Diseño de Muros Especiales
Diseño de Muros Especiales
Note that Aj = effective cross-sectional area within the joint equal to the joint depth times an effective
width. The effective width is the smaller of
Observe the joint shear is a function of effective cross-sectional area Aj of the joint and the square root
of the concrete compressive strength fc′ only. If the net shear exceeds the nominal shear strength φVc
(equal to 20 fc′ Aj ,15 fc′ Aj , or 12 fc′ Aj , depending on the confinement provided at the joint), then the
designer has no choice but to increase fc′ of concrete and/or the size of columns.
A column face is considered confined by a beam if the beam width is equal to at least 75% of the
column width. (No mention is made in ACI 318-02 for the required depth of beam.) When joints are
confined on all four sides, transverse reinforcement within the joint required per Section 21.4.4 may
be reduced by 50%. Hoop spacing is permitted to a maximum of 6 in (see Figure 6.29).
Frame column
Column hoops and
crossties
Frame beam Frame beam top reinforcement
2 in.
FIGURE 6.29 Beam–column joint; special moment frame. Transverse reinforcing in the joint is the same
as for the frame column. A 50% reduction is allowed if the joint is confined on all the four faces. Maximum
spacing of transverse reinforcement is equal to 6 in.
578 Reinforced Concrete Design of Tall Buildings
2nd
PD = 1600 kip
PL = 300 kip Ag = 5856 in.2
Vu = VE = 1350 kip Section modulus = 3,57,216 in.3
Mu = ME = 70,000 kip-ft 1st
16 in.
366 in.
FIGURE 6.30 Design example; partial shear wall elevation and plan.
Figure 6.30 shows a partial elevation and plan of the wall along with the ultimate axial forces
and moments due to gravity and lateral loads. The dead load, P D, includes the self-weight of the
wall. P L is the reduced live load. Also shown therein are the section properties of the wall and the
horizontal displacement δe equal to 2.15 in. at the roof level. The displacement is the lateral elastic
deflection due to design basis code level earthquake loads. As will be seen presently, this displace-
ment multiplied by the Cd factor is used to determine the requirements for detailing boundary
elements.
The wall has been analyzed using the following assumptions:
It should be noted that a computer analysis is almost always necessary to determine the build-
ing’s response. This is because it is mandated in recent seismic codes to consider variables such as
uncracked and cracked concrete section properties and some soil or foundation deformation beneath
the structure’s base.
Required:
• The calculation of ultimate design loads and moments using ASCE 7-05 load combinations.
• The preliminary sizing of the wall using a rule-of-thumb approach.
• The design of wall for shear.
• The design of wall for combined axial load and bending moment.
• The determination of boundary element requirements using both stress index and displace-
ment-based methods.
• The design of boundary elements.
• The schematics showing reinforcement layout.
• The design shall be in accordance with ACI 318-05.
Seismic Design Examples and Details 579
Solution:
Load Combinations:
where
Vn is the nominal shear capacity
φ is the strength-reduction factor = 0.6 (see Section 9.3.4)
ACV is the gross area of wall equal to its length times the thickness
580 Reinforced Concrete Design of Tall Buildings
αc is the coefficient defining the relative contribution of concrete strength to wall strength,
typically taken as equal to 2.0. (Note that Section 21.7.4.1 permits αc = 3.0 for squat walls
with hw /lw ≤ 2.0, and a linear variation between 3.0 and 2.0 for intermediate values of hw /lw.
The controlling ratio for the design of wall pier is based on the larger of overall dimensions
of the wall or a segment of the wall. It is permitted to use αc = 2.0 in all cases.)
ρn is the ratio of area horizontal reinforcement to gross concrete area perpendicular to it
fc′ is the specified compressive strength of concrete, psi
fy is the specified yield strength of reinforcement, psi
Vu = VE = 1350 kip
Vn ≯ 8 ACV fc′
Vn = Avf fy μ (11.25)
Seismic Design Examples and Details 581
where
Avf is the area of shear friction reinforcement, in.2 that crosses the potential sliding plane
μ is the coefficient of friction = 1.0 for a normal weight concrete surface roughened to 1/4 in.
amplitude.
Additionally, ACI 318-05 permits permanent net compression across the shear plane as additive
to the resistance provided by shear friction reinforcement. For the example shear wall, we will con-
servatively ignore the beneficial effect of compression.
As will be seen presently, the vertical reinforcement, Avf, required to satisfy the governing axial
load and moment combination is equal to
Avf = 32 # 11 plus 36 # 7
= 32 × 1.56 + 36 × 0.60
= 71.5 in.2
P (klp)
25,000
fs = 0
fs = 0.5f y
+1
+2
100,000
My (k-ft)
–10,000
(a)
366 × 16 in.
(b)
FIGURE 6.31 (a) Shear wall load/moment interaction diagram and (b) cross section of wall.
reinforcement ratio equal to 0.0025 and a maximum spacing of 18 in. is specified for both Pn and
Pu. However, a reduction in the reinforcement ratio is permitted if the design shear force, Vu, is less
than Ac fc′ .
The minimum ratios of Pu if Vu ≤ Ac fc′ (see Section 14.3) are
The minimum ratios of Pv (vertical reinforcement) for the same condition are
In seismic design, the vertical reinforcement at the bottom few stories of a shear wall is typically
controlled by bending requirements. The upper levels are likely to be controlled by the ACI 318-02
minimum reinforcement ratio of 0.0025.
For the example wall,
ACV fc′ = 2 × 366 × 16/1000 5000/1000 = 414 kip < Vu = 1400 kip
= 0.0025 × b × t
= 0.0025 × 16 × 12
= 0.48 in.2
Seismic Design Examples and Details 583
Since Vu = 1350 kip is greater than 828 kip, we use two layers of #5 at 15. The reason for two layers
of reinforcement is to place web reinforcement close to the wall surface to inhibit fragmentation of
concrete in the event of a severe cracking of concrete during an earthquake.
= 0.2 × 5000
= 1.0 ksi
δu is the design displacement at the top of a wall or segment equal to elastic displacement, δc,
due to code level seismic forces multiplied by Cd, the deflection amplification factor given in
governing codes
hw is the height of entire wall or wall segment
The displacement-based approach is founded on the assumption that the inelastic response of
the wall is due to flexural yielding at a critical section, typically at its base. Given this proviso, the
method of determining whether or not boundary elements are required is as follows:
• Analytically displace the wall at the top equal to the design displacement, δu. This dis-
placement is equal to the elastic displacement, δc, calculated for code seismic loads,
multiplied by a deflection amplification factor, Cd. Thus, δu = δc × Cd.
• Calculate the strain in the extreme compression fiver of the wall corresponding to the
horizontal displacement of δu. Since the strain is related to the depth of neutral axis, c, it is
used indirectly for evaluating the strain. Equation 21.8 of ACI 318/05 is used to calculate c.
The depth c may be considered, in a conceptual sense, as an index depth of neutral axis
for comparing against the actual depth calculated for the largest ultimate load, Pu, and the
corresponding moment, Mn.
• Next, compute the neutral axis depth c, using a linear strain distribution (Section 10.2),
or by assuming yielding of all vertical reinforcement in compression or tension. The lat-
ter is recommended by the 1999 Blue Book of the Structural Engineers Association of
California (SEAOC). The depth c is calculated for the factored axial force and nominal
moment strength consistent with the displacement, δu, at the top of the wall resulting in the
largest neutral axis depth.
• If the calculated value of c is greater than the index value, then special boundary elements
detailed are similar to those of a ductile column.
For the example wall, we have the following two load combinations:
Using the PCACOL column design program, the depth of the neutral axis was found to be 108 in.
The term δu is design displacement defined as the lateral displacement expected for the design-
based earthquake. It is invariably larger than the elastic displacement, δe, calculated for code-level
forces applied to a linear elastic model. Although the analysis may consider the effects of cracked
sections, torsion, PΔ forces, and foundation flexibility, it does not account for the expected inelastic
response. Thus, δu is calculated by multiplying δe by a deflection amplification factor Cd given in
the governing codes or standards. For example, ASCE 7-05 and IBC-06 specify Cd = 5.5 and 6.5
for special reinforced concrete moment fames and dual systems consisting of SMRF and special
reinforced concrete walls. For the example problem, having a building system of special reinforced
concrete wall, Cd = 5.0, by both ASCE and IBC.
The elastic deflection δe of the shear wall at the roof level = 2.15 in., as obtained from a linear
elastic analysis of the building under code-prescribed seismic forces. This is given in the statement
of the problem.
Seismic Design Examples and Details 585
Therefore
Cd δ e 5 × 2.15
δu = = = 10.75 in.
IE 1
δ u 10.75
= = 0.0076 > 0.007(min)
hw 18 × 12
lw
c= = 366/(600 × 0.0076) = 80.26 in. < 108 in.
⎛ hw ⎞
600 ⎜ ⎟
⎝ lw ⎠
Special boundary elements are therefore required. It is interesting to note that for the example wall, both
the stress index and the strain index methods lead to the same conclusion, namely, that boundary
elements are required. This may not be the case in all designs. A more likely scenario would be for the
stress index method to show that boundary elements are required, while the strain method does not.
Although ACI 318-05 does not require both criteria to be satisfied, many engineers choose to detail the
boundary zones as required by the stress index method. Keep in mind, in seismic design, more is less!
• The required width of boundary element is given by the larger of c − 0.1lw and c/2
• Where required, special boundary elements are extended from the critical section a distance
not less than lw or Mu /4Vu
For the example wall, the width of boundary element is the larger of
C = 0.1 lw = 108 − 0.1 × 366 = 71.4 in. ← controls
c/2 = 108/2 = 54 in.
Considering the placement of vertical bars, detail a boundary element for a width of 75 in.
(Figure 6.32).
15 ft 3 in. CL
75 in.
Width of boundary element
The vertical extension of the boundary element must not be less than
lw = 366 in. or ← controls
Mu /4Vu = 71,000 × 12/1400 = 608.6 in.
The confinement of 16 × 75 in. boundary elements:
Confinement perpendicular to the wall: The maximum allowable spacing of hoops and crossties,
assuming #5 bars,
Smax = 0.25 × minimum member dimensions
= 0.25 × 16 = 4 in. (Controls)
= 6 × diameter of longitudinal bar
= 6 × 1.41 = 8.5 in.
= sx = 4 + (14 − bx /3) = 4 + (14 − 10/3) = 5.33 in.
The required cross-sectional area of confining reinforcement Ash, in the 16 × 75 in. boundary
elements, using s = 4 in., is given by
No. 5 hoops with two legs provide Ash = 2 × 0.31 = 0.62 in.2 > 0.36 in.2
With two hoops consisting of two legs each, and five crossties,
Ash provided = 9 × 0.31 = 2.79 in.2 > 2.13 in.2
In most designs, special boundary elements may not be required by calculations for the entire
height of walls. However, to prevent the buckling of boundary longitudinal elements even in cases
where they are not done by design, Section 21.7.6.5 requires transverse ties not exceeding a vertical
spacing of 8 in., if the vertical reinforcement ratio is greater than 400/fy. The transverse reinforce-
ment shall consist of either single or overlapping hooks. As in ductile columns, crossties are per-
mitted. For calculating the ratio 400/fy, only the reinforcement within the wall boundary element is
included.
Using the most common value of fy = 60,000 psi, the ratio 400/fy = 400/60,000 = 0.0067. If the
ratio of vertical reinforcement is greater than this value, then hoops supplemented with crossties
are required. What if the ratio of vertical bars placed in between the boundary zones is greater
than 0.0067? Do they also need to be tied? Yes, but only if the vertical reinforcement ratio is
greater than 0.01, or where the vertical reinforcement is required as a compression reinforcement
(see Section 14.3.6). A schematic placement of reinforcement is shown in Figure 6.33.
Seismic Design Examples and Details 587
30 ft 6 in.
16 in.
Roof
10th floor
9th floor
8th floor
9 @ 13 ft 0 in. = 17 ft 0 in.
7th floor
133 ft 0 in.
6th floor