3.room Checksums
3.room Checksums
By Trane
0B1F-Dispensary (Y te)
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 18 Mo/Hr: 8 / 18 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 19 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.5 20.7
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.48 0.48 32.88 0.48 35.29 Partition/Door -1.53 -1.53 103.38 Diffuser 120 120
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 120 120
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 120 120
Infiltration 0.10 0.10 6.85 0.02 1.47 Infiltration -0.06 -0.06 4.05 Sec Fan 0 0
Sub Total ==> 0.58 0.00 0.58 39.73 0.50 36.76 Sub Total ==> -1.59 -1.59 107.43 Nom Vent 14 14
AHU Vent 14 14
Internal Loads Internal Loads Infil 2 2
Lights 0.10 0.02 0.12 8.22 0.10 7.35 Lights 0.10 0.12 -8.11 MinStop/Rh 0 0
People 0.26 0 0 17.81 0.16 11.76 People 0.16 0 -10.81 Return 122 122
Misc 0.15 0.00 0.15 10.27 0.15 11.03 Misc 0.15 0.15 -10.14 Exhaust 16 16
Sub Total ==> 0.51 0.02 0.53 36.30 0.41 30.15 Sub Total ==> 0.41 0.43 -29.05 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.06 -0.06 0.00 0.00 0.06 4.41 Ceiling Load -0.02 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.08 -5.48 0.00 0.00 Ventilation Load 0.00 -0.19 12.84 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.39 0.39 26.71 0.39 28.68 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.09 6.08
Sup. Fan Heat 0.04 2.74 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 11.5 11.5
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.04 2.70 Lps/m² 11.96 11.96
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 63.58
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.31
W/m² 188.05 -138.00
Grand Total ==> 1.54 -0.04 1.46 100.00 1.36 100.00 Grand Total ==> -1.20 -1.48 100.00 No. People 2
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 1 of 80
Room Checksums
By Trane
0B1F-Employee Lounge
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 20 Mo/Hr: 8 / 20 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 24 / 18 OADB: 27 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.2 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.3 20.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 3.46 0.40 3.86 17.49 3.46 17.24 Wall Cond -3.32 -3.75 15.66
Partition/Door 5.60 5.60 25.37 5.60 27.90 Partition/Door -18.93 -18.93 79.07 Diffuser 1,779 1,779
Floor 0.48 0.48 2.17 0 2.39 Floor -2.30 -2.30 9.61 Terminal 1,779 1,779
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,779 1,779
Infiltration 1.81 1.81 8.20 0.33 1.64 Infiltration -1.37 -1.37 5.72 Sec Fan 0 0
Sub Total ==> 11.35 0.40 11.75 53.24 9.87 49.18 Sub Total ==> -25.92 -26.35 110.07 Nom Vent 304 304
AHU Vent 304 304
Internal Loads Internal Loads Infil 54 54
Lights 2.11 0.53 2.64 11.96 2.11 10.51 Lights 2.11 2.64 -11.03 MinStop/Rh 0 0
People 5.72 0 6 25.92 3.52 17.54 People 3.52 4 -14.70 Return 1,833 1,833
Misc 3.30 0.00 3.30 14.95 3.30 16.44 Misc 3.30 3.30 -13.78 Exhaust 357 357
Sub Total ==> 11.13 0.53 11.66 52.83 8.93 44.49 Sub Total ==> 8.93 9.46 -39.52 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 1.27 -1.27 0.00 0.00 1.27 6.33 Ceiling Load -0.38 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -1.99 -9.02 0.00 0.00 Ventilation Load 0.00 -4.19 17.50 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -0.48 -0.48 2.01
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -1.90 7.94
Sup. Fan Heat 0.65 2.95 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 17.1 17.1
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.48 2.01 Lps/m² 8.09 8.09
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 56.88
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.04
W/m² 142.05 -99.11
Grand Total ==> 23.75 -0.34 22.07 100.00 20.07 100.00 Grand Total ==> -17.85 -23.94 100.00 No. People 44
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 2 of 80
Room Checksums
By Trane
0B1F-F&B areas
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 18 Mo/Hr: 8 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 19 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 18.0 18.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 18.0 17.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 7.25 7.25 50.14 7.29 54.12 Partition/Door -11.75 -11.75 35.33 Diffuser 2,147 2,147
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 2,147 2,147
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 2,147 2,147
Infiltration 1.57 1.57 10.86 0.40 2.97 Infiltration -0.67 -0.67 2.01 Sec Fan 0 0
Sub Total ==> 8.82 0.00 8.82 61.00 7.69 57.09 Sub Total ==> -12.42 -12.42 37.34 Nom Vent 62 62
AHU Vent 62 62
Internal Loads Internal Loads Infil 33 33
Lights 1.30 0.32 1.62 11.20 1.30 9.65 Lights 1.30 1.62 -4.87 MinStop/Rh 0 0
People 1.17 0 1 8.09 0.72 5.35 People 0.72 1 -2.16 Return 2,180 2,180
Misc 2.02 0.00 2.02 13.97 2.02 15.00 Misc 2.02 2.02 -6.07 Exhaust 95 95
Sub Total ==> 4.49 0.32 4.81 33.26 4.04 29.99 Sub Total ==> 4.04 4.36 -13.11 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 1.72 -1.72 0.00 0.00 1.74 12.92 Ceiling Load 0.74 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.04 0.28 0.00 0.00 Ventilation Load 0.00 -0.55 1.65 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -24.67 -24.67 74.17
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.39 1.17
Sup. Fan Heat 0.79 5.46 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 2.9 2.9
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.41 -1.23 Lps/m² 15.91 15.91
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 137.54
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.65
W/m² 115.57 -242.70
Grand Total ==> 15.03 -1.40 14.46 100.00 13.47 100.00 Grand Total ==> -32.31 -33.26 100.00 No. People 9
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 3 of 80
Room Checksums
By Trane
0B1F-F&B Store
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 19 Mo/Hr: 8 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 18 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.2 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 18.0 18.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 18.0 17.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 2.73 2.73 68.59 2.73 72.99 Partition/Door -4.41 -4.41 48.30 Diffuser 597 597
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 597 597
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 597 597
Infiltration 0.24 0.24 6.03 0.07 1.87 Infiltration -0.11 -0.11 1.20 Sec Fan 0 0
Sub Total ==> 2.97 0.00 2.97 74.62 2.80 74.87 Sub Total ==> -4.52 -4.52 49.51 Nom Vent 10 10
AHU Vent 10 10
Internal Loads Internal Loads Infil 5 5
Lights 0.21 0.05 0.26 6.53 0.21 5.61 Lights 0.21 0.26 -2.85 MinStop/Rh 0 0
People 0.19 0 0 4.77 0.12 3.21 People 0.12 0 -1.31 Return 602 602
Misc 0.33 0.00 0.33 8.29 0.33 8.82 Misc 0.33 0.33 -3.61 Exhaust 16 16
Sub Total ==> 0.73 0.05 0.78 19.60 0.66 17.65 Sub Total ==> 0.66 0.71 -7.78 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.28 -0.28 0.00 0.00 0.28 7.49 Ceiling Load 0.12 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.01 0.25 0.00 0.00 Ventilation Load 0.00 -0.09 0.99 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -5.24 -5.24 57.39
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.06 0.66
Sup. Fan Heat 0.22 5.53 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 1.7 1.7
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.07 -0.77 Lps/m² 27.12 27.12
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 142.70
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.26
W/m² 189.93 -411.42
Grand Total ==> 3.98 -0.23 3.98 100.00 3.74 100.00 Grand Total ==> -8.98 -9.13 100.00 No. People 1
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 4 of 80
Room Checksums
By Trane
0B1F-F&B Store and Pre
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 18 Mo/Hr: 8 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 19 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 18.0 18.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 18.0 17.7
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 11.02 11.02 48.57 11.09 53.16 Partition/Door -17.90 -17.90 34.44 Diffuser 3,328 3,328
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 3,328 3,328
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 3,328 3,328
Infiltration 2.13 2.13 9.39 0.54 2.59 Infiltration -0.91 -0.91 1.75 Sec Fan 0 0
Sub Total ==> 13.15 0.00 13.15 57.96 11.63 55.75 Sub Total ==> -18.81 -18.81 36.19 Nom Vent 126 126
AHU Vent 126 126
Internal Loads Internal Loads Infil 45 45
Lights 1.76 0.44 2.20 9.70 1.76 8.44 Lights 1.76 2.20 -4.23 MinStop/Rh 0 0
People 2.38 0 2 10.49 1.46 7.00 People 1.46 1 -2.81 Return 3,373 3,373
Misc 3.66 0.00 3.66 16.13 3.66 17.55 Misc 3.66 3.66 -7.04 Exhaust 171 171
Sub Total ==> 7.80 0.44 8.24 36.32 6.88 32.98 Sub Total ==> 6.88 7.32 -14.08 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 2.33 -2.33 0.00 0.00 2.35 11.27 Ceiling Load 1.00 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.08 0.35 0.00 0.00 Ventilation Load 0.00 -1.11 2.14 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -39.15 -39.15 75.32
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.79 1.52
Sup. Fan Heat 1.22 5.38 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 3.8 3.8
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.56 -1.08 Lps/m² 18.18 18.18
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 132.97
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.31
W/m² 136.67 -278.71
Grand Total ==> 23.28 -1.89 22.69 100.00 20.86 100.00 Grand Total ==> -50.08 -51.98 100.00 No. People 18
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 5 of 80
Room Checksums
By Trane
0B1F-FCC
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 18 Mo/Hr: 8 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 19 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.6 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.95 0.95 33.10 0.95 35.98 Partition/Door -3.05 -3.05 108.93 Diffuser 235 235
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 235 235
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 235 235
Infiltration 0.20 0.20 6.97 0.03 1.14 Infiltration -0.12 -0.12 4.29 Sec Fan 0 0
Sub Total ==> 1.15 0.00 1.15 40.07 0.98 37.12 Sub Total ==> -3.17 -3.17 113.21 Nom Vent 23 23
AHU Vent 23 23
Internal Loads Internal Loads Infil 5 5
Lights 0.19 0.05 0.24 8.36 0.19 7.20 Lights 0.19 0.24 -8.57 MinStop/Rh 0 0
People 0.43 0 0 14.98 0.27 10.23 People 0.27 0 -9.64 Return 240 240
Misc 0.40 0.00 0.40 13.94 0.40 15.15 Misc 0.40 0.40 -14.29 Exhaust 28 28
Sub Total ==> 1.02 0.05 1.07 37.28 0.86 32.58 Sub Total ==> 0.86 0.91 -32.50 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.11 -0.11 0.00 0.00 0.11 4.17 Ceiling Load -0.03 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.13 -4.53 0.00 0.00 Ventilation Load 0.00 -0.32 11.43 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.69 0.69 24.04 0.69 26.14 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.14 5.00
Sup. Fan Heat 0.09 3.14 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 9.8 9.8
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.08 2.86 Lps/m² 11.73 11.73
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 65.72
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.60
W/m² 178.39 -132.66
Grand Total ==> 2.97 -0.06 2.87 100.00 2.64 100.00 Grand Total ==> -2.34 -2.80 100.00 No. People 3
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 6 of 80
Room Checksums
By Trane
0B1F-Foot massage
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 12 / 14 Mo/Hr: 12 / 14 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 24 / 21 / 14 OADB: 24 OADB: 2 SADB 13.0 30.0
Ra Plenum 23.7 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.8 21.5
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 9.96 0.00 9.96 75.68 9.96 81.44 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.03 0.00 0.03 0.23 0.03 0.25 Glass/Door Cond -1.35 -1.35 11.32
Cooling Heating
Wall Cond 0.45 0.12 0.57 4.33 0.45 3.68 Wall Cond -0.84 -1.10 9.22
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 1,083 1,083
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,083 1,083
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,083 1,083
Infiltration 0.31 0.31 2.36 0.03 0.25 Infiltration -0.38 -0.38 3.19 Sec Fan 0 0
Sub Total ==> 10.75 0.12 10.87 82.60 10.47 85.61 Sub Total ==> -2.57 -2.83 23.72 Nom Vent 53 53
AHU Vent 53 53
Internal Loads Internal Loads Infil 15 15
Lights 0.59 0.15 0.74 5.62 0.59 4.82 Lights 0.59 0.73 -6.12 MinStop/Rh 0 0
People 0.99 0 1 7.52 0.61 4.99 People 0.61 1 -5.11 Return 1,098 1,098
Misc 0.37 0.00 0.37 2.81 0.37 3.03 Misc 0.37 0.37 -3.10 Exhaust 68 68
Sub Total ==> 1.95 0.15 2.10 15.96 1.57 12.84 Sub Total ==> 1.57 1.71 -14.33 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.19 -0.19 0.00 0.00 0.19 1.55 Ceiling Load -0.11 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.21 -1.60 0.00 0.00 Ventilation Load 0.00 -0.73 6.12 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -9.75 -9.75 81.73
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.33 2.77
Sup. Fan Heat 0.40 3.04 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.9 4.9
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 17.75 17.75
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 73.41
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.14
W/m² 241.62 -189.26
Grand Total ==> 12.89 0.08 13.16 100.00 12.23 100.00 Grand Total ==> -10.86 -11.93 100.00 No. People 8
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 7 of 80
Room Checksums
By Trane
0B1F-Kitchen
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 20 Mo/Hr: 8 / 21 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 24 / 18 OADB: 26 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.2 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.9 21.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.76 0.09 0.85 1.37 0.79 1.35 Wall Cond -0.74 -0.83 1.53
Partition/Door 3.94 3.94 6.36 4.02 6.88 Partition/Door -15.71 -15.71 28.99 Diffuser 5,180 5,180
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 5,180 5,180
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 5,180 5,180
Infiltration 2.14 2.14 3.46 0.31 0.53 Infiltration -1.49 -1.49 2.75 Sec Fan 0 0
Sub Total ==> 6.84 0.09 6.93 11.19 5.12 8.76 Sub Total ==> -17.94 -18.03 33.27 Nom Vent 110 110
AHU Vent 110 110
Internal Loads Internal Loads Infil 58 58
Lights 2.87 0.72 3.59 5.80 2.87 4.91 Lights 2.87 3.58 -6.61 MinStop/Rh 0 0
People 2.07 0 2 3.34 1.27 2.17 People 1.27 1 -2.34 Return 5,239 5,239
Misc 47.80 0.00 47.80 77.21 47.80 81.77 Misc 47.80 47.80 -88.21 Exhaust 168 168
Sub Total ==> 52.74 0.72 53.46 86.35 51.94 88.85 Sub Total ==> 51.94 52.65 -97.16 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 1.38 -1.38 0.00 0.00 1.40 2.39 Ceiling Load -0.42 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.39 -0.63 0.00 0.00 Ventilation Load 0.00 -1.52 2.80 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -85.56 -85.56 157.89
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.69 1.27
Sup. Fan Heat 1.91 3.09 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 2.1 2.1
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -1.04 1.92 Lps/m² 21.67 21.67
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 79.41
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.66
W/m² 272.76 -223.37
Grand Total ==> 60.96 -0.57 61.91 100.00 58.46 100.00 Grand Total ==> -51.98 -54.19 100.00 No. People 16
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 8 of 80
Room Checksums
By Trane
0B1F-Lobby lift 1
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 21 Mo/Hr: 8 / 22 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 23 / 17 OADB: 26 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.3 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.7 21.3
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 1.14 1.14 24.15 1.15 26.02 Partition/Door -4.46 -4.46 100.22 Diffuser 392 392
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 392 392
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 392 392
Infiltration 0.24 0.24 5.08 0.03 0.68 Infiltration -0.19 -0.19 4.27 Sec Fan 0 0
Sub Total ==> 1.38 0.00 1.38 29.24 1.18 26.70 Sub Total ==> -4.65 -4.65 104.49 Nom Vent 26 26
AHU Vent 26 26
Internal Loads Internal Loads Infil 7 7
Lights 0.29 0.07 0.36 7.63 0.29 6.56 Lights 0.29 0.36 -8.09 MinStop/Rh 0 0
People 0.49 0 0 10.38 0.30 6.79 People 0.30 0 -6.74 Return 399 399
Misc 0.18 0.00 0.18 3.81 0.18 4.07 Misc 0.18 0.18 -4.04 Exhaust 33 33
Sub Total ==> 0.96 0.07 1.03 21.82 0.77 17.42 Sub Total ==> 0.77 0.84 -18.88 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.18 -0.18 0.00 0.00 0.18 4.07 Ceiling Load -0.05 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.12 -2.54 0.00 0.00 Ventilation Load 0.00 -0.36 8.09 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 2.29 2.29 48.52 2.29 51.81 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.16 3.60
Sup. Fan Heat 0.14 2.97 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 6.6 6.6
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.12 2.70 Lps/m² 13.06 13.06
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 71.13
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.45
W/m² 183.44 -142.20
Grand Total ==> 4.81 -0.11 4.72 100.00 4.42 100.00 Grand Total ==> -3.93 -4.45 100.00 No. People 4
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 9 of 80
Room Checksums
By Trane
0B1F-Lobby lift 2
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 21 Mo/Hr: 8 / 22 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 23 / 17 OADB: 26 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.3 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.8 21.4
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 1.72 1.72 23.59 1.74 25.36 Partition/Door -6.79 -6.79 100.00 Diffuser 607 607
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 607 607
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 607 607
Infiltration 0.32 0.32 4.39 0.05 0.73 Infiltration -0.25 -0.25 3.68 Sec Fan 0 0
Sub Total ==> 2.04 0.00 2.04 27.98 1.79 26.09 Sub Total ==> -7.04 -7.04 103.68 Nom Vent 35 35
AHU Vent 35 35
Internal Loads Internal Loads Infil 10 10
Lights 0.38 0.10 0.48 6.58 0.38 5.54 Lights 0.38 0.48 -7.07 MinStop/Rh 0 0
People 0.65 0 1 8.92 0.40 5.83 People 0.40 0 -5.89 Return 617 617
Misc 0.24 0.00 0.24 3.29 0.24 3.50 Misc 0.24 0.24 -3.53 Exhaust 44 44
Sub Total ==> 1.27 0.10 1.37 18.79 1.02 14.87 Sub Total ==> 1.02 1.12 -16.49 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.23 -0.23 0.00 0.00 0.24 3.50 Ceiling Load -0.07 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.15 -2.06 0.00 0.00 Ventilation Load 0.00 -0.48 7.07 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 3.81 3.81 52.26 3.81 55.54 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.22 3.24
Sup. Fan Heat 0.22 3.02 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 5.7 5.7
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.17 2.50 Lps/m² 15.17 15.17
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 72.78
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.80
W/m² 208.34 -163.42
Grand Total ==> 7.35 -0.13 7.29 100.00 6.86 100.00 Grand Total ==> -6.09 -6.79 100.00 No. People 5
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 10 of 80
Room Checksums
By Trane
0B1F-Materials
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 21 Mo/Hr: 8 / 22 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 23 / 17 OADB: 26 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.3 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.7 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.87 0.87 24.72 0.87 26.28 Partition/Door -3.40 -3.40 101.19 Diffuser 294 294
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 294 294
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 294 294
Infiltration 0.14 0.14 3.98 0.02 0.60 Infiltration -0.11 -0.11 3.27 Sec Fan 0 0
Sub Total ==> 1.01 0.00 1.01 28.69 0.89 26.89 Sub Total ==> -3.51 -3.51 104.46 Nom Vent 21 21
AHU Vent 21 21
Internal Loads Internal Loads Infil 4 4
Lights 0.17 0.04 0.21 5.97 0.17 5.14 Lights 0.17 0.22 -6.55 MinStop/Rh 0 0
People 0.39 0 0 11.08 0.24 7.25 People 0.24 0 -7.14 Return 298 298
Misc 0.18 0.00 0.18 5.11 0.18 5.44 Misc 0.18 0.18 -5.36 Exhaust 25 25
Sub Total ==> 0.74 0.04 0.78 22.16 0.59 17.82 Sub Total ==> 0.59 0.64 -19.05 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.11 -0.11 0.00 0.00 0.11 3.32 Ceiling Load -0.03 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.10 -2.84 0.00 0.00 Ventilation Load 0.00 -0.29 8.63 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 1.72 1.72 48.86 1.72 51.96 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.13 3.87
Sup. Fan Heat 0.11 3.13 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 7.0 7.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.07 2.08 Lps/m² 16.32 16.32
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 70.64
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.33
W/m² 230.92 -178.71
Grand Total ==> 3.58 -0.07 3.52 100.00 3.31 100.00 Grand Total ==> -2.95 -3.36 100.00 No. People 3
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 11 of 80
Room Checksums
By Trane
0B1F-MSB
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 18 Mo/Hr: 8 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 19 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 18.0 18.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 18.0 18.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 6.18 6.18 35.99 6.22 38.42 Partition/Door -10.05 -10.05 25.88 Diffuser 2,581 2,581
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 2,581 2,581
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 2,581 2,581
Infiltration 0.92 0.92 5.36 0.23 1.42 Infiltration -0.38 -0.38 0.98 Sec Fan 0 0
Sub Total ==> 7.10 0.00 7.10 41.35 6.45 39.84 Sub Total ==> -10.43 -10.43 26.85 Nom Vent 0 0
AHU Vent 0 0
Internal Loads Internal Loads Infil 19 19
Lights 0.74 0.18 0.92 5.36 0.74 4.57 Lights 0.74 0.92 -2.37 MinStop/Rh 0 0
People 0.50 0 1 2.91 0.31 1.91 People 0.31 0 -0.80 Return 2,600 2,600
Misc 7.70 0.00 7.70 44.85 7.70 47.56 Misc 7.70 7.70 -19.82 Exhaust 19 19
Sub Total ==> 8.94 0.18 9.12 53.12 8.75 54.05 Sub Total ==> 8.75 8.93 -22.99 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.98 -0.98 0.00 0.00 0.99 6.11 Ceiling Load 0.42 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.00 0.00 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -37.57 -37.57 96.73
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.95 5.53 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 0.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.23 -0.59 Lps/m² 33.52 33.52
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 150.32
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.48
W/m² 222.85 -504.26
Grand Total ==> 17.02 -0.80 17.17 100.00 16.19 100.00 Grand Total ==> -38.83 -38.84 100.00 No. People 4
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 12 of 80
Room Checksums
By Trane
0B1F-Office
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 18 Mo/Hr: 8 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 19 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.7 21.1
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.76 0.76 38.38 0.76 41.53 Partition/Door -2.44 -2.44 128.42 Diffuser 162 162
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 162 162
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 162 162
Infiltration 0.12 0.12 6.06 0.02 1.09 Infiltration -0.07 -0.07 3.68 Sec Fan 0 0
Sub Total ==> 0.88 0.00 0.88 44.44 0.78 42.62 Sub Total ==> -2.51 -2.51 132.11 Nom Vent 14 14
AHU Vent 14 14
Internal Loads Internal Loads Infil 3 3
Lights 0.12 0.03 0.15 7.58 0.12 6.56 Lights 0.12 0.14 -7.37 MinStop/Rh 0 0
People 0.26 0 0 13.13 0.16 8.74 People 0.16 0 -8.42 Return 165 165
Misc 0.70 0.00 0.70 35.35 0.70 38.25 Misc 0.70 0.70 -36.84 Exhaust 17 17
Sub Total ==> 1.08 0.03 1.11 56.06 0.98 53.55 Sub Total ==> 0.98 1.00 -52.63 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.07 -0.07 0.00 0.00 0.07 3.83 Ceiling Load -0.02 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.07 -3.54 0.00 0.00 Ventilation Load 0.00 -0.19 10.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -0.06 -0.06 3.16
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.09 4.74
Sup. Fan Heat 0.06 3.03 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 8.5 8.5
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.05 2.63 Lps/m² 13.46 13.46
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 67.67
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.03
W/m² 198.85 -150.05
Grand Total ==> 2.03 -0.04 1.98 100.00 1.83 100.00 Grand Total ==> -1.61 -1.90 100.00 No. People 2
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 13 of 80
Room Checksums
By Trane
0B1F-Pantry
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 18 Mo/Hr: 8 / 18 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 19 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.6 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.29 0.29 0.00 0.29 0.00 Partition/Door -0.92 -0.92 0.00 Diffuser 74 74
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 74 74
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 74 74
Infiltration 0.07 0.07 0.00 0.01 0.00 Infiltration -0.04 -0.04 0.00 Sec Fan 0 0
Sub Total ==> 0.36 0.00 0.36 0.00 0.30 0.00 Sub Total ==> -0.96 -0.96 0.00 Nom Vent 8 8
AHU Vent 8 8
Internal Loads Internal Loads Infil 2 2
Lights 0.07 0.02 0.09 0.00 0.07 0.00 Lights 0.07 0.08 0.00 MinStop/Rh 0 0
People 0.15 0 0 0.00 0.09 0.00 People 0.09 0 0.00 Return 76 76
Misc 0.07 0.00 0.07 0.00 0.07 0.00 Misc 0.07 0.07 0.00 Exhaust 10 10
Sub Total ==> 0.29 0.02 0.31 0.00 0.23 0.00 Sub Total ==> 0.23 0.24 0.00 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.04 -0.04 0.00 0.00 0.04 0.00 Ceiling Load -0.01 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.05 0.00 0.00 0.00 Ventilation Load 0.00 -0.11 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.26 0.26 0.00 0.26 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.05 0.00
Sup. Fan Heat 0.03 0.00 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 10.9 10.9
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.03 0.00 Lps/m² 10.55 10.55
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 64.21
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.08
W/m² 164.25 -120.86
Grand Total ==> 0.95 -0.02 0.91 100.00 0.83 100.00 Grand Total ==> -0.74 -0.91 100.00 No. People 1
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 14 of 80
Room Checksums
By Trane
0B1F-Reception & Gallery
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 12 / 14 Mo/Hr: 12 / 14 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 24 / 21 / 14 OADB: 24 OADB: 2 SADB 13.0 30.0
Ra Plenum 23.7 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.8 21.5
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 43.82 0.00 43.82 78.56 43.82 84.37 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.19 0.00 0.19 0.34 0.19 0.37 Glass/Door Cond -7.63 -7.63 15.24
Cooling Heating
Wall Cond 0.30 0.38 0.68 1.22 0.30 0.58 Wall Cond -0.63 -1.53 3.06
Partition/Door -0.14 -0.14 -0.25 -0.14 -0.27 Partition/Door -3.05 -3.05 6.09 Diffuser 4,601 4,601
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 4,601 4,601
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 4,601 4,601
Infiltration 1.47 1.47 2.64 0.16 0.31 Infiltration -1.77 -1.77 3.53 Sec Fan 0 0
Sub Total ==> 45.64 0.38 46.02 82.50 44.33 85.35 Sub Total ==> -13.08 -13.98 27.92 Nom Vent 197 197
AHU Vent 197 197
Internal Loads Internal Loads Infil 70 70
Lights 2.74 0.68 3.42 6.13 2.74 5.28 Lights 2.74 3.42 -6.83 MinStop/Rh 0 0
People 3.70 0 4 6.63 2.28 4.39 People 2.28 2 -4.55 Return 4,670 4,670
Misc 1.71 0.00 1.71 3.07 1.71 3.29 Misc 1.71 1.71 -3.41 Exhaust 266 266
Sub Total ==> 8.15 0.68 8.83 15.83 6.73 12.96 Sub Total ==> 6.73 7.41 -14.80 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.88 -0.88 0.00 0.00 0.88 1.69 Ceiling Load -0.50 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.76 -1.36 0.00 0.00 Ventilation Load 0.00 -2.71 5.41 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -39.29 -39.29 78.45
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -1.23 2.46
Sup. Fan Heat 1.69 3.03 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.3 4.3
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.28 0.56 Lps/m² 16.14 16.14
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 74.50
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.62
W/m² 216.51 -170.88
Grand Total ==> 54.67 0.18 55.78 100.00 51.94 100.00 Grand Total ==> -46.14 -50.08 100.00 No. People 28
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 15 of 80
Room Checksums
By Trane
0B1F-Reception SPa
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 21 Mo/Hr: 8 / 22 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 23 / 17 OADB: 26 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.3 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.9 21.7
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.25 0.03 0.28 1.65 0.24 1.50 Wall Cond -0.37 -0.42 2.78
Partition/Door 3.93 3.93 23.13 3.97 24.87 Partition/Door -15.50 -15.50 102.58 Diffuser 1,414 1,414
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,414 1,414
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,414 1,414
Infiltration 0.81 0.81 4.77 0.11 0.69 Infiltration -0.62 -0.62 4.10 Sec Fan 0 0
Sub Total ==> 4.99 0.03 5.02 29.55 4.32 27.07 Sub Total ==> -16.49 -16.54 109.46 Nom Vent 46 46
AHU Vent 46 46
Internal Loads Internal Loads Infil 24 24
Lights 0.95 0.24 1.19 7.00 0.95 5.95 Lights 0.95 1.19 -7.88 MinStop/Rh 0 0
People 0.86 0 1 5.06 0.53 3.32 People 0.53 1 -3.51 Return 1,439 1,439
Misc 0.99 0.00 0.99 5.83 0.99 6.20 Misc 0.99 0.99 -6.55 Exhaust 70 70
Sub Total ==> 2.80 0.24 3.04 17.89 2.47 15.48 Sub Total ==> 2.47 2.71 -17.94 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.58 -0.58 0.00 0.00 0.58 3.63 Ceiling Load -0.17 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.18 -1.06 0.00 0.00 Ventilation Load 0.00 -0.63 4.17 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 8.59 8.59 50.56 8.59 53.82 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.29 1.92
Sup. Fan Heat 0.52 3.06 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 3.2 3.2
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.36 2.38 Lps/m² 14.28 14.28
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 77.05
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.39
W/m² 185.28 -149.26
Grand Total ==> 16.96 -0.31 16.99 100.00 15.96 100.00 Grand Total ==> -14.19 -15.11 100.00 No. People 7
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 16 of 80
Room Checksums
By Trane
0B1F-Recyc Str
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 19 Mo/Hr: 8 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 18 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.2 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 18.0 18.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 18.0 17.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 2.27 2.27 75.17 2.27 79.37 Partition/Door -3.68 -3.68 52.80 Diffuser 457 457
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 457 457
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 457 457
Infiltration 0.11 0.11 3.64 0.03 1.05 Infiltration -0.05 -0.05 0.72 Sec Fan 0 0
Sub Total ==> 2.38 0.00 2.38 78.81 2.30 80.42 Sub Total ==> -3.73 -3.73 53.52 Nom Vent 7 7
AHU Vent 7 7
Internal Loads Internal Loads Infil 3 3
Lights 0.14 0.04 0.18 5.96 0.14 4.90 Lights 0.14 0.18 -2.58 MinStop/Rh 0 0
People 0.13 0 0 4.30 0.08 2.80 People 0.08 0 -1.15 Return 460 460
Misc 0.15 0.00 0.15 4.97 0.15 5.24 Misc 0.15 0.15 -2.15 Exhaust 9 9
Sub Total ==> 0.42 0.04 0.46 15.23 0.37 12.94 Sub Total ==> 0.37 0.41 -5.88 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.19 -0.19 0.00 0.00 0.19 6.64 Ceiling Load 0.08 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.01 0.33 0.00 0.00 Ventilation Load 0.00 -0.06 0.86 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -3.60 -3.60 51.65
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.04 0.57
Sup. Fan Heat 0.17 5.63 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 1.5 1.5
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.05 -0.72 Lps/m² 30.47 30.47
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 145.13
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.76
W/m² 209.79 -461.75
Grand Total ==> 2.99 -0.15 3.02 100.00 2.86 100.00 Grand Total ==> -6.88 -6.97 100.00 No. People 1
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 17 of 80
Room Checksums
By Trane
0B1F-Restaurant
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 12 / 16 Mo/Hr: 12 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 24 / 21 / 14 OADB: 24 OADB: 2 SADB 13.0 30.0
Ra Plenum 23.8 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.1 19.5
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 21.21 0.00 21.21 47.29 21.21 52.47 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.11 0.00 0.11 0.25 0.11 0.27 Glass/Door Cond -4.38 -4.38 8.36
Cooling Heating
Wall Cond 0.66 0.38 1.04 2.32 0.66 1.63 Wall Cond -1.41 -2.36 4.51
Partition/Door 0.01 0.01 0.02 0.01 0.02 Partition/Door -2.29 -2.29 4.37 Diffuser 3,581 3,581
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 3,581 3,581
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 3,581 3,581
Infiltration 0.72 0.72 1.61 0.09 0.22 Infiltration -1.02 -1.02 1.95 Sec Fan 0 0
Sub Total ==> 22.71 0.38 23.09 51.48 22.08 54.63 Sub Total ==> -9.10 -10.05 19.19 Nom Vent 819 819
AHU Vent 819 819
Internal Loads Internal Loads Infil 40 40
Lights 2.31 0.58 2.89 6.44 2.31 5.71 Lights 2.31 2.89 -5.52 MinStop/Rh 0 0
People 20.89 0 21 46.58 12.85 31.79 People 12.85 13 -24.54 Return 3,622 3,622
Misc 2.41 0.00 2.41 5.37 2.41 5.96 Misc 2.41 2.41 -4.60 Exhaust 860 860
Sub Total ==> 25.61 0.58 26.19 58.39 17.57 43.47 Sub Total ==> 17.57 18.15 -34.66 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.77 -0.77 0.00 0.00 0.77 1.90 Ceiling Load -0.42 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -5.75 -12.82 0.00 0.00 Ventilation Load 0.00 -11.30 21.58 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -43.99 -43.99 84.00
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -5.14 9.81
Sup. Fan Heat 1.32 2.94 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 22.9 22.9
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.04 0.08 Lps/m² 14.86 14.86
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 51.41
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.46
W/m² 288.82 -193.41
Grand Total ==> 49.09 0.19 44.85 100.00 40.42 100.00 Grand Total ==> -35.94 -52.37 100.00 No. People 161
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 18 of 80
Room Checksums
By Trane
0B1F-Security
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 18 Mo/Hr: 8 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 19 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.7 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 1.11 1.11 36.51 1.12 39.86 Partition/Door -3.63 -3.63 125.61 Diffuser 249 249
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 249 249
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 249 249
Infiltration 0.22 0.22 7.24 0.04 1.42 Infiltration -0.14 -0.14 4.84 Sec Fan 0 0
Sub Total ==> 1.33 0.00 1.33 43.75 1.16 41.28 Sub Total ==> -3.77 -3.77 130.45 Nom Vent 19 19
AHU Vent 19 19
Internal Loads Internal Loads Infil 5 5
Lights 0.21 0.05 0.26 8.55 0.21 7.47 Lights 0.21 0.26 -9.00 MinStop/Rh 0 0
People 0.36 0 0 11.84 0.22 7.83 People 0.22 0 -7.61 Return 255 255
Misc 1.10 0.00 1.10 36.18 1.10 39.15 Misc 1.10 1.10 -38.06 Exhaust 24 24
Sub Total ==> 1.67 0.05 1.72 56.58 1.53 54.45 Sub Total ==> 1.53 1.58 -54.67 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.12 -0.12 0.00 0.00 0.12 4.27 Ceiling Load -0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.10 -3.29 0.00 0.00 Ventilation Load 0.00 -0.26 9.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -0.23 -0.23 7.96
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.12 4.15
Sup. Fan Heat 0.09 2.96 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 7.6 7.6
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.09 3.11 Lps/m² 11.34 11.34
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 68.75
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.07
W/m² 164.79 -124.95
Grand Total ==> 3.12 -0.07 3.04 100.00 2.81 100.00 Grand Total ==> -2.51 -2.89 100.00 No. People 3
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 19 of 80
Room Checksums
By Trane
0B1F-SPA 01
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 10 / 10 Mo/Hr: 12 / 10 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 23 / 21 / 15 OADB: 21 OADB: 2 SADB 13.0 30.0
Ra Plenum 24.3 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.8 21.5
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 6.89 0.00 6.89 76.81 7.44 88.05 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond -0.01 0.00 -0.01 -0.11 -0.14 -1.66 Glass/Door Cond -1.06 -1.06 12.96
Cooling Heating
Wall Cond 0.20 0.06 0.26 2.90 0.11 1.30 Wall Cond -0.70 -1.03 12.59
Partition/Door 0.00 0.00 0.00 -0.17 -2.01 Partition/Door -1.09 -1.09 13.33 Diffuser 750 750
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 750 750
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 750 750
Infiltration 0.22 0.22 2.45 -0.02 -0.24 Infiltration -0.24 -0.24 2.93 Sec Fan 0 0
Sub Total ==> 7.30 0.06 7.36 82.05 7.22 85.44 Sub Total ==> -3.09 -3.42 41.81 Nom Vent 33 33
AHU Vent 33 33
Internal Loads Internal Loads Infil 9 9
Lights 0.36 0.09 0.45 5.02 0.36 4.26 Lights 0.36 0.46 -5.62 MinStop/Rh 0 0
People 0.62 0 1 6.91 0.38 4.50 People 0.38 0 -4.65 Return 759 759
Misc 0.38 0.00 0.38 4.24 0.38 4.50 Misc 0.38 0.38 -4.65 Exhaust 42 42
Sub Total ==> 1.36 0.09 1.45 16.16 1.12 13.25 Sub Total ==> 1.12 1.22 -14.91 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.16 -0.16 0.00 0.00 0.11 1.30 Ceiling Load -0.07 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.12 -1.34 0.00 0.00 Ventilation Load 0.00 -0.45 5.50 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -5.49 -5.49 67.11
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.21 2.57
Sup. Fan Heat 0.28 3.12 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.4 4.4
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.17 -2.08 Lps/m² 19.72 19.72
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 75.24
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.82
W/m² 261.94 -209.05
Grand Total ==> 8.82 -0.01 8.97 100.00 8.45 100.00 Grand Total ==> -7.53 -8.18 100.00 No. People 5
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 20 of 80
Room Checksums
By Trane
0B1F-SPA 02
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 3 / 9 Mo/Hr: 3 / 9 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 23 / 19 / 12 OADB: 23 OADB: 2 SADB 13.0 30.0
Ra Plenum 24.5 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.8 21.4
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 5.91 0.00 5.91 77.56 5.91 81.97 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond -0.01 0.00 -0.01 -0.13 -0.01 -0.14 Glass/Door Cond -0.77 -0.77 10.89
Cooling Heating
Wall Cond 0.01 0.01 0.02 0.26 0.01 0.14 Wall Cond -0.06 -0.15 2.12
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 639 639
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 639 639
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 639 639
Infiltration 0.13 0.13 1.71 0.01 0.14 Infiltration -0.24 -0.24 3.39 Sec Fan 0 0
Sub Total ==> 6.04 0.01 6.05 79.40 5.92 82.11 Sub Total ==> -1.07 -1.16 16.41 Nom Vent 33 33
AHU Vent 33 33
Internal Loads Internal Loads Infil 9 9
Lights 0.36 0.09 0.45 5.91 0.36 4.99 Lights 0.36 0.46 -6.51 MinStop/Rh 0 0
People 0.62 0 1 8.14 0.38 5.27 People 0.38 0 -5.37 Return 649 649
Misc 0.38 0.00 0.38 4.99 0.38 5.27 Misc 0.38 0.38 -5.37 Exhaust 42 42
Sub Total ==> 1.36 0.09 1.45 19.03 1.12 15.53 Sub Total ==> 1.12 1.22 -17.26 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.17 -0.17 0.00 0.00 0.17 2.36 Ceiling Load -0.07 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.12 -1.57 0.00 0.00 Ventilation Load 0.00 -0.45 6.36 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -6.40 -6.40 90.52
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.21 2.97
Sup. Fan Heat 0.24 3.15 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 5.1 5.1
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.07 0.99 Lps/m² 16.82 16.82
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 74.30
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.42
W/m² 226.23 -179.95
Grand Total ==> 7.57 -0.07 7.62 100.00 7.21 100.00 Grand Total ==> -6.42 -7.07 100.00 No. People 5
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 21 of 80
Room Checksums
By Trane
0B1F-SPA 03
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 3 / 9 Mo/Hr: 3 / 9 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 23 / 19 / 12 OADB: 23 OADB: 2 SADB 13.0 30.0
Ra Plenum 24.5 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.8 21.4
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 5.91 0.00 5.91 77.56 5.91 81.97 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond -0.01 0.00 -0.01 -0.13 -0.01 -0.14 Glass/Door Cond -0.77 -0.77 10.89
Cooling Heating
Wall Cond 0.01 0.01 0.02 0.26 0.01 0.14 Wall Cond -0.06 -0.15 2.12
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 639 639
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 639 639
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 639 639
Infiltration 0.13 0.13 1.71 0.01 0.14 Infiltration -0.24 -0.24 3.39 Sec Fan 0 0
Sub Total ==> 6.04 0.01 6.05 79.40 5.92 82.11 Sub Total ==> -1.07 -1.16 16.41 Nom Vent 33 33
AHU Vent 33 33
Internal Loads Internal Loads Infil 9 9
Lights 0.36 0.09 0.45 5.91 0.36 4.99 Lights 0.36 0.46 -6.51 MinStop/Rh 0 0
People 0.62 0 1 8.14 0.38 5.27 People 0.38 0 -5.37 Return 649 649
Misc 0.38 0.00 0.38 4.99 0.38 5.27 Misc 0.38 0.38 -5.37 Exhaust 42 42
Sub Total ==> 1.36 0.09 1.45 19.03 1.12 15.53 Sub Total ==> 1.12 1.22 -17.26 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.17 -0.17 0.00 0.00 0.17 2.36 Ceiling Load -0.07 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.12 -1.57 0.00 0.00 Ventilation Load 0.00 -0.45 6.36 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -6.40 -6.40 90.52
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.21 2.97
Sup. Fan Heat 0.24 3.15 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 5.1 5.1
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.07 0.99 Lps/m² 16.82 16.82
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 74.30
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.42
W/m² 226.23 -179.95
Grand Total ==> 7.57 -0.07 7.62 100.00 7.21 100.00 Grand Total ==> -6.42 -7.07 100.00 No. People 5
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 22 of 80
Room Checksums
By Trane
0B1F-Staff entry
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 3 / 9 Mo/Hr: 3 / 9 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 23 / 19 / 12 OADB: 23 OADB: 2 SADB 13.0 30.0
Ra Plenum 24.5 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.8 21.5
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 2.96 0.00 2.96 72.20 2.96 77.89 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond -0.01 0.00 -0.01 -0.24 -0.01 -0.26 Glass/Door Cond -0.40 -0.40 10.78
Cooling Heating
Wall Cond 0.08 0.01 0.09 2.20 0.08 2.11 Wall Cond -0.39 -0.49 13.21
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 337 337
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 337 337
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 337 337
Infiltration 0.07 0.07 1.71 0.01 0.26 Infiltration -0.14 -0.14 3.77 Sec Fan 0 0
Sub Total ==> 3.10 0.01 3.11 75.85 3.04 80.00 Sub Total ==> -0.93 -1.03 27.76 Nom Vent 16 16
AHU Vent 16 16
Internal Loads Internal Loads Infil 6 6
Lights 0.18 0.05 0.23 5.61 0.18 4.74 Lights 0.18 0.23 -6.20 MinStop/Rh 0 0
People 0.60 0 1 14.63 0.37 9.74 People 0.37 0 -9.97 Return 343 343
Misc 0.11 0.00 0.11 2.68 0.11 2.89 Misc 0.11 0.11 -2.96 Exhaust 22 22
Sub Total ==> 0.89 0.05 0.94 22.93 0.66 17.37 Sub Total ==> 0.66 0.71 -19.14 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.10 -0.10 0.00 0.00 0.10 2.63 Ceiling Load -0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.07 -1.71 0.00 0.00 Ventilation Load 0.00 -0.22 5.93 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -3.08 -3.08 83.02
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.10 2.70
Sup. Fan Heat 0.12 2.93 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.8 4.8
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 -0.27 Lps/m² 14.65 14.65
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 73.39
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.01
W/m² 199.44 -156.03
Grand Total ==> 4.09 -0.04 4.10 100.00 3.80 100.00 Grand Total ==> -3.39 -3.71 100.00 No. People 5
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 23 of 80
Room Checksums
By Trane
0B1F-Trash
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 18 Mo/Hr: 8 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 19 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 18.0 18.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 18.0 18.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 3.91 3.91 52.48 3.94 56.29 Partition/Door -6.37 -6.37 37.89 Diffuser 1,118 1,118
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,118 1,118
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,118 1,118
Infiltration 0.45 0.45 6.04 0.11 1.57 Infiltration -0.19 -0.19 1.13 Sec Fan 0 0
Sub Total ==> 4.36 0.00 4.36 58.52 4.05 57.86 Sub Total ==> -6.56 -6.56 39.02 Nom Vent 0 0
AHU Vent 0 0
Internal Loads Internal Loads Infil 9 9
Lights 0.36 0.09 0.45 6.04 0.36 5.14 Lights 0.36 0.46 -2.74 MinStop/Rh 0 0
People 0.33 0 0 4.43 0.20 2.86 People 0.20 0 -1.19 Return 1,127 1,127
Misc 1.90 0.00 1.90 25.50 1.90 27.14 Misc 1.90 1.90 -11.30 Exhaust 9 9
Sub Total ==> 2.59 0.09 2.68 35.97 2.46 35.14 Sub Total ==> 2.46 2.56 -15.23 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.48 -0.48 0.00 0.00 0.49 7.00 Ceiling Load 0.21 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.00 0.00 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -12.93 -12.93 76.92
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.41 5.50 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 0.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.12 -0.71 Lps/m² 29.41 29.41
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 149.84
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.10
W/m² 196.14 -442.42
Grand Total ==> 7.43 -0.39 7.45 100.00 7.00 100.00 Grand Total ==> -16.82 -16.81 100.00 No. People 3
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 24 of 80
Room Checksums
By Trane
0B1F-Waiting lounge
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 19 Mo/Hr: 8 / 22 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 18 OADB: 26 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.2 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.2 19.7
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.89 0.89 26.81 0.95 30.65 Partition/Door -3.61 -3.61 93.04 Diffuser 274 274
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 274 274
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 274 274
Infiltration 0.37 0.37 11.14 0.05 1.61 Infiltration -0.26 -0.26 6.70 Sec Fan 0 0
Sub Total ==> 1.26 0.00 1.26 37.95 1.00 32.26 Sub Total ==> -3.87 -3.87 99.74 Nom Vent 57 57
AHU Vent 57 57
Internal Loads Internal Loads Infil 10 10
Lights 0.33 0.08 0.41 12.35 0.33 10.65 Lights 0.33 0.41 -10.57 MinStop/Rh 0 0
People 1.07 0 1 32.23 0.66 21.29 People 0.66 1 -17.01 Return 284 284
Misc 0.20 0.00 0.20 6.02 0.20 6.45 Misc 0.20 0.20 -5.15 Exhaust 67 67
Sub Total ==> 1.60 0.08 1.68 50.60 1.19 38.39 Sub Total ==> 1.19 1.27 -32.73 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.23 -0.23 0.00 0.00 0.24 7.74 Ceiling Load -0.07 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.39 -11.75 0.00 0.00 Ventilation Load 0.00 -0.78 20.10 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.67 0.67 20.18 0.67 21.61 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.35 9.02
Sup. Fan Heat 0.10 3.01 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 20.7 20.7
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.15 3.87 Lps/m² 6.68 6.68
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 54.51
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.16
W/m² 122.42 -84.99
Grand Total ==> 3.76 -0.15 3.32 100.00 3.10 100.00 Grand Total ==> -2.75 -3.88 100.00 No. People 8
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 25 of 80
Room Checksums
By Trane
0B2F-Employee Lounge
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 3 / 9 Mo/Hr: 3 / 9 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 23 / 19 / 12 OADB: 23 OADB: 2 SADB 13.0 30.0
Ra Plenum 24.5 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.6 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 9.04 0.00 9.04 70.35 9.04 74.34 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond -0.02 0.00 -0.02 -0.16 -0.02 -0.16 Glass/Door Cond -1.24 -1.24 9.58
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 1,078 1,078
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,078 1,078
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,078 1,078
Infiltration 0.17 0.17 1.32 0.01 0.08 Infiltration -0.33 -0.33 2.55 Sec Fan 0 0
Sub Total ==> 9.19 0.00 9.19 71.52 9.03 74.26 Sub Total ==> -1.57 -1.57 12.12 Nom Vent 108 108
AHU Vent 108 108
Internal Loads Internal Loads Infil 13 13
Lights 0.75 0.19 0.94 7.32 0.75 6.17 Lights 0.75 0.94 -7.26 MinStop/Rh 0 0
People 2.03 0 2 15.80 1.25 10.28 People 1.25 1 -9.65 Return 1,091 1,091
Misc 0.78 0.00 0.78 6.07 0.78 6.41 Misc 0.78 0.78 -6.02 Exhaust 121 121
Sub Total ==> 3.56 0.19 3.75 29.18 2.78 22.86 Sub Total ==> 2.78 2.97 -22.93 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.35 -0.35 0.00 0.00 0.35 2.88 Ceiling Load -0.14 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.49 -3.81 0.00 0.00 Ventilation Load 0.00 -1.48 11.43 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -11.88 -11.88 91.74
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.67 5.17
Sup. Fan Heat 0.40 3.11 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 10.0 10.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.32 2.47 Lps/m² 13.81 13.81
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 66.89
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.84
W/m² 206.39 -156.55
Grand Total ==> 13.10 -0.16 12.85 100.00 12.16 100.00 Grand Total ==> -10.81 -12.95 100.00 No. People 16
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 26 of 80
Room Checksums
By Trane
0B2F-Female Lockers
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 18 Mo/Hr: 8 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 19 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.0 22.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 3.55 3.55 26.85 3.58 30.92 Partition/Door -11.80 -11.80 114.45 Diffuser 1,027 1,027
Floor 0.25 0.25 1.89 0 2.16 Floor -1.26 -1.26 12.22 Terminal 1,027 1,027
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,027 1,027
Infiltration 0.82 0.82 6.20 0.14 1.21 Infiltration -0.51 -0.51 4.95 Sec Fan 0 0
Sub Total ==> 4.62 0.00 4.62 34.95 3.97 34.28 Sub Total ==> -13.57 -13.57 131.62 Nom Vent 0 0
AHU Vent 0 0
Internal Loads Internal Loads Infil 20 20
Lights 1.15 0.29 1.44 10.89 1.15 9.93 Lights 1.15 1.44 -13.97 MinStop/Rh 0 0
People 2.60 0 3 19.67 1.60 13.82 People 1.60 2 -15.52 Return 1,027 1,027
Misc 0.72 0.00 0.72 5.45 0.72 6.22 Misc 0.72 0.72 -6.98 Exhaust 0 0
Sub Total ==> 4.47 0.29 4.76 36.01 3.47 29.97 Sub Total ==> 3.47 3.76 -36.47 Rm Exh 20 20
Auxiliary 0 0
Ceiling Load 0.67 -0.67 0.00 0.00 0.68 5.87 Ceiling Load -0.21 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.00 0.00 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 3.46 3.46 26.17 3.46 29.88 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.38 2.87 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 0.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.50 4.85 Lps/m² 8.56 8.56
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 77.66
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.08
W/m² 110.10 -85.81
Grand Total ==> 13.22 -0.38 13.22 100.00 11.58 100.00 Grand Total ==> -10.31 -10.31 100.00 No. People 20
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 27 of 80
Room Checksums
By Trane
0B2F-Female Toilet
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 20 Mo/Hr: 8 / 21 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 24 / 18 OADB: 26 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.2 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.0 22.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.44 0.07 0.51 14.70 0.44 15.02 Wall Cond -0.65 -0.78 30.00
Partition/Door 0.66 0.66 19.02 0.68 23.21 Partition/Door -2.65 -2.65 101.92 Diffuser 259 259
Floor 0.05 0.05 1.44 0 1.71 Floor -0.25 -0.25 9.62 Terminal 259 259
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 259 259
Infiltration 0.17 0.17 4.90 0.03 1.02 Infiltration -0.13 -0.13 5.00 Sec Fan 0 0
Sub Total ==> 1.32 0.07 1.39 40.06 1.20 40.96 Sub Total ==> -3.68 -3.81 146.54 Nom Vent 0 0
AHU Vent 0 0
Internal Loads Internal Loads Infil 5 5
Lights 0.24 0.06 0.30 8.65 0.24 8.19 Lights 0.24 0.30 -11.54 MinStop/Rh 0 0
People 0.97 0 1 27.95 0.60 20.48 People 0.60 1 -23.08 Return 264 264
Misc 0.30 0.00 0.30 8.65 0.30 10.24 Misc 0.30 0.30 -11.54 Exhaust 5 5
Sub Total ==> 1.51 0.06 1.57 45.24 1.14 38.91 Sub Total ==> 1.14 1.20 -46.15 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.17 -0.17 0.00 0.00 0.18 6.14 Ceiling Load -0.05 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.00 0.00 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.41 0.41 11.82 0.41 13.99 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.10 2.88 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 0.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 -0.38 Lps/m² 8.64 8.64
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 74.49
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.63
W/m² 115.86 -86.62
Grand Total ==> 3.41 -0.04 3.47 100.00 2.93 100.00 Grand Total ==> -2.59 -2.60 100.00 No. People 7
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 28 of 80
Room Checksums
By Trane
0B2F-Guest Standard
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 20 OADB: 29 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.6 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 15.08 0.00 15.08 44.17 15.08 46.34 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.12 0.00 0.12 0.35 0.12 0.37 Glass/Door Cond -0.46 -0.46 1.24
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 8.23 8.23 24.11 8.23 25.29 Partition/Door -25.95 -25.95 69.70 Diffuser 2,883 2,883
Floor 0.63 0.63 1.85 1 1.94 Floor -3.35 -3.35 9.00 Terminal 2,883 2,883
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 2,883 2,883
Infiltration 2.41 2.41 7.06 0.47 1.44 Infiltration -1.36 -1.36 3.65 Sec Fan 0 0
Sub Total ==> 26.47 0.00 26.47 77.53 24.53 75.38 Sub Total ==> -31.12 -31.12 83.59 Nom Vent 300 300
AHU Vent 300 300
Internal Loads Internal Loads Infil 53 53
Lights 3.07 0.77 3.84 11.25 3.07 9.43 Lights 3.07 3.84 -10.31 MinStop/Rh 0 0
People 2.60 0 3 7.62 1.60 4.92 People 1.60 2 -4.30 Return 2,686 2,686
Misc 1.60 0.00 1.60 4.69 1.60 4.92 Misc 1.60 1.60 -4.30 Exhaust 103 103
Sub Total ==> 7.27 0.77 8.04 23.55 6.27 19.27 Sub Total ==> 6.27 7.04 -18.91 Rm Exh 250 250
Auxiliary 0 0
Ceiling Load 1.74 -1.74 0.00 0.00 1.74 5.35 Ceiling Load -0.56 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -1.43 -4.19 0.00 0.00 Ventilation Load 0.00 -4.14 11.12 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -3.52 -3.52 9.45
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -4.16 11.17
Sup. Fan Heat 1.06 3.10 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 10.4 10.4
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -1.33 3.57 Lps/m² 9.01 9.01
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 58.47
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.49
W/m² 153.97 -108.05
Grand Total ==> 35.48 -0.97 34.14 100.00 32.54 100.00 Grand Total ==> -28.93 -37.23 100.00 No. People 20
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 29 of 80
Room Checksums
By Trane
0B2F-Housekeeping area
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 18 Mo/Hr: 8 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 19 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.6 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 2.30 2.30 32.26 2.31 35.00 Partition/Door -7.57 -7.57 106.02 Diffuser 585 585
Floor 0.19 0.19 2.66 0 2.88 Floor -0.96 -0.96 13.45 Terminal 585 585
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 585 585
Infiltration 0.51 0.51 7.15 0.09 1.36 Infiltration -0.31 -0.31 4.34 Sec Fan 0 0
Sub Total ==> 3.00 0.00 3.00 42.08 2.59 39.24 Sub Total ==> -8.84 -8.84 123.81 Nom Vent 64 64
AHU Vent 64 64
Internal Loads Internal Loads Infil 12 12
Lights 0.89 0.22 1.11 15.57 0.89 13.48 Lights 0.89 1.11 -15.55 MinStop/Rh 0 0
People 1.20 0 1 16.83 0.74 11.21 People 0.74 1 -10.36 Return 597 597
Misc 1.48 0.00 1.48 20.76 1.48 22.42 Misc 1.48 1.48 -20.73 Exhaust 76 76
Sub Total ==> 3.57 0.22 3.79 53.16 3.11 47.12 Sub Total ==> 3.11 3.33 -46.64 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.41 -0.41 0.00 0.00 0.42 6.36 Ceiling Load -0.13 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.36 -5.05 0.00 0.00 Ventilation Load 0.00 -0.88 12.32 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.48 0.48 6.73 0.48 7.27 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.40 5.60
Sup. Fan Heat 0.22 3.09 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 10.9 10.9
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.35 4.90 Lps/m² 7.90 7.90
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 64.60
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.18
W/m² 122.25 -90.51
Grand Total ==> 7.46 -0.19 7.13 100.00 6.60 100.00 Grand Total ==> -5.86 -7.14 100.00 No. People 9
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 30 of 80
Room Checksums
By Trane
0B2F-HR
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 3 / 9 Mo/Hr: 3 / 9 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 23 / 19 / 12 OADB: 23 OADB: 2 SADB 13.0 30.0
Ra Plenum 24.5 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.7 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 5.37 0.00 5.37 66.79 5.37 70.57 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond -0.01 0.00 -0.01 -0.12 -0.01 -0.13 Glass/Door Cond -0.71 -0.71 9.11
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 674 674
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 674 674
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 674 674
Infiltration 0.10 0.10 1.24 0.01 0.13 Infiltration -0.19 -0.19 2.44 Sec Fan 0 0
Sub Total ==> 5.46 0.00 5.46 67.91 5.37 70.57 Sub Total ==> -0.90 -0.90 11.55 Nom Vent 52 52
AHU Vent 52 52
Internal Loads Internal Loads Infil 8 8
Lights 0.54 0.13 0.67 8.33 0.54 7.10 Lights 0.54 0.67 -8.60 MinStop/Rh 0 0
People 0.97 0 1 12.06 0.60 7.88 People 0.60 1 -7.70 Return 681 681
Misc 0.90 0.00 0.90 11.19 0.90 11.83 Misc 0.90 0.90 -11.55 Exhaust 59 59
Sub Total ==> 2.41 0.13 2.54 31.59 2.04 26.81 Sub Total ==> 2.04 2.17 -27.86 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.20 -0.20 0.00 0.00 0.20 2.63 Ceiling Load -0.08 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.21 -2.61 0.00 0.00 Ventilation Load 0.00 -0.71 9.11 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -7.82 -7.82 100.39
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.32 4.11
Sup. Fan Heat 0.25 3.11 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 7.7 7.7
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.21 2.70 Lps/m² 14.98 14.98
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 70.12
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.68
W/m² 213.44 -165.20
Grand Total ==> 8.07 -0.07 8.04 100.00 7.61 100.00 Grand Total ==> -6.76 -7.79 100.00 No. People 7
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 31 of 80
Room Checksums
By Trane
0B2F-Laudry hotel
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 20 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 20.5 17.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 4.63 4.63 16.74 4.78 16.27 Partition/Door -15.08 -15.08 25.56 Diffuser 2,603 2,603
Floor 0.59 0.59 2.13 1 2.18 Floor -3.14 -3.14 5.32 Terminal 2,603 2,603
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 2,603 2,603
Infiltration 2.43 2.43 8.79 0.38 1.29 Infiltration -1.37 -1.37 2.32 Sec Fan 0 0
Sub Total ==> 7.65 0.00 7.65 27.66 5.80 19.74 Sub Total ==> -19.59 -19.59 33.21 Nom Vent 960 960
AHU Vent 960 960
Internal Loads Internal Loads Infil 54 54
Lights 3.88 0.97 4.85 17.53 3.88 13.21 Lights 3.88 4.84 -8.20 MinStop/Rh 0 0
People 2.80 0 3 10.12 1.72 5.85 People 1.72 2 -2.92 Return 1,643 1,643
Misc 16.15 0.00 16.15 58.39 16.15 54.97 Misc 16.15 16.15 -27.38 Exhaust 0 0
Sub Total ==> 22.83 0.97 23.80 86.04 21.75 74.03 Sub Total ==> 21.75 22.71 -38.50 Rm Exh 1,014 1,014
Auxiliary 0 0
Ceiling Load 1.76 -1.76 0.00 0.00 1.83 6.23 Ceiling Load -0.56 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -4.75 -17.17 0.00 0.00 Ventilation Load 0.00 -13.24 22.44 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -27.71 -27.71 46.97
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -19.63 33.28
Sup. Fan Heat 0.96 3.47 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 36.9 36.9
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -1.53 2.59 Lps/m² 8.06 8.06
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 30.16
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.74
W/m² 267.00 -156.45
Grand Total ==> 32.24 -0.79 27.66 100.00 29.38 100.00 Grand Total ==> -26.11 -58.99 100.00 No. People 22
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 32 of 80
Room Checksums
By Trane
0B2F-Lobby lift & corridor
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 18 Mo/Hr: 8 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 19 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.8 21.5
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 12.92 12.92 27.37 13.04 29.15 Partition/Door -43.26 -43.26 99.49 Diffuser 3,965 3,965
Floor 0.37 0.37 0.78 0 0.85 Floor -1.88 -1.88 4.32 Terminal 3,965 3,965
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 3,965 3,965
Infiltration 2.86 2.86 6.06 0.47 1.05 Infiltration -1.70 -1.70 3.91 Sec Fan 0 0
Sub Total ==> 16.15 0.00 16.15 34.22 13.89 31.05 Sub Total ==> -46.84 -46.84 107.73 Nom Vent 184 184
AHU Vent 184 184
Internal Loads Internal Loads Infil 67 67
Lights 3.84 0.96 4.80 10.17 3.84 8.58 Lights 3.84 4.80 -11.04 MinStop/Rh 0 0
People 2.73 0 3 5.78 1.91 4.27 People 1.91 2 -4.39 Return 4,032 4,032
Misc 2.00 0.00 2.00 4.24 2.00 4.47 Misc 2.00 2.00 -4.60 Exhaust 251 251
Sub Total ==> 8.57 0.96 9.53 20.19 7.75 17.32 Sub Total ==> 7.75 8.71 -20.03 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 2.22 -2.22 0.00 0.00 2.27 5.07 Ceiling Load -0.70 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.77 -1.63 0.00 0.00 Ventilation Load 0.00 -2.54 5.84 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 20.83 20.83 44.13 20.83 46.56 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -1.15 2.64
Sup. Fan Heat 1.46 3.09 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.6 4.6
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -1.66 3.82 Lps/m² 9.91 9.91
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 75.12
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.58
W/m² 131.86 -105.41
Grand Total ==> 47.77 -1.26 47.20 100.00 44.74 100.00 Grand Total ==> -39.79 -43.48 100.00 No. People 27
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 33 of 80
Room Checksums
By Trane
0B2F-Lobby lift & corridor hotel
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 21 Mo/Hr: 8 / 22 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 23 / 17 OADB: 26 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.3 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.8 21.5
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 3.65 3.65 22.41 3.68 23.59 Partition/Door -14.29 -14.29 94.26 Diffuser 1,383 1,383
Floor 0.32 0.32 1.96 0 2.12 Floor -1.46 -1.46 9.63 Terminal 1,383 1,383
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,383 1,383
Infiltration 0.78 0.78 4.79 0.11 0.71 Infiltration -0.59 -0.59 3.89 Sec Fan 0 0
Sub Total ==> 4.75 0.00 4.75 29.16 4.12 26.41 Sub Total ==> -16.34 -16.34 107.78 Nom Vent 64 64
AHU Vent 64 64
Internal Loads Internal Loads Infil 23 23
Lights 1.34 0.34 1.68 10.31 1.34 8.59 Lights 1.34 1.68 -11.08 MinStop/Rh 0 0
People 0.96 0 1 5.89 0.67 4.29 People 0.67 1 -4.42 Return 1,406 1,406
Misc 0.70 0.00 0.70 4.30 0.70 4.49 Misc 0.70 0.70 -4.62 Exhaust 88 88
Sub Total ==> 3.00 0.34 3.34 20.50 2.71 17.37 Sub Total ==> 2.71 3.05 -20.12 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.82 -0.82 0.00 0.00 0.82 5.26 Ceiling Load -0.24 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.26 -1.60 0.00 0.00 Ventilation Load 0.00 -0.89 5.87 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 7.95 7.95 48.80 7.95 50.96 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.40 2.64
Sup. Fan Heat 0.51 3.13 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.7 4.7
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.58 3.83 Lps/m² 9.88 9.88
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 75.81
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.68
W/m² 130.22 -105.08
Grand Total ==> 16.52 -0.48 16.29 100.00 15.60 100.00 Grand Total ==> -13.87 -15.16 100.00 No. People 9
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 34 of 80
Room Checksums
By Trane
0B2F-Male Lockers
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 18 Mo/Hr: 8 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 19 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.0 22.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 3.35 3.35 27.64 3.38 31.65 Partition/Door -11.13 -11.13 117.28 Diffuser 946 946
Floor 0.22 0.22 1.82 0 2.15 Floor -1.15 -1.15 12.12 Terminal 946 946
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 946 946
Infiltration 0.75 0.75 6.19 0.13 1.22 Infiltration -0.47 -0.47 4.95 Sec Fan 0 0
Sub Total ==> 4.32 0.00 4.32 35.64 3.74 35.02 Sub Total ==> -12.75 -12.75 134.35 Nom Vent 0 0
AHU Vent 0 0
Internal Loads Internal Loads Infil 18 18
Lights 0.88 0.22 1.10 9.08 0.88 8.24 Lights 0.88 1.10 -11.59 MinStop/Rh 0 0
People 2.38 0 2 19.64 1.47 13.76 People 1.47 1 -15.49 Return 946 946
Misc 1.10 0.00 1.10 9.08 1.10 10.30 Misc 1.10 1.10 -11.59 Exhaust 0 0
Sub Total ==> 4.36 0.22 4.58 37.79 3.45 32.30 Sub Total ==> 3.45 3.67 -38.67 Rm Exh 18 18
Auxiliary 0 0
Ceiling Load 0.61 -0.61 0.00 0.00 0.62 5.81 Ceiling Load -0.19 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.00 0.00 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 2.87 2.87 23.68 2.87 26.87 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.35 2.89 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 0.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.41 4.32 Lps/m² 8.60 8.60
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 78.00
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.07
W/m² 110.23 -86.28
Grand Total ==> 12.16 -0.39 12.12 100.00 10.68 100.00 Grand Total ==> -9.49 -9.49 100.00 No. People 18
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 35 of 80
Room Checksums
By Trane
0B2F-Male Toilet
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 20 Mo/Hr: 8 / 21 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 24 / 18 OADB: 26 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.2 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.0 22.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.44 0.07 0.51 14.70 0.44 15.02 Wall Cond -0.65 -0.78 30.00
Partition/Door 0.66 0.66 19.02 0.68 23.21 Partition/Door -2.65 -2.65 101.92 Diffuser 259 259
Floor 0.05 0.05 1.44 0 1.71 Floor -0.25 -0.25 9.62 Terminal 259 259
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 259 259
Infiltration 0.17 0.17 4.90 0.03 1.02 Infiltration -0.13 -0.13 5.00 Sec Fan 0 0
Sub Total ==> 1.32 0.07 1.39 40.06 1.20 40.96 Sub Total ==> -3.68 -3.81 146.54 Nom Vent 0 0
AHU Vent 0 0
Internal Loads Internal Loads Infil 5 5
Lights 0.24 0.06 0.30 8.65 0.24 8.19 Lights 0.24 0.30 -11.54 MinStop/Rh 0 0
People 0.97 0 1 27.95 0.60 20.48 People 0.60 1 -23.08 Return 264 264
Misc 0.30 0.00 0.30 8.65 0.30 10.24 Misc 0.30 0.30 -11.54 Exhaust 5 5
Sub Total ==> 1.51 0.06 1.57 45.24 1.14 38.91 Sub Total ==> 1.14 1.20 -46.15 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.17 -0.17 0.00 0.00 0.18 6.14 Ceiling Load -0.05 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.00 0.00 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.41 0.41 11.82 0.41 13.99 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.10 2.88 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 0.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.01 -0.38 Lps/m² 8.64 8.64
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 74.49
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.63
W/m² 115.86 -86.62
Grand Total ==> 3.41 -0.04 3.47 100.00 2.93 100.00 Grand Total ==> -2.59 -2.60 100.00 No. People 7
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 36 of 80
Room Checksums
By Trane
0B2F-Medical
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 9 Mo/Hr: 8 / 9 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 23 / 16 OADB: 26 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.7 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 2.27 0.00 2.27 67.16 2.27 71.61 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.04 0.00 0.04 1.18 0.04 1.26 Glass/Door Cond -0.40 -0.40 12.38
Cooling Heating
Wall Cond 0.08 0.03 0.11 3.25 0.08 2.52 Wall Cond -0.22 -0.32 9.91
Partition/Door 0.15 0.15 4.44 0.15 4.73 Partition/Door -1.14 -1.14 35.29 Diffuser 281 281
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 281 281
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 281 281
Infiltration 0.09 0.09 2.66 0.01 0.32 Infiltration -0.08 -0.08 2.48 Sec Fan 0 0
Sub Total ==> 2.63 0.03 2.66 78.70 2.55 80.44 Sub Total ==> -1.84 -1.94 60.06 Nom Vent 21 21
AHU Vent 21 21
Internal Loads Internal Loads Infil 3 3
Lights 0.17 0.04 0.21 6.21 0.17 5.36 Lights 0.17 0.22 -6.81 MinStop/Rh 0 0
People 0.39 0 0 11.54 0.24 7.57 People 0.24 0 -7.43 Return 284 284
Misc 0.11 0.00 0.11 3.25 0.11 3.47 Misc 0.11 0.11 -3.41 Exhaust 24 24
Sub Total ==> 0.67 0.04 0.71 21.01 0.52 16.40 Sub Total ==> 0.52 0.57 -17.65 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.10 -0.10 0.00 0.00 0.10 3.15 Ceiling Load -0.03 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.09 -2.66 0.00 0.00 Ventilation Load 0.00 -0.29 8.98 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -1.47 -1.47 45.51
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.13 4.02
Sup. Fan Heat 0.10 2.96 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 7.4 7.4
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.03 -0.93 Lps/m² 15.60 15.60
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 70.05
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.49
W/m² 222.57 -171.48
Grand Total ==> 3.40 -0.03 3.38 100.00 3.17 100.00 Grand Total ==> -2.82 -3.23 100.00 No. People 3
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 37 of 80
Room Checksums
By Trane
0B2F-Uniform
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 18 Mo/Hr: 8 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 19 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.6 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 1.81 1.81 29.01 1.83 31.44 Partition/Door -6.06 -6.06 96.81 Diffuser 515 515
Floor 0.10 0.10 1.60 0 1.72 Floor -0.49 -0.49 7.83 Terminal 515 515
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 515 515
Infiltration 0.33 0.33 5.29 0.06 1.03 Infiltration -0.20 -0.20 3.19 Sec Fan 0 0
Sub Total ==> 2.24 0.00 2.24 35.90 1.99 34.19 Sub Total ==> -6.75 -6.75 107.83 Nom Vent 54 54
AHU Vent 54 54
Internal Loads Internal Loads Infil 8 8
Lights 0.56 0.14 0.70 11.22 0.56 9.62 Lights 0.56 0.70 -11.18 MinStop/Rh 0 0
People 1.02 0 1 16.35 0.63 10.82 People 0.63 1 -10.06 Return 523 523
Misc 0.47 0.00 0.47 7.53 0.47 8.08 Misc 0.47 0.47 -7.51 Exhaust 62 62
Sub Total ==> 2.05 0.14 2.19 35.10 1.66 28.52 Sub Total ==> 1.66 1.80 -28.75 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.26 -0.26 0.00 0.00 0.27 4.64 Ceiling Load -0.08 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.28 -4.49 0.00 0.00 Ventilation Load 0.00 -0.75 11.98 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 1.90 1.90 30.45 1.90 32.65 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.34 5.43
Sup. Fan Heat 0.19 3.04 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 10.5 10.5
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.22 3.51 Lps/m² 10.96 10.96
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 65.41
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.97
W/m² 167.44 -124.93
Grand Total ==> 6.45 -0.12 6.24 100.00 5.82 100.00 Grand Total ==> -5.17 -6.26 100.00 No. People 8
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 38 of 80
Room Checksums
By Trane
0B2F-Uniform Laudry
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 18 Mo/Hr: 8 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 19 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.5 20.6
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 2.70 2.70 30.34 2.71 32.97 Partition/Door -8.87 -8.87 96.62 Diffuser 728 728
Floor 0.22 0.22 2.47 0 2.80 Floor -1.13 -1.13 12.31 Terminal 728 728
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 728 728
Infiltration 0.74 0.74 8.31 0.13 1.58 Infiltration -0.46 -0.46 5.01 Sec Fan 0 0
Sub Total ==> 3.66 0.00 3.66 41.12 3.07 37.35 Sub Total ==> -10.46 -10.46 113.94 Nom Vent 93 93
AHU Vent 93 93
Internal Loads Internal Loads Infil 18 18
Lights 1.30 0.32 1.62 18.20 1.30 15.82 Lights 1.30 1.62 -17.65 MinStop/Rh 0 0
People 1.75 0 2 19.66 1.08 13.14 People 1.08 1 -11.76 Return 746 746
Misc 2.16 0.00 2.16 24.27 2.16 26.28 Misc 2.16 2.16 -23.53 Exhaust 111 111
Sub Total ==> 5.21 0.32 5.53 62.13 4.54 55.23 Sub Total ==> 4.54 4.86 -52.94 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.60 -0.60 0.00 0.00 0.61 7.42 Ceiling Load -0.19 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.56 -6.29 0.00 0.00 Ventilation Load 0.00 -1.29 14.05 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -1.20 -1.20 13.07
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.58 6.32
Sup. Fan Heat 0.27 3.03 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 12.8 12.8
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.51 5.56 Lps/m² 6.74 6.74
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 62.13
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.22
W/m² 108.43 -78.87
Grand Total ==> 9.47 -0.28 8.90 100.00 8.22 100.00 Grand Total ==> -7.31 -9.18 100.00 No. People 13
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 39 of 80
Room Checksums
By Trane
0B3F-BOH
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 21 Mo/Hr: 8 / 22 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 23 / 17 OADB: 26 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.3 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.6 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.58 0.58 26.73 0.59 29.06 Partition/Door -2.26 -2.26 103.67 Diffuser 180 180
Floor 0.05 0.05 2.30 0 2.46 Floor -0.23 -0.23 10.55 Terminal 180 180
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 180 180
Infiltration 0.12 0.12 5.53 0.02 0.99 Infiltration -0.09 -0.09 4.13 Sec Fan 0 0
Sub Total ==> 0.75 0.00 0.75 34.56 0.66 32.51 Sub Total ==> -2.58 -2.58 118.35 Nom Vent 19 19
AHU Vent 19 19
Internal Loads Internal Loads Infil 4 4
Lights 0.26 0.07 0.33 15.21 0.26 12.81 Lights 0.26 0.33 -15.14 MinStop/Rh 0 0
People 0.36 0 0 16.59 0.22 10.84 People 0.22 0 -10.09 Return 183 183
Misc 0.33 0.00 0.33 15.21 0.33 16.26 Misc 0.33 0.33 -15.14 Exhaust 23 23
Sub Total ==> 0.95 0.07 1.02 47.00 0.81 39.90 Sub Total ==> 0.81 0.88 -40.37 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.13 -0.13 0.00 0.00 0.13 6.40 Ceiling Load -0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.10 -4.61 0.00 0.00 Ventilation Load 0.00 -0.26 11.93 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.43 0.43 19.82 0.43 21.18 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.12 5.50
Sup. Fan Heat 0.07 3.23 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 10.6 10.6
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.10 4.59 Lps/m² 8.17 8.17
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 65.70
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.04
W/m² 124.29 -93.21
Grand Total ==> 2.26 -0.06 2.17 100.00 2.03 100.00 Grand Total ==> -1.81 -2.18 100.00 No. People 3
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 40 of 80
Room Checksums
By Trane
0B3F-Fitness BOH
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 19 Mo/Hr: 8 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 18 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.2 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.8 21.4
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 2.08 2.08 28.07 2.08 29.80 Partition/Door -6.92 -6.92 101.32 Diffuser 618 618
Floor 0.05 0.05 0.67 0 0.72 Floor -0.23 -0.23 3.37 Terminal 618 618
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 618 618
Infiltration 0.24 0.24 3.24 0.04 0.57 Infiltration -0.15 -0.15 2.20 Sec Fan 0 0
Sub Total ==> 2.37 0.00 2.37 31.98 2.17 31.09 Sub Total ==> -7.30 -7.30 106.88 Nom Vent 31 31
AHU Vent 31 31
Internal Loads Internal Loads Infil 6 6
Lights 0.44 0.11 0.55 7.42 0.44 6.30 Lights 0.44 0.55 -8.05 MinStop/Rh 0 0
People 0.59 0 1 7.96 0.36 5.16 People 0.36 0 -5.27 Return 624 624
Misc 0.36 0.00 0.36 4.86 0.36 5.16 Misc 0.36 0.36 -5.27 Exhaust 38 38
Sub Total ==> 1.39 0.11 1.50 20.24 1.16 16.62 Sub Total ==> 1.16 1.27 -18.59 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.21 -0.21 0.00 0.00 0.21 3.01 Ceiling Load -0.06 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.13 -1.75 0.00 0.00 Ventilation Load 0.00 -0.43 6.30 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 3.44 3.44 46.42 3.44 49.28 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.20 2.93
Sup. Fan Heat 0.23 3.10 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 5.1 5.1
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.17 2.49 Lps/m² 16.93 16.93
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 73.96
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.37
W/m² 228.81 -181.09
Grand Total ==> 7.41 -0.10 7.41 100.00 6.98 100.00 Grand Total ==> -6.20 -6.83 100.00 No. People 5
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 41 of 80
Room Checksums
By Trane
0B3F-Guest Standard
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 20 OADB: 29 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.6 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 16.58 0.00 16.58 44.17 16.58 46.33 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.14 0.00 0.14 0.37 0.14 0.39 Glass/Door Cond -0.50 -0.50 1.22
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 9.04 9.04 24.08 9.04 25.26 Partition/Door -28.55 -28.55 69.75 Diffuser 3,170 3,170
Floor 0.69 0.69 1.84 1 1.93 Floor -3.68 -3.68 8.99 Terminal 3,170 3,170
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 3,170 3,170
Infiltration 2.65 2.65 7.06 0.52 1.45 Infiltration -1.49 -1.49 3.64 Sec Fan 0 0
Sub Total ==> 29.10 0.00 29.10 77.52 26.97 75.36 Sub Total ==> -34.22 -34.22 83.61 Nom Vent 330 330
AHU Vent 330 330
Internal Loads Internal Loads Infil 59 59
Lights 3.38 0.84 4.22 11.24 3.38 9.44 Lights 3.38 4.22 -10.31 MinStop/Rh 0 0
People 2.86 0 3 7.62 1.76 4.92 People 1.76 2 -4.30 Return 2,954 2,954
Misc 1.76 0.00 1.76 4.69 1.76 4.92 Misc 1.76 1.76 -4.30 Exhaust 114 114
Sub Total ==> 8.00 0.84 8.84 23.55 6.90 19.28 Sub Total ==> 6.90 7.74 -18.91 Rm Exh 275 275
Auxiliary 0 0
Ceiling Load 1.92 -1.92 0.00 0.00 1.92 5.36 Ceiling Load -0.61 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -1.57 -4.18 0.00 0.00 Ventilation Load 0.00 -4.55 11.12 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -3.86 -3.86 9.43
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -4.58 11.19
Sup. Fan Heat 1.17 3.12 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 10.4 10.4
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -1.46 3.57 Lps/m² 9.01 9.01
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 58.47
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.49
W/m² 153.94 -108.02
Grand Total ==> 39.02 -1.08 37.54 100.00 35.79 100.00 Grand Total ==> -31.79 -40.93 100.00 No. People 22
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 42 of 80
Room Checksums
By Trane
0B3F-Gym
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 3 / 9 Mo/Hr: 3 / 9 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 23 / 19 / 12 OADB: 23 OADB: 2 SADB 13.0 30.0
Ra Plenum 24.5 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.7 21.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 12.02 0.00 12.02 71.59 12.02 75.69 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond -0.03 0.00 -0.03 -0.18 -0.03 -0.19 Glass/Door Cond -1.90 -1.90 11.79
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 1,407 1,407
Floor 0.11 0.11 0.66 0 0.69 Floor -1.23 -1.23 7.64 Terminal 1,407 1,407
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,407 1,407
Infiltration 0.26 0.26 1.55 0.02 0.13 Infiltration -0.49 -0.49 3.04 Sec Fan 0 0
Sub Total ==> 12.36 0.00 12.36 73.62 12.12 76.32 Sub Total ==> -3.62 -3.62 22.47 Nom Vent 100 100
AHU Vent 100 100
Internal Loads Internal Loads Infil 19 19
Lights 1.39 0.35 1.74 10.36 1.39 8.75 Lights 1.39 1.74 -10.80 MinStop/Rh 0 0
People 1.88 0 2 11.20 1.16 7.30 People 1.16 1 -7.20 Return 1,427 1,427
Misc 0.70 0.00 0.70 4.17 0.70 4.41 Misc 0.70 0.70 -4.35 Exhaust 119 119
Sub Total ==> 3.97 0.35 4.32 25.73 3.25 20.47 Sub Total ==> 3.25 3.60 -22.35 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.51 -0.51 0.00 0.00 0.51 3.21 Ceiling Load -0.20 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.41 -2.44 0.00 0.00 Ventilation Load 0.00 -1.38 8.57 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -13.53 -13.53 83.99
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.63 3.91
Sup. Fan Heat 0.52 3.10 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 7.1 7.1
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.55 3.41 Lps/m² 12.13 12.13
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 71.00
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.85
W/m² 170.74 -132.92
Grand Total ==> 16.84 -0.16 16.79 100.00 15.88 100.00 Grand Total ==> -14.10 -16.11 100.00 No. People 14
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 43 of 80
Room Checksums
By Trane
0B3F-Indoor swimming pool
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 12 / 14 Mo/Hr: 12 / 14 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 24 / 21 / 14 OADB: 24 OADB: 2 SADB 13.0 30.0
Ra Plenum 23.7 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 26.0 26.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 24.6 23.4
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 51.64 0.00 51.64 83.83 51.64 84.61 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond -1.70 0.00 -1.70 -2.76 -1.70 -2.79 Glass/Door Cond -12.51 -12.51 35.47
Cooling Heating
Wall Cond 0.36 0.37 0.73 1.19 0.36 0.59 Wall Cond -1.48 -2.36 6.69
Partition/Door -2.55 -2.55 -4.14 -2.55 -4.18 Partition/Door -12.26 -12.26 34.76 Diffuser 3,743 3,743
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 3,743 3,743
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 3,743 3,743
Infiltration 1.49 1.49 2.42 -0.26 -0.43 Infiltration -2.85 -2.85 8.08 Sec Fan 0 0
Sub Total ==> 49.24 0.37 49.61 80.54 47.49 77.81 Sub Total ==> -29.10 -29.98 85.00 Nom Vent 658 658
AHU Vent 658 658
Internal Loads Internal Loads Infil 94 94
Lights 2.52 0.63 3.15 5.11 2.52 4.13 Lights 2.52 3.16 -8.96 MinStop/Rh 0 0
People 3.42 0 3 5.55 2.10 3.44 People 2.10 2 -5.95 Return 3,837 3,837
Misc 10.00 0.00 10.00 16.23 10.00 16.39 Misc 10.00 10.00 -28.35 Exhaust 751 751
Sub Total ==> 15.94 0.63 16.57 26.90 14.62 23.96 Sub Total ==> 14.62 15.26 -43.27 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load -1.08 1.08 0.00 0.00 -1.08 -1.77 Ceiling Load -2.35 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -5.96 -9.68 0.00 0.00 Ventilation Load 0.00 -12.37 35.07 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -1.96 -1.96 5.56
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -4.12 11.68
Sup. Fan Heat 1.38 2.24 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 17.6 17.6
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -2.10 5.95 Lps/m² 14.23 14.23
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 40.60
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 2.85
W/m² 350.34 -118.38
Grand Total ==> 64.10 2.08 61.60 100.00 61.03 100.00 Grand Total ==> -18.79 -35.27 100.00 No. People 26
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 44 of 80
Room Checksums
By Trane
0B3F-Lobby lift & corridor 1
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 21 Mo/Hr: 8 / 22 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 23 / 17 OADB: 26 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.3 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.9 21.6
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 3.25 3.25 21.96 3.28 23.03 Partition/Door -12.78 -12.78 94.74 Diffuser 1,262 1,262
Floor 0.21 0.21 1.42 0 1.47 Floor -0.94 -0.94 6.97 Terminal 1,262 1,262
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,262 1,262
Infiltration 0.51 0.51 3.45 0.07 0.49 Infiltration -0.38 -0.38 2.82 Sec Fan 0 0
Sub Total ==> 3.97 0.00 3.97 26.82 3.56 25.00 Sub Total ==> -14.10 -14.10 104.52 Nom Vent 41 41
AHU Vent 41 41
Internal Loads Internal Loads Infil 15 15
Lights 0.72 0.18 0.90 6.08 0.72 5.06 Lights 0.72 0.90 -6.67 MinStop/Rh 0 0
People 0.62 0 1 4.19 0.43 3.02 People 0.43 0 -3.19 Return 1,277 1,277
Misc 0.45 0.00 0.45 3.04 0.45 3.16 Misc 0.45 0.45 -3.34 Exhaust 56 56
Sub Total ==> 1.79 0.18 1.97 13.31 1.60 11.24 Sub Total ==> 1.60 1.78 -13.19 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.53 -0.53 0.00 0.00 0.53 3.72 Ceiling Load -0.16 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.15 -1.01 0.00 0.00 Ventilation Load 0.00 -0.57 4.23 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 8.55 8.55 57.77 8.55 60.04 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.26 1.93
Sup. Fan Heat 0.46 3.11 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 3.3 3.3
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.34 2.52 Lps/m² 14.02 14.02
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 78.61
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.61
W/m² 178.27 -146.65
Grand Total ==> 14.84 -0.35 14.80 100.00 14.24 100.00 Grand Total ==> -12.66 -13.49 100.00 No. People 6
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 45 of 80
Room Checksums
By Trane
0B3F-Lobby lift & corridor 2
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 21 Mo/Hr: 8 / 22 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 23 / 17 OADB: 26 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.3 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.9 21.6
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 3.03 3.03 22.05 3.06 23.16 Partition/Door -11.88 -11.88 94.06 Diffuser 1,172 1,172
Floor 0.22 0.22 1.60 0 1.67 Floor -0.99 -0.99 7.84 Terminal 1,172 1,172
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,172 1,172
Infiltration 0.53 0.53 3.86 0.07 0.53 Infiltration -0.40 -0.40 3.17 Sec Fan 0 0
Sub Total ==> 3.78 0.00 3.78 27.51 3.35 25.36 Sub Total ==> -13.27 -13.27 105.07 Nom Vent 44 44
AHU Vent 44 44
Internal Loads Internal Loads Infil 16 16
Lights 0.76 0.19 0.95 6.91 0.76 5.75 Lights 0.76 0.95 -7.52 MinStop/Rh 0 0
People 0.65 0 1 4.73 0.45 3.41 People 0.45 0 -3.56 Return 1,187 1,187
Misc 0.47 0.00 0.47 3.42 0.47 3.56 Misc 0.47 0.47 -3.72 Exhaust 60 60
Sub Total ==> 1.88 0.19 2.07 15.07 1.68 12.72 Sub Total ==> 1.68 1.87 -14.81 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.56 -0.56 0.00 0.00 0.56 4.24 Ceiling Load -0.17 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.16 -1.16 0.00 0.00 Ventilation Load 0.00 -0.60 4.75 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 7.62 7.62 55.46 7.62 57.68 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.27 2.14
Sup. Fan Heat 0.43 3.13 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 3.7 3.7
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.36 2.85 Lps/m² 12.33 12.33
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 77.74
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.30
W/m² 158.52 -129.68
Grand Total ==> 13.84 -0.37 13.74 100.00 13.21 100.00 Grand Total ==> -11.76 -12.63 100.00 No. People 6
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 46 of 80
Room Checksums
By Trane
0B3F-Lobby lift & corridor hotel
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 21 Mo/Hr: 8 / 22 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 23 / 17 OADB: 26 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.3 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.8 21.4
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 3.66 3.66 22.54 3.69 23.75 Partition/Door -14.29 -14.29 93.46 Diffuser 1,378 1,378
Floor 0.36 0.36 2.22 0 2.38 Floor -1.64 -1.64 10.73 Terminal 1,378 1,378
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,378 1,378
Infiltration 0.87 0.87 5.36 0.12 0.77 Infiltration -0.67 -0.67 4.38 Sec Fan 0 0
Sub Total ==> 4.89 0.00 4.89 30.11 4.18 26.90 Sub Total ==> -16.60 -16.60 108.57 Nom Vent 72 72
AHU Vent 72 72
Internal Loads Internal Loads Infil 26 26
Lights 1.51 0.38 1.89 11.64 1.51 9.72 Lights 1.51 1.88 -12.30 MinStop/Rh 0 0
People 1.07 0 1 6.59 0.75 4.83 People 0.75 1 -4.91 Return 1,404 1,404
Misc 0.78 0.00 0.78 4.80 0.78 5.02 Misc 0.78 0.78 -5.10 Exhaust 98 98
Sub Total ==> 3.36 0.38 3.74 23.03 3.04 19.56 Sub Total ==> 3.04 3.41 -22.30 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.92 -0.92 0.00 0.00 0.92 5.92 Ceiling Load -0.27 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.30 -1.85 0.00 0.00 Ventilation Load 0.00 -1.00 6.54 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 7.40 7.40 45.57 7.40 47.62 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.45 2.94
Sup. Fan Heat 0.51 3.14 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 5.2 5.2
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.65 4.25 Lps/m² 8.78 8.78
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 74.77
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.52
W/m² 117.31 -94.03
Grand Total ==> 16.57 -0.54 16.24 100.00 15.54 100.00 Grand Total ==> -13.83 -15.29 100.00 No. People 10
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 47 of 80
Room Checksums
By Trane
0B3F-Lobby service lift
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 21 Mo/Hr: 8 / 22 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 23 / 17 OADB: 26 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.3 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.4 20.3
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.51 0.51 25.37 0.51 26.02 Partition/Door -1.96 -1.96 85.96 Diffuser 173 173
Floor 0.05 0.05 2.49 0 2.55 Floor -0.21 -0.21 9.21 Terminal 173 173
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 173 173
Infiltration 0.11 0.11 5.47 0.02 1.02 Infiltration -0.08 -0.08 3.51 Sec Fan 0 0
Sub Total ==> 0.67 0.00 0.67 33.33 0.58 29.59 Sub Total ==> -2.25 -2.25 98.68 Nom Vent 28 28
AHU Vent 28 28
Internal Loads Internal Loads Infil 3 3
Lights 0.16 0.04 0.20 9.95 0.16 8.16 Lights 0.16 0.20 -8.77 MinStop/Rh 0 0
People 0.41 0 0 20.40 0.29 14.80 People 0.29 0 -12.72 Return 176 176
Misc 0.10 0.00 0.10 4.98 0.10 5.10 Misc 0.10 0.10 -4.39 Exhaust 31 31
Sub Total ==> 0.67 0.04 0.71 35.32 0.55 28.06 Sub Total ==> 0.55 0.59 -25.88 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.12 -0.12 0.00 0.00 0.12 6.12 Ceiling Load -0.03 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.14 -6.97 0.00 0.00 Ventilation Load 0.00 -0.38 16.67 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.71 0.71 35.32 0.71 36.22 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.17 7.46
Sup. Fan Heat 0.06 2.99 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 15.9 15.9
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.07 3.07 Lps/m² 8.66 8.66
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 60.92
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.04
W/m² 141.99 -104.83
Grand Total ==> 2.17 -0.08 2.01 100.00 1.96 100.00 Grand Total ==> -1.73 -2.28 100.00 No. People 4
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 48 of 80
Room Checksums
By Trane
0B3F-Lockers men
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 18 Mo/Hr: 8 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 19 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.0 22.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 2.40 2.40 26.46 2.42 29.69 Partition/Door -8.01 -8.01 110.64 Diffuser 722 722
Floor 0.13 0.13 1.43 0 1.60 Floor -0.65 -0.65 8.98 Terminal 722 722
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 722 722
Infiltration 0.43 0.43 4.74 0.07 0.86 Infiltration -0.26 -0.26 3.59 Sec Fan 0 0
Sub Total ==> 2.96 0.00 2.96 32.64 2.62 32.15 Sub Total ==> -8.92 -8.92 123.20 Nom Vent 0 0
AHU Vent 0 0
Internal Loads Internal Loads Infil 10 10
Lights 0.60 0.15 0.75 8.27 0.60 7.36 Lights 0.60 0.74 -10.22 MinStop/Rh 0 0
People 1.34 0 1 14.77 0.83 10.18 People 0.83 1 -11.46 Return 722 722
Misc 0.37 0.00 0.37 4.08 0.37 4.54 Misc 0.37 0.37 -5.11 Exhaust 0 0
Sub Total ==> 2.31 0.15 2.46 27.12 1.80 22.09 Sub Total ==> 1.80 1.94 -26.80 Rm Exh 10 10
Auxiliary 0 0
Ceiling Load 0.34 -0.34 0.00 0.00 0.35 4.29 Ceiling Load -0.11 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.00 0.00 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 3.38 3.38 37.27 3.38 41.47 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.27 2.98 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 0.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.26 3.59 Lps/m² 11.64 11.64
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 79.66
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.84
W/m² 146.03 -116.74
Grand Total ==> 8.99 -0.19 9.07 100.00 8.15 100.00 Grand Total ==> -7.23 -7.24 100.00 No. People 10
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 49 of 80
Room Checksums
By Trane
0B3F-Lockers woman
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 18 Mo/Hr: 8 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 19 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.0 22.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 2.33 2.33 27.38 2.35 30.88 Partition/Door -7.79 -7.79 115.07 Diffuser 675 675
Floor 0.13 0.13 1.53 0 1.71 Floor -0.65 -0.65 9.60 Terminal 675 675
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 675 675
Infiltration 0.43 0.43 5.05 0.07 0.92 Infiltration -0.26 -0.26 3.84 Sec Fan 0 0
Sub Total ==> 2.89 0.00 2.89 33.96 2.55 33.51 Sub Total ==> -8.70 -8.70 128.51 Nom Vent 0 0
AHU Vent 0 0
Internal Loads Internal Loads Infil 10 10
Lights 0.60 0.15 0.75 8.81 0.60 7.88 Lights 0.60 0.74 -10.93 MinStop/Rh 0 0
People 1.34 0 1 15.75 0.83 10.91 People 0.83 1 -12.26 Return 675 675
Misc 0.62 0.00 0.62 7.29 0.62 8.15 Misc 0.62 0.62 -9.16 Exhaust 0 0
Sub Total ==> 2.56 0.15 2.71 31.84 2.05 26.94 Sub Total ==> 2.05 2.19 -32.35 Rm Exh 10 10
Auxiliary 0 0
Ceiling Load 0.34 -0.34 0.00 0.00 0.35 4.60 Ceiling Load -0.11 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.00 0.00 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 2.66 2.66 31.26 2.66 34.95 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.25 2.94 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 0.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.26 3.84 Lps/m² 10.88 10.88
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 79.28
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.28
W/m² 137.20 -109.15
Grand Total ==> 8.45 -0.19 8.51 100.00 7.61 100.00 Grand Total ==> -6.76 -6.77 100.00 No. People 10
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 50 of 80
Room Checksums
By Trane
0B3F-Yoga
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 18 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 20 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.3 20.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.94 0.16 1.10 28.28 0.93 26.72 Wall Cond -0.93 -1.11 26.94
Partition/Door 0.78 0.78 20.05 0.81 23.28 Partition/Door -2.67 -2.67 64.81 Diffuser 308 308
Floor 0.07 0.07 1.80 0 2.30 Floor -0.39 -0.39 9.47 Terminal 308 308
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 308 308
Infiltration 0.27 0.27 6.94 0.05 1.44 Infiltration -0.16 -0.16 3.88 Sec Fan 0 0
Sub Total ==> 2.06 0.16 2.22 57.07 1.87 53.74 Sub Total ==> -4.15 -4.33 105.10 Nom Vent 51 51
AHU Vent 51 51
Internal Loads Internal Loads Infil 6 6
Lights 0.44 0.11 0.55 14.14 0.44 12.64 Lights 0.44 0.55 -13.35 MinStop/Rh 0 0
People 0.96 0 1 24.68 0.59 16.95 People 0.59 1 -14.32 Return 314 314
Misc 0.37 0.00 0.37 9.51 0.37 10.63 Misc 0.37 0.37 -8.98 Exhaust 57 57
Sub Total ==> 1.77 0.11 1.88 48.33 1.40 40.23 Sub Total ==> 1.40 1.51 -36.65 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.20 -0.20 0.00 0.00 0.21 6.03 Ceiling Load -0.06 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.32 -8.23 0.00 0.00 Ventilation Load 0.00 -0.70 16.99 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -0.28 -0.28 6.80
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.32 7.77
Sup. Fan Heat 0.11 2.83 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 16.6 16.6
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.00 0.00 Lps/m² 8.31 8.31
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 56.37
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.78
W/m² 147.40 -101.40
Grand Total ==> 4.03 0.07 3.89 100.00 3.48 100.00 Grand Total ==> -3.09 -4.12 100.00 No. People 7
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 51 of 80
Room Checksums
By Trane
1F- Female toilet
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 10 / 19 Mo/Hr: 10 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 25 / 22 / 16 OADB: 25 OADB: 2 SADB 13.0 30.0
Ra Plenum 24.6 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 24.0 24.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 24.0 24.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.70 0.17 1.87 49.87 1.70 59.03 Wall Cond -1.70 -1.85 116.35
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 210 210
Floor -0.01 -0.01 -0.27 0 -0.35 Floor -0.35 -0.35 22.01 Terminal 210 210
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 210 210
Infiltration 0.22 0.22 5.87 0.01 0.35 Infiltration -0.28 -0.28 17.61 Sec Fan 0 0
Sub Total ==> 1.91 0.17 2.08 55.47 1.70 59.03 Sub Total ==> -2.33 -2.48 155.97 Nom Vent 0 0
AHU Vent 0 0
Internal Loads Internal Loads Infil 10 10
Lights 0.24 0.06 0.30 8.00 0.24 8.33 Lights 0.24 0.30 -18.87 MinStop/Rh 0 0
People 0.99 0 1 26.40 0.61 21.18 People 0.61 1 -38.36 Return 220 220
Misc 0.30 0.00 0.30 8.00 0.30 10.42 Misc 0.30 0.30 -18.87 Exhaust 10 10
Sub Total ==> 1.53 0.06 1.59 42.40 1.15 39.93 Sub Total ==> 1.15 1.21 -76.10 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.03 1.04 Ceiling Load -0.16 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.00 0.00 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -0.25 -0.25 15.72
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.08 2.13 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 0.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.07 4.40 Lps/m² 6.87 6.87
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 55.84
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.12
W/m² 123.01 -51.70
Grand Total ==> 3.47 0.20 3.75 100.00 2.88 100.00 Grand Total ==> -1.59 -1.59 100.00 No. People 8
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 52 of 80
Room Checksums
By Trane
1F- Male toilet
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 10 / 19 Mo/Hr: 10 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 25 / 22 / 16 OADB: 25 OADB: 2 SADB 13.0 30.0
Ra Plenum 24.6 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 24.0 24.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 24.0 24.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 1.69 0.17 1.86 54.55 1.69 63.30 Wall Cond -1.70 -1.85 126.71
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 193 193
Floor -0.01 -0.01 -0.29 0 -0.37 Floor -0.29 -0.29 19.86 Terminal 193 193
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 193 193
Infiltration 0.18 0.18 5.28 0.01 0.37 Infiltration -0.23 -0.23 15.75 Sec Fan 0 0
Sub Total ==> 1.86 0.17 2.03 59.53 1.69 63.30 Sub Total ==> -2.22 -2.37 162.33 Nom Vent 0 0
AHU Vent 0 0
Internal Loads Internal Loads Infil 8 8
Lights 0.20 0.05 0.25 7.33 0.20 7.49 Lights 0.20 0.25 -17.12 MinStop/Rh 0 0
People 0.81 0 1 23.75 0.50 18.73 People 0.50 1 -34.25 Return 193 193
Misc 0.25 0.00 0.25 7.33 0.25 9.36 Misc 0.25 0.25 -17.12 Exhaust 0 0
Sub Total ==> 1.26 0.05 1.31 38.42 0.95 35.58 Sub Total ==> 0.95 1.00 -68.49 Rm Exh 8 8
Auxiliary 0 0
Ceiling Load 0.03 -0.03 0.00 0.00 0.03 1.12 Ceiling Load -0.13 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.00 0.00 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -0.06 -0.06 4.11
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.07 2.05 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 0.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.03 2.05 Lps/m² 7.73 7.73
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 56.61
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.33
W/m² 136.44 -58.14
Grand Total ==> 3.15 0.19 3.41 100.00 2.67 100.00 Grand Total ==> -1.46 -1.46 100.00 No. People 6
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 53 of 80
Room Checksums
By Trane
1F-Admin & FO
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 21 Mo/Hr: 8 / 21 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 23 / 17 OADB: 26 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.3 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.6 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 6.53 0.56 7.09 22.11 6.53 22.53 Wall Cond -6.26 -6.87 22.05
Partition/Door 3.06 3.06 9.54 3.06 10.56 Partition/Door -11.94 -11.94 38.33 Diffuser 2,567 2,567
Floor 0.54 0.54 1.68 1 1.86 Floor -2.45 -2.45 7.87 Terminal 2,567 2,567
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 2,567 2,567
Infiltration 2.42 2.42 7.55 0.41 1.41 Infiltration -1.95 -1.95 6.26 Sec Fan 0 0
Sub Total ==> 12.55 0.56 13.11 40.89 10.54 36.37 Sub Total ==> -22.60 -23.21 74.51 Nom Vent 269 269
AHU Vent 269 269
Internal Loads Internal Loads Infil 77 77
Lights 2.25 0.56 2.81 8.76 2.25 7.76 Lights 2.25 2.81 -9.02 MinStop/Rh 0 0
People 5.07 0 5 15.81 3.12 10.77 People 3.12 3 -10.02 Return 2,644 2,644
Misc 11.70 0.00 11.70 36.49 11.70 40.37 Misc 11.70 11.70 -37.56 Exhaust 346 346
Sub Total ==> 19.02 0.56 19.58 61.07 17.07 58.90 Sub Total ==> 17.07 17.63 -56.60 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 1.37 -1.37 0.00 0.00 1.37 4.73 Ceiling Load -0.41 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -1.57 -4.90 0.00 0.00 Ventilation Load 0.00 -3.71 11.91 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -19.81 -19.81 63.60
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -1.69 5.43
Sup. Fan Heat 0.94 2.93 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 10.5 10.5
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.36 1.16 Lps/m² 10.97 10.97
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 63.82
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.82
W/m² 171.78 -125.03
Grand Total ==> 32.94 -0.25 32.06 100.00 28.98 100.00 Grand Total ==> -25.75 -31.15 100.00 No. People 39
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 54 of 80
Room Checksums
By Trane
1F-Corridor
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 18 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 20 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.4 20.4
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 2.51 2.51 28.85 2.58 34.35 Partition/Door -8.27 -8.27 96.27 Diffuser 667 667
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 667 667
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 667 667
Infiltration 1.90 1.90 21.84 0.36 4.79 Infiltration -1.15 -1.15 13.39 Sec Fan 0 0
Sub Total ==> 4.41 0.00 4.41 50.69 2.94 39.15 Sub Total ==> -9.42 -9.42 109.66 Nom Vent 95 95
AHU Vent 95 95
Internal Loads Internal Loads Infil 45 45
Lights 1.32 0.33 1.65 18.97 1.32 17.58 Lights 1.32 1.66 -19.32 MinStop/Rh 0 0
People 1.79 0 2 20.57 1.10 14.65 People 1.10 1 -12.81 Return 712 712
Misc 1.38 0.00 1.38 15.86 1.38 18.38 Misc 1.38 1.38 -16.07 Exhaust 140 140
Sub Total ==> 4.49 0.33 4.82 55.40 3.80 50.60 Sub Total ==> 3.80 4.14 -48.20 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.75 -0.75 0.00 0.00 0.77 10.25 Ceiling Load -0.24 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.78 -8.97 0.00 0.00 Ventilation Load 0.00 -1.31 15.25 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -0.83 -0.83 9.66
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.60 6.98
Sup. Fan Heat 0.25 2.87 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 14.3 14.3
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.57 6.64 Lps/m² 4.83 4.83
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 57.50
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 11.91
W/m² 83.93 -57.44
Grand Total ==> 9.65 -0.42 8.70 100.00 7.51 100.00 Grand Total ==> -6.69 -8.59 100.00 No. People 14
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 55 of 80
Room Checksums
By Trane
1F-Function store
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 9 / 18 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 20 OADB: 27 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.0 22.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 3.23 0.27 3.50 58.82 3.31 67.97 Wall Cond -3.61 -3.96 91.45
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 432 432
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 432 432
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 432 432
Infiltration 0.76 0.76 12.77 0.11 2.26 Infiltration -0.44 -0.44 10.16 Sec Fan 0 0
Sub Total ==> 3.99 0.27 4.26 71.60 3.42 70.23 Sub Total ==> -4.05 -4.40 101.62 Nom Vent 0 0
AHU Vent 0 0
Internal Loads Internal Loads Infil 17 17
Lights 0.51 0.13 0.64 10.76 0.51 10.47 Lights 0.51 0.64 -14.78 MinStop/Rh 0 0
People 0.57 0 1 9.58 0.35 7.19 People 0.35 0 -8.08 Return 449 449
Misc 0.32 0.00 0.32 5.38 0.32 6.57 Misc 0.32 0.32 -7.39 Exhaust 17 17
Sub Total ==> 1.40 0.13 1.53 25.71 1.18 24.23 Sub Total ==> 1.18 1.31 -30.25 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.29 -0.29 0.00 0.00 0.27 5.54 Ceiling Load -0.09 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.00 0.00 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -1.37 -1.37 31.64
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.16 2.69 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 0.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.13 -3.00 Lps/m² 8.15 8.15
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 72.48
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.89
W/m² 112.36 -81.73
Grand Total ==> 5.68 0.11 5.95 100.00 4.87 100.00 Grand Total ==> -4.33 -4.33 100.00 No. People 4
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 56 of 80
Room Checksums
By Trane
1F-Kitchen
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 15 Mo/Hr: 8 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 30 / 26 / 21 OADB: 29 OADB: 2 SADB 13.0 30.0
Ra Plenum 24.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.9 21.7
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 3.20 0.28 3.48 15.21 3.21 15.48 Wall Cond -3.04 -3.33 16.99
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 1,838 1,838
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,838 1,838
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,838 1,838
Infiltration 1.57 1.57 6.86 0.30 1.45 Infiltration -0.83 -0.83 4.23 Sec Fan 0 0
Sub Total ==> 4.77 0.28 5.05 22.07 3.51 16.92 Sub Total ==> -3.87 -4.16 21.22 Nom Vent 57 57
AHU Vent 57 57
Internal Loads Internal Loads Infil 32 32
Lights 1.19 0.30 1.49 6.51 1.19 5.74 Lights 1.19 1.48 -7.55 MinStop/Rh 0 0
People 1.07 0 1 4.68 0.66 3.18 People 0.66 1 -3.37 Return 1,870 1,870
Misc 14.85 0.00 14.85 64.90 14.85 71.60 Misc 14.85 14.85 -75.77 Exhaust 89 89
Sub Total ==> 17.11 0.30 17.41 76.09 16.70 80.52 Sub Total ==> 16.70 16.99 -86.68 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.52 -0.52 0.00 0.00 0.53 2.56 Ceiling Load -0.17 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.26 -1.14 0.00 0.00 Ventilation Load 0.00 -0.79 4.03 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -31.10 -31.10 158.67
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.36 1.84
Sup. Fan Heat 0.68 2.97 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 3.1 3.1
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.18 0.92 Lps/m² 18.56 18.56
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 74.70
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.02
W/m² 248.33 -193.67
Grand Total ==> 22.40 0.06 22.88 100.00 20.74 100.00 Grand Total ==> -18.44 -19.60 100.00 No. People 8
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 57 of 80
Room Checksums
By Trane
1F-Lobby lift & corridor
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 18 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 20 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.4 20.3
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 1.28 1.28 24.24 1.32 29.07 Partition/Door -4.13 -4.13 78.37 Diffuser 402 402
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 402 402
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 402 402
Infiltration 1.23 1.23 23.30 0.24 5.29 Infiltration -0.75 -0.75 14.23 Sec Fan 0 0
Sub Total ==> 2.51 0.00 2.51 47.54 1.56 34.36 Sub Total ==> -4.88 -4.88 92.60 Nom Vent 62 62
AHU Vent 62 62
Internal Loads Internal Loads Infil 30 30
Lights 0.86 0.22 1.08 20.45 0.86 18.94 Lights 0.86 1.08 -20.49 MinStop/Rh 0 0
People 1.17 0 1 22.16 0.72 15.86 People 0.72 1 -13.66 Return 431 431
Misc 0.90 0.00 0.90 17.05 0.90 19.82 Misc 0.90 0.90 -17.08 Exhaust 92 92
Sub Total ==> 2.93 0.22 3.15 59.66 2.48 54.63 Sub Total ==> 2.48 2.70 -51.23 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.49 -0.49 0.00 0.00 0.50 11.01 Ceiling Load -0.16 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.53 -10.04 0.00 0.00 Ventilation Load 0.00 -0.86 16.32 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -1.47 -1.47 27.89
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.39 7.40
Sup. Fan Heat 0.15 2.84 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 15.5 15.5
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.37 7.02 Lps/m² 4.47 4.47
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 56.12
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 12.57
W/m² 79.52 -53.79
Grand Total ==> 5.93 -0.27 5.28 100.00 4.54 100.00 Grand Total ==> -4.03 -5.27 100.00 No. People 9
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 58 of 80
Room Checksums
By Trane
1F-Luggage
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 20 Mo/Hr: 8 / 22 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 24 / 18 OADB: 26 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.2 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.8 21.5
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.81 0.81 22.56 0.84 25.23 Partition/Door -3.18 -3.18 98.45 Diffuser 295 295
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 295 295
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 295 295
Infiltration 0.28 0.28 7.80 0.04 1.20 Infiltration -0.20 -0.20 6.19 Sec Fan 0 0
Sub Total ==> 1.09 0.00 1.09 30.36 0.88 26.43 Sub Total ==> -3.38 -3.38 104.64 Nom Vent 14 14
AHU Vent 14 14
Internal Loads Internal Loads Infil 8 8
Lights 0.19 0.05 0.24 6.69 0.19 5.71 Lights 0.19 0.24 -7.43 MinStop/Rh 0 0
People 0.26 0 0 7.24 0.16 4.80 People 0.16 0 -4.95 Return 302 302
Misc 0.12 0.00 0.12 3.34 0.12 3.60 Misc 0.12 0.12 -3.72 Exhaust 22 22
Sub Total ==> 0.57 0.05 0.62 17.27 0.47 14.11 Sub Total ==> 0.47 0.52 -16.10 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.14 -0.14 0.00 0.00 0.14 4.20 Ceiling Load -0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.07 -1.95 0.00 0.00 Ventilation Load 0.00 -0.19 5.88 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 1.84 1.84 51.25 1.84 55.26 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.09 2.79
Sup. Fan Heat 0.11 3.06 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.7 4.7
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.09 2.79 Lps/m² 12.27 12.27
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 73.47
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.99
W/m² 166.93 -130.58
Grand Total ==> 3.64 -0.09 3.59 100.00 3.33 100.00 Grand Total ==> -2.95 -3.23 100.00 No. People 2
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 59 of 80
Room Checksums
By Trane
1F-Pantry
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 19 Mo/Hr: 8 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 18 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.2 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.8 21.3
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.88 0.07 0.95 17.06 0.88 17.64 Wall Cond -1.24 -1.36 27.25
Partition/Door 1.15 1.15 20.65 1.15 23.05 Partition/Door -3.72 -3.72 74.55 Diffuser 442 442
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 442 442
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 442 442
Infiltration 0.58 0.58 10.41 0.11 2.20 Infiltration -0.39 -0.39 7.82 Sec Fan 0 0
Sub Total ==> 2.61 0.07 2.68 48.11 2.14 42.89 Sub Total ==> -5.35 -5.47 109.62 Nom Vent 27 27
AHU Vent 27 27
Internal Loads Internal Loads Infil 15 15
Lights 0.45 0.11 0.56 10.05 0.45 9.02 Lights 0.45 0.56 -11.22 MinStop/Rh 0 0
People 0.51 0 1 9.16 0.31 6.21 People 0.31 0 -6.21 Return 457 457
Misc 0.23 0.00 0.23 4.13 0.23 4.61 Misc 0.23 0.23 -4.61 Exhaust 42 42
Sub Total ==> 1.19 0.11 1.30 23.34 0.99 19.84 Sub Total ==> 0.99 1.10 -22.04 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.27 -0.27 0.00 0.00 0.27 5.41 Ceiling Load -0.08 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.16 -2.87 0.00 0.00 Ventilation Load 0.00 -0.37 7.41 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 1.59 1.59 28.55 1.59 31.86 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.17 3.41
Sup. Fan Heat 0.16 2.87 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 6.1 6.1
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.08 1.60 Lps/m² 9.40 9.40
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 69.07
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.35
W/m² 136.00 -101.77
Grand Total ==> 5.66 -0.09 5.57 100.00 4.99 100.00 Grand Total ==> -4.44 -4.99 100.00 No. People 4
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 60 of 80
Room Checksums
By Trane
1F-Pre Function
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 10 / 14 Mo/Hr: 12 / 14 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 24 / 17 OADB: 24 OADB: 2 SADB 13.0 30.0
Ra Plenum 24.4 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 20.5 17.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 5.70 0.00 5.70 35.06 6.95 45.75 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 0.31 0.01 0.07 Glass/Door Cond -0.37 -0.37 1.57
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.55 0.55 3.38 -0.30 -1.97 Partition/Door -6.20 -6.20 26.25 Diffuser 1,346 1,346
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 1,346 1,346
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,346 1,346
Infiltration 1.49 1.49 9.16 0.11 0.72 Infiltration -1.22 -1.22 5.17 Sec Fan 0 0
Sub Total ==> 7.79 0.00 7.79 47.91 6.77 44.57 Sub Total ==> -7.79 -7.79 32.98 Nom Vent 504 504
AHU Vent 504 504
Internal Loads Internal Loads Infil 48 48
Lights 1.40 0.35 1.75 10.76 1.40 9.22 Lights 1.40 1.75 -7.41 MinStop/Rh 0 0
People 9.49 0 9 58.36 5.84 38.45 People 5.84 6 -24.72 Return 1,394 1,394
Misc 0.73 0.00 0.73 4.49 0.73 4.81 Misc 0.73 0.73 -3.09 Exhaust 552 552
Sub Total ==> 11.62 0.35 11.97 73.62 7.97 52.47 Sub Total ==> 7.97 8.32 -35.22 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.62 -0.62 0.00 0.00 0.45 2.96 Ceiling Load -0.25 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -4.00 -24.60 0.00 0.00 Ventilation Load 0.00 -6.95 29.42 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -13.43 -13.43 56.86
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -3.16 13.38
Sup. Fan Heat 0.50 3.08 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 37.4 37.4
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.61 2.58 Lps/m² 9.22 9.22
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 42.71
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.63
W/m² 215.66 -137.48
Grand Total ==> 20.03 -0.27 16.26 100.00 15.19 100.00 Grand Total ==> -13.50 -23.62 100.00 No. People 73
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 61 of 80
Room Checksums
By Trane
1F-Reception & Gallery
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 12 / 15 Mo/Hr: 12 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 24 / 21 / 14 OADB: 24 OADB: 2 SADB 13.0 30.0
Ra Plenum 23.7 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.8 21.5
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 114.90 0.00 114.90 76.90 114.90 82.75 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.69 0.00 0.69 0.46 0.69 0.50 Glass/Door Cond -21.14 -21.14 15.59
Cooling Heating
Wall Cond 0.00 0.26 0.26 0.17 0.00 0.00 Wall Cond 0.00 -0.54 0.40
Partition/Door -0.30 -0.30 -0.20 -0.30 -0.22 Partition/Door -14.88 -14.88 10.98 Diffuser 12,302 12,302
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 12,302 12,302
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 12,302 12,302
Infiltration 4.97 4.97 3.33 0.58 0.42 Infiltration -5.86 -5.86 4.32 Sec Fan 0 0
Sub Total ==> 120.26 0.26 120.52 80.66 115.87 83.45 Sub Total ==> -41.88 -42.42 31.29 Nom Vent 606 606
AHU Vent 606 606
Internal Loads Internal Loads Infil 230 230
Lights 6.74 1.68 8.42 5.64 6.74 4.85 Lights 6.74 8.42 -6.21 MinStop/Rh 0 0
People 11.41 0 11 7.64 7.02 5.06 People 7.02 7 -5.18 Return 12,532 12,532
Misc 7.02 0.00 7.02 4.70 7.02 5.06 Misc 7.02 7.02 -5.18 Exhaust 836 836
Sub Total ==> 25.17 1.68 26.85 17.97 20.78 14.97 Sub Total ==> 20.78 22.46 -16.57 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 2.20 -2.20 0.00 0.00 2.20 1.58 Ceiling Load -1.23 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -2.49 -1.67 0.00 0.00 Ventilation Load 0.00 -8.35 6.16 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -101.09 -101.09 74.57
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -3.80 2.80
Sup. Fan Heat 4.53 3.03 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 4.9 4.9
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -2.37 1.75 Lps/m² 17.52 17.52
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 73.32
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.18
W/m² 238.82 -186.99
Grand Total ==> 147.63 -0.26 149.41 100.00 138.85 100.00 Grand Total ==> -123.42 -135.57 100.00 No. People 88
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 62 of 80
Room Checksums
By Trane
1F-Server
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 15 Mo/Hr: 8 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 30 / 26 / 21 OADB: 29 OADB: 2 SADB 13.0 30.0
Ra Plenum 24.9 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.0 22.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.95 0.16 1.11 10.77 0.95 9.98 Wall Cond -0.90 -1.07 12.63
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 844 844
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 844 844
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 844 844
Infiltration 0.31 0.31 3.01 0.06 0.63 Infiltration -0.16 -0.16 1.89 Sec Fan 0 0
Sub Total ==> 1.26 0.16 1.42 13.77 1.01 10.61 Sub Total ==> -1.06 -1.23 14.52 Nom Vent 0 0
AHU Vent 0 0
Internal Loads Internal Loads Infil 6 6
Lights 0.46 0.11 0.57 5.53 0.46 4.83 Lights 0.46 0.57 -6.73 MinStop/Rh 0 0
People 0.41 0 0 3.98 0.25 2.63 People 0.25 0 -2.95 Return 850 850
Misc 7.60 0.00 7.60 73.71 7.60 79.83 Misc 7.60 7.60 -89.73 Exhaust 6 6
Sub Total ==> 8.47 0.11 8.58 83.22 8.31 87.29 Sub Total ==> 8.31 8.42 -99.41 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.20 -0.20 0.00 0.00 0.20 2.10 Ceiling Load -0.07 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 0.00 0.00 0.00 0.00 Ventilation Load 0.00 0.00 0.00 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -15.65 -15.65 184.77
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. 0.00 0.00
Sup. Fan Heat 0.31 3.01 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 0.0 0.0
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.01 0.12 Lps/m² 22.20 22.20
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 81.78
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 3.68
W/m² 271.32 -222.67
Grand Total ==> 9.93 0.07 10.31 100.00 9.52 100.00 Grand Total ==> -8.47 -8.47 100.00 No. People 3
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 63 of 80
Room Checksums
By Trane
1F-Workshop
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 12 / 14 Mo/Hr: 12 / 13 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 24 / 21 / 14 OADB: 23 OADB: 2 SADB 13.0 30.0
Ra Plenum 23.7 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 20.6 18.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 13.61 0.00 13.61 39.96 13.75 42.50 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.02 0.00 0.02 0.06 0.00 0.00 Glass/Door Cond -0.69 -0.69 1.39
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.00 0.00 0.00 0.00 0.00 Partition/Door 0.00 0.00 0.00 Diffuser 2,867 2,867
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 2,867 2,867
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 2,867 2,867
Infiltration 1.61 1.61 4.73 0.15 0.46 Infiltration -2.38 -2.38 4.81 Sec Fan 0 0
Sub Total ==> 15.24 0.00 15.24 44.74 13.90 42.97 Sub Total ==> -3.07 -3.07 6.20 Nom Vent 1,035 1,035
AHU Vent 1,035 1,035
Internal Loads Internal Loads Infil 93 93
Lights 2.74 0.68 3.42 10.04 2.74 8.47 Lights 2.74 3.42 -6.90 MinStop/Rh 0 0
People 19.50 0 20 57.25 12.00 37.09 People 12.00 12 -24.23 Return 2,960 2,960
Misc 2.85 0.00 2.85 8.37 2.85 8.81 Misc 2.85 2.85 -5.75 Exhaust 1,129 1,129
Sub Total ==> 25.09 0.68 25.77 75.66 17.59 54.37 Sub Total ==> 17.59 18.27 -36.89 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.88 -0.88 0.00 0.00 0.86 2.66 Ceiling Load -0.50 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -8.00 -23.49 0.00 0.00 Ventilation Load 0.00 -14.28 28.83 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -42.78 -42.78 86.37
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -6.49 13.10
Sup. Fan Heat 1.05 3.08 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 36.1 36.1
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -1.18 2.38 Lps/m² 10.06 10.06
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 43.82
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 4.36
W/m² 229.36 -148.28
Grand Total ==> 41.21 -0.20 34.06 100.00 32.35 100.00 Grand Total ==> -28.76 -49.53 100.00 No. People 150
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 64 of 80
Room Checksums
By Trane
2~4F-Guest Standard
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 20 OADB: 29 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.6 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 135.73 0.00 135.73 44.56 135.73 46.76 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 1.12 0.00 1.12 0.37 1.12 0.39 Glass/Door Cond -4.12 -4.12 1.24
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 75.16 75.16 24.68 75.16 25.89 Partition/Door -233.58 -233.58 70.20 Diffuser 25,720 25,720
Floor 1.91 1.91 0.63 2 0.66 Floor -10.04 -10.04 3.02 Terminal 25,720 25,720
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 25,720 25,720
Infiltration 21.71 21.71 7.13 4.23 1.46 Infiltration -12.22 -12.22 3.67 Sec Fan 0 0
Sub Total ==> 235.63 0.00 235.63 77.36 218.15 75.15 Sub Total ==> -259.96 -259.96 78.13 Nom Vent 2,700 2,700
AHU Vent 2,700 2,700
Internal Loads Internal Loads Infil 480 480
Lights 27.65 6.91 34.56 11.35 27.65 9.52 Lights 27.65 34.56 -10.39 MinStop/Rh 0 0
People 23.40 0 23 7.68 14.40 4.96 People 14.40 14 -4.33 Return 23,950 23,950
Misc 14.40 0.00 14.40 4.73 14.40 4.96 Misc 14.40 14.40 -4.33 Exhaust 930 930
Sub Total ==> 65.45 6.91 72.36 23.76 56.45 19.45 Sub Total ==> 56.45 63.36 -19.04 Rm Exh 2,250 2,250
Auxiliary 0 0
Ceiling Load 15.69 -15.69 0.00 0.00 15.69 5.40 Ceiling Load -5.03 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -12.88 -4.23 0.00 0.00 Ventilation Load 0.00 -37.25 11.20 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -49.49 -49.49 14.87
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -37.44 11.25
Sup. Fan Heat 9.46 3.11 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 10.5 10.5
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -11.94 3.59 Lps/m² 8.93 8.93
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 58.32
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.53
W/m² 153.03 -107.25
Grand Total ==> 316.77 -8.78 304.57 100.00 290.29 100.00 Grand Total ==> -258.03 -332.72 100.00 No. People 180
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 65 of 80
Room Checksums
By Trane
2~4F-HK
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 18 Mo/Hr: 8 / 18 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 19 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.6 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 1.64 1.64 33.47 1.64 36.04 Partition/Door -5.19 -5.19 106.57 Diffuser 403 403
Floor 0.04 0.04 0.82 0 0.88 Floor -0.23 -0.23 4.72 Terminal 403 403
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 403 403
Infiltration 0.45 0.45 9.18 0.09 1.98 Infiltration -0.28 -0.28 5.75 Sec Fan 0 0
Sub Total ==> 2.13 0.00 2.13 43.47 1.77 38.90 Sub Total ==> -5.70 -5.70 117.04 Nom Vent 41 41
AHU Vent 41 41
Internal Loads Internal Loads Infil 11 11
Lights 0.63 0.16 0.79 16.12 0.63 13.85 Lights 0.63 0.79 -16.22 MinStop/Rh 0 0
People 0.78 0 1 15.92 0.48 10.55 People 0.48 0 -9.86 Return 414 414
Misc 0.66 0.00 0.66 13.47 0.66 14.51 Misc 0.66 0.66 -13.55 Exhaust 52 52
Sub Total ==> 2.07 0.16 2.23 45.51 1.77 38.90 Sub Total ==> 1.77 1.93 -39.63 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.37 -0.37 0.00 0.00 0.37 8.13 Ceiling Load -0.12 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.25 -5.10 0.00 0.00 Ventilation Load 0.00 -0.57 11.70 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.64 0.64 13.06 0.64 14.07 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.26 5.34
Sup. Fan Heat 0.15 3.06 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 10.3 10.3
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.27 5.54 Lps/m² 6.10 6.10
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 65.43
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 10.72
W/m² 93.24 -69.41
Grand Total ==> 5.21 -0.21 4.90 100.00 4.55 100.00 Grand Total ==> -4.05 -4.87 100.00 No. People 6
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 66 of 80
Room Checksums
By Trane
2~4F-Lobby lift & corridor hotel
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 19 Mo/Hr: 8 / 20 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 18 OADB: 27 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.2 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.8 21.4
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 8.12 1.25 9.37 11.94 8.53 11.64 Wall Cond -12.12 -14.42 19.93
Partition/Door 18.47 18.47 23.54 18.18 24.81 Partition/Door -61.64 -61.64 85.17 Diffuser 6,494 6,494
Floor 0.38 0.38 0.48 0 0.55 Floor -1.88 -1.88 2.60 Terminal 6,494 6,494
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 6,494 6,494
Infiltration 5.11 5.11 6.51 0.80 1.09 Infiltration -3.32 -3.32 4.59 Sec Fan 0 0
Sub Total ==> 32.08 1.25 33.33 42.47 27.91 38.08 Sub Total ==> -78.96 -81.26 112.28 Nom Vent 360 360
AHU Vent 360 360
Internal Loads Internal Loads Infil 131 131
Lights 7.52 1.88 9.40 11.98 7.52 10.26 Lights 7.52 9.40 -12.99 MinStop/Rh 0 0
People 5.35 0 5 6.82 3.75 5.12 People 3.75 4 -5.18 Return 6,624 6,624
Misc 3.91 0.00 3.91 4.98 3.91 5.33 Misc 3.91 3.91 -5.40 Exhaust 491 491
Sub Total ==> 16.78 1.88 18.66 23.78 15.18 20.71 Sub Total ==> 15.18 17.06 -23.57 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 4.44 -4.44 0.00 0.00 4.52 6.17 Ceiling Load -1.37 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -1.59 -2.03 0.00 0.00 Ventilation Load 0.00 -4.97 6.87 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 25.68 25.68 32.73 25.68 35.04 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -2.26 3.12
Sup. Fan Heat 2.39 3.05 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 5.5 5.5
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.94 1.30 Lps/m² 8.29 8.29
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 72.63
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.76
W/m² 114.10 -89.17
Grand Total ==> 78.98 -1.31 78.47 100.00 73.29 100.00 Grand Total ==> -65.15 -72.37 100.00 No. People 52
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 67 of 80
Room Checksums
By Trane
2~4F-Regency Suit
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 2 / 16 Mo/Hr: 2 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 22 / 16 OADB: 26 OADB: 2 SADB 13.0 30.0
Ra Plenum 24.2 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.6 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 32.80 0.00 32.80 70.13 32.80 73.56 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.14 0.00 0.14 0.30 0.14 0.31 Glass/Door Cond -1.21 -1.21 2.58
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 1.66 1.66 3.55 1.66 3.72 Partition/Door -15.57 -15.57 33.23 Diffuser 3,951 3,951
Floor -0.02 -0.02 -0.04 0 -0.04 Floor -0.67 -0.67 1.43 Terminal 3,951 3,951
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 3,951 3,951
Infiltration 1.99 1.99 4.25 0.32 0.72 Infiltration -1.78 -1.78 3.80 Sec Fan 0 0
Sub Total ==> 36.57 0.00 36.57 78.19 34.90 78.27 Sub Total ==> -19.23 -19.23 41.04 Nom Vent 360 360
AHU Vent 360 360
Internal Loads Internal Loads Infil 70 70
Lights 4.03 1.01 5.04 10.78 4.03 9.04 Lights 4.03 5.04 -10.76 MinStop/Rh 0 0
People 3.12 0 3 6.67 1.92 4.31 People 1.92 2 -4.10 Return 3,871 3,871
Misc 2.10 0.00 2.10 4.49 2.10 4.71 Misc 2.10 2.10 -4.48 Exhaust 280 280
Sub Total ==> 9.25 1.01 10.26 21.94 8.05 18.05 Sub Total ==> 8.05 9.06 -19.33 Rm Exh 150 150
Auxiliary 0 0
Ceiling Load 1.64 -1.64 0.00 0.00 1.64 3.68 Ceiling Load -0.73 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -1.51 -3.23 0.00 0.00 Ventilation Load 0.00 -4.97 10.61 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -27.72 -27.72 59.15
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -2.26 4.82
Sup. Fan Heat 1.45 3.10 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 9.1 9.1
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -1.74 3.71 Lps/m² 9.41 9.41
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 66.27
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.05
W/m² 141.84 -106.16
Grand Total ==> 47.46 -0.63 46.77 100.00 44.59 100.00 Grand Total ==> -39.63 -46.86 100.00 No. People 24
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 68 of 80
Room Checksums
By Trane
5F-Executive Suit
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 12 / 15 Mo/Hr: 12 / 15 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 24 / 21 / 14 OADB: 24 OADB: 2 SADB 13.0 30.0
Ra Plenum 23.7 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.7 21.3
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 12.53 0.00 12.53 79.76 12.53 83.64 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.05 0.00 0.05 0.32 0.05 0.33 Glass/Door Cond -1.56 -1.56 10.32
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door -0.04 -0.04 -0.25 -0.04 -0.27 Partition/Door -2.60 -2.60 17.20 Diffuser 1,327 1,327
Floor -0.04 -0.04 -0.25 0 -0.27 Floor -0.33 -0.33 2.18 Terminal 1,327 1,327
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,327 1,327
Infiltration 0.40 0.40 2.55 0.05 0.33 Infiltration -0.47 -0.47 3.11 Sec Fan 0 0
Sub Total ==> 12.90 0.00 12.90 82.11 12.55 83.78 Sub Total ==> -4.96 -4.96 32.80 Nom Vent 90 90
AHU Vent 90 90
Internal Loads Internal Loads Infil 18 18
Lights 1.06 0.26 1.32 8.40 1.06 7.08 Lights 1.06 1.32 -8.73 MinStop/Rh 0 0
People 0.78 0 1 4.96 0.48 3.20 People 0.48 0 -3.17 Return 1,321 1,321
Misc 0.55 0.00 0.55 3.50 0.55 3.67 Misc 0.55 0.55 -3.64 Exhaust 83 83
Sub Total ==> 2.39 0.26 2.65 16.87 2.09 13.95 Sub Total ==> 2.09 2.35 -15.54 Rm Exh 25 25
Auxiliary 0 0
Ceiling Load 0.34 -0.34 0.00 0.00 0.34 2.27 Ceiling Load -0.19 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.33 -2.10 0.00 0.00 Ventilation Load 0.00 -1.24 8.20 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -10.25 -10.25 67.79
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.56 3.70
Sup. Fan Heat 0.49 3.12 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 6.8 6.8
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.46 3.04 Lps/m² 12.07 12.07
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 71.96
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.96
W/m² 167.57 -131.88
Grand Total ==> 15.63 -0.08 15.71 100.00 14.98 100.00 Grand Total ==> -13.31 -15.12 100.00 No. People 6
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 69 of 80
Room Checksums
By Trane
5F-Guest Standard
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 20 OADB: 29 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.6 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 43.85 0.00 43.85 44.08 43.85 46.26 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.36 0.00 0.36 0.36 0.36 0.38 Glass/Door Cond -1.33 -1.33 1.23
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 24.15 24.15 24.28 24.15 25.47 Partition/Door -75.26 -75.26 69.47 Diffuser 8,399 8,399
Floor 1.83 1.83 1.84 2 1.93 Floor -9.71 -9.71 8.96 Terminal 8,399 8,399
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 8,399 8,399
Infiltration 7.00 7.00 7.04 1.36 1.43 Infiltration -3.94 -3.94 3.64 Sec Fan 0 0
Sub Total ==> 77.19 0.00 77.19 77.60 71.55 75.47 Sub Total ==> -90.24 -90.24 83.30 Nom Vent 870 870
AHU Vent 870 870
Internal Loads Internal Loads Infil 155 155
Lights 8.91 2.23 11.14 11.20 8.91 9.40 Lights 8.91 11.14 -10.28 MinStop/Rh 0 0
People 7.54 0 8 7.58 4.64 4.89 People 4.64 5 -4.28 Return 7,829 7,829
Misc 4.64 0.00 4.64 4.66 4.64 4.89 Misc 4.64 4.64 -4.28 Exhaust 300 300
Sub Total ==> 21.09 2.23 23.32 23.44 18.19 19.19 Sub Total ==> 18.19 20.42 -18.85 Rm Exh 725 725
Auxiliary 0 0
Ceiling Load 5.06 -5.06 0.00 0.00 5.06 5.34 Ceiling Load -1.62 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -4.13 -4.15 0.00 0.00 Ventilation Load 0.00 -12.00 11.08 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -10.60 -10.60 9.78
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -12.06 11.13
Sup. Fan Heat 3.09 3.11 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 10.4 10.4
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -3.85 3.55 Lps/m² 9.05 9.05
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 58.55
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.47
W/m² 154.46 -108.46
Grand Total ==> 103.34 -2.83 99.47 100.00 94.80 100.00 Grand Total ==> -84.27 -108.33 100.00 No. People 58
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 70 of 80
Room Checksums
By Trane
5F-HK
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 18 Mo/Hr: 8 / 19 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 19 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.6 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.55 0.55 30.39 0.55 32.54 Partition/Door -1.73 -1.73 97.19 Diffuser 150 150
Floor 0.04 0.04 2.21 0 2.96 Floor -0.23 -0.23 12.92 Terminal 150 150
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 150 150
Infiltration 0.15 0.15 8.29 0.03 1.78 Infiltration -0.09 -0.09 5.06 Sec Fan 0 0
Sub Total ==> 0.74 0.00 0.74 40.88 0.63 37.28 Sub Total ==> -2.05 -2.05 115.17 Nom Vent 14 14
AHU Vent 14 14
Internal Loads Internal Loads Infil 4 4
Lights 0.21 0.05 0.26 14.36 0.21 12.43 Lights 0.21 0.26 -14.61 MinStop/Rh 0 0
People 0.26 0 0 14.36 0.16 9.47 People 0.16 0 -8.99 Return 153 153
Misc 0.22 0.00 0.22 12.15 0.22 13.02 Misc 0.22 0.22 -12.36 Exhaust 17 17
Sub Total ==> 0.69 0.05 0.74 40.88 0.59 34.91 Sub Total ==> 0.59 0.64 -35.96 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.12 -0.12 0.00 0.00 0.12 7.10 Ceiling Load -0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.08 -4.42 0.00 0.00 Ventilation Load 0.00 -0.19 10.67 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.35 0.35 19.34 0.35 20.71 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.09 5.06
Sup. Fan Heat 0.06 3.31 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 9.2 9.2
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.09 5.06 Lps/m² 6.80 6.80
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 66.92
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 9.84
W/m² 101.54 -76.38
Grand Total ==> 1.90 -0.07 1.81 100.00 1.69 100.00 Grand Total ==> -1.50 -1.78 100.00 No. People 2
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 71 of 80
Room Checksums
By Trane
5F-Lobby lift & corridor hotel
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 19 Mo/Hr: 8 / 20 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 18 OADB: 27 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.2 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.8 21.4
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 2.71 0.42 3.13 11.33 2.84 10.99 Wall Cond -4.04 -4.81 18.94
Partition/Door 6.16 6.16 22.29 6.06 23.44 Partition/Door -20.55 -20.55 80.94 Diffuser 2,290 2,290
Floor 0.38 0.38 1.38 0 1.55 Floor -1.88 -1.88 7.40 Terminal 2,290 2,290
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 2,290 2,290
Infiltration 1.71 1.71 6.19 0.27 1.04 Infiltration -1.11 -1.11 4.37 Sec Fan 0 0
Sub Total ==> 10.96 0.42 11.38 41.19 9.57 37.02 Sub Total ==> -27.58 -28.35 111.66 Nom Vent 120 120
AHU Vent 120 120
Internal Loads Internal Loads Infil 44 44
Lights 2.51 0.63 3.14 11.36 2.51 9.71 Lights 2.51 3.13 -12.33 MinStop/Rh 0 0
People 1.78 0 2 6.44 1.25 4.84 People 1.25 1 -4.92 Return 2,333 2,333
Misc 1.30 0.00 1.30 4.71 1.30 5.03 Misc 1.30 1.30 -5.12 Exhaust 164 164
Sub Total ==> 5.59 0.63 6.22 22.51 5.06 19.57 Sub Total ==> 5.06 5.68 -22.37 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 1.48 -1.48 0.00 0.00 1.51 5.84 Ceiling Load -0.46 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.52 -1.88 0.00 0.00 Ventilation Load 0.00 -1.66 6.54 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 9.71 9.71 35.14 9.71 37.56 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.75 2.95
Sup. Fan Heat 0.84 3.04 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 5.2 5.2
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.31 1.22 Lps/m² 8.77 8.77
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 73.23
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.35
W/m² 119.71 -93.98
Grand Total ==> 27.74 -0.43 27.63 100.00 25.85 100.00 Grand Total ==> -22.98 -25.39 100.00 No. People 17
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 72 of 80
Room Checksums
By Trane
5F-Regency Suit
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 2 / 16 Mo/Hr: 2 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 22 / 16 OADB: 26 OADB: 2 SADB 13.0 30.0
Ra Plenum 24.2 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.6 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.00 0.00 0.00 0.00 0.00 Roof Cond 0.00 0.00 0.00
Glass Solar 5.40 0.00 5.40 70.40 5.40 73.97 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.02 0.00 0.02 0.26 0.02 0.27 Glass/Door Cond -0.20 -0.20 2.60
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.23 0.23 3.00 0.23 3.15 Partition/Door -2.40 -2.40 31.17 Diffuser 648 648
Floor -0.01 -0.01 -0.13 0 -0.14 Floor -0.33 -0.33 4.29 Terminal 648 648
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 648 648
Infiltration 0.33 0.33 4.30 0.05 0.68 Infiltration -0.30 -0.30 3.90 Sec Fan 0 0
Sub Total ==> 5.97 0.00 5.97 77.84 5.69 77.95 Sub Total ==> -3.23 -3.23 41.95 Nom Vent 60 60
AHU Vent 60 60
Internal Loads Internal Loads Infil 12 12
Lights 0.67 0.17 0.84 10.95 0.67 9.18 Lights 0.67 0.84 -10.91 MinStop/Rh 0 0
People 0.52 0 1 6.78 0.32 4.38 People 0.32 0 -4.16 Return 634 634
Misc 0.35 0.00 0.35 4.56 0.35 4.79 Misc 0.35 0.35 -4.55 Exhaust 47 47
Sub Total ==> 1.54 0.17 1.71 22.29 1.34 18.36 Sub Total ==> 1.34 1.51 -19.61 Rm Exh 25 25
Auxiliary 0 0
Ceiling Load 0.27 -0.27 0.00 0.00 0.27 3.70 Ceiling Load -0.12 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.25 -3.26 0.00 0.00 Ventilation Load 0.00 -0.83 10.78 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -4.48 -4.48 58.18
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.38 4.94
Sup. Fan Heat 0.24 3.13 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 9.3 9.3
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat -0.29 3.77 Lps/m² 9.25 9.25
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 66.03
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.14
W/m² 139.99 -104.58
Grand Total ==> 7.78 -0.10 7.67 100.00 7.30 100.00 Grand Total ==> -6.49 -7.70 100.00 No. People 4
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 73 of 80
Room Checksums
By Trane
6F-Guest Standard
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 17 Mo/Hr: 8 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 20 OADB: 29 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.6 20.8
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 16.20 16.20 19.67 0.00 0.00 Roof Cond 0.00 -20.19 27.79
Glass Solar 29.38 0.00 29.38 35.68 29.38 46.60 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.25 0.00 0.25 0.30 0.25 0.40 Glass/Door Cond -0.92 -0.92 1.27
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 15.15 15.15 18.40 15.15 24.03 Partition/Door -51.91 -51.91 71.45 Diffuser 5,587 5,587
Floor 1.30 1.30 1.58 1 2.06 Floor -6.69 -6.69 9.21 Terminal 5,587 5,587
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 5,587 5,587
Infiltration 4.82 4.82 5.85 0.94 1.49 Infiltration -2.72 -2.72 3.74 Sec Fan 0 0
Sub Total ==> 50.90 16.20 67.10 81.48 47.02 74.58 Sub Total ==> -62.24 -82.43 113.46 Nom Vent 600 600
AHU Vent 600 600
Internal Loads Internal Loads Infil 107 107
Lights 6.14 1.54 7.68 9.33 6.14 9.74 Lights 6.14 7.68 -10.57 MinStop/Rh 0 0
People 5.20 0 5 6.31 3.20 5.08 People 3.20 3 -4.40 Return 5,193 5,193
Misc 3.20 0.00 3.20 3.89 3.20 5.08 Misc 3.20 3.20 -4.40 Exhaust 207 207
Sub Total ==> 14.54 1.54 16.08 19.53 12.54 19.89 Sub Total ==> 12.54 14.08 -19.38 Rm Exh 500 500
Auxiliary 0 0
Ceiling Load 3.49 -3.49 0.00 0.00 3.49 5.54 Ceiling Load -1.12 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -2.89 -3.51 0.00 0.00 Ventilation Load 0.00 -8.28 11.40 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -5.24 -5.24 7.21
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -8.32 11.45
Sup. Fan Heat 2.06 2.50 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 10.7 10.7
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 17.54 -24.14 Lps/m² 8.73 8.73
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 49.58
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 5.68
W/m² 175.93 -105.23
Grand Total ==> 68.93 14.25 82.35 100.00 63.05 100.00 Grand Total ==> -56.06 -72.65 100.00 No. People 40
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 74 of 80
Room Checksums
By Trane
6F-HK
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 18 Mo/Hr: 8 / 18 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 19 OADB: 28 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.1 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.6 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 0.61 0.61 25.10 0.00 0.00 Roof Cond 0.00 -0.69 38.76
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.51 0.51 20.99 0.51 30.18 Partition/Door -1.73 -1.73 97.19 Diffuser 150 150
Floor 0.05 0.05 2.06 0 2.96 Floor -0.23 -0.23 12.92 Terminal 150 150
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 150 150
Infiltration 0.15 0.15 6.17 0.03 1.78 Infiltration -0.09 -0.09 5.06 Sec Fan 0 0
Sub Total ==> 0.71 0.61 1.32 54.32 0.59 34.91 Sub Total ==> -2.05 -2.74 153.93 Nom Vent 14 14
AHU Vent 14 14
Internal Loads Internal Loads Infil 4 4
Lights 0.21 0.05 0.26 10.70 0.21 12.43 Lights 0.21 0.26 -14.61 MinStop/Rh 0 0
People 0.26 0 0 10.70 0.16 9.47 People 0.16 0 -8.99 Return 153 153
Misc 0.22 0.00 0.22 9.05 0.22 13.02 Misc 0.22 0.22 -12.36 Exhaust 17 17
Sub Total ==> 0.69 0.05 0.74 30.45 0.59 34.91 Sub Total ==> 0.59 0.64 -35.96 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.12 -0.12 0.00 0.00 0.12 7.10 Ceiling Load -0.04 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.08 -3.29 0.00 0.00 Ventilation Load 0.00 -0.19 10.67 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 0.39 0.39 16.05 0.39 23.08 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.09 5.06
Sup. Fan Heat 0.06 2.47 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 9.2 9.2
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 0.60 -33.71 Lps/m² 6.80 6.80
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 52.55
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.73
W/m² 129.32 -76.38
Grand Total ==> 1.91 0.54 2.43 100.00 1.69 100.00 Grand Total ==> -1.50 -1.78 100.00 No. People 2
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 75 of 80
Room Checksums
By Trane
6F-Hospitality Suit
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 16 Mo/Hr: 10 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 20 OADB: 26 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.6 20.9
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 4.43 4.43 24.02 0.00 0.00 Roof Cond 0.00 -5.55 37.65
Glass Solar 7.48 0.00 7.48 40.56 9.18 66.19 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.44 0.00 0.44 2.39 0.20 1.44 Glass/Door Cond -1.61 -1.61 10.92
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.73 0.73 3.96 0.33 2.38 Partition/Door -2.60 -2.60 17.64 Diffuser 1,229 1,229
Floor 0.06 0.06 0.33 0 0.07 Floor -0.33 -0.33 2.24 Terminal 1,229 1,229
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,229 1,229
Infiltration 1.39 1.39 7.54 0.16 1.15 Infiltration -0.75 -0.75 5.09 Sec Fan 0 0
Sub Total ==> 10.10 4.43 14.53 78.80 9.88 71.23 Sub Total ==> -5.29 -10.84 73.54 Nom Vent 120 120
AHU Vent 120 120
Internal Loads Internal Loads Infil 29 29
Lights 1.69 0.42 2.11 11.44 1.69 12.18 Lights 1.69 2.11 -14.31 MinStop/Rh 0 0
People 1.04 0 1 5.64 0.64 4.61 People 0.64 1 -4.34 Return 1,233 1,233
Misc 0.88 0.00 0.88 4.77 0.88 6.34 Misc 0.88 0.88 -5.97 Exhaust 124 124
Sub Total ==> 3.61 0.42 4.03 21.85 3.21 23.14 Sub Total ==> 3.21 3.63 -24.63 Rm Exh 25 25
Auxiliary 0 0
Ceiling Load 0.94 -0.94 0.00 0.00 0.78 5.62 Ceiling Load -0.31 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.57 -3.09 0.00 0.00 Ventilation Load 0.00 -1.66 11.26 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -9.94 -9.94 67.44
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.75 5.09
Sup. Fan Heat 0.45 2.44 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 9.8 9.8
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 4.82 -32.70 Lps/m² 6.98 6.98
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 55.67
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.97
W/m² 125.33 -78.93
Grand Total ==> 14.65 3.91 18.44 100.00 13.87 100.00 Grand Total ==> -12.33 -14.74 100.00 No. People 8
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 76 of 80
Room Checksums
By Trane
6F-Lobby lift & corridor hotel
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 20 Mo/Hr: 8 / 20 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 27 / 24 / 18 OADB: 27 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.2 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.8 21.4
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 7.14 7.14 20.59 0.00 0.00 Roof Cond 0.00 -8.23 32.41
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 2.77 0.43 3.20 9.23 2.77 10.72 Wall Cond -4.04 -4.81 18.94
Partition/Door 5.87 5.87 16.93 5.87 22.71 Partition/Door -20.55 -20.55 80.94 Diffuser 2,290 2,290
Floor 0.40 0.40 1.15 0 1.55 Floor -1.88 -1.88 7.40 Terminal 2,290 2,290
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 2,290 2,290
Infiltration 1.56 1.56 4.50 0.27 1.04 Infiltration -1.11 -1.11 4.37 Sec Fan 0 0
Sub Total ==> 10.60 7.57 18.17 52.39 9.31 36.02 Sub Total ==> -27.58 -36.58 144.07 Nom Vent 120 120
AHU Vent 120 120
Internal Loads Internal Loads Infil 44 44
Lights 2.51 0.63 3.14 9.05 2.51 9.71 Lights 2.51 3.13 -12.33 MinStop/Rh 0 0
People 1.78 0 2 5.13 1.25 4.84 People 1.25 1 -4.92 Return 2,333 2,333
Misc 1.30 0.00 1.30 3.75 1.30 5.03 Misc 1.30 1.30 -5.12 Exhaust 164 164
Sub Total ==> 5.59 0.63 6.22 17.94 5.06 19.57 Sub Total ==> 5.06 5.68 -22.37 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 1.51 -1.51 0.00 0.00 1.51 5.84 Ceiling Load -0.46 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.52 -1.50 0.00 0.00 Ventilation Load 0.00 -1.66 6.54 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0.00 0.00 0.00
Ov/Undr Sizing 9.97 9.97 28.75 9.97 38.57 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.75 2.95
Sup. Fan Heat 0.84 2.42 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 5.2 5.2
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 7.92 -31.19 Lps/m² 8.77 8.77
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 59.74
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.81
W/m² 146.75 -93.98
Grand Total ==> 27.67 6.69 34.68 100.00 25.85 100.00 Grand Total ==> -22.98 -25.39 100.00 No. People 17
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 77 of 80
Room Checksums
By Trane
6F-Pantry
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 21 Mo/Hr: 8 / 20 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 26 / 23 / 17 OADB: 27 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.3 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.0 19.2
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 2.22 2.22 34.58 0.00 0.00 Roof Cond 0.00 -2.46 46.42
Glass Solar 0.00 0.00 0.00 0.00 0.00 0.00 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.00 0.00 0.00 0.00 0.00 0.00 Glass/Door Cond 0.00 0.00 0.00
Cooling Heating
Wall Cond 0.89 0.13 1.02 15.89 0.90 22.78 Wall Cond -1.40 -1.66 31.32
Partition/Door 0.32 0.32 4.98 0.34 8.61 Partition/Door -1.14 -1.14 21.51 Diffuser 350 350
Floor 0.00 0.00 0.00 0 0.00 Floor 0.00 0.00 0.00 Terminal 350 350
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 350 350
Infiltration 0.39 0.39 6.07 0.08 2.03 Infiltration -0.33 -0.33 6.23 Sec Fan 0 0
Sub Total ==> 1.60 2.35 3.95 61.53 1.32 33.42 Sub Total ==> -2.87 -5.59 105.47 Nom Vent 90 90
AHU Vent 90 90
Internal Loads Internal Loads Infil 13 13
Lights 0.75 0.19 0.94 14.64 0.75 18.99 Lights 0.75 0.94 -17.74 MinStop/Rh 0 0
People 1.69 0 2 26.32 1.04 26.33 People 1.04 1 -19.62 Return 363 363
Misc 0.39 0.00 0.39 6.07 0.39 9.87 Misc 0.39 0.39 -7.36 Exhaust 103 103
Sub Total ==> 2.83 0.19 3.02 47.04 2.18 55.19 Sub Total ==> 2.18 2.37 -44.72 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 0.46 -0.46 0.00 0.00 0.45 11.39 Ceiling Load -0.14 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.68 -10.59 0.00 0.00 Ventilation Load 0.00 -1.24 23.40 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -2.68 -2.68 50.57
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.56 10.57
Sup. Fan Heat 0.13 2.02 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 25.6 25.6
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 2.40 -45.28 Lps/m² 4.48 4.48
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 38.27
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 8.54
W/m² 117.08 -59.98
Grand Total ==> 4.89 2.08 6.42 100.00 3.95 100.00 Grand Total ==> -3.51 -5.30 100.00 No. People 13
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 78 of 80
Room Checksums
By Trane
6F-Regency Club Lounge
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 8 / 16 Mo/Hr: 5 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 29 / 26 / 20 OADB: 29 OADB: 2 SADB 13.0 30.0
Ra Plenum 25.0 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 22.0 22.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 5.18 5.18 20.40 0.00 0.00 Roof Cond 0.00 -6.12 40.61
Glass Solar 7.06 0.00 7.06 27.81 7.18 42.71 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.07 0.00 0.07 0.28 0.07 0.42 Glass/Door Cond -0.23 -0.23 1.53
Cooling Heating
Wall Cond 0.31 0.21 0.52 2.05 0.34 2.02 Wall Cond -0.65 -1.25 8.29
Partition/Door 0.66 0.66 2.60 0.63 3.75 Partition/Door -2.60 -2.60 17.25 Diffuser 1,489 1,489
Floor 0.07 0.07 0.28 0 0.36 Floor -0.33 -0.33 2.19 Terminal 1,489 1,489
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 1,489 1,489
Infiltration 1.46 1.46 5.75 0.30 1.78 Infiltration -0.82 -0.82 5.44 Sec Fan 0 0
Sub Total ==> 9.63 5.39 15.02 59.16 8.58 51.04 Sub Total ==> -4.63 -11.35 75.32 Nom Vent 7 7
AHU Vent 7 7
Internal Loads Internal Loads Infil 32 32
Lights 1.86 0.47 2.33 9.18 1.86 11.06 Lights 1.86 2.33 -15.46 MinStop/Rh 0 0
People 5.60 0 6 22.06 3.45 20.52 People 3.45 3 -22.89 Return 1,496 1,496
Misc 1.94 0.00 1.94 7.64 1.94 11.54 Misc 1.94 1.94 -12.87 Exhaust 14 14
Sub Total ==> 9.40 0.47 9.87 38.87 7.25 43.13 Sub Total ==> 7.25 7.72 -51.23 Rm Exh 25 25
Auxiliary 0 0
Ceiling Load 1.04 -1.04 0.00 0.00 0.98 5.83 Ceiling Load -0.34 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.05 -0.20 0.00 0.00 Ventilation Load 0.00 -0.10 0.66 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -17.21 -17.21 114.20
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.04 0.27
Sup. Fan Heat 0.55 2.17 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 0.5 0.5
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 5.91 -39.22 Lps/m² 7.67 7.67
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 58.13
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 7.58
W/m² 131.92 -77.43
Grand Total ==> 20.07 4.82 25.39 100.00 16.81 100.00 Grand Total ==> -14.93 -15.07 100.00 No. People 43
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 79 of 80
Room Checksums
By Trane
6F-Regency Suit
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 9 / 16 Mo/Hr: 2 / 16 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 28 / 25 / 19 OADB: 26 OADB: 2 SADB 13.0 30.0
Ra Plenum 24.7 21.0
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 22.0 22.0
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 21.6 21.0
kW kW kW (%) kW (%) kW kW (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Solar 0.00 0.00 0.00 Fn Frict 0.2 0.0
Skylite Cond 0.00 0.00 0.00 0.00 0.00 0.00 Skylite Cond 0.00 0.00 0.00
Roof Cond 0.00 1.47 1.47 16.94 0.00 0.00 Roof Cond 0.00 -2.21 29.27
Glass Solar 4.45 0.00 4.45 51.27 5.27 73.91 Glass Solar 0.00 0.00 0.00 AIRFLOWS
Glass/Door Cond 0.04 0.00 0.04 0.46 0.02 0.28 Glass/Door Cond -0.20 -0.20 2.65
Cooling Heating
Wall Cond 0.00 0.00 0.00 0.00 0.00 0.00 Wall Cond 0.00 0.00 0.00
Partition/Door 0.50 0.50 5.76 0.19 2.66 Partition/Door -2.40 -2.40 31.79 Diffuser 633 633
Floor 0.04 0.04 0.46 0 -0.14 Floor -0.33 -0.33 4.37 Terminal 633 633
Adjacent Floor 0 0 0 0 0 0 Adjacent Floor 0 0 0.00 Main Fan 633 633
Infiltration 0.49 0.49 5.65 0.05 0.70 Infiltration -0.30 -0.30 3.97 Sec Fan 0 0
Sub Total ==> 5.52 1.47 6.99 80.53 5.52 77.42 Sub Total ==> -3.23 -5.44 72.05 Nom Vent 60 60
AHU Vent 60 60
Internal Loads Internal Loads Infil 12 12
Lights 0.67 0.17 0.84 9.68 0.67 9.40 Lights 0.67 0.84 -11.13 MinStop/Rh 0 0
People 0.52 0 1 5.99 0.32 4.49 People 0.32 0 -4.24 Return 620 620
Misc 0.35 0.00 0.35 4.03 0.35 4.91 Misc 0.35 0.35 -4.64 Exhaust 47 47
Sub Total ==> 1.54 0.17 1.71 19.70 1.34 18.79 Sub Total ==> 1.34 1.51 -20.00 Rm Exh 25 25
Auxiliary 0 0
Ceiling Load 0.34 -0.34 0.00 0.00 0.27 3.79 Ceiling Load -0.12 0 0.00 Leakage Dwn 0 0
Ventilation Load 0.00 0.00 -0.25 -2.88 0.00 0.00 Ventilation Load 0.00 -0.83 10.99 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing -4.33 -4.33 57.35
Ov/Undr Sizing 0.00 0.00 0.00 0.00 0.00 Exhaust Heat 0.00 0.00 ENGINEERING CKS
Exhaust Heat 0.00 0.00 0.00 OA Preheat Diff. -0.38 5.03
Sup. Fan Heat 0.23 2.65 RA Preheat Diff. 0.00 0.00 Cooling Heating
Ret. Fan Heat 0.00 0.00 0.00 Additional Reheat 0.00 0.00 % OA 9.5 9.5
Duct Heat Pkup 0.00 0.00 0.00 System Plenum Heat 1.92 -25.43 Lps/m² 9.04 9.04
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 Lps/kW 58.47
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 m²/kW 6.47
W/m² 154.55 -102.51
Grand Total ==> 7.40 1.30 8.68 100.00 7.13 100.00 Grand Total ==> -6.34 -7.55 100.00 No. People 4
Project Name: Hyatt Regency SaPa TRACE® 700 v6.2.5 calculated at 05:23 PM on 12/24/2021
Dataset Name: HYATT REGENCY.TRC Alternative - 1 System Checksums Report Page 80 of 80