User Manual: Hybrid 3.6KW/5.6KW Inverter / Charger
User Manual: Hybrid 3.6KW/5.6KW Inverter / Charger
Hybrid 3.6KW/5.6KW
INVERTER / CHARGER
Version: 1.0
Table Of Contents
Purpose ............................................................................................................................................................ 1
Scope ............................................................................................................................................................... 1
SAFETY INSTRUCTIONS.................................................................................................................................. 1
INTRODUCTION ............................................................................................................................................... 2
INSTALLATION ................................................................................................................................................. 4
OPERATION ..................................................................................................................................................... 10
Overview ........................................................................................................................................................ 36
Clearance and Maintenance .......................................................................................................................... 36
SPECIFICATIONS ........................................................................................................................................... 37
Scope
This manual provides safety and installation guidelines as well as information on tools and wiring.
SAFETY INSTRUCTIONS
WARNING: This chapter contains important safety and operating instructions. Read and
keep this manual for future reference.
1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries and all
appropriate sections of this manual.
2. CAUTION --To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries.
Other types of batteries may burst, causing personal injury and damage.
3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required.
Incorrect re-assembly may result in a risk of electric shock or fire.
4. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning.
Turning off the unit will not reduce this risk.
5. CAUTION – Only qualified personnel can install this device with battery.
6. NEVER charge a frozen battery.
7. For optimum operation of this inverter/charger, please follow required spec to select appropriate cable
size. It’s very important to correctly operate this inverter/charger.
8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop
a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please
refer to INSTALLATION section of this manual for the details.
10. Fuses are provided as over-current protection for the battery supply.
11. GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded
wiring system. Be sure to comply with local requirements and regulation to install this inverter.
12. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input
short circuits.
13. Warning!! Only qualified service persons are able to service this device. If errors still persist after
following troubleshooting table, please send this inverter/charger back to local dealer or service center
for maintenance.
1
INTRODUCTION
This hybrid PV inverter can provide power to connected loads by utilizing PV power, utility power and battery
power.
Hybrid inverter
Distribution Box
PV module
Electric grids
Battery Load
Figure 1 Basic hybrid PV System Overview
Depending on different power situations, this hybrid inverter is designed to generate continuous power from PV
solar modules (solar panels), battery, and the utility. When MPP input voltage of PV modules is within
acceptable range (see specification for the details), this inverter is able to generate power to feed the grid
(utility) and charge battery. Never connect the positive and negative terminals of the solar panel to
the ground. See Figure 1 for a simple diagram of a typical solar system with this hybrid inverter.
2
Product Overview
1. RGB LED ring (refer to LCD Setting section for the details)
2. LCD display
3. Function buttons
4. PV connectors
5. AC input connectors
6. AC output connectors (Load connection)
7. Battery connectors
8. Current sharing port
9. Parallel communication port
10. Circuit breaker
11. Power switch
12. Dry contact
13. USB port as USB communication port and USB function port
14. RS-232 communication port
15. BMS communication port: CAN, RS-485 or RS-232
3
INSTALLATION
Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should
have received the following items inside of package:
Preparation
Before connecting all wirings, please take off bottom cover by removing two screws as shown below.
4
Install the unit by screwing three screws. It’s recommended to use M4 or M5 screws.
Battery Connection
CAUTION: For safety operation and regulation compliance, it’s requested to install a separate DC over-current
protector or disconnect device between battery and inverter. It may not be requested to have a disconnect
device in some applications, however, it’s still requested to have over-current protection installed. Please refer
to typical amperage in below table as required fuse or breaker size.
Ring terminal:
5
WARNING: Shock Hazard
Installation must be performed with care due to high battery voltage in series.
CAUTION!! Do not place anything between the flat part of the inverter terminal and the ring
terminal. Otherwise, overheating may occur.
CAUTION!! Do not apply anti-oxidant substance on the terminals before terminals are connected
tightly.
CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure
positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between
inverter and AC input power source. This will ensure the inverter can be securely disconnected during
maintenance and fully protected from over current of AC input.
CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input
and output connectors.
WARNING:
Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
4. Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws.
Be sure to connect PE protective conductor ( ) first.
6
→Ground (yellow-green)
L→LINE (brown or black)
N→Neutral (blue)
CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it’s required
to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a
short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check
manufacturer of air conditioner if it’s equipped with time-delay function before installation. Otherwise, this
inverter/charger will trig overload fault and cut off output to protect your appliance but sometimes it still causes
internal damage to the air conditioner.
PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter
and PV modules.
PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:
1. Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
2. Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
Solar Charging Mode
INVERTER MODEL 3.6KW 5.6KW
Max. PV Array Open Circuit Voltage 500 Vdc 450 Vdc
PV Array MPPT Voltage Range 120~430Vdc
MPP Number 1
7
Please follow below steps to implement PV module connection:
1. Remove insulation sleeve 10 mm for positive and negative conductors.
2. Check correct polarity of connection cable from PV modules and PV input
connectors. Then, connect positive pole (+) of connection cable to positive
pole (+) of PV input connector. Connect negative pole (-) of connection
cable to negative pole (-) of PV input connector.
Final Assembly
After connecting all wirings, please put bottom cover back by screwing two screws as shown below.
8
Communication Connection
Serial Connection
Please use supplied communication cable to connect to inverter and PC. Insert bundled CD into a computer and
follow on-screen instruction to install the monitoring software. For the detailed software operation, please
check user manual of software inside of CD.
Wi-Fi Connection
Wi-Fi module can enable wireless communication between off-grid inverters and monitoring platform. Users
have complete and remote monitoring and controlling experience for inverters when combining Wi-Fi module
with SolarPower APP, available for both iOS and Android based device. All data loggers and parameters are
saved in iCloud. For quick installation and operation, please refer to Appendix III - The Wi-Fi Operation Guide
for details.
9
OPERATION
Power ON/OFF
Once the unit has been properly installed and the batteries are connected well, simply press On/Off switch
to turn on the unit.
LCD Display
Touchable
Function keys
10
LCD Display Icons
11
Indicate the output voltage, load in VA, load in Watt and output
frequency.
Battery Information
Indicates battery level in battery mode and charging status in line mode
by 0-24%, 25-49%, 50-74% and 75-100%.
When battery is charging, it will present battery charging status.
Status Battery voltage LCD Display
<2V/cell 4 bars will flash in turns.
Constant The right bar will be on and the other three bars
2 ~ 2.083V/cell
will flash in turns.
Current mode / The right two bars will be on and the other two
2.083 ~ 2.167V/cell
Constant bars will flash in turns.
Voltage mode The right three bars will be on and the left bar
> 2.167 V/cell
will flash.
Floating mode. Batteries are fully charged. 4 bars will be on.
In battery mode, it will present battery capacity.
Load Percentage Battery Voltage LCD Display
< 1.85V/cell
1.85V/cell ~ 1.933V/cell
Load >50%
1.933V/cell ~ 2.017V/cell
> 2.017V/cell
< 1.892V/cell
1.892V/cell ~ 1.975V/cell
Load < 50%
1.975V/cell ~ 2.058V/cell
> 2.058V/cell
Load Information
Indicates overload.
0%~24% 25%~49%
50%~74% 75%~100%
12
Output source priority setting display
13
LCD Setting
After pressing and holding ENTER button for 3 seconds, the unit will enter setting mode. Press “UP” or “DOWN”
button to select setting programs. And then, press “ENTER” button to confirm the selection or ESC button to
exit.
Escape
03 Output voltage
14
240Vac
04 Output frequency
15
If this inverter/charger is working in Line, Standby or Fault mode,
charger source can be programmed as below:
Charger source priority: Solar and Utility (default) Solar energy and utility will charge
10 To configure charger battery at the same time.
source priority
Maximum utility
13
charging current 40A 50A
60A 70A
16
80A 90A
17
3rd party Lithium battery If selected, programs of 02, 26, 27
and 29 will be automatically set up.
No need for further setting. Please
contact the battery supplier for
installation procedure.
Default setting: 56.4V If self-defined is selected in program
14, this program can be set up.
Bulk charging voltage
17 Setting range is from 48.0V to 64.0V.
(C.V voltage)
Increment of each click is 0.1V.
18
Return to default display If selected, no matter how users
screen (default) switch display screen, it will
automatically return to default display
screen (Input voltage /output
voltage) after no button is pressed for
Auto return to default
22 1 minute.
display screen
Stay at latest screen If selected, the display screen will
stay at latest screen user finally
switches.
23 Backlight control
24 Alarm control
19
L3 phase The inverter is operated in L3 phase in
3-phase application.
20
On/Off control for RGB
Enabled (default) Disable
LED
*It’s necessary to
35
enable this setting to
activate RGB LED
lighting function.
Low Normal (default)
21
LED lighting portion will be changed
by battery capacity percentage.
Battery capacity percentage
If “Solid on” is selected in #38, LED
(Default)
ring will light up with background
color setting in #40.
If “Power wheel” is selected in #38,
LED ring will light up in 4 levels.
If “cycling” or “chasing” is selected in
#38, LED ring will light up in 12 levels.
LED lighting portion will be changed
by load percentage.
Data Presentation of
Load percentage. If “Solid on” is selected in #38, LED
data color
ring will light up with background
*Energy source
color setting in #40.
(Grid-PV-Battery) and
If “Power wheel” is selected in #38,
39 battery
LED ring will light up in 4 levels.
charge/discharge status
If “cycling” or “chasing” is selected in
only available when
#38, LED ring will light up in 12 levels.
RGB LED effect is set to
Energy source If selected, the LED color will be
“Solid on”.
(Grid-PV-Battery) background color setting in #40 in AC
mode. If PV power is active, the LED
color will be data color setting in #41.
If the remaining status, the LED color
will be set in #42.
Battery charge/discharge
If selected, the LED color will be
status
background color setting in #40 in
battery charging status. The LED
color will be data color setting in #41
in battery discharging status.
Pink Orange
Yellow Green
Background color of
40
RGB LED
22
Purple White (Default)
Background color of
40
RGB LED Other
Pink Orange
Yellow Green
Pink Orange
Background color of
RGB LED only available
when data Presentation
42
of data color is set to Yellow Green
Energy source
(Grid-PV-Battery).
23
Blue Sky blue
24
USB Function Setting
Follow below steps to upgrade firmware.
Procedure LCD Screen
Step 1: Insert an USB disk into the USB port (N in product overview). Press and
hold “ ” button for 3 seconds to enter USB Function Setting Mode. It will show
“ ” on the top right corner and “ ” in LCD.
Step 2: Press “ ” button to read the file from the USB disk. If there is no burning file, the LCD will alert "U01".
Otherwise it will enter the next step.
Step 3:
Press “ ” button choose “yes” to start the firmware upgrade.
Or press “ ”or “ ” button to return to main screen.
Step 4: If “yes” is select, it will start the firmware upgrade. The LCD will
If any error occurs, error code will only show 3 seconds. After 3 seconds, it will automatically return to
display screen.
25
Display Setting
The LCD display information will be switched in turns by pressing “ ” or “ ” key. The selectable information
is switched as the following table in order.
Default PV voltage/ PV
Display current/ PV power
Screen
Battery voltage,
charging stage/
Configured battery
parameters/ Charging
or discharging current
26
Selectable information LCD display
Battery voltage=54.0V, Floating charging voltage=54.0V, Charging
current=7.8A
Battery voltage,
charging stage/
Configured battery
Battery voltage=50.0V, Low DC cut-off voltage=42.0V, Discharging
parameters/ Charging
current=10A
or discharging current
Default
Display
Screen
Output voltage=230V, Output frequency=50Hz
27
Selectable information LCD display
Load in Watt=1.9KW, Output frequency=50Hz
Default
Display
Real date 2020-08-18.
Screen
Real date.
Real time.
28
Selectable information LCD display
This PV month energy = 8kWh.
29
Selectable information LCD display
Secondary CPU version 00022.01.
Standby mode
Note:
Battery is charged by PV energy.
*Standby mode: The inverter
is not turned on yet but at
this time, the inverter can
charge battery without AC No output power, solar
output. or utility charger
*Power saving mode: If available
enabled, the output of
inverter will be off when
connected load is pretty low
or not detected. Battery is charged by utility and PV energy.
30
Battery is charged by PV energy and feed PV energy to
grid.
Standby mode
Note:
*Standby mode: The inverter
is not turned on yet but at
this time, the inverter can
charge battery without AC No output power, solar
output. or utility charger
*Power saving mode: If available No charging.
enabled, the output of
inverter will be off when
connected load is pretty low
or not detected.
31
PV energy and utility charge battery, and utility
provides power to load.
32
PV energy charges battery and provides power to the
load.
No charging.
Fault mode
Note:
*Fault mode: Errors are No output, no
caused by inside circuit error charging.
or external reasons such as
over temperature, output
short circuited and so on.
33
Warning Indicator
Warning Code Warning Event Icon flashing
01 Fan locked
02 Over temperature
04 Low battery
07 Overload
34
Faults Reference Code
Fault Code Fault Event Icon on
01 Fan is locked.
02 Over temperature
10 PV current is over.
11 PV voltage is over.
35
CLEARANCE AND MAINTENANCE FOR ANTI-DUST KIT
Overview
Every inverter is already installed with anti-dusk kit from factory. Inverter will automatically detect this kit and
activate internal thermal sensor to adjust internal temperature. This kit also keeps dusk from your inverter and
increases product reliability in harsh environment.
Step 2: Then, dustproof case can be removed and take out air filter foam as shown in below chart.
Step 3: Clean air filter foam and dustproof case. After clearance, re-assemble the dust-kit back to the inverter.
NOTICE: The anti-dust kit should be cleaned from dust every one month.
36
SPECIFICATIONS
MODEL 3.6KW 5.6KW
RATED OUPUT POWER 3600W 5600W
PV INPUT (DC)
Max. PV Power 5000W 6000W
Max. PV Array Open Circuit Voltage 500 VDC 450 VDC
PV Input Voltage Range 120 VDC~500 VDC 120 VDC~450 VDC
MPPT Range @ Operating Voltage 120 VDC~430 VDC
Max. PV Array Short Circuit Current 18A 27A
Number of MPP Tracker 1
GRID-TIE OPERATION
GRID OUTPUT (AC)
Nominal Output Voltage 220/230/240 VAC
195.5~253 VAC @India regulation
Feed-in Grid Voltage Range 184 ~ 264.5 VAC @Germany regulation
184 ~ 264.5 VAC @South America regulation
49~51Hz @India regulation
Feed-in Grid Frequency Range 47.5~51.5Hz @Germany regulation
57~62Hz @South America
Nominal Output Current 15.6A 24.3A
Power Factor Range >0.99
Maximum Conversion Efficiency (DC/AC) 96%
OFF-GRID, HYBRID OPERATION
GRID INPUT
Acceptable Input Voltage Range 90 - 280 VAC or 170 - 280 VAC
Frequency Range 50 Hz/60 Hz (Auto sensing)
< 10ms (For UPS)
Transfer Time < 20ms (For Home Appliances)
< 50ms (For parallel operation)
Rating of AC Transfer Relay 40A
BATTERY MODE OUTPUT (AC)
Nominal Output Voltage 220/230/240 VAC
Output Waveform Pure Sine Wave
Efficiency (DC to AC) 93%
BATTERY & CHARGER
Nominal DC Voltage 48 VDC
Maximum Charging Current (from Grid) 100A 120A
Maximum Charging Current (from PV) 100A 120A
Maximum Charging Current 100A 120A
GENERAL
Dimension, D X W X H (mm) 140 x 295 x 468
Net Weight (kgs) 11 12
INTERFACE
Parallel-able Yes
External Safety Box (Optional) Yes
Communication RS232/Dry-Contact/WiFi
ENVIRONMENT
Humidity 0 ~ 90% RH (No condensing)
Operating Temperature -10°C to 50°C
37
TROUBLE SHOOTING
Problem LCD/LED/Buzzer Explanation / Possible cause What to do
Unit shuts down LCD/LEDs and buzzer
automatically will be active for 3 The battery voltage is too low 1. Re-charge battery.
during startup seconds and then (<1.91V/Cell) 2. Replace battery.
process. complete off.
1. The battery voltage is far too 1. Check if batteries and the
No response after low. (<1.4V/Cell) wiring are connected well.
No indication.
power on. 2. Battery polarity is connected 2. Re-charge battery.
reversed. 3. Replace battery.
Input voltage is
Check if AC breaker is tripped
displayed as 0 on the
Input protector is tripped and AC wiring is connected
LCD and green LED is
well.
flashing.
1. Check if AC wires are too
Mains exist but the
thin and/or too long.
unit works in
Insufficient quality of AC power. 2. Check if generator (if
battery mode. Green LED is flashing.
(Shore or Generator) applied) is working well or if
input voltage range setting is
correct. (UPSAppliance)
Set “Solar First” as the priority of Change output source priority
Green LED is flashing.
output source. to Utility first.
When the unit is
turned on, internal LCD display and LEDs Check if battery wires are
Battery is disconnected.
relay is switched on are flashing connected well.
and off repeatedly.
Reduce the connected load by
Overload error. The inverter is
Fault code 07 switching off some
overload 110% and time is up.
equipment.
Check if wiring is connected
Fault code 05 Output short circuited. well and remove abnormal
load.
Check whether the air flow of
Internal temperature of inverter the unit is blocked or whether
Fault code 02
component is over 100°C. the ambient temperature is
too high.
Battery is over-charged. Return to repair center.
Fault code 03 Check if spec and quantity of
The battery voltage is too high. batteries are meet
requirements.
Fault code 01 Fan fault Replace the fan.
Buzzer beeps
continuously and Output abnormal (Inverter voltage 1. Reduce the connected
red LED is on. Fault code 06/58 below than 190Vac or is higher load.
than 260Vac) 2. Return to repair center
Fault code
Internal components failed. Return to repair center.
08/09/53/57
Fault code 10 Surge
38
Appendix I: Parallel function
1. Introduction
This inverter can be used in parallel with two different operation modes.
1. Parallel operation in single phase is with up to 9 units. The supported maximum output power for 3.6KW is
32.4KW/32.4KVA. The supported maximum output power for 5.6KW is 50.4KW/50.4KVA.
2. Maximum 9 units work together to support three-phase equipment. Maximum seven units support one
phase.
NOTE: If this unit is bundled with share current cable and parallel cable, this inverter is default supported
parallel operation. You may skip section 3. If not, please purchase parallel kit and install this unit by following
instruction from professional technical personnel in local dealer.
WARNING: Please make sure all output N wires of each inverter should be connected always. Otherwise, it will
cause fault in error #72.
2. Package Contents
In parallel kit, you will find the following items in the package:
Step 2: Remove two screws as below chart and remove 2-pin and 14-pin cables. Take out the board under the
communication board.
39
Step 3: Remove two screws as below chart to take out cover of parallel communication.
Step 8: Put wire cover back to the unit. Now the inverter is providing parallel operation function.
40
4. Mounting the Unit
When installing multiple units, please follow below chart.
NOTE: For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx.
50 cm above and below the unit. Be sure to install each unit in the same level.
5. Wiring Connection
NOTICE: It’s requested to connect to battery for parallel operation.
The cable size of each inverter is shown as below:
Recommended battery cable and terminal size for each inverter:
Ring Terminal Ring terminal:
Torque
Model Wire Size Cable Dimensions
value
mm2 D (mm) L (mm)
3.6KW 1*4AWG 22 6.4 33.5 2~ 3 Nm
1*2AWG or
5.6KW 28 6.4 42.7 2~ 3 Nm
2*6AWG
WARNING: Be sure the length of all battery cables is the same. Otherwise, there
will be voltage difference between inverter and battery to cause parallel inverters not working.
You need to connect the cables of each inverter together. Take the battery cables for example: You need to use
a connector or bus-bar as a joint to connect the battery cables together, and then connect to the battery
terminal. The cable size used from joint to battery should be X times cable size in the tables above. “X” indicates
the number of inverters connected in parallel.
Regarding AC input and output, please also follow the same principle.
WARNING!! Make sure all output N wires of each inverter must be connected all the time. Otherwise, it will
cause inverter fault in error code #72.
CAUTION!! Please install the breaker at the battery and AC input side. This will ensure the inverter can be
securely disconnected during maintenance and fully protected from over current of battery or AC input. The
recommended mounted location of the breakers is shown in the figures in 5-1 and 5-2.
41
Recommended breaker specification of battery for each inverter:
Model 1 unit*
3.6KW 100A/70VDC
5.6KW 140A/70VDC
*If you want to use only one breaker at the battery side for the whole system, the rating of the breaker should
be X times current of 1 unit. “X” indicates the number of inverters connected in parallel.
Battery Capacity for 3.6KW 400AH 600AH 800AH 1000AH 1200AH 1400AH 1600AH 1800AH
Battery Capacity for 5.6KW 400AH 600AH 800AH 1000AH 1200AH 1400AH 1600AH 1800AH
WARNING! Be sure that all inverters will share the same battery bank. Otherwise, the inverters will transfer to
fault mode.
N
L
N
Load L
42
Communication Connection
N
L
N
Load L
Communication Connection
43
Four inverters in parallel:
Power Connection
N
L
N
Load L
Communication Connection
N
L
N
Load L
Communication Connection
44
Six inverters in parallel:
Power Connection
N
L
N
Load L
Communication Connection
N
L
N
Load L
Communication Connection
❶ ❷ ❸ ❹ ❺ ❻ ❼
45
Eight inverters in parallel:
Power Connection
N
L
N
Load L
Communication Connection
❶ ❷ ❸ ❹ ❺ ❻ ❼ ❽
N
L
N
Load L
Communication Connection
❶ ❷ ❸ ❹ ❺ ❻ ❼ ❽ ❾
N
L1
L2
L3
N
Load L1
L2
L3
46
Communication Connection
❶ ❷ ❸ ❹ ❺ ❻ ❼ ❽ ❾
Three inverters in one phase, three inverters in second phase and two inverter for the third phase:
Power Connection
P1 P2 P3
N
L1
L2
L3
N
Load L1
L2
L3
Communication Connection
❶ ❷ ❸ ❹ ❺ ❻ ❼ ❽
Seven inverters in one phase and one inverter for the other two phases:
Power Connection
P1 P2 P3
N
L1
L2
L3
N
Load L1
L2
L3
P1
P2 P3
① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨
Note: If there is only one unit in one phase, this unit doesn’t need to connect the current sharing cable.
Or you connect it like as below:
47
⑧
Three inverters in one phase, two inverters in second phase and two inverters for the third phase:
Power Connection
P1 P2 P3
N
L1
L2
L3
N
Load L1
L2
L3
Communication Connection
❶ ❷ ❸ ❹ ❺ ❻ ❼
P1 P2 P3
N
L1
L2
L3
N
Load L1
L2
L3
Communication Connection
48
Four inverters in one phase and one inverter for the other two phases:
Power Connection
P1 P2 P3
N
L1
L2
L3
N
Load L1
L2
L3
Communication Connection
Three inverters in one phase, two inverters in second phase and one inverter for the third phase:
Power Connection
P1 P2 P3
N
L1
L2
L3
N
Load L1
L2
L3
Communication Connection
49
Three inverters in one phase and only one inverter for the remaining two phases:
Power Connection
P1 P2 P3
N
L1
L2
L3
N
Load L1
L2
L3
Communication Connection
Two inverters in two phases and only one inverter for the remaining phase:
Power Connection
P1 P2 P3
N
L1
L2
L3
N
Load L1
L2
L3
50
Communication Connection
Two inverters in one phase and only one inverter for the remaining phases:
Power Connection
P1 P2 P3
N
L1
L2
L3
N
Load L1
L2
L3
Communication Connection
N
L1
L2
L3
N
Load L1
L2
L3
51
Communication Connection
WARNING: Do not connect the current sharing cable between the inverters which are in different phases.
Otherwise, it may damage the inverters.
6. PV Connection
Please refer to user manual of single unit for PV Connection.
CAUTION: Each inverter should connect to PV modules separately.
52
Fault code display:
80 CAN fault
81 Host loss
82 Synchronization loss
Code Reference:
HS Master unit
SL Slave unit
53
8. Commissioning
Parallel in single phase
Step 1: Check the following requirements before commissioning:
Correct wire connection
Ensure all breakers in Line wires of load side are open and each Neutral wires of each unit are connected
together.
Step 2: Turn on each unit and set “PAL” in LCD setting program 28 of each unit. And then shut down all units.
NOET: It’s necessary to turn off switch when setting LCD program. Otherwise, the setting can not be
programmed.
Step 3: Turn on each unit.
LCD display in Master unit LCD display in Slave unit
NOTE: Master and slave units are randomly defined. Step 4: Switch on all AC breakers of Line wires in AC input.
It’s better to have all inverters connect to utility at the same time. If not, it will display fault 82 in following-order
inverters. However, these inverters will automatically restart. If detecting AC connection, they will work
normally.
LCD display in Master unit LCD display in Slave unit
Step 5: If there is no more fault alarm, the parallel system is completely installed.
Step 6: Please switch on all breakers of Line wires in load side. This system will start to provide power to the
load.
Step 4: Switch on all AC breakers of Line wires in AC input. If AC connection is detected and three phases are
matched with unit setting, they will work normally. Otherwise, the AC icon will flash and they will not work
in line mode.
54
LCD display in L1-phase unit LCD display in L2-phase unit LCD display in L3-phase unit
Step 5: If there is no more fault alarm, the system to support 3-phase equipment is completely installed.
Step 6: Please switch on all breakers of Line wires in load side. This system will start to provide power to the
load.
Note 1: To avoid overload occurring, before turning on breakers in load side, it’s better to have whole system in
operation first.
Note 2: Transfer time for this operation exists. Power interruption may happen to critical devices, which cannot
bear transfer time.
9. Trouble shooting
Situation
Fault Solution
Fault Event Description
Code
1. Restart the inverter.
2. Check if L/N cables are not connected reversely in all inverters.
3. For parallel system in single phase, make sure the sharing are
Current feedback into the connected in all inverters.
60
inverter is detected. For supporting three-phase system, make sure the sharing cables are
connected in the inverters in the same phase, and disconnected in the
inverters in different phases.
4. If the problem remains, please contact your installer.
1. Update all inverter firmware to the same version.
The firmware version of 2. Check the version of each inverter via LCD setting and make sure the
71 each inverter is not the CPU versions are same. If not, please contact your instraller to provide
same. the firmware to update.
3. After updating, if the problem still remains, please contact your installer.
The output current of 1. Check if sharing cables are connected well and restart the inverter.
72
each inverter is different. 2. If the problem remains, please contact your installer.
80 CAN data loss 1. Check if communication cables are connected well and restart the
81 Host data loss inverter.
82 Synchronization data loss 2. If the problem remains, please contact your installer.
1. Make sure all inverters share same groups of batteries together.
2. Remove all loads and disconnect AC input and PV input. Then, check
The battery voltage of battery voltage of all inverters. If the values from all inverters are close,
83 each inverter is not the please check if all battery cables are the same length and same material
same. type. Otherwise, please contact your installer to provide SOP to calibrate
battery voltage of each inverter.
3. If the problem still remains, please contact your installer.
1. Check the utility wiring conncetion and restart the inverter.
AC input voltage and 2. Make sure utility starts up at same time. If there are breakers installed
84 frequency are detected between utility and inverters, please be sure all breakers can be turned
different. on AC input at same time.
3. If the problem remains, please contact your installer.
1. Restart the inverter.
2. Remove some excessive loads and re-check load information from LCD
AC output current
85 of inverters. If the values are different, please check if AC input and
unbalance
output cables are in the same length and material type.
3. If the problem remains, please contact your installer.
1. Switch off the inverter and check LCD setting #28.
2. For parallel system in single phase, make sure no 3P1, 3P2 or 3P3 is set
AC output mode setting is
86 on #28.
different.
For supporting three-phase system, make sure no “PAL” is set on #28.
3. If the problem remains, please contact your installer.
55
Appendix II: BMS Communication Installation
1. Introduction
If connecting to lithium battery, it is recommended to purchase a custom-made RJ45 communication cable.
Please check with your dealer or integrator for details.
This custom-made RJ45 communication cable delivers information and signal between lithium battery and the
inverter. These information are listed below:
Re-configure charging voltage, charging current and battery discharge cut-off voltage according to the
lithium battery parameters.
Have the inverter start or stop charging according to the status of lithium battery.
LIO-4805 LIO-4810-150A
ID switch
ID switch
ID Switch indicates the unique ID code for each battery module. It's required to assign an identical ID to each
battery module for normal operation. We can set up the ID code for each battery module by rotating the PIN
number on the ID switch. From number 0 to 9, the number can be random; no particular order. Maximum 10
battery modules can be operated in parallel.
56
PYLONTECH
Dip Switch: There are 4 Dip Switches that sets different baud rate and battery group address. If switch position
is turned to the “OFF” position, it means “0”. If switch position is turned to the “ON” position, it means “1”.
57
Step 2: Use supplied RJ45 cable (from battery module package) to connect inverter and Lithium battery.
Step 3: Turn the breaker switch “ON". Now, the battery module is ready for DC output.
Step 4: Press Power on/off button on battery module for 5 secs, the battery module will start up.
*If the manual button cannot be approached, just simply turn on the inverter module. The battery module will
be automatically turned on.
58
If communication between the inverter and battery is successful, the battery icon on LCD display will
flash. Generally speaking, it will take longer than 1 minute to establish communication.
PYLONTECH
After configuration, please set up LCD panel in inverter and make wiring connection to Lithium battery as the
following steps.
Step 1. Use custom-made RJ45 cable to connect inverter and Lithium battery.
Step 3. Press more than three seconds to start Lithium battery, power output ready.
59
Step 5. Be sure to select battery type as “PYL” in LCD program 14.
WECO
Step 1. Use custom-made RJ45 cable to connect inverter and Lithium battery.
SOLTARO
Step 1. Use custom-made RJ45 cable to connect inverter and Lithium battery.
60
Note for parallel system:
1. Only support common battery installation.
2. Use custom-made RJ45 cable to connect any inverter (no need to connect to a specific inverter) and
Lithium battery. Simply set this inverter battery type to “SOL” in LCD program 5. Others should be “USE”.
61
4. LCD Display Information
Press “UP” or “DOWN” key to switch LCD display information. It will show battery pack and battery group
number before “Main CPU version checking” as below screen.
Selectable information LCD display
Battery pack numbers & Battery Battery pack numbers = 3, battery group numbers = 1
group numbers
5. Code Reference
Related information code will be displayed on LCD screen. Please check inverter LCD screen for the operation.
Code Description
If battery status is not allowed to charge and discharge after the communication
between the inverter and battery is successful, it will show code 60 to stop
charging and discharging battery.
Communication lost (only available when the battery type is setting as “Pylontech
Battery” or “WECO Battery” or “Soltaro Battery”)
After battery is connected, communication signal is not detected for 3
minutes, buzzer will beep. After 10 minutes, inverter will stop charging and
discharging to lithium battery.
Communication lost occurs after the inverter and battery is connected
successfully, buzzer beeps immediately.
If battery status is not allowed to charge after the communication between the
inverter and battery is successful, it will show code 69 to stop charging battery.
If battery status must to charge after the communication between the inverter
and battery is successful, it will show code 70 to charge battery.
If battery status is not allowed to discharge after the communication between the
inverter and battery is successful, it will show code 71 to stop discharge battery.
62
Appendix III: The Wi-Fi Operation Guide in Remote
Panel
1. Introduction
Wi-Fi module can enable wireless communication between off-grid inverters and monitoring platform. Users
have complete and remote monitoring and controlling experience for inverters when combining Wi-Fi module
with SolarPower APP, available for both iOS and Android based device. All data loggers and parameters are
saved in iCloud.
The major functions of this APP:
Delivers device status during normal operation.
Allows to configure device setting after installation.
Notifies users when a warning or alarm occurs.
Allows users to query inverter history data.
2. SolarPower App
2-1. Download and install APP
Please scan the following QR code with your smart phone and download SolarPower App.
63
Then, a “Registration success” window will pop up. Tap “Go now” to continue setting local Wi-Fi network
connection.
Enter the “SettingsWi-Fi” and select connected Wi-Fi name. The connected Wi-Fi name is the same to your
Wi-Fi PN number and enter default password “12345678”.
64
Then, return to SolarPower APP and tap “ ” button when Wi-Fi module is connected
successfully.
Step 3: Wi-Fi Network settings
Tap icon to select your local Wi-Fi router name (to access the internet) and enter password.
Step 4: Tap “Confirm” to complete the Wi-Fi configuration between the Wi-Fi module and the Internet.
Diagnose Function
If the module is not monitoring properly, please tap “ ” on the top right corner of the screen for further
details. It will show repair suggestion. Please follow it to fix the problem. Then, repeat the steps in the chapter
4.2 to re-set network setting. After all setting, tap “Rediagnosis” to re-connect again.
65
2-3. Login and APP Main Function
After finishing the registration and local Wi-Fi configuration, enter registered name and password to login.
Note: Tick “Remember Me” for your login convenience afterwards.
Overview
After login is successfully, you can access “Overview” page to have overview of your monitoring devices,
including overall operation situation and Energy information for Current power and Today power as below
diagram.
66
Devices
Tap the icon (located on the bottom) to enter Device List page. You can review all devices here by adding
or deleting Wi-Fi Module in this page.
Add device Delete device
Tap icon on the top right corner and manually enter part number to add device. This part number label is
pasted on the bottom of inverter. After entering part number, tap “Confirm” to add this device in the Device list.
For more information about Device List, please refer to the section 2.4.
ME
In ME page, users can modify “My information”, including【User’s Photo】,【Account security】, 【Modify
password】,【Clear cache】,and【Log-out】, shown as below diagrams.
67
2-4. Device List
In Device List page, you can pull down to refresh the device information and then tap any device you want to
check up for its real-time status and related information as well as to change parameter settings. Please refer
to the parameter setting list.
Device Mode
On the top of screen, there is a dynamic power flow chart to show live operation. It contains five icons to
present PV power, inverter, load, utility and battery. Based on your inverter model status, there will be
【Standby Mode】,【Line Mode】,【Battery Mode】.
【Standby Mode】Inverter will not power the load until “ON” switch is pressed. Qualified utility or PV source
can charge battery in standby mode.
【Line Mode】Inverter will power the load from the utility with or without PV charging. Qualified utility or PV
source can charge battery.
【Battery Mode】Inverter will power the load from the batter with or without PV charging. Only PV source can
charge battery.
68
Device Information Data
Users can check up 【Basic Information】,【Product Information】,【Rated information】,【History】, and
【Wi-Fi Module Information】by swiping left.
Swipe left
【Basic Information】displays basic information of the inverter, including AC voltage, AC frequency, PV input
voltage, Battery voltage, Battery capacity, Charging current, Output voltage, Output frequency, Output
apparent power, Output active power and Load percent. Please slide up to see more basic information.
【Production Information】displays Model type (Inverter type), Main CPU version, Bluetooth CPU version
and secondary CPU version.
【Wi-Fi Module Information】displays of Wi-Fi Module PN, status and firmware version.
Parameter Setting
This page is to activate some features and set up parameters for inverters. Please be noted that the listing in
“Parameter Setting” page in below diagram may differ from the models of monitored inverter. Here will briefly
highlight some of it,【Output Setting】【
, Battery Parameter Setting】【, Enable/ Disable items】【, Other Settings】,
【Restore to the defaults】to illustrate.
69
There are three ways to modify setting and they vary according to each parameter.
a) Listing options to change values by tapping one of it.
b) Activate/Shut down functions by clicking “Enable” or “Disable” button.
c) Changing values by clicking arrows or entering the numbers directly in the column.
Each function setting is saved by clicking “Set” button.
Please refer to below parameter setting list for an overall description and be noted that the available
parameters may vary depending on different models. Please always see the original product manual for
detailed setting instructions.
Parameter setting list:
Item Description
Output setting Output source To configure load power source priority.
priority
AC input range Input voltage range selection
Output voltage To set output voltage.
Output To set output frequency.
frequency
Battery Battery Type Select connected battery type
parameter Battery Cut-off
Set battery cut-off voltage
setting Voltage
Bulk Charging Set battery bulk charging voltage
Voltage
Battery Float
Set battery floating charging voltage
Voltage
Max Charging To configure total charging current for solar and utility chargers.
Current
Max AC
Charging Set maximum utility charging current
Current
Charging
To configure charger source priority
Source Priority
Back To Grid
Set battery voltage to stop discharging when grid is available
Voltage
Back To
Discharge Set battery voltage to stop charging when grid is available
Voltage
Enable/Disable Overload Auto
If disabled, the unit won’t be restarted after overload occurs.
Functions Restart
70
Overload If disabled, the unit won't be restarted after over-temperature fault is
Temperature solved.
Auto Restart
Overload
If enabled, the unit will enter bypass mode when overload occurs.
Bypass
Beeps While If enabled, buzzer will alarm when primary source is abnormal.
Primary Source
Interrupt
Buzzer If disabled, buzzer won’t be on when alarm/fault occurred.
Backlight If disabled, LCD backlight will be off when panel button is not operated
for 1 minute.
LCD Screen If selected, no matter how users switch display screen, it will
Return To automatically return to default display screen (Input voltage /output
Default Display voltage) after no button is pressed for 1 minute.
Fault Code If enabled, fault code will be recorded in the inverter when any fault
Record happens.
Solar Feed To If selected, solar energy is allowed to feed to the grid.
Grid
Solar Supply
Set solar power as priority to charge the battery or to power the load.
Priority
Reset PV
If clicked, PV energy storage data will be reset.
Energy Storage
Start Time For
The setting range of start charging time for AC charger is from 00:00 to
Enable AC
23:00. The increment of each click is 1 hour.
Charge Working
Ending Time
The setting range of stop charging time for AC charger is from 00:00 to
For Enable AC
23:00. The increment of each click is 1 hour.
Charge Working
Other Settings
Scheduled Time
The setting range of scheduled time for AC output on is from 00:00 to
For AC Output
23:00. The increment of each click is 1 hour.
On
Scheduled Time
The setting range of scheduled time for AC output off is from 00:00 to
For AC Output
23:00. The increment of each click is 1 hour.
Off
Country
Customized Select inverter installed area to meet local regulation.
Regulations
Set Date Time Set date time.
Restore to the This function is to restore all settings back to default settings.
default
71