Control MPC: Grundfos Instructions
Control MPC: Grundfos Instructions
Control MPC
Installation and operating instructions
Declaration of Conformity
We Grundfos declare under our sole responsibility that the products
Control MPC, to which this declaration relates, are in conformity with
these Council Directives on the approximation of the laws of the EC
Member States:
— Machinery Directive (98/37/EC)
Standard used: EN 60204-1:2006.
— EMC Directive (2004/108/EC)
Attestation of conformity: Certificate Control MPC 1:2007.
— Low Voltage Directive (2006/95/EC)
Standard used: EN 60439-1:2002.
These products must not be put into service until the system into which
they are to be incorporated has been declared in conformity with the
provisions of the Machinery Directive (98/37/EC).
2
CONTENTS 11.7.10 S-system configuration (4.1.8) 31
11.7.11 Pump cascade control (4.2) 32
Page
11.7.12 Min. time between start/stop (4.2.1) 32
1. Symbols used in this document 4 11.7.13 Max. number of starts/hour (4.2.1) 32
2. Scope of these instructions 4 11.7.14 Standby pumps (4.2.3) 33
3. Product description 4 11.7.15 Forced pump changeover (4.2.4) 33
4. Applications 4 11.7.16 Pump test run (4.2.5) 34
4.1 Pumps 4 11.7.17 Pilot pump (4.2.6) 34
4.2 Control variant 4 11.7.18 Pump stop attempt (4.2.7) 35
11.7.19 Pump start and stop speed (4.2.8) 35
5. Nameplate 5
11.7.20 Min. performance (4.2.9) 36
6. Software label 5 11.7.21 Compensation for pump start-up time (4.2.10) 36
7. Type key 6 11.7.22 Secondary functions (4.3) 37
8. Overview of control variants, examples 7 11.7.23 Stop function (4.3.1) 37
9. Installation 9 11.7.24 Soft pressure build-up (4.3.3) 39
9.1 Mechanical installation 9 11.7.25 Emergency run (4.3.5) 40
9.2 Electrical installation 9 11.7.26 Digital inputs (4.3.7) 40
9.3 Start-up 9 11.7.27 Functions of digital inputs (4.3.7.1) 41
11.7.28 Analog inputs (4.3.8) 41
10. Control panel 9
11.7.29 Analog inputs (4.3.8.1 to 4.3.8.7) 42
10.1 Display (pos. 1) 10
11.7.30 Analog inputs and measured value
10.1.1 Menu line 10
(4.3.8.1.1 to 4.3.8.7.1) 42
10.1.2 Top line 10
11.7.31 Digital outputs (4.3.9) 43
10.1.3 Graphical illustration 10
11.7.32 Functions of digital outputs (4.3.9.1 to 4.3.9.16) 43
10.1.4 Scroll bar 10
11.7.33 Min., max. and user-defined duty (4.3.14) 44
10.1.5 Bottom line 10
11.7.34 Min. duty (4.3.14.1) 44
10.2 Buttons and indicator lights 10
11.7.35 Max. duty (4.3.14.2) 45
10.2.1 Arrow to the right (pos. 2) 10
11.7.36 User-defined duty (4.3.14.3) 45
10.2.2 Help (pos. 3) 10
11.7.37 Pump curve data (4.3.19) 46
10.2.3 Up and down (pos. 4 and 5) 10
11.7.38 Control source (4.3.20) 47
10.2.4 Plus and minus (pos. 6 and 7) 10
11.7.39 Fixed inlet pressure (4.3.22) 47
10.2.5 Esc (pos. 8) 10
11.7.40 Flow estimation (4.3.23) 48
10.2.6 Home (pos. 9) 10
11.7.41 Monitoring functions (4.4) 48
10.2.7 Ok (pos. 10) 10
11.7.42 Dry-running protection (4.4.1) 49
10.2.8 Indicator lights (pos. 11 and 12) 10
11.7.43 Dry-running protection with pressure/level switch
10.2.9 Contrast (pos. 13) 10
(4.4.1.1) 49
10.2.10 Back light 10
11.7.44 Dry-running protection with pressure transmitter
11. Functions 11 (4.4.1.2) 50
11.1 Tree of functions 11 11.7.45 Dry-running protection with level transmitter
11.2 Overview 13 (4.4.1.3) 50
11.3 Description of functions 15 11.7.46 Min. pressure (4.4.2) 51
11.4 Status (1) 15 11.7.47 Max. pressure (4.4.3) 51
11.4.1 Current alarms (3.1) 15 11.7.48 External fault (4.4.4) 52
11.4.2 System (1.2) 15 11.7.49 Limit 1 and 2 exceeded (4.4.5 and 4.4.6) 52
11.4.3 Operating mode (1.2.1) 16 11.7.50 Pumps outside duty range (4.4.7) 53
11.4.4 Setpoint (1.2.2) 16 11.7.51 Pressure relief (4.4.8) 54
11.4.5 Setpoint influence (1.2.3) 16 11.7.52 Functions, CU 351 (4.5) 55
11.4.6 Measured values (1.2.4) 17 11.7.53 Display language (4.5.1) 55
11.4.7 Analog inputs (1.2.5) 17 11.7.54 Display units (4.5.2) 56
11.4.8 Pump 1...6 (1.3 to 1.8) 17 11.7.55 Date and time (4.5.3) 57
11.5 Operation (2) 18 11.7.56 Passwords (4.5.4) 57
11.5.1 Operation (2) 18 11.7.57 Ethernet (4.5.5) 58
11.5.2 System operating mode (2.1.1) 18 11.7.58 GENIbus number (4.5.6) 58
11.5.3 Control mode (2.1.2) 19 11.7.59 Software status (4.5.9) 58
11.5.4 Setpoints (2.1.3) 21 11.8 Data communication 59
11.5.5 Individual pump control (2.1.4) 21 11.8.1 Ethernet 59
11.5.6 Setting of individual operating mode 11.8.2 GENIbus 60
(2.1.4.1 to 2.1.4.6) 22
12. Measuring parameters 61
11.6 Alarm (3) 23
12.1 Transmitter types 61
11.6.1 Alarm status (3) 23
12.2 Parameter list 61
11.6.2 Current alarms (3.1) 24
11.6.3 Alarm log (3.2) 24 13. Fault finding chart 62
11.7 Settings (4) 25 14. Maintenance 63
11.7.1 Primary controller (4.1) 25 14.1 CU 351 63
11.7.2 PI controller (4.1.1) 26 15. Taking out of operation 63
11.7.3 Alternative setpoints (4.1.2) 27 16. Technical data 63
11.7.4 Alternative setpoints 2 to 7 (4.1.2.1 to 4.1.2.7) 27 16.1 Temperature 63
11.7.5 External setpoint influence (4.1.3) 28 16.2 Relative humidity 63
11.7.6 Setting of influence function (4.1.3.2) 29
17. Electrical data 63
11.7.7 Primary sensor (4.1.4) 29
11.7.8 Clock program (4.1.6) 30 18. Related documents 63
11.7.9 Proportional pressure (4.1.7) 31 19. Disposal 63
3
Warning 4. Applications
Prior to installation, read these installation and Control MPC is used for control and monitoring of pumps in these
operating instructions. Installation and operation applications:
must comply with local regulations and accepted • booster systems
codes of good practice. • circulation systems for heating, cooling and air-conditioning.
2. Scope of these instructions The main pumps of the system must be of the
Note
same type and size.
These installation and operating instructions apply to Grundfos
Control MPC. 4.2 Control variant
Grundfos Control MPC is a complete solution for control and Control MPC is divided into four groups based on control variant:
monitoring of up to six identical pumps.
Control
Description
3. Product description variant
Two to six electronically speed-controlled pumps.
From 0,37 to 22 kW, Control MPC-E is equipped with
Grundfos pumps with integrated frequency converter.
-E
As from 30 kW, Control MPC-E is equipped with
mains-operated pumps connected to external
Grundfos CUE frequency converters (one per pump).
Series
Two to six MAGNA, UPE or TPE Series 2000 pumps
2000
Two to six pumps connected to an external Grundfos
-F CUE frequency converter. The speed-controlled
operation alternates between the pumps.
-S Two to six mains-operated pumps
4
5. Nameplate 6. Software label
The nameplate of the Control MPC is fitted on the base frame. The software label is placed on the back of the CU 351 controller.
See position 2 in fig. 2.
1. Control MPC 3. Hydro MPC
Type: 1 1 3
Mains supply: 4
P Un
No. kW V
CONFIGURATION STEPS - PLEASE FOLLOW THE NUMBERS 96586126
Fixed speed pumps: 7 8 9
E-pumps: 10 11 12
13 14 15
Fig. 3 Software label
Pilot Pump:
Order No.: 16
Pos. Description
Options: 17 18 19
1 Control MPC - GSC file number
20 21 22
2 Control MPC options - GSC file numbers
IP 23
Weight: 24 kg 3 Hydro MPC - GSC file number*
4 Hydro MPC options - GSC file numbers*
5 Pump data - GSC file numbers**
TM03 9956 4707
25 Made in 26 * Applies only to booster systems.
** Applies only to CR, CRI, CRE and CRIE pumps.
96778609
Pos. Description
1 Type designation
2 Model
3 Serial number
4 Supply voltage
5 Nominal current [A]
6 Maximum ambient temperature in °C
7 Number of mains-operated pumps
8 Motor power in kW for mains-operated pumps
9 Nominal voltage in volts for mains-operated pumps
10 Number of pumps with frequency converter
11 Motor power in kW for pumps with frequency converter
Nominal voltage in volts for pumps with frequency
12
converter
13 Number of pilot pumps
14 Motor power in kW for pilot pump
15 Nominal voltage in volts for pilot pump
16 Order number
17-22 Options
23 Enclosure class
24 Weight [kg]
25 CE-mark
26 Country of origin
5
7. Type key
Type range
Subgroups:
E: Pumps with integrated frequency converter (0.37 - 22 kW) - one per pump
E: Pumps with external Grundfos CUE frequency converter (30 kW and above) -
one per pump
F: Pumps with external Grundfos CUE frequency converter
S: Mains-operated pumps (start/stop)
Number of pumps with frequency converter
Power [kW]
Starting method:
E: Electronic soft starter (pumps with integrated frequency converter)
ESS: Electronic soft starter (pumps with external Grundfos CUE frequency converter)
Number of mains-operated pumps
Power [kW]
Starting method:
DOL: Direct-on-line starting
SD: Star-delta starting
Supply voltage, frequency
6
8. Overview of control variants
The examples below are based on booster systems.
Hstop
TM00 7995 2296
Q Q Q
Hstop
TM00 7996 2296
Q Q Q
• Control MPC-E maintains a constant • Control MPC-F maintains a constant • Control MPC-S maintains an almost
pressure through continuous adjustment pressure through continuous adjustment constant pressure through cutting in/out
of the speed of the pumps. of the speed of the pump connected to the the required number of pumps.
• The system performance is adjusted to external Grundfos CUE frequency • The operating range of the pumps will lie
the demand through cutting in/out the converter. The speed-controlled operation between Hset and Hstop (cut-out pressure).
required number of pumps and through alternates between the pumps. • Pump changeover is automatic and
parallel control of the pumps in operation. • One pump connected to the external depends on load, operating hours and
• Pump changeover is automatic and Grundfos CUE frequency converter fault.
depends on load, operating hours and always starts first. If the pressure cannot
fault. be maintained by the pump, one or two
• All pumps in operation will run at equal mains-operated pumps will be cut in.
speed. • Pump changeover is automatic and
• The number of pumps in operation also depends on load, operating hours and
depends on the energy consumption of fault.
the pumps. If only one pump is required,
two pumps will be running at a lower
speed if this results in a lower energy
consumption. This requires that the
differential pressure of the pump is
measured.
7
The example below is based on a circulation system.
Hset
Q
Three E-pumps in operation.
H
TM04 0212 5107
Hset
Q
• Control MPC Series 2000 maintains a
constant pressure through adjustment of
the speed of the pumps connected.
• The performance is adjusted to the demand
through cutting in/out the required number
of pumps and through parallel control of the
pumps in operation.
• Pump changeover is automatic and
depends on load, operating hours and fault.
• All pumps in operation will run at equal
speed.
• The number of pumps in operation is also
depending on the energy consumption of
the pumps. If only one pump is required,
the Control MPC will run with two pumps in
operation at a lower speed if this results in
a lower energy consumption. This requires
that the differential pressure of the pump is
measured.
8
9. Installation 10. Control panel
The control panel in the front cover of the control cabinet features
Warning
a display, a number of buttons and two indicator lights. The
Installation and operation must comply with local control panel enables manual setting and monitoring of the
regulations and accepted codes of good performance of the system.
practice.
Before installation check that
2
• the Control MPC corresponds to the one ordered CU 351
3
• no visible parts have been damaged.
1
5
9.1 Mechanical installation 4
6
The Control MPC must be installed in a well ventilated room to
ensure sufficient cooling of the control cabinet. 7
8
Install the pumps according to the installation and operating
9
instructions supplied with the pumps.
Warning Key
The electrical installation should be carried out
by an authorised person in accordance with local Pos. Description
regulations and the relevant wiring diagram. 1 Display
• The electrical installation of the Control MPC must comply with 2 Arrow to the right
enclosure class, IP54. 3 Help
• Make sure that the Control MPC is suitable for the electricity 4 Up
supply to which it is connected.
5 Down
• Make sure that the wire cross-section corresponds to the
6 Plus
specifications in the wiring diagram.
7 Minus
9.3 Start-up 8 Esc
The start-up description presupposes that the selected pumps 9 Home
have been installed correctly according to the installation and 10 Ok
operating instructions supplied with the pumps. 11 Indicator light, operation (green)
After having carried out the installation of the Control MPC as 12 Indicator light, fault (red)
described in section 9. Installation, proceed as follows:
13 Contrast
1. Turn on the electricity supply.
2. Wait for the first display to appear.
3. The first time the CU 351 is switched on, a start-up wizard will
guide the user through the basic settings.
4. Follow the instructions in each display.
5. When the wizard is completed, check that all pumps are set to
Auto in the Status menu.
6. Go to the Operation menu (2), select operating mode Normal,
and press .
7. Control MPC is now ready for operation.
9
10.1 Display (pos. 1) 10.2 Buttons and indicator lights
The buttons (pos. 2 to 10 in fig. 4) on the CU 351 are active when
A they are illuminated.
B
10.2.1 Arrow to the right (pos. 2)
Press the button to move to the next menu in the menu
structure. If you press when the Settings menu is
highlighted, you go to the Status menu.
10.2.2 Help (pos. 3)
When the button is illuminated, a help text applying to the
D
current display will appear if the button is pressed.
Close the text by pressing the button.
10.2.3 Up and down (pos. 4 and 5)
Settings: Change of settings (password option) Use the button to go one display back in the menu.
If a value has been changed and the button is pressed, the
10.1.2 Top line new value will not be saved. For further information, see section
The top line (B) is illustrated in fig. 5. 10.2.7 Ok (pos. 10).
The top line shows If the button is pressed before the button, the new
value will be saved. For further information, see section
• the display number and title (left side)
10.2.7 Ok (pos. 10).
• the selected menu (left side)
10.2.6 Home (pos. 9)
• the symbol in case of alarm (right side)
• the symbol if the service language has been selected Press the button to return to the Status menu.
(right side). 10.2.7 Ok (pos. 10)
10.1.3 Graphical illustration Use the button as an enter button.
The graphical illustration (D) may show a status, an indication or The button is also used to start the setting of a value.
other elements, depending on the position in the menu structure. If a value has been changed and the button is pressed, the
The illustration may show the entire system or part of it as well as new value will be activated.
various settings. 10.2.8 Indicator lights (pos. 11 and 12)
10.1.4 Scroll bar The control panel incorporates a green and red indicator light.
If the list of illustration elements exceeds the display, the symbols The green indicator light is on when the Control MPC is in
and will appear in the scroll bar to the right. Use the operation.
and buttons to move up and down in the list. The green indicator light is flashing if the Control MPC has been
10.1.5 Bottom line set to stop.
The red indicator light is on if there is an alarm or a warning.
The bottom line (C) shows the date and time.
The fault can be identified from the alarm list.
10.2.9 Contrast (pos. 13)
The contrast in the display can be changed by means of the
button:
1. Press .
2. Adjust the contrast with and .
10.2.10 Back light
If no button is touched for 15 minutes, the back light of the panel
will be dimmed, and the first display in the Status menu will
appear.
Press any button to re-activate the back light.
10
11. Functions
11.1 Tree of functions
Key to the four main menus, Status, Operation, Alarm and Settings
Status
The Status menu shows alarms and the status of system and pumps.
Note: No settings can be made in this menu.
Operation
In the Operation menu, the most basic parameters can be set, such as setpoint,
operating mode, control mode and individual pump control.
Alarm
The Alarm menu gives an overview of alarms and warnings.
Alarms and warnings can be reset in this menu.
Settings
In the Settings menu, it is possible to set various functions:
• Primary controller
Setting of alternative setpoints, external setpoint influence, primary sensor, clock
program, proportional pressure and S-system configuration.
• Pump cascade control
Setting of min. time between start/stop, max. number of starts/hour, number of
standby pumps, forced pump changeover, pump test run, pilot pump, pump stop
attempt, pump start and stop speed, min. performance and compensation for
pump start-up time.
• Secondary functions
Setting of stop function, soft pressure build-up, digital and analog inputs, digital
outputs, emergency run, min., max. and user-defined duty, pump curve data,
flow estimation, control source and fixed inlet pressure.
• Monitoring functions
Setting of dry-running protection, min. and max. pressure, external fault, limit 1
and 2 exceeded, pumps outside duty range and pressure relief.
• Functions, CU 351
Selection of service language, main language and units.
Setting of date and time, passwords, Ethernet connection, GENIbus number and
software status.
11
Continued from page 11 4. Settings
4.1 Primary controller
4.1.1 PI controller
4.1.2 Alternative setpoints
4.1.2.1 Alternative setpoints 2...7
4.1.3 External setpoint influence
4.1.3.1 Input value to be influenced by
4.1.3.2 Setting of influence function
4.1.4 Primary sensor
4.1.6 Clock program
4.1.7 Proportional pressure
4.1.8 S-system configuration
4.2 Pump cascade control
Min. time between start/stop
4.2.1
Max. number of starts/hour
4.2.3 Standby pumps
4.2.4 Forced pump changeover
4.2.5 Pump test run
4.2.6 Pilot pump
4.2.7 Pump stop attempt
4.2.8 Pump start and stop speed
4.2.9 Min. performance
4.2.10 Compensation for pump start-up time
4.3 Secondary functions
4.3.1 Stop function
4.3.1.1 Stop parameters
4.3.3 Soft pressure build-up
4.3.5 Emergency run
4.3.7 Digital inputs
Function, DI1..DI3 (CU 351), [10, 12, 14]
Function, DI1..DI9 (IO 351-41), [10...46]
Function, DI1..DI9 (IO 351-42), [10...46]
4.3.8 Analog inputs
Setting, analog input AI1..AI3 (CU 351), [51, 54, 57]
Function, AI1...AI3 (CU 351), [51, 54, 57]
12
11.2 Overview
13
Section Display and display number See page
11.7.41 Monitoring functions (4.4) 48
11.7.42 Dry-running protection (4.4.1) 49
11.7.43 Dry-running protection with pressure/level switch (4.4.1.1) 49
11.7.44 Dry-running protection with pressure transmitter (4.4.1.2) 50
11.7.45 Dry-running protection with level transmitter (4.4.1.3) 50
11.7.46 Min. pressure (4.4.2) 51
11.7.47 Max. pressure (4.4.3) 51
11.7.48 External fault (4.4.4) 52
11.7.49 Limit 1 and 2 exceeded (4.4.5 and 4.4.6) 52
11.7.51 Pressure relief (4.4.8) 54
11.7.52 Functions, CU 351 (4.5) 55
11.7.53 Display language (4.5.1) 55
11.7.54 Display units (4.5.2) 56
11.7.55 Date and time (4.5.3) 57
11.7.56 Passwords (4.5.4) 57
11.7.57 Ethernet (4.5.5) 58
11.7.58 GENIbus number (4.5.6) 58
11.7.59 Software status (4.5.9) 58
14
11.3 Description of functions To open a menu line, mark the line with or , and press
.
The description of functions is based on the four main menus of
the CU 351 control unit: Status, Operation, Alarm and Settings. The display makes it possible to open status displays showing
The functions apply to all control variants unless otherwise • current alarms
stated. • system status
• status of each pump.
11.4 Status (1)
11.4.1 Current alarms (3.1)
The first status display is shown below. This display is shown
when the Control MPC is switched on, and it appears when the
buttons of the control panel have not been touched for
15 minutes.
F
G
H
E A
Description
In this display, current unreset alarms and warnings are shown.
Fig. 6 Status
For further information, see sections 11.6.2 Current alarms (3.1)
Description and 11.6.3 Alarm log (3.2).
No settings can be made in this menu. 11.4.2 System (1.2)
The current value (process value, PV) of the control parameter,
usually the discharge pressure, is shown in the upper right corner
(G) together with the selected setpoint (SP) (H).
The upper half of the display (A) shows a graphic illustration of
the pump system. The selected measuring parameters are shown
with sensor symbol and current value.
In the middle of the display, an information field (I) will be shown if
any of the following events occur
• limited operation due to standby pump
• proportional pressure influence active
• external setpoint influence active
• alternative setpoint active
15
11.4.3 Operating mode (1.2.1) 11.4.4 Setpoint (1.2.2)
Description Description
Here the operating mode of the system is shown as well as from This display shows the selected setpoint and whether it comes
where the Control MPC is controlled. from the CU 351 or an external bus.
Operating modes The display also shows all seven possible setpoints from CU 351
(for closed- and open-loop control). At the same time, the
Control MPC has six operating modes:
selected setpoint is shown.
1. Normal
The pumps adapt their performance to the requirement. As it is a status display, no settings can be made.
16
11.4.6 Measured values (1.2.4) 11.4.8 Pump 1...6 (1.3 to 1.8)
Description Description
This display gives a general status of all measured and calculated This display shows the operational state of the individual pumps.
parameters. The pumps may have different operating modes:
The lines "Power consumption" and "Energy • Auto
Note consumption" are only shown in Control MPC-E Together with the other pumps in automatic operation, the
systems. pump is controlled by the PI controller which ensures that the
system delivers the required performance.
11.4.7 Analog inputs (1.2.5)
• Manual
The pump is not controlled by the PI controller. In manual
operation, the pump has one of the following operating modes:
– Max.
The pump runs at a set maximum speed. (This operating
mode can only be selected for variable-speed pumps.)
– Normal
The pump runs at a set speed.
– Min.
The pump runs at a set minimum speed. (This operating
mode can only be selected for variable-speed pumps.)
– Stop
The pump has been forced to stop.
TM03 8949 4807
17
11.5 Operation (2) 11.5.2 System operating mode (2.1.1)
In this menu, the most basic parameters can be set, such as
setpoint, operating mode, control mode and forced control of
pumps.
11.5.1 Operation (2)
Description
Control MPC can be set to six different operating modes. Normal
is the typical setting. See section 11.4.3 Operating mode (1.2.1).
Fig. 15 Operation The performance of the operating modes Max., Min., User-
defined and Emergency run can be set in the Settings menu.
Description
In the display shown, it is possible to go directly to the Settings
The column shows the setting range. In closed-loop control, it
menu in order to set the pump performance or the setpoint.
corresponds to the range of the primary sensor, here 0-16 bar.
In open-loop control, the setting range is 0-100 %. Setting range
At the left hand of the column, the selected setpoint 1 (A) is It is possible to select the operating modes Normal, Max., Min.,
shown, i.e. the value set in the display. At the right hand of the User-defined, Stop and Emergency run.
column, the current setpoint (B) is shown, i.e. the setpoint acting Setting via control panel
as reference for the PI controller. If no kind of external setpoint
1. Mark the Operation menu with .
influence has been selected, the two values will be identical. The
current measured value (discharge pressure) is shown as the 2. Mark Further settings with or , and press .
grey part of the column (C). See sections 11.7.5 External setpoint 3. Mark System operating mode with or , and press
influence (4.1.3) and 11.7.6 Setting of influence function (4.1.3.2). .
Below the display is a menu line for setting of setpoint 1 and 4. Select the desired operating mode by marking one of the lines
selection of operating mode, including the operating modes with check boxes with or , and press .
Normal and Stop. It is possible to select further settings: system 5. In order to set the performance in min., max., user-defined
operating mode, control mode, setpoints for closed and open loop duty or emergency run, mark the desired line at the bottom of
as well as individual pump control. the display, and press .
Setting range See sections 11.7.33 Min., max. and user-defined duty
(4.3.14) and 11.7.25 Emergency run (4.3.5).
Setpoint:
Factory setting
Closed-loop control: Measuring range of the primary sensor
Normal.
Open-loop control: 0-100 %
Setting via control panel
Setpoint:
1. Mark the Operation menu with .
2. Mark Setpoint 1 with or . Set the value with or
.
3. Save with .
Operating mode:
1. Mark the Operation menu with .
2. Mark operating mode Normal or Stop with or .
Save with .
Further settings:
1. Mark the Operation menu with .
2. Mark Further settings with or , and press .
3. Select one of the settings below with or , and press
:
• System operating mode (see section 11.5.2).
• Control mode (see section 11.5.3).
• Setpoints (see section 11.5.4).
• Individual pump control (see section 11.5.6).
Factory setting
The setpoint is a value suitable for the system in question.
Thefactory setting may have been changed in the start-up menu.
18
11.5.3 Control mode (2.1.2) Open loop
In open-loop control, the pumps run at a fixed speed.
The pump speed is calculated from the performance set by the
user (0-100 %). The pump performance in percentage is
proportional with the flow rate.
Open-loop control is usually used when the system is controlled
by an external controller which controls the performance via an
external signal. The external controller could for instance be a
building management system connected to the Control MPC.
In such cases the Control MPC is like an actuator.
See figs 20 and 21.
Description
There are two control modes, namely closed and open loop.
Examples: Fig. 20 Booster system with external controller (open loop)
Closed loop
The typical control mode is closed loop where the built-in Flow rate [m3/h]
PI controller ensures that the system reaches and maintains the
selected setpoint. The performance is based on the setpoint set
for closed loop. See figs 18 and 19.
external controller
5
100
P [bar]
75
Flow rate
Pump 1
50 Pump 2
Setpoint Pump 3
Pump 4
TM03 2390 4105
25
TM03 9977 4807
Time [sec]
19
Setting via control panel
Flow rate [m3/h] To set an external control source to control the system, proceed
as follows:
100 1. Mark the Operation menu with .
2. Mark the operating mode Stop with or , and press
. The check mark in the right box shows that the
75 operation has been stopped.
Flow rate 3. Mark Further settings with or , and press .
Pump 1 4. Mark Control mode with or , and press .
50
Pump 2 5. Select Open loop with or , and press .
Pump 3 6. Return by pressing twice.
Pump 4
25 7. Mark Set setpoint 1, open loop with or .
8. Set the setpoint to 100 % with , and save with .
20
11.5.4 Setpoints (2.1.3) 11.5.5 Individual pump control (2.1.4)
Description Description
In addition to the primary setpoint 1 (shown in the display 2 in the It is possible to change the operating mode from automatic
Operation menu), six alternative setpoints can be set for closed- operation to one of the manual operating modes.
loop control. It is furthermore possible to set seven setpoints for Auto
open-loop control. The pumps are controlled by the PI controller, ensuring that the
As described in sections 11.7.3 Alternative setpoints (4.1.2) and system delivers the required performance.
11.7.4 Alternative setpoints 2 to 7 (4.1.2.1 to 4.1.2.7), it is
Manual
possible to activate one of the alternative setpoints by means of
The pump is not controlled by the PI controller, but set to one of
external contacts.
the following manual operating modes:
Setting range
• Max.
The setting range of setpoints for closed-loop control depends on The pump runs at a set maximum speed. (This operating
the range of the primary sensor. See section 11.7.7 Primary mode can only be selected for variable-speed pumps.)
sensor (4.1.4).
• Normal
In open loop control, the setting range is 0-100 %. The pump runs at a set speed.
Setting via control panel • Min.
1. Mark the Operation menu with . The pump runs at a set minimum speed. (This operating mode
can only be selected for variable-speed pumps.)
2. Mark Further settings with or , and press .
• Stop
3. Mark Setpoints with or , and press .
The pump has been forced to stop.
4. Select the setpoint with or .
Pumps in manual operation are not part of the normal pump
5. Set the setpoint with or , and press .
cascade and speed control. The manual pumps are a
Factory setting "disturbance" of the normal operation of Control MPC.
Setpoint 1 for closed-loop control is a value suitable for the If one or more pumps are in manual operation, the system may
Control MPC in question. not be able to deliver the set performance.
The alternative setpoints for closed-loop control are 3 bar. There are two displays for the function. In the first display, the
All setpoints for open-loop control are 70 %. pump to be set is selected, and in the next display, the operating
mode is selected.
Setting range
All pumps can be selected.
Setting via control panel
1. Mark the Operation menu with .
2. Mark Further settings with or , and press .
3. Mark Individual pump control with or , and press
.
4. Select the pump with or , and press .
21
11.5.6 Setting of individual operating mode (2.1.4.1 to 2.1.4.6)
Description
This display is shown for the individual pumps and makes it
possible to set an operating mode.
Setting range
It is possible to select Auto or Manual as well as the operating
mode of the pump for manual operation - Max., Normal, Min. or
Stop. For mains-operated pumps only Normal or Stop can be
selected.
Setting via control panel
1. Mark the Operation menu with .
2. Mark Individual pump control with or , and press
.
3. Select the pump with or , and press .
4. Mark Auto or Manual with or , and press .
5. Manual: Select the operating mode with or , and
press .
6. Normal: Mark Setpoint with or .
Set the speed of the variable-speed pump with or ,
and press .
Factory setting
Auto.
22
11.6 Alarm (3)
)
The Alarm menu gives an overview of alarms and warnings.
Change of operating
) / alarm(
In this menu, it is possible to reset alarms and to see the alarm
Reset of alarm
11.6.1 Alarm status (3) Fault
Alarm code
Warning(
mode to
Restart
menu
Water shortage Man/auto X 206
Man/auto
Pressure low X 211
Stop Man/auto
Man/auto
External fault X 3
Fig. 28 Alarm status Stop Man/auto
Dissimilar sensor
Description Auto 204
signals
A fault in the system or one of the components monitored can
cause an alarm or a warning . Besides the fault signal via Fault, primary sensor Stop Auto 89
the alarm/warning signal relay and the red indicator light on the
CU 351, an alarm can also cause a change of operating mode, Fault, sensor Auto 88
for instance from Normal to Stop. A warning only causes a fault Communication fault Auto 10
indication.
The table shows the possible causes of fault together with an Phase failure Auto 2
alarm code number, and whether they result in an alarm or a
7, 40,
warning. It also shows to what operating mode the system Undervoltage, pump Auto
42, 73
changes in case of alarm, and whether restart of the system and
reset of the alarm is manual or automatic. Overvoltage, pump Auto 32
The table also shows that the reaction to some of the fault causes 48, 50,
mentioned can be set in the Settings menu. See sections Overload, pump Auto
51, 54
11.7.24 Soft pressure build-up (4.3.3) and 11.7.41 Monitoring
functions (4.4) to 11.7.51 Pressure relief (4.4.8). Motor temperature too 64, 65,
Auto
high 67, 70
Other fault, pump Auto 76, 83
83,
Internal fault, CU 351 Auto
157
72, 83,
Internal fault, IO 351 Stop Auto
157
VFD not ready Auto 213
231,
Fault, Ethernet Auto
232
Limit 1 exceeded Man/auto X 190
23
11.6.2 Current alarms (3.1) 11.6.3 Alarm log (3.2)
The alarm log can store up to 24 warnings and alarms.
24
11.7 Settings (4) 11.7.1 Primary controller (4.1)
25
11.7.2 PI controller (4.1.1) PI controller settings for heating and cooling
If another application than pressure boosting has been selected
in the start-up wizard, the values of Kp and Ti will be set
automatically according to the table below. As Control MPC does
not know the pipe length, the default parameters will be set
according to the table to a pipe length (L1 or L2) of 5 metres.
Kp
Ti
System/application Heating Cooling [Seconds]
system 1) system 2)
0.5 1
L1 < 5 m: 1
L 1 [m]
Fig. 33 PI controller 0.5 L1 > 5 m: 3
L1 > 10 m: 5
ǻS
Description
Control MPC includes a standard PI controller which ensures that
the pressure is stable and corresponds to the setpoint.
It is possible to adjust the PI controller if a faster or slower
reaction to changes of consumption is required. 0.5 1
Q
A faster reaction is obtained if Kp is increased and Ti is reduced.
A slower reaction is obtained if Kp is reduced and Ti is increased.
Setting range
• Gain Kp: –30 to 30.
0.5 -0.5 10 + 5L2
Note: For inverse control, set Kp to a negative value. t
26
11.7.3 Alternative setpoints (4.1.2) 11.7.4 Alternative setpoints 2 to 7 (4.1.2.1 to 4.1.2.7)
Description For each alternative setpoint, select the digital input to activate
This function makes it possible to select up to six setpoints (No 2 the setpoint.
to 7) as alternatives to the primary setpoint (No 1). The primary It is possible to set a setpoint for closed loop and for open loop.
setpoint (No 1) is set in the Operation menu.
Setting via control panel
Every alternative setpoint can be addressed manually to a
separate digital input (DI). When the contact of the input is 1. Mark the Settings menu with .
closed, the alternative setpoint applies. 2. Mark Primary controller with or , and press .
If more than one alternative setpoint has been selected and they 3. Mark Alternative setpoints with or , and press .
are activated at the same time, the CU 351 selects the setpoint 4. Select the alternative setpoint with or , and press
with the lowest number. .
Setting range 5. Mark Go to setting of digital input with or , and
press .
• Six setpoints, No 2 to 7.
Now the display Digital inputs (4.3.7) appears. Set the input
Factory setting and return with .
No alternative setpoints have been selected. 6. Mark the menu line of the setpoint (closed or open loop) with
or .
7. Set the required setpoint with or , and save with .
Set both setpoints if the system is to be controlled both in
open and closed loop.
Factory setting
No alternative setpoints have been set.
27
11.7.5 External setpoint influence (4.1.3) Setting via control panel
1. Mark the Settings menu with .
2. Mark Primary controller with or , and press .
3. Mark External setpoint influence with or , and press
.
4. Mark Input value to be influenced by with or , and
press .
Now a list of available parameters appear.
5. Mark the parameter which is to influence the setpoint with
or , and press .
6. Return with .
7. Mark Set the influence function with or , and press
. For details, see section 11.7.6 Setting of influence
28
11.7.6 Setting of influence function (4.1.3.2) Setting via control panel
1. Mark the Settings menu with .
2. Mark Primary controller with or , and press .
3. Mark External setpoint influence with or , and press
.
4. Mark Set the influence function with or , and press
.
5. Mark the menu line for number of points with or , and
press .
6. Select the required number of points with or , and
save with .
7. Mark External input value (point 1) with or .
8. Set the value of the external input value with or , and
100
25 Description
TM03 9978 4707
In this display, select the control parameter of the system and set
the sensor to measure the value.
0 10 100 140
For booster systems, the control parameter is usually the
Temperature [°C]
discharge pressure which is measured by a sensor fitted on the
Fig. 38 Relation between setpoint influence and flow rate discharge manifold. In heating and cooling systems, the control
parameter is typically a differential pressure or a temperature.
The control unit draws straight lines between the points. A See section 12. Measuring parameters.
horizontal line is drawn from the minimum value of the relevant
Setting range
sensor (0 m3/h in the example) to the first point. This is also the
case from the last point to the sensor's maximum value (example • Discharge pressure
50 m3/h). • Differential pressure, external
Setting range • Differential pressure, pump
Two to eight points can be selected. Each point contains the • Series 2000, differential pressure
relation between the value of the parameter which is to influence • External pressure
the setpoint and the influence of the value. • Differential pressure, inlet
• Differential pressure, outlet
• Flow rate
• Series 2000, flow rate
• Flow pipe temperature
• Return pipe temperature
• Differential temperature
• Ambient temperature
• Return pipe temperature, external
• 0-100 % signal
• Not used.
29
Setting via control panel Setting range
1. Mark the Settings menu with . • Activation of the function.
2. Mark Primary controller with or , and press . • Activation and setting of event.
3. Mark Primary sensor with or , and press . Setting via control panel
4. Mark Go to setting of analog input with or , and 1. Mark the Settings menu with .
press .
2. Mark Primary controller with or , and press .
Now the display Analog inputs (4.3.8) appears. Select the
3. Mark Clock program with or , and press .
analog input (AI) for the primary sensor, and set the
parameters for this sensor. Return to display Primary sensor 4. Mark Event 1 with or , and press .
(4.1.4) with .
5. Select the control parameter for the primary sensor with
or , and press .
Factory setting
The primary parameter is discharge pressure. The sensor is
connected to AI1 (CU 351). Other primary parameters can be
selected in the start-up wizard.
11.7.8 Clock program (4.1.6)
30
11.7.9 Proportional pressure (4.1.7) 11.7.10 S-system configuration (4.1.8)
Description Description
The function can only be activated in pressure-controlled systems The function makes it possible to invert the control of mains-
and automatically adapts the setpoint set to the current flow rate. operated pumps (Control MPC-S). That is to set whether pumps
The adaptation can be linear or square. See fig. 43. are to be started or stopped depending on the current value.
A start/stop band must be set in order to use this function.
Pump curve See fig. 45.
Setpoint Normal control: A pump is stopped when the current value
Resultant setpoint, linear becomes higher than Hset + start/stop band. And a pump is
Resultant setpoint, square started when the current value becomes lower than Hset.
See fig. 45.
Inverse control: A pump is started when the current value
Hset becomes higher than Hset + start/stop band. And a pump is
stopped when the current value becomes lower than Hset.
See fig. 45.
TM03 8524 1807
31
11.7.11 Pump cascade control (4.2) Factory setting
The setting is done in the start-up wizard and depends on the
application.
11.7.13 Max. number of starts/hour (4.2.1)
Factory setting
32
11.7.14 Standby pumps (4.2.3) 11.7.15 Forced pump changeover (4.2.4)
Description Description
This function makes it possible to limit the maximum performance This function ensures that the pumps run for the same number of
of the system, by selecting one or more pumps as standby operating hours.
pumps. In certain applications, the requirement remains constant for long
If a three-pump system has one standby pump, maximum two periods and does not require all pumps to run. In such situations,
pumps are allowed to be in operation at a time. pump changeover does not take place naturally, and forced pump
If one of the two pumps in operation has a fault and is stopped, changeover may thus be required.
the standby pump will be started. The performance of the system Once every 24 hours, the CU 351 checks if any pump running has
is thus not reduced. a larger number of operating hours than pumps that are stopped.
The status as standby pump alternates between all pumps. If this is the case, the pump will be stopped and replaced by a
pump with a lower number of operating hours.
Setting range
The number of possible standby pumps in a system is equal to Setting range
the total number of pumps in the system minus 1. The function can be activated/deactivated. The hour of the day at
which the changeover is to take place can be set.
Setting via control panel
1. Mark the Settings menu with . Setting via control panel
2. Mark Pump cascade control with or , and press 1. Mark the Settings menu with .
. 2. Mark Pump cascade control with or , and press
.
3. Mark Standby pumps with or , and press .
3. Mark Forced pump changeover with or , and press
4. Select the number of standby pumps with or , and
.
save with .
4. Mark Activated with or , and press . The check
Factory setting
mark in the right box shows that the function has been
The number of standby pumps is set to 0, i.e. function is activated.
deactivated.
5. Mark Time for changeover with , and press .
6. Set the time with or , and save with .
Factory setting
The function is activated. The time is set to 03:00.
33
11.7.16 Pump test run (4.2.5) 11.7.17 Pilot pump (4.2.6)
Description Description
This function is primarily used in situations where the forced The function controls a pilot pump via a digital output. The pilot
pump takes over the operation from the main pumps in periods
pump changeover is deactivated, and/or if the Control MPC is set
when the consumption is so small that the stop function of the
to operating mode Stop, for instance in a period when the system
is not needed. main pumps is activated. See section 11.7.23 Stop function
(4.3.1).
In such situations, it is important to test the pumps regularly.
Via a digital input, the operational state of the pilot pump is
The function ensures that
monitored, i.e. whether it is operational or in a fault condition.
• pumps do not seize up during a long standstill due to deposits
The purpose is to
from the pumped liquid.
• save energy
• the pumped liquid does not decay in the pump.
• reduce the number of operating hours of the main pumps.
• trapped air is removed from the pump.
If the pilot pump cannot keep the pressure by itself, one or more
The pumps start automatically one by one and run for five
seconds. main pumps are started. If only one main pump is started and
runs on/off operation, the pilot pump remains cut in. If one or
Pumps in the operating mode Manual are not more main pumps run continuously, the pilot pump is cut out.
included in the test run. If there is an alarm, the
Note Set the setpoint of the pilot pump to this value:
test run will not be carried out.
Hset + 1/2 on/off band + 8 metres.
Pilot pumps are included in the pump test run. Note
If the setpoint of the main pumps is changed, the
Setting range setpoint of the pilot pump must be changed too.
• Not used.
Setting range
• Once every 24 hours. • See section 11.7.31 Digital outputs (4.3.9).
• Once every 48 hours. • See section 11.7.26 Digital inputs (4.3.7).
• Once a week.
Setting via control panel
Setting via control panel
1. Mark the Settings menu with .
1. Mark the Settings menu with .
2. Mark Pump cascade control with or , and press
2. Mark Pump cascade control with or , and press .
. 3. Mark Pilot pump with or , and press .
3. Mark Pump test run with or , and press . 4. Mark Go to setting of digital output with or , and
4. Select the interval with or . press .
5. Activate the function with . 5. Select a digital output with or , and press .
Factory setting 6. Mark Pilot pump control with or , and save with
The setting is done in the start-up wizard and depends on the .
application. 7. Return by pressing twice.
8. Mark Go to setting of digital input with or , and
press .
9. Select a digital input or , and press .
10. Mark Pilot pump fault with or , and save with .
Factory setting
The function is deactivated.
34
11.7.18 Pump stop attempt (4.2.7) 11.7.19 Pump start and stop speed (4.2.8)
Description
The function controls the starting and stopping of pumps.
There are two options:
1. Use calculated speed
This function ensures that the optimum number of pumps is
always running at a desired duty point, in terms of energy
consumption. The CU 351 calculates the required number of
pumps and their speed. This requires that the differential
pressure of the pump is measured by a differential pressure
sensor or separate pressure sensors on the inlet and
discharge side.
When calculated speed has been selected, the CU 351
ignores the percentages set.
Description
The function makes it possible to set automatic stop attempts of a
pump when several pumps are running. It ensures that the
optimum number of pumps is always running, in terms of energy
consumption. See 11.7.19 Pump start and stop speed (4.2.8). At
the same time, the purpose is to avoid disturbances in connection
with automatic stop of pumps.
Stop attempts can either take place with a fixed interval set under
Interval between stop attempts or by self learning. If self
learning is selected, the interval between stop attempts will be
increased if repeated attempts to stop the pump fail.
Factory setting
2. Use fixed speed
The function is activated, and self learning is selected.
TM03 8965 4807
35
Setting via control panel 11.7.21 Compensation for pump start-up time (4.2.10)
1. Mark the Settings menu with .
2. Mark Pump cascade control with or , and press
.
3. Mark Pump start and stop speed with or , and press
.
4. Mark Use fixed speed with or , and press .
5. Mark Start of next pump at: 1->2 with or , and press
.
6. Set the speed as percentage with or , and save with
. Set the other pumps in the same way.
7. Mark Instant pump stop at: 1->0 with or , and press
.
Description
The function is used for Control MPC-F systems only.
The purpose is to avoid disturbances when a mains-operated
pump with fixed speed is started. The function compensates for
the time it takes a mains-operated pump to reach its full
performance after start. The start-up time of the mains-operated
pump must be known.
Setting via control panel
1. Mark the Settings menu with .
2. Mark Pump cascade control with or , and press
.
3. Mark Compensation for pump start-up time with or
TM03 8967 4807
, and press .
4. Set the start-up time with or , and save with .
Factory setting
The start-up time is set to 0 seconds.
Fig. 56 Min. performance
Description
This function ensures circulation in a system. Note that the stop
function, if activated, can influence this function. See section
11.7.23 Stop function (4.3.1). Examples:
• If 0 pumps have been selected, the stop function can stop the
pump if there is no or a very small consumption.
• If pumps have been selected, the stop function is not active.
Setting via control panel
1. Mark the Settings menu with .
2. Mark Pump cascade control with or , and press
.
3. Mark Min. performance with or , and press .
4. Set Number of pumps with or , and save with .
5. Mark Speed with or . Set the speed with or ,
and save with .
Factory setting
The number of pumps is set to 0. The speed in closed loop is set
to 25 %.
36
11.7.22 Secondary functions (4.3)
H
The flow rate is estimated by the CU 351 when the pump is in the
stop period. As long as the flow rate is lower than Qmin, the pump
will run on/off. If the flow rate is increased to above Qmin, the
pump returns to normal operation, Hset. Hset is equal to the
current setpoint. See section 11.4.4 Setpoint (1.2.2).
Detection of low flow rate
Low flow rate can be detected by means of
• direct flow measurement with a flowmeter or flow switch
TM03 2355 4607
37
Diaphragm tank size 8. Select one of the stop parameters with or , and save
with . If Customised settings are selected, the
Recommended diaphragm tank size [litres] parameters shown in fig. 63 must be set. See examples
Pump type below.
-E -F -S
CRI(E) 3 8 8 80
CRI(E) 5 12 12 120
CRI(E) 10 18 18 180
CRI(E) 15 80 80 300
CRI(E) 20 80 80 400
CR(E) 32 80 80 600
CR(E) 45 120 120 800
CR(E) 64 120 120 1000
CR(E) 90 180 180 1500
CR(E) 120 180 180 1500
CR(E) 150 180 180 1500
38
System with flow switch
Make the following additional settings: H [m] 1. Filling phase 2. Pressure build-up phase
1. Mark Go to setting of digital input with or , and
press . Now the display Digital inputs (4.3.7) appears.
2. Select the digital input where the flow switch is connected with
or , and press .
3. Mark Flow switch with or , press and return with
.
39
11.7.25 Emergency run (4.3.5) 11.7.26 Digital inputs (4.3.7)
Description Description
This function is used in booster applications. When this function In this menu, the digital inputs of the CU 351 can be set. Each
has been activated, the pumps will keep running regardless of input, except DI1, can be activated and related to a certain
warnings or alarms. The pumps will run according to a setpoint function.
set specifically for this function. As standard, the Control MPC has three digital inputs. If the
Control MPC incorporates an IO 351B module (option), the
In case of sensor fault, both main and standby
Caution number of digital inputs is 12.
pumps will run at 100 % speed!
In the display, all digital inputs are shown so that their physical
Setting range position in the Control MPC can be identified.
• Setting of digital input (11.7.26 Digital inputs (4.3.7)).
Example
• Setting of digital output (11.7.31 Digital outputs (4.3.9)).
DI1 (IO 351-41), [10]:
• Setting of setpoint for emergency run.
Setting via control panel DI1: Digital input No 1
1. Mark the Settings menu with (IO 351-41): IO 351, GENIbus number 41
3. Mark Emergency run with or , and press . For further information on the connection of various digital inputs,
4. Mark Go to setting of digital input with or , and see the wiring diagram supplied with the control cabinet.
press . Setting range
5. Select a digital input with or , and press . The digital input to be set is selected in the display Digital inputs
6. Mark Emergency run with or , and save with . (4.3.7).
7. Return by pressing twice.
Note DI1 (CU 351) cannot be selected.
8. Mark Go to setting of digital output with or , and
press . Setting via control panel
9. Select a digital output with or , and press . 1. Mark the Settings menu with .
10. Mark Emergency run with or , and save with . 2. Mark Secondary functions with or , and press .
11. Return by pressing twice. 3. Mark Digital inputs or , and press .
12. Mark Setpoint, emergency run with or . 4. Select the digital input with or , and press .
13. Set the value with or , and save with .
40
11.7.27 Functions of digital inputs (4.3.7.1) Factory setting
Description
In the displays 4.3.7.1, a function can be related to the digital
inputs.
Setting range
It is possible to select one function in each display:
Not used
41
11.7.29 Analog inputs (4.3.8.1 to 4.3.8.7) 11.7.30 Analog inputs and measured value (4.3.8.1.1 to
4.3.8.7.1)
42
11.7.31 Digital outputs (4.3.9) 11.7.32 Functions of digital outputs (4.3.9.1 to 4.3.9.16)
Description Description
In this display, the digital relay outputs of the Control MPC can be In the displays Functions of digital outputs (4.3.9.1 to 4.3.9.16), a
set. Each output can be activated and related to a certain function can be related to the individual outputs.
function.
Setting range
As standard, the Control MPC has two digital outputs.
It is possible to select one function in each display:
If the Control MPC incorporates an IO 351B module (option), the
• No function
number of digital outputs is 9.
• Operation, system
In the display, all digital outputs are shown so that their physical
position in the Control MPC can be identified. • Alarm, system
• Warning, system
Example
• Ready, system
DO1 (IO 351-41) [71]:
• Water shortage
DO1 Digital output No 1 • Min. pressure
(IO 351-41) IO 351B, GENIbus number 41 • Max. pressure
[71] Terminal No 71 • Emergency run
For further information on the connection of various digital • Pilot pump control
outputs, see the wiring diagram supplied with the CU 351. • Pressure relief valve
Setting range • Operation, pump 1 to 6
In the display Digital outputs (4.3.9), the digital output to be used • Alarm, pump 1 to 6
is selected. • Alarm, limit 1 exceeded
• Warning, limit 1 exceeded
• Alarm, limit 2 exceeded
• Warning, limit 2 exceeded.
Setting via control panel
1. Mark the Settings menu with .
2. Mark Secondary functions with or , and press .
3. Mark Digital outputs with or , and press .
4. Select the digital output with or , and press .
5. Mark the desired function with or , and activate it with
.
The activation is indicated by a check mark in the box.
Factory setting
43
11.7.33 Min., max. and user-defined duty (4.3.14) 11.7.34 Min. duty (4.3.14.1)
Description Description
This function makes it possible to let the pumps run in open loop In all systems, apart from Control MPC-S, minimum duty is only
at a set pump performance. possible for variable-speed pumps. In Control MPC-S systems,
only the number of pumps running at 100 % speed can be set.
Setting range
The CU 351 makes it possible to change between three operating Setting range
modes: • Number of pumps in operation.
1. Min. duty (4.3.14.1). • Speed as percentage (25 to 100 %) for variable-speed pumps.
2. Max. duty (4.3.14.2). Setting via control panel
3. User-defined duty (4.3.14.3). 1. Mark the Settings menu with .
For each of these modes, the number of 2. Mark Secondary functions with or , and press .
Note operating pumps and the pump performance 3. Mark Min., max. and user-defined duty with or , and
(speed) can be set. press .
4. Mark Min. duty with or , and press .
5. Mark Number of pumps in operation, min. duty with or
.
6. Set the number with or , and save with .
7. Mark Speed with or .
8. Set the value with or , and save with .
Factory setting
44
11.7.35 Max. duty (4.3.14.2) 11.7.36 User-defined duty (4.3.14.3)
Description Description
The function makes it possible for a set number of pumps to run In this display, it is possible to set a user-defined performance,
at maximum performance when the function is activated. typically a performance between min. and max. duty.
Setting range The function makes it possible to set a pump performance by
selecting the number of pumps to run and the speed of variable-
In this display, the number of pumps to run in the operating mode
Max. can be set. All pumps run at 100 % speed. speed pumps.
This function primarily selects the variable-speed pumps. If the
Setting via control panel number of selected pumps exceeds the number of variable-speed
1. Mark the Settings menu with . pumps, mains-operated pumps are started too.
2. Mark Secondary functions with or , and press . Setting range
3. Mark Min., max. and user-defined duty with or , and • Number of pumps in operation.
press .
• Speed as percentage for variable-speed pumps.
4. Mark Max. duty with or , and press .
Note: In Control MPC systems with only variable-speed
5. Mark Number of pumps in operation at 100 % speed, max. pumps, the speed can be set between 25 and 100 %; in
duty with or . systems with both variable-speed pumps and mains-operated
6. Set the number with or , and save with . pumps the speed can be set between 70 and 100 %.
Factory setting Setting via control panel
1. Mark the Settings menu with .
Number of pumps in operation All pumps (except standby
during max. duty: pumps) 2. Mark Secondary functions with or , and press .
3. Mark Min., max. and user-defined duty with or , and
press .
4. Mark User-defined duty with or , and press .
5. Mark Number of pumps in operation, user-defined duty
with or .
6. Set the number with or , and save with .
7. Mark Speed with or .
8. Set the value with or , and save with .
Factory setting
The function is not activated, as the following has been set:
45
a
Hmax
Hnom
TM03 9996 4807
46
Setting via control panel 11.7.39 Fixed inlet pressure (4.3.22)
1. Mark the Settings menu with .
2. Mark Secondary functions with or , and press .
3. Mark Pump curve data with or , and press .
4. Mark Nominal flow rate Qnom with or .
5. Set the value with or , and save with .
6. Mark Nominal head Hnom with or .
7. Set the value with or , and save with .
8. Mark Max. head Hmax with or .
9. Set the value with or , and save with .
10. Mark Max. flow rate Qmax with or .
11. Set the value with or , and save with .
Description
Control MPC can be remote-controlled via an external bus
connection (option). See section 11.8.2 GENIbus. Control can
also take place via the bus connection. For further information,
see section 11.8 Data communication.
In this display, the control source, CU 351 or the external bus
connection, is selected.
Setting via control panel
1. Mark the Settings menu with .
2. Mark Secondary functions with or , and press .
3. Mark Control source with or , and press .
4. Select the desired control source with or , and save
with .
Factory setting
The control source is CU 351.
47
11.7.40 Flow estimation (4.3.23) 11.7.41 Monitoring functions (4.4)
Description Description
As described in section 11.7.37 Pump curve data (4.3.19), the Control MPC has a series of functions that constantly monitor the
CU 351 can optimise operation according to performance curves operation of the system.
and motor data. In this display, curve types are selected which The primary purpose of the monitoring functions is to ensure that
the CU 351 will use for the optimisation if they are available. faults do not damage pumps or the system.
At large flow rates, there may be a considerable head loss Setting range
between the pump discharge flange and the pressure sensor. The
The following functions can be selected:
loss is caused by non-return valves and pipe bends. To improve
the flow estimation of the system, it is necessary to compensate • Dry-running protection (4.4.1)
for the difference between the measured and the actual • Min. pressure (4.4.2)
differential pressure across the pump. This is done by entering • Max. pressure (4.4.3)
the head loss in non-return valves and pipe bends at the rated • External fault (4.4.4)
flow rate of one pump.
• Limit 1 and 2 exceeded (4.4.5 and 4.4.6)
Setting range • Pumps outside duty range (4.4.7)
• 2nd order QH polynomial • Pressure relief (4.4.8).
• 5th order QH polynomial
Setting via control panel
• Power polynomial, QP
1. Mark the Settings menu with .
• Head loss.
2. Mark Monitoring functions with or , and press .
It is possible to select several curve types, as the 3. Select the function with or , and press .
Note CU 351 makes a priority based on the data
available.
Setting via control panel
1. Mark the Settings menu with .
2. Mark Secondary functions with or , and press .
3. Mark Flow estimation with or , and press .
4. Select the curve type by marking one of the lines at the
selection box with or , and press .
Factory setting
All polynomials are selected.
48
11.7.42 Dry-running protection (4.4.1) 11.7.43 Dry-running protection with pressure/level switch
(4.4.1.1)
2. Mark Monitoring functions with or , and press . 4. Mark Pressure/level switch with or , and press .
3. Mark Dry-running protection with or , and press 5. Mark Go to setting of digital input, and press . Now the
display Digital inputs (4.3.7) appears. Set the input to dry-
.
running protection. Return with .
4. Select the method with or , and press .
6. Mark Warning or Alarm + stop with or , and save
with .
7. Mark Manual or Auto with or , and save with .
Factory setting
The setting is done in the start-up wizard and depends on the
application.
49
11.7.44 Dry-running protection with pressure transmitter 11.7.45 Dry-running protection with level transmitter (4.4.1.3)
(4.4.1.2)
50
11.7.46 Min. pressure (4.4.2) 11.7.47 Max. pressure (4.4.3)
Description Description
The discharge pressure is monitored if the application is pressure The discharge pressure is monitored if the application is pressure
boosting. In all other applications, the system pressure is boosting. In all other applications, the system pressure is
monitored. The CU 351 will react if the pressure becomes lower monitored. The CU 351 will react if the pressure becomes higher
than a set minimum level for an adjustable time. than a set maximum level.
The minimum pressure can be monitored if a fault indication is In certain installations, a too high discharge pressure may cause
required in situations where the discharge pressure becomes damage. It may therefore be necessary to stop all pumps for a
lower than the set minimum pressure. short period if the pressure is too high.
It is possible to set whether the indication is to be just a warning It is possible to set whether the Control MPC is to restart
or an alarm stopping the pumps. This may be desirable if Control automatically after the pressure has dropped below the maximum
MPC is used for an irrigation system where a very low discharge level, or if the system must be reset manually. Restart will be
pressure may be due to pipe fracture and thus an extraordinarily delayed by an adjustable time. See section 11.7.12 Min. time
high consumption and a very low counter-pressure. In such between start/stop (4.2.1).
situations, it is desirable that the system stops and indicates
Setting range
alarm. This situation will require a manual reset of alarms.
• Activation of the function.
It is possible to set a start-up delay ensuring that the system can
• Maximum pressure level within the range of the primary
build up pressure before the function is activated. It is also
possible to set a time delay, i.e. for how long time the discharge sensor.
pressure may be lower than the set minimum pressure before the • Manual or automatic restart after fault.
alarm is activated. Setting via control panel
Setting range 1. Mark the Settings menu with .
• Activation of the function. 2. Mark Monitoring functions with or , and press .
• Minimum pressure level within the range of the primary 3. Mark Max. pressure with or , and press .
sensor. 4. Mark Activated with or , and press to activate/
• Activation of stop when the pressure falls below the minimum deactivate the function.
pressure. 5. Mark Max. pressure with or . Set the pressure with
• Time delay at start-up. or , and save with .
• Time delay during operation. 6. Mark Manual or Auto with or . Activate the function
with .
Setting via control panel
1. Mark the Settings menu with . Factory setting
2. Mark Monitoring functions with or , and press . The function is deactivated.
3. Mark Min. pressure with or , and press .
4. Mark Activated with or , and press to activate/
deactivate the function.
5. Mark Min. pressure with or . Set the pressure with
or , and save with .
6. Mark Stop at min. pressure with or , and press
to activate/deactivate the function.
7. Mark Time delay of function at start-up with or .
Set the time with or , and save with .
8. Mark Time delay of function during operation with or
. Set the time with or , and save with .
Factory setting
The function is deactivated.
51
11.7.48 External fault (4.4.4) 11.7.49 Limit 1 and 2 exceeded (4.4.5 and 4.4.6)
52
10. Set the minimum sensor value with or , and save with 11.7.50 Pumps outside duty range (4.4.7)
.
11. Set the maximum sensor value with or , and save
with .
12. Return by pressing twice.
13. Mark Measured value to be monitored with or ., and
press . Select the input with or , and press .
14. Return with .
15. Mark Min. limit or Max. limit with or ., and press
.
16. Mark Set delays with or , and press
17. Mark Time delay of function at start-up with or .
Set the time with or , and save with .
53
11.7.51 Pressure relief (4.4.8) Setting via control panel
1. Mark the Settings menu with
2. Mark Monitoring functions with or , and press .
3. Mark Pressure relief with or , and press .
4. Mark Go to setting of digital output with or , and
press .
5. Select a digital output with or , and press .
6. Mark Pressure relief with or , and save with .
7. Return by pressing twice.
8. Mark Pressure to be monitored with or , and press
.
9. Mark Discharge pressure, System pressure or External
pressure with or , and save with .
1 2 3 4 5
Valve opening
pressure Band
TM03 9206 3607
Time [sec]
Valve opening pressure Warning
minus band delay
Fig. 97 Pressure relief
Setting range
• Setting of digital output.
• Setting of pressure to be monitored.
• Setting of valve opening pressure.
• Setting of band for valve opening pressure.
• Setting of warning or alarm.
• Activation of the function.
54
11.7.52 Functions, CU 351 (4.5) 11.7.53 Display language (4.5.1)
Description Description
In this submenu, it is possible to make the basic settings of the Here the language for the CU 351 display is selected.
CU 351.
Setting range
CU 351 comes with most of these settings, or they are made at
• British English
start-up and normally not to be changed.
• German
The service language, English, can be activated for service
• Danish
purposes. If no buttons are touched for 15 minutes, the display
will return to the language selected at start-up or to the language • Spanish
set in section 11.7.53 Display language (4.5.1). • Finnish
• French
If the service language is selected, the symbol
Note will be shown to the right of the top line of all • Greek
displays. • Italian
Setting range • Dutch
• Activation of service language, British English. • Polish
• Re-activation of start-up wizard. • Portuguese
(After start-up, the wizard is inactive.) • Russian
• Selection of display language. • Swedish
• Selection of display units. • Chinese
• Setting date and time. • Korean
• Selection of password for the menus Operation and Settings. • Japanese
• Setting of Ethernet communication. • Czech
• Setting of GENIbus number. • Turkish
• Reading of software status. Setting via control panel
1. Mark the Settings menu with .
2. Mark Functions, CU 351 with or , and press .
3. Mark Display language with or , and press .
4. Select language with or , and save with .
Factory setting
The display language is British English. It can be changed at
start-up.
55
11.7.54 Display units (4.5.2)
Basic setting
Parameter Possible units
SI US
kPa, MPa, mbar,
Pressure bar psi
bar, m, psi
kPa, MPa, mbar,
Differential pressure m psi
bar, m, psi
Head m ft m, cm, ft, in
Level m ft m, cm, ft, in
m3/s, m3/h, l/s, gpm,
Flow rate m3/h gpm
yd3/s, yd3/min, yd3/h
Volume m3 gal l, m3, gal, yd3
kWh/m3, Wh/gal,
Specific energy kWh/m3 Wh/gal Wh/kgal, BTU/gal,
HPh/gal
Temperature °C °F K, °C, °F
Differential temperature K K K
Power kW HP W, kW, MW, HP
kWh, MWh, BTU,
Energy kWh kWh
HPh
56
11.7.55 Date and time (4.5.3) 11.7.56 Passwords (4.5.4)
Description Description
In this display, date and time are set as well as how they are to be In this display, it is possible to limit the access to the Operation
shown in the display. and Settings menus by means of a password. If the access is
The clock has a built-in rechargeable voltage supply which can limited, it is not possible to view or set any parameters in the
supply the clock for up to 20 days if the voltage supply to the menus.
Control MPC is interrupted. The password must consist of four digits and may be used for
If the clock is without voltage for more than 20 days, it must be both menus.
set again.
If you have forgotten the password(s), contact
Setting range Note
Grundfos.
The date can be set as day, month and year. The time can be set Setting via control panel
as a 24-hour clock showing hours and minutes.
1. Mark the Settings menu with .
There are three formats.
2. Mark Functions, CU 351 with or , and press .
Examples of format 3. Mark Password with or , and press .
2005-09-27 13:49 4. Mark the password to be activated, and press .
27-09-2005 13:49 5. Mark Enter password, and press .
Now the first digit of the password is flashing.
9/27/2005 1:49pm
6. Select the digit with or , and save with .
It is also possible to select if Sunday or Monday is to be the first Now the second digit of the password is flashing.
day of week. 7. Repeat steps 4 to 6 if it is necessary to activate the other
Setting via control panel password.
1. Mark the Settings menu with . Factory setting
2. Mark Functions, CU 351 with or , and press . Both passwords are deactivated. If a password is activated, the
3. Mark Date and time with or , and press . factory setting will be "1234".
4. Mark Day, Month and Year with or , and set the date
with or . Save with .
5. Mark Hours and Minutes with or , and set the time
with or . Save with .
6. Select the format with or , and save with .
7. Mark First day of week, Sunday or Monday with or ,
and save with
Factory setting
Local time.
57
11.7.57 Ethernet (4.5.5) 11.7.59 Software status (4.5.9)
Description Description
The CU 351 is equipped with an Ethernet connection for This display shows the status of the software installed in the
communication with a computer, either directly or via Internet. CU 351. Furthermore, the version code and the product numbers
For further information, see section 11.8.1 Ethernet. of configuration files (GSC) read into the unit are shown.
11.7.58 GENIbus number (4.5.6) As it is a status display, no settings can be made.
TM03 2297 4807
Description
CU 351 can communicate with external units via an RS-485
interface (option). For further information, see fig. 107 and
section 11.8.2 GENIbus.
Communication is carried out according to the Grundfos bus
protocol, GENIbus, and enables connection to a building
management system or another external control system.
Operating parameters, such as setpoint and operating mode, can
be set via the bus signal. Furthermore, status about important
parameters, such as current value and input power, and fault
indications can be read from the CU 351.
Contact Grundfos for further information.
Setting range
The number can be set between 1 and 64.
Setting via control panel
1. Mark the Settings menu with .
2. Mark Functions, CU 351 with or , and press .
3. Mark GENIbus number with or , and press .
4. Select the number with or , and save with .
Factory setting
No number is set ("–").
58
11.8 Data communication
CU 351 is equipped with a hardware enabling communication
with external units, such as a computer, via an external GENIbus
or Ethernet connection.
Grundfos CIU
Third- communication
party interface Internet
gateway
Intranet
External
External GENIbus connection GENIbus module
(factory option)
Fig. 107 Data communication via external GENIbus and Ethernet connection
11.8.1 Ethernet
Ethernet is the most widely used standard for local networks Dynamic assignment of an IP address for the CU 351 requires a
(LAN). The standardisation of this technology has created some DHCP server in the network. The DHCP server assigns a number
of the easiest and cheapest ways of creating communication of IP addresses to the electrical units and makes sure that two
between electrical units, for instance between computers or units do not receive the same IP address.
between computers and control units. A traditional Internet browser is used for connection to the web
The web server of the CU 351 makes it possible to connect a server of the CU 351.
computer to the CU 351 via an Ethernet connection. The user If you want to use the factory-set IP address, no changes are
interface can thus be exported from the CU 351 to a computer so required in the display. Open the Internet browser and enter the
that the CU 351 and consequently the system can be monitored IP address of the CU 351.
and controlled externally.
In order to use dynamic assignment, the function must be
Grundfos recommends that you protect the activated. Click Use DHCP in the menu line. A check mark
connection to the CU 351 according to your next to the menu line shows that activation has been made.
Note After activation in the display, open the Internet and enter the
safety requirements in consultation with the
system administrator. host name of the CU 351 instead of the IP address. The Internet
browser will now try to connect to the CU 351. The host name can
In order to use the web server, you must know the IP address of
be read in the display, but can only be changed by either a GSC-
the CU 351. All network units must have a unique IP address in
file (configuration file) or via a web server. See Change of
order to communicate with each other. The IP address of the network setting on page 60.
CU 351 from factory is 192.168.0.102.
Alternatively to the factory-set IP address, it is possible to use a Note To use DHCP, a host name is required.
dynamic assignment of IP address. This is possible by activating
a DHCP (Dynamic Host Configuration Protocol) either directly in This is the first display shown when connecting to the CU 351.
the CU 351 or via the web server. See the example in fig. 108.
TM03 2048 3505
TM03 2298 4807
59
Factory setting Change of network setting
User name: admin When connection to the web server of the CU 351 has been
Password: admin established, it is possible to change the network setting.
When user name and password have been entered, a Java
Runtime Environment application starts up in the CU 351,
provided that it has been installed on the computer in question.
If this is not the case, but the computer is connected to Internet,
then use the link on the screen to download and install the Java
Runtime Environment application.
60
12. Measuring parameters
12.1 Transmitter types
The transmitter types in the table below can be used for the
measurement of values in the system.
17 11 16 14
Abbreviation Transmitter
1
4
TM03 8823 3507
2 14
61
13. Fault finding chart
Warning
Before making any connections in pumps, terminal boxes or breaker cabinet, make sure that the electricity supply
has been switched off for at least 5 minutes and that it cannot be accidentally switched on.
62
14. Maintenance Digital outputs (relay outputs)
0-20 mA
Input current and voltage: 4-20 mA
0-10 V
Tolerance: ±3.3 % of full scale
Repetitive accuracy: ±1% of full scale
Input resistance, current: < 250 Ω
Input resistance, voltage, CU 351: 10 kΩ ±10 %
Input resistance, voltage, IO 351: > 50 kΩ ± 10 %
24 V, maximum 50 mA,
Supply to sensor:
short-circuit protected
Subject to alterations.
63
64
65
66
Argentina Estonia Latvia Slovenia
Bombas GRUNDFOS de Argentina S.A. GRUNDFOS Pumps Eesti OÜ SIA GRUNDFOS Pumps Latvia GRUNDFOS PUMPEN VERTRIEB
Ruta Panamericana km. 37.500 Lote Peterburi tee 92G Deglava biznesa centrs Ges.m.b.H.,
34A 11415 Tallinn Augusta Deglava ielā 60, LV-1035, Rīga, Podružnica Ljubljana
1619 - Garin Tel: + 372 606 1690 Tālr.: + 371 714 9640, 7 149 641 Šlandrova 8b, SI-1231 Ljubljana-Črnuče
Pcia. de Buenos Aires Fax: + 372 606 1691 Fakss: + 371 914 9646 Phone: +386 1 568 0610
Phone: +54-3327 414 444 Telefax: +386 1 568 0619
Telefax: +54-3327 411 111 Finland Lithuania E-mail: [email protected]
OY GRUNDFOS Pumput AB GRUNDFOS Pumps UAB
Australia Mestarintie 11 Smolensko g. 6 Spain
GRUNDFOS Pumps Pty. Ltd. FIN-01730 Vantaa LT-03201 Vilnius Bombas GRUNDFOS España S.A.
P.O. Box 2040 Phone: +358-3066 5650 Tel: + 370 52 395 430 Camino de la Fuentecilla, s/n
Regency Park Telefax: +358-3066 56550 Fax: + 370 52 395 431 E-28110 Algete (Madrid)
South Australia 5942 Tel.: +34-91-848 8800
Phone: +61-8-8461-4611 France Malaysia Telefax: +34-91-628 0465
Telefax: +61-8-8340 0155 Pompes GRUNDFOS Distribution S.A. GRUNDFOS Pumps Sdn. Bhd.
Parc d’Activités de Chesnes 7 Jalan Peguam U1/25 Sweden
Austria 57, rue de Malacombe Glenmarie Industrial Park GRUNDFOS AB
GRUNDFOS Pumpen Vertrieb F-38290 St. Quentin Fallavier (Lyon) 40150 Shah Alam Box 333 (Lunnagårdsgatan 6)
Ges.m.b.H. Tél.: +33-4 74 82 15 15 Selangor 431 24 Mölndal
Grundfosstraße 2 Télécopie: +33-4 74 94 10 51 Phone: +60-3-5569 2922 Tel.: +46(0)771-32 23 00
A-5082 Grödig/Salzburg Telefax: +60-3-5569 2866 Telefax: +46(0)31-331 94 60
Tel.: +43-6246-883-0 Germany
Telefax: +43-6246-883-30 GRUNDFOS GMBH México Switzerland
Schlüterstr. 33 Bombas GRUNDFOS de México S.A. de GRUNDFOS Pumpen AG
Belgium 40699 Erkrath C.V. Bruggacherstrasse 10
N.V. GRUNDFOS Bellux S.A. Tel.: +49-(0) 211 929 69-0 Boulevard TLC No. 15 CH-8117 Fällanden/ZH
Boomsesteenweg 81-83 Telefax: +49-(0) 211 929 69-3799 Parque Industrial Stiva Aeropuerto Tel.: +41-1-806 8111
B-2630 Aartselaar e-mail: [email protected] Apodaca, N.L. 66600 Telefax: +41-1-806 8115
Tél.: +32-3-870 7300 Service in Deutschland: Phone: +52-81-8144 4000
Télécopie: +32-3-870 7301 e-mail: [email protected] Telefax: +52-81-8144 4010 Taiwan
GRUNDFOS Pumps (Taiwan) Ltd.
Belorussia Greece Netherlands 7 Floor, 219 Min-Chuan Road
Представительство ГРУНДФОС в GRUNDFOS Hellas A.E.B.E. GRUNDFOS Netherlands Taichung, Taiwan, R.O.C.
Минске 20th km. Athinon-Markopoulou Av. Veluwezoom 35 Phone: +886-4-2305 0868
220123, Минск, P.O. Box 71 1326 AE Almere Telefax: +886-4-2305 0878
ул. В. Хоружей, 22, оф. 1105 GR-19002 Peania Postbus 22015
Тел.: +(37517) 233 97 65, Phone: +0030-210-66 83 400 1302 CA ALMERE Thailand
Факс: +(37517) 233 97 69 Telefax: +0030-210-66 46 273 Tel.: +31-88-478 6336 GRUNDFOS (Thailand) Ltd.
E-mail: [email protected] Telefax: +31-88-478 6332 92 Chaloem Phrakiat Rama 9 Road,
Hong Kong e-mail: [email protected] Dokmai, Pravej, Bangkok 10250
Bosnia/Herzegovina GRUNDFOS Pumps (Hong Kong) Ltd. Phone: +66-2-725 8999
GRUNDFOS Sarajevo Unit 1, Ground floor New Zealand Telefax: +66-2-725 8998
Trg Heroja 16, Siu Wai Industrial Centre GRUNDFOS Pumps NZ Ltd.
BiH-71000 Sarajevo 29-33 Wing Hong Street & 17 Beatrice Tinsley Crescent Turkey
Phone: +387 33 713 290 68 King Lam Street, Cheung Sha Wan North Harbour Industrial Estate GRUNDFOS POMPA San. ve Tic. Ltd.
Telefax: +387 33 659 079 Kowloon Albany, Auckland Sti.
e-mail: [email protected] Phone: +852-27861706 / 27861741 Phone: +64-9-415 3240 Gebze Organize Sanayi Bölgesi
Telefax: +852-27858664 Telefax: +64-9-415 3250 Ihsan dede Caddesi,
Brazil 2. yol 200. Sokak No. 204
Mark GRUNDFOS Ltda. Hungary Norway 41490 Gebze/ Kocaeli
Av. Humberto de Alencar Castelo GRUNDFOS Hungária Kft. GRUNDFOS Pumper A/S Phone: +90 - 262-679 7979
Branco, 630 Park u. 8 Strømsveien 344 Telefax: +90 - 262-679 7905
CEP 09850 - 300 H-2045 Törökbálint, Postboks 235, Leirdal E-mail: [email protected]
São Bernardo do Campo - SP Phone: +36-23 511 110 N-1011 Oslo
Phone: +55-11 4393 5533 Telefax: +36-23 511 111 Tlf.: +47-22 90 47 00 Ukraine
Telefax: +55-11 4343 5015 Telefax: +47-22 32 21 50 ТОВ ГРУНДФОС УКРАЇНА
India 01010 Київ, Вул. Московська 8б,
Bulgaria GRUNDFOS Pumps India Private Lim- Poland Тел.:(+38 044) 390 40 50
GRUNDFOS Pumpen Vertrieb ited GRUNDFOS Pompy Sp. z o.o. Фах.: (+38 044) 390 40 59
Representative Office - Bulgaria 118 Old Mahabalipuram Road ul. Klonowa 23 E-mail: [email protected]
Bulgaria, 1421 Sofia Thoraipakkam Baranowo k. Poznania
Lozenetz District Chennai 600 096 PL-62-081 Przeźmierowo United Arab Emirates
105-107 Arsenalski blvd. Phone: +91-44 2496 6800 Tel: (+48-61) 650 13 00 GRUNDFOS Gulf Distribution
Phone: +359 2963 3820, 2963 5653 Fax: (+48-61) 650 13 50 P.O. Box 16768
Telefax: +359 2963 1305 Indonesia Jebel Ali Free Zone
PT GRUNDFOS Pompa Portugal Dubai
Canada Jl. Rawa Sumur III, Blok III / CC-1 Bombas GRUNDFOS Portugal, S.A. Phone: +971-4- 8815 166
GRUNDFOS Canada Inc. Kawasan Industri, Pulogadung Rua Calvet de Magalhães, 241 Telefax: +971-4-8815 136
2941 Brighton Road Jakarta 13930 Apartado 1079
Oakville, Ontario Phone: +62-21-460 6909 P-2770-153 Paço de Arcos United Kingdom
L6H 6C9 Telefax: +62-21-460 6910 / 460 6901 Tel.: +351-21-440 76 00 GRUNDFOS Pumps Ltd.
Phone: +1-905 829 9533 Telefax: +351-21-440 76 90 Grovebury Road
Telefax: +1-905 829 9512 Ireland Leighton Buzzard/Beds. LU7 8TL
GRUNDFOS (Ireland) Ltd. România Phone: +44-1525-850000
China Unit A, Merrywell Business Park GRUNDFOS Pompe România SRL Telefax: +44-1525-850011
GRUNDFOS Pumps (Shanghai) Co. Ltd. Ballymount Road Lower Bd. Biruintei, nr 103
51 Floor, Raffles City Dublin 12 Pantelimon county Ilfov U.S.A.
No. 268 Xi Zang Road. (M) Phone: +353-1-4089 800 Phone: +40 21 200 4100 GRUNDFOS Pumps Corporation
Shanghai 200001 Telefax: +353-1-4089 830 Telefax: +40 21 200 4101 17100 West 118th Terrace
PRC E-mail: [email protected] Olathe, Kansas 66061
Phone: +86-021-612 252 22 Italy Phone: +1-913-227-3400
Telefax: +86-021-612 253 33 GRUNDFOS Pompe Italia S.r.l. Russia Telefax: +1-913-227-3500
Via Gran Sasso 4 ООО Грундфос
Croatia I-20060 Truccazzano (Milano) Россия, 109544 Москва, ул. Школьная Usbekistan
GRUNDFOS predstavništvo Zagreb Tel.: +39-02-95838112 39 Представительство ГРУНДФОС в
Cebini 37, Buzin Telefax: +39-02-95309290 / 95838461 Тел. (+7) 495 737 30 00, 564 88 00 Ташкенте
HR-10010 Zagreb Факс (+7) 495 737 75 36, 564 88 11 700000 Ташкент ул.Усмана Носира 1-й
Phone: +385 1 6595 400 Japan E-mail тупик 5
Telefax: +385 1 6595 499 GRUNDFOS Pumps K.K. [email protected] Телефон: (3712) 55-68-15
Gotanda Metalion Bldg., 5F, Факс: (3712) 53-36-35
Czech Republic 5-21-15, Higashi-gotanda Serbia
GRUNDFOS s.r.o. Shiagawa-ku, Tokyo GRUNDFOS Predstavništvo Beograd
Čajkovského 21 141-0022 Japan Dr. Milutina Ivkovića 2a/29
779 00 Olomouc Phone: +81 35 448 1391 YU-11000 Beograd
Phone: +420-585-716 111 Telefax: +81 35 448 9619 Phone: +381 11 26 47 877 / 11 26 47
Telefax: +420-585-716 299 496
Korea Telefax: +381 11 26 48 340
Denmark GRUNDFOS Pumps Korea Ltd.
GRUNDFOS DK A/S 6th Floor, Aju Building 679-5 Singapore
Martin Bachs Vej 3 Yeoksam-dong, Kangnam-ku, 135-916 GRUNDFOS (Singapore) Pte. Ltd.
DK-8850 Bjerringbro Seoul, Korea 24 Tuas West Road
Tlf.: +45-87 50 50 50 Phone: +82-2-5317 600 Jurong Town
Telefax: +45-87 50 51 51 Telefax: +82-2-5633 725 Singapore 638381
E-mail: [email protected] Phone: +65-6865 1222
www.grundfos.com/DK Telefax: +65-6861 8402
96768036 0509
GB
Repl. 96768036 0308
www.grundfos.com