
Scale 0% Scale (page
constant
Value 62)
Select a data
point
(not available

InteliSCADA 2.1.0 Global Guide 70


Category Name Note Input type Range Default
for Default)
Scale Constant/Data
Select Select Default
100%Type Point/Default
Based on Scale 100%
Type:
Enter a
Scale 100% constant Scale (page
Value Select a data 62)
point
(not available
for Default)
Expands existing scale
Expand Scale Checkbox 0/1 Unchecked
to 125%
Border color of the
instrument. The
Color picker
Border Color transparent color can #3B415B
(page 65)
be set to make the
border invisible.
Background color of
the instrument. The
Background Color picker
transparent color can #272D43
Color (page 65)
be set to make the
background invisible.
Color picker
Text Text Color Color of the text #FFFFFF
(page 65)
Warning limit
Active Checkbox 0/1 Unchecked
activation
value type selection –
Constant (numeric Constant/Data
Type Select Constant
Warning value) or Data Point Point
limits (e.g. a setpoint)
(Warning Based on Type:
limit 1, 2, 3, Enter a
4) constant (e.g. Warning
Value 250) limits (page 0
Select a data 62)
point (e.g.
Nominal power)

InteliSCADA 2.1.0 Global Guide 71


Category Name Note Input type Range Default
Level 1 for warning
(yellow),
Limit Level Select Level 1/Level 2 Level 1
Level 2 for shutdown
(red)
Warning limit direction:
Limit direction Up for over limit, Down Select Up/Down Up
for under limit
Link to another screen
Link Link Select no link
in site

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

6.4 Bar Graph


The Bar Graph instrument is used for monitoring or comparison of multiple values. Each column represents
one data point. From 1 to 6 data points (all from the same device) can be selected and monitored.
Warning / Shutdown limits can be indicated on Bar Graph with yellow (warning) / red (shutdown) color by
setting up warning limits.

Editor properties
Category Name Note Input type Range Default
User name of the
Name Text 1 .. 64 UNICODE char *)
instrument
0 .. screen width –
X Number
[X, Y] coordinates instrument width
of top left corner 0 .. screen height –
General Y Number
instrument height
(expanded)
100 .. screen height –
Width Number 200
Width and height of instrument height
the instrument 100 .. screen height –
Height Number 200
instrument height
Keep Aspect Keeps aspect ratio Checkbox Unchecked

InteliSCADA 2.1.0 Global Guide 72


Category Name Note Input type Range Default
Ratio during resizing
Device that
Source Device instrument is Select List of devices
connected to
Bars Number of bars Number 1 .. 6 1
Source data point Data point
Bars Filter: numeric data
Bar # # is the bar number selection
points
(order) (page 63)
Type of the label
(custom or
automatically set to Data Point Data Point
Label Type Select
the name of the Name/Custom Name
selected data
point)
User defined label,
available for Name (for
Header Label Text 1 .. 64 UNICODE char
Custom label type Custom type)
only
Background color
of the header. The
Color
Background transparent color
picker #3B415B
Color can be set to make
(page 65)
the background
invisible.
Orientation of the
Type Select Vertical/Horizontal Vertical
instrument
* Base of the bar
Bar Base Select Default/Low/High Default
value
One of the
following types can
be used:
Constant –
numeric
Design value
defined by
Scale 0% Constant/Data
user Select Default
Type Point/Default
Data Point –
usually a
setpoint
Default –
low limit of
the Bar 1
data point

InteliSCADA 2.1.0 Global Guide 73


Category Name Note Input type Range Default
Based on Scale
0% type:
Enter a
constant
Scale 0% Scale
Select a
Value (page 62)
data point
(not
available for
Default)
One of the
following types can
be used:
Constant –
numeric
value
defined by
Scale 100% Constant/Data
user Select Default
Type Point/Default
Data Point –
usually a
setpoint
Default –
high limit of
the Bar 1
data point
Based on Scale
100% Type:
Enter a
constant
Scale 100% Scale
Select a
Value (page 62)
data point
(not
available for
Default)
Expands existing
Expand Scale Checkbox Unchecked
scale to 125%
Border color of the
instrument. The
Color
transparent color
Border Color picker #3B415B
can be set to make
(page 65)
the border
invisible.
Background Color
Background color #3B415B
Color picker

InteliSCADA 2.1.0 Global Guide 74


Category Name Note Input type Range Default
of the instrument.
The transparent
color can be set to
(page 65)
make the
background
invisible.
Background color
of the bar. The
Bar transparent color Color
Background can be set to make picker #272D43
Color the bar (page 65)
background
invisible.
Color
Text Text Color Color of the text picker #FFFFFF
(page 65)
Warning limit
Active Checkbox 0/1 Unchecked
activation
value type
selection –
Constant (numeric
Type Select Constant/Data Point Constant
value) or Data
Point (e.g. a
setpoint)
Based on Type:
Enter a
constant
Warning Warning
(e.g. 250)
limits Value limits 0
(Warning limit Select a
(page 62)
1, 2, 3, 4) data point
(e.g. Nominal
power)
Level 1 for warning
(yellow),
Limit Level Select Level 1/Level 2 Level 1
Level 2 for
shutdown (red)
Warning limit
direction:
Limit direction Up for over limit, Select Up/Down Up
Down for under
limit

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

InteliSCADA 2.1.0 Global Guide 75


*Bar base note

Base of bar value – how value is displayed


Default – from data point
Low – value is displayed from bottom to top
High – value is displayed from top to bottom

6.5 Breaker
Instrument that indicates the status of a generator/mains/bus circuit breaker.

Status Description Icon

Inactive Breaker is open

Active Breaker is closed

Device is synchronizing
Breaker's arm is flashing a configurated active and inactive
color as well as regularly closing and opening at the same
Synchronizing time.
*The image is for illustrative purposes only and may differ
from the actual visualization based on the current state of
the device and the configuration of breaker's properties.
Breaker mode required by device does not match the current
breaker state
Unsafe open – breaker is open, but the device requires
Unsafe
breaker to be closed
Unsafe closed – breaker is closed, but the device requires
breaker to be open

Init Device is not able to run its application

InteliSCADA 2.1.0 Global Guide 76


Editor properties
Category Name Note Input type Range Default
User name of the 1..64 UNICODE
Name Text *)
instrument chars
0 .. screen width –
X Number 0
[X, Y] coordinates of top instrument width
General
left corner 0 .. screen height –
Y Number 0
instrument height
Width Width and height of the Number 10 .. screen width 40
Height instrument Number 10 .. screen height 40
Device that instrument is
Device Select List of devices
connected to
Source List of breakers supported Data point
Data Point in the selected device (e.g. selection
Generator circuit breaker) (page 63)
4 options: None,
Vertical, Horizontal,
Mirroring Mirroring of the instrument Select None
Both (vertical +
horizontal)
Rotation of the instrument, 4 options: 0°,
Rotation Select 0°
unit: °, clockwise 90°,180°, 270°
Design
Color
Active State Color of the closed
picker #1DD322
Color breaker.
(page 65)
Color
Inactive State Color of the opened
picker #7C7C7C
Color breaker.
(page 65)

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

6.6 Breaker Button

This button is used to open or close a breaker. The breaker type depends on the selected Source.

InteliSCADA 2.1.0 Global Guide 77


Editor properties
Category Name Note Input type Range Default
1 .. 64 UNICODE
Name User name of the instrument Text *)
chars
0 .. screen width –
X Number 0
instrument width
[X, Y] coordinates of top left
0 .. screen height
General corner
Y Number – instrument 0
height
Width Number 10 .. screen width 40
Width and height of the
10 .. screen
Height instrument Number 40
height
Device that instrument is
Device Select List of devices
connected to
Source List of supported breaker Data point
Data
commands (e.g. Breakers - GCB selection
Point
ON/OFF) (page 63)

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

6.7 Bus

Status of the instrument Bus is indicated by color:


Green – OK
Yellow – warning
Red – shutdown
Grey – inactive

Note: The color reflects the status of the respective LEDs of the controller (yellow = green + red) and
depends on the controller type.

InteliSCADA 2.1.0 Global Guide 78


Editor properties
Category Name Note Input type Range Default
User name of the 1..64 UNICODE
Name Text *)
instrument chars
0 .. screen width –
X Number
[X, Y] coordinates of instrument width
General
top left corner 0 .. screen height –
Y Number
instrument height
Width Width and height of Number 10 .. screen width 40
Height the instrument Number 10 .. screen height 40
Device that instrument
Device Select List of devices
is connected to
Source List of bus LED data Data point
Bus, Bus left, Bus
Data Point points supported in the selection (page
right, PSC
selected device 63)
4 options: None,
Mirroring of the Vertical, Horizontal,
Mirroring Select None
instrument Both (vertical +
Design horizontal)
Rotation of the
4 options: 0°,
Rotation instrument, unit: °, Select 0°
90°,180°, 270°
clockwise
Link to another screen
Link Link Select Screen selection No link
in site

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

6.8 Busbar

Busbar instrument is used in wiring diagrams. It can be linked to a LED type data point to indicate its status in
color.

InteliSCADA 2.1.0 Global Guide 79


Editor properties
Name Note Input type Range Default
User name of the 1 .. 64
General Name Text *)
instrument UNICODE char
X1 Number
[X, Y] coordinates of P1 0 .. screen width
Y1 Number
Position – instrument
X2 Number X1 + 100
[X, Y] coordinates of P2 width
Y2 Number Y1
Device that instrument is
Device Select List of devices
connected to
Data source that
Data point
instrument is connected to. LED type data
Data Point selection
It can be data point of points
(page 63)
either BIT or LED type.
Source
Available only for data
point of BIT type.
Invert bit value
Invert Value Checkbox 0/1 Unchecked
if checked: 0 = On, 1 = Off
if unchecked: 1 = On, 0 =
Off
Line Width Line width Number 1 .. 100 2
Available only for data
Active State point of BIT type. Color picker
#1DD322
Color Defines color for bit in On (page 65)
Design state.
Available only for data
Inactive point of BIT type. Color picker
#7C7C7C
State Color Defines color for bit in Off (page 65)
state.

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

Shortcut Action
Keeps horizontal or vertical orientation of the busbar when drag &
drop.
Shift + Mouse down -> Mouse move
Flips the busbar orientation according to the mouse moving to
horizontal or vertical.

6.9 Control Button


Control Button is used to send the specified command to a selected device. User can define a label and select
one of the pre-defined colors.

InteliSCADA 2.1.0 Global Guide 80


Editor properties
Category Name Note Input type Range Default
User name of
Name Text 1 .. 64 UNICODE char *)
the instrument
0 .. screen width –
X [X, Y] Number
instrument width
coordinates of
0 .. screen height –
Y top left corner Number
General instrument height

Width Width and Number 10 .. screen width 320


height of the
Height instrument Number 10 .. screen height 48

Keeps aspect
Keep Aspect
ratio during Checkbox Unchecked
Ratio
resizing
Device that
Device instrument is Select List of devices
connected to
List of all
commands
Source
supported by Data point
Data Point the selected selection List of commands
device (e.g. (page 63)
UserButton 2 –
ON/OFF)

InteliSCADA 2.1.0 Global Guide 81


Category Name Note Input type Range Default
Button
background
color.
The text color
Based on: Bootstrap colors
and the
Options: Default (BS
background Color
Primary), Green (BS
Design Color color for effects picker Default
Success), Red (BS Danger),
(hover, (page 65)
Yellow (BS Warning), Blue
pressed,...) are
(BS Info), Light, Dark
set
automatically
based on the
selection.
User defined
Label Text 0 .. 64 UNICODE char Command
button label
Text
Font size of the
Font Size Number 6-200 px 16 px
text

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

6.10 Data Row

Image 6.2 Data Row instrument

Image 6.3 Data Row instrument when Compact mode is on

Data point name

Data point value and unit

The Data Row instrument is used to display a value of a data point (device value or setpoint) in a text form.
Data Row can be configured as editable if its Data Point property is set to a setpoint.
Data point name, value and unit can be displayed or just some of them.
Different data types are supported:
Number – eg. generator frequency value
Text – eg. engine state ("not ready")

InteliSCADA 2.1.0 Global Guide 82


Timer – eg. remaining time for engine state in seconds
An invalid value is represented by "####".

Editor properties
Category Name Note Input type Range Default
1 .. 64
Name User name of the instrument Text UNICODE *)
chars
0 .. screen
width –
X Number 0
instrument
[X, Y] coordinates of top left width
corner 0 .. screen
General height –
Y Number 0
instrument
height
15 .. screen
Width Number 320
Width and height of the width
instrument 15 .. screen
Height Number 48
height
Keep Aspect Keeps aspect ratio during
Checkbox Unchecked
Ratio resizing
Device that instrument is List of
Device Select
connected to devices
Data source that instrument is
Source Data point
connected to (e.g. Nominal
Data Point selection
Power setpoint, Generator
(page 63)
frequency value, etc.)
Label Font Font size of the label shown in
Number 6-200 px 14 px
Size compact mode.
Font Size Font size of the text Number 6-200 px 18 px
Text
Color
Text Color Color of the text picker #FFFFFF
(page 65)
Enables or disables possibility to
Editable edit value. Visible only for Checkbox 0/1 1
setpoint data points.
Compact mode on / off.
Compact The Compact mode has a tile (2 Checkbox 0/1 0
Design
rows) design.
Data point name displayed on /
Label Checkbox 0/1 1
off
Data point value displayed on /
Value Checkbox 0/1 1
off

InteliSCADA 2.1.0 Global Guide 83


Category Name Note Input type Range Default
Units Data point unit displayed on / off Checkbox 0/1 1
Adjusts the unit position towards
the right datarow border.
Unit Space Number 8 .. 300 px 48 px
This property is hidden for
Compact mode.
Border color of the instrument. Color
Border Color Transparent color can be set to picker #3B415B
make the border invisible. (page 65)
Color
Background Background Color of the
picker #3B415B
Color instrument
(page 65)

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

6.11 Engine

The Engine instrument represents the status of an engine, which is indicated by color:
Green – OK
Yellow – warning
Red – shutdown
Grey – inactive

Note: The color reflects the status of the respective LEDs of the controller (yellow = green + red) and
depends on the controller type.

Editor properties
Category Name Note Input type Range Default
1 .. 64 UNICODE
Name User name of the instrument Text *)
char
0 .. screen width –
X Number 0
instrument width
General [X, Y] coordinates of top left corner
0 .. screen height –
Y Number 0
instrument height
Width Number 10 .. screen width 40
Width and height of the instrument
Height Number 10 .. screen height 40
Source Device Device that instrument is Select List of devices

InteliSCADA 2.1.0 Global Guide 84


Category Name Note Input type Range Default
connected to
Engine (or empty if not supported Data point automatically
Data
or found in the selected device), the selection selected along with
Point
property is read-only (page 63) device if available
Link Link Link to another screen in site Select Screen selection No link

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

6.12 Fault Reset

Button used to confirm alarms (execute Fault reset command):


alarms for Source device in Alarm list will no longer be marked with asterisk
inactive alarms for Source device will be deleted from Alarm list

Editor properties
Category Name Note Input type Range Default
{Instrument Type} * {Last
1 .. 64
User name of the number +1 of
Name Text UNICODE
instrument in*)struments according
chars
type}
0 .. screen
width –
X Number 0
instrument
[X, Y] coordinates of top width
General
left corner 0 .. screen
height –
Y Number 0
instrument
height
10 .. screen
Width Number 40
Width and height of the width
instrument 10 .. screen
Height Number 40
height
Device that instrument is List of
Device Select
connected to devices
Source Engine – Fault Reset Data point
Data
command (if available), selection
Point
the property is read-only (page 63)

InteliSCADA 2.1.0 Global Guide 85


Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

6.13 Generator

The Generator instrument represents the status of a generator which is indicated by color:
Green – OK
Yellow – warning
Red – shutdown
Grey – inactive

Note: The color reflects the status of the respective LEDs of the controller (yellow = green + red) and
depends on the controller type.

Editor properties
Category Name Note Input type Range Default
1 .. 64 UNICODE
Name User name of the instrument Text *)
char
0 .. screen width –
X Number 0
instrument width
General [X, Y] coordinates of top left corner
0 .. screen height –
Y Number 0
instrument height
Width Number 10 .. screen width 40
Width and height of the instrument
Height Number 10 .. screen height 40
Device that instrument is connected
Device Select List of devices
to
Generator (or empty if not supported Data point automatically
Data
or found in the selected device), the selection selected along with
Point
property is read-only (page 63) device if available
Link Link Link to another screen in site Select Screen selection No link

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

InteliSCADA 2.1.0 Global Guide 86


6.14 Horn Reset

Button that executes the Horn Reset command.

Editor properties
Category Name Note Input type Range Default
1 .. 64 UNICODE
Name User name of the instrument Text *)
chars
0 .. screen width
X Number – instrument 0
[X, Y] coordinates of top left corner width
General 0 .. screen height
Y Number – instrument 0
height
Width Number 10 .. screen width 40
Width and height of the instrument
10 .. screen
Height Number 40
height
Device that instrument is
Device Select List of devices
connected to
Source Engine – Horn Reset command (if Data point
Data
available), the property is read- selection
Point
only (page 63)

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

6.15 IFrame
Instrument that represents inline frame for embedding another content. With the IFrame instrument it is
possible to have for example an instruction video embedded in a custom screen.
To configure IFrame instrument, user has to set its Url (src) property to a valid source path to a content that
supports embedding by an iframe element.
Here is an example how to insert an IFrame Url for a video:

InteliSCADA 2.1.0 Global Guide 87


1. Click "Share" button below the YouTube video

2. Select "Embed" share option

3. Select and copy only the src value of generated IFrame component

4. Paste the src value to the Url (src) property of an IFrame instrument in the Editor
If there is a configured source for the instrument, the path is visible within the top of the instrument
container in Editor. This information can not overlap instrument size so only first path row is visible.

InteliSCADA 2.1.0 Global Guide 88


5. IFrame content is then loaded in Runtime and Preview. Rendered content fits the instrument size.

If no source is set or the source is not accessible the IFrame instrument content in Runtime or Preview is
empty.

Editor properties
Category Name Note Input type Range Default
1 .. 64
User name of the
Name Text UNICODE *)
instrument
chars
0 .. screen
width –
X Number 0
General instrument
[X, Y] coordinates of top width
left corner 0 .. screen
height –
Y Number 0
instrument
height

InteliSCADA 2.1.0 Global Guide 89


Category Name Note Input type Range Default
20 .. screen
Width Number 480
Width and height of the width
instrument 20 .. screen
Height Number 320
height
Keep Aspect Keeps aspect ratio during
Checkbox Unchecked
Ratio resizing
0 .. 256
<iframe> element source
Source Url (src) Text UNICODE
path (url)
chars
Border color of the
instrument. The
Color picker
Border Color transparent color can be #3B415B
(page 65)
set to make the border
invisible.
Design
Background color of the
instrument. The
Background Color picker
transparent color can be #3B415B
Color (page 65)
set to make the
background invisible.

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

6.16 Image

Instrument that represents an image. Use the Image instrument from the Instruments panel, or simply an
image from the Image Gallery for which the Source property is already set.

InteliSCADA 2.1.0 Global Guide 90


Editor properties
Category Name Note Input type Range Default
1 .. 64
User name of the
Name Text UNICODE *)
instrument
chars
0 .. screen
width –
X Number 0
instrument
[X, Y] coordinates of top width
left corner 0 .. screen
height –
X Number 0
instrument
General
height
10 .. screen
Width Number 320
Width and height of the width
instrument 10 .. screen
Height Number 320
height
Checked for
images from
Keep Aspect Keeps aspect ratio during
Checkbox the Gallery,
Ratio resizing
Unchecked
otherwise
file name for
The size of
images from
Image the image file
Source Source image file name the Gallery,
Source is restricted to
Image empty
28 MB
otherwise
Adjust the instrument size
Adjust size Button
to fit the image
Border color of the
instrument. The Color
Border Color transparent color can be picker Transparent
set to make the border (page 65)
invisible.
Design
Background color of the
instrument. The Color
Background
transparent color can be picker Transparent
Color
set to make the (page 65)
background invisible.
Device that instrument is
List of
Device connected to (used for Select
Dynamic devices
image dynamic switching)
image
Binary bit data point used Data point Filter: binary
Binary Bit Data
for image dynamic selection data points

InteliSCADA 2.1.0 Global Guide 91


Category Name Note Input type Range Default
Point – blue
color
the most switching (page 63)
significant bit
(MSB)
Binary Bit Data
Point – yellow
Binary bit data point used Data point
color Filter: binary
for image dynamic selection
the least data points
switching (page 63)
significant bit
(LSB)
Image source for 00 value
Value combination of the Image
Combination 00 selected Binary Bit Data Source
Points
Image source for 10 value
Value combination of the Image
Combination 10 selected Binary Bit Data Source
Points
Image source for 01 value
Value combination of the Image
Combination 01 selected Binary Bit Data Source
Points
Image source for 11 value
Value combination of the Image
Combination 11 selected Binary Bit Data Source
Points
Link to another screen in Screen
Link Link Select No link
site selection

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

6.16.1 Image source dialog


The modal Image Gallery dialog contains images (illustration image, photo, site topology, ...), which can
be selected as the source of the Image instrument.

Click Save to set the selected image source or Cancel to close dialog without changes.

Some images are pre-defined by default, custom images can be also added to the Image Gallery

Use filter by packs or search by file name or tags function to explore gallery

Click an image to select it & to display image details

InteliSCADA 2.1.0 Global Guide 92


6.16.2 Dynamic Image
The displayed image can be dynamically switched based on the selected bits' values.
It is possible to choose only one of the bits for switching 2 images, or both of them for switching up to 4
images.
If you select only one of the binary bits data points, value of the other one will be 0.
To select the Binary Bit Data Point the Devices has to be selected..
Only image sources for reachable combinations for selected bit(s) will be used (e.g. if you choose only the
most significant bit (blue), then the only combinations 00 and 10 are reachable). Sources for unreachable
combinations are ignored (but they will be saved in instrument definition).
The source for the combination 00 is synchronized with the source for static image.
Editor will show only the image for the 00 value combination, in Preview or Runtime the relevant image will
be displayed.
It is not required to select images for all the combinations.

6.17 LED
LED instrument is used to monitor states (values) of binary communication objects. User can select color and
which bit value (0 or 1) is for "On" state.

InteliSCADA 2.1.0 Global Guide 93


Editor properties
Category Name Note Input type Range Default
User name of the 1 .. 64 UNICODE
Name Text *)
instrument char
0 .. screen width
X Number – instrument
[X, Y] coordinates of width
top left corner 0 .. screen height
General Y Number – instrument
height
Width Number 10 .. screen width 24
Width and height of
10 .. screen
Height the instrument Number 24
height
Keep Aspect Keeps aspect ratio
Checkbox Checked
Ratio during resizing
Device that
Device instrument is Select List of devices
connected to
Data point
Source for instrument Filter: binary data
Data Point selection
data points
Source (page 63)
Invert bit value
if checked: 0 = On, 1
Invert Value = Off Checkbox 0/1 Unchecked
if unchecked: 1 = On,
0 = Off
Shape of an
instrument,
Shape uncheck Keep aspect Select Round, Square Round
ratio for the rectangle
Design
shape
active LED color, Color
Color (inactive LED is picker #ff2b00
always gray) (page 65)

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

InteliSCADA 2.1.0 Global Guide 94


6.18 Line

The Line instrument is defined by two points. The line can also be diagonal.

Editor properties
Category Name Note Input type Range Default
User name of the 1 .. 64 UNICODE
General Name Text *)
instrument chars
0 .. screen width –
X1 Number
[X, Y] coordinates of the instrument width
start point 0 .. screen height –
Y1 Number
instrument height
Position
0 .. screen width –
X2 Number X1 + 100
[X, Y] coordinates of the instrument width
end point 0 .. screen height –
Y2 Number Y1
instrument height
Line
Width of the line Number 1 .. 100 2
Width
Design
Color picker Gray
Color Line color
(page 65) (#7c7c7c)

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

Shortcut Action
Keeps horizontal or vertical orientation of a line when drag & drop.
Shift + Mouse down -> Mouse move Flips the line orientation according to the mouse moving to
horizontal or vertical.

6.19 Load

The Load instrument represents the status of the load, which is indicated by color:

InteliSCADA 2.1.0 Global Guide 95


Green – OK
Yellow – warning
Red – shutdown
Grey – inactive

Note: The color reflects the status of the respective LEDs of the controller (yellow = green + red) and
depends on the controller type.

Editor properties
Category Name Note Input type Range Default
1 .. 64 UNICODE
Name User name of the instrument Text *)
char
0 .. screen width –
X Number
instrument width
General [X, Y] coordinates of top left corner
0 .. screen height –
Y Number
instrument height
Width Number 10 .. screen width 40
Width and height of the instrument
Height Number 10 .. screen height 40
Device that instrument is
Device Select List of devices
connected to
Source Load (or empty if not supported or Data point automatically
Data
found in the selected device), the selection selected along with
Point
property is read-only (page 63) device if available
Link Link Link to another screen in site Select Screen selection No link

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

6.20 Mains

The Mains instrument represents the status of mains, which is indicated by color:
Green – OK
Yellow – warning
Red – shutdown
Grey – inactive

Note: The color reflects the status of the respective LEDs of the controller (yellow = green + red) and
depends on the controller type.

InteliSCADA 2.1.0 Global Guide 96


Editor properties
Category Name Note Input type Range Default
User name of the
Name Text 1 .. 64 UNICODE char *)
instrument
0 .. screen width –
X Number
[X, Y] coordinates of instrument width
General
top left corner 0 .. screen height –
Y Number
instrument height
Width Width and height of the Number 10 .. screen width 40
Height instrument Number 10 .. screen height 40
Device that instrument
Device Select List of devices
is connected to
Mains (or empty if not
Source supported or found in automatically selected
Scale (page
Data Point the selected device), along with device if
62)
the property is read- available
only
Link to another screen
Link Link Select Screen selection No link
in site

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

6.21 Markdown Text

The Markdown Text instrument is used for a custom text. It supports the Markdown (markup language) and
some HTML syntax, which allows text formatting.
The Markdown Text instrument provides a validation of the inserted input, so it is not possible to process any
XSS vulnerabilities. Any part of the text that is evaluated as a possible security threat is automatically ignored.
Example: "javascript:...", "<script>/*+...+*/</script>" or "<iframe>...</iframe>".

Note: The IFrame (page 87) is available instead.

InteliSCADA 2.1.0 Global Guide 97


Editor properties
Category Name Note Input type Range Default
1 .. 64
Name User name of the instrument Text UNICODE *)
chars
0 .. screen
width –
X Number 0
instrument
[X, Y] coordinates of top left width
corner 0 .. screen
General height –
Y Number 0
instrument
height
20 .. screen
Width Number 320
Width and height of the width
instrument 20 .. screen
Height Number 48
height
Keep Aspect
Keeps aspect ratio during resizing Checkbox Unchecked
Ratio
Button that opens a dialog where
Text "Edit text" Button
custom text can be inserted
Color of the instrument border. Color
Border Color Transparent color can be set to picker #3B415B
make the border invisible (page 65)
Design
Color
Background Color of the instrument
picker #3B415B
Color background
(page 65)
Screen
Link Link Link to another screen in site Select No link
selection

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

Note: See Markdown Guide for details.(Examples can be found there.)

InteliSCADA 2.1.0 Global Guide 98


Examples

# Heading level 1
## Heading level 2
### Heading level 3
Heading
#### Heading level 4
##### Heading level 5
###### Heading level 6

<font face="arial" color="green">Green


Text color
text</font>

using &#10240 (Braille blank) example:


White space
<p>big &#10240 &#10240 space</p>
1<br>
Line Break
2
<p>1</p>
Paragraf
2

**This is bold text**


__This is bold text__
*This is italic text*
Emphasis _This is italic text_
~~Strikethrough~~
Note: Use Line break <br> at the end of
each line to get the result on the right

+ Create a list by starting a line with `+`,


`-`, or `*`
- Sub-lists are made by indenting 2
spaces:

Unordered _ _- Marker character change forces


list new list start:
_ _ _ _- New list start
_ _ _ _- New list start
_ _- New list start
* New list

InteliSCADA 2.1.0 Global Guide 99


Note: Symbol "_" stands for a space.

1. List level 1
Ordered list
2. List level 2

Ordered list
(Start 57. List level 57
numbering 1. List level 58
with offset)

| Col 1 | Col 2 |

Table | ------ | ----------- |


(Left aligned | Row 1 | Row 1 value |
columns) | Row 2 | Row 2 value |
| Row 3 | Row 3 value |

| Col 1 | Col 2 |
Table | ------: | -----------: |
(Right
| Row 1 | Row 1 value |
aligned
columns) | Row 2 | Row 2 value |
| Row 3 | Row 3 value |

6.22 Mode Selector

Mode Selector shows all available controller modes (depends on the device type). User can change the
controller mode (setpoint) by clicking any available mode on Mode Selector (there is a visual feedback -
button pressed).

Current Active mode (e.g. OFF) is always highlighted in green color

Mode requested by user, different from active mode and not-yet active is
highlighted

InteliSCADA 2.1.0 Global Guide 100


Editor properties
Category Name Note Input type Range Default
User name of the 1 .. 64 UNICODE
Name Text *)
instrument chars
0 .. screen width –
X Number 0
[X, Y] coordinates of instrument width
top left corner 0 .. screen height –
Y Number 0
General instrument height
Width Width and height of the Number 30 .. screen width 320
Height instrument Number 30 .. screen height 48
Keep
Keeps aspect ratio
Aspect Checkbox Unchecked
during resizing
Ratio
Device that instrument
Device Select List of devices
is connected to
Source Data point
Data Controller mode, the
selection (page
Point property is read-only
63)
Text Font Size Font size of the text Number 6-200 px 18 px

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

6.23 Multi Alarm List


The Multi Alarm List instrument is used to display alarms on a site for all connected devices. New alarms are
added at the top of the list. Multi Alarm List contains following information:

InteliSCADA 2.1.0 Global Guide 101


Red when an alarm record exists
Exclamation mark icon Red & flashing when an unconfirmed alarm record exists
Grey when the alarm list is empty

Number of alarm records Active / unconfirmed (alarms marked with asterisk) / total

Level 1 (Warnings) highlighted in yellow


Level 2 (Shutdowns) highlighted in red
List of active alarms
Sensor Fail – black&white
ECU alarm – blue
Number of connected devices – green icon
Connection status of all
Number of not connected (connecting or disconnected)
devices in the site
devices – yellow&brown icon

Editor properties
Category Name Note Input type Range Default
1 .. 64
Name User name of the instrument Text UNICODE *)
chars
0 .. screen
width –
X Number 0
instrument
[X, Y] coordinates of top left width
corner 0 .. screen
General height –
Y Number 0
instrument
height
300 .. screen
Width Number 320
Width and height of the width
instrument 150 .. screen
Height Number 320
height
Keep Aspect Keeps aspect ratio during
Checkbox Unchecked
Ratio resizing
Background color of the
Color
Background header. The transparent color
Header picker #3B415B
Color can be set to make the
(page 65)
background invisible.

InteliSCADA 2.1.0 Global Guide 102


Category Name Note Input type Range Default
Border color of the instrument. Color
Border Color Transparent color can be set to picker #3B415B
make the border invisible. (page 65)
Design Background color of the
Color
Background instrument. The transparent
picker Transparent
Color color can be set to make the
(page 65)
background invisible.
Color
Text Text Color Color of the text picker #FFFFFF
(page 65)

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

6.24 Rectangle

Instrument that represents a rectangle (filled or just outline).

Editor properties
Category Name Note Input type Range Default
1 .. 64
User name of the
Name Text UNICODE *)
instrument
char
0 .. screen
width –
X Number
instrument
[X, Y] coordinates of top width
General left corner 0 .. screen
width –
Y Number
instrument
width
5 .. screen
width –
Width Number 200
instrument
width

InteliSCADA 2.1.0 Global Guide 103


Category Name Note Input type Range Default
5 .. screen
height –
Height Number 100
instrument
height
Keep Aspect Keeps aspect ratio during
Checkbox Unchecked
Ratio resizing
Border width Width of the border line Number 0 ..100 2
Color picker Gray
Border color Color of the border line
Design (page 65) (#7c7c7c)
Background Background color or Color picker
Transparent
color transparent (page 65)
Link to another screen in Screen
Link Link Select No link
site selection

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

6.25 Start Engine

The Start Engine button is used to star an engine (it sends the Start command to the selected device). The
button conveys 2 possible states:
Enabled – green color
Disabled – gray color (eg. "Access lock" state applied on the button)

Editor properties
Category Name Note Input type Range Default
1 .. 64 UNICODE
Name User name of the instrument Text *)
char
0 .. screen width –
X Number
[X, Y] coordinates of top left instrument width
General
corner 0 .. screen height –
Y Number
instrument height
Width and height of the
Width Number 10 .. screen width 40
instrument

InteliSCADA 2.1.0 Global Guide 104


Category Name Note Input type Range Default
Height Number 10 .. screen height 40
Device that instrument is
Device Select List of devices
connected to
Source Engine – Start command (if Data point
Data
available), the property is read- selection
Point
only (page 63)

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

6.26 Stop Engine

The Stop Engine button is used to stop an engine (it sends the Stop command to the selected device). The
button conveys 2 possible states:
Enabled – red color
Disabled – gray color (e.g. "Access lock" state applied on the button)

Editor properties
Category Name Note Input type Range Default
1 .. 64 UNICODE
Name User name of the instrument Text *)
chars
0 .. screen width –
X Number
[X, Y] coordinates of top left instrument width
General
corner 0 .. screen height –
Y Number
instrument height
Width Width and height of the Number 10 .. screen width 40
Height instrument Number 10 .. screen height 40
Device that instrument is
Device Select List of devices
connected to
Source Engine – Stop command (if Data point
Data
available), the property is read- selection
Point
only (page 63)

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

InteliSCADA 2.1.0 Global Guide 105


6.27 Trend

The Trend instrument shows a trend of selected data point values.

Editor properties
Category Name Note Input type Range Default
User name of the 1 .. 64 UNICODE
Name Text *)
instrument chars
0 .. screen width –
X Number
[X, Y] coordinates of top instrument width
left corner 0 .. screen height –
Y Number
General instrument height
Width Number 100 .. screen width 320
Width and height of the
100 .. screen
Height instrument Number 320
height
Keep Aspect Keeps aspect ratio during
Checkbox Unchecked
Ratio resizing
Device that Trend is
Device Select List of devices
connected to
Source Data point
A source for Trend plotting Filter: numeric or
Data Point selection
data (eg. Actual power) binary data points
(page 63)
One of the following types
can be used:
Constant – numeric
value defined by
Scale 0% Scale
Scale user Constant/Default Default
Type (page 62)
Default – low limit of
the Source data
point

InteliSCADA 2.1.0 Global Guide 106


Category Name Note Input type Range Default
Based on Scale 0% type:
Scale 0% Enter a constant
Number
Value (not available for
Default)
One of the following types
can be used:
Constant – numeric
Scale 100% value defined by
Select Constant/Default Default
Type user
Default – high limit
of the Source data
point
Based on Scale 100%
Type:
Scale 100%
Enter a constant Number
Value
(not available for
Default)
Maximum data time span
Time Range Number 1 .. 24 h 1
[h]
Sample Sampling period for data
Number 2 .. 300 s 2
Period point value acquisition
Header Toggle header visibility Checkbox Checked
1..32 UNICODE
Text Header text Text Trend
char
Header Background color of the
Color
Background header. The transparent
picker #3B415B
Color color can be set to make
(page 65)
the background invisible.

InteliSCADA 2.1.0 Global Guide 107


Category Name Note Input type Range Default
Border color of the
instrument. The Color
Border Color transparent color can be picker #3B415B
set to make the border (page 65)
invisible.
Background color of the
instrument. The Color
Background
transparent color can be picker #3B415B
Color
set to make the (page 65)
Design background invisible.
Color
Line Color Color of the trend line picker #ff2b00
(page 65)
Line Width Trend line width Number 1 .. 20 2
Legend Toggle legend visibility Checkbox Checked
Left Margin Margin for left border Number 0 .. 200 34
Bottom
Margin for bottom border Number 0 .. 200 28
Margin
Size for trend legend and
Font Size Number 6 .. 200 18
axis font
Text Color
Text Color Color of the text picker #FFFFFF
(page 65)
Link to another screen in
Link Link Select Screen selection No link
site

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

6.28 Wire Junction

Instrument that represents a connection of 2 busbars (wires). It can be linked to a LED type data point to
indicate its status in color.

InteliSCADA 2.1.0 Global Guide 108


Editor properties
Category Name Note Input type Range Default
1 .. 64
Name User name of the instrument Text UNICODE *)
chars
0 .. screen
width –
X Number
instrument
[X, Y] coordinates of top left width
General corner 0 .. screen
height –
Y Number
instrument
height
6 .. screen
Width Width and height of the Number 10
width
instrument – fixed ratio
6 .. screen
Height (height=width) Number 10
height
Device that instrument is
Device Select List of devices
connected to
Data source that instrument is Data point
Data LED type data
connected to. It can be data selection
Point points
point of either BIT or LED type. (page 63)
Source
Available only for data point of
BIT type.
Invert
Invert bit value Checkbox 0/1 Unchecked
Value
if checked: 0 = On, 1 = Off
if unchecked: 1 = On, 0 = Off
Active Available only for data point of Color
State BIT type. picker #1DD322
Color Defines color for bit in On state. (page 65)
Design
Inactive Available only for data point of Color
State BIT type. picker #7C7C7C
Color Defines color for bit in Off state. (page 65)

Note: *)
{Instrument Type} * {Last number +1 of instruments according type}

InteliSCADA 2.1.0 Global Guide 109


7 Automatically generated screen
6 back to Table of contents
The automatically generated screen is named "Auto-screen" and cannot be deleted. The "Auto-screen" can
be found in Screens panel (page 37). The content of this screen is generated automatically when entering in
the Preview (page 47) tab or in the Runtime (page 50). Each device in a site has a predefined column
template, which is rendered in the screen.
There are template instruments shared by all devices, see Device templates (page 111)
Single-line diagrams are application-specific and can be different, see Single-line diagrams: (page 117)
The device column template can show specific states, see Device column template states (page 124)
Any instrument within the template can show specific states, see Instrument non-standard states
(page 124)

InteliSCADA 2.1.0 Global Guide 110


Device templates
Controllers
Application Default template Instrument
SPTM
Device name – defined by user
SPI
Single-line diagram (see table below for
MINT
details)
AMF
Mode selector

Analog meter
Warning limit (yellow color) is
automatically set from Nominal
power Setpoint value up
Scale is defined from 0 kW to
125% value of Nominal power
Setpoint.

Engine State

Breaker State

Timer Text (eg. "Cooling")

Timer Value (eg. "Cooling" time left –


seconds)

Generator Frequency

Generator Voltage L1-N


Generator Voltage ph-ph (only for
GeCon Marine controllers)

Alarm List

Horn Reset Button

Fault Reset Button

InteliSCADA 2.1.0 Global Guide 111


Application Default template Instrument
MCB
Device name = defined by user
MGCB
Single-line diagram (see Single-line
diagrams: (page 117) for more information)

Mode selector

Analog meter
Warning limit (yellow color) is
automatically set from Mains Import
value
Scale is defined from 0 kW to 125%
value of Mains Import.

Breaker State

Timer Text

Timer Value

Mains Voltage L1

Mains Current L1

Bus Frequency

Alarm List

Horn Reset Button

Fault Reset Button

InteliSCADA 2.1.0 Global Guide 112


Application Default template Instrument
BTB (IGS NT)
Device name = defined by user

Single-line diagram (see Single-line


diagrams: (page 117) for more information)

Mode selector

Analog meter
Warning limit (yellow color) is
automatically set from Bus Left Import
value
Scale is defined from 0 kW to 125%
value of Bus Left Import.

Breaker State

Timer Text

Timer Value

Alarm List

Horn Reset Button

Fault Reset Button

InteliSCADA 2.1.0 Global Guide 113


Application Default template Instrument
PSC (IGS)
Device name = defined by user

Single-line diagram (see Single-line


diagrams: (page 117) for more information)

Mode selector

Analog meter

TotAvlPnom

Aux load

Aux Pwr fct

CURR. PwrBand

TotRunPact Q

NEXT PwrBand

Alarm List

Horn Reset Button

Fault Reset

InteliSCADA 2.1.0 Global Guide 114


Application Default template Instrument
BTB
Device name = defined by user
(InteliLite3)
Single-line diagram (see Single-line
diagrams: (page 117) for more information)

Mode selector

Analog meter
Warning limit (yellow color) is
automatically set from Bus Left Import
value
Scale is defined from 0 kW to 125%
value of Bus Left Import.

Breaker State

Timer Text

Timer Value

Bus Right Frequency

Bus Right Voltage

Alarm List

Horn Reset Button

Fault Reset Button

InteliSCADA 2.1.0 Global Guide 115


Application Default template Instrument
AS
Device name = defined by user
SS
Single-line diagram (see Single-line
AUX
diagrams: (page 117) for more information)
CMB
Mode selector
EME
PRP
Analog meter

Engine State

Timer Text

Timer Value

Run Hours

CPU Temperature

Speed Request

Battery Voltage

Oil Press

DEF Level

DPF Soot Load

Alarm List

Horn Reset Button

Fault Reset

InteliSCADA 2.1.0 Global Guide 116


Single-line diagrams:
Application diagram Instruments
SPtM / AMF
Load

Mains

Breaker (MCB)

Breaker (GCB)

Generator

Start Engine

Stop Engine

Breaker Button (GCB)

Breaker Button (MCB)


Note: DP = data point
SPI
Load

Mains

Breaker (MCB)

Breaker (GCB)

Generator

Start Engine

Breaker Button (GCB)

Stop Engine
Note: DP = data point

InteliSCADA 2.1.0 Global Guide 117


Application diagram Instruments
MINT

Breaker (GCB)

Breaker Button (GCB)

Start Engine

Stop Engine

Generator

Note: DP = data point


MCB
Load

Bus

Breaker (MCB)

Breaker Button (MCB)

Mains

Start Engine

Stop Engine
Note: DP = data point

InteliSCADA 2.1.0 Global Guide 118


Application diagram Instruments
MGCB
Load

Breaker (MGCB)

Breaker Button (MGCB)

Bus

Breaker (MCB)

Breaker Button (MCB)

Mains

Start Engine

Stop Engine
Note: DP = data point
BTB

Bus (Left)

Bus (BTB)

Breaker Button (BTB)

Bus (Right)

Note: DP = data point

InteliSCADA 2.1.0 Global Guide 119


Application diagram Instruments
AS, SS, AUX, CMB, EME, PRP
Breaker Button (Clutch Button/Close
Load)

Engine

Start Engine

Stop Engine

PSC

Load

Bus

Communication modules
Communication
Default template Instrument
module
InteliGateway
Device name – defined by
InteliFieldbus user
Gateway

Identification text

1. configured value (*)

2. configured value (*)

3. configured value (*)

4. configured value (*)

5. configured value (*)

InteliSCADA 2.1.0 Global Guide 120


Note: (*)
Actual displayed value depends on the user configuration of InteliFieldbus Gateway.

6 back to Automatically generated screen

InteliSCADA 2.1.0 Global Guide 121


8 Troubleshooting
8.1 Connection to server 122
8.2 Instrument non-standard states 124
8.3 Device column template states 124
8.4 Database compatibility 127
8.5 Error and warning notifications 128
8.6 Reporting an issue 130

6 back to Table of contents

8.1 Connection to server


When the connection to the server is lost, an error message is displayed on the screen. There are generally
two reasons that cause this error:
The server is overloaded with requests. In this case, the connection will be re-established as soon as
possible and InteliSCADA will continue working normally.
The server is down. Check the service status, see InteliSCADA as service on page 11.

InteliSCADA 2.1.0 Global Guide 122


When Runtime or Designer is started and the service is still not running, another error page is displayed.

InteliSCADA 2.1.0 Global Guide 123


8.2 Instrument non-standard states
Illustration picture State Reason
Client-server
communication error
No communication or server-device
communication error
or Sensor fail indication
Missing or invalid data
point
General error or any other error than No
communication, Access
limited.
It is forbidden to write setpoints or
run commands due to insufficient
Access limited
rights of the currently logged user
in the device
Device is connected, but no data
Waiting for data is available yet (data are still
reading or preparing).
Device is not working correctly.
Applied on Generator, Load and
Device init state
Mains instruments – the gray icon
is flashing

IMPORTANT: Remember to verify whether your personalized color settings are not interfering
with the indication of error states for any of your instruments.

6 back to Troubleshooting

8.3 Device column template states


Device column template is displayed on the Automatically generated screen (page 110) for each device
individually. It can show different states, see the table.

Template example Template state Reason

InteliSCADA 2.1.0 Global Guide 124


Connecting to the device
Column template is
loading. The content is
Loading template created dynamically based
on the connected device
type and device
application

Incorrect device
connection details
Unknown device or
Unknown device or unknown device
application application. For supported
devices and applications
see Supported ComAp
devices on page 17.

InteliSCADA 2.1.0 Global Guide 125


Device is already connected but
Reading data
the data are not loaded yet.

Device is connected and all data


are already loaded. The standard
Communicating communication is being
processed. See also Instrument
non-standard states (page 124)

InteliSCADA 2.1.0 Global Guide 126


An already communicating device
stopped to communicate. The
communication was disrupted for
some reason. Once the
Communication
communication is recovered (e.g.
interruption
device re-programming), the
template is verified and will
eventually reflect the device type
and application.

8.4 Database compatibility


When the InteliSCADA service starts it performs database data compatibility check. There are three possible
outcomes:
1. Both the supported database version and the local database version are the same. Then the service starts
and runs as usually.
2. The supported database version is higher than the local database version. Then a data migration process
is started and, if successful, the service starts and runs as usually.
3. The supported database version is lower than the local database version or the migration fails. Then the
service starts but responds with error page "ERROR - data version mismatch". You either have to upgrade
the InteliSCADA to higher version, which supports the version of local database or use older database file
with lower version. An older database file can be obtained from the backup created automatically before
installation.

InteliSCADA 2.1.0 Global Guide 127


Note: This scenario cannot occur unless you downgrade InteliSCADA to older version which doesn't
support the newer database version.

Note: The version of the database is different than the version of InteliSCADA. The version of the
database increases only when data schema changes.

6 back to Troubleshooting

8.5 Error and warning notifications


If an error occurred on the server, the user will be notified by an error message.

8.5.1 Data point import notifications:


Notification message Reason

Invalid token type – provided access token is


invalid

Not authorized to access site definition –


requested site definition is not included in the
access token

Site definition not found – storage does not


contain requested site definition

Device definition not found – storage does not


contain requested device definition

Task is already running – task was already started

Unable to get data from the device – it is not


possible to read data from the device

Unable to update data – it is not possible to write


data to database

InteliSCADA 2.1.0 Global Guide 128


8.5.2 Communication error notifications:
Notification message Reason
Failed for device Device 01 with error
Invalid archive.
The archive file is corrupted.
Failed for device Device 01 with error
Access denied. Please check the Wrong access code.
access code.
Failed for device Device 01 with error Wrong username or password.
The controller credentials are not Communication error will occur, if only the password is filled in for
valid. the controller, where the username is also required.
Failed for device Device 01 with error
Cannot connect to the controller with Not registered AirGate ID.
the specified AirGate ID.
Failed for device Device 01 with error Each ComAp device has limited number of slots used for clients
Currently no slot available to connect connections. Currently, there is no free slot, try to disconnect other
to the controller. client or try to connect later.
Failed for device Device 01 with error
Cannot connect to the controller.
Connection issues.
Please check the connectivity and
the connection parameters.
Failed for device Device 01 with error
The controller configuration is not Invalid controller configuration.
valid.
Failed for device Device 01 with error
Serial port is used by another application.
Access to the serial port is denied.
Failed for device Device 01 with error
Cannot connect to the controller. Access code is not set although it is required for the connection.
Please provide the access code.
Failed for device Device 01 with error
Cannot connect to the controller. The Public key read from AirGate server during ComAp Crypto Suite 2
AirGate server certificate is exchange is unknown.
unknown.

InteliSCADA 2.1.0 Global Guide 129


Notification message Reason
Failed for device Device 01 with error
Cannot connect to the controller on Entered password was invalid and because it was on untrusted
the untrusted interface. Please interface connection must be closed.
provide a password or verify it.
Failed for device Device 01 with error
The controller responded with an Other controller errors.
error (error name – error code).
Failed for device Device 01 with error
Internal server error (error name – Other communication errors.
error code).

8.5.3 License error notifications:


Notification message Reason
Unallowed device
The site "Site 01" doesn’t comply with the current license (Communication
detected in the opened
Gateway detected). To open it you need to upgrade your license.
site.

8.5.4 Disk space notifications:


Notification message Reason
Please free up some space to secure InteliSCADA can run smoothly. Minimum Disk space is running
disk space: 5 GB out

To free up the disk space please consider these actions:


Uninstall unused applications that are not needed for InteliSCADA functionality
Delete redundant InteliSCADA exported files, like exported history files, exported sites, etc...
Delete backup directories except for the latest at C:\ProgramData\ComAp PC
Suite\InteliSCADA-Backup

8.6 Reporting an issue


Open Settings section from the Preview (page 47) tab or from the Runtime (page 50) and click on Export All
button to export all the site data (site, device archives, images and logs incl. HW and OS specifications will be
packed into a single ZIP file).
Due to security concerns the connection details of all devices will be removed and the site will be locked by
universal password "support".
The file will be either downloaded automatically to the destination folder or a "Save as" dialog will appear
depending on your browser settings.
Attach this file when reporting an issue to your distributor or ComAp technical support at support@comap-
control.com.
6 back to Troubleshooting

InteliSCADA 2.1.0 Global Guide 130

You might also like