Victaulic Reducing Coupling Style 750: 1.0 Product Description
Victaulic Reducing Coupling Style 750: 1.0 Product Description
2.0 CERTIFICATION/LISTINGS
NOTE
• Download publication 10.01 for Fire Protection Certifications/Listings Reference Guide.
ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT.
victaulic.com
06.08 1536 Rev M Updated 05/2020 © 2020 Victaulic Company. All rights reserved.
1
victaulic.com
06.08 1536 Rev M Updated 05/2020 © 2020 Victaulic Company. All rights reserved.
victaulic.com 2
victaulic.com
4.0 DIMENSIONS
Style 750 Reducing Coupling
Y Z Y Z
X X
Pipe End
Size Separation3 Deflect. From CL3 Bolt/Nut Dimensions Weight
Actual Outside Approximate
Nominal Diameter Allowable Per Cplg. Pipe Qty. Size X Y Z (Each)
inches inches inches in/ft inches inches inches inches lb
DN mm mm Degrees mm/m mm mm mm mm kg
2 1 2.375 1.315 0 - 0.07 0.20 3.38 5.28 1.88 2.7
x x 0° - 57' 2 3/8 x 2
DN50 DN25 60.3 33.7 0 - 1.8 17 85 134 48 1.2
1 1/2 1.900 0 - 0.07 0.20 3.38 5.28 1.88 2.0
0° - 57' 2 3/8 x 2
DN40 48.3 0 - 1.8 17 85 134 48 1.0
2 1/2 2 2.875 2.375 0 - 0.07 0.16 4.00 5.93 1.88 3.1
x x 0° - 47' 2 3/8 x 2
DN50 73.0 60.3 0 - 1.8 14 102 151 48 1.4
2 3.000 2.375 0 - 0.07 0.16 4.38 6.63 1.88 4.6
x x 0° - 47' 2 1/2 x 2 3/4
DN65 DN50 76.1 60.3 0 - 1.8 14 111 168 48 2.1
3 2 3.500 2.375 0 - 0.07 0.13 4.75 7.13 1.88 4.9
x x 0° - 39' 2 1/2 x 2 3/4
DN80 DN50 88.9 60.3 0 - 1.8 11 121 181 48 2.2
2 1/2 2.875 0 - 0.07 0.13 4.75 7.13 1.88 4.3
0° - 39' 2 1/2 x 2 3/4
73.0 0 - 1.8 11 121 181 48 2.0
3.00 0 - 0.07 0.13 4.75 7.13 1.88 4.2
0° - 39' 2 1/2 x 2 3/4
DN65 76.1 0 - 1.8 11 121 181 48 1.9
4 2 4.500 2.375 0 - 0.13 0.28 6.25 8.90 2.25 8.1
x x 1° - 19' 2 5/8 x 3 1/4
DN100 DN50 114.3 60.3 0 - 3.2 25 159 226 57 3.7
2 1/2 2.875 0 - 0.13 0.28 6.25 8.90 2.25 8.6
1° - 19' 2 5/8 x 3 1/4
73.0 0 - 3.2 25 159 226 57 3.9
3.000 0 - 0.13 0.28 6.25 8.90 2.25 6.9
1° - 19' 2 5/8 x 3 1/4
DN65 76.1 0 - 3.2 25 159 226 57 3.1
3 3.500 0 - 0.13 0.28 6.00 8.90 2.25 6.7
1° - 19' 2 5/8 x 3 1/4
DN80 88.9 0 - 3.2 25 152 226 57 3.0
5 4 5.563 4.500 0 - 0.13 0.22 7.18 10.70 2.13 11.2
x x 1° - 3' 2 3/4 x 4 1/4
DN100 141.3 114.3 0 - 3.2 19 182 272 54 5.1
4 6.500 4.500 0 - 0.13 0.19 8.63 11.90 2.25 15.2
x x 0° - 55' 2 3/4 x 4 1/4
165.1 DN100 165.1 114.3 0 - 3.2 16 219 302 57 6.9
6 4 6.625 4.500 0 - 0.13 0.18 8.63 11.90 2.25 16.7
x x 0° - 52' 2 3/4 x 4 1/4
DN150 DN100 168.3 114.3 0 - 3.2 15 219 302 57 7.6
5 5.563 0 - 0.13 0.18 8.31 11.90 2.25 12.9
0° - 52' 2 3/4 x 4 1/4
141.3 0 - 3.2 15 211 302 57 5.9
8 8.625 6.500 0 - 0.13 0.13 10.75 14.88 2.50 23.2
x x 0° - 38' 2 7/8 x 5
DN200 165.1 219.1 165.1 0 - 3.2 11 273 378 64 10.5
6 6.625 0 - 0.13 0.13 10.81 14.88 2.50 22.4
0° - 38' 2 7/8 x 5
DN150 168.3 0 - 3.2 11 275 378 64 10.2
10 8 10.750 8.625 0 - 0.13 0.90 13.12 17.26 2.62 31.4
x x 0° - 25' 2 1 x 5 1/2
DN250 DN200 273.0 219.1 0 - 3.2 8 333 438 67 14.2
3 Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe.
Figures for standard cut grooved pipe may be doubled. These figures are maximums; for design and installation purposes, these figures should be reduced by:
50% for ¾ – 3 ½"/DN20 – DN90; and 25% for 4"/DN100 and larger.
NOTE
• Metric thread size bolts are available (color-coded gold) for all coupling sizes upon request. Contact Victaulic for details.
06.08 1536 Rev M Updated 05/2020 © 2020 Victaulic Company. All rights reserved.
victaulic.com 3
victaulic.com
5.0 PERFORMANCE
Style 750 Reducing Coupling
06.08 1536 Rev M Updated 05/2020 © 2020 Victaulic Company. All rights reserved.
victaulic.com 4
victaulic.com
5.1 PERFORMANCE
Flow Data - Head Loss
Equivalent lengths of standard weight steel pipe are shown in the tables. All data is based on water flowing at
+60°F/+16°C.
06.08 1536 Rev M Updated 05/2020 © 2020 Victaulic Company. All rights reserved.
victaulic.com 5
victaulic.com
6.0 NOTIFICATIONS
WARNING
• Victaulic RX roll sets must be used when grooving light-wall/thin-wall stainless steel pipe for use with Victaulic
Couplings.
Failure to use Victaulic RX roll sets when grooving light-wall/thin-wall stainless steel pipe may cause joint failure,
resulting in serious personal injury and/or property damage.
WARNING
• Read and understand all instructions before attempting to install, remove, adjust, or maintain any Victaulic pip-
ing products.
• Depressurize and drain the piping system before attempting to install, remove, adjust, or maintain any Victaulic
piping products.
• Wear safety glasses, hardhat, and foot protection.
• Only No. 61 bull plugs shall be used with Style 750 reducing couplings in systems where a vacuum may de-
velop.
Failure to follow these instructions could result in death or serious personal injury and property damage.
NOTICE
• Victaulic does not recommend the use of any furnace butt-welded pipe with sizes NPS 2”/DN50 and smaller
Victaulic gasketed joint products. This includes, but is not limited to, ASTM A53 Type F pipe.
06.08 1536 Rev M Updated 05/2020 © 2020 Victaulic Company. All rights reserved.
victaulic.com 6