HDL Bacnet Server Manual

The document describes an HDL-BACnet module that allows control from a BACnet system to an HDL-BUS system. It provides instructions on configuring the module, including setting basic information like the Ethernet IP address and mapping BACnet control points to HDL-BUS devices and parameters.

Uploaded by

Ehsan Rezazadeh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
107 views

HDL Bacnet Server Manual

The document describes an HDL-BACnet module that allows control from a BACnet system to an HDL-BUS system. It provides instructions on configuring the module, including setting basic information like the Ethernet IP address and mapping BACnet control points to HDL-BUS devices and parameters.

Uploaded by

Ehsan Rezazadeh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 5

HDL® BACNet Manual

1. Introduction

HDL-Bacnet module is a Bacnet HDL Data convertor, it can realize the control from
Bacnet system to HDL-BUS system.

Bacnet HDL-BUS
Data convertor

RJ45 BACNet system


( the manual is based on
BACNet client app )

HDL-BUS

………
.
2.HDL-BUS
HDL-Bacnet module configuration instruction

Relay Dimmer Sensor DLP Panel


HDL-BUS system devices should be setup inside HDL-BUS configuration software when
controlled by Bacnet client. Open HDL-BUS configuration software, search and set
parameters of the HDL-Bacnet module.

2.1 Basic information setting

0
HDL® BACNet Manual

HDL-Bacnet convertor embedded HDL-BUS IP


gateway function, need to set Ethernet
parameters firstly

Attention: the IP address of Ethernet parameters should be in the same Ethernet


segment with Bacnet client.
2.2 Parameters setting
Select to enable IP switch function

Default value, fixed

Control target ,
Maximum 150

(1) (2) (3) (4) (5)

(1) Bacnet ID includes different types: AI, AO, AV, BI, BO, BV, MI, MO, MV, other, not much
differences between different types, but for the convenience of management by client.
The value of ID is control point, it is user-defined, cannot be duplicate.
(2) The Hex value is auto generated according Bacnet ID type and ID value
(3) type of control target, It indicates the type of HDL-BUS controlled targets
(4) ID of HDL-BUS controlled devices.
(5) the parameter of controlled target, all supported parameters up to now, refer to below
table

1
HDL® BACNet Manual

3. Example setting

Take example of control the third ch of relay module


parameters setting in HDL-BUS configuration software:

Control ID of relay Controlled Remarks


target type module channel

Corresponding Setting in Bacnet client:

Double click to type the vale

Control target

Type 100, switch on the channel

Type 0, switch off the channel.

Addendum: supported parameter type and parameter settings


Configuration tab BACnet control parameters

2
HDL® BACNet Manual

HDL control BACNET WP Present Value


Parameter 1 Parameter 2
type definition and validation scope
0invalid switch xxx xxx invalid

Area Scene No.: 0-12


Scene control Device Area No. N/A “0” means switch off Scene,1-
12 is Scene No.
Sequence
Device Area No. N/A Area Sequence No.: 1-6
control
universal switch Switch No. N/A Switch status: 1: on, 0: off
single channel Device channel adjustment Intensity value of ch: 0-100
lighting No. time 0: off, 100: on
time switch Channel No. N/A Switch status: 1: on, 0: off
Curtain switch status: 0: stop,
curtain switch Curtain No. N/A
1: open, 2: close
Command Status: 0: invalid,
GPRS control Command No. N/A
1: SMS, 2: remote

Panel control IR Receiving


N/A 1: enable 0: disable
enabling
Panel locking N/A 1: lock 0: unlock
AC switch N/A 1: on 0: off
temperature value setting scope: 
cooling
N/A 0-30 degree Celsius
temperature of AC
degrees Fahrenheit 32-86
0: Auto, 1: high,
Fan speed of AC N/A
2: Medium 3: low
0: cooling, 1: heating
AC mode N/A 2: Ventilaiton, 3: Auto,
4: dehumidification.
temperature value setting scope:
Heating
N/A 0-30 degree Celsius
temperature of AC
degrees Fahrenheit 32-86
temperature value setting scope:
Auto temperature
N/A 0-30 degree Celsius
of AC
degrees Fahrenheit 32-86
increase Temperature increasing Value :(1-
N/A
temperature 5℃/℉)
decrease Temperature decreasing Value :
N/A
temperature (1-5℃/℉)
Backlight switch N/A 1: on 0: off
AC locking N/A 1:lock 0:unlock
Backlight intensity N/A Backlight intensity value (0-100%)

3
HDL® BACNet Manual

status indicator Status indicator intensity value (0-


N/A
intensity 100%)
button shielding of
Button No. 0: shielded,1: unshielded
panel
page shielding of
Page No. 0: shielded,1: unshielded
panel
temperature value setting scope:
dehumidification
N/A 0-30 degree Celsius
temperature of AC
degrees Fahrenheit 32-86
heating switch N/A 0: off,1: on
Mode: (5: time,4: leaving mode,
Heating mode N/A
3: night, 2: daytime,1: normal)
increase heating Temperature increasing Value :(1-
N/A
temperature 5℃/℉)
decrease heating Temperature decreasing Value :
N/A
temperature (1-5℃/℉)
setting page
panel control N/A 1: lock 0: unlock
locking

broadcast scene All areas(255) N/A Scene No.: 0-12


broadcast All
N/A Intensity of light ch: 0-100
channel Channel(255)
Security modes(1-6):01:
Security Area Vacation, 02: leaving, 03: night,
Security module N/A
(1-8) 04: night party, 05: daytime,
06: disalarm