5. After the AW-D319 module is installed and checked, connect the power supply of the fire alarm control
system.Upon successful login, the inspection indicator of the AW-D319 module will blink once about every
12 seconds, which suggests that the AW-D319 module has begun to operate.
6. Conduct debugging after the installation is completed. Make the fire alarm control system send out a
starting signal and have the starting signal sent by the AW-D319 module to the fire linkage equipment
connected with it. After that, the fire linkage equipment will operate correspondingly and the inspection
indicator of the AW-D319 module will be lit. The operating fire linkage equipment will give a feedback
signal. After receiving the feedback signal, the AW-D319 module will have its input indicator lit, which
suggests that it has begun to operate normally.
7. After the debugging, reset the AW-D319 module and related equipment.
V. Precautions
1. Do not connect the output to the AC signal, or the AW-D319 module may be damaged.
2. For active output, NO1 should be connected with DC24 passive, and NO2 with DC24 negative.
3. Confirm the type of the input equipment connected with the AW-D319 module (feedback equipment or
fire alarm equipment) and have the corresponding equipment type of the AW-D319 module set in the fire
alarm control panel. After automatic login, the AW-D319 module will treat the input equipment as fire alarm
equipment by default.