0% found this document useful (0 votes)
401 views

Instruction Manual Edc 2: Compressed Air Dryers

This document provides instructions for installing, operating, and maintaining a compressed air dryer. It outlines important safety precautions including ensuring the dryer is depressurized and power is cut off before maintenance. The dryer uses a process of adsorption to remove moisture from compressed air using desiccant-filled cylinders that alternate between drying air and regenerating. Installation requirements include providing suitable space for maintenance and grounding electrical components according to codes. Daily, biannual, and annual maintenance tasks are also outlined.

Uploaded by

Tam
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
401 views

Instruction Manual Edc 2: Compressed Air Dryers

This document provides instructions for installing, operating, and maintaining a compressed air dryer. It outlines important safety precautions including ensuring the dryer is depressurized and power is cut off before maintenance. The dryer uses a process of adsorption to remove moisture from compressed air using desiccant-filled cylinders that alternate between drying air and regenerating. Installation requirements include providing suitable space for maintenance and grounding electrical components according to codes. Daily, biannual, and annual maintenance tasks are also outlined.

Uploaded by

Tam
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 17

INSTRUCTION MANUAL EDC 2

Installation, operation and maintenance

COMPRESSED AIR DRYERS

DENO MARINE COMPRESSED AIRSYSTEMS


Contact:

van der Giessenweg 49


2921 LP Krimpen a/d IJssel
The Netherlands
Tel : +31 180 442 288
Fax : +31 180 522 222
@ : [email protected]
www.denocomp.nl

Read this manual carefully before installation, operation or maintenance.

Pay close attention to ensure your safety when working on the on the machine.
Make sure that it’s completely depressurised, cooled down and power supply is
securely cut off before attending any adjusting or checking.

2
Table of Content

2. Safety Instructions 4
2.1 General
2.2 Installation
2.3 Equipment
2.4 Maintenance
3. Introduction 5
3.1 Serial no.
3.2 Purpose of this dryer
3.3 Decals on the dryer
3.4 General characteristics
3.5 Construction
3.6 Operation
4. Installation 7
4.1 Requirements
4.2 Transport
4.3 Connecting into the system
5. Operation 10
5.1 System start up
5.2 Dryer start up
5.3 Shut down
6. Maintenance 10
6.1 Daily
6.2 Twice a year
6.3 Yearly
7. Trouble shooting list 11
8. Appendix 13
8.1 Technical specifications
8.1.1 General
8.1.2 Dryer specifications
8.1.3 Nominal operating conditions
8.1.4 Operating conditions
8.2 Diagrams
8.2.1 Flow diagram
8.2.2 Electrical diagram
8.2.3 Pneumatic control (option)
8.2.4 Dimensional drawings
8.3 Spare parts

3
2. Safety

2.1 General
Compressed air and electricity can be dangerous. In addition to the usual safety
instructions the following safety directives and measures are most important:
- Safety valve conforming to local codes shall be installed by the user in
the final discharge line ahead of the first stop valve.
- Do not operate this equipment in excess of its rated capacity, pressure
and tem-perature, nor otherwise than in accordance with the instructions
contained in this manual.
- Operation of the equipment in excess of the conditions set forth in the
sales contract will subject it to stresses and strains which it was not
designed to withstand.
- Before doing any work involving maintenance, or adjustment, be sure the
electrical supply has been disconnected, and the dryer.s entire air system
has been vented of all pressure.
- Those responsible for installation of this equipment must provide suitable
grounds, maintenance clearance and lightning arrestors for all electrical
components as stipulated in the national and local codes applicable.
- Before starting the dryer, its maintenance instructions should be
thoroughly read and understood.
- The user is responsible for safe operating conditions. Parts and accessories
must be replaced if inspection shows that safe operation cannot be
assured.
- Installation, operation, maintenance and repair are only to be performed
by authorised, trained and skilled employees.
- If any statement in this manual does not comply with the local legislation,
the strictest standard is to be applied.
The safe operation of the dryer cannot be guaranteed when the above
mentioned regulations are not followed. Also, this may result in the dryer
performing below its stated capacity. Any deviations will invalidate the dryer.s
warranty.

2.2 Installation
In addition to the general construction procedures and local regulations, the
following instructions need to be emphasized:
- Installation, operation, maintenance and repair are only to be performed
by authorized, trained and skilled employees.
- Safety devices, protecting covers or insulations on the air dryer are never
to be dismantled or adjusted. Each pressure vessel or accessory installed
outside the air dryer and containing air above atmospheric pressure,
must be secured by the required pressure venting devices.

4
2.3 Equipment check
Before the dryer is to be put into operation, the following points are to be
considered:
- The piping must be of the correct diameter and be adjusted to the
operating presssure. Only use joints and connections of the fitting type
and correct diameter. Make sure that the system is depressurized, before
disconnecting a pipe.
- Never let the dryer operate at pressures below minimum or above
maximum limit values, as indicated in the technical specifications.

2.4 Maintenance
Maintenance and repair are only to be performed under the supervision of an
authorized person.
- Use appropriate tools only for maintenance and repair
- Maintenance is only to be performed when the air dryer is shut down and
depressurized and the main power switch is turned off.

3. Introduction

3.1 Serial no.


Adsorption Compressed Air Dryers covered by this manual:

Euro---dry 2
Euro---dry 3
Euro---dry 5
Euro---dry 7
Euro---dry 10
Euro---dry 17
Euro---dry 23
Euro---dry 36
Serial number 010013000 onwards

3.2 Purpose of this dryer


The Euro---dry adsorption compressed air dryer is designed to remove water
vapours from compressed air for industrial purposes.
This dryer is designed for indoor use.
The minimum and maximum values as stated in Part 8 must be observed, as well
as the safety precautions (Part 2).

5
3.3 Decals on the dryer
The following decals are present on the Euro---dry compressed air dryer:

Read the entire manual Warning: Voltage


before starting
the dryer

Compressed air outlet

Dew point too high


Compressed air inlet

Dew point correct

3.4 General characteristics


The Euro---dry compressed air dryer eliminates water vapour from compressed air.
Its construction is simple and it is therefore very reliable and easy to service. The
dryer has two cylinders, the so called adsorbers (see fig. 1), each containing
adsorbing material or desiccant. When one cylinder is drying, the other is being
regenerated. The moisture accumulated in the cylinder is removed from the
compressed air dryer during the regeneration by means of purge air.
The desiccant is a very porous grain material. This material can adsorb large
amounts of water vapour, but is not affected by water vapour.

1 Left cylinder

2 Right cylinder

3 Type plate

4 Moisture indicator

Fig. 1 Front panel removed

Each dryer is provided with a rating plate on which the type, serial number,
voltage and maximum operating pressure are indicated.

3.5 Construction
The aluminium cylinders contain drying cartridges (see fig. 1). The top and
bottom heads are held together by tie rods.

6
3.6 Operation
The description of the operating cycle starts when valve Y1 (see fig. 4, fig. 5,)
is energized and opens.
The entering moist compressed air is directed to one of the cylinders by shuttle
valve V1 and flows upstream through the drying cartridge, which adsorbs the
water and dries the air. The dried air flows through shuttle valve V2 to the dryer
outlet.
At the same time, a limited amount of dried compressed air is passed from the
dryer outlet in the top head and expanded to atmospheric pressure through
orifice O1. This regeneration air flows downwards through the other cylinder.
Because the vapour pressure of the regeneration air is much lower than that of
the desiccant, the desiccant is regenerated, i.e. restored to full adsorption
capacity. The regeneration air containing the adsorbed moisture is discharged
through the solenoid valve and the exhaust silencer.
After 95 seconds valve Y1 closes. The cylinder is slowly pressurized through orifice
O1. After a further 25 seconds solenoid valve Y2 opens. The pressure in the
cylinder is vented and shuttle valves V1 and V2 switch as a result of the pressure
difference between the two cylinders. The fully regenerated cylinder will now dry
the air while the other is being regenerated.

4. Installation

Installation, operation, maintenance and repair are only to be performed by


authorized, trained and skilled employees.

4.1 Requirements
When installing the Euro---dry adsorption compressed air dryer, the following
applies:
- Place the dryer at a location where the ambient air is as clean as
possible and where the temperature of the air never exceeds the
minimum or maximum values.
- Provide enough space around the dryer so that the purge air can
circulate freely.
- Maintain a free space of 1 metre minimum around the dryer for servicing.

4.2 Transport
To hoist the air dryer an adapted hoist must be used which complies with the
local safety instructions. Before hoisting, all loose or rotating parts must be
secured. It is strictly forbidden to stay in the danger zone under a hoisted load.
The acceleration or deceleration of the hoisting movement must remain
within safe limits.

7
4.3 Connecting into the system

4.3.1 Piping
To ensure correct operation of the Euro---dry air dryer it has to be properly fitted
into the compressed air system (see fig. 2).
Correct installation simplifies maintenance and the rectification of possible faults.

1 Euro---dry
A Inlet, moist air
B Outlet, dry air
BV1 Inlet valve
BV2 Outlet valve
BV3 Valve, before by pass
BV4 Valve, after by pass
F1 Prefilter, PF/HF or 810
F2 Afterfilter, PF
F3 Filter PF/HF or 810 by pass
Fig. 2 Compressed air system lay-out

It is essential to install appropriate prefilters to remove water and oil droplets to


prevent damage or contamination of the drying cartridges, to prevent
unnecessary overloading of the Euro---dry and to prolong the life of the dryer.
Always use of prefilters with an automatic drain.
It is recommended that an afterfilter is installed downstream of the Euro---dry to
remove possible dust from the dryer.
Deno Compressors BV recommends the following filters for these applications:
- Prefilter: PF + HF or 810 series
- Afterfilter: PF series
The installation of a bypass system allows the dryer and filters to be serviced while
the non-purified air flows through the bypass piping (only valid if permitted by the
particular application).
A filter in the bypass is recommended to protect the compressed air system at all
times against dirt, liquid water and oil.
For this purpose the PF/HF combination or the 810 series is recommended.
If during maintenance the passage of moist air is not acceptable, the installation
of a standby filter-dryer should be considered.
Plugs and caps must be removed before connecting the pipes.
To ensure troublefree operation, the airdryer must be positioned vertically.
Make sure while assembling that all valves and pipes are clean. Also check the
electrical connections of the Euro---dry compressed air dryer. The rear panel is
equipped with carriage holes to fix the dryer against a wall (see fig. 7). An
optional floor stand is available.
The incoming connection is on the lower side, the outgoing connection is on the
upper side.
Make sure that all pipes, filters, valves, etc. are clean. Install the piping and filter
system as shown on the installation lay---out (fig. 2).
No external force is to be exerted on air inlet and outlet pipes and the
connected pipe should not be live.

8
4.3.2 Electric wiring connections
The electrical connections must comply with the local regulations. The air dryers
must be earthed and protected by fuses in all phases against short-circuiting.
Before switching on the main power check the voltage requirements on the dryer
name plate.

4.3.3 Pneumatic control version


When the Euro---dry is fitted with the pneumatic control option, the reducer is
packaged separately from the dryer to prevent damage during transport.
To mount the reducer, screw the union on to the union counter part that is
already fitted into the dryer.
Push the hoses to the “push in Unions”, hoses and fittings with the same number
belong together (the primary pressure goes to the pneumatic switches, the
secondary pressure goes to the pneumatic timer motor).
The setting of the reducer determines the cycle time. The reducer is set to 4.2 bar.
This results in a cycle time of 2 minutes per tower.

4.3.4 Checks
Check if:
- All tubes and/or pipes in the air dryer are in proper condition, firmly
attached and do not rub.
- There are no leaks.
- All fixings are firmly attached.
- The electical connections are secured and in proper condition.
- Safety valves and other pressure venting devices are not plugged by dirt
or paint.
- The air outlet valve and the air system, i.e. pipes, joints, manifolds, valves,
tubes etc. are in proper condition without any wear or defect.

9
5. Operation

5.1 System start up


When the Euro---dry is installed it can be put into operation (see fig. 2):
1. Close bypass valves BV3 and BV4.
2. Close the valve (BV2) of the afterfilter (F2). Close the valve (BV1) at the
inlet of the prefilter (F1).
3. Start the compressor. Slowly open the inlet valve (BV1) at the prefilter.
4. Check the connections of the dryer for air leaks and repair if necessary.
5. Switch the power on.
6. Let the dryer operate for several hours with outlet valve (BV2) closed to
completely regenerate the drying cartridges.

5.2 Dryer start up


When the Euro---dry initial start up procedure is complete, it can be put into
operation. The (daily) start-up of the dryer is described below (see fig. 2):
1. If the dryer has not been used for over three months, the drying
cartridges must be regenerated, as described in the “System start up”
section above.
2. Switch the power on.
3. Gradually open the valve (BV2) of the afterfilter.
4. Close bypass valves BV3 and BV4 when necessary.

5.3 Shut down


To shut down the Euro---dry: 1. Open bypass valves BV3 and BV4 when necessary.
1. Open bypass-kleppen BV3 en BV4 in dien nodig.
2. Close the inlet valve (BV1) of the prefilter. Close the valve (BV2) of the
afterfilter.
3. Check the venting of the pressure through the silencers. When the
venting stops, the dryer is depressurized (when not, consult the trouble-
shooting list). Now turn off the dryer.

6. Maintenance

This chapter covers the periodic maintenance schedule. Please note the points
below when performing maintenance.
1. Use original replacement parts only.
2. Before doing any work involving maintenance, or adjustment, be sure
the electrical supply has been disconnected, and the dryer.s entire air
system has been vented of all pressure.
3. Use a damp cloth to clean the parts.
4. Never leave tools, loose parts or cleaning rags in or on top of the air
dryer.
5. Check the condition of the silencers of the air dryer. If it is not in good
condition, replace the damaged material, using genuine spare parts.
6. Check operating pressures, temperatures and time settings after
maintenance or revision. If operating and safety devices function properly,
the air dryer can be used.

10
6.1 Daily
- Check the correct operation of the automatic drain devices of the prefilters.
Prefilters without automatic drain have to be purged regularly.
- Regularly check the correct switching of the cylinders.
This can be observed by listening to the purge air sounds every 2 minutes.

6.2 Twice a year


The following points are to be checked at 6 month intervals:
1. Check for damaged wiring and loose connections.
2. Check the correct functioning of the PCB or the cam switch and the
solenoid valves.
3. Check the exhaust silencers for contamination.
When the silencers are contaminated, maintenance as shown in the
next paragraph is necessary.

6.3 Yearly
Annually, the dryer requires some extra attention.
To simplify the annual maintenance, we assembled a service set (as shown in the
spare parts list, part 8.3).
The life of the drying cartridges depends on the operating conditions.
Under normal circumstances, the dryer will retain its full drying capacity for 18000
to 20000 operating hours or 3 years, whichever comes first, after which the drying
capacity will reduce.
To maintain optimal performance, preventive maintenance needs to be
performed before the above mentioned period period ends.
For this preventive maintenance, a maintenance set is available (as shown in the
spare parts list, part 8.3).
This set contains all necessary parts, including drying cartridges.
The filter elements of the prefilters and afterfilters have to be replaced at least
once a year. They have to be replaced earlier if the pressure differential indicator
is within the orange or red coloured zone.

7. Trouble shooting

Before starting maintenance or repair on the dryer switch the power off,
depressurize the cylinders (see part 5) and take measures to prevent accidental
start-up of the dryer.
An electrical failure should be repaired by an electrician. He must make sure that
the wiring is not worn out, damaged or broken and that the clamps are tightly
connected.

11
Trouble shooting list
Cause Action
The power is switched on but the dryer does not
function or the cylinders fail to switch.
Remove the silencer(s) or the
silencer tube and check again
The exhaust silencer(s) is(are)plugged (wear ear protection!).
If the dryer functions properly in these
conditions, the silencer(s) need to be
replaced.*
The fuse has blown
The transformer (if present) is defective
Check and replace when necessary.
The PCB board is defective
The 4/2 way valve is defective
The dew point is too high or the moisture indicator has turned pink.
The operating pressure is too low.
The compressed air inlet temperature
Check and remedy
is too high.
when necessary
The compressed airflow exceeds the
dryer capacity.
Check the drain function.
The prefilter doesn’t purge, or the Dismantle and check the filters.
condensate is not regularly purged. If the filters are operated manually,
they need to be purged more often.
The cylinders fail to switch
See “The power switched on,
The cylinders remain under pressure
but the dryer does not fun tion or
The regeneration air exhaust silencers
the cylinders fail to switch”
are plugged
The throttle tube or the orifices are Dismantle and clean the top head.
plugged. Replace when necessary.*
Have the drying cartridges replaced
if all previous steps have been
The drying cartridge is contaminated
checked and proved to be in order.
or obsolete.
Do not forget that malfunctions
influence the dewpoint.*
Excessive pressure drop over filter—dryer combination
One of the filters is plugged. Replace the contaminated
filter elements.

* If the dryer functions properly after repair, the dryer needs maintenance as
shown in part 6. Fit the parts in the maintenance kit (see the spare parts list from
part 8.3 onwards)
Contact the service department when the problem can not be solved on the
basis of this trouble shooting list.

12
8. Appendix

8.1 Technical Specifications

8.1.1 General

Euro-dry type 2 3 5 7 10 17 23 36

Width B 237 237 237 237 237 362 362 362 Mm


Height H 653 653 653 941 941 824 824 1323 Mm
Dept D 137 137 137 137 137 198 198 198 Mm
Weight 13 13 17 19 24 37 43 64 Kg
Tread connect. 1/4 1/4 1/4 1/4 1/4 3/4 3/4 3/4 “bsp Fig. 3

8.1.2 Dryer specifications

Euro-dry type 2 3 5 7 10 17 23 36

Nom. Inlet Capacity


at 20ºC, 1bar, 5,8 9,7 17,5 22,4 33,4 56,1 77,4 120,9 M3/hr
Dew point -40ºC
Optional Capacity
3,8 6,3 11,4 14,1 21,7 36,5 50,3 78,6 M3/hr
Dew point -70ºC
Regenerated air con- 0,9 1,5 2,6 3,4 5,0 8,4 11,6 18,1 M3/hr
sumption (nom cap)
Pressure drop 0,01 0,02 0,08 0,11 0,26 0,07 0,11 0,32 Bar
Desiccant 1,3 1,3 2,9 3,2 5,1 7,9 10,8 21,4 Kg
Power consumption 47 47 47 47 47 47 47 47 W
Sound level at 1mtr 74 74 75 79 79 76 68 78 dB

8.1.3 Nominal operating conditions


Compressed air inlet pressure 7 bar(g)
Compressed air inlet temperature 35 ºC
Relative moisture at inlet 100 %
Pressure dewpoint -40 ºC
Mains voltage, switchable. 115-230 V
Check the fuse!

13
8.1.4 Operating conditions
min max
Compressed air inlet pressure 4 10.5 bar(g)
Ambient temperature 5 50 ºC
Compressed air inlet temperature 5 50 ºC

When one or more of there values change, the capacity of the dryer may increase or
decrease (with an equal compressed air inlet capacity) as shown in the graphs below.

Inlet pressure Inlet Temperature Pressure dew point

8.2 Diagrams

8.2.1 Flow diagram

1 Left drying vessel

2 Right drying vessel

4 Drying Cartridge

5 Wet compressed air (in)

6 Dry compressed air (out)

7 Silencer
O1
Orifice
O2
V1
Shuttle valve
V2
Y1
Solenoid valve Fig. 4
Y2

14
8.2.2 Electrical diagram

Item Description
F1 Fuse main voltage
F2 Fuse control voltage
H1 Power on Lamp
S1 “On/off switch”
S2 Voltage selection
X0 Plug
Y1 Solenoid valve
Y2 Solenoid valve
Y3 Solenoid valve *
Y4 Solenoid valve *
* ED2085-2090 only

S.valve Timer Total


230v P P I P I
Watt amp Watt amp Watt amp
Edc Y1/Y2 PCB
41 0,3
02-10 11 1,3 30 0,15
Edc Y1/Y2 PCB
47 0,35
17-36 17 0,15 30 0,15
Edc Y1,2-Y3,4 PCB
17 2,0 64 0,60
55-72 30 0,15

S.valve Timer Total


115v P P I P I
Timing Watt amp Watt amp Watt amp
Sec. Edc Y1/Y2 PCB
41 0,6
02-10 11 1,3 30 0,3
Edc Y1/Y2 PCB
47 0,7
17-36 17 0,15 30 0,3
Edc Y1,2-Y3,4 PCB
17 2,0 64 1,2
55-72 30 0,3
Fig.5 Electrical diagram

8.2.3 Pneumatic control (option)

BV5 Control air valve

M1 Cam timer motor

FR Filter – reducer

S1/1
Cam timer switches
S1/2

Y1
3/2 way valve
Y2
Fig.6 air dryer set-up

15
8.2.4 Dimensional drawings

Fig.7 Dimensional drawing Edc 02-10


Type H Li Lu C D G
Edc 02/03 653 120 360 200 393 G¼
Edc 05 653 120 493 200 393 G¼
Edc 07 941 150 601 230 641 G¼
Edc 10 941 150 781 230 641 G¼

Fig.8 Dimensional drawing Edc17-36


Type H Li Lu C D G
Edc 17 824 200 558 280 484 G¾
Edc 23 824 200 654 280 484 G¾
Edc 30 * 1323 350 982 430 833 G¾ * as special only
Edc 36 1323 350 1153 430 833 G¾

16
8.3 Spare parts

No. Part Qty 2 3 5 7 10 17 23 36


10 Front panel 1 0319075 0319075 0319075 0319078 0319078 0319080 0319080 0319082
16 Bottom head 1 0307001 0307001 0307001 0307001 0307001 0307003 0307003 0307003
17 Top head 1 0307000 0307000 0307000 0307000 0307000 0307002 0307002 0307002
18 Plug shuttle valve 2 0310447 0310447 0310447 0310447 0310447 0310455 0310455 0310455
Fuse 230v: 5x20 0,8A 1 0311779 0311779 0311779 0311779 0311779 0311779 0311779 0311779
F1
115v: 5x20 1,6A 1 0311780 0311780 0311780 0311780 0311780 0311780 0311780 0311780
F2 Fuse 230v: 5x20 5A 1 0260317 0260317 0260317 0260317 0260317 0260317 0260317 0260317
Pcb Control Pvb 1 3263100 3263100 3263100 3263100 3263100 3263100 3263100 3263100
S1 Switch 1 0234950 0234950 0234950 0234950 0234950 0234950 0234950 0234950
Y1 Valve 50/60hz 2 8066020 8066020 8066020 8066010 8066010 8066010 8066010 8066010
Y2 Valve pneumatic 2 0310059 0310059 0310059 0310040 0310040 0310040 0310040 0310040
*13 Service set, containing:
7 Silencer 2
15 O-ring for shuttle 2 0416178 0416178 0416178 0416300 0416300 0416203 0416203 0416301
21 Humidity indicator 1
V1 shuttle 2
*14 Maintenance set, cont: -40ºC -40ºC -40ºC -40ºC -40ºC -40ºC -40ºC -40ºC
4 Drying cartridge 2 0416176 0416176 0416180 0416222 0416224 0416204 0416207 0416226
11 O-ring drying cartridge 4 -70ºC -70ºC -70ºC -70ºC -70ºC -70ºC -70ºC -70ºC
13 Service set 1 0416177 0416177 0416181 0416223 0416225 0416205 0416208 0416227

Options
19 Pressure gauge 2 0317959 0317959 0317959 0317959 0317959 0317959 0317959 0317959
20 Floor stand 1 0311760 0311760 0311760 0311760 0311760 0311761 0311761 0311762
Element prefilter HF 1 6112200 6112200 6112200 6112200 6112200 6112200 6112300 6112500
22
810 1 6116200 6116200 6116200 6116200 6116200 6116200 6116300 6116400
23 Element afterfilter PF 1 6110200 6110200 6110200 6110200 6110200 6110200 6110200 6110500
FR Filter reducer 1 0333192 0333192 0333192 0333192 0333192 0333192 0333192 0333192
M1 Camtimer 1 0310035 0310035 0310035 0310035 0310035 0310035 0310035 0310035

Note 13 Service---set, contains all spare parts for annual service


14 Maintenance kit, contains all spare parts for maintenance after 18000 to 20000
operating hours or 3 years, whichever comes first.
* Recommended spare parts for 2 years of operation.

17

You might also like