Coolmay: QM3G HMI/PLC All-In-One Programming Manual
Coolmay: QM3G HMI/PLC All-In-One Programming Manual
V21.81
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Catalog
1. Overview............................................................................................................1
1.1. QM3G-FH PLC/HMI All-in-one Main Advantage:................................ 1
1.2. Specification.............................................................................................. 3
1.3. Hardware description............................................................................... 4
1.3.1. QM3G-43FH structure description and dimension......................4
1.3.2. QM3G-50FH structure description and dimension......................5
1.3.3. QM3G-70KFH structure description and dimension...................6
1.3.4. QM3G-70FH/HD structure description and dimension...............7
1.3.5. QM3G-100FH structure description and dimension................... 8
1.3.6. Introduction of each interface and indicator................................. 9
2. PLC................................................................................................................... 10
2.1. Precautions for PLC programming...................................................... 10
2.2. Soft element table...................................................................................11
2.3. Special relay number and content....................................................... 13
2.4. Special register number and content...................................................18
2.5. Function application instructions (Contrast with Mitsubishi FX3G
PLC instruction)........................................................................................................ 22
2.6. Analog input.............................................................................................31
2.6.1. Analog input type............................................................................31
2.6.2. Analog input reading......................................................................32
2.6.3. Sampling of analog input.............................................................. 34
2.6.4. Example of analog input................................................................34
2.7. Analog output.......................................................................................... 37
2.8. PID instruction.........................................................................................38
2.9. Application of high speed counter........................................................43
2.9.1. Assignment table of built-in high speed counter....................... 43
2.9.2. Related soft element......................................................................44
2.10. Application of high speed pulse......................................................... 45
2.10.1. High speed pulse output............................................................. 45
2.10.2. Circular interpolation....................................................................46
2.10.3. Pulse width modulation PWM.................................................... 51
2.10.4. Handwheel pulse function.......................................................... 54
2.11. PLC communication port instruction................................................. 57
2.11.1. MODBUS instruction explanation and communication address
.....................................................................................................................................57
2.11.1.1. Function and operation description of read/write data
command................................................................................................................... 57
2.11.1.2. ADPRW instruction function and operation description 58
2.11.1.3. Word device communication address number................59
2.11.1.4. Bit device communication address number.................... 60
2.11.1.5. ADPRW instruction function parameters......................... 60
2.11.2. Serial port 2: RS485 (A B).......................................................... 61
I https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
II https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
1. Overview
1.1. QM3G-FH PLC/HMI All-in-one Main Advantage:
◆Upper computer programming software compatible with Works 2/GX
Developer8.86 (supports Ladder diagram and SFC language, does not support
structured programming/labels).
◆Powerful, compatible with FX3G/FX3U/FX3S PLC, high processing
speed.
◆Military level 32 bit CPU adopted, which is faster and more adapted to
industrial environment of high electromagnetic interference.
◆Special encryption, prevent illegal reading thoroughly. 8-bit encryption,
12345678 as password can thoroughly prevent reading of ladder logic
program.
◆Clock supported, rechargeable battery adopted.
◆Default with 1 HMI download port, 2 PLC programming ports
(RS232/MiniB USB port or Type-C), and one USB port.
◆7 inch and 10 inch HMI/PLC all-in-one, PLC is optional to add 1 485 or 2
485(One of the 485 ports is changed from the default 232 port)/CAN/network
port/WIFI(which will occupy the default port 232); HMI defaults to 1 RS232,
optional 1 RS485. 43FH/50FH, PLC is optional to add 1 485 or 2 485(When 2
485 are selected, one of the 485 ports is specially changed from the default
232); HMI defaults to 1 RS232. Used for external equipment such as HMI and
converter.
◆Support Mitsubishi programming protocol/MODBUS protocol/RS
protocol/BD board protocol, easily realize PLC interconnection and
communication with external devices.
◆High-speed counting, conventionally single-phase 6 channels 60KHz or
AB (Z) phase 2 channels 60KHz + AB phase 1 channel 10KHz. High-speed
pulse, conventionally 8 channels: Y0-Y3 is 100KHz, Y4-Y7 is 10KHz.
High-speed counting+ High-speed pulse cannot exceed 480KHz; acceleration
1 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
2 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
1.2. Specification
Model QM3G-43FH QM3G-50FH QM3G-70FH QM3G-70KFH QM3G-100FH
Image
1 RS485 or 2 RS485
COM ports (RS485 port 1 RS485 or 2 RS485 COM ports (one is changed from
1 RS485 or 2 RS485 COM ports (one of on HMI and RS232 on the default RS232 port)
Optional COM which is changed from the default RS232 PLC will be unavailable)
port port);
1 WIFI (occupy default RS232 port)
CAN (2.0A/B) port, Ethernet port, WIFI (will occupy default RS232 port)
AO type (optional) 0~10V /0~5V/ 0~20mA/ 4~20mA/ mixed 0~10V /0~5V/ 0~20mA/ 4~20mA/ mixed/
-5~5V/ -10~10V (2AO for 1 minus voltage)
3 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
4 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Power indicator
Communication
indicator
PLC running
indicator
5 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
6 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
7 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
8 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
9 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
2. PLC
2.1. Precautions for PLC programming
The PLC is compatible with GX Developer8.86/GX Works2 and below. If you
use other versions of software, incompatibility may occur.
When the PLC program is downloaded, there is a prompt error: Cannot
specify the com port,
GX 8.86 software: Online-Transfer settings change com port;
Works 2: All targets-Change the com port in all connected targets;
If there is a communication abnormality, cable abnormality and other
prompts, remove it by cutting off the power, checking the cable, checking
whether the power supply is normal, or replacing the computer.
In the GX Developer8.86 software version, choose the figure:
In the Works 2 software version, choose the figure: (Note: the label is
forbidden)
10 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
11 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Name Content
Data register (32 bits when used in pairs)
General (16 bit) D0~D127 128 points
EEPROM hold (16 bit) D128~D7999 7872 points
D8000~
Special (16 bit) 512 points
D8511
V0~V7,Z0~
Index (16 bit) 16 points
Z7
Extended register·extended file register
R0~R22999 23000 points Support power-off retention
Extended register(16 bit) R23000~
1000 points for system internal
R23999
Pointer
JUMP,CALL branch P0~P1280 1281 points CJ instruct、CALL instruct
Input interrupt I0□□~I5□□ 6 points
Timer interrupt I6□□~I8□□ 3 points
Counter interrupt I010~I060 6 points
Nest
Master control N0~N7 8 points MC instruct
Constant
16 bit -32,768~+32,767
Decimal (K)
32 bit -2,147,483,648~+2,147,483,647
16 bit 0000~FFFF
Hexadecimal (H)
32 bit 00000000~FFFFFFFF
-1.0×2128~-1.0×2-126,0,1.0×2-126~1.0×2128
Real number (E) 32 bit
Can be expressed in decimal and exponential form
※1: The 10ms timer will be affected by the scan cycle. If the scan period is
12ms, the timer becomes 12ms and executes once.
12 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
13 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
14 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
15 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
16 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
17 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
18 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
19 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
20 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
21 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
22 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
23 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
3.Comparison instructions
Mnemonic FNC No. Function Support
LD= 224 Contact compare LD (S1)=(S2) ★
LD> 225 Contact compare LD (S1)>(S2) ★
LD< 226 Contact compare LD (S1)<(S2) ★
LD<> 228 Contact compare LD (S1)≠(S2) ★
LD<= 229 Contact compare LD (S1)≦(S2) ★
LD>= 230 Contact compare LD (S1)≧(S2) ★
AND= 232 Contact compare AND (S1)=(S2) ★
AND> 233 Contact compare AND (S1)>(S2) ★
AND< 234 Contact compare AND (S1)<(S2) ★
AND<> 236 Contact compare AND (S1)≠(S2) ★
AND<= 237 Contact compare AND (S1)≦(S2) ★
AND>= 238 Contact compare AND (S1)≧(S2) ★
OR= 240 Contact compare OR (S1)=(S2) ★
OR> 241 Contact compare OR (S1)>(S2) ★
OR< 242 Contact compare OR (S1)<(S2) ★
OR<> 244 Contact compare OR (S1)≠(S2) ★
OR<= 245 Contact compare OR (S1)≦(S2) ★
OR>= 246 Contact compare OR (S1)≧(S2) ★
CMP 10 Compare ★
ZCP 11 Zone Compare ★
ECMP 110 Floating Point Compare ★
EZCP 111 Floating Point Zone Compare ★
HSCS 53 High speed counter set ★
HSCR 54 High speed counter reset ★
HSZ 55 High Speed Counter Zone Compare ★
HSCT 280 High speed counter table compare ★
BKCMP= 194 Block compare (S1)=(S2) ★
BKCMP> 195 Block compare (S1)>(S2) ★
BKCMP< 196 Block compare (S1)<(S2) ★
BKCMP<> 197 Block compare (S1)≠(S2) ★
BKCMP<= 198 Block compare (S1)≦(S2) ★
BKCMP>= 199 Block compare (S1)≧(S2) ★
24 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
25 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
7.Rotate instructions
Mnemonic FNC No. Function Support
ROR 30 Rotation Right ★
ROL 31 Rotation Left ★
RCR 32 Rotation right With Carry ★
RCL 33 Rotation Left with Carry ★
8.Shift instructions
Mnemonic FNC No. Function Support
SFTR 34 Bit Shift Right ★
SFTL 35 Bit Shift Left ★
SFR 213 Bit Shift Right with Carry ★
SFL 214 Bit Shift Left with Carry ★
WSFR 36 Word Shift Right ★
WSFL 37 Word Shift left ★
SFWR 38 Shift Write [FIFO/FILO Control] ★
SFRD 39 Shift Read [FIFO Control] ★
POP 212 Shift Last Data Read [FILO Control] ★
26 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
27 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
28 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
29 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
30 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
31 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
The transmitter integrated inside the PLC is one or a mixture of the above
types. When ordering, you can choose one or more of them mixed to order.
32 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
When the analog input has a thermocouple type, only 15 channels can be
used, and AD4 is the ambient temperature of the thermocouple. When there is
no thermocouple type, 16 channels can be used.
For 4-20mA type, the register reads less than 3.8mA and the value is 32760,
which is the disconnection value.
The value of the thermistor NTC is shown in the following table:
NO. Register value
AD0 R23660
AD1 R23661
AD2 R23662
AD3 R23663
AD4 R23664
AD5 R23665
AD6 R23666
AD7 R23667
AD8 R23668
AD9 R23669
AD10 R23670
AD11 R23671
AD12 R23672
AD13 R23673
AD14 R23674
AD15 R23675
R23960 starts with the zero point correction value, and the default value is 0
(that is, the size correction).
The 16 registers starting with R23620 are the corresponding values of
0~10V or 0~20mA, which are real-time sampling values.
The type of analog input needs to be set, refer to the following table:
Read
Register NO. Type Remark
value
R23940~R23955 0 0~10V(or 0~20mA) The four types of analog
R23940~R23955 1 4~20mA input types use different
R23940~R23955 2 PT100\PT1000 hardware. After the read
value is set, it cannot be
R23940~R23955 3 10K\50K\100K NTC
changed.
R23940~R23943 K-type thermocouple The thermocouple type is
4
R23945~R23955 positive temperature not much different in
33 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
That is, the setting of R23944 on the fifth channel must be less than 4.
34 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Connect the signal end of the temperature sensor to the AD0 input port of
the PLC, and connect the other end to the GND of the analog input port. When
the PLC is running, the value of the data register D8030 corresponding to AD0
will be transferred to D0, the value of D0 will be put into D10 after floating-point
operations, and then floating-point division operations will be performed on
D10, the result of the operation will be put into D20, and the result D20 is The
actual temperature value. In the ladder diagram, you can also directly divide
the value of D8030.
Note: When the input is 0-10V analog, the actual analog value = register
reading/400;
When the input is temperature, the actual temperature value = register
reading/10;
When the input is 0-20mA analog quantity, the actual analog value = register
reading/200;
When the input is 4-20mA analog quantity, the actual analog value = register
reading/250+4.
The analog correction is corrected for the size.The following figure is an
example of correcting the temperature of AD0 after acquisition:
35 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
In the above figure, when M0 is closed, the value -100 is sent to the
correction register R23960. At this time, it can be seen that the value of the
actual measured temperature D20 is close to the actual temperature of 37.9°C.
36 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
For example:
0-10V voltage analog output is shown in the figure below.
At this time, use a multimeter to check the DA0 terminal voltage, that is,
connect the red pen of the multimeter to the DA0 terminal and the black pen to
the GND terminal, you can see that the multimeter has a 5V voltage value
display.
37 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Parameter description:
38 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Setting item
Setting item Content Occupied points
Set target value (SV)
S1. Target value(SV) 1 point
PID instruction does not change the setting contents
S2. Measured value(PV) The input value of the PID operation 1 point
Auto-tuning: step response method
a) ACT setting:when bit1,bit2,bit5 are all not
"0",occupy 25points Soft Component starting from the 25 points
S3. Parameter Initial Soft Component specified in S3.
b) ACT setting:when bit1,bit2,bit5 are all "0",occupy 20 points
20points Soft Component starting from the Initial Soft
Component specified in S3.
Auto-tuning: step response method
Set the step output value on the user side before the
1 point
D. Output value (MV) instruction is driven.
During the auto-tuning process, the MV output cannot
be changed on the side of the PID instruction.
39 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
S3.+7
PID operation internal processing occupied, please do not change the data.
S3.+19
40 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
*1: When S3+1 action setting (ACT) bit1=1, bit2=1 or bit5=1, S3+20~24 is
occupied.
4.Notice
When using multiple instructions: It can be executed multiple times at
the same time (the number of loops is not limited), but note that the S3 and D
devices used in the operation cannot be repeated.
Occupied points of parameter S3. : Step response method
1)ACT setting:when bit1,bit2,bit5 are all not "0",occupy 25points Soft
Component starting from the Initial Soft Component specified in S3.
2)ACT setting:when bit1,bit2,bit5 are all "0",occupy 20points Soft
Component starting from the Initial Soft Component specified in S3.
Step response mode: The self-tuning mode in the PID instruction has only
a step response mode, and the step value is S0+22, which is the upper limit
value.
When specifying the soft component in the power failure holding area:
If D. is specified in the program to hold the data register in the power failure,
needs to clear the specified register at the time of program start-up.
Action flag:
bit 0=0 of S3+1 is positive action,bit 0=0 is reverse action;
When heating, is reverse action.
5.For example
41 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
42 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
43 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
44 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
45 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
46 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
47 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Note 1: The current address of X and Y must be on the same circle as the
destination address.
Note 2: When the current address coincides with the target address, it
indicates that the motion track is a full circle.
In the radius interpolation: D100 is speed, D102 is the X-axis target
address, D104 is the Y-axis target address, and D106 is the radius length. Y0
and Y1 respectively pulse the X-axis and Y-axis.(The example below is
clockwise, i.e. M8435=0)
48 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
49 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
=0:clockwise rotation
b7~b4 =1:counterclockwise rotation
= any other value: linear mode
=1:relative position
b11~b8
=2:absolute position
=00000:continuous interpolation execution
b31~b12
=AAAAA:continuous interpolation stop
PS: When using linear mode interpolation, b7~b4 is ignored and can be set
to any value from 2~F.
S1. and S2. may be set discontinuous. For example, S1.=D100,
S2.=D120.
S2. Must be consecutive with the next four 32-bit registers. For example,
it must be set to D102, D104, D106, D108, D110.
Example: draw a line and two arcs, as shown:
Program as below :
50 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
51 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Parameter Description:
Operand
content type of data Character device Ranges
type
Pulse width (ms) data or word device KnX、KnY、KnM、KnS、T、 0~32767
S1. BIN16 bit
number for storing data C、D、R、V、Z、K、H ms
Cycle (ms) data or word device KnX、KnY、KnM、KnS、T、 1~32767
S2. BIN16 bit
number for storing data C、D、R、V、Z、K、H ms
D. Output pulse device (Y) number BIN16 bit Y0-Y7 Y0-Y7
4.Sample program
In this example, the data range of D10 is changed from 0 to 50, and the
average output of Y0 is 0 to 100%. If the data of D10 is greater than 50, an
error will occur.
Example of smooth loop:
52 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
R >> P
t = R(KΩ) * C(µF) = 470ms >>T0
The time constant τ of the filter is a very large value compared to the pulse
period T0.
The fluctuation value Δe in the average output current e is approximately
5.Special instructions
Conventional PWM
1) Support Y0-Y7 total 8 channels (please select transistor MT output);
2) There are no restrictions on pulse width and cycle, both in milliseconds
(ms).
Special customized PWM-analog output port
The following parameters need to be provided during customizing selection:
1) The output voltage of the required PWM;
2) The output frequency of the required PWM;
3) Confirm the numbers of customized PWM, up to 8 PWMs. (depending
on analog outputs that customer make).
4) Customize whether PWM coexists with other analog quantities. (If the
product is additionally equipped with analog, analog output terminals
DA0~DA3 are a group, DA4~DA7 are a group. When QM3G
customizes PWM, the output frequency can only be installed with other
analogs in a group when the output frequency is only 21KHz ).
Special customized PWM - output frequency setting
When customizing the PWM, you do not need to use the PWM command,
53 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
just set the special register and then turn on the hardware.
The special registers used by each analog quantity correspond to the
following table.
Analog output
DA0 DA1 DA2 DA3 DA4 DA5 DA6 DA7
address
Duty cycle
D8050 D8051 D8052 D8053 D8054 D8055 D8056 D8057
setting
PWM frequency
division coefficient D8268 D8268 D8268 D8268 D8278 D8278 D8278 D8278
setting
D8050 to D8057: the corresponding duty cycle, the value range is 0~4000,
each 1 is 0.025%, and the total corresponds to 0~100%;
D8268 and D8278: the value range is 1~100000Hz (32 bits);
D8050 to D8057 ≦ D8268 and D8278
When D8268 and D8278 are powered on, the default setting is 21000Hz,
and the power is not maintained. Program assignment is required when using.
54 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Parameter Description:
Operand type content type of data Character device
Set the numerator of the input to
S1. BIN16 set K、D
output ratio
Set the denominator of the input to
S2. BIN16 set K、D
output ratio
Pulse:Y0-Y5
D. Output pulse device (Y) number BIN16 set Corresponding direction:
Y10-Y15
PS: When setting S1. and S2., S1. must be an integer multiple of S2. If it is
1:1, it means that the hand wheel rotates one pulse and the motor rotates one
pulse; if it is an integer multiple of n, it means that the hand wheel rotates one
pulse and the motor rotates n pulses;
The function program of the hand wheel is shown in the figure below:
55 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
This program is 1:1 pulse output, that is, how many pulses will Y0 output
when the handwheel rotates how many pulse.
56 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
address
When PLC is used as the host, it supports ADPRW instruction, RD3A
instruction and WR3A instruction. This section explains these three
commands.
57 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Modbus.
m1 represents the station number of the slave device to be written, ranging
from 1-247.
m2 represents the first address number of the written register in the slave
device;
S. indicates the number of registers to be written, the range is 1-123 (the
range is 1-45 in Modbus ASCII, and the range is 1-90 in CAN communication).
The data to be written is sequentially stored in the host S.+1, S.+2.
When S=1, WR3A instruction corresponds to Modbus function 06;
When S=2-123, WR3A instruction corresponds to Modbus No. 10 function;
S.-1 address value must be set (=0: serial port 2; =1: serial port 3; =2: CAN;
=3: network MODBUS)
RD3A and WR3A only support the following functions of MODBUS
RTU:
No. 03 function: read the holding register, and obtain the current binary
value range 1-125 in one or more holding registers.
No. 06 function: Load the specific binary value into a holding register (write
register), the range is 1.
No. 10 function: preset multiple registers, load specific binary values into a
series of continuous holding registers (write multiple registers), the range is
1-123.
58 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
ADPRW:
S. indicates the station number of the slave device to be read and written,
ranging from 1-247;
S1. Represents the function code (that is, the 01-06, 15, 16 functions written
above);
S2. The function parameter corresponding to each function code (for
example, the operand represents the start address of MODBUS when the
function is 01);
S3. The function parameter corresponding to each function code (for
example, the operand indicates the number of access points in the 01 function,
and the parameter is fixed to 0 in the 05 function);
D. Represents the starting position of the data storage device.
59 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
- 0x2140~0x7EFF R0~R23999
- 0x7F00~0xA13F Unused address
- 0xA140~0xA27F TN0~TN319
- 0xA280~0xA33F Unused address
- 0xA340~0xA407 CN0~CN199
- 0xA408~0xA477 CN200~CN255
- 0xA478~0xA657 M0~M7679
- 0xA658~0xA677 M8000~M8511
- 0xA678~0xA777 S0~S4095
- 0xA778~0xA78B TS0~TS319
- 0xA78C~0xA797 Unused address
- 0xA798~0xA7A7 CS0~CS255
- 0xA7A8~0xA7AF Y0~Y177
0xA7B0~0xA7B7 - Unused address
0xA7B8~0xA7BF - X0~X177
An error occurs when accessing an unused address
CN200~255 are 32-bit counters
60 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
61 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
M8196=1
MODBUS function M8192=1 -
M8125=1
RD3A/WR3A Receive correct
M8128 M8408 M8428 Automatic reset
mark
RD3A\WR3A communication
M8129 M8409 M8429 Automatic reset
over-time mark
ADPRW command completion
M8029 M8029 M8029 Command execution end mark
mark
Communication parameters D8120 D8400 D8420
Communication mode - D8401 D8421
D8434 D8434: CAN slave station NO
Master-slave station number D8121 D8414 D8440 D8440/D8442: multi-device
D8442 mode ID NO
Unit: ms (detailed setting,
RD3A/WR3A overtime D8129 D8409 D8429
refer to explanation)
RD3A/WR3A interval period D8126 D8406 D8426
RD3A\WR3A end operation -1 0 1 2
ADPRW command settings D8126=0 D8126=1 D8126=2
ADPRW command settings D8397=0 D8397=1 D8397=2
CAN data frame - - M8427
M8196: the activation flag of using programming port protocol and other
protocol.
M8125: the activation flag of using MODBUS and the original Mitsubishi
function.
M8122: RS sending flag (this bit needs to be set 1 when using the RS
instruction, and it will automatically reset after sending).
M8123: RS receiving completion flag ( need to reset manually).
M8124: RS command data is being received.
M8161: 8-bit/16-bit mode flag of RS instruction
M8128: RD3A / WR3A receive the correct flag.
M8129:RD3A/WR3A communication over-time flag. (when communication
is over-time, flag is ON)
M8029: Communication complete flag (communication complete flag when
using ADPRW instruction, manual reset is required)
D8120: Save the communication parameter settings of Modbus RTU
62 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
b1 Parity (b2,b1)
b2 00: None; 01: Odd; 11: Even
Stop bit
b3
0:1 bit
63 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
1: 2 bits
Program example:
The data obtained by using the serial port tool to monitor the serial port 2 is:
[2019:11:01:10:49:16] [Receive] 31 32 33
64 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Host program:
65 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Program explanation:
D300 saves the number of registers read, here it means reading 10 data.
When using serial port 2, D.-1, here D299 must be set to 0.
The program means to read a total of 10 data from registers D100-D109 in
the PLC whose slave station is 1, and save them in the registers D301-D310 of
the master station PLC.
66 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Slave program:
Program explanation:
The program means to write 1 data of register D301 in the master station
PLC to the slave station as 1 PLC, and save it in the slave station PLC register
D100.
67 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Host program:
Slave program:
Use the serial port tool to monitor the serial port 2 to get the following data:
[2017:11:01:17:48:54][ receive]01 03 00 00 00 06 C5 C8
[2017:11:01:17:48:54][ receive]01 03 0C 00 0C 00 17 00 22 00 38 00 4E 00
63 C4 29
68 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
chapter 2.11.2.3.
Note: In Modbus ASCII protocol, ADPRW command is not supported.
Program example:
Host program:
Slave program:
The data display status of the host D300~D303 before and after program
execution is shown in the figure below.
69 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
70 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
mark
Communication parameters D8120 D8400 D8420
Communication mode - D8401 D8421
D8434:CAN slave station
D8434
Number
Master-slave station number D8121 D8414 D8440
D8440\D8442 multi-device
D8442
mode ID Number
Unit: ms (detailed
RD3A/WR3A overtime D8129 D8409 D8429
setting,refer to explanation)
RD3A/WR3A interval period D8126 D8406 D8426 26232 or higher version
RD3A/WR3A end operation -1 0 1 2
ADPRW command settings D8126=0 D8126=1 D8126=2
ADPRW command settings D8397=0 D8397=1 D8397=2
CAN data frame - - M8427
M8192: Use the programming port protocol and the enable flag of other
protocols.
M8402: Send flag (used in RS2 command).
M8403: Communication end flag (communication end flag when using RS2
instruction, needs to be reset manually).
M8404: Data receiving.
M8408: Communication completion flag (valid when using RD3A and WR3A
for MODBUS communication, manual reset is required).
M8409: Communication timeout.
M8029: Communication completion flag (communication completion flag
when using ADPRW instruction, manual reset is required).
M8161: 8-bit/16-bit mode distinction flag for RS/RS2 instructions
D8400: Save the communication parameters of Modbus RTU protocol, see
the setting introduction in the table for details.
D8401: Save the communication mode of serial port 3.
D8401=H0 means RS2 free communication mode.
For Modbus RTU: D8401=H11 means the PLC is the slave station;
D8401=H1 means the PLC is the master station.
For Modbus ASCII: D8401=H111 indicates that the PLC is a slave station;
71 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Select protocol
1: MODBUS protocol
72 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Master/slave setting
b4 0: MODBUS master
1: MODBUS slave
The data obtained by using the serial port tool to monitor the serial port 3 is:
[2017:11:01:11:49:16][ receive]31 32 32
RS2 command last parameter =1: Serial port 3;
=2: CAN.
73 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Slave program:
Use the serial port tool to monitor the serial port 3 data, and get the following
results:
[2017:11:01:09:00:11][receive]01 03 00 64 00 0A 84 12
[2017:11:01:09:00:11][receive]01 03 14 00 42 00 4D 00 58 00 58 00 63 00
74 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
37 00 2C 00 21 00 16 00 0B 9F C7
WR3A program example (refer to chapter 2.11.1.1 for instruction
introduction):
Host program:
Slave program:
Use the serial port tool to monitor the serial port 3 data, and get the following
results:
[2017:11:01:09:25:20][receive]01 10 00 64 00 08 10 00 0B 00 16 00 21 00
2C 00 37 00 42 00 4D 00 58 D1 6C
75 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Slave program:
Use the serial port tool to monitor data of serial port 3 , and get the following
results:
[2017:11:01:17:38:34][receive]01 04 00 00 00 06 70 08
[2017:11:01:17:38:34][receive]01 04 0C 00 15 00 20 00 2B 00 41 00 57 00
00 5F A7
76 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Demo program:
Master program:
Slave program:
The data display status of slave D100~D109 before and after program
execution is shown in the figure below.
77 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
78 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
79 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
80 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
81 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Slave program:
Monitoring the master station program, the master station D301-D316 has a
total of 16 data at the speed of subtracting 1 per second and changing
between 300-200.
82 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Slave program:
Monitoring the program of the slave station, a total of 16 data from the
stations D100-D115 can be changed between 200-400 at the speed of adding
1 per second.
83 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Slave program:
It means to communicate with the CAN port of the slave PLC through the
CAN port of this PLC, and read the 4-bit M0~M3 of the slave PLC to D0 of the
master PLC.
84 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
M8193:=1 Indicates that there is a network chip, and the network is ready
M8197:=1 Write the network address and reset automatically.
M8062:=1 Indicates MODBUS timeout, MODBUS_TCP is used.
M8063:=1 Indicates an IP address conflict.
D8395:Mitsubishi function and MODBUS_TCP switch
D8395=0:Mitsubishi function
D8395=1: MODBUS_UDP slave station
D8395=2: MODBUS_UDP master station
D8395=3: MODBUS_TCP slave station
D8395=4: MODBUS_TCP master station
D8395=5: EtherNet/IP slave (server)
D8397: When using MODBUS_TCP for ADPRW instruction, D8397 needs to
be set to 3.
R23800 and 23801 are router addresses. The default is 192.168.1.1. That is,
R23800=0XC0A8, R23801=0X0101.
R23802 and 23803 are the mask addresses, and the default is 0 .0. 0 .0.
85 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
86 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Slave program:
87 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Station No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Relay M8184 M8185 M8186 M8187 M8188 M8189 M8190 M8496 M8497 M8498 M8499 M8500 M8501 M8502 M8503
3.Link device
It is a device used to send and receive information between each
programmable controller. Depending on the station number set in the
corresponding station number setting and the mode set in the refresh range
setting, the device numbers and points used are also different.
88 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
1) In mode 0 (D8178=0):
Station
Station 0 Station 1 Station 2 Station 3 Station 4 Station 5 Station 6 Station 7
No.
Word
device (4 D10~D1 D20~D2 D30~D3 D40~D4 D50~D5 D60~D6 D70~D7
D0~D3
points 3 3 3 3 3 3 3
each)
Station Station Station Station Station Station Station
Station 8 Station 9
No. 10 11 12 13 14 15
Bit device
D80~D8 D90~D9 D100~ D110~ D120~ D130~ D140~ D150~
(4 points
3 3 D103 D113 D123 D133 D143 D153
each)
2) In mode 1 (D8178=1)
Station No. Station 0 Station 1 Station 2 Station 3 Station 4 Station 5 Station 6 Station 7
Word
device M1000~ M1064~ M1128~ M1192~ M1256~ M1320~ M1384~ M1448~
(32 points M1031 M1095 M1159 M1223 M1287 M1351 M1415 M1479
each)
Bit device
D10~ D20~ D30~ D40~ D50~ D60~ D70~
(4 points D0~D3
D13 D23 D33 D43 D53 D63 D73
each)
Station Station Station Station Station Station
Station No. Station 8 Station 9
10 11 12 13 14 15
Bit devices
M1512~ M1576~ M1640~ M1704~ M1768~ M1832~ M1896~ M1960~
(32 points
M1543 M1607 M1671 M1735 M1799 M1863 M1927 M1991
each)
Word
device D80~ D90~ D100~ D110~ D120~ D130~ D140~ D150~
(4 points D83 D93 D103 D113 D123 D133 D143 D153
each)
3) In mode 2 (D8178=2):
Station No. Station 0 Station 1 Station 2 Station 3 Station 4 Station 5 Station 6 Station 7
Bit devices
M1000~ M1064~ M1128~ M1192~ M1256~ M1320~ M1384~ M1448~
(64 points
M1063 M1127 M1191 M1255 M1319 M1383 M1447 M1511
each)
Word D10~ D20~ D30~ D40~ D50~ D60~ D70~
D0~D7
device (8 D17 D27 D37 D47 D57 D67 D77
89 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
points each)
Slave program:
90 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
2. Serial port 3
Such as serial port 2, only need the master and slave program to set D8394=3
3. CAN port
Master program:
Slave program:
91 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
3. HMI part
3.1. How to install mView software
(Please go to the official website :WWW.COOLMAY.COM to download the
latest version)
This chapter will detaily introduce the installation process of mView software.
Hardware requirements
The basic hardware requirements for installing mView editing software are
as follows:
1. Personal computer host: It is recommended to use a CPU of 80486 or
higher.
2. Memory: It is recommended to use more than 128MB RAM to expand the
memory.
3. Hard disk: The hard disk must have more than 100MB of space.
4. Display: General VGA or SVGA display card.
5. Mouse: Use a Windows compatible mouse.
6. Printer: Use a Windows compatible printer.
Before you install it, please check whether the computer hardware is as
above or higher. In order to avoid problems with hardware incompatibility,
please use the recommended specifications as much as possible. If you have
any questions, please contact our customer service.
Software source
You can enter our company's website WWW.COOLMAY.COM to obtain the
latest version of the software.
Installation steps (take the simplified Chinese version of mView as an
example), note that "mView ***" software version is subject to the official
website.
Select mView 13802.exe in the installer window to start the installer and
start the installation;
Set the storage path of the installation file, select the default, or enter the
92 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
address, or click the [Browse ...] button to select the address, and then
click the [Next] button;
Set the name of the saved folder. It is recommended to select the default and
click the [Next] button directly.
Choose whether to create a desktop shortcut icon, and then click the [Next]
button.
93 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Confirm the installation path and other installation information, and then click
the [Install] button to install.
94 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
95 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
96 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Choose either of the above two methods to open the mView programming
software, and the startup window will pop up when the application is opened,
as shown in the figure below. After the software is opened, it will follow the
menu bar [View] -> [Auxiliary Settings] -> [File]->Program automatically opens
the check box of the old project, to determine whether to start the last project
file when the software is opened, or not to open any file.
97 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
98 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
99 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Title bar: Displays the currently opened project path and file name, window
number, and window name.
Menu bar: A menu that displays various commands of CoolMayView. These
menus are all pull-down menus.
Standard toolbar: Shortcut buttons for placing some commands.
Corresponding buttons and editing tools for displaying files, editing,
printing and other functions.
Design components: Command buttons for component objects.
Screen management: The management window of the screen used by the
project.
Communication management: The project designer manages and sets the
window for communication with PLC or other serial devices.
Label management: Set labels for system variables and external variables to
facilitate users to quickly find the corresponding variables.
Status bar: Display the current operating status, human-machine interface
parameters, and communication equipment.
100 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
4.1.1.On-Line Run
This function needs to be connected to the controller, and the program will
modify the corresponding contacts and registers set by the controller during
execution. It can be used to verify whether the planned program can normally
act on the controller.
Before [On-Line Run], you need to set up the communication, as shown in
the figure below:
101 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Among them, COM1 and COM2 on the left of [Communication Setup] refer
to the communication ports on HMI, and the setting on the right is the set of
communication ports designated by the user on the PC side to simulate the
sex-corresponding communication ports of HMI side ,As shown below:
4.1.2.Off-Line Run
This function does not need to be actually connected to the controller, it can
be used to test the normal operation of the program and the verification of
various functions.
102 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
4.2.1.Download to HMI
Before downloading the program to HMI, you need to make communication
settings first, please select [HMI]→[Setup]→[Communication Setup], as shown
in the figure below:
103 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
104 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
4.2.3.Update HMI OS
Generally speaking, when the new version of mView software is updated, it
will be matched with the corresponding version of the OS. This OS supports
the old version of the planning software downwards, but if the user wants to
use the functions provided by the new version of the planning software, the
new version must be matched OS and HMI OS are updated as follows.
Step 1: Select [Tools]→[Update HMI OS].
105 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Step 3: Start downloading. (Note: During the OS download process, the HMI
must can not be powered off!)
106 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
Step 4: After the download is complete, restart the power of the HMI.
107 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
108 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
To make the uploaded program editable, you must add the decompiled
information before downloading the program, otherwise the uploaded program
can only be used for downloading, and the user cannot edit it.
Select [View]→[Option(H)]→[File], and tick [Add Decompiled Information].
As shown below:
109 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
110 https://en.coolmay.com/
Coolmay QM3G Series HMI/PLC All-in-one Programming Manual
111 https://en.coolmay.com/