ASENWARE AW-FP 300 Addressable Input Output Module User Manual

The AW-D319 Addressable I/O Module is used with fire alarm control panels to control fire equipment and receive feedback. It has one output contact that can control equipment, voltage inputs and outputs, and indicators to show operation. The document provides instructions on installation, wiring, setting jumpers and addresses, and testing the module. Precautions include not connecting to AC power and properly setting the equipment type.

Uploaded by

linggau fe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
290 views3 pages

ASENWARE AW-FP 300 Addressable Input Output Module User Manual

The AW-D319 Addressable I/O Module is used with fire alarm control panels to control fire equipment and receive feedback. It has one output contact that can control equipment, voltage inputs and outputs, and indicators to show operation. The document provides instructions on installation, wiring, setting jumpers and addresses, and testing the module. Precautions include not connecting to AC power and properly setting the equipment type.

Uploaded by

linggau fe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Version: V1.

0 Apr 28th,2018

Instruction Manual of AW-D319


Addressable I/O Module
----- Please read this Manual carefully before installing and using the product. -----
I. Overview
The AW-D319 Addressable I/O Module (AW-D319 for short) is used with AW-FP300 fire alarm control
panel. It is mainly used to realize an output control for fire linkage equipment (such as smoke dampers,
blow valves and fire dampers) and receive the feedback signals of the fire linkage equipment so that a
judgment on whether or not the fire linkage equipment is operating normally can be done.
II. Feature and technical parameters
1. Executive standard: EN54-18
2.Operation voltage: loop DC24V (polarity-insensitive);power DC24V(polarity-insensitive)
3. Quiescent current: loop current<0.8mA; power current<2mA
4. Action current: loop current<5mA; power current<15mA
5.Capacity of the output control contact: 1A@DC30V
6.Operation indicator: The inspection indicator will blink once about every 12 seconds in the inspection
status or remain lit in the output status; the input indicator will remain lit in the feedback status.
7.Operating environment: Temperature: -10℃ ~ 55℃; RH: ≤95% (40 ℃±2℃, without condensation)
8.External dimensions: 86×86×41(mm,With base)
9. Weight: about 148g(With base)
III. Instructions for use
1.Terminal description (see Fig.2)
Terminal Name Function
D1,D2 DC24V power input, non-polarized
L1,L2 Loop connection, non-polarized
Voltage-free Input, factory default mode is normally open. For normally closed
TO+,TO-
mode, Jumper JP4(see Fig1)’s Pin1 & Pin2 should be shorted.
Normally open contact. For voltage output, NO1 and NO2 should be connected
NO1,NO2
with DC24V positive and DC24V negative respective.
NC1,NC2 Normally closed contact.
Common contact.When set to voltage output, the controlled equipment should
COM1,COM2
be connected between COM1 and COM2.

ASENWARE LTD
ADDRESS: 6 PROSPECT WAY, ROYAL OAK INDUSTRIAL ESTATE DAVENTRY,
NORTHAMPTONSHIRE, ENGLAND, NN118PL
WEBSITE: www.asenware.com EMAIL: [email protected]

1
Version: V1.0 Apr 28th,2018

Fig. 1 Main part (unit mm) Fig. 2 Base(unit mm)

2. Jumper setting and wiring method


1) For normally close input,short JP4’s Pin 1 & Pin2; for normally open input,short JP4’s Pin 2 & Pin3.
2) For project application, Jumper JP1,JP2,JP3’s Pin1 & Pin2 should be shorted(Pin2 & Pin3 are shorted
as factory default , only for production test) .
3) The ends of input and output circuit should correctly use a 47KΩ resistor (shown in Fig. 3) , so that the
Addressable I/O Module can identify the short-circuit fault or open-circuit fault of the input and the output
circuit.
4) For voltage output, NO1 and NO2 should be connected with DC24V positive and DC24V negative
respectively, and a 1N4007 diode should be in series between COM1 and COM2 then connected with the
controlled equipment. The details of the wiring method is shown in Fig. 3.

L1 L1
L1 COM1 L1 COM
L2 L2 1 47KΩ resister
47KΩ resister L2
L2
COM2 COM
+24V +24V D1 2
D1 TO+
NO1 TO+ NO1 47KΩ resister
47KΩ resister
GN D2 GND D2 TO-
TO- NO2 Normal closed input
NO2 Normal open input

Fig 3. Wiring method of Voltage Output

IV. Installation and debugging


1. Make sure the AW-D319 module matches the type given on the construction drawings.
2. Connect the 4-pin coding plug on the coder with the 4-pin coding socket (see Fig.1) on the main body
of the AW-D319 module and then set the coder with the coding function and compile the correct address
code to finish the address coding.
3. Conduct correct wiring as instructed in Fig.3 or Fig.4.
4. Use two M4 screws to fix the module base via the two elliptic screw holes shown in Fig.2 and then
insert the main body of the AW-D319 module into the module base and make sure they contact each other
ASENWARE LTD
ADDRESS: 6 PROSPECT WAY, ROYAL OAK INDUSTRIAL ESTATE DAVENTRY,
NORTHAMPTONSHIRE, ENGLAND, NN118PL
WEBSITE: www.asenware.com EMAIL: [email protected]

2
Version: V1.0 Apr 28th,2018

well.
5. After the AW-D319 module is installed and checked, connect the power supply of the fire alarm control
system.Upon successful login, the inspection indicator of the AW-D319 module will blink once about every
12 seconds, which suggests that the AW-D319 module has begun to operate.
6. Conduct debugging after the installation is completed. Make the fire alarm control system send out a
starting signal and have the starting signal sent by the AW-D319 module to the fire linkage equipment
connected with it. After that, the fire linkage equipment will operate correspondingly and the inspection
indicator of the AW-D319 module will be lit. The operating fire linkage equipment will give a feedback
signal. After receiving the feedback signal, the AW-D319 module will have its input indicator lit, which
suggests that it has begun to operate normally.
7. After the debugging, reset the AW-D319 module and related equipment.
V. Precautions
1. Do not connect the output to the AC signal, or the AW-D319 module may be damaged.
2. For active output, NO1 should be connected with DC24 passive, and NO2 with DC24 negative.
3. Confirm the type of the input equipment connected with the AW-D319 module (feedback equipment or
fire alarm equipment) and have the corresponding equipment type of the AW-D319 module set in the fire
alarm control panel. After automatic login, the AW-D319 module will treat the input equipment as fire alarm
equipment by default.