Operating Instructions
DANGER
Hazardous voltage can cause death or serious injury.
Disconnect power before working on equipment.
CAUTION
Reliable functioning of the equipment is only ensured
with certified components.
Overvoltage category III
(Refer IEC 60947-1)
NOTICE
This product has been designed for environment A. Use of this product
7UG0572-1GT21
in environment B may cause unwanted electromagnetic disturbances in
which case the user may require to take adequate mitigation measures.
Technical Data
1
Terminal connections
Wiring Diagram
3 Phas e - 4 W ire 1 Phas e - 2 W ire
Control Supply
K1 Control Supply K1
K12 K12
Control Supply
Control Supply
K12 K1 K12 K1
Note : • For N/W selection 2P2W voltage (VLL) applied between V1 & V2 and connect CT for l1 [Do not use V3, N l2 & l3 terminal]
• For N/W selection 1P2W voltage (VLN) applied between V1 & N and connect CT for l1 [Do not use V2, V3, l2 & l3 terminal]
7UG057.. Note: The distance between APFC and external Current transformer should be kept as
short as possible. Use shielded cable or twisted pair cable between APFC and Current
transformer for long distance (Greater than 1m).
0.5 Nm
2
Front Panel Description Serial Number Description
Configuration Press ESC ( ESC ) key for 10sec. to display 8 digit serial number.
Press For decrement Note: The distance between APFC and external Current transformer
should be kept as short as possible. Use shielded cable or twisted pair
To save the setting and
Press OK
move on to next page cable between APFC and Current transformer for long distance (Greater
than 1m).
Press ESC To go back
Configuration Menu
Main Menu Leve l Sub Menu
nge
Cha word k l sh o
ld
wor se tion omina
Pa s / N o
s Ne w word rima
ry CT
nda
ry Net ction Pha pensa N age Thre age
Ye s Pass CT P Seco S e l e C o m V o l t V o l t
Installation
Passw ord trol
ng harg
e Con itivity Lo w ent
o tchi et s
(PW1) Au t lization Ma x y No. Swi ram Targ ime Disc S e n Curr ng
a ode g T e ing i
Initi Rela M P r o P. F St ep T i m Sett Sett
nge
Cha word k inal sh o
ld
wor se ion
Pass / N o Ne w word rima
ry CT
nda
ry Net ction Pha pensat Nom age Thre age
Ye s Pass CT P Seco Sele Com V ol t V ol t
trol
ng harg
e Con itivity Lo w ent
o tchi et s
Au t lization Max y No. Swi ram Ta rg ime Disc S e n Curr ng
a ode
T e ing i
wo r
d Initi Rela M Prog P. F St ep Tim Sett Sett
Pass
age ge
V olt olta ity
e
ltag Over g a ge der V r ion er ion olar
age
r Vo er V
o l t Un ng Ove pensat Und pensat CT P r
V olt v e t t in d t t i m m r o
No O S e Un S e C o C o E r
Te chnical
OK
Passw ord
+
(PW2)
sis sis r
tere tere ory
Hys age Hys er Facto Fact ult
PRES S
Vo lt Pow Defa
k1 k2 k3 k4 k5 k6 k7 k8
Ban Ban Ban Ban Ban Ban Ban Ban
k9 k 10 k 11 k 12
Ban Ban Ban Ban
NOTE: LE-3 will be prompted only
when mode is set to manual in LE-1.
3
Level 1 Level 2
Displa y Description Default Value Range Condition Displa y Description Default Value Range Condition
10(PW1); N.VLT No voltage ON ON / OFF
PSWD Passward 0000 - 9999
11(PW2) O.VLT Over voltage ON ON / OFF
C.PWD Change Password No No / Yes This option
This option will be
will be 260V (L-N) 50 - 277V (L-N) prompted
OV.S Over voltage setting
prompted 460V (L-L) 85 - 480V (L-L) only when
N.PWD New Password 0 0000 to 9999 O.VLT option
only when
C.PWD is ON.
set to YES. U.VLT Under voltage OFF ON / OFF
1 to 9999 This option
(CT.S=1) will be
CT.P CT Primary 5A 5 to 9999A 5 to 9999 190V (L-N) 50 - 240V (L-N) prompted
UV.S Under voltage setting
(CT.S=5) 340V (L-L) 85 - 415V (L-L) only when
CT Secondary U.VLT option
CT.S 5A 1A / 5A
made ON.
1P2W / 2P2W / Over compensation
NETW Network Selection 3P4W O.CMP ON ON / OFF
3P3W / 3P4W
U.CMP Under compensation ON ON / OFF
Phase 0º, 90º, 120º, Only for
PCMA compensation 0º CT.ER CT Polarity error ON ON / OFF
210º, 240º, 330º 1P2W / 2P2W
240V (L-N) H.VLT Hysteresis voltage 2 1% to 10%
VOLT Nominal Voltage 50V-440V
415V (L-L) H.PF Hysteresis power factor 1 1% to 5%
V.TH Voltage Threshold 0% 0% to 100% DFLT Factory Default No No / Yes
A.INT Auto Initialization Yes No / Yes
RLY Max Relay Numbers 12 1 to 12 Level 3
MODE Mode Auto Auto / MANL Display Description Default Value Range Condition
Automatic (AUTO) RL.01 Bank 1 OFF ON / OFF
SWPG Switching Program Auto Linear (LINR) RL.02 Bank 2 OFF ON / OFF
Rotational (ROTN) RL.03 Bank 3 OFF ON / OFF
T.PF Targeted P.F 1.000 -0.800 to 0.800 RL.04 Bank 4 OFF ON / OFF
STP.T Step Time 5s 1s to 999s RL.05 Bank 5 OFF ON / OFF Prompted
Discharge time RL.06 Bank 6 OFF ON / OFF only if
DIS.T 180s 1s to 999s MODE
(Reconnection time) RL.07 Bank 7 OFF ON / OFF is set to
C.SNS C/K Setting 60% 55% to 100% MANUAL
RL.08 Bank 8 OFF ON / OFF
L.CUR Low Current Setting 0 0% to 50% RL.09 Bank 9 OFF ON / OFF
Note: RL.10 Bank 10 OFF ON / OFF
• Auto-Initialization (A.INT) is working at best, under stable load conditions. RL.11 Bank 11 OFF ON / OFF
• Auto-Initialization (A.INT) works only with capacitor banks and not with reactors. RL.12 Bank 12 OFF ON / OFF
• If V.TH value is set to zero, A.IN will be done only at power ON.
• (A.INT) will be update 'NO' automatically in configue after Auto
• Reauto - Initialization will be done by only changing( A.INT) - YES in configue
Note:
• Recommended that number of relays not to be changed during normal operation • When condition of Low Current occurs, the display of controller will show the
If done so, restart the unit. 'CURR'
• Recommended to restart the unit if Switching program(SWPG) is changed • Low current setting is applicable for no load condition only. ( i.e. minimum load) &
during normal operation for proper functionality in accordance with the chosen to be done at no load condition on site.
control mode. • No Voltage Alarm deactivation time is 90 sec.
4
User Guide
a) Manual switching (MANL)
When this switching program is selected, the capacitor steps are controlled manually by the user.
b) Rotational switching (ROTN)
This switching program is based on rotational first-in-first-out sequence. This option will automatically switch in and out the capacitors according to the
targeted power factor, sensitivity setting and the re-connection time setting.
c) Automatic switching (AUTO)
This automatic switching program uses intelligent switching sequence. The step switching sequence is not fixed and the program automatically selects
the most appropriate steps to switch in or out in order to achieve shortest reaction time with minimum number of steps.
d) Linear switching (LINR)
In this switching sequence it works in last in first out mode. This option will automatically switch in and out the capacitors according to the targeted
power factor, sensitivity setting and the re-connection time setting.
Phase-Angle Setting
Voltage L1-N L2-N L3-N L2-L3 L3-L1 L1-L2 L1-N L2-N L3-N L2-L3 L3-L1 L1-L2 L1-N L2-N L3-N L2-L3 L3-L1 L1-L2
CT L1 L2 L3 L1 L2 L3 L3 L1 L2 L3 L1 L2 L2 L3 L1 L2 L3 L1
Phase-Angle 0º 0º 0º 90º 90º 90º 120º 120º 120º 210º 210º 210º 240º 240º 240º 330º 330º 330º
Side
144
138
Front bezel
view
144 50 138
5
Disposal
Siemens product are environment friendly, which predominantly PLASTICS: Segregate as per material type for recycling through
consist of recyclable materials. authorised dealer. Because of the long lifetime of Siemens
For disposals we recommend disassembling and separation into products the disposal guidelines may be replaced by other national
following materials: regulations when taking the product out of service.
METALS: Segregate into Ferrous & Non Ferrous types for recycling The local customer care service is available at any time to answer
through authorised dealer. disposal-related questions
Customer Care Toll free no. 1800 209 0987 Email: [email protected] Order No. A5E41790585A