Recommended Generator Report - 2250DQKAG Project - AMNS - CGL#4 Comments - PTIN EAL1
Recommended Generator Report - 2250DQKAG Project - AMNS - CGL#4 Comments - PTIN EAL1
Project - AMNS_CGL#4
Comments - PTIN EAL1
Project Requirements
Emissions : No Preference
Step01 Emergency Illumination 1 100.0 142.86 100.0 142.86 None None 35.0 10.0 0.0
Step01 26V104- 1 32.0 40.0 32.0 40.0 None None 35.0 10.0 0.0
EMERGENCY-ACDB-
DB
Step01 26V102- 1 32.0 40.0 32.0 40.0 None None 35.0 10.0 0.0
EMERGENCY-ACDB-
DB
Step01 27V102- 1 25.0 31.25 25.0 31.25 None None 35.0 10.0 0.0
EMERGENCY-ACDB-
DB
Step Summary 189.0 254.0 189.0 254.0 None None 35.0 10.0 0.0
Step02 COATING POT AND 1 32.26 39.83 141.74 301.57 None None 35.0 10.0 0.0
REFRACTORY FOR
ZN WATER COOLING
SY
Step02 COATING POT AND 1 16.3 19.64 79.93 150.82 None None 35.0 10.0 0.0
REFRACTORY FOR
ZN INDUCTOR
BLOWERS
Step Summary 49.0 59.0 222.0 452.0 None None 35.0 10.0 0.0
Step03 ZINC PUMPS AND 1 16.3 19.64 79.93 150.82 None None 35.0 10.0 0.0
MOULDS ZINC
PUMPS
Step03 EMERGENCY DRIVE 1 20.0 22.22 17.78 22.22 None None 35.0 10.0 0.0
LINEUP -4 AUXILIARY
POWER
Step Summary 36.0 42.0 98.0 173.0 None None 35.0 10.0 0.0
Step04 COATING POT AND 1 16.3 19.64 79.93 150.82 None None 35.0 10.0 0.0
REFRACTORY FOR
ZNMG INDUCTOR
BLOWE
Step Summary 49.0 59.0 222.0 452.0 None None 35.0 10.0 0.0
Step05 2.2kW VFD Motor 2 1.22 1.26 0.98 1.09 None None 35.0 10.0 10.0
Step05 3.5kW VFD Motor 26 1.45 1.49 1.16 1.29 None None 35.0 10.0 10.0
Step05 5kW VFD Motor 2 2.78 2.87 2.22 2.47 None None 35.0 10.0 10.0
Step05 UPS Load 1 1 61.34 76.67 24.54 30.67 None None 35.0 10.0 10.0
Step Summary 107.0 124.0 61.0 71.0 None None 35.0 10.0 10.0
Step06 POT Through 644kVA 1 203.88 221.61 160.0 200.0 None None 35.0 10.0 10.0
Auto Transformer
Step Summary 204.0 222.0 160.0 200.0 None None 35.0 10.0 10.0
Step07 POT Through 644kVA 1 203.88 221.61 160.0 200.0 None None 35.0 10.0 10.0
Auto Transformer
Step Summary 204.0 222.0 160.0 200.0 None None 35.0 10.0 10.0
Step08 POT Through 644kVA 1 203.88 221.61 160.0 200.0 None None 35.0 10.0 10.0
Auto Transformer
Step Summary 204.0 222.0 160.0 200.0 None None 35.0 10.0 10.0
Step09 POT Through 644kVA 1 203.88 221.61 160.0 200.0 None None 35.0 10.0 10.0
Auto Transformer
Step Summary 204.0 222.0 160.0 200.0 None None 35.0 10.0 10.0
Step10 ZINC POT CRANE 1 22.22 22.91 22.22 24.69 None None 35.0 10.0 10.0
HANDLING
EQUIPMENT FOR
POT AREA FEE
Step Summary 22.0 23.0 22.0 25.0 None None 35.0 10.0 10.0
Step11 30kW SUMP PUMP 1 32.26 39.83 141.74 301.57 None None 35.0 10.0 0.0
Step Summary 32.0 40.0 142.0 302.0 None None 35.0 10.0 10.0
Step12 30kW SUMP PUMP 1 32.26 39.83 141.74 301.57 None None 35.0 10.0 0.0
Step Summary 32.0 40.0 142.0 302.0 None None 35.0 10.0 10.0
Step13 30kW SUMP PUMP 1 32.26 39.83 141.74 301.57 None None 35.0 10.0 0.0
Step Summary 32.0 40.0 142.0 302.0 None None 35.0 10.0 10.0
Step14 30kW SUMP PUMP 1 32.26 39.83 141.74 301.57 None None 35.0 10.0 0.0
Step Summary 32.0 40.0 142.0 302.0 None None 35.0 10.0 10.0
Step15 30kW SUMP PUMP 1 32.26 39.83 141.74 301.57 None None 35.0 10.0 0.0
Step Summary 32.0 40.0 142.0 302.0 None None 35.0 10.0 10.0
Step16 30kW SUMP PUMP 1 32.26 39.83 141.74 301.57 None None 35.0 10.0 0.0
Step Summary 32.0 40.0 142.0 302.0 None None 35.0 10.0 10.0
Project
Running Max Starting Cumulative Step Cumulative Peak
VTHD%
Project Summary
kW kVA kW kVA kW kVA kW kVA Limit
Emissions : No Preference
Running kVA : 1686.9 Max. Step kVA : 452.4 In Step 2 Cumulative Step kVA : 1948.7
Running NLL kVA : 1033.0 Peak kVA : None Cumulative Peak kVA : None
Alternator kW : 1838.15
Step1
Running kVA : 254.0 Starting kVA : 254.0 Cumulative Step kVA : 254.0
Alternator kW : 189.0
Running Amps : 198.5 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Running Amps : 55.58 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Running Amps : 43.42 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Step2
Running kVA : 59.0 Starting kVA : 452.0 Cumulative Step kVA : 707.0
Alternator kW : 48.56
COATING POT AND REFRACTORY FOR ZN WATER COOLING SY Three Phase Quantity : 1 In this Step
Category : Motor
Running Amps : 55.34 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
COATING POT AND REFRACTORY FOR ZN INDUCTOR BLOWERS Three Phase Quantity : 1 In this Step
Category : Motor
Step3
Running kVA : 42.0 Starting kVA : 173.0 Cumulative Step kVA : 487.0
Alternator kW : 36.3
ZINC PUMPS AND MOULDS ZINC PUMPS Three Phase Quantity : 1 In this Step
Category : Motor
Running Amps : 27.29 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
EMERGENCY DRIVE LINEUP -4 AUXILIARY POWER Three Phase Quantity : 1 In this Step
Running Amps : 30.88 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Step4
Running kVA : 59.0 Starting kVA : 452.0 Cumulative Step kVA : 808.0
Alternator kW : 48.56
Category : Motor
Running Amps : 55.34 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
COATING POT AND REFRACTORY FOR ZNMG INDUCTOR BLOWE Three Phase Quantity : 1 In this Step
Category : Motor
Running Amps : 27.29 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Step5
Running kVA : 124.0 Starting kVA : 71.0 Cumulative Step kVA : 486.0
Alternator kW : 149.82
Category : Motor
Running Amps : 1.75 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Alternator kW : 1.71
Category : Motor
Running Amps : 2.07 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Alternator kW : 2.03
Category : Motor
Running Amps : 3.99 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Alternator kW : 3.89
Category : UPS
Running Amps : 106.53 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Alternator kW : 85.84
THDI % : 26 THDV % : 10
Step6
Running kVA : 222.0 Starting kVA : 200.0 Cumulative Step kVA : 739.0
Alternator kW : 285.31
POT Through 644kVA Auto Transformer Three Phase Quantity : 1 In this Step
Running Amps : 307.93 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Alternator kW : 285.31
THDV % : 10
Step7
Running kVA : 222.0 Starting kVA : 200.0 Cumulative Step kVA : 960.0
Alternator kW : 285.31
POT Through 644kVA Auto Transformer Three Phase Quantity : 1 In this Step
Running Amps : 307.93 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Alternator kW : 285.31
THDV % : 10
Running kVA : 222.0 Starting kVA : 200.0 Cumulative Step kVA : 1182.0
Alternator kW : 285.31
POT Through 644kVA Auto Transformer Three Phase Quantity : 1 In this Step
Running Amps : 307.93 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Alternator kW : 285.31
THDV % : 10
Step9
Running kVA : 222.0 Starting kVA : 200.0 Cumulative Step kVA : 1403.0
Alternator kW : 285.31
POT Through 644kVA Auto Transformer Three Phase Quantity : 1 In this Step
Running Amps : 307.93 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Alternator kW : 285.31
THDV % : 10
Step10
Alternator kW : 31.11
ZINC POT CRANE HANDLING EQUIPMENT FOR POT AREA FEE Three Phase Quantity : 1 In this Step
Category : Motor
Running Amps : 31.83 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Alternator kW : 31.11
Step11
Running kVA : 40.0 Starting kVA : 302.0 Cumulative Step kVA : 1750.0
Alternator kW : 32.26
Category : Motor
Running Amps : 55.34 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Step12
Alternator kW : 32.26
Category : Motor
Running Amps : 55.34 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Step13
Running kVA : 40.0 Starting kVA : 302.0 Cumulative Step kVA : 1829.0
Alternator kW : 32.26
Category : Motor
Running Amps : 55.34 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Step14
Running kVA : 40.0 Starting kVA : 302.0 Cumulative Step kVA : 1869.0
Alternator kW : 32.26
Category : Motor
Running Amps : 55.34 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Step15
Running kVA : 40.0 Starting kVA : 302.0 Cumulative Step kVA : 1909.0
Alternator kW : 32.26
Category : Motor
Running Amps : 55.34 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
Step16
Running kVA : 40.0 Starting kVA : 302.0 Cumulative Step kVA : 1949.0
Alternator kW : 32.26
Category : Motor
Running Amps : 55.34 Max. % Voltage Dip : 35.0 Max. % Frequency Dip : 10.0
1 35 3 0.1 10 1 0.1
2 35 4 0.1 10 1 0.1
3 35 2 0.1 10 1 0.1
4 35 4 0.1 10 1 0.1
5 35 1 0.1 10 1 0.1
6 35 3 0.1 10 1 0.1
7 35 3 0.1 10 1 0.1
8 35 3 0.1 10 1 0.1
9 35 3 0.1 10 1 0.1
10 35 1 0.1 10 1 0.1
11 35 3 0.1 10 1 0.1
12 35 3 0.1 10 1 0.1
13 35 3 0.1 10 1 0.1
14 35 3 0.1 10 1 0.1
15 35 3 0.1 10 1 0.1
16 35 3 0.1 10 1 0.1
Note: Please refer to the model Spec. sheet for bandwidths used to report recovery times. For products manufactured in the United
Kingdom it may be assumed that recovery times are based on ISO8528-5 G2 class bandwidths. Voltage and frequency recovery times
are estimates. Typically, allow five to ten seconds between application of load steps when designing your system.
**Please note that in some cases the voltage and frequency recovery time estimates are not shown in list. This is a result of "dummy"
data points temporarily being used to fill data gaps in the GenSize database. Please disregard these blank results.
Value
0 1 2 3 4 5 6 7 8 9 10