Fire Alarm System Components & General Notes
Fire Alarm System Components & General Notes
2-2020
INTRODUCTION:
The aim of the system is to make an early warning indicating that the building has a fire and to
allow people to be able to vacate the building in a timely manner and give a signal to the
firefighting system to start working.
1) Detectors
2) Manual call point
3) Bell / alarm devices
4) Fire alarm control panel
5) Other items.
1- DETECTORS:
The function of the sensors is to detect the presence of fire and thus is the main component of the
system.
DETECTORS TYPE:
The function of the sensors is to detect the presence of fire and thus is the main component of the
system. Detector types include:
Smoke detectors:
The smoke detector is responding to smoke particles in the air. And it is the most used type.
1
Heat detectors:
Heat detectors respond to the temperature.
Type B: Rate-of-Rise
Rate-of-Rise (ROR) heat detectors operate on a rapid rise in element
temperature of 6.7° to 8.3°C (12° to 15°F) increase per minute,
irrespective of the starting temperature.
2
Flame detectors:
Very Early Smoke Detection Apparatus (VESDA) /Aspirated smoke detectors (ASD)
3
Duct detectors:
Gas detectors:
There are many shapes and models for each type, depending on the manufacturer
4
DETECTOR TYPE SELECTION:
5
6
According to building height
7
8
DETECTOR COVERAGE AREA NOTES:
DETECTORS DISTRIBUTION:
9
2- BREAK GLASS FOR MANUAL FIRE CALL POINT:
- A manual call point is a device which enables personnel to raise an alarm in the event of a fire incident by
pressing a frangible element to activate the alarm system.
- A fire alarm call point should be installed at a height of 1.4m above floor level at easily accessible and
conspicuous positions. This includes on exit routes, at the entry floor landing of staircases and at all exits to the
open air.
- A fire alarm call point should also be spaced so that one may always be found within a maximum distance of 30m
apart.
10
3- ALARM ITEMS:
The minimum sound level of a sounder device should be 65dB(A) or 5dB(A) above a background noise (if lasting more
than 30 seconds) and at a frequency between 500Hz and 1000Hz. The maximum sound level should not exceed 120dB(A).
The panel receives information from devices designed to detect and report fires, monitors their operational integrity and
provides for automatic control of equipment, and transmission of information necessary to prepare the facility for fire
based on a predetermined sequence. The panel may also supply electrical energy to operate any associated initiating
device, notification appliance, control, transmitter, or relay. There are four basic types of panels: coded panels,
conventional panels, addressable panels, and multiplex systems.
Conventional type:
11
Addressable type:
5- other items:
12
Isolation module Module to isolate a fault at the fire alarm loop put
each 20 device of the loop.
Battery calculation:
STANDBY TOTAL STANDBY
ALARM CURRENT TOTAL ALARM
DESCRIPTION CURRENT PER QUANTITY CURRENT PER QUANTITY
PER UNIT (AMP) CURRNT PER ITEM
UNIT (AMP) ITEM
FIRE ALARM CONTROL PANEL 0.4 X 1 = 0.4 0.4 X 1 = 0.4
Fire Alarm Bell 0 X 31 = 0 0.225 X 31 = 6.975
Fire Alarm Horn With Strobe Light 0 X 3 = 0 0.225 X 3 = 0.675
MANUAL CALL POINT 0.0004 X 31 = 0.0124 0.0065 X 31 = 0.2015
SMOKE DETECTOR WITH AUDIBLE BASE 0.0004 X 128 = 0.0512 0.0065 X 128 = 0.832
SMOKE DETECTOR 0.0003 X 243 = 0.0729 0.0065 X 243 = 1.5795
HEAT DETECTOR 0.0003 X 14 = 0.0042 0.0065 X 14 = 0.091
Combined Smoke Heat Detector 0.0003 X 28 = 0.0084 0.0065 X 28 = 0.182
MIMIC 0.03 X 14 = 0.42 0.15 X 14 = 2.1
FAULT ISOLATOR 0.0004 X 31 = 0.0124 0.005 X 31 = 0.155
CONTROL MODULE 0.0004 X 12 = 0.0048 0.007 X 12 = 0.084
MONITOR MODULE 0.0004 X 7 = 0.0028 0.007 X 7 = 0.049
TOTAL SYSTEM STANDBY CURRENT (AMP) 0.9891 TOTAL SYSTEM ALARM CURRENT (AMP) 13.324
REQUIRED
REQUIRED TOTAL SYSTEM TOTAL SYSTEM REQUIRED ALARM
STANDBY REQUIRED ALARM
STANDBY STADBY CURRENT ALARM CURRENT CAPACITY (AMP-
CAPACITY (AMP- TIME (HRS)
TIME(HRS) (AMP) (AMP) HOURS)
PREPARED FOR: HOURS)
24 X 0.9891 = 23.7384 0.5 X 13.324 = 6.662
REQUIRED
REQUIRED ALARM ADJSTED BATTERY
STANDBY TOTAL CAPACITY TOTAL CAPACITY
CAPACITY (AMP- SAFETY FACTOR CAPACITY (AMP-
CAPACITY (AMP- (AMP-HOURS) (AMP-HOURS)
HOURS) HOURS)
HOURS)
23.7384 + 6.662 = 30.4004 30.4004 X 1.25 = 38.0005
USE: 2X12V, 40 Ah
13
GENERAL NOTES:
Detectors distribution:
14
15
Call point:
16
Bell:
17
At bedrooms especially at hotels, detector with sounder base used
Sources
NFPA
Cooper A guide to fire alarm systems design BS 5839 Part 1:2002
menvier FIRE SYSTEM DESIGN GUIDE
PDH Course M219
www.PDHonline.org
Introduction to Fire Alarm & Detection Systems
Course Content
siemens synova tm product catalog
global system technology fire alarm datasheet
Novar GmbH a Honeywell Company
Blogger: Engfreelancer
2-2020
18