KFSS Manual TCS
KFSS Manual TCS
PAGE : 1 of 15
INNOVATIVE SOLUTIONS.
902, SPARTA BUILDING,
HIRANANDANI ESTATE,
Thane (W) 400 604,
Website : www.innovativesol.in
TABLE OF CONTENTS
PAGE : 2 of 15
1.1 Purpose:
The intent of this manual is to provide the user with the information necessary to adequately select,
operate and maintain FIRETOL Kitchen Fire Extinguishment System, required to protect a specific
hazard.
The system is operated and controlled automatically by the controller in the Control Panel. The Control
Panel has features like Battery Back-up & Battery fault Indication etc. Remote Manual Pull Station is
provided in the system so as to operate the system manually.
System Operation
As the fire is detected by Heat Sensing Cable, controller activates the Cylinder and Extinguishing Agent
is expelled through the Discharge outlet, Discharge Piping and Nozzles on to the fire.
SECTION 2 : SYSTEM COMPONENTS
PAGE : 6 of 15
Extinguishing Agent is a specially formulated foam solution of Polyvalent and Hetero-organic compounds
designed for fast Extinguishment of grease-related fires. The agent is shipped in a translucent plastic
container. The agent is brownish in colour.
2.1.2 Nozzles:
There are various types of discharge nozzles each designed to distribute the liquid agent in a uniform
pattern throughout the hazard area.
The Blow-off Cap is used to cover the tip of the nozzle preventing any grease accumulation.
STAINLESS
STEEL WIRE
METAL CAP
In FIRETOL Kitchen Fire Extinguishment System Heat Sensing Cable is used for sensing the heat and
detecting the fire.
Fixed Temperature heat sensing cable is comprised of two steel conductors individually insulated with a
heat sensitive polymer that are twisted together. At 185°C temperature the heat sensitive polymer
insulation breaks down permitting the steel conductors to move into contact with each other. This forms a
closed switch contact that can be used to signal an alarm condition at the control panel.
2.2.2 Thermocouple:
In FIRETOL Kitchen Fire Extinguishment System Thermocouple is used for sensing the heat.
Thermocouple Operation:
The Thermocouple detect the heat when temperature reaches at 120°C & it gives pre activation alarm.
When the temperature reaches at 185°C, system will activate through Control Panel.
It is used to operate FIRETOL Kitchen Fire Extinguishment System manually when required. System
immediately operates when activated.
The Remote Manual Pull Station is required for the manual actuation of the system. It is of Lift and pull
design for avoiding accidental actuation. It is provided with 10 A, 120VAC snap Action Switch which on
actuation generates signal to the control panel for actuation. The remote manual pull station should be
mounted at a point of egress and positioned at a height determined by the authority having jurisdiction.
2.5 Hooter:
It is designed as flash wall mount for easy installation. It generates audio alarm of 100 db along
with flashing light. It is placed where it is clearly visible and audible.
SECTION 3 : SYSTEM DESIGN
PAGE : 9 of 15
The FIRETOL Kitchen Fire Extinguishment System is designed to be used on a number of different types of
restaurant cooking appliances and hood and duct configurations. The FIRETOL Kitchen Fire
Extinguishment System use compatible agents and components; therefore, they may be used together for
cooking appliance, hood, and duct protection.
All duct protection is without limitation of maximum duct length (unlimited length). This includes all
varieties of ductworks both horizontal and vertical including ducts that run at angles to the horizontal and
ducts with directional bends. The FIRETOL Kitchen Fire Extinguishment System uses different duct nozzles
depending on the size of duct being protected.
Hazard Zone
The hazard zone is defined as a theoretical, flat and level, rectangular surface that includes all of the
cooking hazards of the protected appliances under a common hood. The purpose of the hazard zone is
to provide a means of locating the appliances and the overlapping nozzles, as well as aiming the
overlapping nozzles.
It is defined as overlapping nozzles appliance protection that covers the appliance line-up located under
the total hood length. All appliances requiring protection are the appliances under the hood that can be
an ignition source of grease in the hood, grease removal device or the duct.
1. All overlapping appliance nozzles must be located under a common hood at the same height above
the hazard zone, in a straight line aimed at the centreline of the hazard zone. The overlapping and
multiple group overlapping protection.
2. The hazard zone must be positioned (located) so that all appliance hazard surfaces within the zone.
The distribution piping network is broken down into four specific pipe runs: Supply Line, Duct Branch Line,
Plenum Branch Line, and Appliance Branch Line.
The Supply Line is defined as the length of pipe which runs from the Cylinder outlet to the last branch line
(whether a duct, appliance, or plenum branch line). This includes all supply line fittings except for the tees
or elbows leading to the branch lines.
The Duct Branch Line is defined as the length of pipe which runs from the supply line to the duct
nozzle(s). This indicates all branch line fittings as well as the tee or elbow used to start the branch line.
The Plenum Branch Line is defined as the length of pipe which runs from the supply line to the plenum
nozzle(s). This includes all branch line fittings as well as the tee or elbow used to start the branch line.
The Appliance Branch Line is defined as the length of pipe which runs from the supply line to the
appliance nozzle(s). This includes all branch line fittings as well as the tee or elbow used to start the
branch line.
SECTION 4 : WORKING PROCEDURE
PAGE : 11 of 15
As soon as the fire (heat) is detected the signal is send to the Control Panel.
The Cylinder is actuated and Extinguishing Agent discharges through the Distribution piping,
Nozzles on to the fire.
Simultaneously the other operations are also carried out by Control Panel e.g. activation of Audio
visual alarm, turning off the Exhaust fan.
The system is also provided with an additional feature like Battery backup in case when power
supply cutoff.
SECTION 5 : CLEAN-UP PROCEDURE
PAGE : 12 of 15
Check the pressure of the cylinder and release by Manual Actuator on the valve if any pressure
observed.
Flush the discharge line along with nozzles with clean water.
Wash all the discharged areas with clean water and wipe it dry.
SECTION 6 : RECHARGE / RESTTING
PAGE : 13 of 15
If no faults indicated on Panel display, reconnect the Cylinder and Solenoid Valve.
Abbreviations:
FREQUENCY:
1. Dy = Daily 2. Wk = Weekly 3. Mo = Monthly
4. Qt = Quarterly 5. Se = Semi-annually 6. An = Annually
TYPE ACTIVITY:
1. I = Inspection 2. T = Testing 3. PM = Preventive
Maintenance
PERFORMED BY:
1. F = Facility Personnel 2. C = Contractor
Equipment / Task Freq. Type By
General Condition Mo I F
System Servicing Se PM C
Control Panel Dy I F
Piping Se T C
Nozzle Se T C
Pressure Gauge Mo I F
Battery An I C