0% found this document useful (0 votes)
197 views

EG III Generator Unit Manual

This technical manual provides operating instructions for controls and indicators on a generator system and its EG-III control module. The generator has controls for its circuit breakers, meters to monitor output parameters like power and temperature, and indicator lamps. The EG-III control module is used to operate the generator and has its own set of controls and indicators described in the manual. Figures and tables are included to depict the actual location of components and explain the purpose and function of each.

Uploaded by

LIVIA
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
197 views

EG III Generator Unit Manual

This technical manual provides operating instructions for controls and indicators on a generator system and its EG-III control module. The generator has controls for its circuit breakers, meters to monitor output parameters like power and temperature, and indicator lamps. The EG-III control module is used to operate the generator and has its own set of controls and indicators described in the manual. Figures and tables are included to depict the actual location of components and explain the purpose and function of each.

Uploaded by

LIVIA
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 15

Technical Manual

EG III Generator Unit

RIG/PLANT REFERENCE REFERENCE DESCRIPTION

ADDITIONAL CODE SDRL CODE TOTAL PGS


This document contains proprietary and confidential information National-Oilwell L.P.
which belongs to National Oilwell; it is loaned for limited purposes 1530 W. Sam Houston Pkwy. N
REMARKS only and remains the property of National Oilwell. Reproduction, in
whole or in part; or use of this design or distribution of this Houston, Texas 77043
MAIN TAG NUMBER DISCIPLINE information to others is not permitted without the express written USA
consent of National Oilwell. This document is to be returned to Phone +1 713 935 8000
National Oilwell upon request and in any event upon completion of
CLIENT PO NUMBER the use for which it was loaned. Fax +1 713 935 8382
 National Oilwell
CLIENT DOCUMENT NUMBER DOCUMENT NUMBER REV

Client Document Number 20603-79 E

www.natoil.com
Document number 20603-79
Revision E
Page 2

REVISION HISTORY

E 09.04.2005 Updated to New Template BKF


Rev Date (dd.mm.yyyy) Reason for issue Prepared Checked Approved

CHANGE DESCRIPTION

Revision Change Description


A Initial Release
B Convert to Word 97.
C Add Table of Contents Codes. Correct Level 5 and Level 6 styles and errors.
D Correct typo in Table 2-1. Replace "KV/KVA" with "KW/KVA".
E Updated to New Template.

www.natoil.com 24 HOUR SERVICE (713) 935-8000


Document number 20603-79
Revision E
Page 3

TABLE OF CONTENTS

1 INTRODUCTION............................................................................................................... 4
2 OPERATING CONTROLS AND INDICATORS ................................................................ 4
2.1 Generator ............................................................................................................... 4
2.2 EG-III CONTROL MODULE ................................................................................... 4

www.natoil.com 24 HOUR SERVICE (713) 935-8000


Document number 20603-79
Revision E
Page 4

1 INTRODUCTION

This chapter provides the theory of operation, operating instructions and illustrations
depicting actual operating controls and indicators for the SCR Drive Generator System with
a brief explanation pertaining to purpose and function.

2 OPERATING CONTROLS AND INDICATORS

2.1 Generator

The locations of the controls and indicators for a typical generator are shown in Figure 2-1.
A brief explanation of the purpose and function of each is given in Table 2-1.

2.2 EG-III CONTROL MODULE

The EG-III Control Module is used to operate and control the generator. The locations of
the controls and indicators for the EG-III Control Module are shown in Figure 2-2. A brief
explanation of the purpose and function of each is given in Table 2-2.

Figure 2-1. Typical Generator Cubicle Controls and Indicators

www.natoil.com 24 HOUR SERVICE (713) 935-8000


Document number 20603-79
Revision E
Page 5

Table 2-1. Generator Controls and Indicators

ITEM NAME FUNCTIONAL DESCRIPTION


6 POWER FACTOR Meter This meter (located on Generator Cubicle 4) indicates the percentage of
the total power (KW/KVA) being produced is actually being used by the
load.
7 TRANSFORMER NO. 1 Closing this circuit breaker supplies power to Transformer No. 1. This
FDR BREAKER - F91 circuit breaker is located on Generator Cubicle 2.
8 TRANSFORMER NO. 2 Closing this circuit breaker supplies power to Transformer No. 2. This
FDR BREAKER - F92 circuit breaker is located on Generator Cubicle 3.
9 GENERATOR CIRCUIT The generator circuit breaker connects the generator to the main AC Bus.
BREAKER The following two buttons are located on the front panel of each
generator circuit breaker.
• PUSH ON button is pushed to close the generator circuit breaker.
• PUSH OFF button is pushed to open the generator circuit breaker.

Never use the generator circuit breaker PUSH ON button to


manually close the generator circuit breaker.

The front panel of the generator circuit breaker also has indicators which
show if the generator circuit breaker is open (or closed) and if the
generator circuit breaker is charged or discharged. The generator circuit
breaker cannot be charged by pushing the PUSH ON button on the front
of the generator circuit breaker. There is one of these circuit breakers
located on each of the four Generator Cubicles.
10 AC KILOWATTS Meter This meter displays the AC power that the generator is outputting. There
is one of these meters located on each of the four Generator Cubicles.
11 TEMPERATURE Meter Indicates the temperatures of various points in the winding of the
generator. RTDs installed in the windings of the generator are used to
monitor the temperatures. There is one of these meters located on each
of the four Generator Cubicles.
12 KVAR Meter Indicates the KVARs are supplied by the generator. Calibration is Zero to
2,000 KVARs. There is one of these meters located on each of the four
Generator Cubicles.
13 AC AMMETER Indicates the AC current of A, B, or C phase of the generator or the A
phase of the AC bus is supplied by the generator. Calibration is Zero to
2,500 AAC. There is one of these meters located on each of the four
Generator Cubicles.
14 AC VOLTMETER Indicates the AC line-to-line voltage of AB, BC, or CA phase of the
generator OR the AB phase of the AC bus supplied by the generator.
Calibration is Zero to 750 VAC. There is one of these meters located on
each of the four Generator Cubicles.

www.natoil.com 24 HOUR SERVICE (713) 935-8000


Document number 20603-79
Revision E
Page 6

Table 2-1. Generator Controls and Indicators (Continued)

ITEM NAME FUNCTIONAL DESCRIPTION


15 GENERATOR HOUR Indicates the total length of time on-line, measured in hours, for the
Meter generator. There is one of these meters located on each of the four
Generator Cubicles.
16 GENERATOR RUN This lamp illuminates when the generator is running. There is one of
Lamp these lamps located on each of the four Generator Cubicles.
17 GENERATOR HEATER This lamp illuminates when the Generator Heater is operating. There is
ON Lamp one of these lamps located on each of the four Generator Cubicles.
18 GENERATOR ONLINE Illuminates if the engine/generator is on-line and ready to supply power
Lamp to a load. There is one of these lamps located on each of the four
Generator Cubicles.
19 PUSH TO CHARGE This switch must be depressed to charge Circuit Breaker LP8 before LP8
CIRCUIT BREAKER LP8 is closed. There is one of these pushbutton switches located on each of
Switch the four Generator Cubicles.
20 AMMETER Switch Five-position switch (AΦ/OFF/BΦ/OFF/CΦ) selects the phase of the
generator current to be monitored on the AC AMMETER (Item 13 in this
table). There is one of these switches located on each of the four
Generator Cubicles.
21 TEMPERATURE Switch Ten-position switch (TEST/OFF/1/2/3/4/5/6/7/8) selects the test point in
the generator winding to display on the TEMPERATURE Meter (Item 11
in this table). There is one of these switches located on each of the four
Generator Cubicles.
22 VOLTMETER Switch Five-position switch (BUS/OFF/AΦ/BΦ/CΦ) selects the AC voltage of
AB, BC, or CA of the generator or the AB of the AC Bus (BUS) as
supplied by the generator. The AC voltage selected is displayed on the
AC VOLTMETER (Item 14 in this table). There is one of these switches
located on each of the four Generator Cubicles.
23 % AC GROUND AMPS This meter displays the percentage of the AC current which is going to
Meter ground. This meter is located on Generator Cubicle 3.
24 % DC GROUND AMPS This meter displays the percentage of the DC current which is going to
Meter ground. This meter is located on Generator Cubicle 3.
25 GROUND FAULT These lamps illuminate to give indications on an AC or DC ground fault
INDICATOR Lamps (3) condition. All three lamps will dimly illuminate if no ground faults are
detected. If an AC ground fault is detected, the lamp corresponding to the
grounded phase will be extinguished. If a DC ground fault is detected, all
three lamps will be brightly illuminated. These lamps are located on
Generator Cubicle 3.
26 GROUND FAULT Since an AC ground fault causes a GROUND LAMP INDICATOR lamp
INDICATOR TEST to be extinguished, depressing this pushbutton switch will cause the
Pushbutton GROUND FAULT INDICATOR Lamp to illuminate, thus checking that the
lamp is good. This pushbutton is located on Generator Cubicle 3.
27 POWER LIMIT Lamps This lamp illuminates when the system approaches the amount of power
that it is designed to produce. This is located on Generator Cubicle 1.

www.natoil.com 24 HOUR SERVICE (713) 935-8000


Document number 20603-79
Revision E
Page 7

Table 2-1. Generator Controls and Indicators (Concluded)

ITEM NAME FUNCTIONAL DESCRIPTION


28 ONCOMING This meter displays the AC frequency of the generator being connected
GENERATOR to the Main AC Bus. This is located on Generator Cubicle 2.
FREQUENCY Meter
29 SYNCHROSCOPE This meter displays how synchronous the frequency of the oncoming
generator as compared to the frequency of the Main AC Bus. When the
SYNCHROSCOPE needle points vertically (the 12 o’clock position), the
two frequencies are matched. This meter is used in conjunction with the
SYNCH Lamp (Item 31 of this table). The meter is located on Generator
Cubicle 2.
30 BUS FREQUENCY This meter displays the AC frequency of the Main AC Bus. This is located
Meter on Generator Cubicle 2.
31 SYNCH Lamps (2) The illumination of these lamps goes out when the oncoming generator’s
frequency is synchronous with that of the Main AC Bus. At the same time
of the SYNCH Lamps going out, the needle of the SYNCHROSCOPE
(Item 29 of this table) will point vertically (the 12 o’clock position). These
lamps are located on Generator Cubicle 1.
32 SYNCHRONIZING This is a four position switch (Generator 1, Generator 2, Generator 3, and
SWITCH Generator 4) that allows selection of the generator to be placed on line. If
the generator selected by the SYNCHRONIZING SWITCH is not running,
the circuitry will not allow the non-running generator to be connected to
the Main AC Bus. This switch is located on Generator Cubicle 2.
33 AC MODULE Electronic governor and voltage regulator. This module controls the
operation of the generator. There is one of these modules located on
each of the four Generator Cubicles.

www.natoil.com 24 HOUR SERVICE (713) 935-8000


Document number 20603-79
Revision E
Page 8

Figure 2-2. EG-III Control Module Front Panel Controls and Indicators (Excerpt of
Drawing 7708-00 Rev. B)

In Figure 2-2, a section entitled ANNUNCIATOR has various generator


protection and engine shutdown trouble indicators (OVER VOLTS, REVERSE
POWER, etc.). The yellow LED to the right of each trouble indicator illuminates when
a trouble condition is detected which may progress to a system TRIP. The red LED to
the right of each trouble indicator illuminates to indicate a trouble has occurred
which is serious to trip the generator's circuit breaker (this disconnects the
generator from the AC Bus). In all but one condition, the red LED is latched (kept
illuminated) even if the trouble is fixed. To extinguish the illuminated red LED,
depress the ANNUNCIATOR RESET. If the trouble still exists, it will not extinguish
and the generator's circuit breaker cannot be closed.

www.natoil.com 24 HOUR SERVICE (713) 935-8000


Document number 20603-79
Revision E
Page 9

Table 2-2. EG-III Control Module Front Panel Controls and Indicators

CONTROL/INDICATOR DESCRIPTION
POWER ON Green LED Illuminates when power is supplied to the electronic circuitry inside the EG-III
Control Module. This is done by turning the Engine Control switch to the LOW
IDLE position.
IN SYNC Green LED Illuminates when generator output is in sync with the common 600 VAC Bus
voltage.
OVER VOLTS LEDs The yellow LED illuminates when the generator output voltage is approaching
Yellow - ALARM TRIP level. The red LED illuminates when the Overvoltage Latch is set, indicating
Red - TRIP Latched the generator output voltage is >660 VAC. The Overvoltage latch is enabled only
when the generator is at RUN frequency.

In all of the cases where the red TRIP LED is latched (kept lighted):
this is done to help troubleshoot the indicated problem.

UNDER VOLTS LEDs The yellow LED illuminates when the generator output voltage <600 VAC. The red
Yellow - ALARM LED illuminates when the Undervoltage Latch is set (indicating generator output
Red - TRIP Latched voltage is <540 VAC). The Undervoltage latch can be set only when the generator
is at RUN frequency.
OVER FREQUENCY The yellow LED illuminates when the generator frequency has increased above 60
LEDs Hz and is approaching 67 Hz. The red LED illuminates when the Overfrequency
Yellow - ALARM Latch is set (indicating the generator output voltage frequency is >67 Hz) and the
Red - TRIP Latched Generator Circuit Breaker trips.
UNDER FREQUENCY The yellow LED illuminates when the generator frequency has decreased below
LEDs 60 Hz and is approaching 50 Hz. The red LED illuminates when the
Yellow - ALARM Underfrequency Latch is set (indicating the generator output voltage frequency is
Red - TRIP Latched <50 Hz). The Underfrequency Latch can be set only when the Generator Output
Circuit Breaker is closed.
EXCITER OVER Illuminates when the field of the generator is being over-excited. The Overcurrent
CURRENT LEDs Latch becomes set if the current in the Exciter is higher than 5.25 amps for an
Yellow - ALARM extended time (7.0 Amps for >20 seconds).
Red - TRIP Latched
EXCITER LOSS LEDs The yellow LED illuminates when the field of the generator is <5.25 Amps. The red
Yellow - ALARM LED illuminates when the Exciter Loss Latch is set (current through the generator
Red - TRIP Latched field winding is 0.0 Amps for 20 seconds). The Exciter Loss Latch can be set only
when the generator is running at RUN frequency.
OVER CURRENT LEDs The yellow LED illuminates when the generator output current has increased to
Yellow - ALARM >100%. The red LED illuminates when the Over Current Latch is set (indicating the
Red - TRIP Latched generator output current is >150% of rated current).
PHASE UNBALANCE The PHASE UNBALANCE circuit is not implemented in this application.
LEDs
Yellow - ALARM
Red - TRIP Latched

www.natoil.com 24 HOUR SERVICE (713) 935-8000


Document number 20603-79
Revision E
Page 10

Table 2-2. EG-III Control Module Front Panel Controls and Indicators (Continued)

CONTROL/ DESCRIPTION
INDICATOR
REVERSE POWER The yellow LED illuminates at .-6% of the generator’s rated KW (i.e., the generator
LEDs is pulling power from the bus). The red LED illuminates if the reverse power level
Yellow - ALARM reaches -10% of the generator’s rated KW. The amount of time required before the
Red - TRIP Latched TRIP is initiated is usually six to 20 seconds (the time it takes is not critical).
FEEDBACK LOSS The Feedback Loss Circuit monitors both speed and voltage feedback. The loss of
LEDs either speed or voltage feedback will cause BOTH the yellow ALARM and red
Yellow - ALARM TRIP LEDs to simultaneously illuminate. A Feedback Loss trips the Generator
Red - TRIP Circuit Breaker but it is not latched. You, therefore, do not need to press the
ANNUNCIATOR RESET pushbutton.
ANNUNCIATOR This resets TRIPS that are no longer active. Active TRIPS will continue to latch
RESET (illuminate) red TRIP indications in the Annunciator section of the panel. If an TRIP
Pushbutton Switch is active, the red TRIP LED will continue to be illuminated and the Generator Circuit
Breaker cannot be closed.
BUS ENERGIZED Illuminates when at least one generator is connected to the AC bus.
Green LED
EXCITER POWER Illuminates if the field of the generator is being excited. It should illuminate when the
Green LED ENGINE CONTROL SWITCH is set to either the HIGH IDLE or RUN positions.
LOAD COMMAND Illuminates when the generator is ready to supply current to a load. Supplying
Green LED current to the load is done by closing the generator circuit breaker. When the
ENGINE CONTROL SWITCH is turned to one of the IDLE positions, the LOAD
COMMAND lamp will extinguish before the generator circuit breaker is
automatically opened.
LINE DEMODULATION Illuminates when the EG-III Control Module is detecting the frequency of the output
Green LED voltages of the generator. In this case, the EG-III Control Module controls the
frequency by controlling the speed of the engine. When the ENGINE CONTROL
SWITCH is set to the HIGH IDLE or RUN position, the LINE DEMODULATION
LED should illuminate.
PULSE PICKUP Green Illuminates when the engine is turning, causing the Tach-pickup to produce pulses.
LED
ENGINE CONTROL Four position switch (OFF/LOW IDLE/HIGH IDLE/RUN) to control engine speed.
Switch Before turning this switch to the RUN position, use the LOW or HIGH IDLE
positions to allow the engine to idle until it has reached it’s recommended
temperature.
CIRCUIT BREAKER Indicates the selected generator’s output is in synchronization with the 600 VAC
Red LED Main Bus and that there are no active TRIP conditions.
CIRCUIT BREAKER Closes the Generator Output Circuit Breaker when the CIRCUIT BREAKER LED is
Pushbutton illuminated (refer to the previous listing in this table).
VOLTAGE TRIM This green LED indicates unit output voltage is greater than the other units
MASTER LED connected on-line and is therefore considered the master (the controlling unit).
VOLTAGE TRIM This potentiometer permits adjustment of generator output voltage.
Potentiometer

www.natoil.com 24 HOUR SERVICE (713) 935-8000


Document number 20603-79
Revision E
Page 11

Table 2-2. EG-III Control Module Front Panel Controls and Indicators (Concluded)

CONTROL/ DESCRIPTION
INDICATOR
FREQUENCY TRIM Indicates unit output frequency is greater than other units on-line and is therefore
MASTER LED the master (the controlling unit).
FREQUENCY TRIM This potentiometer permits manual adjustment of generator output frequency.
Potentiometer
HIGH IDLE TRIM This potentiometer permits adjustment of generator output frequency when the
Potentiometer ENGINE CONTROL switch (refer to a previous listing in this table) is set to the
HIGH IDLE position.

2.2.1 To Start an Engine and Connect the Associated Generator to the AC BUS

To start an engine and connect the associated generator to the AC Bus, perform the
procedure given in Table 2-3.

Table 2-3. Procedure to Start an Engine and Connect the Associated Generator to the
AC Bus

STEP PROCEDURE
1 Move the ENGINE CONTROL switch (refer to Figure 2-2) from the OFF position to the LOW IDLE or
HIGH IDLE position.

With the EG-III Control Module ENGINE CONTROL switch set to the HIGH IDLE
position, the engine warms more quickly.
2 Connect the Hands Off Cranking (HOC) battery by closing the HOC Circuit Breaker.

The HOC Circuit Breaker can be located at a number of various locations. Refer to
Drawing XXXX-001-00 in the drawing package for this job to determine the specific
location. (XXXX in the Ross Hill drawing number for your equipment)
3 Verify the PULSE PICKUP LED (refer to Figure 2-2) is illuminated. This indicates that the engine is
running.
4 Allow the engine to run at idle until it reaches the recommended operating temperature. Monitor the
temperature on the TEMPERATURE METER (Item 11 on Figure 2-1) of the engine/generator that you
are operating.
5 Once the engine has reached the recommended operating temperature, move the ENGINE
CONTROL switch (refer to Figure 2-2) from the LOW IDLE or HIGH IDLE position to the RUN
position.

www.natoil.com 24 HOUR SERVICE (713) 935-8000


Document number 20603-79
Revision E
Page 12

Table 2-3. Procedure to Start an Engine and Connect the Associated Generator to
the AC Bus (Concluded)

STEP PROCEDURE
6 Verify the EXCITER POWER and LINE DEMODULATION LEDs (refer to Figure 2-2) are illuminated
when engine speed has increased.

This will not happen in LOW IDLE or HIGH IDLE if the HIGH IDLE TRIM potentiometer
(refer to Figure 2-2) is set to a low setting.

7 Use the SYNCHRONIZING SWITCH (Item 32 on Figure 2-1) to select the generator which is going to
be brought online.
8 Adjust the FREQUENCY TRIM potentiometer (refer to Figure 2-2) clockwise until the FREQUENCY
METER (Item 28 on Figure 2-1) indicates 60 Hz.
9 Adjust the VOLTAGE TRIM potentiometer (refer to Figure 2-2) until the AC VOLTMETER (Item 14 on
Figure 2-1) of the appropriate Generator Cubicle indicates 600 VAC.
10 Charge the GENERATOR CIRCUIT BREAKER (Item 9 on Figure 2-1) for the generator being
brought on line. Charging the GENERATOR CIRCUIT BREAKER is done by pumping the black
handle located on the front of the GENERATOR CIRCUIT BREAKER.
11 To connect the generator to the AC Bus, depress the lighted PUSH TO CLOSE pushbutton switch
(refer to Figure 2-2).

www.natoil.com 24 HOUR SERVICE (713) 935-8000


Document number 20603-79
Revision E
Page 13

2.2.2 Connecting the Second Generator to the AC BUS

To connect the second generator to the AC Bus, perform the steps listed in Table 2-4.

Table 2-4. Procedure for Connecting the Second Generator to the AC Bus

STEP PROCEDURE
1 Turn the SYNCHRONIZING SWITCH (Item 32 on Figure 2-1) to the number of the second generator
to be connected to the AC Bus.
2 Turn the VOLTMETER SWITCH (Item 22 on Figure 2-1) on the second Generator Cubicle to select
the A phase voltage of the second generator. This will cause the AC VOLTMETER (Item 14 on Figure
2-1) to display the selected generator’s A phase voltage.
3 Turn the EG-III Control Module VOLTAGE TRIM potentiometer (refer to Figure 2-2) to set the voltage
shown on the AC VOLTMETER (Item 14 on Figure 2-1) to 600 VAC.
4 Turn the EG-III Control Module FREQUENCY TRIM potentiometer (refer to Figure 2-2) to cause the
SYNCHROSCOPE (Item 29 on Figure 2-1) to rotate slowly clockwise and the SYNC lamp (Item 31 on
Figure 2-1) to brighten and dim very slowly.
5 Charge the GENERATOR CIRCUIT BREAKER (Item 9 on Figure 2-1) for the generator being
brought on line. Charging the GENERATOR CIRCUIT BREAKER is done by pumping the black
handle located on the front of the GENERATOR CIRCUIT BREAKER.
6 Verify that both the CIRCUIT BREAKER red LED and IN SYNC green LEDs (refer to Figure 2-2) are
illuminated. When the needle on the SYNCHROSCOPE, (Item 29 on Figure 2-1) points straight up
and the SYNC lamps (Items 31 on Figure 2-1) are extinguished, press the EG-III Control Module
CIRCUIT BREAKER pushbutton (refer to Figure 2-2). The second generator is now on-line.
7 Verify the EG-III Control Module LOAD COMMAND LED (refer to Figure 2-2) is illuminated. This
indicates that the generator is ready to supply power. Turn the SYNCHRONIZING SWITCH (Item 32
on Figure 2-1) to the OFF position.

2.2.3 To Connect the Third or Fourth Generator to the AC BUS

Follow the procedures listed in Table 2-4 to connect the third or fourth generator to the AC
bus.

2.2.4 Adjusting Frequency Trim and Voltage Trim Potentiometers on the EG-III Control
Module

Adjusting the speed of the engine of an engine/generator affects the output AC frequency
of that engine/generator. When the engine speed of a particular engine/generator is
adjusted higher than that of the other engine/generators connected to the AC Bus, it's
FREQUENCY TRIM MASTER LED (refer to Figure 2-2) will illuminate, indicating that it is
controlling the frequency of the AC Bus.

www.natoil.com 24 HOUR SERVICE (713) 935-8000


Document number 20603-79
Revision E
Page 14

Adjusting the output of the generator of an engine/generator affects the output AC voltage
level. When the output voltage of a generator of a particular engine/generator is adjusted
higher than that of the other engine/generators connected to the AC Bus, it's VOLTAGE
TRIM MASTER LED (refer to Figure 2-2) will illuminate, indicating that it is controlling the
frequency of the AC Bus.

Normally, it is not necessary to have an engine operating as a Master Engine, or to have a


generator operating as the Master Generator. If it becomes desirable to have a Master
Engine or a Master Generator, refer to the following pertinent information.

The EG-III Control Module for the Master Engine will control the output AC
frequency of each and every one of the engine/generators. The EG-III Control
Module for the Master Generator will control the output AC voltage of each
and every one of the engine/generators connected to the AC Bus.

2.2.5 Selecting and Engine to be the Master Engine

Perform the steps listed in Table 2-5 to select an engine to be the master engine.

Table 2-5. Procedure for Selecting an Engine to be the Master Engine

STEP PROCEDURE
1 Connect all the desired engine/generators to the AC Bus. Decide which engine will be the Master
Engine. Rotate the FREQUENCY TRIM potentiometer (refer to Figure 2-2) for each of the other
engine/generators counterclockwise until the FREQUENCY TRIM LED (refer to Figure 2-2) adjacent
to each of the FREQUENCY TRIM knobs (refer to Figure 2-2) are extinguished. Ensure that the
FREQUENCY TRIM LEDs (refer to Figure 2-2) for all of the engine/generators which are not going to
be the Master Engine are all extinguished.
2 The FREQUENCY TRIM LED (refer to Figure 2-2) adjacent to the FREQUENCY TRIM knob (refer to
Figure 2-2) on the EG-III Control Module which has NOT been adjusted should be illuminated. This
indicates that the engine/generator controlled by that EG-III Control Module is the Master Engine.
3 Lock the settings of all of the FREQUENCY TRIM potentiometers (refer to Figure 2-2) in position by
turning the locking rings on the FREQUENCY TRIM potentiometers clockwise.

2.2.6 Selecting a Generator to be the Master Generator

Perform the steps listed in Table 2-6 to select an engine to be the master generator.

It may be desirable to select a master engine or master generator just


after adding a generator to the AC Bus or just before disconnecting a
generator from the AC Bus.

www.natoil.com 24 HOUR SERVICE (713) 935-8000


Document number 20603-79
Revision E
Page 15

Table 2-6. Procedure for Selecting a Generator to be the Master Generator

STEP PROCEDURE
1 Connect all the desired engine/generators to the AC Bus. Decide which generator will be the Master
Generator. Rotate the VOLTAGE TRIM potentiometer (refer to Figure 2-2) for each of the other
engine/generators counterclockwise until the VOLTAGE TRIM LED (refer to Figure 2-2) adjacent to
each of the FREQUENCY TRIM knobs (refer to Figure 2-2) are extinguished. Ensure that the
VOLTAGE TRIM LEDs (refer to Figure 2-2) for all of the engine/generators which are not going to be
the Master Generator are all extinguished.
2 The VOLTAGE TRIM LED (refer to Figure 2-2) adjacent to the VOLTAGE TRIM knob (refer to Figure
2-2) on the EG-III Control Module which has NOT been adjusted should be illuminated. This indicates
that the engine/generator controlled by that EG-III Control Module is the Master Engine.
3 Lock the settings of all of the VOLTAGE TRIM potentiometers (refer to Figure 2-2) in position by
turning the locking rings on the VOLTAGE TRIM potentiometers clockwise.

2.2.7 Disconnecting a Generator from the AC Bus

To disconnect a generator from the AC Bus, perform the steps in Table 2-7.

Table 2-7. Procedure for Disconnecting a Generator from the AC Bus

STEP PROCEDURE
1 Move the ENGINE CONTROL switch (refer to Figure 2-2) of the engine/generator which is going to be
disconnected to the LOW IDLE or HIGH IDLE position. Verify that the LOAD COMMAND LED (refer
to Figure 2-2) of that engine/generator has extinguished. Verify the circuit breaker connecting that
engine/generator to the AC bus has tripped. The selected engine/generator will start to slow down.
2 Allow the engine a cooling-off period before stopping the engine. The engine will cool faster if the
LOW IDLE position of the ENGINE CONTROL has been selected. Once the engine has cooled
sufficiently, move the ENGINE CONTROL switch (refer to Figure 2-2) of the engine/generator which
has been disconnected from the AC Bus to the OFF position. This will stop the selected
engine/generator.

www.natoil.com 24 HOUR SERVICE (713) 935-8000

You might also like