Modbus Register Mapping

Control

PS0500
PC500/PC550
PCC1301
PowerCommand 1.1
PowerCommand 1.2
PowerCommand 2.2
PowerCommand 2.3
PowerCommand 3.3
DMC 1000
DMC 1500
MCM 3320
AUX101/102

English
Original Instructions 3−2015 A029X159 (Issue 13)
Table of Contents
SECTION TITLE PAGE
SAFETY PRECAUTIONS III
1. PCC1301/POWERCOMMAND 1.X/PS0500 MODBUS REGISTER MAP . . . . . . . . . . . . . . . . . . . . . 1
2. POWERCOMMAND 2.X/3.X MODBUS REGISTER MAP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3. POWERCOMMAND 2.X/3.X MODBUS FAULT STATUS BITMAPS . . . . . . . . . . . . . . . . . . . . . . . . . 325
4. NFPA 110 & EXTENDED ANNUNCIATION BITMAP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 381
5. DMC 1000 MODBUS PARAMETRIC DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 383
6 DMC 1000 MODBUS ENUMERATED DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 413
7 DMC 1000 MODBUS BITMAP DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 433
8. DMC 1500 COMMUNICATION SERVER 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 437
Modbus Address: 2 (Slave). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 437
Generator Set Bus Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 439
Utility Bus Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 441
ATS 1−5 DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 442
Word Data (Reference Tables ATS 1-5 and 6-10) . . . . . . . . . . . . . . . . . . . . . . . . . 443
ATS 6−10 DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 444
9. DMC 1500 COMMUNICATION SERVER 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 447
Modbus Address: 1 (Slave). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 447
Generator Raw Data Gen 1-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 450
10. MCM3320 MODBUS REGISTER MAP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 455
Modbus Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 455
Reference Documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 455
Serial Port Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 455
Device Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 455
Power-Up Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 455
Response Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 455
Data Formatting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 455
Modbus Activity LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 455
Supported Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 455
Holding Register Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456
Preset Single/Preset Multiple Registers Function . . . . . . . . . . . . . . . . . . . . . . . . . 456
Diagnostic Counters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456
Register Maps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456
Application Layer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456
Read Hold Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456
Set Single Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456
Modbus Loopback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456
Set Multiple Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 457
Modbus Register Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 457
11. MCM3320 MODBUS FAULT STATUS BITMAPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 539
12. MCM3320 MODBUS ADDRESS 42506, 42507 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 543

i
13. PC500/550 MODBUS REGISTER MAP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 545
14. AUX101/102 MODBUS REGISTER MAP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 553

ii
Safety Precautions

SAVE THESE INSTRUCTIONS − This manual contains important instructions that should be followed during
installation and maintenance of the generator set and batteries.
Before operating the generator set (genset), read the Operator’s Manual and become familiar with it and
the equipment. Safe and efficient operation can be achieved only if the equipment is properly operated
and maintained. Many accidents are caused by failure to follow fundamental rules and precautions.
The following symbols, found throughout this manual, alert you to potentially dangerous conditions to the op-
erator, service personnel, or the equipment.
DANGER This symbol warns of immediate hazards which will result in severe personal injury or
death.

WARNING This symbol refers to a hazard or unsafe practice which can result in severe personal in-
jury or death.

CAUTION This symbol refers to a hazard or unsafe practice which can result in personal injury or
product or property damage.

FUEL AND FUMES ARE FLAMMABLE


Fire, explosion, and personal injury or death can result from improper practices.
 DO NOT fill fuel tanks while engine is running, unless tanks are outside the engine compartment. Fuel
contact with hot engine or exhaust is a potential fire hazard.
 DO NOT permit any flame, cigarette, pilot light, spark, arcing equipment, or other ignition source near the
generator set or fuel tank.
 Fuel lines must be adequately secured and free of leaks. Fuel connection at the engine should be made
with an approved flexible line. Do not use zinc coated or copper fuel lines with diesel fuel.
 Natural gas is lighter than air, and will tend to gather under hoods. Propane is heavier than air, and will
tend to gather in sumps or low areas. NFPA code requires all persons handling propane to be trained and
qualified.
 Be sure all fuel supplies have a positive shutoff valve.
 Be sure battery area has been well-ventilated prior to servicing near it. Lead-acid batteries emit a highly
explosive hydrogen gas that can be ignited by arcing, sparking, smoking, etc.

EXHAUST GASES ARE DEADLY


 Provide an adequate exhaust system to properly expel discharged gases away from enclosed or shel-
tered areas and areas where individuals are likely to congregate. Visually and audibly inspect the exhaust
for leaks daily or per the maintenance schedule. Make sure that exhaust manifolds are secured and not
warped. Do not use exhaust gases to heat a compartment.
 The exhaust vent should be high enough to help clear gases, avoid accumulation of snow, and in accor-
dance with local mechanical codes.
 Be sure the unit is well ventilated.
 Engine exhaust and some of its constituents are known to the state of California to cause cancer, birth
defects, and other reproductive harm.

MOVING PARTS CAN CAUSE SEVERE PERSONAL INJURY OR DEATH


 Keep your hands, clothing, and jewelry away from moving parts.

iii
 Before starting work on the generator set, disconnect battery charger from its AC source, then disconnect
starting batteries, negative (−) cable first. In lean-burn natural gas (LBNG) gensets, also make sure the
starter’s air supply line is disconnected or completely vented until the generator set is ready to start. This
will prevent accidental starting.
 Make sure that fasteners on the generator set are secure. Tighten supports and clamps, keep guards
in position over fans, drive belts, etc.
 Do not wear loose clothing or jewelry in the vicinity of moving parts, or while working on electrical equip-
ment. Loose clothing and jewelry can become caught in moving parts.
 If adjustment must be made while the unit is running, use extreme caution around hot manifolds, moving
parts, etc.
DO NOT OPERATE IN FLAMMABLE AND EXPLOSIVE ENVIRONMENTS
Flammable vapor can cause an engine to overspeed and become difficult to stop, resulting in possible fire,
explosion, severe personal injury and death. Do not operate a genset where a flammable vapor environment
can be created by fuel spill, leak, etc., unless the genset is equipped with an automatic safety device to block
the air intake and stop the engine. The owners and operators of the genset are solely responsible for operating
the genset safely. Contact your authorized Cummins Power Generation distributor for more information.
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH
 Remove electric power before removing protective shields or touching electrical equipment. Use rubber
insulative mats placed on dry wood platforms over floors that are metal or concrete when around electrical
equipment. Do not wear damp clothing (particularly wet shoes) or allow skin surface to be damp when
handling electrical equipment. Do not wear jewelry. Jewelry can short out electrical contacts and cause
shock or burning.
 Use extreme caution when working on electrical components. High voltages can cause injury or death.
DO NOT tamper with interlocks.
 Follow all applicable state and local electrical codes. Have all electrical installations performed by a quali-
fied licensed electrician. Tag and lock open switches to avoid accidental closure.
 DO NOT CONNECT GENERATOR SET DIRECTLY TO ANY BUILDING ELECTRICAL SYSTEM. Haz-
ardous voltages can flow from the generator set into the utility line. This creates a potential for electrocu-
tion or property damage. Connect only through an approved isolation switch or an approved paralleling
device.
MEDIUM VOLTAGE GENERATOR SETS (601V to 15kV)
 Medium voltage acts differently than low voltage. Special equipment and training is required to work on
or around medium voltage equipment. Operation and maintenance must be done only by persons trained
and qualified to work on such devices. Improper use or procedures will result in severe personal injury
or death.
 Do not work on energized equipment. Unauthorized personnel must not be permitted near energized
equipment. Due to the nature of medium voltage electrical equipment, induced voltage remains even af-
ter the equipment is disconnected from the power source. Plan the time for maintenance with authorized
personnel so that the equipment can be de-energized and safely grounded.
GENERAL SAFETY PRECAUTIONS
 Coolants under pressure have a higher boiling point than water. DO NOT open a radiator or heat ex-
changer pressure cap while the engine is running. To prevent severe scalding, let engine cool down be-
fore removing coolant pressure cap. Turn cap slowly, and do not open it fully until the pressure has been
relieved.
 Used engine oils have been identified by some state or federal agencies as causing cancer or reproduc-
tive toxicity. When checking or changing engine oil, take care not to ingest, breathe the fumes, or contact
used oil.

iv
 Keep multi-class ABC fire extinguishers handy. Class A fires involve ordinary combustible materials such
as wood and cloth; Class B fires, combustible and flammable liquid fuels and gaseous fuels; Class C fires,
live electrical equipment. (ref. NFPA No. 10).
 Make sure that rags or combustible material are not left on or near the generator set.
 Make sure generator set is mounted in a manner to prevent combustible materials from accumulating
under or near the unit.
 Remove all unnecessary grease and oil from the unit. Accumulated grease and oil can cause overheating
and engine damage which present a potential fire hazard.
 Keep the generator set and the surrounding area clean and free from obstructions. Remove any debris
from the set and keep the floor clean and dry.
 Do not work on this equipment when mentally or physically fatigued, or after consuming any alcohol or
drug that makes the operation of equipment unsafe.
 Substances in exhaust gases have been identified by some state or federal agencies as causing cancer
or reproductive toxicity. Take care not to breath or ingest or come into contact with exhaust gases.
 Do not store any flammable liquids, such as fuel, cleaners, oil, etc., near the generator set. A fire or explo-
sion could result.
 Wear hearing protection when near an operating generator set.
 To prevent serious burns, avoid contact with hot metal parts such as radiator system, turbo charger sys-
tem and exhaust system.

DISPOSE OF THIS UNIT PROPERLY

v
THIS PAGE LEFT INTENTIONALLY BLANK

vi
1. PCC1301/PowerCommand 1.x/PS0500 Modbus Register Map
The controller contains data that can be read by a re- bus Serial Line Implementation Guide v1.02, both
mote device communicating via Modbus RTU proto- available at www.modbus.org.
col on a two-wire RS−485 master/slave multi−drop
bus. In this arrangement the remote device is the Multi-Drop Network Mode Pins
master and the controller is the slave.  Hi (+) TB2-3

For more information about the Modbus protocol, re-  Lo (−) TB2-4
fer to Modbus Application Protocol v1.1b and Mod-  Shield TB2-1
Note: Earlier versions of software may not support all of the Modbus registers in the following table. If a particu-
lar register is not available in your installation, it is possible that the Modbus connection is working but the con-
troller software does not support that particular register.

Note: For the PS0500 control, Modbus functionality is ONLY available from software version 6.02 and later.

Note: If an address or bit is not listed in this table it is not used.

Note: The external device can read 1−16 contiguous registers, write 1−16 contiguous registers, or read diagnos-
tic counters.

Addr. Parameter Access Specifications Description Control


40004 Save Trims Read and 0: No action Save adjustments PC1.x,
Write 1: Save Unconditional saves to non volatile PS0500,
memory all the write PCC1301
parameters listed in
this table
40009 Controller Read Only Multiplier: 1 Device type of Con- PC1.x,
Type Size(Bits): 8 troller PS0500,
Sign: U PCC1301
Lower Limit: 0
Upper Limit: 255
40010 Operation Read Only 0: Off Current position of PC1.x,
Mode Switch 1: Auto the generator set PS0500,
Position 2: Manual switch panel off− PCC1301
Run−Auto switch as
seen by the genera-
tor set control
40011 Genset Read Only 0: Ready The parameter re- PC1.x,
State 1: Precrank flects current state PS0500,
2: Ramp of genset PCC1301
3: Running
40012 Active Fault Read Only Multiplier: 1 This register con- PC1.x,
Offset: 0 tains the fault code PS0500,
Size(Bits) 16 number of currently PCC1301
Sign: U active fault. See ser-
Units: NA vice manual for list
Lower Limit: 0 of supported fault
Upper Limit: 65535 codes.
Default: 0
40013 Active Fault Read Only 0: Normal Fault TypeThis reg- PC1.x,
Type 1: Warning ister contains the PS0500,
4: Shutdown fault type of current- PCC1301
ly active fault

1
Addr. Parameter Access Specifications Description Control
40016 NFPA 110 Read Only Multiplier: 1 16 bit number to PC1.x,
fault register Offset: 0 represent the status PS0500,
Size(Bits): 16 of the NFPA110 log- PCC1301
Sign: U ical. (See Section 4
Units: NA Table 4−1)
Lower Limit: NA
Upper Limit: NA
Default: NA

40017 Extended Read Only Multiplier: 1 16 bit number to PC1.x,


Annunci- Offset: 0 represent the status PS0500,
ation fault Size(Bits): 16 of the NFPA110 log- PCC1301
register Sign: U ical. (See Section 4
Units: NA Table 4−1)
Lower Limit: NA
Upper Limit: NA
Default: NA

40018 Alternator Read Only Multiplier: 1 Generator set L1−N PC1.x,


L1−N Volt- Offset: 0 Voltage PS0500,
age Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA

40019 Alternator Read Only Multiplier: 1 Generator set L2−N PC1.x,


L2−N Volt- Offset: 0 Voltage PS0500,
age Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA

40020 Alternator Read Only Multiplier: 1 Generator set L3−N PC1.x,


L3−N Volt- Offset: 0 Voltage PS0500,
age Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA

40022 Alternator Read Only Multiplier: 1 Generator set PC1.x,


L1−L2 Volt- Offset: 0 L1−L2 Voltage PS0500,
age Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA

2
Addr. Parameter Access Specifications Description Control
40023 Alternator Read Only Multiplier: 1 Generator set PC1.x,
L2−L3 Volt- Offset: 0 L2−L2 Voltage PS0500,
age Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA

40024 Alternator Read Only Multiplier: 1 Generator set PC1.x,


L3−L1 Volt- Offset: 0 L3−L1 Voltage PS0500,
age Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA

40025 Alt Voltage Read Only Multiplier: 1 Generator set line to PC1.x,
Offset: 0 line average voltage PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA

40026 Alternator L1 Read Only Multiplier: 0.1 Monitors the gener- PC1.x,
Current Offset: 0 ator set L1 current PS0500,
Size(Bits): 16 value PCC1301
Sign: U
Units: amps
Lower Limit: 0
Upper Limit: 65535
Default: NA

40027 Alternator L2 Read Only Multiplier: 0.1 Monitors the gener- PC1.x,
Current Offset: 0 ator set L2 current PS0500,
Size(Bits): 16 value PCC1301
Sign: U
Units: amps
Lower Limit: 0
Upper Limit: 65535
Default: NA

40028 Alternator L3 Read Only Multiplier: 0.1 Monitors the gener- PC1.x,
Current Offset: 0 ator set L3 current PS0500,
Size(Bits): 16 value PCC1301
Sign: U
Units: amps
Lower Limit: 0
Upper Limit: 65535
Default: NA

3
Addr. Parameter Access Specifications Description Control
40029 Genset av- Read Only Multiplier: 0.1 Generator set aver- PC1.x,
erage cur- Offset: 0 age current PS0500,
rent Size(Bits): 16 PCC1301
Sign: U
Units: amps
Lower Limit: 0
Upper Limit: 65535
Default: NA

40040 Alternator Read Only Multiplier: 1 Alternator output PC1.x,


output volt− Offset: 0 volt−amperes PS0500,
amperes Size(Bits): 16 (phase a) PCC1301
(phase a) Sign: U
Units: kVa
Lower Limit: 0
Upper Limit: 65535
Default: NA

40041 Alternator Read Only Multiplier: 1 Alternator output PC1.x,


output volt− Offset: 0 volt−amperes PS0500,
amperes Size(Bits): 16 (phase b) PCC1301
(phase b) Sign: U
Units: kVa
Lower Limit: 0
Upper Limit: 65535
Default: NA

40042 Alternator Read Only Multiplier: 1 Alternator output PC1.x,


output volt− Offset: 0 volt−amperes PS0500,
amperes Size(Bits): 16 (phase c) PCC1301
(phase c) Sign: U
Units: kVa
Lower Limit: 0
Upper Limit: 65535
Default: NA

40043 Alternator Read Only Multiplier: 1 Alternator output PC1.x,


output volt− Offset: 0 volt−amperes (total) PS0500,
amperes (to- Size(Bits): 16 PCC1301
tal) Sign: U
Units: kVa
Lower Limit: 0
Upper Limit: 65535
Default: NA

40044 Average Alt Read Only Multiplier: 0.1 Average alternator PC1.x,
Line Fre- Offset: 0 line frequency PS0500,
quency Size(Bits): 16 PCC1301
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 65535
Default: NA

4
Addr. Parameter Access Specifications Description Control
40058 Rated Alter- Read Only Multiplier: 0.1 Monitors the gener- PC1.x,
nator L1 Offset: 0 ator set standby L1 PS0500,
Current (%) Size(Bits): 16 current percentage PCC1301
Sign: U output.
Units: %
Lower Limit: 0
Upper Limit: 65535
Default: NA

40059 Rated Alter- Read Only Multiplier: 0.1 Monitors the gener- PC1.x,
nator L2 Offset: 0 ator set standby L2 PS0500,
Current (%) Size(Bits): 16 current percentage PCC1301
Sign: U output.
Units: %
Lower Limit: 0
Upper Limit: 65535
Default: NA

40060 Rated Alter- Read Only Multiplier: 0.1 Monitors the gener- PC1.x,
nator L3 Offset: 0 ator set standby L3 PS0500,
Current (%) Size(Bits): 16 current percentage PCC1301
Sign: U output.
Units: %
Lower Limit: 0
Upper Limit: 65535
Default: NA

40061 Battery Volt- Read Only Multiplier: 0.1 Value of battery vol- PC1.x,
age Offset: 0 tage PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA

40062 Oil Pressure Read Only Multiplier: 1 Monitor point for oil PC1.x,
Offset: 0 pressure PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: kPa
Lower Limit: 0
Upper Limit: 65535
Default: NA

40064 Coolant Read Only Multiplier: 0.1 Monitor point for PC1.x,
Temperature Offset: 0 Coolant Temperatu- PS0500,
Size(Bits): 16 re PCC1301
Sign: U
Units: degc
Lower Limit: 0
Upper Limit: 65535
Default: NA

5
Addr. Parameter Access Specifications Description Control
40068 Engine Read Only Multiplier: 1 Monitor point for Av- PC1.x,
Speed Offset: 0 erage Engine Speed PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Rpm
Lower Limit: 0
Upper Limit: 65535
Default: NA

40069 Total Runs Read Only Multiplier: 1 Parameter reflects PC1.x,


Offset: 0 total number of PS0500,
Size(Bits): 16 starts PCC1301
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

40070 Engine Run Read Only Multiplier: 1 Total Engine Run PC1.x,
Time (High Offset: 0 Time PS0500,
byte) Size(Bits): 16 PCC1301
Sign: U
Units: Sec
Lower Limit: 0
Upper Limit: 65535
Default: NA

40071 Engine Run Read Only Multiplier: 1 Total Engine Run PC1.x,
Time (Low Offset: 0 time PS0500,
byte) Size(Bits): 16 PCC1301
Sign: U
Units: Sec
Lower Limit: 0
Upper Limit: 65535
Default: NA

40210 AUX101 Read Only Multiplier: 0.01 AUX101 Speed Bias PCC1301
Speed Bias Offset: 0
Size(Bits): 16
Sign: S
Units: RPM
Lower Limit: −100
Upper Limit: 100
Default: NA

40211 AUX101 Read Only Multiplier: 0.01 AUX101 Voltage PCC1301


Voltage Bias Offset: 0 Bias
Size(Bits): 16
Sign: S
Units: Volt
Lower Limit: −100
Upper Limit: 100
Default: NA

6
Addr. Parameter Access Specifications Description Control
40229 Barometric Read Only Multiplier : 0.1 Monitor point for the PC 1.x
Absolute Offset: 0 Barometric Absolute
Pressure Size (Bits) : 16 Pressure
Sign: U
Units: PSI
Lower Limit: 0
Upper Limit: 19
Default: NA
40242 LTA Read Only Multiplier : 1 The processed val- PC 1.x
Temperature Offset: 0 ue of the LTA Tem-
Size (Bits) : 16 perature sensor for
Sign: S the System IO Mod-
Units: degF ule.
Lower Limit: NA
Upper Limit: NA
Default: NA
40254 Fuel Pres- Read Only 0. Invalid Indicates if the fuel PC 1.x
sure Valid 1. Valid pressure is valid/in-
valid from the
AUX101 or ECM
datalink.
40278 Configurable Read Only 0. Inactive Measured state of PC 1.x
Input #4 1. Active hardware input
Status
40300 Genset start Read and 0: Stop Remote start via PC1.x,
stop control Write 1: Start Modbus PS0500,
via Modbus PCC1301
40301 Fault reset Read and 0: Inactive Fault reset PC1.x,
via Modbus Write 1: Active PCC1301,
(No logical) PS0500
40535 Customer Read Only 0. Inactive Output of Customer PC 1.x
Output 1 1. Active Output 1 Event
Event command
40536 Customer Read Only 0. Inactive Output of Customer PC 1.x
Output 2 1. Active Output 2 Event
Event command
40583 Dead Bat- Read Only Multiplier : 1 Tracks the number PC 1.x
tery Preven- Offset: 0 of crank attempts in
tion Counter Size (Bits) : 8 order to limit the at-
Sign: U tempts when the
Units: NA battery is so low that
Lower Limit: NA the control resets
Upper Limit: NA
Default: NA

40587 Exercise Read Only 0. Inactive Displays the status PC 1.x


Scheduler 1. Active of Exercise Sched-
Status uler

7
Addr. Parameter Access Specifications Description Control
43000 Alternator Read and Multiplier: 1 This register repre- PC1.x,
Nominal Write Offset: 0 sents Alternator PS0500,
Voltage Size(Bits): 16 nominal voltage PCC1301
Sign: U
Units: Vac
Lower Limit: 190
Upper Limit: 600
Default: 208
43001 Alternator Read and 0: 60 Hz Set to 50 Hz or 60 PC1.x,
Frequency Write 1: 50 Hz Hz PS0500,
Switch PCC1301
43002 Single/3 Read and 0: Single Phase Generator output PC1.x
Phase Con- Write 1: Three Phase connection type
nection
43003 Connection Read and 0: Delta Alternator connec- PC1.x,
Type Write 1: Wye tion type PS0500,
PCC1301
43004 Glow Plug Read and 0: Disable Glow plug driver PC1.x,
Enable Write 1: Enable feature enable PS0500,
PCC1301
43005 Charging Al- Read and 0: Disable Used to disable the PC1.x,
ternator Write 1: Enable controller related PS0500,
Functions charging alt func- PCC1301
Disable tions.
43006 Start Time Read and Multiplier: 1 Remote start time PC1.x,
Delay Write Offset: 0 delay setting PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Sec
Lower Limit: 0
Upper Limit: 300
Default: 0
43007 Stop Time Read and Multiplier: 1 Remote stop time PC1.x,
Delay Write Offset: 0 delay setting PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Sec
Lower Limit: 0
Upper Limit: 600
Default: 0
43008 Cycle Crank Read and Multiplier: 1 Maximum number of PC1.x,
Attempts Write Offset: 0 start attempts for PS0500,
Size(Bits): 16 cycle crank mode PCC1301
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 7
Default: 3

8
Addr. Parameter Access Specifications Description Control
43009 Cycle Crank Read and Multiplier: 1 Maximum starter PC1.x,
Engage Write Offset: 0 engage time for PS0500,
Time Size(Bits): 16 cycle crank mode PCC1301
Sign: U
Units: sec
Lower Limit: 3
Upper Limit: 30
Default: 15

43010 Cycle Crank Read and Multiplier: 1 Engine starting PC1.x,


Reset Time Write Offset: 0 cycle crank attempts PS0500,
Size(Bits): 16 setting PCC1301
Sign: U
Units: sec
Lower Limit: 0
Upper Limit: 60
Default: 30

43011 Fault bypass Read and 0: Disable Operator panel En- PC1.x,
(battle short) Write 1: Enable able for Battle Short PCC1301
feature en-
able

43012 Battle Short Read and 0: None, Switch Input for PC1.x
Switch Input Write 1: Configurable Input #1, Battle Short.
2: Configurable Input #2, 0= None
3: Configurable Input #3, 1=Customer Input 1
4: Configurable Input #4, 2=Customer Input 2
5: Operator Panel 3 =Customer Input 3
4 =Customer Input 4
5=Operator Panel
PCC1301 Modbus
mapping for param-
eters having differ-
ent limits as
compared to PC1.x
and PS0500 See
Table 1-1

NOTE: For PC1.x


SW versions less
than 2.73, ’Battle
Short Switch Input’
range is 0 to 3. For
PC1.x SW versions
2.73 and greater
’Battle Short Switch
Input’ range is 0 to 5

43013 AVR Enable Read and 0: Disable Automatic voltage PC1.x,


Write 1: Enable regulation enable PCC1301

9
Addr. Parameter Access Specifications Description Control
43014 V/Hz Knee Read and Multiplier: 0.1 Automatic voltage PC1.x,
Frequency Write Offset: 0 regulator volts per PCC1301
Size(Bits): 16 hertz roll off knee
Sign: S setting
Units: Hz
Lower Limit: 0
Upper Limit: 1000
Default: 500
43015 V/Hz Rolloff Read and Multiplier: 0.1 Automatic voltage PC1.x,
Slope Write Offset: 0 regulator volts per PCC1301
Size(Bits): 16 hertz roll off slope
Sign: U setting
Units: %v/Hz
Lower Limit: 0
Upper Limit: 50
Default: 22
43016 AVR Gain Read and Multiplier: 1 Automatic voltage PC1.x,
Adjust Write Offset: 0 regulator gain set- PCC1301
Size(Bits): 16 ting
Sign: U
Units: %
Lower Limit: 5
Upper Limit: 1000
Default: 100
43017 AVR K2 Read and Multiplier: 1 Automatic voltage PC1.x,
Gain Adjust Write Offset: 0 regulator K2 gain PCC1301
Size(Bits): 16 setting
Sign: U
Units: %
Lower Limit: 5
Upper Limit: 1000
Default: 100
43018 AVR D Gain Read and Multiplier: 1 Automatic voltage PC1.x,
Adjust Write Offset: 0 regulator K2 gain PCC1301
Size(Bits): 16 setting
Sign: U
Units: %
Lower Limit: 95
Upper Limit: 105
Default: 100
43019 Electronic Read and 0: Disable Electronic governor PC1.x,
Governor Write 1: Enable enable feature PCC1301
Enable

10
Addr. Parameter Access Specifications Description Control
43020 Initial Crank Read and Multiplier: 0.1 Electronic governing PC1.x,
Fueling Write Offset: 0 initial duty cycle set- PCC1301
Command Size(Bits): 16 ting
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 500
Default: 250

43021 Initial Crank Read and Multiplier: 0.1 Time spent at Initial PC1.x,
Fueling Peri- Write Offset: 0 Crank Fueling Com- PCC1301
od Size(Bits): 8 mand
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 100
Default: 20

43022 Crank Fuel- Read and Multiplier: 0.1 Electronic governing PC1.x,
ing Ramp Write Offset: 0 start ramp duty PCC1301
Rate Size(Bits): 16 cycle setting
Sign: U
Units: %/sec
Lower Limit: 50
Upper Limit: 1000
Default: 250

43023 Maximum Read and Multiplier: 0.1 Electronic governing PC1.x,


Crank Fuel- Write Offset: 0 maximum duty cycle PCC1301
ing Size(Bits): 16 setting
Sign: U
Units: %
Lower Limit: 500
Upper Limit: 1000
Default: 1000

43024 Governor Read and Multiplier: 1 Electronic governing PC1.x,


Gain Adjust Write Offset: 0 gain setting PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 5
Upper Limit: 1000
Default: 100

43025 Gov K2 Gain Read and Multiplier: 1 Electronic governor PC1.x,


Adjust Write Offset: 0 K2 gain setting PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 5
Upper Limit: 1000
Default: 100

11
Addr. Parameter Access Specifications Description Control
43026 Gov D Gian Read and Multiplier: 1 Electronic governor PC1.x,
Adjust Write Offset: 0 damping adjustment PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 95
Upper Limit: 105
Default: 100

43027 Crank Exit Read and Multiplier: 0.1 Electronic governing PC1.x,
Fueling Write Offset: 0 crank exit fuel duty PCC1301
Command Size(Bits): 16 cycle setting
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 1000
Default: 250

43028 Dither Fac- Read and Multiplier: 1 Electronic governing PC1.x,


tor Write Offset: 0 dither factor setting PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 30
Default: 25

43029 Governor Read and Multiplier: 1 Electronic governing PC1.x,


Ramp Time Write Offset: 0 start ramp time set- PCC1301
Size(Bits): 16 ting
Sign: U
Units: sec
Lower Limit: 0
Upper Limit: 15000
Default: 25

43030 Governor Read and Multiplier: 1 Engine speed at PC1.x,


Enable Write Offset: 0 which governor is PS0500,
Speed Size(Bits): 16 enabled PCC1301
Sign: U
Units: RPM
Lower Limit: 0
Upper Limit: 1400
Default: 1100

43031 Minimum Read and Multiplier: 1 Setting for electronic PC1.x,


Governor Write Offset: 0 governor minimum PCC1301
Duty Cycle Size(Bits): 8 duty cycle
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 100
Default: 20

12
Addr. Parameter Access Specifications Description Control
43032 Maximum Read and Multiplier: 1 Setting for electronic PC1.x,
Governor Write Offset: 0 governor maximum PCC1301
Duty Cycle Size(Bits): 8 duty cycle
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 100
Default: 95

43033 Model num- Read and Multiplier: 1 Byte 1 for model PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #1 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43034 Model num- Read and Multiplier: 1 Byte 2 for model PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #2 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43035 Model num- Read and Multiplier: 1 Byte 3 for model PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #3 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43036 Model num- Read and Multiplier: 1 Byte 4 for model PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #4 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43037 Model num- Read and Multiplier: 1 Byte 5 for model PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #5 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

13
Addr. Parameter Access Specifications Description Control
43038 Model num- Read and Multiplier: 1 Byte 6 for model PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #6 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43039 Model num- Read and Multiplier: 1 Byte 7 for model PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #7 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43040 Model num- Read and Multiplier: 1 Byte 8 for model PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #8 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43041 Model num- Read and Multiplier: 1 Byte 9 for model PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #9 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43042 Model num- Read and Multiplier: 1 Byte 10 for model PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #10 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43043 Model num- Read and Multiplier: 1 Byte 11 for model PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #11 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

14
Addr. Parameter Access Specifications Description Control
43044 Model num- Read and Multiplier: 1 Byte 12 for model PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #12 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43045 Model num- Read and Multiplier: 1 Byte 13 for model PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #13 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43046 Model num- Read and Multiplier: 1 Byte 14 for model PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #14 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43047 Model num- Read and Multiplier: 1 Byte 15 for model PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #15 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43048 Model num- Read and Multiplier: 1 Byte 16 for model PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #16 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43049 Serial num- Read and Multiplier: 1 Byte 1 for serial PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #1 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

15
Addr. Parameter Access Specifications Description Control
43050 Serial num- Read and Multiplier: 1 Byte 2 for serial PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #2 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43051 Serial num- Read and Multiplier: 1 Byte 3 for serial PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #3 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43052 Serial num- Read and Multiplier: 1 Byte 4 for serial PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #4 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43053 Serial num- Read and Multiplier: 1 Byte 5 for serial PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #5 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43054 Serial num- Read and Multiplier: 1 Byte 6 for serial PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #6 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43055 Serial num- Read and Multiplier: 1 Byte 7 for serial PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #7 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

16
Addr. Parameter Access Specifications Description Control
43056 Serial num- Read and Multiplier: 1 Byte 8 for serial PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #8 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43057 Serial num- Read and Multiplier: 1 Byte 9 for serial PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #9 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43058 Serial num- Read and Multiplier: 1 Byte 10 for serial PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #10 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43059 Serial num- Read and Multiplier: 1 Byte 11 for serial PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #11 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43060 Serial num- Read and Multiplier: 1 Byte 12 for serial PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #12 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43061 Serial num- Read and Multiplier: 1 Byte 13 for serial PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #13 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

17
Addr. Parameter Access Specifications Description Control
43062 Serial num- Read and Multiplier: 1 Byte 14 for serial PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #14 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43063 Serial num- Read and Multiplier: 1 Byte 15 for serial PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #15 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43064 Serial num- Read and Multiplier: 1 Byte 16 for serial PC1.x,
ber charac- Write Offset: 0 number PS0500,
ter #16 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

43065 Configurable Read and 0: None Configurable Input PC1.x,


Input #1 Write 1: Warning #1 Fault Level Re- PS0500,
Fault Level 2: Shutdown sponse PCC1301
Response

43066 Configurable Read and 0: None Configurable Input PC1.x,


Input #2 Write 1: Warning #2 Fault Level Re- PS0500,
Fault Level 2: Shutdown sponse PCC1301
Response

43067 Configurable Read and Multiplier: 1 Configurable cus- PC1.x,


Customer Write Offset: 0 tomer output 1. De- PS0500,
Output 1 Size(Bits): 16 fault set for FC 1540 PCC1301
Sign: U which is COMMON
Units: NA WARNING fault.
Lower Limit: 0
Upper Limit: 65535
Default: 1540

43068 Configurable Read and Multiplier: 1 Configurable cus- PC1.x,


Customer Write Offset: 0 tomer output 2. De- PS0500,
Output 2 Size(Bits): 16 fault set for FC 1541 PCC1301
Sign: U which is COMMON
Units: NA SHUTDOWN fault.
Lower Limit: 0
Upper Limit: 65535
Default: 1541

18
Addr. Parameter Access Specifications Description Control
43069 Voltage Read and Multiplier: 0.0001 Make actual voltage PC1.x
Regulator Write Offset: 0 match Nominals
Calibration Size(Bits): 16 60Hz when Set
60Hz Sign: U point = 100%.
Units: % PCC1301 Modbus
Lower Limit: 9000 mapping for param-
Upper Limit: 11000 eters having differ-
Default: 10000 ent limits as
compare to PC1.x
See table 1-1.

43070 Voltage Read and Multiplier: 0.0001 Make actual voltage PC1.x
Regulator Write Offset: 0 match Nominals
Calibration Size(Bits): 16 50Hz when Set
50Hz Sign: U point = 100%.
Units: % PCC1301 Modbus
Lower Limit: 9000 mapping for param-
Upper Limit: 11000 eters having differ-
Default: 10000 ent limits as
compare to PC1.x
See table 1-1.

43071 Frequency Read and Multiplier: 0.1 PC1.x,


Adjust Trim Write Offset: 0 PCC1301
Size(Bits): 16
Sign: S
Units: Hz
Lower Limit: −600
Upper Limit: 600
Default: 0

43072 Alternator Read and Multiplier: 0.0001 60 Hz line 1 to neu- PC1.x,


L1−N 60Hz Write Offset: 0 tral metering voltage PS0500
Voltage Dis- Size(Bits): 16 calibration.
play Adjust Sign: U PCC1301 Modbus
Units: % mapping for param-
Lower Limit: 9000* eters having differ-
Upper Limit: 11000* ent limits as
Default: 10000 compare to PC1.x
and PS0500 See
Table 1-1

*NOTE: For PS0500


control, SW ver-
sions <6.03 the
range is 6000 to
14000. For PS0500
control, SW ver-
sions >6.03 the
range is 9000 to
11000.

19
Addr. Parameter Access Specifications Description Control
43073 Alternator Read and Multiplier: 0.0001 60 Hz line 2 to neu- PC1.x,
L2−N 60Hz Write Offset: 0 tral metering voltage PS0500
Voltage Dis- Size(Bits): 16 calibration
play Adjust Sign: U *NOTE: For PS0500
Units: % control, SW ver-
Lower Limit: 9000* sions <6.03 the
Upper Limit: 11000* range is 6000 to
Default: 10000 14000. For PS0500
control, SW ver-
sions >6.03 the
range is 9000 to
11000.

43074 Alternator Read and Multiplier: 0.0001 60 Hz line 3 to neu- PC1.x,


L3−N 60Hz Write Offset: 0 tral metering voltage PS0500
Voltage Dis- Size(Bits): 16 calibration
play Adjust Sign: U *NOTE: For PS0500
Units: % control, SW ver-
Lower Limit: 9000* sions <6.03 the
Upper Limit: 11000* range is 6000 to
Default: 10000 14000. For PS0500
control, SW ver-
sions >6.03 the
range is 9000 to
11000.

43075 Alternator Read and Multiplier: 0.0001 50 Hz line 1 to neu- PC1.x,


L1−N 50Hz Write Offset: 0 tral metering voltage PS0500
Voltage Dis- Size(Bits): 16 calibration
play Adjust Sign: U *NOTE: For PS0500
Units: % control, SW ver-
Lower Limit: 9000* sions <6.03 the
Upper Limit: 11000* range is 6000 to
Default: 10000 14000. For PS0500
control, SW ver-
sions >6.03 the
range is 9000 to
11000.

43076 Alternator Read and Multiplier: 0.0001 50 Hz line 2 to neu- PC1.x,


L2−N 50Hz Write Offset: 0 tral metering voltage PS0500
Voltage Dis- Size(Bits): 16 calibration
play Adjust Sign: U *NOTE: For PS0500
Units: % control, SW ver-
Lower Limit: 9000* sions <6.03 the
Upper Limit: 11000* range is 6000 to
Default: 10000 14000. For PS0500
control, SW ver-
sions >6.03 the
range is 9000 to
11000.

20
Addr. Parameter Access Specifications Description Control
43077 Alternator Read and Multiplier: 0.0001 50 Hz line 3 to neu- PC1.x,
L3−N 50Hz Write Offset: 0 tral metering voltage PS0500
Voltage Dis- Size(Bits): 16 calibration
play Adjust Sign: U *NOTE: For PS0500
Units: % control, SW ver-
Lower Limit: 9000* sions <6.03 the
Upper Limit: 11000* range is 6000 to
Default: 10000 14000. For PS0500
control, SW ver-
sions >6.03 the
range is 9000 to
11000.
43078 Alternator L1 Read and Multiplier: 0.001 60 Hz line 1 meter- PC1.x,
60Hz Cur- Write Offset: 0 ing current calibra- PS0500,
rent Adjust Size(Bits): 16 tion PCC1301
Sign: U
Units: %
Lower Limit: 8000
Upper Limit: 12000*
Default: 1000
43079 Alternator L2 Read and Multiplier: 0.001 60 Hz line 2 meter- PC1.x,
60Hz Cur- Write Offset: 0 ing current calibra- PS0500,
rent Adjust Size(Bits): 16 tion PCC1301
Sign: U
Units: %
Lower Limit: 8000
Upper Limit: 12000*
Default: 1000
43080 Alternator L3 Read and Multiplier: 0.0001 Adjust to make dis- PC1.x
60Hz Cur- Write Offset: 0 played current
rent Adjust Size(Bits): 16 match actual values
Sign: U in 50Hz applica-
Units: NA tions.
Lower Limit: .8
Upper Limit: 1.2
Default: 1
43081 Alternator L1 Read and Multiplier: 0.001 50 Hz line 1 meter- PC1.x,
50Hz Cur- Write Offset: 0 ing current calibra- PS0500,
rent Adjust Size(Bits): 16 tion PCC1301
Sign: U
Units: %
Lower Limit: 8000
Upper Limit: 12000*
Default: 1000

21
Addr. Parameter Access Specifications Description Control
43082 Alternator L2 Read and Multiplier: 0.001 50 Hz line 2 meter- PC1.x,
50Hz Cur- Write Offset: 0 ing current calibra- PS0500,
rent Adjust Size(Bits): 16 tion PCC1301
Sign: U
Units: %
Lower Limit: 8000
Upper Limit: 12000*
Default: 1000
43083 Alternator L3 Read and Multiplier: 0.001 50 Hz line 3 meter- PC1.x,
50Hz Cur- Write Offset: 0 ing current calibra- PS0500,
rent Adjust Size(Bits): 16 tion PCC1301
Sign: U
Units: %
Lower Limit: 8000
Upper Limit: 12000*
Default: 1000
43084 Annunciator Read and 0: None Sets the genset re- PC1.x,
#1 Switch Write 1: Warning sponse to an active PCC1301
Fault Re- 2: Shutdown Annunciator #1
sponse switch input.
43085 Annunciator Read and 0: None Sets the genset re- PC1.x,
#2 Switch Write 1: Warning sponse to an active PCC1301
Fault Re- 2: Shutdown Annunciator #2
sponse switch input.
43086 Annunciator Read and 0: None Sets the genset re- PC1.x,
#3 Switch Write 1: Warning sponse to an active PCC1301
Fault Re- 2: Shutdown Annunciator #3
sponse switch input.
43087 Annunciator Read and Multiplier: 1 Annunciator confi- PC1.x,
Output 1 Write Offset: 0 gurable output #1 PCC1301
Event Size(Bits): 16 event code number
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43088 Annunciator Read and Multiplier: 1 Annunciator confi- PC1.x,
Output 2 Write Offset: 0 gurable output #2 PCC1301
Event Size(Bits): 16 event code number
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

22
Addr. Parameter Access Specifications Description Control
43089 Annunciator Read and Multiplier: 1 Annunciator confi- PC1.x,
Output 3 Write Offset: 0 gurable output #3 PCC1301
Event Size(Bits): 16 event code number
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43090 Annunciator Read and Multiplier: 1 Annunciator confi- PC1.x,
Output 4 Write Offset: 0 gurable output #4 PCC1301
Event Size(Bits): 16 event code number
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43344 Clock Date Read Write Multiplier : 1 Use to set or read PC 1.x
Offset: 0 the current date.
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 31
Default: NA
43345 Clock Hours Read Write Multiplier : 1 Use to set or read PC 1.x
Offset: 0 the current hour.
Size (Bits) : 8
Sign: U
Units: hours
Lower Limit: 1
Upper Limit: 12
Default: 0
43346 Clock Read Write Multiplier : 1 Use to set or read PC 1.x
Minutes Offset: 0 the current minute.
Size (Bits) : 8
Sign: U
Units: minutes
Lower Limit: 0
Upper Limit: 59
Default: 0
43347 Clock Mode Read Write 0. NORMAL_MODE Allows user to go PC 1.x
1. SET_MODE into Set Mode for
2. SAVE_CLOCK_MODE Clock setup and in
Clock Save Mode

23
Addr. Parameter Access Specifications Description Control
43348 Clock Month Read Write Multiplier : 1 Use to set or read PC 1.x
Offset: 0 the current month.
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 12
Default: NA

43349 Clock Sec- Read Only Multiplier : 1 Use to set or read PC 1.x
onds Offset: 0 the current second.
Size (Bits) : 8
Sign: U
Units: seconds
Lower Limit: NA
Upper Limit: NA
Default: 0

43350 Clock Year Read Write Multiplier : 1 Use to set or read PC 1.x
Offset: 0 the current year.
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 99
Default: NA

43351 Daylight Read Write Multiplier : 1 Use to set the hour PC 1.x
Savings End Offset: 0 of the day when
Hour Size (Bits) : 8 daylight savings
Sign: U time ends.
Units: NA
Lower Limit: 0
Upper Limit: 23
Default: 2

43352 Daylight Read Write Multiplier : 1 Use to set the PC 1.x


Savings End Offset: 0 month when day-
Month Size (Bits) : 8 light savings time
Sign: U ends.
Units: NA
Lower Limit: 1
Upper Limit: 12
Default: 10

43353 Daylight Read Write 0. Default Use to set the end PC 1.x
Savings End 1.FIRST_OCCURANCE week occurance in a
Week Occ 2. SECOND_OCCU- daylight savings
Month RANCE End month.
3. THIRD_OCCURANCE
4. FOURTH_OCCU-
RANCE
5. FIFTH_OCCURANCE

24
Addr. Parameter Access Specifications Description Control
43354 Daylight Read Write 0. Sunday Use to set the day PC 1.x
Savings 1. Monday of the week when
Start Day 2. Tuesday daylight savings
3. Wednesday time starts.
4. Thursday
5. Friday
6. Saturday
43355 Daylight Read Write Multiplier : 1 Use to set the hour PC 1.x
Savings Offset: 0 of the day when
Start Hour Size (Bits) : 8 daylight savings
Sign: U time starts.
Units: NA
Lower Limit: 0
Upper Limit: 23
Default: 2
43356 Daylight Read Write Multiplier : 1 Use to set the PC 1.x
Savings Offset: 0 month when day-
Start Month Size (Bits) : 8 light savings time
Sign: U starts.
Units: NA
Lower Limit: 1
Upper Limit: 12
Default: 4
43357 Daylight Read Write 0. Default Use to set the week PC 1.x
Savings 1.FIRST_OCCURANCE occurance in a day-
Start Week 2. SECOND_OCCU- light savings start
Occ Month RANCE month.
3. THIRD_OCCURANCE
4. FOURTH_OCCU-
RANCE
5. FIFTH_OCCURANCE
43358 Daylight Read Write Multiplier : 1 Use to set the PC 1.x
Savings Offset: 0 amount of daylight
Time Adjust- Size (Bits) : 8 savings time adjust-
ment Sign: U ment applied.
Units: minutes
Lower Limit: 0
Upper Limit: 120
Default: 60
43359 Daylight Read Write 0. Disabled Use to enable the PC 1.x
Savings 1. Enabled daylight savings
Time Enable time feature.
43376 Scheduler Read Write 0. PCCnet Devices User to set Duration PC 1.x
Prog Dura- 1. Group for PCCnet de- in Minutes for Exer-
tion (Mins) vice interface parameters cise Scheduler
43377 Scheduler Read Write 0. Disabled Trim − user to edit PC 1.x
Prog x En- 1. Enabled for running the
able Scheduler Exercise
Program

25
Addr. Parameter Access Specifications Description Control
43378 Scheduler Read Write 0. Weekly User to select the PC 1.x
Prog Repeat 1. Bi_Monthly Exercise Scheduler
Interval 2. Monthly Interval
3. Quarterly
4. Semi−Annual
43380 Scheduler Read Write 0. Sunday User can set the PC 1.x
Prog Start 1. Monday Start Day of the
Day 2. Tuesday week, month for Ex
3. Wednesday Scheduler
4. Thursday
5. Friday
6. Saturday
43381 Scheduler Read Write Multiplier : 1 User to set Start PC 1.x
Prog Start Offset: 0 Hour For Ex
Hour Size (Bits) : 8 Scheduler
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 12
Default: 2
43382 Scheduler Read Write Multiplier : 1 User to set Start PC 1.x
Prog Start Offset: 0 Minute for Exercise
Minute Size (Bits) : 8 Scheduler
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 59
Default: 1
43383 Daylight Read Write 0. Sunday Use to set the day PC 1.x
Savings End 1. Monday of the week when
Day 2. Tuesday daylight savings
3. Wednesday time ends.
4. Thursday
5. Friday
6. Saturday
43719 AUX101 Al- Read Only Multiplier: 1 AUX101 input as al- PCC1301
ternator Offset: 0 ternator temperature
Temp Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

26
Addr. Parameter Access Specifications Description Control
43722 AUX101 Read Only Multiplier: 1 AUX101 input as PCC1301
Ambient Offset: 0 ambient tempera-
Temp Size(Bits): 16 ture
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

43723 AUX101 in- Read Only Multiplier: 1 AUX101 input 1 PCC1301


put 1 voltage Offset: 0 voltage
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

43724 AUX101 in- Read Only Multiplier: 1 AUX101 input 2 PCC1301


put 2 voltage Offset: 0 voltage
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

43725 AUX101 in- Read Only Multiplier: 1 AUX101 input 3 PCC1301


put 3 voltage Offset: 0 voltage
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

43726 AUX101 in- Read Only Multiplier: 1 AUX101 input 4 PCC1301


put 4 voltage Offset: 0 voltage
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

43727 AUX101 in- Read Only Multiplier: 1 AUX101 input 5 PCC1301


put 5 voltage Offset: 0 voltage
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

27
Addr. Parameter Access Specifications Description Control
43728 AUX101 in- Read Only Multiplier: 1 AUX101 input 6 PCC1301
put 6 voltage Offset: 0 voltage
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

43729 AUX101 in- Read Only Multiplier: 1 AUX101 input PCC1301


put 67volt- Offset: 0 67voltage
age Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

43730 AUX101 in- Read Only Multiplier: 1 AUX101 input 8 PCC1301


put 8 voltage Offset: 0 voltage
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

43741 AUX101 Ex- Read Only Multiplier: 1 AUX101 input as PCC1301


haust Temp Offset: 0 Exhaust tempera-
Size(Bits): 16 ture
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

43745 AUX101 Read Only Multiplier: 1 AUX101 input as PCC1301


Fuel Level Offset: 0 Fuel level
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

43750 AUX101 In- Read Only Multiplier: 1 AUX101 input as In- PCC1301
take Man- Offset: 0 take Manifold Temp
ifold Temp Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

28
Addr. Parameter Access Specifications Description Control
43757 AUX101 Oil Read Only Multiplier: 1 AUX101 input as oil PCC1301
Temp Offset: 0 Temp
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43793 Configurable Read Only 0. Inactive Measured state of PC 1.x
Input #1 1. Active hardware input
Status
43794 Configurable Read Only 0. Inactive Measured state of PC 1.x
Input #2 1. Active hardware input
Status
43795 Configurable Read Only 0. Inactive Measured state of PC 1.x
Input #3 1. Active hardware input
Status
43822 Re−Transfer Read Write Multiplier : 1 This is the delay af- PC 1.x
Delay Offset: 0 ter the Utility has re-
Size (Bits) : 8 turned and before
Sign: U the Transfer switch
Units: NA is moved back to
Lower Limit: 0 the Utility side posi-
Upper Limit: 59 tion
Default: 1
43825 Transfer Read Write Multiplier : 1 This is the delay PC 1.x
Delay Offset: 0 afte the genset is
Size (Bits) : 16 started before the
Sign: U transfer switch is
Units: seconds moved to the genset
Lower Limit: 60 side position.
Upper Limit: 600
Default: 300
43905 Network Read and 0: Normal Used to command PC1.x
Speed Ad- Write 1: Active a fixed 0.5 Hz in-
just Com- crease in the speed
mand setpoint.

29
Table 1-1 PCC1301 Modbus Mapping for Parameters Having
Different Limits as Compared to PC1.x and PS05000

Addr. Parameter Access Specifications Description Control

43012 Battle Short Read and 0: None, Switch Input for PCC1301
Switch Input Write 1: Configurable Input #1, Battle Short ONLY
2: Configurable Input #2,
3: Configurable Input #3
43069 Voltage Read and Multiplier: 0.0001 Make actual voltage PCC1301
Regulator Write Offset: 0 match Nominals ONLY
Calibration Size(Bits): 16 60Hz when Set
60Hz Sign: U point = 100%.
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
43070 Voltage Read and Multiplier: 0.0001 Make actual voltage PCC1301
Regulator Write Offset: 0 match Nominals ONLY
Calibration Size(Bits): 16 50Hz when Set
50Hz Sign: U point = 100%.
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
43072 Alternator Read and Multiplier: 0.0001 60 Hz line 1 to neu- PCC1301
L1−N 60Hz Write Offset: 0 tral metering voltage ONLY
Voltage Dis- Size(Bits): 16 calibration.
play Adjust Sign: U
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
43073 Alternator Read and Multiplier: 0.0001 60 Hz line 2 to neu- PCC1301
L2−N 60Hz Write Offset: 0 tral metering voltage ONLY
Voltage Dis- Size(Bits): 16 calibration
play Adjust Sign: U
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
43074 Alternator Read and Multiplier: 0.0001 60 Hz line 3 to neu- PCC1301
L3−N 60Hz Write Offset: 0 tral metering voltage ONLY
Voltage Dis- Size(Bits): 16 calibration
play Adjust Sign: U
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000

30
43075 Alternator Read and Multiplier: 0.0001 50 Hz line 1 to neu- PCC1301
L1−N 50Hz Write Offset: 0 tral metering voltage ONLY
Voltage Dis- Size(Bits): 16 calibration
play Adjust Sign: U
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
43076 Alternator Read and Multiplier: 0.0001 50 Hz line 2 to neu- PCC1301
L2−N 50Hz Write Offset: 0 tral metering voltage ONLY
Voltage Dis- Size(Bits): 16 calibration
play Adjust Sign: U
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
43077 Alternator Read and Multiplier: 0.0001 50 Hz line 3 to neu- PCC1301
L3−N 50Hz Write Offset: 0 tral metering voltage ONLY
Voltage Dis- Size(Bits): 16 calibration
play Adjust Sign: U
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
47031 Auto Mains Read Write 0. At Utility Trim to Enable Dis- PC 1.x
Failure 1. At Genset able the ATS Func-
Enable 2. Unkown Position tionality
3. Not Available
47032 Transition to Read Write Multiplier : 1 This is the delay af- PC 1.x
Genset Offset: 0 ter the transfer
Delay Size (Bits) : 8 switch is command-
Sign: U ed to move to gen-
Units: seconds erator side awaiting
Lower Limit: 1 for the feedback.
Upper Limit: 10
Default: 3
47033 Re−Transi- Read Write Multiplier : 1 This is the delay af- PC 1.x
tion to Utility Offset: 0 ter the transfer
Delay Size (Bits) : 8 switch is command-
Sign: U ed to move to utility
Units: seconds side awaiting for the
Lower Limit: 1 feedback.
Upper Limit: 10
Default: 3

31
47034 Utility Fail To Read Write Multiplier : 1 This is the delay af- PC 1.x
Close Delay Offset: 0 ter the transfer
Size (Bits) : 8 switch is moved to
Sign: U utility side, awaiting
Units: seconds for the fault to be-
Lower Limit: 1 come active or inac-
Upper Limit: 10 tive.
Default: 3

47035 Genset Fail Read Write Multiplier : 1 This is the delay af- PC 1.x
To Close Offset: 0 ter the transfer
Delay Size (Bits) : 8 switch is moved to
Sign: U genset side, await-
Units: seconds ing for the fault to
Lower Limit: 1 become active or in-
Upper Limit: 10 active.
Default: 5

47036 Transfer Read Write Multiplier : 1 This is the delay af- PC 1.x
Switch Sig- Offset: 0 ter the transfer
nal Un- Size (Bits) : 8 switch is moved to
known Sign: U any of the sides,
Warning Units: seconds awaiting for the fault
Delay Lower Limit: 5 to become active or
Upper Limit: 10 inactive.
Default: 5

47037 Transfer Read Only 0. At Utility This is the status of PC 1.x


Switch 1. At Genset the transfer switch
Feedback 2. Unkown Position depending upon the
Status 3. Not Available feedback received
47038 Transfer Re- Read Only 0. Not Available This is the status of PC 1.x
transfer 1. OFF the transfer and re-
Status 2. Transfer Start transfer process
3. Retransfer Start
4. Transfer Progress
5. Retransfer Progress
6. Transfer Complete
7. Retransfer Complete
8. Transfer Failed
9. Retransfer Failed
47039 Transfer Read Only 0. At Utility This is the status of PC 1.x
Switch 1. At Genset the transfer switch
2. Unkown Position depending upon the
3. Not Available fault
47040 Clock Cycle Read Write 0. AM Used to set AM_PM PC 1.x
1. PM Cycle or Read the
same

47041 Scheduler Read Write 0. AM User can set the PC 1.x


Prog Start 1. PM AM/PM period for
Period Scheduler

32
47042 Transfer Read Write 0. Disable Trim to enable PC 1.x
Switch 1. Enable transfer switch feed-
Feedback back logic
Enable
47043 Fuel System Read Write 0. Diesel Type of fuel and PC 1.x
1. Gas ignition system used
by genset
47044 Gas Fuel Read Write 0. Natural Gas Trim to set the type PC 1.x
Type 1. Propane of gaseous fuel
2. Dual
47045 Low Fuel Read Only 0.Inactive Displays Inactive/ PC 1.x
Pressure 1.Active Active status of
Switch Switch
47046 Low Fuel Read Write 0. Active Closed State selection of PC 1.x
Pressure 1. Active Open Low fuel pressure
Switch Ac- switch
tive State
Selection
47047 LTA Temper- Read Only Multiplier : 1 The processed val- PC 1.x
ature Offset: 0 ue of the LTA Tem-
Size (Bits) : 16 perature sensor for
Sign: S the System IO Mod-
Units: DegF ule
Lower Limit: NA
Upper Limit: NA
Default: NA
47048 Intake Man- Read Write 0. Disabled Trim to enable the PC 1.x
ifold Over 1. Enabled detection of Intake
Pres- Manifold Backfire
sure(IMOP) condition
Enable
47049 Intake Man- Read Write 0. SPN 105 Source for Intake PC 1.x
ifold Tem- 1. SPN 52 Manifold Tempera-
perature ture. SPN 105 De-
Source fault Source and
SPN 52 when the
IMOP is Enabled
47050 Intake Man- Read Write Multiplier : 0.1 Threshold to decide PC 1.x
ifold Temp Offset: 0 the Intake Manifold
Rate of Size (Bits) : 8 Backfire condition,
Change Sign: U Value entered is for
Threshold Units: DegF/sec degF/secs,
Lower Limit: 2 degF/2secs is ob-
Upper Limit: 10 tained by a scalar of
Default: 5 2 in PCC software
47051 Annunciator Read Only 0. Driver Off State of output as PC 1.x
Output 1 1.Driver On seen by the Annun-
Status ciator

33
47052 Annunciator Read Only 0. Driver Off State of output as PC 1.x
Output 1 1.Driver On seen by the Annun-
Status ciator
47053 Annunciator Read Only 0. Driver Off State of output as PC 1.x
Output 3 1.Driver On seen by the Annun-
Status ciator
47054 Annunciator Read Only 0. Driver Off State of output as PC 1.x
Output 4 1.Driver On seen by the Annun-
Status ciator
47055 KTA Fuel Read Only Multiplier : 0.1 The D.F.P for the PC 1.x
Differential Offset: 0 KTA engines high
Pressure Size (Bits) : 16 side sensor
High Side Sign: S
Units: PSI
Lower Limit: NA
Upper Limit: NA
Default: NA
47056 KTA Fuel Read Only Multiplier : 0.1 The D.F.P for the PC 1.x
Differential Offset: 0 KTA engines low
Pressure Size (Bits) : 16 side sensor
Low Side Sign: S
Units: PSI
Lower Limit: NA
Upper Limit: NA
Default: NA
47057 Air Shutoff Read Only Multiplier : 0.01 The Air Shutoff PC 1.x
Valve Offset: 0 Valve Voltage con-
Voltage Size (Bits) : 16 figured for SID
Sign: S sender input 7 or 8.
Units: Vdc (Enabled only for Oil
Lower Limit: NA and Gas Features)
Upper Limit: NA
Default: NA
47058 Percent Read Only Multiplier : 0.1 The calculated level PC 1.x
Dirty Fuel Offset: 0 at which the fuel fil-
Filter Size (Bits) : 16 ter is clogged
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
47059 QSK Differ- Read Only Multiplier : 0.1 The fuel pressure PC 1.x
ential Pres- Offset: 0 measure on the
sure Low Size (Bits) : 16 QSK engines low
Side Sign: S side of the fuel filter
Units: PSI
Lower Limit: NA
Upper Limit: NA
Default: NA

34
47060 Main Relay Read Only Multiplier : 1 System IO Main PC 1.x
Status Offset: 0 Relay Status
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
47061 Expansion Read Only Multiplier : 1 System IO Expan- PC 1.x
Relay Status Offset: 0 sion Relay Status
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA

35
THIS PAGE LEFT INTENTIONALLY BLANK

36
2. PowerCommand 2.x/3.x Modbus Register Map

Modbus Communications Network Failed Data==> “Network Failure” data


shall be represented as three less than the highest
Use the following equation to calculate the value of positive value for that parameter. For example for a
32-bit parameters. two byte, unsigned integer that would be 65532. For
A = high register value a signed integer that would be 32764.
B = low register value
parameter = (A * 65536 * multiplier) + (B * multiplier)  Data that comes from a network that has failed,
such as sensors on the PCCnet I/O Module or sensor
For example, Engine Running Time is a 32-bit pa- data coming in via the CAN datalink will be classified
rameter in registers 40070 and 40071. like this.
Register 40070 has 322 (high register value = A).
Register 40071 has 15637 (low register value = B). Hardware/Component Failure==> “Hardware/
Component Failure” data shall be represented as
Engine Running Time = (322 * 65536 * 0.1) + (15637 * four less than the highest positive value for that pa-
0.1) rameter. For example for a two byte, unsigned inte-
ger that would be 65531. For a signed integer that
The engine run-time is 2111823 seconds, or 586.6 would be 32763.
hours.
 A hardware/component failure that provides the
To write a 32−bit value to 2 modbus registers, calcu- data, such as the voltage, current and power data
late the value for each register as follows: that comes from an external metering chip will be
A (High register value) = INT ((Parameter / Multiplier) classified like this.
/ 65536))
B (Low register value) = INT ((Parameter / Multiplier)
% (65536)) Out of Range High/Out of Range==> “Out of Range
% = Modulus (the remainder of integer division) High/Out of Range” data shall be represented as one
less than the highest positive value for that parame-
For example: ter. For example for a two byte, unsigned integer that
To write Load Demand Genset Run Hours = 80000.5 would be 65534. For a signed integer that would be
Register 40769 (high register value A) should be writ- 32766.
ten to INT ((80000.5/0.1)/65536) = 12
Register 40770 (low register value B) should be writ-  Data that has been determined to be out of range
ten to INT ((80000.5/.01)%65536) = 13573 high or out of range (when there is no distinction be-
tween out of range high and out of range low) due to
To write 32−bit values to 2 modbus addresses always an open sensor for example, will be classified like
write the high register value followed by the low regis- this.
ter value. Both registers must be written to change
the 32−bit value in the control. Out of Range Low==> “Out of Range Low” data
shall be represented as two less than the highest
positive value for that parameter. For example for a
Parametrics (Analog Values) two byte, unsigned integer that would be 65533. For
a signed integer that would be 32765.
Unsupported (Not Available) Data==> “Not Avail-
able” data shall be represented as highest positive  Data that has been determined to be out of range
value for that parameter. For example for a two byte, low due to a shorted sensor for example, will be clas-
unsigned integer that would be 65535. For a signed sified like this.
integer that would be 32767.
Data within Normal Operating Range (Valid)==>
 Parameters which are not available due to the sen- Basically anything other than above.
sor not being installed, or not enabled in the control-
lers configuration will classified like this.

37
Note: Earlier versions of software may not support all of the Modbus registers in the following table. If a particu-
lar register is not available in your installation, it is possible that the Modbus connection is working but the con-
troller software does not support that particular register.

Note: If an address or bit is not listed in this table it is not used.

Note: The external device can read 1−40 contiguous registers, write 1−40 contiguous registers, or read diagnos-
tic counters.

Note: The Lowest modbus register value is considered as the High Register Value and the highest modbus reg-
ister value is considered as the low Register Value.

Addr. Parameter Access Specifications Description Control


40010 Control Switch Read 0: Off Current position of the generator PC 2.x,
Position Only 1: Auto set switch panel Off−Run−Auto PC 3.x
2: Manual switch as seen by the generator
set control. SEE ALSO AD-
DRESS 40580.
NOTE: Both address 40580 and
40010 show the same information
however the specification for
each is different.
40011 Genset Run Read 0: Stop Current genset operating PC 2.x
Sequence State Only 1: Time Delay to Start mode.Modbus mapping shall be PC3.x
2: Warmup at Idle in both addresses 43500 and
3: Rated Freq and Voltage 40011
4: Cooldown / Stop Delay
5:
5 CCooldown
ld att Idle
Idl
6: Rated to Idle Transition Delay
40012 Most Recent Read Multiplier: 1 This Modbus Register displays PC 2.x,
Fault or Warn- Only Offset: 0 most recent Fault or Warning. It is PC 3.x
ing Size (bits): 16 not mapped with any logical.
Sign: U
Unit:
L
Lower Limit:
Li it
Upper Limit: 65530
40013 Modbus regis
regis- Read 0: None This register returns the Fault PC 2.x,
ter 40013 Onlyy 1: Warning
g Type
yp of the Fault Code. This is PC 3.x
2: Shutdown not associated with any logical.
40014 Genset % Read Multiplier: 0.01 Monitors the total generator set PC 2.x,
Standby Total Only Offset: 0 standby KW percentage output. PC 3.x
kW Size (bits): 16
Sign: S
Unit: %
L
Lower Limit:
Li it
Upper Limit:
40016 NFPA 110 Log- Read Multiplier: 1.0 16−bit number to represent the PC 2.x,
ical Status Only Offset: 0 status of the NFPA 110 logical. PC 3.x
Size (bits): 16 See NFPA 110 bitmap.
Sign: U
Unit:
Lower
L Limit:
Li it
Upper Limit:

38
Addr. Parameter Access Specifications Description Control
40017 Extended NFPA Read Multiplier: 1.0 16−bit number to represent the PC 2.x,
110 Logical Only Offset: 0 status of the NFPA 110 logical. PC 3.x
Status Size (bits): 16 See NFPA 110 bitmap.
Sign: U
Unit:
Lower
L Limit:
Li it
Upper Limit:
40018 Genset L1N Read Multiplier: 1 Generator set L1N voltage PC 2.x,
Voltage Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: Vac
Lower
L Limit:
Li it
Upper Limit:
40019 Genset L2N Read Multiplier: 1 Generator set L2N voltage PC 2.x,
Voltage Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: Vac
L
Lower Limit:
Li it
Upper Limit:
40020 Genset L3N Read Multiplier: 1 Generator set L3N voltage PC 2.x,
Voltage Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: Vac
L
Lower Limit:
Li it
Upper Limit:
40021 Genset LN Av- Read Multiplier : 1 Genset Line to Neutral average PC 2.X
erage Voltage Only Offset: 0 voltage PC3.X
Size (Bits) : 16
Sign: U
Units: Vac
U
Upper Limit:
Li it NA
Default: 0
40022 Genset L1L2 Read Multiplier: 1 Generator set L1L2 voltage PC 2.x,
Voltage Only Lower Limit: NA PC 3.x
Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40023 Genset L2L3 Read Multiplier: 1 Generator set L2L3 voltage PC 2.x,
Voltage Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: Vac
Lower
L Limit:
Li it
Upper Limit:

39
Addr. Parameter Access Specifications Description Control
40024 Genset L3L1 Read Multiplier: 1 Generator set L3L1 voltage PC 2.x,
Voltage Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: Vac
Lower
L Limit:
Li it
Upper Limit:

40025 Genset LL Av- Read Multiplier: 1 Generator set Line to Line aver- PC 2.x,
erage Voltage Only Offset: 0 age voltage PC 3.x
Size (bits): 16
Sign: U
Unit: Vac
L
Lower Limit:
Li it
Upper Limit:

40026 Genset L1 Cur- Read Multiplier: 1 Monitors the generator set L1 cur- PC 2.x,
rent Only Offset: 0 rent value. PC 3.x
Size (bits): 16
Sign: U
Unit: Amps
Lower
L Limit:
Li it
Upper Limit:

40027 Genset L2 Read Multiplier: 1 Generator set L2 current PC 2.x,


Current Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: Amps
L
Lower Limit:
Li it
Upper Limit:

40028 Genset L3 Read Multiplier: 1 Generator set L3 current PC 2.x,


Current Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: Amps
L
Lower Limit:
Li it
Upper Limit:

40029 Genset Aver- Read Multiplier: 1 Generator set average current PC 2.x,
age Current Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:

40030 Genset Neutral Read Multiplier: 1 Generator set neutral current PC 3.x
Current Only Offset: 0
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:

40
Addr. Parameter Access Specifications Description Control
40031 Genset L1 kW Read Multiplier: 1 Generator set L1 kW PC 2.x,
Only Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: kW
Lower Limit:
Upper Limit:

40032 Genset L2 kW Read Multiplier: 1 Generator set L2 kW PC 2.x,


Only Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: kW
Lower Limit: −32768
Upper Limit: 32762

40033 Genset L3 kW Read Multiplier: 1 Generator set L3 kW PC 2.x,


Only Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: kW
Lower Limit: −32768
Upper Limit: 32762

40034 Genset Total Read Multiplier: 1 Generator set total kW PC 2.x,


kW Only Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: kW
Lower Limit:
Upper Limit:

40035 Genset L1 Read Multiplier: 1 Generator set L1 KVAR PC 2.x,


kVAR Only Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit:

40036 Genset L2 Read Multiplier: 1 Generator set L2 Kvar PC 2.x,


kVAR Only Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit: −32768
Upper Limit: 32762

40037 Genset L3 Read Multiplier: 1 Generator set L3 Kvar PC 2.x,


kVAR Only Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit

41
Addr. Parameter Access Specifications Description Control
40038 Genset Total Read Multiplier: 1 Generator set total kVAR PC 2.x,
kVAR Only Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit

40039 Genset Total Read Multiplier: 0.01 Generator set total power factor PC 2.x,
Power Factor Only Offset: 0 (L1+L2+L3) PC 3.x
Size (bits): 8
Sign: S
Unit: PF
Lower Limit:
Upper Limit

40040 Genset L1 kVA Read Multiplier: 1 Generator set L1 kVA PC 2.x,


Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit

40041 Genset L2 kVA Read Multiplier: 1 Generator set L2 kVA PC 2.x,


Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit

40042 Genset L3 kVA Read Multiplier: 1 Generator set L3 kVA PC 2.x,


Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit kVA
Lower Limit:
Upper Limit

40043 Genset Total Read Multiplier: 1 Generator set total kVA PC 2.x,
kVA Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit

40044 Genset Fre- Read Multiplier : 0.01 Genset Frequency OP. Modbus ”PC 2.X
quency OP Only Offset: 0 has different multiplier than PC3.X”
Size (bits): 16 PCCnet. For Modbus use only,
Sign: U Multiplier/Units = 0.1 Hz
Unit: Hz
Lower Limit: NA
Upper Limit: NA

42
Addr. Parameter Access Specifications Description Control
40046 Genset Total Read Multiplier: 1 Generator set total negative kWh PC 2.x,
Negative kWh Only Offset: 0 accumulation PC 3.x
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:

40047 Genset Total Read Multiplier: 1 Generator set total negative kWh PC 2.x,
Negative kWh Only Offset: 0 accumulation PC 3.x
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:

40048 Genset Total Read Multiplier: 1 Generator set total positive kWh PC 2.x,
Positive kWh Only Offset: 0 accumulation PC 3.x
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit: 0
Upper Limit: 4294967290

40049 Genset Total Read Multiplier: 1 Generator set total positive kWh PC 2.x,
Positive kWh Only Offset: 0 accumulation PC 3.x
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit: 0
Upper Limit: 4294967290

40050 Genset Total Read Multiplier: 1 Generator set total net kWh accu- PC 2.x,
Net kWh Only Offset: 0 mulation PC 3.x
Size (bits): 32
Sign: S
Unit: kWh
Lower Limit: −2147483648
Upper Limit: 2147483643

40051 Genset Total Read Multiplier: 1 Generator set total net kWh accu- PC 2.x,
Net kWh Only Offset: 0 mulation PC 3.x
Size (bits): 32
Sign: S
Unit: kWh
Lower Limit: −2147483648
Upper Limit: 2147483643

40052 Genset Total Read Multiplier: 1 Generator set total negative PC 2.x,
Negative Only Offset: 0 kVARh accumulation PC 3.x
kVARh Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:

43
Addr. Parameter Access Specifications Description Control
40053 Genset Total Read Multiplier: 1 Generator set total negative PC 2.x,
Negative Only Offset: 0 kVARh accumulation PC 3.x
kVARh Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:

40054 Genset Total Read Multiplier: 1 Generator set total positive PC 2.x,
Positive kVARh Only Offset: 0 kVARh accumulation PC 3.x
Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit: 0
Upper Limit: 4294967290

40055 Genset Total Read Multiplier: 1 Generator set total positive PC 2.x,
Positive kVARh Only Offset: 0 kVARh accumulation PC 3.x
Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit: 0
Upper Limit: 4294967290

40056 Genset Total Read Multiplier: 1 Generator set total net kVARh ac- PC 2.x,
Net kVARh Only Offset: 0 cumulation PC 3.x
Size (bits): 32
Sign: S
Unit: kVARh
Lower Limit: −2147483648
Upper Limit: 2147483643

40057 Generator set Read Multiplier: 1 Generator set total net kVARh ac- PC 2.x,
Total Net Only Offset: 0 cumulation PC 3.x
kVARh Size (bits): 32
Sign: S
Unit: kVARh
Lower Limit: −2147483648
Upper Limit: 2147483643

40058 Genset % Read Multiplier: 0.1 Monitors the generator set stand- PC 2.x,
Standby L1 Only Offset: 0 by L1 current percentage output. PC 3.x
Current Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:

40059 Genset % Read Multiplier: 0.1 Monitors the generator set stand- PC 2.x,
Standby L2 Only Offset: 0 by L2 current percentage output. PC 3.x
Current Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:

44
Addr. Parameter Access Specifications Description Control
40060 Genset % Read Multiplier: 0.1 Monitors the generator set stand- PC 2.x,
Standby L3 Only Offset: 0 by L3 current percentage output. PC 3.x
Current Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
40061 Battery Voltage Read Multiplier: 0.1 Battery voltage value. Modbus PC 2.x,
Only Offset: 0 and PCCnet has different multipli- PC 3.x
Size (bits): 16 er value. For Modbus use only,
Sign: U multiplier/units = 0.1 volts
Unit: Vdc
Lower Limit:
Upper Limit:
40062 Oil Pressure Read Multiplier: 1 Monitor point for the Oil Pressure. PC 2.x,
Only Offset: 0 Modbus and PCCnet have differ- PC 3.x
Size (bits): 16 ent multiplier value. For Modbus
Sign: U use only, Multiplier/Units = 1kPa
Unit: kPa
Lower Limit:
Upper Limit:
40063 Oil Tempera- Read Multiplier: 0.1 Monitor point for the Oil Tempera- PC 2.x,
ture Only Offset: 0 ture PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit:
Upper Limit:
40064 Coolant Tem- Read Multiplier: 0.1 Monitor point for the Coolant PC 2.x,
perature Only Offset: 0 Temperature. Modbus mapping PC 3.x
Size (bits): 16 shall be to both 46126 and 40064
Sign: S addresses. For Modbus use only,
Unit: degC Multiplier/Units = 0.1C
Lower Limit:
Upper Limit:
40065 Intake Manifold Read Multiplier: 0.1 To monitor Intake Manifold Tem- PC 2.x,
Temperature Only Offset: 0 perature. This parameter repre- PC 3.x
Size (bits): 16 sents ”Intake Manifold Tempera-
Sign: S ture 1”.
Unit: degF
Lower Limit: −40
Upper Limit: 410
40065 Intake Manifold Read Multiplier: 0.1 To monitor Intake Manifold Tem- PC 2.x,
Temperature Only Offset: 0 perature. This parameter repre- PC 3.x
Size (bits): 16 sents ”Intake Manifold Tempera-
Sign: S ture 1”.
Unit: degF
Lower Limit: −40
Upper Limit: 410

45
Addr. Parameter Access Specifications Description Control
40066 Fuel Tempera- Read Multiplier: 0.1 Monitor point for the Fuel Temper- PC 2.x,
ture Only Offset: 0 ature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −40
Upper Limit: 410

40067 Fuel Rate Read Multiplier: 0.05 Monitor point for the Fuel Rate PC 2.x,
Only Offset: 0 PC 3.x
Size (bits): 16
Sign: S
Unit: gal/hr
Lower Limit:
Upper Limit:

40068 Average Engine Read Multiplier: 1 Monitor point for the Average En- PC 2.x,
Speed Only Offset: 0 gine Speed. Modbus and PCCnet PC 3.x
Size (bits): 16 have different multiplier value. For
Sign: U Modbus use only, Multiplier/Units
Unit: RPM = 1 RPM
Lower Limit:
Upper Limit:

40069 Total Start At- Read Multiplier : 1 Total number of start attempts ”PC 2.X,
tempts OP Only Offset: 0 PC3.X”
Size (bits): 16
Sign: U
Unit: NAr
Lower Limit: 0
Upper Limit: 65535

40070 Engine Running Read Multiplier: 0.1 Total engine run time. Modbus PC 2.x,
Time Only Offset: 0 has different multiplier than PC 3.x
Size (bits): 32 PCCnet. For Modbus use only,
Sign: U multiplier/units = 0.1 Sec
Unit: seconds
Lower Limit:
Upper Limit:

40071 Engine Running Read Multiplier: 0.1 Total engine run time. Modbus PC 2.x,
Time Only Offset: 0 has different multiplier than PC 3.x
Size (bits): 32 PCCnet. For Modbus use only,
Sign: U multiplier/units = 0.1 Sec
Unit: seconds
Lower Limit:
Upper Limit:

40072 Total Fuel Con- Read Multiplier: 0.1 Total fuel consumption since start PC 2.x,
sumption Only Offset: 0 of engine. PC 3.x
Size (bits): 32
Sign: U
Unit: gallons
Lower Limit:
Upper Limit:

46
Addr. Parameter Access Specifications Description Control
40073 Total Fuel Con- Read Multiplier: 0.1 Total fuel consumption since start PC 2.x,
sumption Only Offset: 0 of engine. PC 3.x
Size (bits): 32
Sign: U
Unit: gallons
Lower Limit:
Upper Limit:

40074 Total Number of Read Multiplier: 1 Total number of generator set PC 2.x,
Runs Only Offset: 0 runs. PC 3.x
Size (bits): 32
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967295

40075 Total Number of Read Multiplier: 1 Total number of generator set PC 2.x,
Runs Only Offset: 0 runs. PC 3.x
Size (bits): 32
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967295

40076 Runs Reset Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Time Only Offset: 0 the last time the Run Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40076−40092 for 17 char of this
string.

40077 Runs Reset Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Time Only Offset: 0 the last time the Run Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40076−40092 for 17 char of this
string.

40078 Runs Reset Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Time Only Offset: 0 the last time the Run Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40076 − 40092 for 17 char of this
string.

47
Addr. Parameter Access Specifications Description Control
40079 Runs Reset Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Time Only Offset: 0 the last time the Run Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40076−40092 for 17 char of this
string.
40080 Runs Reset Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Time Only Offset: 0 the last time the Run Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40076−40092 for 17 char of this
string.
40081 Runs Reset Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Time Only Offset: 0 the last time the Run Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40076−40092 for 17 char of this
string.
40082 Runs Reset Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Time Only Offset: 0 the last time the Run Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40076−40092 for 17 char of this
string.
40083 Runs Reset Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Time Only Offset: 0 the last time the Run Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40076−40092 for 17 char of this
string.

48
Addr. Parameter Access Specifications Description Control
40084 Runs Reset Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Time Only Offset: 0 the last time the Run Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40076−40092 for 17 char of this
string.
40085 Runs Reset Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Time Only Offset: 0 the last time the Run Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40076−40092 for 17 char of this
string.
40086 Runs Reset Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Time Only Offset: 0 the last time the Run Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40076−40092 for 17 char of this
string.
40087 Runs Reset Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Time Only Offset: 0 the last time the Run Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40076−40092 for 17 char of this
string.
40088 Runs Reset Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Time Only Offset: 0 the last time the Run Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40076−40092 for 17 char of this
string.

49
Addr. Parameter Access Specifications Description Control
40089 Runs Reset Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Time Only Offset: 0 the last time the Run Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40076−40092 for 17 char of this
string.
40090 Runs Reset Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Time Only Offset: 0 the last time the Run Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40076−40092 for 17 char of this
string.
40091 Runs Reset Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Time Only Offset: 0 the last time the Run Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40076−40092 for 17 char of this
string.
40092 Runs Reset Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Time Only Offset: 0 the last time the Run Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40076−40092 for 17 char of this
string.
40096 Start Attempts Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Reset Time Only Offset: 0 the last time the Start Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40096−0112 for 17 char of this
string.

50
Addr. Parameter Access Specifications Description Control
40097 Start Attempts Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Reset Time Only Offset: 0 the last time the Start Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40096−0112 for 17 char of this
string.
40098 Start Attempts Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Reset Time Only Offset: 0 the last time the Start Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40096−0112 for 17 char of this
string.
40099 Start Attempts Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Reset Time Only Offset: 0 the last time the Start Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40096−0112 for 17 char of this
string.
40100 Start Attempts Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Reset Time Only Offset: 0 the last time the Start Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40096−0112 for 17 char of this
string.
40101 Start Attempts Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Reset Time Only Offset: 0 the last time the Start Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40096−0112 for 17 char of this
string.

51
Addr. Parameter Access Specifications Description Control
40102 Start Attempts Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Reset Time Only Offset: 0 the last time the Start Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40096−0112 for 17 char of this
string.
40103 Start Attempts Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Reset Time Only Offset: 0 the last time the Start Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40096−0112 for 17 char of this
string.
40104 Start Attempts Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Reset Time Only Offset: 0 the last time the Start Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40096−0112 for 17 char of this
string.
40105 Start Attempts Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Reset Time Only Offset: 0 the last time the Start Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40096−0112 for 17 char of this
string.
40106 Start Attempts Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Reset Time Only Offset: 0 the last time the Start Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40096−0112 for 17 char of this
string.

52
Addr. Parameter Access Specifications Description Control
40107 Start Attempts Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Reset Time Only Offset: 0 the last time the Start Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40096−0112 for 17 char of this
string.
40108 Start Attempts Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Reset Time Only Offset: 0 the last time the Start Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40096−0112 for 17 char of this
string.
40109 Start Attempts Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Reset Time Only Offset: 0 the last time the Start Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40096−0112 for 17 char of this
string.
40110 Start Attempts Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Reset Time Only Offset: 0 the last time the Start Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40096−0112 for 17 char of this
string.
40111 Start Attempts Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Reset Time Only Offset: 0 the last time the Start Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40096−0112 for 17 char of this
string.

53
Addr. Parameter Access Specifications Description Control
40112 Start Attempts Read Multiplier: 1 Real Time Clock stamp record of PC 2.x,
Reset Time Only Offset: 0 the last time the Start Attempts PC 3.x
Size (bits): 144 were reset. This parameter is
Sign: C READ/WRITE for Mon and
Unit: PCCNet and READ ONLY for
Lower Limit: Modbus. Modbus implementation
Upper Limit: or the Real time stamp will use
40096−0112 for 17 char of this
string.
40118 Utility L1N Volt- Read Multiplier: 1 Utility L1N voltage PC 3.x
age Only Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

40119 Utility L2N Volt- Read Multiplier: 1 Utility L2N voltage PC 3.x
age Only Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40120 Utility L3N Volt- Read Multiplier: 1 Utility L3N voltage PC 3.x
age Only Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40121 Utility LN Read Multiplier : 1 Utility Line to Neutral average PC3.X
Average Volt- Only Offset: 0 voltage
age Size (bits): 16
Sign: U
Unit: Vac
Lower Limit: NA
Upper Limit: NA
40122 Utility L1L2 Read Multiplier: 1 Utility L1L2 voltage PC 3.x
Voltage Only Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

54
Addr. Parameter Access Specifications Description Control
40123 Utility L2L3 Read Multiplier: 1 Utility L2L3 voltage PC 3.x
Voltage Only Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40124 Utility L3L1 Read Multiplier: 1 Utility L3L1 voltage PC 3.x
Voltage Only Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40125 Utility LL Aver- Read Multiplier: 1 Utility Line to Line average volt- PC 3.x
age Voltage Only Offset: 0 age
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40126 Utility L1 Cur- Read Multiplier: 1 Utility L1 current PC 3.x
rent Only Offset: 0
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:

40127 Utility L2 Cur- Read Multiplier: 1 Utility L2 current PC 3.x


rent Only Offset: 0
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:
40128 Utility L3 Cur- Read Multiplier: 1 Utility L3 current PC 3.x
rent Only Offset: 0
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:
Offset: 0

55
Addr. Parameter Access Specifications Description Control
40129 Utility Average Read Multiplier : 1 Utility average current PC3.X
Current Only Offset: 0
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit: NA
Upper Limit: NA
Default: NA
40131 Utility L1 kW Read Multiplier: 1 Utility L1 kW PC 3.x
Only Offset: 0
Size (bits): 16
Sign: S
Unit: kW
Lower Limit:
Upper Limit:

40132 Utility L2 kW Read Multiplier: 1 Utility L2 kW PC 3.x


Only Offset: 0
Size (bits): 16
Sign: S
Unit: kW
Lower Limit:
Upper Limit:
40133 Utility L3 kW Read Multiplier: 1 Utility L3 kW PC 3.x
Only Offset: 0
Size (bits): 16
Sign: S
Unit: kW
Lower Limit:
Upper Limit:
40134 Utility Total kW Read Multiplier: 1 Utility total kW PC 3.x
Only Offset: 0
Size (bits): 16
Sign: S
Unit: kW
Lower Limit:
Upper Limit:
40135 Utility L1 kVAR Read Multiplier: 1 Utility L1 Kvar PC 3.x
Only Offset: 0
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit:

56
Addr. Parameter Access Specifications Description Control
40136 Utility L2 kVAR Read Multiplier: 1 Utility L2 Kvar PC 3.x
Only Offset: 0
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit:

40137 Utility L3 kVAR Read Multiplier: 1 Utility L3 Kvar PC 3.x


Only Offset: 0
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit:

40138 Utility Total Read Multiplier: 1 Utility total kVAR PC 3.x


kVAR Only Offset: 0
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit:

40139 Utility Total Read Multiplier: 0.01 Utility total power factor PC 3.x
Power Factor Only Offset: 0
Size (bits): 8
Sign: S
Unit: PF
Lower Limit:
Upper Limit:

40140 Utility L1 kVA Read Multiplier: 1 Utility L1 kVA PC 3.x


Only Offset: 0
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:

40141 Utility L2 kVA Read Multiplier: 1 Utility L2 kVA PC 3.x


Only Offset: 0
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:

40142 Utility L3 kVA Read Multiplier: 1 Utility L3 kVA PC 3.x


Only Offset: 0
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:

57
Addr. Parameter Access Specifications Description Control
40143 Utility Total kVA Read Multiplier: 1 Utility total kVA PC 3.x
Only Offset: 0
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:
40144 Utility Frequen- Read Multiplier: 0.001 Utility line frequency PC 3.x
cy Only Offset: 0
Size (bits): 32
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
40145 Utility Frequen- Read Multiplier: 0.001 Utility line frequency PC 3.x
cy Only Offset: 0
Size (bits): 32
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
40146 Utility Total Read Multiplier: 1 Utility total negative kWh accu- PC 3.x
Negative kWh Only Offset: 0 mulation
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:

40147 Utility Total Read Multiplier: 1 Utility total negative kWh accu- PC 3.x
Negative kWh Only Offset: 0 mulation
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:
40148 Utility Total Read Multiplier: 1 Utility total positive kWh accu- PC 3.x
Positive kWh Only Offset: 0 mulation
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:
40149 Utility Total Read Multiplier: 1 Utility total positive kWh accu- PC 3.x
Positive kWh Only Offset: 0 mulation
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:

58
Addr. Parameter Access Specifications Description Control
40150 Utility Total Net Read Multiplier: 1 Utility total net kWh accumulation PC 3.x
kWh Only Offset: 0
Size (bits): 32
Sign: S
Unit: kWh
Lower Limit:
Upper Limit:

40151 Utility Total Net Read Multiplier: 1 Utility total net kWh accumulation PC 3.x
kWh Only Offset: 0
Size (bits): 32
Sign: S
Unit: kWh
Lower Limit:
Upper Limit:

40152 Utility Total Read Multiplier: 1 Utility total negative kVARh accu- PC 3.x
Negative Only Offset: 0 mulation
kVARh Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:

40153 Utility Total Read Multiplier: 1 Utility total negative kVARh accu- PC 3.x
Negative Only Offset: 0 mulation
kVARh Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:

40154 Utility Total Read Multiplier: 1 Utility total positive kVARh accu- PC 3.x
Positive kVARh Only Offset: 0 mulation
Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:

40155 Utility Total Read Multiplier: 1 Utility total positive kVARh accu- PC 3.x
Positive kVARh Only Offset: 0 mulation
Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:

40156 Utility Total Net Read Multiplier: 1 Utility total net kVARh accumula- PC 3.x
kVARh Only Offset: 0 tion
Size (bits): 32
Sign: S
Unit: kVARh
Lower Limit:
Upper Limit:

59
Addr. Parameter Access Specifications Description Control
40157 Utility Total Net Read Multiplier: 1 Utility total net kVARh accumula- PC 3.x
kVARh Only Offset: 0 tion
Size (bits): 32
Sign: S
Unit: kVARh
Lower Limit:
Upper Limit:
40158 Genset Bus Read Multiplier: 1 Generator set Bus L1N voltage PC 3.x
L1N Voltage Only Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

40159 Genset Bus Read Multiplier: 1 Generator set Bus L2N voltage PC 3.x
L2N Voltage Only Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40160 Genset Bus Read Multiplier: 1 Generator set Bus L3N voltage PC 3.x
L3N Voltage Only Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40161 Genset Bus LN Read Multiplier : 1 Genset Bus Line to Neutral aver- PC3.X
Average Volt- Only Offset: 0 age voltage
age Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40162 Genset Bus Read Multiplier: 1 Generator set Bus L1L2 voltage PC 3.x
L1L2 Voltage Only Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40163 Genset Bus Read Multiplier: 1 Generator set Bus L2L3 voltage PC 3.x
L2L3 Voltage Only Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

60
Addr. Parameter Access Specifications Description Control
40164 Genset Bus Read Multiplier: 1 Generator set Bus L3L1 voltage PC 3.x
L3L1 Voltage Only Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

40165 Genset Bus LL Read Multiplier: 1 Generator set Bus Line to Line PC 3.x
Average Volt- Only Offset: 0 average voltage
age Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

40166 Genset Bus L1 Read Multiplier: 1 Generator set Bus L1 current PC 3.x
Current Only Offset: 0
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit: 0
Upper Limit: 65530

40167 Genset Bus L2 Read Multiplier: 1 Generator set Bus L2 current PC 3.x
Current Only Offset: 0
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:

40168 Genset Bus L3 Read Multiplier: 1 Generator set Bus L3 current PC 3.x
Current Only Offset: 0
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:

40169 Genset Bus Av- Read Multiplier : 1 Genset Bus Average current PC3.X
erage Current Only Offset: 0
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit: NA
Upper Limit: NA

40171 Genset Bus L1 Read Multiplier: 1 Generator set Bus L1 kW PC 3.x


kW Only Offset: 0
Size (bits): 16
Sign: S
Unit: kW
Lower Limit: −32768
Upper Limit: 32762

61
Addr. Parameter Access Specifications Description Control
40172 Genset Bus L2 Read Multiplier: 1 Generator set Bus L2 kW PC 3.x
kW Only Offset: 0
Size (bits): 16
Sign: S
Unit: kW
Lower Limit: −32768
Upper Limit: 32762

40173 Genset Bus L3 Read Multiplier: 1 Generator set Bus L3 kW PC 3.x


kW Only Offset: 0
Size (bits): 16
Sign: S
Unit: kW
Lower Limit:
Upper Limit:

40174 Genset Bus To- Read Multiplier: 1 Generator set Bus total kW PC 3.x
tal kW Only Offset: 0
Size (bits): 16
Sign: S
Unit: kW
Lower Limit:
Upper Limit:

40175 Genset Bus L1 Read Multiplier: 1 Generator set bus L1 Kvar PC 3.x
kVAR Only Offset: 0
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit: −32678
Upper Limit: 32672

40176 Genset Bus L2 Read Multiplier: 1 Generator set bus L2 Kvar PC 3.x
kVAR Only Offset: 0
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit: −32678
Upper Limit: 32672

40177 Genset Bus L3 Read Multiplier: 1 Generator set bus L3 Kvar PC 3.x
kVAR Only Offset: 0
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit:

40178 Genset Bus To- Read Multiplier: 1 Generator set bus total kVAR PC 3.x
tal kVAR Only Offset: 0
Size (bits): 16
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit:

62
Addr. Parameter Access Specifications Description Control
40179 Genset Bus To- Read Multiplier: 0.01 Generator set Bus Total power PC 3.x
tal Power Fac- Only Offset: 0 factor
tor Size (bits): 8
Sign: S
Unit: PF
Lower Limit:
Upper Limit:

40180 Genset Bus L1 Read Multiplier: 1 Generator set Bus L1 kVA PC 3.x
kVA Only Offset: 0
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:

40181 Genset Bus L2 Read Multiplier: 1 Generator set Bus L2 kVA PC 3.x
kVA Only Offset: 0
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:

40182 Genset Bus L3 Read Multiplier: 1 Generator set Bus L3 kVA PC 3.x
kVA Only Offset: 0
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:

40183 Genset Bus To- Read Multiplier: 1 Generator set bus total kVA PC 3.x
tal kVA Only Offset: 0
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:

40184 Genset Bus Read Multiplier: 0.001 Generator set bus line frequency PC 3.x
Frequency Only Offset: 0
Size (bits): 32
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:

40185 Genset Bus Read Multiplier: 0.001 Generator set bus line frequency PC 3.x
Frequency Only Offset: 0
Size (bits): 32
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:

63
Addr. Parameter Access Specifications Description Control
40186 Genset Bus To- Read Multiplier: 1 Generator set bus total negative PC 3.x
tal Negative Only Offset: 0 kWh accumulation
kWh Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:

40187 Genset Bus To- Read Multiplier: 1 Generator set bus total negative PC 3.x
tal Negative Only Offset: 0 kWh accumulation
kWh Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:

40188 Genset Bus To- Read Multiplier: 1 Generator set bus total positive PC 3.x
tal Positive kWh Only Offset: 0 kWh accumulation
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:

40189 Genset Bus To- Read Multiplier: 1 Generator set bus total positive PC 3.x
tal Positive kWh Only Offset: 0 kWh accumulation
Size (bits): 32
Sign: U
Unit: kWh
Lower Limit:
Upper Limit:

40190 Genset Bus To- Read Multiplier: 1 Generator set bus total net kWh PC 3.x
tal Net kWh Only Offset: 0 accumulation
Size (bits): 32
Sign: S
Unit: kWh
Lower Limit:
Upper Limit:

40191 Genset Bus To- Read Multiplier: 1 Generator set bus total net kWh PC 3.x
tal Net kWh Only Offset: 0 accumulation
Size (bits): 32
Sign: S
Unit: kWh
Lower Limit:
Upper Limit:

40192 Genset Bus To- Read Multiplier: 1 Generator set bus total negative PC 3.x
tal Negative Only Offset: 0 kVARh accumulation
kVARh Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:

64
Addr. Parameter Access Specifications Description Control
40193 Genset Bus To- Read Multiplier: 1 Generator set bus total negative PC 3.x
tal Negative Only Offset: 0 kVARh accumulation
kVARh Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:

40194 Genset Bus To- Read Multiplier: 1 Generator set bus total positive PC 3.x
tal Positive Only Offset: 0 kVARh accumulation
kVARh Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:

40195 Genset Bus To- Read Multiplier: 1 Generator set bus total positive PC 3.x
tal Positive Only Offset: 0 kVARh accumulation
kVARh Size (bits): 32
Sign: U
Unit: kVARh
Lower Limit:
Upper Limit:

40196 Genset Bus To- Read Multiplier: 1 Generator set Bus total net PC 3.x
tal Net kVARh Only Offset: 0 kVARh accumulation
Size (bits): 32
Sign: S
Unit: kVARh
Lower Limit:
Upper Limit:

40197 Genset Bus To- Read Multiplier: 1 Generator set Bus total net PC 3.x
tal Net kVARh Only Offset: 0 kVARh accumulation
Size (bits): 32
Sign: S
Unit: kVARh
Lower Limit:
Upper Limit:

40198 Ground Current Read Multiplier: 0.1 Ground current PC 3.x


Only Offset: 0
Size (bits): 16
Sign: U
Unit: amp
Lower Limit:
Upper Limit:

40199 Genset Nega- Read Multiplier: 0.01 Generator set Negative Se- PC 3.x
tive Sequence Only Offset: 0 quence Current as Percent of
Current % Size (bits): 16 Standby Current Rating
Sign: U
Unit: %
Lower Limit:
Upper Limit:

65
Addr. Parameter Access Specifications Description Control
40201 Coolant Tem- Read 0: PGBU Either PGBU(Onan) or PC 2.x,
perature Sen- Only 1: EBU EBU(Cummins) sensor. PC 3.x
sor Type

40207 Battery Charger Read Multiplier: 0.001 The Battery Charger Alternator PC 2.x,
Alternator Flash Only Offset: 0 Flash Voltage after all scaling and PC 3.x
Voltage Size (bits): 16 validity checks.
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 35

40208 Battery 1 Volt- Read Multiplier : 0.01 Battery 1 Voltage measured PC3.X
age (Aux101) Only Offset: 0 through AUX101. Applicable
Size (bits): 16 when multiple batteries are used.
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 3850
Default: NA

40209 Battery 2 Volt- Read Multiplier : 0.01 Battery 2 Voltage measured PC3.X
age (Aux101) Only Offset: 0 through AUX101. Applicable
Size (bits): 16 when multiple batteries are used.
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 3850
Default: NA

40210 External Speed Read Multiplier: 0.01 Monitor point for the external PC 2.x,
Bias Input Only Offset: 0 speed bias input. PC 3.x
Size (bits): 16
Sign: S
Unit: %
Lower Limit: −100
Upper Limit: 100

40211 External Volt- Read Multiplier: 0.01 Monitor point for the external volt- PC 2.x,
age Bias Input Only Offset: 0 age bias input. PC 3.x
Size (bits): 16
Sign: S
Unit: %
Lower Limit: −100
Upper Limit: 100

40212 Battery 3 Volt- Read Multiplier : 0.01 Battery 3 Voltage measured PC3.X
age (Aux101) Only Offset: 0 through AUX101. Applicable
Size (bits): 16 when multiple batteries are used.
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 3850
Default: NA

66
Addr. Parameter Access Specifications Description Control
40213 Battery 4 Volt- Read Multiplier : 0.01 Battery 4 Voltage measured PC3.X
age (Aux101) Only Offset: 0 through AUX101. Applicable
Size (bits): 16 when multiple batteries are used.
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 3850
Default: NA

40214 kVAR Load Set- Read Multiplier : 0.01 EU scaled value for the kVAR PC3.X
point Only Offset: 0 load setpoint
Size (bits): 16
Sign: S
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA

40217 kVAR Load Read Multiplier : 0.01 EU Scaled value for the kVAR PC3.X
Share Level Only Offset: 0 load share level analog input
Size (bits): 16
Sign: S
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA

40219 kW load set- Read Multiplier : 0.01 EU scaled value for the kW load PC3.X
point Only Offset: 0 setpoint
Size (bits): 16
Sign: S
Unit: %
Lower Limit:
Upper Limit: 125.01
Default: NA

40222 kW Load Share Read Multiplier : 0.01 EU Scaled value for the kW load PC3.X
Level Only Offset: 0 share level analog input
Size (bits): 16
Sign: S
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA

40224 KVAR Load Read Multiplier : 0.1 uA signal being injected into a PC3.X
Share Output Only Offset: 0 10K ohm resistor network
Predictor Size (bits): 16
Sign: S
Unit: uA
Lower Limit: NA
Upper Limit: NA
Default: NA

67
Addr. Parameter Access Specifications Description Control
40225 KW Load Share Read Multiplier : 0.1 uA signal being injected into a PC3.X
Output Predic- Only Offset: 0 10K ohm resistor network
tor Size (bits): 16
Sign: S
Unit: uA
Lower Limit: NA
Upper Limit: NA
Default: NA

40226 Speed Bias Read Multiplier: 0.01 Configurable analog output volt- PC 3.x
Output / Confi- Only Offset: 0 age output value (predicted)
gurable Analog Size (bits): 16
output #1 Out- Sign: S
put Predictor Unit: Vdc
Lower Limit: NA
Upper Limit: NA

40227 Voltage Bias Read Multiplier: 0.01 Configurable analog output volt- PC 3.x
Output / Confi- Only Offset: 0 age output value (predicted)
gurable Analog Size (bits): 16
output #2 Out- Sign: S
put Predictor Unit: Vdc
Lower Limit:
Upper Limit:

40228 Amber Warning Read 0: Inactive Engine Control System indicates PC 2.x,
Lamp Status Only 1: Active a warning condition. PC 3.x

40229 Barometric Ab- Read Multiplier: 0.1 Monitor point for the Barometric PC 2.x,
solutee Pres- Only Offset: 0 Absolutee Pressure. Displayed as PC 3.x
sure Size (bits): 16 ”Ambient Pressure” in the HMI.
Sign: U
Unit: psi
Lower Limit:
Upper Limit:

40230 Boost Pressure Read Multiplier: 0.1 Monitor point for the Boost Abso- PC 2.x,
Only Offset: 0 lutee Pressure PC 3.x
Size (bits): 16
Sign: U
Unit: psi
Lower Limit:
Upper Limit:

40231 CAN Datalink Read 0: Inactive Indicates the status of the CAN PC 2.x,
Status Only 1: Active datalink PC 3.x
2: Failed

40232 Crankcase Read Multiplier: 0.1 Monitor point for the Crankcase PC 2.x,
Pressure Only Offset: 0 Pressure. PC 3.x
Size (bits): 16
Sign: S
Unit: psi
Lower Limit: −35.67
Upper Limit: 38

68
Addr. Parameter Access Specifications Description Control
40235 ECM Derate Read 0: No Derate Request Request made by the ECS for a PC 2.x,
Request Only 1: Derate Request reduction in load PC 3.x
2: Error
3: Don’t Care

40236 Engine Applica- Read 0: ECM Monitor point for the output of the PC 2.x,
tion Type Only 1: Hydro−Mechanical Engine application type. Either PC 3.x
ECM (CAN) or Hydro−Mechani-
cal.

40237 Engine State Read 0: Stop ECS engine state indication PC 2.x,
Only 1: Ventilationl PC 3.x
2: Start
3: Run
4: Normal Shutdown
5: Emergency Shutdown
6: Error
7: Don’t Care
8: Rapid Start
9: Reserved
10: Reserved
11: Reserved
12: Reserved
13: Reserved
14: Reserved
15: Don’t Care / Take No Action

40238 PGI Major Ver- Read Multiplier :1 Displays Power Generation Inter- PC3.X
sion Only Offset: 0 face Major Version to which En-
Size (bits): 8 gine Software is complying
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 225
Default: NA

40239 PGI Minor Ver- Read Multiplier :1 Displays Power Generation Inter- PC3.X
sion Only Offset: 0 face Minor Version to which En-
Size (bits): 8 gine Software is complying
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 225
Default: NA

40240 PGI Informa- Read Multiplier :1 Displays Power Generation Inter- PC3.X
tional Version Only Offset: 0 face Informational Version to
Size (bits): 8 which Engine Software is comply-
Sign: U ing
Unit: NA
Lower Limit: 0
Upper Limit: 225
Default: NA

69
Addr. Parameter Access Specifications Description Control
40242 Aftercooler Read Multiplier: 0.1 Monitor point for the Aftercooler PC 2.x,
Temperature Only Offset: 0 Temperature. PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −40
Upper Limit: 410
Default: NA

40243 Internal ECM Read Multiplier : 0.1 Internal temperature of the engine PC3.X
Module 1 Tem- Only Offset: 0 electronic control module 1
perature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: NA
Upper Limit: NA
Default: NA

40244 Internal ECM Read Multiplier : 0.1 Internal temperature of the engine PC3.X
Module 2 Tem- Only Offset: 0 electronic control module 2
perature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: NA
Upper Limit: NA
Default: NA

40245 Internal ECM Read Multiplier : 0.1 Internal temperature of the engine PC3.X
Module 3 Tem- Only Offset: 0 electronic control module 3
perature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: NA
Upper Limit: NA
Default: NA

40246 Internal ECM Read Multiplier : 0.1 Internal temperature of the engine PC3.X
Module 4 Tem- Only Offset: 0 electronic control module 4
perature Size (bits): 16
Sign: S
Unit: degF
Lower Limit: NA
Upper Limit: NA
Default: NA

40247 ECM Module 1 Read Multiplier : 0.1 Engine Control Module 1 Battery PC3.X
Battery Voltage Only Offset: 0 Voltage.
Size (bits): 16
Sign: U
Units: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA

70
Addr. Parameter Access Specifications Description Control
40248 ECM Module 2 Read Multiplier : 0.1 Engine Control Module 2 Battery PC3.X
Battery Voltage Only Offset: 0 Voltage.
Size (bits): 16
Sign: U
Units: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA
40249 ECM Module 3 Read Multiplier : 0.1 Engine Control Module 3 Battery PC3.X
Battery Voltage Only Offset: 0 Voltage.
Size (bits): 16
Sign: U
Units: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA
40250 ECM Module 4 Read Multiplier : 0.1 Engine Control Module 4 Battery PC3.X
Battery Voltage Only Offset: 0 Voltage.
Size (bits): 16
Sign: U
Units: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA
40254 Fuel Supply Read Multiplier: 0.1 Monitor point for the Fuel Supply PC 2.x,
Pressure Only Offset: 0 Pressure. Displayed as ”Fuel PC 3.x
Size (bits): 16 Supply Pressure” in the HMI.
Sign: U
Unit: psi
Lower Limit: 0
Upper Limit: 145
40257 Intake Manifold Read Multiplier : 0.1 Monitor point for the Intake Man- PC 2.X,
4 Temperature Only Offset: 0 ifold 4 Temperature PC3.X
Size (bits): 16
Sign: S
Units: degF
Lower Limit: −40
Upper Limit: 410
Default: NA
40258 Fuel Outlet Read Multiplier: 0.1 Monitor point for the Fuel Outlet PC 2.x,
Pressure Only Offset: 0 Pressure Pressure. Displayed as PC 3.x
Size (bits): 32 ”Fuel Rail Pressure” in the HMI.
Sign: U
Unit: psi
Lower Limit: 0
Upper Limit: 36404

71
Addr. Parameter Access Specifications Description Control
40259 Fuel Outlet Read Multiplier: 0.1 Monitor point for the Fuel Outlet PC 2.x,
Pressure Only Offset: 0 Pressure Pressure. Displayed as PC 3.x
Size (bits): 32 ”Fuel Rail Pressure” in the HMI.
Sign: U
Unit: psi
Lower Limit: 0
Upper Limit: 36404
40260 Intake Manifold Read Multiplier: 0.1 Monitor point for the Intake Man- PC 2.x,
2 Temperature Only Offset: 0 ifold 2 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −40
Upper Limit: 410
40261 Intake Manifold Read Multiplier: 0.1 Monitor point for the Intake Man- PC 2.x,
3 Temperature Only Offset: 0 ifold 3 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −40
Upper Limit: 410
40264 Percent Engine Read Multiplier: 1 Monitor point for the percent en- PC 2.x,
Torque/Duty Only Offset: 0 gine torque output and the gover- PC 3.x
Cycle Size (bits): 16 nor percent duty cycle output
Sign: S when used with the HM ECM
Unit: %
Lower Limit: −40
Upper Limit: 410
40276 Post−Filter Oil Read Multiplier: 0.1 Monitor point for the Post−Filter PC 2.x,
Pressure Only Offset: 0 Oil Pressure PC 3.x
Size (bits): 16
Sign: U
Unit: psi
Lower Limit: 0
Upper Limit: 145
40277 Pre−Filter Oil Read Multiplier: 0.1 Monitor point for the Pre−Filter Oil PC 2.x,
Pressure Only Offset: 0 Pressure PC 3.x
Size (bits): 16
Sign: U
Unit: psi
Lower Limit: 0
Upper Limit: 145
40278 Configurable Read 0: Inactive Configurable Input #14 input soft- PC 2.x,
Input #14 Only 1: Active ware state status. Gives software PC 3.x
Switch Inactive/Active state

72
Addr. Parameter Access Specifications Description Control
40279 Turbocharger 1 Read Multiplier: 1 Monitor point for the Turbochar- PC 2.x,
Speed Only Offset: 0 ger 1 Speed PC 3.x
Size (bits): 32
Sign: U
Unit: RPM
Lower Limit: 0
Upper Limit: 257000

40280 Turbocharger 1 Read Multiplier: 1 Monitor point for the Turbochar- PC 2.x,
Speed Only Offset: 0 ger 1 Speed PC 3.x
Size (bits): 32
Sign: U
Unit: RPM
Lower Limit: 0
Upper Limit: 257000

40281 Turbocharger 2 Read Multiplier: 0.1 Monitor point for the Turbochar- PC 2.x,
Boost Pressure Only Offset: 0 ger 2 Boost Pressure PC 3.x
Size (bits): 32
Sign: U
Unit: psi
Lower Limit:
Upper Limit:

40282 Water in Fuel Read 0: No Water in Fuel Indication PC 2.x,


Indicator Only 1: Yes PC 3.x

40282 Water in Fuel Read 0: Off The controller mode PC 2.x,


Indicator Only 1: Ready PC 3.x
2: Setup
3: Starting
4: Idle
5: Rated
6: Stop Normal
7: Stop Emergency
8: Factory Test
9: Wait to Power Down

40285 Power Down Read Multiplier: 1 Timer to count down the time be- PC 2.x,
Mode Timer Only Offset: 0 fore the control goes to sleep PC 3.x
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 600

40286 Setup Mode Read Multiplier : 1 Time spent in Setup Mode. PC 2.X
Timer Only Offset: 0 PC3.X
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: NA
Upper Limit: NA
Default: NA

73
Addr. Parameter Access Specifications Description Control
40287 Tool Wake−up Read 0: Inactive 1: Active The control output to the common PC 2.X
Command only wake−up line to wake up other PC3.X
devices

40289 Active Sched


Sched- Read 0: None Indicates the currently active PC 2.X
ule only 1: Program 1 scheduler program or exception. PC3.X
2: Program
g 2
3: Program
g 3
g
4: Program 4
5: Program 5
6: Program
P 6
7 P
7: Program 7
8 P
8: Program 8
9: Program 9
10: Program 10
11: Program 11
12: Program 12
13: Exception 1
14: Exception 2

40290 Controller On Read Multiplier : 1 Controller ON time in seconds. PC 2.X


Time Only Offset: 0 Upper limit is 136 years. PC3.X
Size (bits): 32
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 4294967295
Default: NA

40291 Controller On Read Multiplier : 1 Controller ON time in seconds. PC 2.X


Time Only Offset: 0 Upper limit is 136 years. PC3.X
Size (bits): 32
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 4294967295
Default: NA

40298 Runs Since Re- Read Multiplier: 1 Number of runs since the last re- PC 2.x,
set Only Offset: 0 set. Upper limit is 2^32 −1. PC 3.x
Size (bits): 32
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967290

40299 Runs Since Re- Read Multiplier: 1 Number of runs since the last re- PC 2.x,
set Only Offset: 0 set. Upper limit is 2^32 −1. PC 3.x
Size (bits): 32
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967290

74
Addr. Parameter Access Specifications Description Control
40300 Remote Start Read/ 0: Inactive Modbus Remote Start PC 2.x,
Switch(Mod- Write 1: Active PC 3.x
bus)
40301 Fault Reset Read/ 0: Inactive Modbus fault reset. PC 2.x,
(Modbus) Write 1: Active PC 3.x
40320 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No1 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40321 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No1 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40322 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No1 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40323 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No1 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40324 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No1 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40325 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No1 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:

75
Addr. Parameter Access Specifications Description Control
40326 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No1 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:

40327 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No1 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:

40328 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No1 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:

40329 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No1 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:

40330 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No1 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:

40331 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No1 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:

40332 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No1 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:

76
Addr. Parameter Access Specifications Description Control
40333 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No1 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40334 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No1 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40335 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No1 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40336 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No1 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:

40337 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No1 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40338 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No1 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:
40339 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No1 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active
Sign: C
Unit:
Lower Limit:
Upper Limit:

77
Addr. Parameter Access Specifications Description Control
40340 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No2 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40341 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No2 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40342 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No2 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40343 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No2 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40344 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No2 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40345 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No2 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40346 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No2 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

78
Addr. Parameter Access Specifications Description Control
40347 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No2 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40348 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No2 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40349 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No2 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40350 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No2 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40351 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No2 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40352 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No2 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40353 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No2 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

79
Addr. Parameter Access Specifications Description Control
40354 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No2 Fault Text Write Offset: 0 string for use by the operator pan-
Size (bits): 168 el when this fault becomes active.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40355 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No2 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40356 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No2 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40357 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No2 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40358 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No2 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40359 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No2 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40360 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No3 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

80
Addr. Parameter Access Specifications Description Control
40361 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No3 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40362 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No3 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40363 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No3 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40364 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No3 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40365 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No3 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40366 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No3 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40367 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No3 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

81
Addr. Parameter Access Specifications Description Control
40368 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No3 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40369 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No3 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40370 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No3 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40371 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No3 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40372 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No3 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40373 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No3 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40374 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No3 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

82
Addr. Parameter Access Specifications Description Control
40375 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No3 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:
40376 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No3 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:
40377 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No3 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:
40378 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No3 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:
40379 Start Inhibit Read/ Multiplier: 1 Trim to define the 20 character PC 3.x
No3 Fault Text Write Offset: 0 string for use by the Operator
Size (bits): 168 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:
40422 Fault Status Bit- Read Multiplier : 1 16 bit fault bitmap for modbus in- PC 2.x
map 23 Only Offset: 0 terface. PC3.x
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA
40423 Fault Status Bit- Read Multiplier : 1 16 bit fault bitmap for modbus in- PC 2.x
map 24 Only Offset: 0 terface. PC3.x
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA

83
Addr. Parameter Access Specifications Description Control
40424 Fault Status Bit- Read Multiplier : 1 16 bit fault bitmap for modbus in- PC 2.x
map 25 Only Offset: 0 terface. PC3.x
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA

40425 Event Status Read Multiplier : 1 16 bit fault bitmap for modbus in- PC 2.x
Bitmap 2 Only Offset: 0 terface. PC3.x
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40426 Event Status Read Multiplier : 1 16 bit fault bitmap for modbus in- PC 2.x
Bitmap 3 Only Offset: 0 terface. PC3.x
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40427 Fault Status Bit- Read Multiplier : 1 16 bit fault bitmap for modbus in- PC 2.x
map 26 Only Offset: 0 terface. PC3.x
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40428 Fault Status Bit- Read Multiplier : 1 16 bit event bitmap for modbus PC3.x
map 32 Only Offset: 0 interface and Tier4F 16 bit Diesel
Size (bits): 16 Fault Bitmap for modbus interface
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40430 Event Status Read Multiplier : 1 16 bit fault bitmap for modbus in- PC 2.x
Bitmap 1 Only Offset: 0 terface. PC3.x
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

84
Addr. Parameter Access Specifications Description Control
40431 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 1 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40432 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 2 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40433 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 3 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40434 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 4 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40435 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 5 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40436 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 6 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

85
Addr. Parameter Access Specifications Description Control
40437 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 7 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40438 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.X
Gas Bitmap 8 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40439 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 9 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40440 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 10 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40441 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 11 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40442 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 12 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

86
Addr. Parameter Access Specifications Description Control
40443 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 13 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40444 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 14 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40445 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 15 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40446 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 16 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40447 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 17 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40448 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 18 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

87
Addr. Parameter Access Specifications Description Control
40449 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 19 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40450 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 20 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40451 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 21 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40452 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 22 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40453 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 23 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40454 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 24 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

88
Addr. Parameter Access Specifications Description Control
40455 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 25 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40456 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 26 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40457 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 27 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40458 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 28 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40459 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 29 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40460 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 30 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

89
Addr. Parameter Access Specifications Description Control
40461 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 31 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40462 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 32 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40463 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 33 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40464 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 34 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40465 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 35 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40466 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 36 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

90
Addr. Parameter Access Specifications Description Control
40467 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 37 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40468 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 38 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40469 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 39 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA

40470 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 40 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40471 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 41 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40472 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 42 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

91
Addr. Parameter Access Specifications Description Control
40473 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 43 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40474 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 44 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40475 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 45 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40476 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 46 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40477 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 47 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40478 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 48 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

92
Addr. Parameter Access Specifications Description Control
40479 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 49 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40480 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 50 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40481 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 51 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40482 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 52 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40483 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 53 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40484 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 54 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

93
Addr. Parameter Access Specifications Description Control
40485 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 55 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40486 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 56 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40487 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 57 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40488 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 58 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40489 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 59 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40490 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 60 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

94
Addr. Parameter Access Specifications Description Control
40491 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 61 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40492 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 62 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40493 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 63 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40494 Fault Status Read Multiplier : 1 16 bit Gas fault bitmap for mod- PC3.x
Gas Bitmap 64 Only Offset: 0 bus interface.
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40495 AT Fault Status Read Multiplier : 1 16 bit AT Fault Bitmap for mod- PC3.x
Bitmap 1 Only Offset: 0 bus interface
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: NA

40496 Fault Status Bit- Read Multiplier : 1 16 bit fault bitmap for modbus in- PC3.x
map 27 Only Offset: 0 terface
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA

95
Addr. Parameter Access Specifications Description Control
40497 Fault Status Bit- Read Multiplier : 1 16 bit fault bitmap for modbus in- PC3.x
map 28 Only Offset: 0 terface
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA
40498 Fault Status Bit- Read Multiplier : 1 16 bit fault bitmap for modbus in- PC3.x
map 29 Only Offset: 0 terface
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA
40499 Fault Status Bit- Read Multiplier : 1 16 bit fault bitmap for modbus in- PC3.x
map 30 Only Offset: 0 terface
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA
40500 Low Fuel Read 0: Inactive Low Fuel input software state sta- PC 2.x,
Switch Only 1: Active tus. Gives software Inactive/Ac- PC 3.x
tive state
40501 Low Fuel/Confi- Read 0: Inactive This is the status of the Configur- PC 2.x,
gurable Input Only 1: Active able Input #6. PC 3.x
#6 Switch
40503 Differential Read 0: Inactive Differential fault trip monitor point PC3.X
Fault Trip Only 1: Active
2: Reserved
3: Not Available
40504 Master First Read 0: Inactive This is the status of the Master PC3.X
Start Input A Only 1: Active First Start A input
40505 Fire Trip Read 0: Inactive Fire trip monitor point. PC3.X
Only 1: Active
40506 Master First Read 0: Inactive Master First Start Input B input PC3.X
Start Input B Only 1: Active software state status. Gives soft-
Switch ware Inactive/Active state.
40507 Masterless Read 0: Inactive Masterless Load Demand Enable PC3.X
Load Demand Only 1: Active Switch function output status.
Enable Switch Gives software Inactive/Active
state
40508 Predictive Load Read 0: Inactive Predictive Load Enable Switch PC3.X
Enable Switch Only 1: Active function output status. Gives
software Inactive/Active state

96
Addr. Parameter Access Specifications Description Control
40509 PTC Mode Read 0: Inactive PTC Mode Switch function output PC 3.x
Switch Only 1: Active status. Gives software Inactive/
Active state
40510 Extended Par- Read 0: Inactive This is the status of the Configur- PC 3.x
allel/Configur- Only 1: Active able Input #32.
able Input #32
Switch
40511 Ramp Load/Un- Read 0: Load Ramp Load/Unload input soft- PC3.X
load Switch Only 1: Unload ware state status
40512 Remote E−stop Read 0: Inactive Remote E-stop input software PC 2.x,
Switch Only 1: Active state status. Gives software Inac- PC 3.x
tive/Active state
40513 Remote Start Read 0: Inactive Remote Start input software state PC 2.x,
Switch Only 1: Active status. Gives software Inactive/ PC 3.x
Active state
40514 Retransfer In- Read 0: Inactive Retransfer Inhibit input software PC3.X
hibit Switch Only 1: Active state status. Gives software Inac-
tive/Active state
40515 Retransfer In- Read 0: Inactive This is the status of the Configur- PC 3.x
hibit/Configur- Only 1: Active able Input #21.
able Input #21
Switch
40516 Rupture Basin Read 0: Inactive Rupture Basin input software PC 2.x,
Switch Only 1: Active state status. Gives software Inac- PC 3.x
tive/Active state
40517 Rupture Basin/ Read 0: Inactive This is the status of the Configur- PC 2.x,
Configurable Only 1: Active able Input #12. PC 3.x
Input #12
Switch
40518 Speed Droop Read 0: Inactive Monitors the Speed Droop Enable PC 2.X
Enable Switch Only 1: Active Switch function; Inactive or Ac- PC3.X
tive state
40519 Start Type Read 0: Inactive Start Type input software state PC 2.x,
Switch Only 1: Active status. Gives software Inactive/ PC 3.x
Active state
40520 Sync Enable Read 0: Inactive Sync Enable input software state PC3.X
Switch Only 1: Active status. Gives software Inactive/
Active state
40521 Sync Enable/ Read 0: Inactive This is the status of the Configur- PC 3.x
Configurable Only 1: Active able Input #30.
Input #30
Switch
40522 Tool Wakeup Read 0: Inactive Tool Wake−up input software PC 2.X
Switch Only 1: Active state status. Gives software Inac- PC3.X
tive/Active state
40523 Transfer Inhibit Read 0: Inactive Transfer Inhibit input software PC3.X
Switch Only 1: Active state status. Gives software Inac-
tive/Active state

97
Addr. Parameter Access Specifications Description Control
40524 Transfer Inhibit/ Read 0: Inactive This is the status of the Configur- PC 3.x
Configurable Only 1: Active able Input #20.
Input #20
Switch
40525 Utility CB Inhib- Read 0: Inactive This is the status of the Configur- PC 3.x
it/Configurable Only 1: Active able Input #25.
Input #25
Switch
40526 Utility CB Pos Read 0: Inactive This is the status of the Configur- PC 3.x
B/Configurable Only 1: Active able Input #23.
Input #23
Switch
40527 Utility CB Read 0: Inactive This is the status of the Configur- PC 3.x
Tripped/Confi- Only 1: Active able Input #24.
gurable Input
#24 Switch
40528 Utility Single Read 0: Inactive This is the status of the Configur- PC 3.x
Mode Verify/ Only 1: Active able Input #29.
Configurable
Input #29
Switch
40529 Utility CB Inhibit Read 0: Inactive Utility CB Inhibit input software PC3.X
Switch Only 1: Active state status. Gives software Inac-
tive/Active state
40530 Utility CB Pos A Read 0: Inactive Utility CB Pos A input software PC3.X
Switch Only 1: Active state status. Gives software Inac-
tive/Active state
40531 Utility CB Pos B Read 0: Inactive Utility CB Pos B input software PC3.X
Switch Only 1: Active state status. Gives software Inac-
tive/Active state
40532 Utility CB Read 0: Inactive Utility CB Tripped input software PC3.X
Tripped Switch Only 1: Active state status. Gives software Inac-
tive/Active state
40533 Utility Single Read 0: Inactive Utility Single Mode Verify input PC3.X
Mode Verify Only 1: Active software state status. Gives soft-
Switch ware Inactive/Active state
40534 Voltage Droop Read 0: Inactive Voltage Droop Enable Switch PC 2.X
Enable Switch Only 1: Active function output status. Gives PC3.X
software Inactive/Active state.
40535 Configurable Read 0: Inactive Indicates if the output’s status is PC 2.x,
Output #1 Sta- Only 1: Active Inactive or Active PC 3.x
tus
40536 Configurable Read 0: Inactive Indicates if the output’s status is PC 2.x,
Output #2 Sta- Only 1: Active Inactive or Active PC 3.x
tus
40537 Configurable Read 0: Inactive Indicates if the output’s status is PC 3.x
Output #20 Sta- Only 1: Active Inactive or Active
tus

98
Addr. Parameter Access Specifications Description Control
40538 Configurable Read 0: Inactive Indicates if the output’s status is PC 3.x
Output #21 Sta- Only 1: Active Inactive or Active
tus
40539 Configurable Read 0: Inactive Indicates if the output’s status is PC 3.x
Output #22 Sta- Only 1: Active Inactive or Active
tus
40540 Configurable Read 0: Inactive Indicates if the output’s status is PC 2.x,
Output #3 Sta- Only 1: Active Inactive or Active PC 3.x
tus
40541 Configurable Read 0: Inactive Indicates if the output’s status is PC 2.x,
Output #4 Sta- Only 1: Active Inactive or Active PC 3.x
tus
40542 Delayed Off / Read 0: Inactive Indicates if the output’s status is PC 2.x,
Configurable Only 1: Active Inactive or Active PC 3.x
Output #10 Sta-
tus
40543 Fuel Shutoff Read 0: Inactive Indicates if the output’s status is PC 2.x,
Status Only 1: Active Inactive or Active PC 3.x
40545 Genset CB Read 0: Inactive Indictes if the output’s status is In- PC3.X
Open Status Only 1: Active active or Active
40546 Hold Power On Read 0: Inactive Indicates if the output’s status is PC 2.X
Driver Status Only 1: Active Inactive or Active PC3.X
40547 Keyswitch Sta- Read 0: Inactive Indicates if the output’s status is PC 2.x,
tus Only 1: Active Inactive or Active PC 3.x
40548 KW/KVAR Load Read 0: Inactive Indictes if the output’s status is In- PC3.X
Share Relay Only 1: Active active or Active
Status
40549 Load Dump / Read 0: Inactive Indicates if the output’s status is PC 2.x,
Configurable Only 1: Active Inactive or Active PC 3.x
Output #11 Sta-
tus
40550 Local Status / Read 0: Inactive Indicates if the output’s status is PC 2.x,
Configurable Only 1: Active Inactive or Active PC 3.x
Output #7 Sta-
tus
40551 Master First Read 0: Inactive Indictes if the output’s status is In- PC3.X
Start Output Only 1: Active active or Active
Status
40552 Oil Priming Read 0: Inactive Indicates if the output’s status is PC 2.x,
Pump / Confi- Only 1: Active Inactive or Active PC 3.x
gurable Output
#6 Status
40553 Ready To Load Read 0: Inactive Indicates if the output’s status is PC 2.x,
/Configurable Only 1: Active Inactive or Active PC 3.x
Output #5 Sta-
tus
40554 Run Relay #1 Read 0: Inactive Indicates if the output’s status is PC 2.x,
Status Only 1: Active Inactive or Active PC 3.x

99
Addr. Parameter Access Specifications Description Control
40555 Run Relay #2 Read 0: Inactive Indicates if the output’s status is PC 2.x,
Status Only 1: Active Inactive or Active PC 3.x
40556 Speed/Voltage Read 0: Inactive Indicates if the output’s status is PC 3.x
Bias Relay Sta- Only 1: Active Inactive or Active
tus
40557 Starter Status Read 0: Inactive Indictes if the output’s status is In- PC 2.X
Only 1: Active active or Active PC3.X
40558 Tool Wake−up Read 0: Inactive Indicates if the output’s status is PC 2.X
Driver Status Only 1: Active Inactive or Active PC3.X
40559 Utility CB Close Read 0: Inactive Indictes if the output’s status is In- PC3.X
Status Only 1: Active active or Active
40560 Utility CB Open Read 0: Inactive Indictes if the output’s status is In- PC3.X
Status Only 1: Active active or Active
40561 Common Alarm Read 0: Inactive The status of the Common Alarm PC 2.x,
Fault Status Only 1: Active Fault PC 3.x
40562 Common Shut- Read 0: Inactive The status of the common shut- PC 2.x,
down Com- Only 1: Active down command PC 3.x
mand
40563 Common Shut- Read 0: Inactive The status of the Common Shut- PC 2.x,
down Event Only 1: Active down Event PC 3.x
Status
40564 Common Shut- Read 0: Inactive The status of the common shut- PC3.X
down w/Cool- Only 1: Active down w/Cooldown command
down Com-
mand
40565 Common Warn- Read 0: Inactive The status of the Common Warn- PC 2.x,
ing Event Sta- Only 1: Active ing Event PC 3.x
tus
40566 Delayed Shut- Read 0: Inactive Monitor point for the Delayed PC 2.X
down Flag Only 1: Active shutdown flag. PC3.X
40567 Delayed Shut- Read Multiplier : 0.1 Monitor point for the Delayed PC 2.X
down Timer Only Offset: 0 shutdown timer. PC3.X
Size (bits): 16
Sign: U
Units: Seconds
Lower Limit: 0
Upper Limit: 3
Default: NA
40568 Derate Request Read Multiplier : 1 The requested % derate from the PC 2.X
Only Offset: 0 derate request logic. PC3.X
Size (bits): 8
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 100
Default: NA
40569 Fault Detection Read 0: Inactive The status of the Fault Detection PC 2.X
Reset Only 1: Active Reset logic. PC3.X

100
Addr. Parameter Access Specifications Description Control
40570 Fault Reset Read 0: Inactive One shot due to fault reset switch PC 2.x,
Command Only 1: Active being active. PC 3.x
40571 Remote Shut- Read 0: Inactive Becomes active when a remote PC 2.X
down Fault Re- Only 1: Active fault reset signal has been initi- PC3.X
set Signal ated.
40572 Shutdown Fault Read 0: Inactive The status of the Shutdown Fault PC 2.X
Reset Only 1: Active reset logic. PC3.X
40573 Battle Short Read 0: Inactive Monitor point indicating the en- PC 2.X
Flag Only 1: Active abled/disabled status of the battle PC3.X
short function
40574 Auto Command Read 0: Not Auto The output of the Auto Command PC 2.X
Only 1: Auto OR logic PC3.X
40575 Auto Command Read Multiplier : 1 Bitmask to show the inputs to the PC 2.X
Inputs Only Offset: 0 Command output which are cur- PC3.X
Size (bits): 8 rently on
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
40576 AVR Regulation Read 0: Voltage The operational mode of the AVR PC 2.X
Mode Only 1: Current as a voltage or a current regulator PC3.X
40577 Base Frequen- Read Multiplier: 0.001 Provides a point to monitor the PC 2.x,
cy Only Offset: 0 base frequency PC 3.x
Size (bits): 32
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
40578 Base Frequen- Read Multiplier: 0.001 Provides a point to monitor the PC 2.x,
cy Only Offset: 0 base frequency PC 3.x
Size (bits): 32
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
40579 Battery Charg- Read Multiplier : 0.1 Time spent while the charger is PC 2.X
ing Fault Inte- Only Offset: 0 sensed as failed PC3.X
grator Size (bits): 16
Sign: U
Unit: Hz
Lower Limit: 0
Upper Limit: 300
Default: NA

101
Addr. Parameter Access Specifications Description Control
40580 Control Switch Read 0: Off Current position of the generator PC 2.x,
Position Only 1: Manual set switch panel Off−Run−Auto PC 3.x
2: Auto switch as seen by the generator
set control. SEE ALSO AD-
DRESS 40010.
NOTE: Both address 40580 and
40010 show the same information
however the specification for
each is different.

40581 Controlled Read / 0: Inactive Indicates status of the controlled PC3.X


Shutdown Sta- Write 1: Pending shutdown logic
tus 2: Shutdown

40582 Crank Allowed Read 0: False Monitor Point indicates if Crank- PC 2.X
Only 1: True ing is Allowed by the Prelube PC3.X
State Machin

40583 Dead Battery Read Multiplier : 1 Tracks the number of crank at- PC 2.X
Prevention Only Offset: 0 tempts in order to limit the at- PC3.X
Counter Size (bits): 8 tempts when the battery is so low
Sign: U that the control resets
Units: NA
Lower Limit: 0
Upper Limit: 250
Default: NA

40584 Delayed Off Read 0: Inactive The status of the delayed run PC 2.X
Command Only 1: Active command off logic. PC3.X
2: Reserved
3: Not Available

40586 Excitation State Read 0: Disabled Shows the enable status of the PC 2.x,
Only 1: Enabled excitation enabled = regulator on. PC 3.x

40587 Exercise Com- Read 0: Inactive The output of the Exercise Com- PC 2.x,
mand Only 1: Active mand OR logic PC 3.x
2: Reserved
3: Not Available

40588 Exercise Com- Read Multiplier : 1 Bitmask to show the inputs to the PC 2.X
mand Inputs Only Offset: 0 Command output which are cur- PC3.X
Size (bits): 8 rently on
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 250
Default: NA

40589 Exercise Time Read Multiplier: 0.1 Time remaining until exercise PC 2.x,
Remaining Only Offset: 0 stop sequence begins PC 3.x
Size (bits): 16
Sign: U
Unit: hours
Lower Limit: 0
Upper Limit: 25

102
Addr. Parameter Access Specifications Description Control
40590 Extended Par- Read 0: Stop The output of the Extended Paral- PC 2.X
allel Switch Only 1: Start lel Switch Command OR logic PC3.X
Command
40591 Extended Par- Read Multiplier : 1 Bitmask to show the inputs to the PC3.X
allel Switch Only Offset: 0 Command output which are cur-
Command In- Size (bits): 8 rently on
puts Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
40592 Battle Short Read 0: Inactive Indicates status of battle short in- PC 2.x,
Command Only 1: Active puts PC 3.x
40593 Shutdown Fault Read 0: Inactive Indicates whether or not the gen- PC 2.X
Override Only 1: Active set will ignore non−critical shut- PC3.X
down faults
40595 Final Frequen- Read Multiplier: 0.001 The frequency scaled version of PC 2.x,
cy Reference Only Offset: 0 the final speed reference PC 3.x
Size (bits): 32
Sign: U
Unit: Hz
Lower Limit: 0
Upper Limit: 100
40596 Final Frequen- Read Multiplier: 0.001 The frequency scaled version of PC 2.x,
cy Reference Only Offset: 0 the final speed reference PC 3.x
Size (bits): 32
Sign: U
Unit: Hz
Lower Limit: 0
Upper Limit: 100
40598 Fuel Shutoff Read 0: Inactive The result of the FSO driver out- PC 2.X
Command Only 1: Active put command logic PC3.X
2: Reserved
3: Not Available
40599 Genset Run Read 0: Emergency Stop Genset run / stop states PC 2.X
Command Only 1: Stop PC3.X
2: Load Demand Stop
3: Run
40600 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,
Input #1 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

103
Addr. Parameter Access Specifications Description Control
40601 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,
Input #1 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:
40602 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,
Input #1 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:
40603 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,
Input #1 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:
40604 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,
Input #1 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40605 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #1 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:
40606 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,
Input #1 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:
40607 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,
Input #1 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

104
Addr. Parameter Access Specifications Description Control
40608 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,
Input #1 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40609 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #1 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40610 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #1 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40611 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #1 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40612 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #1 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40613 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #1 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40614 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #1 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

105
Addr. Parameter Access Specifications Description Control
40615 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,
Input #1 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40620 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #2 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40621 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #2 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40622 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #2 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40623 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #2 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40624 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #2 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40625 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #2 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

106
Addr. Parameter Access Specifications Description Control
40626 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,
Input #2 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40627 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #2 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40628 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #2 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40629 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #2 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40630 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #2 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40631 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #2 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40632 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #2 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

107
Addr. Parameter Access Specifications Description Control
40633 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,
Input #2 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40634 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #2 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40635 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #2 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40640 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #13 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40641 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #13 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40642 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #13 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40643 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #13 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

108
Addr. Parameter Access Specifications Description Control
40644 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,
Input #13 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40645 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #13 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40646 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #13 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40647 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #13 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40648 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #13 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40649 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #13 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40650 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #13 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

109
Addr. Parameter Access Specifications Description Control
40651 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,
Input #13 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40652 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #13 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40653 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #13 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40654 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #13 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40655 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #13 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40660 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #14 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40661 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #14 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

110
Addr. Parameter Access Specifications Description Control
40662 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,
Input #14 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40663 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #14 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40664 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #14 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40665 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #14 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40666 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #14 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40667 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #14 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40668 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #14 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

111
Addr. Parameter Access Specifications Description Control
40669 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,
Input #14 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40670 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #14 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40671 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #14 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40672 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #14 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40673 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #14 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40674 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #14 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

40675 Configurable Read/ Multiplier: 1 Trim to define the 16 character PC 2.x,


Input #14 Fault Write Offset: 0 string for use by the Operator PC 3.x
Text Size (bits): 136 panel when this fault becomes
Sign: C active.
Unit:
Lower Limit:
Upper Limit:

112
Addr. Parameter Access Specifications Description Control
40709 Device Type Read Multiplier: 1 This Modbus register is created PC 3.x
(Modlon) Only Offset: 0 for Modlon register mapping. This
Size (bits): 8 parameter is not associated with
Sign: U any logical.
Unit:
Lower Limit:
Upper Limit:
40710 Control Switch Read 0: Off This Modbus register is created PC 3.x
Position (Mod- Only 1: Manual for Modlon register mapping.
lon) 2: Auto
40711 Genset Run Read 0: Stop This Modbus register is created PC 3.x
Sequence State Only 1: Time Delay to Start for Modlon register mapping.
(Modlon) 2: Warmup at Idle
3: Rated Freq and Voltage
4: Cooldown / Stop Delay
5: Cooldown at Idle
6: Rated to Idle Transition Delay
40712 Most Recent Read Multiplier: 1 This Modbus register is created PC 3.x
Fault or Warn- Only Offset: 0 for Modlon register mapping. This
ing (Modlon) Size (bits): 16 Modbus register is not associated
Sign: U with any logical Address
Unit: Fault Code
Lower Limit:
Upper Limit:
40713 Fault Type Read 0: None This Modbus register is created PC 3.x
(Modlon) Only 1: Warning for modlon register mapping. This
2: Derate Modbus register is not associated
3: Shutdown with cooldown with any logical address.
4: Shutdown
40714 Genset % Read Multiplier: 0.5 This Modbus register is created PC 3.x
Standby Total Only Offset: 0 for modlon register mapping.
kW (Modlon) Size (bits): 16 Monitors the total generator set
Sign: U standby KW percentage output.
Unit: % Modbus has different multiplier
Lower Limit: than PCCnet. For Modlon use
Upper Limit: only, use multiplier 0.5 %
40715 Genset Total Read Multiplier: 1 This Modbus register is created PC 3.x
kW (Modlon Only Offset: 0 for modlon register mapping.
GenStatus) Size (bits): 16 Generator set total kW.
Sign: U
Unit: kW
Lower Limit:
Upper Limit:
40716 NFPA 110 Log- Read Multiplier: 1 This Modbus register is created PC 3.x
ical Status Only Offset: 0 for modlon register mapping.
(Modlon) Size (bits): 32 32-bit number to represent the
Sign: U status of the NFPA 110 logical.
Unit: See NFPA110 bitmap. (See Sec-
Lower Limit: tion 4 Table 1-1 page 30).
Upper Limit:

113
Addr. Parameter Access Specifications Description Control
40717 NFPA 110 Log- Read Multiplier: 1 This Modbus register is created PC 3.x
ical Status Only Offset: 0 for modlon register mapping.
(Modlon) Size (bits): 32 32−bit number to represent the
Sign: U status of the NFPA 110 logical.
Unit: (See Section 4 Table 1-1 page
Lower Limit: 30).
Upper Limit:

40718 Genset Fre- Read Multiplier: 0.1 This Modbus register is created PC 3.x
quency OP Only Offset: 0 for modlon register mapping.
(Modlon) Size (bits): 16 Generator set Frequency OP.
Sign: U Modbus has different multiplier
Unit: Hz than PCCnet. For Modlon use
Lower Limit: only, Multiplier/Units = 0.1 Hz
Upper Limit:

40719 Genset Total Read Multiplier: 0.00005 This Modbus register is created PC 3.x
Power Factor Only Offset: 0 for modlon register mapping.
(Modlon) Size (bits): 16 Generator set total power factor
Sign: S (L1+L2+L3). Modbus and PCCnet
Unit: PF has different multiplier value. For
Lower Limit: Modlon, use 0.00005 PF.
Upper Limit:

40720 Genset Total Read Multiplier: 1 This Modbus register is created PC 3.x
kVA (Modlon) Only Offset: 0 for modlon register mapping.Gen-
Size (bits): 16 erator set total kVA
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:

40721 Genset Total Read Multiplier: 1 This Modbus register is created PC 3.x
kW (Modlon Only Offset: 0 for modlon register mapping.
GenACData) Size (bits): 16 Generator set total kW in Gen AC
Sign: S Data.
Unit: kW
Lower Limit:
Upper Limit:

40722 Genset Total Read Multiplier: 1 This Modbus register is created PC 3.x
kVAR (Modlon) Only Offset: 0 for modlon register mapping.
Size (bits): 16 Generator set total kVAR
Sign: S
Unit: kVAR
Lower Limit:
Upper Limit:

40723 Genset L1L2 Read Multiplier: 1 This Modbus register is created PC 3.x
Voltage (Mod- Only Offset: 0 for modlon register mapping.
lon) Size (bits): 16 Generator set L1L2 voltage
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

114
Addr. Parameter Access Specifications Description Control
40724 Genset L2L3 Read Multiplier: 1 This Modbus register is created PC 3.x
Voltage (Mod- Only Offset: 0 for modlon register mapping.
lon) Size (bits): 16 Generator set L2L3 voltage
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

40725 Genset L3L1 Read Multiplier: 1 This Modbus register is created PC 3.x
Voltage (Mod- Only Offset: 0 for modlon register mapping.
lon) Size (bits): 16 Generator set L3L1 voltage
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

40726 Genset L1N Read Multiplier: 1 This Modbus register is created PC 3.x
Voltage (Mod- Only Offset: 0 for modlon register mapping.
lon) Size (bits): 16 Generator set L1N voltage
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

40727 Genset L2N Read Multiplier: 1 This Modbus register is created PC 3.x
Voltage (Mod- Only Offset: 0 for modlon register mapping.
lon) Size (bits): 16 Generator set L2N voltage
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

40728 Genset L3N Read Multiplier: 1 This Modbus register is created PC 3.x
Voltage (Mod- Only Offset: 0 for modlon register mapping.
lon) Size (bits): 16 Generator set L3N voltage
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

40729 Genset L1 Cur- Read Multiplier: 1 Monitors the generator set L1 cur- PC 3.x
rent (Modlon) Only Offset: 0 rent value.
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:

40730 Genset L2 Cur- Read Multiplier: 1 Generator set L2 current PC 3.x


rent (Modlon) Only Offset: 0
Size (bits): 16
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:

115
Addr. Parameter Access Specifications Description Control
40731 Genset L3 Cur- Read Multiplier: 1 This Modbus register is created PC 3.x
rent (Modlon) Only Offset: 0 for modlon register mapping.
Size (bits): 16 Generator set L3 current
Sign: U
Unit: Amps
Lower Limit:
Upper Limit:

40732 Genset % Read Multiplier: 0.5 This Modbus register is created PC 3.x
Standby L1 Only Offset: 0 for modlon register mapping.
Current (Mod- Size (bits): 16 Monitors the generator set stand-
lon) Sign: U by L1 current percentage output.
Unit: % Modbus and PCCnet have differ-
Lower Limit: ent multiplier value. For modlon
Upper Limit: use 0.5 %

40733 Genset % Read Multiplier: 0.5 This Modbus register is created PC 3.x
Standby L2 Only Offset: 0 for modlon register mapping.
Current (Mod- Size (bits): 16 Monitors the generator set stand-
lon) Sign: U by L2 current percentage output.
Unit: % Modbus and PCCnet has different
Lower Limit: multiplier value. For Modlon, use
Upper Limit: 0.5 %

40734 Genset % Read Multiplier: 0.5 This Modbus register is created PC 3.x
Standby L3 Only Offset: 0 for modlon register mapping.
Current (Mod- Size (bits): 16 Monitors the generator set stand-
lon) Sign: U by L3 current percentage output.
Unit: % Modbus and PCCnet has different
Lower Limit: multiplier value. For Modlon use
Upper Limit: 0.5 %

40735 Battery Voltage Read Multiplier: 0.1 This Modbus register is created PC 3.x
(Modlon) Only Offset: 0 for modlon register mapping. Bat-
Size (bits): 16 tery voltage value. Modbus and
Sign: S PCCnet has different multiplier
Unit: Vdc value. For Modlon use 0.1volts
Lower Limit:
Upper Limit:

40736 Oil Pressure Read Multiplier: 0.1 This Modbus register is created PC 3.x
(Modlon) Only Offset: 0 for modlon register mapping.
Size (bits): 16 Monitor point for the Oil Pressure.
Sign: U Modbus and PCCnet have differ-
Unit: kPa ent multiplier value. For modlon,
Lower Limit: use 0.1 KPA
Upper Limit:

40737 Oil Tempera- Read Multiplier: 0.1 This Modbus register is created PC 3.x
ture (Modlon) Only Offset: 0 for modlon register mapping.
Size (bits): 16 Monitor point for the Oil Tempera-
Sign: S ture. Modbus and PCCnet has
Unit: degK different multiplier value. For
Lower Limit: Modlon use 0.1 deg Kelvin
Upper Limit:

116
Addr. Parameter Access Specifications Description Control
40738 Coolant Tem- Read Multiplier: 0.1 This Modbus register is created PC 3.x
perature (Mod- Only Offset: 0 for modlon register mapping.
lon) Size (bits): 16 Monitor point for the Coolant
Sign: S Temperature. Modbus and
Unit: degK PCCnet has different multiplier
Lower Limit: value. For Modlon, use 0.1deg
Upper Limit: Kelvin.

40739 Intake Manifold Read Multiplier: 0.1 This Modbus register is created PC 3.x
Temperature Only Offset: 0 for modlon register mapping. To
(Modlon) Size (bits): 16 monitor Intake Manifold Tempera-
Sign: S ture. Modbus and PCCnet has
Unit: degK different multiplier value. For
Lower Limit: −40 Modlon, use 0.1 deg Kelvin
Upper Limit: 410

40740 Fuel Tempera- Read Multiplier: 0.1 This Modbus register is created PC 3.x
ture (Modlon) Only Offset: 0 for modlon register mapping.
Size (bits): 16 Monitor point for the Fuel Temper-
Sign: S ature. Modbus and PCCnet has
Unit: degK different multiplier value. For
Lower Limit: −40 Modlon, use 0.1 deg Kelvin.
Upper Limit: 410

40741 Fuel Rate Read Multiplier: 0.01 This Modbus register is created PC 3.x
(Modlon) Only Offset: 0 for modlon register mapping.
Size (bits): 16 Monitor point for the Fuel Rate.
Sign: U Modbus and PCCnet has different
Unit: gal/hr multiplier value. For Modlon, use
Lower Limit: 0.01 gph
Upper Limit:

40742 Average Engine Read Multiplier: 1 This Modbus register is created PC 3.x
Speed (Mod- Only Offset: 0 for modlon register mapping.
lon) Size (bits): 16 Monitor point for the Average En-
Sign: U gine Speed. Modbus and PCCnet
Unit: RPM have different multiplier value. For
Lower Limit: Modlon, use 1 RPM.
Upper Limit:

40743 Total Number of Read Multiplier: 1 This Modbus register is created PC 3.x
Runs (Modlon) Only Offset: 0 for modlon register mapping. To-
Size (bits): 32 tal number of generator set runs.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967295

40744 Engine Running Read Multiplier: 0.1 This Modbus register is created PC 3.x
Time (Modlon) Only Offset: 0 for modlon register mapping. To-
Size (bits): 16 tal engine run time. Modbus has
Sign: U different multiplier than PCCnet.
Unit: seconds For Modbus, use 0.1 sec
Lower Limit:
Upper Limit:

117
Addr. Parameter Access Specifications Description Control
40745 Engine Running Read Multiplier: 0.1 This Modbus register is created PC 3.x
Time (Modlon) Only Offset: 0 for modlon register mapping. To-
Size (bits): 16 tal engine run time. Modbus has
Sign: U different multiplier than PCCnet.
Unit: seconds For Modbus, use 0.1 sec
Lower Limit:
Upper Limit:

40746 Genset Total Read Multiplier: 1 This Modbus register is created PC 3.x
Net kWh (Mod- Only Offset: 0 for modlon register mapping.
lon) Size (bits): 32 Generator set total net kWh accu-
Sign: S mulation
Unit: kWh
Lower Limit: −2147483648
Upper Limit: 2147483643

40747 Genset Total Read Multiplier: 1 This Modbus register is created PC 3.x
Net kWh (Mod- Only Offset: 0 for modlon register mapping.
lon) Size (bits): 32 Generator set total net kWh accu-
Sign: S mulation
Unit: kWh
Lower Limit: −2147483648
Upper Limit: 2147483643

40748 Total Fuel Con- Read Multiplier: 0.01 This Modbus register is created PC 3.x
sumption (Mod- Only Offset: 0 for modlon register mapping. To-
lon) Size (bits): 32 tal fuel consumption since start of
Sign: U engine. Modbus and PCCnet has
Unit: gallons different multiplier value. For
Lower Limit: Modlon, use 0.01 Gallons
Upper Limit:

40749 Total Fuel Con- Read Multiplier: 0.01 This Modbus register is created PC 3.x
sumption (Mod- Only Offset: 0 for modlon register mapping. To-
lon) Size (bits): 32 tal fuel consumption since start of
Sign: U engine. Modbus and PCCnet has
Unit: gallons different multiplier value. For
Lower Limit: Modlon, use 0.01 Gallons
Upper Limit:

40750 Utility/Genset Read Multiplier: 0.1 This Modbus register is created PC 3.x
Bus Frequency Only Offset: 0 for modlon register mapping. Util-
(Modlon) Size (bits): 16 ity line frequency or Generator set
Sign: U Bus Frequency depending on
Unit: Hz Paralleling Application. Modbus
Lower Limit: and PCCnet has different multipli-
Upper Limit: er value. For Modlon, use 0.1 Hz.

40751 Utility/Genset Read Multiplier: 1 This Modbus register is created PC 3.x


Bus L1L2 Volt- Only Offset: 0 for modlon register mapping. Util-
age (Modlon) Size (bits): 16 ity L1L2 Voltage or Generator set
Sign: U Bus L1L2 voltage depending on
Unit: Vac paralleling application.
Lower Limit:
Upper Limit:

118
Addr. Parameter Access Specifications Description Control
40752 Utility/Genset Read Multiplier: 1 This Modbus register is created PC 3.x
Bus L2L3 Volt- Only Offset: 0 for modlon register mapping. Util-
age (Modlon) Size (bits): 16 ity L2L3 voltage
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
40753 Utility/Genset Read Multiplier: 1 This Modbus register is created PC 3.x
Bus L3L1 Volt- Only Offset: 0 for modlon register mapping. Util-
age (Modlon) Size (bits): 16 ity L3L1 voltage or Generator set
Sign: U Bus L3L1 voltage depending on
Unit: Vac paralleling application.
Lower Limit:
Upper Limit:
40754 Utility/Genset Read Multiplier: 1 This Modbus register is created PC 3.x
Bus L1N Volt- Only Offset: 0 for modlon register mapping. Util-
age (Modlon) Size (bits): 16 ity L1N voltage or Generator set
Sign: U Bus L1N voltage depending on
Unit: Vac paralleling application.
Lower Limit:
Upper Limit:
40755 Utility/Genset Read Multiplier: 1 This Modbus register is created PC 3.x
Bus L2N Volt- Only Offset: 0 for modlon register mapping. Util-
age (Modlon) Size (bits): 16 ity L2N voltage or Generator set
Sign: U Bus L2N voltage depending on
Unit: Vac paralleling application.
Lower Limit:
Upper Limit:
40756 Utility/Genset Read Multiplier: 1 This Modbus register is created PC 3.x
Bus L3N Volt- Only Offset: 0 for modlon register mapping. Util-
age (Modlon) Size (bits): 16 ity L3N voltage or Generator set
Sign: U Bus L3N voltage depending on
Unit: Vac paralleling application.
Lower Limit:
Upper Limit:
40757 Customer Read Multiplier: 1 This Modbus register is created PC 3.x
Faults (Modlon) Only Offset: 0 for modlon register mapping. 16
Size (bits): 16 bit fault bitmap for Modbus inter-
Sign: U face.
Unit:
Lower Limit: 0
Upper Limit: 65530
40760 ES State (Mod- Read 0: Standby This Modbus register is created PC 3.x
lon) Only 1: Dead Bus for modlon register mapping. In-
2: Synchronize ternal paralleling status variable
3: Load Share
4: Load Goven
40761 Load Demand Read 0: Inactive This Modbus register is created PC 3.x
Stop Command Only 1: Active for modlon register mapping.
(Modlon) Modbus input for load demand
stop command.

119
Addr. Parameter Access Specifications Description Control
40764 Genset CB Read 0: Open This Modbus register is created PC 3.x
Position Status Only 1: Closed for modlon register mapping. indi-
(Modlon) 2: Not Available cates generator set breaker posi-
tion
40765 Utility CB Posi- Read 0: Open This Modbus register is created PC 3.x
tion Status Only 1: Closed for modlon register mapping. indi-
(Modlon) 2: Not Available cates utility breaker position
40766 Remote Start Read/ 0: Inactive This Modbus register is created PC 3.x
Switch(Modlon) Write 1: Active for modlon register mapping.
Modbus Remote Start
40767 Fault Reset Read/ 0: Inactive This Modbus register is created PC 3.x
(Modlon) Write 1: Active for modlon register mapping.
Modbus fault reset.
40768 System Net- Read 0: Inactive Indicates communication status of PC 3.x
work Datalink Only 1: Active the local genset on System Net-
Status 2: Failed work (used for load demand).
Available on PCC3300MLD con-
trols only.
40769 Load Read/ Multiplier: 1 Run hour accumulator used for PC 3.x
Demand Gen- Write Offset: 0 load demand run hour equaliza-
set Run Hours Size: 32 tion. This is writable. Available on
(Upper Register Sign: U PCC3300MLD controls only.
value) Units: Hours
Lower Limit: 0
Upper Limit: 999999.9
Default: 0
40770 Load Read/ Multiplier: 1 Run hour accumulator used for PC 3.x
Demand Gen- Write Offset: 0 load demand run hour equaliza-
set Run Hours Size: 32 tion. This is writable. Available on
(Lower Register Sign: U PCC3300MLD controls only.
value) Units: Hours
Lower Limit: 0
Upper Limit: 999999.9
Default: 0
40771 Load Demand Read 0: Inactive Indicates the status of the spare PC 3.x
Spare Capacity Only 1: Active capacity request input. When AC-
Request Status TIVE additional spare capacity
(set by Load Demand Spare Ca-
pacity Request Value) is re-
quested. Available on
PCC3300MLD controls only.
40772 System Net- Read 0: On Indicates the status of the on− PC 3.x
work Termina- Only 1: Off board CAN termination resistor
tion Resistor switch (S1). Available on
Switch Status PCC3300MLD controls only.

120
Addr. Parameter Access Specifications Description Control
40773 Genset ID Read/ 0: Gen1 9: Gen10 Genset identifier. All load demand PC 3.x
Write 1: Gen2 10: Gen11 gensets must have a unique Gen-
2: Gen3 11: Gen12 set ID. Available on
3: Gen4 12: Gen13 PCC3300MLD controls only. Set-
4: Gen5 13: Gen14 up Mode must be enabled to
5: Gen6 14: Gen15 modify the value. See Modbus
6: Gen7 15: Gen16 Address 43343.
7: Gen8
8: Gen9
40774 Load Demand Read/ Multiplier: 1 Sets the kW value of additional PC 3.x
Spare Capacity Write Offset: 0 capacity to be requested from the
Request Value Size(Bits): 32 system when the Load Demand
(Upper Register Sign: U Spare Capacity Request Status is
value) Units: kW YES. Available on PCC3300MLD
Lower Limit: 0 controls only. Setup Mode must
Upper Limit: 80000 be enabled to modify the value.
Default: 0 See Modbus Address 43343.
40775 Load Demand Read/ Multiplier: 1 Sets the kW value of additional PC 3.x
Spare Capacity Write Offset: 0 capacity to be requested from the
Request Value Size(Bits): 32 system when the Load Demand
(Lower Register Sign: U Spare Capacity Request Status is
value) Units: kW YES. Available on PCC3300MLD
Lower Limit: 0 controls only. Setup Mode must
Upper Limit: 80000 be enabled to modify the value.
Default: 0 See Modbus Address 43343.
40776 Load Demand Read/ 0: Disable Disables or Enables load demand PC 3.x
Genset Enable Write 1: Enable on this genset only. When set to
disable the genset is not included
in the load demand system and
can be removed without triggering
a com error. Available on
PCC3300MLD controls only. Set-
up Mode must be enabled to
modify the value. See Modbus
Address 43343.
40777 System Set- Read 0: Out of Sync Indicates whether the system set- PC 3.x
tings Status Only 1: In Sync tings on the local genset are in
sync with ones from other genset
in the network. Available on
PCC3300MLD controls only.
40800 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

121
Addr. Parameter Access Specifications Description Control
40801 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40802 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40803 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40804 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40805 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40806 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40807 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

122
Addr. Parameter Access Specifications Description Control
40808 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40809 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40810 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40811 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40812 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40813 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40814 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

123
Addr. Parameter Access Specifications Description Control
40815 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40816 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40817 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40818 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40819 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40820 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40821 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

124
Addr. Parameter Access Specifications Description Control
40822 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40823 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40824 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40825 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40826 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40827 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40828 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

125
Addr. Parameter Access Specifications Description Control
40829 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40830 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40831 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40832 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40833 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40834 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40835 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

126
Addr. Parameter Access Specifications Description Control
40836 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40837 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40838 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40839 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40840 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40841 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40842 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

127
Addr. Parameter Access Specifications Description Control
40843 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write to enter the configurable fault text PC 3.x
for this fault.
40844 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40845 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40846 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40847 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40848 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40849 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

128
Addr. Parameter Access Specifications Description Control
40850 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40851 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40852 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40853 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40854 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40855 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40856 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

129
Addr. Parameter Access Specifications Description Control
40857 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40858 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40859 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40860 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40861 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40862 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40863 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

130
Addr. Parameter Access Specifications Description Control
40864 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40865 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40866 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40867 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40868 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40869 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40870 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

131
Addr. Parameter Access Specifications Description Control
40871 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40872 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40873 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40874 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40875 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40876 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

132
Addr. Parameter Access Specifications Description Control
40877 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40878 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40879 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40880 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40881 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40882 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

133
Addr. Parameter Access Specifications Description Control
40883 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40884 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40885 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40886 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40887 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40888 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40889 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

134
Addr. Parameter Access Specifications Description Control
40890 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40891 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40892 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40893 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40894 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40895 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40896 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

135
Addr. Parameter Access Specifications Description Control
40897 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40898 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40899 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40900 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40901 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40902 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40903 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

136
Addr. Parameter Access Specifications Description Control
40904 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40905 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40906 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40907 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40908 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40909 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40910 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

137
Addr. Parameter Access Specifications Description Control
40911 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40912 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40913 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40914 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40915 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40916 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40917 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

138
Addr. Parameter Access Specifications Description Control
40918 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40919 Aux102 0 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40920 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40921 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40922 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40923 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40924 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

139
Addr. Parameter Access Specifications Description Control
40925 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40926 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40927 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40928 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40929 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40930 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40931 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

140
Addr. Parameter Access Specifications Description Control
40932 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40933 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40934 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40935 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40936 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40937 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40938 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

141
Addr. Parameter Access Specifications Description Control
40939 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
9 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40940 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40941 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40942 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40943 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40944 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40945 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

142
Addr. Parameter Access Specifications Description Control
40946 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40947 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40948 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40949 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40950 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40951 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40952 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

143
Addr. Parameter Access Specifications Description Control
40953 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40954 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40955 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40956 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40957 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40958 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40959 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
10 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

144
Addr. Parameter Access Specifications Description Control
40960 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40961 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40962 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40963 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40964 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40965 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40966 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

145
Addr. Parameter Access Specifications Description Control
40967 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40968 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40969 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40970 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40971 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40972 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40973 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

146
Addr. Parameter Access Specifications Description Control
40974 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40975 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40976 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40977 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40978 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40979 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
11 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40980 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

147
Addr. Parameter Access Specifications Description Control
40981 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40982 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40983 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40984 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40985 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40986 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40987 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

148
Addr. Parameter Access Specifications Description Control
40988 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40989 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40990 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40991 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40992 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40993 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

40994 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

149
Addr. Parameter Access Specifications Description Control
40995 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40996 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40997 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40998 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
40999 Aux102 1 Fault Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
12 Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
41000 Load Read/ 0: Disable Disables or Enables load demand PC 3.x
Demand Sys- Write 1: Enable operation of all connected gen-
tem sets. Available on PCC3300MLD
Enable controls only.

41001 Load Read/ 0: Run Hours Equalization (Run Sets the sequencing priority for PC 3.x
Demand Write Hr Eql) load demand. Available on
Type 1: Fixed Sequence (Fixed Seq) PCC3300MLD controls only.

150
Addr. Parameter Access Specifications Description Control
41002 Load Read/ 0: kW Sets whether the load demand PC 3.x
Demand Write 1: %kW start/stop control is based on a
Threshold Me- relative (%) or absolute (kW) thre-
thod shold. Available on
PCC3300MLD controls only.

41003 Load Demand Read/ Multiplier: 1 When the ratio of load to capacity PC 3.x
Start Threshold Write Offset: 0 is greater than this value the next
(%kW) Size(Bits): 8 genset will start. Must be greater
Sign: U than Load Demand Stop Thresh-
Units: % old by at least 5%. Available on
Lower Limit: 25 PCC3300MLD controls only.
Upper Limit: 100
Default: 80
41004 Load Demand Read/ Multiplier: 1 When surplus capacity is less PC 3.x
Start Threshold Write Offset: 0 than this value the next genset
(kW) Size(Bits): 16 will start. Must be less than Load
Sign: U Demand Stop Threshold (kW).
Units: kW Available on PCC3300MLD con-
Lower Limit: 5 trols only.
Upper Limit: 5000
Default: 500
41005 Load Demand Read/ Multiplier: 1 When the ratio of load to capacity PC 3.x
Stop Threshold Write Offset: 0 is less than this value the next
(%kW) Size(Bits): 8 genset will stop. Must be less
Sign: U than Load Demand Start Thresh-
Units: % old by at least 5%. Available on
Lower Limit: 20 PCC3300MLD controls only.
Upper Limit: 95
Default: 60
41006 Load Demand Read/ Multiplier: 1 When surplus capacity is greater PC 3.x
Stop Threshold Write Offset: 0 than this value the next genset
(kW) Size(Bits): 16 will stop. Must be greater than
Sign: U Load Demand Start Threshold
Units: kW (kW). Available on PCC3300MLD
Lower Limit: 5 controls only.
Upper Limit: 5000
Default: 1000
41007 Load Demand Read/ Multiplier: 1 When the difference between PC 3.x
Run Hours Dif- Write Offset: 0 Load Demand Genset Run Hours
ferential Size(Bits): 16 between any running genset and
Sign: U any stopped genset reaches this
Units: Hours value the stopped genset will be
Lower Limit: 1 started. Available on
Upper Limit: 250 PCC3300MLD controls only.
Default: 50

151
Addr. Parameter Access Specifications Description Control
41008 Load Demand Read/ Multiplier: 1 Sets the time delay that the sys- PC 3.x
Genset Fail De- Write Offset: 0 tem waits for a genset to come
lay Size(Bits): 16 online before declaring it as fai-
Sign: U led. Available on PCC3300MLD
Units: seconds controls only.
Lower Limit: 10
Upper Limit: 900
Default: 60
41009 Load Demand Read/ Multiplier: 1 Sets the time delay before gen- PC 3.x
Initial Delay Write Offset: 0 sets are allowed to stop after ini-
Size(Bits): 16 tial start or after resuming halted
Sign: U load demand. Available on
Units: seconds PCC3300MLD controls only.
Lower Limit: 60
Upper Limit: 1500
Default: 300
41010 Load Demand Read/ Multiplier: 1 Sets the time delay before next PC 3.x
Start Delay Write Offset: 0 genset is allowed to start. Avail-
Size(Bits): 16 able on PCC3300MLD controls
Sign: U only.
Units: seconds
Lower Limit: 0
Upper Limit: 1500
Default: 10
41011 Load Demand Read/ Multiplier: 1 Sets the time delay before next PC 3.x
Stop Delay Write Offset: 0 genset is allowed to stop. Avail-
Size(Bits): 16 able on PCC3300MLD controls
Sign: U only.
Units: seconds
Lower Limit: 60
Upper Limit: 1500
Default: 300
41012 Clear Lost Gen- Read/ 0: No When set to YES all gensets in PC 3.x
sets Local Write 1: Yes state ”Lost” will change to state
”Gen Does Not Exist” in order to
clear Lost Genset Warning. Avail-
able on PCC3300MLD controls
only.
41013 Load Read/ 0: Gen1 9: Gen10 Assigns a genset to fixed priority PC 3.x
Demand Fixed Write 1: Gen2 10: Gen11 1. Used when Load Demand
Priority 1 2: Gen3 11: Gen12 Type is set to Fixed Sequence.
3: Gen4 12: Gen13 Available on PCC3300MLD con-
4: Gen5 13: Gen14 trols only.
5: Gen6 14: Gen15
6: Gen7 15: Gen16
7: Gen8
8: Gen9

152
Addr. Parameter Access Specifications Description Control
41014 Load Read/ 0: Gen1 9: Gen10 Assigns a genset to fixed priority PC 3.x
Demand Fixed Write 1: Gen2 10: Gen11 2. Used when Load Demand
Priority 2 2: Gen3 11: Gen12 Type is set to Fixed Sequence.
3: Gen4 12: Gen13 Available on PCC3300MLD con-
4: Gen5 13: Gen14 trols only.
5: Gen6 14: Gen15
6: Gen7 15: Gen16
7: Gen8
8: Gen9
41015 Load Read/ 0: Gen1 9: Gen10 Assigns a genset to fixed priority PC 3.x
Demand Fixed Write 1: Gen2 10: Gen11 3. Used when Load Demand
Priority 3 2: Gen3 11: Gen12 Type is set to Fixed Sequence.
3: Gen4 12: Gen13 Available on PCC3300MLD con-
4: Gen5 13: Gen14 trols only.
5: Gen6 14: Gen15
6: Gen7 15: Gen16
7: Gen8
8: Gen9
41016 Load Read/ 0: Gen1 9: Gen10 Assigns a genset to fixed priority PC 3.x
Demand Fixed Write 1: Gen2 10: Gen11 4. Used when Load Demand
Priority 4 2: Gen3 11: Gen12 Type is set to Fixed Sequence.
3: Gen4 12: Gen13 Available on PCC3300MLD con-
4: Gen5 13: Gen14 trols only.
5: Gen6 14: Gen15
6: Gen7 15: Gen16
7: Gen8
8: Gen9
41017 Load Read/ 0: Gen1 9: Gen10 Assigns a genset to fixed priority PC 3.x
Demand Fixed Write 1: Gen2 10: Gen11 5. Used when Load Demand
Priority 5 2: Gen3 11: Gen12 Type is set to Fixed Sequence.
3: Gen4 12: Gen13 Available on PCC3300MLD con-
4: Gen5 13: Gen14 trols only.
5: Gen6 14: Gen15
6: Gen7 15: Gen16
7: Gen8
8: Gen9
41018 Load Read/ 0: Gen1 9: Gen10 Assigns a genset to fixed priority PC 3.x
Demand Fixed Write 1: Gen2 10: Gen11 6. Used when Load Demand
Priority 6 2: Gen3 11: Gen12 Type is set to Fixed Sequence.
3: Gen4 12: Gen13 Available on PCC3300MLD con-
4: Gen5 13: Gen14 trols only.
5: Gen6 14: Gen15
6: Gen7 15: Gen16
7: Gen8
8: Gen9

153
Addr. Parameter Access Specifications Description Control
41019 Load Read/ 0: Gen1 9: Gen10 Assigns a genset to fixed priority PC 3.x
Demand Fixed Write 1: Gen2 10: Gen11 7. Used when Load Demand
Priority 7 2: Gen3 11: Gen12 Type is set to Fixed Sequence.
3: Gen4 12: Gen13 Available on PCC3300MLD con-
4: Gen5 13: Gen14 trols only.
5: Gen6 14: Gen15
6: Gen7 15: Gen16
7: Gen8
8: Gen9
41020 Load Read/ 0: Gen1 9: Gen10 Assigns a genset to fixed priority PC 3.x
Demand Fixed Write 1: Gen2 10: Gen11 8. Used when Load Demand
Priority 8 2: Gen3 11: Gen12 Type is set to Fixed Sequence.
3: Gen4 12: Gen13 Available on PCC3300MLD con-
4: Gen5 13: Gen14 trols only.
5: Gen6 14: Gen15
6: Gen7 15: Gen16
7: Gen8
8: Gen9
41021 Load Read/ 0: Gen1 9: Gen10 Assigns a genset to fixed priority PC 3.x
Demand Fixed Write 1: Gen2 10: Gen11 9. Used when Load Demand
Priority 9 2: Gen3 11: Gen12 Type is set to Fixed Sequence.
3: Gen4 12: Gen13 Available on PCC3300MLD con-
4: Gen5 13: Gen14 trols only.
5: Gen6 14: Gen15
6: Gen7 15: Gen16
7: Gen8
8: Gen9
41022 Load Read/ 0: Gen1 9: Gen10 Assigns a genset to fixed priority PC 3.x
Demand Fixed Write 1: Gen2 10: Gen11 10. Used when Load Demand
Priority 10 2: Gen3 11: Gen12 Type is set to Fixed Sequence.
3: Gen4 12: Gen13 Available on PCC3300MLD con-
4: Gen5 13: Gen14 trols only.
5: Gen6 14: Gen15
6: Gen7 15: Gen16
7: Gen8
8: Gen9
41023 Load Read/ 0: Gen1 9: Gen10 Assigns a genset to fixed priority PC 3.x
Demand Fixed Write 1: Gen2 10: Gen11 11. Used when Load Demand
Priority 11 2: Gen3 11: Gen12 Type is set to Fixed Sequence.
3: Gen4 12: Gen13 Available on PCC3300MLD con-
4: Gen5 13: Gen14 trols only.
5: Gen6 14: Gen15
6: Gen7 15: Gen16
7: Gen8
8: Gen9

154
Addr. Parameter Access Specifications Description Control
41024 Load Read/ 0: Gen1 9: Gen10 Assigns a genset to fixed priority PC 3.x
Demand Fixed Write 1: Gen2 10: Gen11 12. Used when Load Demand
Priority 12 2: Gen3 11: Gen12 Type is set to Fixed Sequence.
3: Gen4 12: Gen13 Available on PCC3300MLD con-
4: Gen5 13: Gen14 trols only.
5: Gen6 14: Gen15
6: Gen7 15: Gen16
7: Gen8
8: Gen9

41025 Load Read/ 0: Gen1 9: Gen10 Assigns a genset to fixed priority PC 3.x
Demand Fixed Write 1: Gen2 10: Gen11 13. Used when Load Demand
Priority 13 2: Gen3 11: Gen12 Type is set to Fixed Sequence.
3: Gen4 12: Gen13 Available on PCC3300MLD con-
4: Gen5 13: Gen14 trols only.
5: Gen6 14: Gen15
6: Gen7 15: Gen16
7: Gen8
8: Gen9

41026 Load Read/ 0: Gen1 9: Gen10 Assigns a genset to fixed priority PC 3.x
Demand Fixed Write 1: Gen2 10: Gen11 14. Used when Load Demand
Priority 14 2: Gen3 11: Gen12 Type is set to Fixed Sequence.
3: Gen4 12: Gen13 Available on PCC3300MLD con-
4: Gen5 13: Gen14 trols only.
5: Gen6 14: Gen15
6: Gen7 15: Gen16
7: Gen8
8: Gen9

41027 Load Read/ 0: Gen1 9: Gen10 Assigns a genset to fixed priority PC 3.x
Demand Fixed Write 1: Gen2 10: Gen11 15. Used when Load Demand
Priority 15 2: Gen3 11: Gen12 Type is set to Fixed Sequence.
3: Gen4 12: Gen13 Available on PCC3300MLD con-
4: Gen5 13: Gen14 trols only.
5: Gen6 14: Gen15
6: Gen7 15: Gen16
7: Gen8
8: Gen9

41028 Load Read/ 0: Gen1 9: Gen10 Assigns a genset to fixed priority PC 3.x
Demand Fixed Write 1: Gen2 10: Gen11 16. Used when Load Demand
Priority 16 2: Gen3 11: Gen12 Type is set to Fixed Sequence.
3: Gen4 12: Gen13 Available on PCC3300MLD con-
4: Gen5 13: Gen14 trols only.
5: Gen6 14: Gen15
6: Gen7 15: Gen16
7: Gen8
8: Gen9

41029 System Net- Read/ 0: Inactive When set to YES all the system PC 3.x
work Remote Write 1: Active network faults in the system
Fault Reset would be reset. Available on
PCC3300MLD controls only.

155
Addr. Parameter Access Specifications Description Control
41030 Synchronize Read/ 0: No When set to YES system settings PC 3.x
System Set- Write 1: Yes from the genset will be broad-
tings casted and synchronized to all
other gensets in the network.
Available on PCC3300MLD con-
trols only.
41031 Battery Charger Read 0: Inactive Battery Charger 2 Failed Switch PC3.x
2 Failed Switch Only 1: Active function output status; gives soft-
ware Inactive/Active state
41032 Battery Charger Read 0: Inactive Battery Charger 3 Failed Switch PC3.x
3 Failed Switch Only 1: Active function output status; gives soft-
ware Inactive/Active state
41033 Battery Charger Read 0: Inactive Battery Charger 4 Failed Switch PC3.x
4 Failed Switch Only 1: Active function output status; gives soft-
ware Inactive/Active state
41034 Intake Air Re- Read 0: Inactive Intake Air Restriction Indicator 1 PC3.x
striction Indica- Only 1: Active fault switch function output status;
tor 1 fault gives software Inactive/Active
switch state
41035 Intake Air Re- Read 0: Inactive Intake Air Restriction Indicator 2 PC3.x
striction Indica- Only 1: Active fault switch function output status;
tor 2 fault gives software Inactive/Active
switch state
41036 Intake Air Re- Read 0: Inactive Intake Air Restriction Indicator 3 PC3.x
striction Indica- Only 1: Active fault switch function output status;
tor 3 fault gives software Inactive/Active
switch state
41037 Intake Air Re- Read 0: Inactive Intake Air Restriction Indicator 4 PC3.x
striction Indica- Only 1: Active fault switch function output status;
tor 4 fault gives software Inactive/Active
switch state
41038 Starter Air Sup- Read 0: Inactive Starter Air Supply Pressure Low PC3.x
ply Pressure Only 1: Active Fault Switch function output sta-
Low Fault tus; gives software Inactive/Ac-
Switch tive”
41039 Starter Air Tank Read 0: Inactive Starter Air Tank Volume Low PC3.x
Volume Low Only 1: Active Fault Switch function output sta-
Fault Switch tus; gives software Inactive/Active
state
41300 AmpSentry Read 0: Inactive A protection mode that causes PC3.x
Maintenance Only 1: Active the alternator to shutdown in-
Mode Status stantly when a short circuit is de-
tected. Used to limit arc flash en-
ergy with personnel working

156
Addr. Parameter Access Specifications Description Control
41301 AMM PC Tool Read 0: Inactive Detects whether any service tool PC3.x
Detected Only 1: Active is connected via TB15 or J14 by
validating if a read/write com-
mand has been exchanged via
MON using a five second decre-
mental timer. If the timer exprires,
then it is determine service tool is
no longer connected.
41302 AMM Disable Read Multiplier : 1 Units: Seconds Countdown timer when walkaway PC3.x
Walkaway Tim- Only is complete.
er Value
Offset: 0 Lower Limit: NA
Size (Bits) : Upper Limit: NA
16
Sign: U Default: NA
41400 Fault Status Bit- Read Multiplier : 1 Units: NA 16 bit fault bitmap for modbus in- PC3.x
map 31 Only terface.
Offset: 0 Lower Limit: 0
Size (Bits) : Upper Limit:
16 65535
Sign: U Default: NA
41401 Fault Status Bit- Read Multiplier : 1 Units: NA 16 bit Diesel Fault Bitmap for PC3.x
map 33 Only modbus interface
Offset: 0 Lower Limit: 0
Size (Bits) : Upper Limit:
16 65535
Sign: U Default: NA
41402 Fault Status Bit- Read Multiplier : 1 Units: NA 16 bit Diesel Fault Bitmap for PC 2.x
map 34 Only modbus interface PC3.x
Offset: 0 Lower Limit: 0
Size (Bits) : Upper Limit:
16 65535
Sign: U Default: NA
41403 AT Fault Status Read Multiplier : 1 Units: NA 16 bit AT Fault Bitmap for mod- PC3.x
Bitmap 2 Only bus interface
Offset: 0 Lower Limit: 0
Size (Bits) : Upper Limit:
16 65535
Sign: U Default: NA
41404 AT Fault Status Read Multiplier : 1 Units: NA 16 bit AT Fault Bitmap for mod- PC3.x
Bitmap 3 Only bus interface
Offset: 0 Lower Limit: 0
Size (Bits) : Upper Limit:
16 65535
Sign: U Default: NA

157
Addr. Parameter Access Specifications Description Control
41405 AT Fault Status Read Multiplier : 1 Units: NA 16 bit AT Fault Bitmap for mod- PC3.x
Bitmap 4 Only bus interface
Offset: 0 Lower Limit: 0
ize (Bits) : Upper Limit:
16 65535
Sign: U Default: NA
41406 AT Fault Status Read Multiplier : 1 Units: NA 16 bit AT Fault Bitmap for mod- PC3.x
Bitmap 5 Only bus interface
Offset: 0 Lower Limit: 0
Size (Bits) : Upper Limit:
16 65535
Sign: U Default: NA
41407 AT Fault Status Read Multiplier : 1 Units: NA 16 bit AT Fault Bitmap for mod- PC3.x
Bitmap 6 Only bus interface
Offset: 0 Lower Limit: 0
Size (Bits) : Upper Limit:
16 65535
Sign: U Default: NA
41408 AT Fault Status Read Multiplier : 1 Units: NA 16 bit AT Fault Bitmap for mod- PC3.x
Bitmap 7 Only bus interface
Offset: 0 Lower Limit: 0
Size (Bits) : Upper Limit:
16 65535
Sign: U Default: NA
41409 AT Fault Status Read Multiplier : 1 Units: NA 16 bit AT Fault Bitmap for mod- PC3.x
Bitmap 8 Only bus interface
Offset: 0 Lower Limit: 0
Size (Bits) : Upper Limit:
16 65535
Sign: U Default: NA
41416 Fault Status Bit- Read Multiplier : 1 Units: NA 16 bit Diesel Fault Bitmap for PC3.x
map 35 Only modbus interface
Offset: 0 Lower Limit: 0
Size (Bits) : Upper Limit:
16 65535
Sign: U Default: NA
41417 Fault Status Bit- Read Multiplier : 1 Units: NA 16 bit Diesel Fault Bitmap for PC3.x
map 36 Only modbus interface
Offset: 0 Lower Limit: 0
Size (Bits) : Upper Limit:
16 65535
Sign: U Default: NA
41418 Fault Status Bit- Read Multiplier : 1 Units: NA 16 bit Diesel Fault Bitmap for PC3.x
map 37 Only modbus interface

158
Addr. Parameter Access Specifications Description Control
Offset: 0 Lower Limit: 0
Size (Bits) : Upper Limit:
16 65535
Sign: U Default: NA
42000 Load Read 0: Off Indicates the status of Load De- PC 3.x
Demand State Only 1: Halted mand operation.. Available on
2: Initial Delay PCC3300MLD controls only.
3: Load Monitor
42001 Load Demand Read Multiplier: 1.0 Indicates the total load of System PC 3.x
Genset Bus To- Only Offset: 0 Network connected gensets.
tal kW (Upper Size (bits): 32 Available on PCC3300MLD con-
Register value) Sign: U trols only.
Units: kW
Lower Limit: 0
Upper Limit: 80000
Default: 0

42002 Load Demand Read Multiplier: 1.0 Indicates the total load of System PC 3.x
Genset Bus To- Only Offset: 0 Network connected gensets.
tal kW (Lower Size (bits): 32 Available on PCC3300MLD con-
Register value) Sign: U trols only.
Units: kW
Lower Limit: 0
Upper Limit: 80000
Default: 0

42003 Load Demand Read Multiplier: 1.0 Indicates the total load of System PC 3.x
Surplus Capaci- Only Offset: 0 Network connected gensets.
ty (Upper Reg- Size (bits): 32 Available on PCC3300MLD con-
ister value) Sign: U trols only.
Units: kW
Lower Limit: 0
Upper Limit: 80000
Default: 0

159
Addr. Parameter Access Specifications Description Control
42004 Load Demand Read Multiplier: 1.0 Indicates the total load of System PC 3.x
Surplus Capaci- Only Offset: 0 Network connected gensets.
ty (Lower Reg- Size (bits): 32 Available on PCC3300MLD con-
ister value) Sign: U trols only.
Units: kW
Lower Limit: 0
Upper Limit: 80000
Default: 0

42005 Load Demand Read Multiplier: 1.0 Indicates the total amount of on- PC 3.x
Online Capacity Only Offset: 0 line kW bus capacity for load de-
(Upper Register Size (bits): 32 mand. Only gensets which are
value) Sign: U eligible for load demand are
Units: kW counted. Available on
Lower Limit: 0 PCC3300MLD controls only.
Upper Limit: 80000
Default: 0

42006 Load Demand Read Multiplier: 1.0 Indicates the total amount of on- PC 3.x
Online Capacity Only Offset: 0 line kW bus capacity for load de-
(Lower Register Size (bits): 32 mand. Only gensets which are
value) Sign: U eligible for load demand count.
Units: kW Available on PCC3300MLD con-
Lower Limit: 0 trols only.
Upper Limit: 80000
Default: 0

42007 Load Read Multiplier: 1.0 Indicates the time remaining be- PC 3.x
Demand Only Offset: 0 fore gensets are allowed to stop
Initial Delay Size (bits): 16 after initial start or after resuming
Timer Sign: U halted load demand. This timer is
Units: Seconds set by Load Demand Initial Delay.
Lower Limit: 0 Available on PCC3300MLD con-
Upper Limit: 1500 trols only.
Default: 0

160
Addr. Parameter Access Specifications Description Control
42008 Load Read Multiplier: 1.0 Indicates the time remaining be- PC 3.x
Demand Start Only Offset: 0 fore next genset is allowed to
Delay Timer Size (bits): 16 start. This timer is set by Load
Sign: U Demand Start Delay. Available on
Units: Seconds PCC3300MLD controls only.
Lower Limit: 0
Upper Limit: 1500
Default: 0

42009 Load Read Multiplier: 1.0 Indicates the time remaining be- PC 3.x
Demand Stop Only Offset: 0 fore next genset is allowed to
Delay Timer Size (bits): 16 stop. This timer is set by Load
Sign: U Demand Stop Delay. Available on
Units: Seconds PCC3300MLD controls only.
Lower Limit: 0
Upper Limit: 1500
Default: 0

42010 Load Read 0: No Indicates when the current load PC 3.x


Demand Spare Only 1: Yes and spare capacity requirements
Capacity Avail- are satisfied. Available on
able PCC3300MLD controls only.

42011 Load Read Multiplier: 1.0 Indicates the total kW value of all PC 3.x
Demand Only Offset: 0 currently active spare capacity re-
Total Spare Ca- Size (bits): 32 quests in the system. Available
pacity Sign: U on PCC3300MLD controls only.
Requested (Up- Units: kW
per Register Lower Limit: 0
value) Upper Limit: 80000
Default: 0
42012 Load Read Multiplier: 1.0 Indicates the total kW value of all PC 3.x
Demand Only Offset: 0 currently active spare capacity re-
Total Spare Ca- Size (bits): 32 quests in the system. Available
pacity Sign: U on PCC3300MLD controls only.
Requested Units: kW
(Lower Register Lower Limit: 0
value) Upper Limit: 80000
Default: 0

161
Addr. Parameter Access Specifications Description Control
42013 Load Demand Read Multiplier: 1.0 The kW load at which the next PC 3.x
Next Start Only Offset: 0 genset will be started. Available
Threshold (kW) Size (bits): 32 on PCC3300MLD controls only.
(Upper Register Sign: U
value) Units: kW
Lower Limit: 0
Upper Limit: 80000
Default: 0

42014 Load Demand Read Multiplier: 1.0 The kW load at which the next PC 3.x
Next Start Only Offset: 0 genset will be started. Available
Threshold (kW) Size (bits): 32 on PCC3300MLD controls only.
(Lower Register Sign: U
value) Units: kW
Lower Limit: 0
Upper Limit: 80000
Default: 0

42015 Load Demand Read Multiplier: 1.0 The kW load at which the next PC 3.x
Next Stop Thre- Only Offset: 0 genset will be stopped. Available
shold (Upper Size (bits): 32 on PCC3300MLD controls only.
Register value) Sign: U
Units: kW
Lower Limit: 0
Upper Limit: 80000
Default: 0
42016 Load Demand Read Multiplier: 1.0 The kW load at which the next PC 3.x
Next Stop Thre- Only Offset: 0 genset will be stopped. Available
shold (Lower Size (bits): 32 on PCC3300MLD controls only.
Register value) Sign: U
Units: kW
Lower Limit: 0
Upper Limit: 80000
Default: 0
42017 Load Demand Read 0: Gen1 9: Gen10 Indicates the next genset to start PC 3.x
Next Gen to Only 1: Gen2 10: Gen11 by ID. Available on PCC3300MLD
start (kW) 2: Gen3 11: Gen12 controls only.
3: Gen4 12: Gen13
4: Gen5 13: Gen14
5: Gen6 14: Gen15
6: Gen7 15: Gen16
7: Gen8
8: Gen9

162
Addr. Parameter Access Specifications Description Control
42018 Load Demand Read 0: Gen1 9: Gen10 Indicates the next genset to stop PC 3.x
Next Gen to Only 1: Gen2 10: Gen11 by ID. Available on PCC3300MLD
Stop 2: Gen3 11: Gen12 controls only.
3: Gen4 12: Gen13
4: Gen5 13: Gen14
5: Gen6 14: Gen15
6: Gen7 15: Gen16
7: Gen8
8: Gen9

42019 Load Demand Read 0: Inactive Indicates the status of the Load PC 3.x
Inhibit Local Only 1: Active Demand Inhibit input. When AC-
TIVE all the gensets will start.
Available on PCC3300MLD con-
trols only.

43000 Genset % Ap- Read Multiplier: 0.1 Monitors the generator set ap- PC 2.x,
plication L1 Only Offset: 0 plication L1 current percentage PC 3.x
Current Size (bits): 16 output.
Sign: U
Unit: %
Lower Limit:
Upper Limit:

43001 Genset % Ap- Read Multiplier: 0.1 Monitors the generator set ap- PC 2.x,
plication L2 Only Offset: 0 plication L2 current percentage PC 3.x
Current Size (bits): 16 output.
Sign: U
Unit: %
Lower Limit:
Upper Limit:

43002 Genset % Ap- Read Multiplier: 0.1 Monitors the generator set ap- PC 2.x,
plication L1 kVA Only Offset: 0 plication L1 KVA percentage out- PC 3.x
Size (bits): 16 put.
Sign: U
Unit: %
Lower Limit:
Upper Limit:

43003 Genset % Ap- Read Multiplier: 0.1 Monitors the generator set ap- PC 2.x,
plication L3 Only Offset: 0 plication L3 current percentage PC 3.x
Current Size (bits): 16 output.
Sign: U
Unit: %
Lower Limit:
Upper Limit:

43004 Genset % Ap- Read Multiplier: 0.1 Monitors the generator set ap- PC 2.x,
plication L2 kVA Only Offset: 0 plication L2 KVA percentage out- PC 3.x
Size (bits): 16 put.
Sign: U
Unit: %
Lower Limit:
Upper Limit:

163
Addr. Parameter Access Specifications Description Control
43005 Genset % Ap- Read Multiplier: 0.1 Monitors the generator set ap- PC 2.x,
plication L3 kVA Only Offset: 0 plication L3 KVA percentage out- PC 3.x
Size (bits): 16 put.
Sign: U
Unit: %
Lower Limit:
Upper Limit:

43006 Genset % Ap- Read Multiplier: 0.1 Monitors the generator set ap- PC 2.x,
plication L1 kW Only Offset: 0 plication L1 KW percentage out- PC 3.x
Size (bits): 16 put.
Sign: S
Unit: %
Lower Limit:
Upper Limit:

43007 Genset % Ap- Read Multiplier: 0.1 Monitors the generator set ap- PC 2.x,
plication L2 kW Only Offset: 0 plication L2 KW percentage out- PC 3.x
Size (bits): 16 put.
Sign: S
Unit: %
Lower Limit:
Upper Limit:

43008 Genset % Ap- Read Multiplier: 0.1 Monitors the generator set ap- PC 2.x,
plication L3 kW Only Offset: 0 plication L3 KW percentage out- PC 3.x
Size (bits): 16 put.
Sign: S
Unit: %
Lower Limit:
Upper Limit:

43009 Genset % Ap- Read Multiplier: 0.1 Monitors the total generator set PC 2.x,
plication Total Only Offset: 0 application KVA percentage out- PC 3.x
kVA Size (bits): 16 put.
Sign: U
Unit: %
Lower Limit:
Upper Limit:

43010 Genset % Ap- Read Multiplier: 0.1 Monitors the total generator set PC 2.x,
plication Total Only Offset: 0 application KW percentage out- PC 3.x
kW Size (bits): 16 put.
Sign: S
Unit: %
Lower Limit:
Upper Limit:

43011 Genset % Read Multiplier : 0.1 Monitors the genset standby L1 PC 2.X
Standby L1 kVA Only Offset: 0 KVA percentage output. PC3.X
Size (bits): 16
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA

164
Addr. Parameter Access Specifications Description Control
43012 Genset % Read Multiplier : 0.1 Monitors the genset standby L3 PC 2.x
Standby L3 kVA Only Offset: 0 KVA percentage output. PC3.x
Size (bits): 16
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
43013 Genset % Read Multiplier : 0.1 Monitors the genset standby L2 PC 2.x
Standby L2 kVA Only Offset: 0 KVA percentage output. PC3.x
Size (bits): 16
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43014 Genset % Read Multiplier : 0.1 Monitors the genset standby L1 PC 2.x
Standby L1 kW Only Offset: 0 KW percentage output. PC3.x
Size (bits): 16
Sign: S
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43015 Genset % Read Multiplier : 0.1 Monitors the genset standby L2 PC 2.x
Standby L2 kW Only Offset: 0 KW percentage output. PC3.x
Size (bits): 16
Sign: S
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43016 Genset % Read Multiplier : 0.1 Monitors the genset standby L3 PC 2.x
Standby L3 kW Only Offset: 0 KW percentage output. PC3.x
Size (bits): 16
Sign: S
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43017 Genset % Read Multiplier: 0.1 Monitors the total generator set PC 2.x,
Standby Total Only Offset: 0 standby KVA percentage output. PC 3.x
kVA Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:

165
Addr. Parameter Access Specifications Description Control
43018 Genset Applica- Read Multiplier: 0.1 The generator set KVA rating. PC 2.x,
tion kVA rating Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:

43019 Genset Applica- Read Multiplier: 0.1 The generator set KW rating. PC 2.x,
tion kW rating Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: kW
Lower Limit:
Upper Limit:

43020 Genset Applica- Read Multiplier: 1 The value of the generator set ap- PC 2.x,
tion Nominal Only Offset: 0 plication nominal current. Dis- PC 3.x
Current Size (bits): 16 played as ”Generator set Applica-
Sign: U tion Rated Current” in HMI
Unit: Amps
Lower Limit:
Upper Limit:

43021 Genset Aver- Read Multiplier: 0.01 Generator set average voltage PC 2.x,
age Voltage% Only Offset: 0 percentage. PC 3.x
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:

43030 Genset L1 Read Multiplier: 0.01 Generator set L1 power factor PC 2.x,
Power Factor Only Offset: 0 PC 3.x
Size (bits): 8
Sign: S
Unit: PF
Lower Limit:
Upper Limit:

43031 Genset L1L2 Read Multiplier: 0.01 Generator set L1L2 voltage PC 2.x,
Phase Differ- Only Offset: 0 phase angle PC 3.x
ence Size (bits): 16
Sign: U
Unit: Degrees
Lower Limit:
Upper Limit:

43032 Genset L1L2 Read Multiplier: 0.01 Generator set L1L2 voltage% PC 2.x,
Voltage% Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:

166
Addr. Parameter Access Specifications Description Control
43033 Genset L1N Read Multiplier: 0.01 Generator set L1N voltage% PC 2.x,
Voltage% Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:

43044 Genset L2 Read Multiplier: 0.01 Generator set L2 power factor PC 2.x,
Power Factor Only Offset: 0 PC 3.x
Size (bits): 8
Sign: S
Unit: PF
Lower Limit: −1.28
Upper Limit: 1.27

43045 Genset L2L3 Read Multiplier: 0.01 Generator set L2L3 voltage PC 2.x,
Phase Differ- Only Offset: 0 phase angle PC 3.x
ence Size (bits): 8
Sign: U
Unit: Degrees
Lower Limit: 0
Upper Limit: 655.3

43046 Genset L2L3 Read Multiplier: 0.01 Generator set L2L3 voltage% PC 2.x,
Voltage% Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:

43047 Genset L2N Read Multiplier: 0.01 Generator set L2N voltage% PC 2.x,
Voltage% Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: %
Lower Limit: 0
Upper Limit: 655.3

43058 Genset L3 Read Multiplier: 0.01 Generator set L3 power factor PC 2.x,
Power Factor Only Offset: 0 PC 3.x
Size (bits): 8
Sign: S
Unit: PF
Lower Limit: −1.28
Upper Limit: 1.22

43059 Genset L3L1 Read Multiplier: 0.01 Generator set L3L1 voltage PC 2.x,
Phase Differ- Only Offset: 0 phase angle PC 3.x
ence Size (bits): 8
Sign: U
Unit: Degrees
Lower Limit: 0
Upper Limit: 655.3

167
Addr. Parameter Access Specifications Description Control
43060 Genset L3L1 Read Multiplier: 0.01 Generator set L3L1 voltage% PC 2.x,
Voltage% Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: %
Lower Limit: 0
Upper Limit: 655.3

43061 Genset L3N Read Multiplier: 0.01 Generator set L3N voltage% PC 2.x,
Voltage% Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:

43062 Genset Stand- Read Multiplier: 0.1 KVA rating for the generator set in PC 2.x,
by kVA rating Only Offset: 0 Standby configuration. PC 3.x
Size (bits): 16
Sign: U
Unit: kVA
Lower Limit:
Upper Limit:

43063 Genset Stand- Read Multiplier: 0.1 KW rating for the generator set in PC 2.x,
by kW rating Only Offset: 0 Standby configuration. PC 3.x
Size (bits): 16
Sign: U
Unit: kW
Lower Limit:
Upper Limit:

43064 Genset Stand- Read Multiplier: 1 The value of the generator set PC 2.x,
by Nominal Only Offset: 0 standby nominal current. Dis- PC 3.x
Current Size (bits): 16 played as ”Generator set Standby
Sign: U Rated Current” in HMI
Unit: Amps
Lower Limit:
Upper Limit:

43065 Genset Total Read Multiplier: 1 Generator set total kVAh accu- PC 2.x,
kVAh Only Offset: 0 mulation PC 3.x
Size (bits): 32
Sign: U
Unit: kVAh
Lower Limit:
Upper Limit:

43066 Genset Total Read Multiplier: 1 Generator set total kVAh accu- PC 2.x,
kVAh Only Offset: 0 mulation PC 3.x
Size (bits): 32
Sign: U
Unit: kVAh
Lower Limit:
Upper Limit:

168
Addr. Parameter Access Specifications Description Control
43067 Genset Total Read Multiplier: 0.01 Total KVAR’s per Standby KVA. PC 2.x,
kVARs per Only Offset: 0 PC 3.x
Standby kVA Size (bits): 16
Sign: S
Unit: %
Lower Limit:
Upper Limit:
43100 Genset Bus Av- Read Multiplier : 0.01 Genset Bus average voltage% PC3.x
erage Voltage% Only Offset: 0
Size (bits): 16
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43111 Genset Bus L1 Read Multiplier: 0.01 Generator set Bus L1 power fac- PC 3.x
Power Factor Only Offset: 0 tor
Size (bits): 8
Sign: S
Unit: PF
Lower Limit: −1.28
Upper Limit: 1.22
43112 Genset Bus Read Multiplier: 0.01 Generator set bus L1L2 voltage PC 3.x
L1L2 Phase Only Offset: 0 phase angle
Difference Size (bits): 16
Sign: U
Unit: Degrees
Lower Limit:
Upper Limit:
43113 Genset Bus Read Multiplier : 0.01 Genset Bus L1L2 voltage% PC3.x
L1L2 Voltage% Only Offset: 0
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
43114 Genset Bus Read Multiplier : 0.01 Genset Bus L1N voltage% PC3.x
L1N Voltage% Only Offset: 0
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43125 Genset Bus L2 Read Multiplier: 0.01 Generator set Bus L2 power fac- PC 3.x
Power Factor Only Offset: 0 tor
Size (bits): 8
Sign: S
Unit: PF
Lower Limit: NA
Upper Limit: NA

169
Addr. Parameter Access Specifications Description Control
43126 Genset Bus Read Multiplier: 0.01 Generator set bus L2L3 voltage PC 3.x
L2L3 Phase Only Offset: 0 phase angle
Difference Size (bits): 16
Sign: U
Unit: Degrees
Lower Limit: NA
Upper Limit: NA
43127 Genset Bus Read Multiplier : 0.01 Genset Bus L2L3 voltage% PC3.x
L2L3 Voltage% Only Offset: 0
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43128 Genset Bus Read Multiplier : 0.01 Genset Bus L2N voltage% PC3.x
L2N Voltage% Only Offset: 0
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43139 Genset Bus L3 Read Multiplier: 0.01 Generator set Bus L3 power fac- PC 3.x
Power Factor Only Offset: 0 tor
Size (bits): 8
Sign: S
Unit: PF
Lower Limit: −1.28
Upper Limit: 1.22
43140 Genset Bus Read Multiplier: 0.01 Generator set bus L3L1 voltage PC 3.x
L3L1 Phase Only Offset: 0 phase angle
Difference Size (bits): 16
Sign: U
Unit: Degrees
Lower Limit:
Upper Limit:
43141 Genset Bus Read Multiplier : 0.01 Genset Bus L3L1 voltage% PC3.x
L3L1 Voltage% Only Offset: 0
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA

170
Addr. Parameter Access Specifications Description Control
43142 Genset Bus Read Multiplier : 0.01 Genset Bus L3N voltage% PC3.x
L3N Voltage% Only Offset: 0
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43143 Genset Bus To- Read Multiplier: 1 Generator set bus total kVAh ac- PC 3.x
tal kVAh Only Offset: 0 cumulation
Size (bits): 32
Sign: U
Unit: kVAh
Lower Limit:
Upper Limit:
Default: NA
43144 Genset Bus To- Read Multiplier: 1 Generator set bus total kVAh ac- PC 3.x
tal kVAh Only Offset: 0 cumulation
Size (bits): 32
Sign: U
Unit: kVAh
Lower Limit:
Upper Limit:
43145 Sync Phase Read Multiplier : 0.01 Other meter to genset meter L1 PC3.x
Difference Only Offset: 0 voltage phase angle
Size (bits): 16
Sign: S
Units: deg
Lower Limit: NA
Upper Limit: NA
Default: NA
43146 Paralleling Ap- Read/ 0: None Determines what the function of PC 3.x
plication Write 1: Utility the Other Meter is.
2: Genset Bus
43147 System Total Read Multiplier : 1 Sum of genset bus and utility bus PC3.x
kVA Only Offset: 0 kVA
Size (bits): 16
Sign: U
Units: kVA
Lower Limit: NA
Upper Limit: NA
Default: NA
43148 System Total Read Multiplier : 1 Sum of genset bus and utility bus PC3.x
kVAR Only Offset: 0 kVAR
Size (bits): 16
Sign: S
Units: kVAR
Lower Limit: NA
Upper Limit: NA
Default: NA

171
Addr. Parameter Access Specifications Description Control
43149 System Total Read Multiplier : 1 Sum of genset bus and utility bus PC3.x
kW Only Offset: 0 kW
Size (bits): 16
Sign: U
Units: kW
Lower Limit: NA
Upper Limit: NA
Default: NA
43150 System Total Read Multiplier : 0.01 System total power factor (total- PC3.x
Power Factor Only Offset: 0 ized value of utility bus plus gen-
Size (bits): 8 set bus)
Sign: U
Units: PF
Lower Limit: NA
Upper Limit: NA
Default: NA
43151 Utility Average Read Multiplier : 0.01 Utility average voltage% PC3.x
Voltage% Only Offset: 0
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43162 Utility L1 Power Read Multiplier: 0.01 Utility L1 power factor PC 3.x
Factor Only Offset: 0
Size (bits): 8
Sign: S
Unit: PF
Lower Limit: NA
Upper Limit: NA
43163 Utility L1L2 Read Multiplier: 0.01 Utility L1L2 voltage phase angle PC 3.x
Phase Differ- Only Offset: 0
ence Size (bits): 16
Sign: U
Unit: Degrees
Lower Limit: NA
Upper Limit: NA
43164 Utility L1L2 Read Multiplier : 0.01 Utility L1L2 voltage% PC3.x
Voltage% Only Offset: 0
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA

172
Addr. Parameter Access Specifications Description Control
43165 Utility L1N Volt- Read Multiplier : 0.01 Utility L1N voltage% PC3.X
age% Only Offset: 0
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43176 Utility L2 Power Read Multiplier: 0.01 Utility L2 power factor PC 3.x
Factor Only Offset: 0
Size (bits): 8
Sign: S
Unit: PF
Lower Limit:
Upper Limit:
43177 Utility L2L3 Read Multiplier: 0.01 Utility L2L3 voltage phase angle PC 3.x
Phase Differ- Only Offset: 0
ence Size (bits): 16
Sign: U
Unit: Degrees
Lower Limit:
Upper Limit:
43178 Utility L2L3 Read Multiplier : 0.01 Utility L2L3 voltage% PC3.x
Voltage% Only Offset: 0
Size (bits): 16
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
43179 Utility L2N Volt- Read Multiplier : 0.01 Utility L2N voltage% PC3.x
age% Only Offset: 0
Size (bits): 16
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43190 Utility L3 Power Read Multiplier: 0.01 Utility L3 power factor PC 3.x
Factor Only Offset: 0
Size (bits): 8
Sign: S
Unit: PF
Lower Limit: NA
Upper Limit: NA
43191 Utility L3L1 Read Multiplier: 0.01 Utility L3L1 voltage phase angle PC 3.x
Phase Differ- Only Offset: 0
ence Size (bits): 16
Sign: U
Unit: Degrees
Lower Limit: NA
Upper Limit: NA

173
Addr. Parameter Access Specifications Description Control
43192 Utility L3L1 Read Multiplier : 0.01 Utility L3L1 voltage% PC3.x
Voltage% Only Offset: 0
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43193 Utility L3N Volt- Read Multiplier : 0.01 Utility L3N voltage% PC3.x
age% Only Offset: 0
Size (bits): 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA
43194 Utility Total Read Multiplier: 1 Utility total kVAh accumulation PC 3.x
kVAh Only Offset: 0
Size (bits): 32
Sign: U
Unit: kVAh
Lower Limit:
Upper Limit:
43195 Utility Total Read Multiplier: 1 Utility total kVAh accumulation PC 3.x
kVAh Only Offset: 0
Size (bits): 32
Sign: U
Unit: kVAh
Lower Limit:
Upper Limit:
43196 Exhaust Stack Read Multiplier : 0.1 Monitor point for the Exhaust PC3.x
Temperature Only Offset: 0 Stack Temperature Right Bank re-
Right Bank Size (bits): 16 ceived from ECM
Sign: S
Units: degF
Lower Limit: −459
Upper Limit: 3155
Default: NA
43197 Exhaust Stack Read Multiplier : 0.1 Monitor point for the Exhaust PC3.x
Temperature Only Offset: 0 Stack Temperature Left Bank re-
Left Bank Size (bits): 16 ceived from ECM
Sign: S
Units: degF
Lower Limit: −459
Upper Limit: 3155
Default: NA

174
Addr. Parameter Access Specifications Description Control
43200 Genset Model Read Multiplier: 1 Number indentifying the model of PC 2.x,
Number Only Offset: 0 this generator set. Modbus uses PC 3.x
Size (bits): 168 addresses 43200−43219 for the
Sign: C 20 characters of this string. Uses
Unit: logical numbers 2064 − 2083 to
Lower Limit: −459 hold each of the 20 characters.
Upper Limit: 3155

43201 Genset Model Read Multiplier: 1 Number indentifying the model of PC 2.x,
Number Only Offset: 0 this generator set. Modbus uses PC 3.x
Size (bits): 168 addresses 43200−43219 for the
Sign: C 20 characters of this string. Uses
Unit: logical numbers 2064−2083 to
Lower Limit: hold each of the 20 characters.
Upper Limit:

43202 Genset Model Read Multiplier: 1 Number indentifying the model of PC 2.x,
Number Only Offset: 0 this generator set. Modbus uses PC 3.x
Size (bits): 168 addresses 43200−43219 for the
Sign: C 20 characters of this string. Uses
Unit: logical numbers 2064−2083 to
Lower Limit: hold each of the 20 characters.
Upper Limit:

43203 Genset Model Read Multiplier: 1 Number indentifying the model of PC 2.x,
Number Only Offset: 0 this generator set. Modbus uses PC 3.x
Size (bits): 168 addresses 43200−43219 for the
Sign: C 20 characters of this string. Uses
Unit: logical numbers 2064−2083 to
Lower Limit: hold each of the 20 characters.
Upper Limit:

43204 Genset Model Read Multiplier: 1 Number indentifying the model of PC 2.x,
Number Only Offset: 0 this generator set. Modbus uses PC 3.x
Size (bits): 168 addresses 43200−43219 for the
Sign: C 20 characters of this string. Uses
Unit: logical numbers 2064−2083 to
Lower Limit: hold each of the 20 characters.
Upper Limit:

43205 Genset Model Read Multiplier: 1 Number indentifying the model of PC 2.x,
Number Only Offset: 0 this generator set. Modbus uses PC 3.x
Size (bits): 168 addresses 43200−43219 for the
Sign: C 20 characters of this string. Uses
Unit: logical numbers 2064−2083 to
Lower Limit: hold each of the 20 characters.
Upper Limit:

43206 Genset Model Read Multiplier: 1 Number indentifying the model of PC 2.x,
Number Only Offset: 0 this generator set. Modbus uses PC 3.x
Size (bits): 168 addresses 43200−43219 for the
Sign: C 20 characters of this string. Uses
Unit: logical numbers 2064−2083 to
Lower Limit: hold each of the 20 characters.
Upper Limit:

175
Addr. Parameter Access Specifications Description Control
43207 Genset Model Read Multiplier: 1 Number indentifying the model of PC 2.x,
Number Only Offset: 0 this generator set. Modbus uses PC 3.x
Size (bits): 168 addresses 43200−43219 for the
Sign: C 20 characters of this string. Uses
Unit: logical numbers 2064−2083 to
Lower Limit: hold each of the 20 characters.
Upper Limit:

43208 Genset Model Read Multiplier: 1 Number indentifying the model of PC 2.x,
Number Only Offset: 0 this generator set. Modbus uses PC 3.x
Size (bits): 168 addresses 43200−43219 for the
Sign: C 20 characters of this string. Uses
Unit: logical numbers 2064−2083 to
Lower Limit: hold each of the 20 characters.
Upper Limit:

43209 Genset Model Read Multiplier: 1 Number indentifying the model of PC 2.x,
Number Only Offset: 0 this generator set. Modbus uses PC 3.x
Size (bits): 168 addresses 43200 − 43219 for the
Sign: C 20 characters of this string. Uses
Unit: logical numbers 2064 − 2083 to
Lower Limit: hold each of the 20 characters.
Upper Limit:

43210 Genset Model Read Multiplier: 1 Number indentifying the model of PC 2.x,
Number Only Offset: 0 this generator set. Modbus uses PC 3.x
Size (bits): 168 addresses 43200−43219 for the
Sign: C 20 characters of this string. Uses
Unit: logical numbers 2064−2083 to
Lower Limit: hold each of the 20 characters.
Upper Limit:

43211 Genset Model Read Multiplier: 1 Number indentifying the model of PC 2.x,
Number Only Offset: 0 this generator set. Modbus uses PC 3.x
Size (bits): 168 addresses 43200−43219 for the
Sign: C 20 characters of this string. Uses
Unit: logical numbers 2064−2083 to
Lower Limit: hold each of the 20 characters.
Upper Limit:

43212 Genset Model Read Multiplier: 1 Number indentifying the model of PC 2.x,
Number Only Offset: 0 this generator set. Modbus uses PC 3.x
Size (bits): 168 addresses 43200−43219 for the
Sign: C 20 characters of this string. Uses
Unit: logical numbers 2064−2083 to
Lower Limit: hold each of the 20 characters.
Upper Limit:

43213 Genset Model Read Multiplier: 1 Number indentifying the model of PC 2.x,
Number Only Offset: 0 this generator set. Modbus uses PC 3.x
Size (bits): 168 addresses 43200−43219 for the
Sign: C 20 characters of this string. Uses
Unit: logical numbers 2064−2083 to
Lower Limit: hold each of the 20 characters.
Upper Limit:

176
Addr. Parameter Access Specifications Description Control
43214 Genset Model Read Multiplier: 1 Number indentifying the model of PC 2.x,
Number Only Offset: 0 this generator set. Modbus uses PC 3.x
Size (bits): 168 addresses 43200−43219 for the
Sign: C 20 characters of this string. Uses
Unit: logical numbers 2064−2083 to
Lower Limit: hold each of the 20 characters.
Upper Limit:

43215 Genset Model Read Multiplier: 1 Number indentifying the model of PC 2.x,
Number Only Offset: 0 this generator set. Modbus uses PC 3.x
Size (bits): 168 addresses 43200−43219 for the
Sign: C 20 characters of this string. Uses
Unit: logical numbers 2064−2083 to
Lower Limit: hold each of the 20 characters.
Upper Limit:

43216 Genset Model Read Multiplier: 1 Number indentifying the model of PC 2.x,
Number Only Offset: 0 this generator set. Modbus uses PC 3.x
Size (bits): 168 addresses 43200−43219 for the
Sign: C 20 characters of this string. Uses
Unit: logical numbers 2064−2083 to
Lower Limit: hold each of the 20 characters.
Upper Limit:

43217 Genset Model Read Multiplier: 1 Number indentifying the model of PC 2.x,
Number Only Offset: 0 this generator set. Modbus uses PC 3.x
Size (bits): 168 addresses 43200−43219 for the
Sign: C 20 characters of this string. Uses
Unit: logical numbers 2064−2083 to
Lower Limit: hold each of the 20 characters.
Upper Limit:

43218 Genset Model Read Multiplier: 1 Number indentifying the model of PC 2.x,
Number Only Offset: 0 this generator set. Modbus uses PC 3.x
Size (bits): 168 addresses 43200−43219 for the
Sign: C 20 characters of this string. Uses
Unit: logical numbers 2064−2083 to
Lower Limit: hold each of the 20 characters.
Upper Limit:

43219 Genset Model Read Multiplier: 1 Number indentifying the model of PC 2.x,
Number Only Offset: 0 this generator set. Modbus uses PC 3.x
Size (bits): 168 addresses 43200−43219 for the
Sign: C 20 characters of this string. Uses
Unit: logical numbers 2064−2083 to
Lower Limit: hold each of the 20 characters.
Upper Limit:

43220 Genset Serial Read Multiplier: 1 Serial number of identifying this PC 2.x,
Number Only Offset: 0 generator set. Modbus uses ad- PC 3.x
Size (bits): 168 dresses 43220−43239 for the 20
Sign: C characters of this string. Uses
Unit: logical addresses 2048−6063 to
Lower Limit: store the first 16 characters. The
Upper Limit: last 4 are stored in 691−694.

177
Addr. Parameter Access Specifications Description Control
43221 Genset Serial Read Multiplier: 1 Serial number of identifying this PC 2.x,
Number Only Offset: 0 generator set. Modbus uses ad- PC 3.x
Size (bits): 168 dresses 43220−43239 for the 20
Sign: C characters of this string. Uses
Unit: logical addresses 2048−6063 to
Lower Limit: store the first 16 characters. The
Upper Limit: last 4 are stored in 691−694.

43222 Genset Serial Read Multiplier: 1 Serial number of identifying this PC 2.x,
Number Only Offset: 0 generator set. Modbus uses ad- PC 3.x
Size (bits): 168 dresses 43220−43239 for the 20
Sign: C characters of this string. Uses
Unit: logical addresses 2048 − 6063 to
Lower Limit: store the first 16 characters. The
Upper Limit: last 4 are stored in 691−694.

43223 Genset Serial Read Multiplier: 1 Serial number of identifying this PC 2.x,
Number Only Offset: 0 generator set. Modbus uses ad- PC 3.x
Size (bits): 168 dresses 43220−43239 for the 20
Sign: C characters of this string. Uses
Unit: logical addresses 2048 − 6063 to
Lower Limit: store the first 16 characters. The
Upper Limit: last 4 are stored in 691−694.

43224 Genset Serial Read Multiplier: 1 Serial number of identifying this PC 2.x,
Number Only Offset: 0 generator set. Modbus uses ad- PC 3.x
Size (bits): 168 dresses 43220−43239 for the 20
Sign: C characters of this string. Uses
Unit: logical addresses 2048−6063 to
Lower Limit: store the first 16 characters. The
Upper Limit: last 4 are stored in 691−694.

43225 Genset Serial Read Multiplier: 1 Serial number of identifying this PC 2.x,
Number Only Offset: 0 generator set. Modbus uses ad- PC 3.x
Size (bits): 168 dresses 43220−43239 for the 20
Sign: C characters of this string. Uses
Unit: logical addresses 2048−6063 to
Lower Limit: store the first 16 characters. The
Upper Limit: last 4 are stored in 691−694.

43226 Genset Serial Read Multiplier: 1 Serial number of identifying this PC 2.x,
Number Only Offset: 0 generator set. Modbus uses ad- PC 3.x
Size (bits): 168 dresses 43220−43239 for the 20
Sign: C characters of this string. Uses
Unit: logical addresses 2048−6063 to
Lower Limit: store the first 16 characters. The
Upper Limit: last 4 are stored in 691−694.

43227 Genset Serial Read Multiplier: 1 Serial number of identifying this PC 2.x,
Number Only Offset: 0 generator set. Modbus uses ad- PC 3.x
Size (bits): 168 dresses 43220−43239 for the 20
Sign: C characters of this string. Uses
Unit: logical addresses 2048−6063 to
Lower Limit: store the first 16 characters. The
Upper Limit: last 4 are stored in 691−694.

178
Addr. Parameter Access Specifications Description Control
43228 Genset Serial Read Multiplier: 1 Serial number of identifying this PC 2.x,
Number Only Offset: 0 generator set. Modbus uses ad- PC 3.x
Size (bits): 168 dresses 43220−43239 for the 20
Sign: C characters of this string. Uses
Unit: logical addresses 2048−6063 to
Lower Limit: store the first 16 characters. The
Upper Limit: last 4 are stored in 691−694.

43229 Genset Serial Read Multiplier: 1 Serial number of identifying this PC 2.x,
Number Only Offset: 0 generator set. Modbus uses ad- PC 3.x
Size (bits): 168 dresses 43220−43239 for the 20
Sign: C characters of this string. Uses
Unit: logical addresses 2048−6063 to
Lower Limit: store the first 16 characters. The
Upper Limit: last 4 are stored in 691−694.

43230 Genset Serial Read Multiplier: 1 Serial number of identifying this PC 2.x,
Number Only Offset: 0 generator set. Modbus uses ad- PC 3.x
Size (bits): 168 dresses 43220−43239 for the 20
Sign: C characters of this string. Uses
Unit: logical addresses 2048−6063 to
Lower Limit: store the first 16 characters. The
Upper Limit: last 4 are stored in 691−694.

43231 Genset Serial Read Multiplier: 1 Serial number of identifying this PC 2.x,
Number Only Offset: 0 generator set. Modbus uses ad- PC 3.x
Size (bits): 168 dresses 43220−43239 for the 20
Sign: C characters of this string. Uses
Unit: logical addresses 2048−6063 to
Lower Limit: store the first 16 characters. The
Upper Limit: last 4 are stored in 691−694.

43232 Genset Serial Read Multiplier: 1 Serial number of identifying this PC 2.x,
Number Only Offset: 0 generator set. Modbus uses ad- PC 3.x
Size (bits): 168 dresses 43220−43239 for the 20
Sign: C characters of this string. Uses
Unit: logical addresses 2048−6063 to
Lower Limit: store the first 16 characters. The
Upper Limit: last 4 are stored in 691−694.

43233 Genset Serial Read Multiplier: 1 Serial number of identifying this PC 2.x,
Number Only Offset: 0 generator set. Modbus uses ad- PC 3.x
Size (bits): 168 dresses 43220−43239 for the 20
Sign: C characters of this string. Uses
Unit: logical addresses 2048−6063 to
Lower Limit: store the first 16 characters. The
Upper Limit: last 4 are stored in 691−694.

43234 Genset Serial Read Multiplier: 1 Serial number of identifying this PC 2.x,
Number Only Offset: 0 generator set. Modbus uses ad- PC 3.x
Size (bits): 168 dresses 43220−43239 for the 20
Sign: C characters of this string. Uses
Unit: logical addresses 2048−6063 to
Lower Limit: store the first 16 characters. The
Upper Limit: last 4 are stored in 691−694.

179
Addr. Parameter Access Specifications Description Control
43235 Genset Serial Read Multiplier: 1 Serial number of identifying this PC 2.x,
Number Only Offset: 0 generator set. Modbus uses ad- PC 3.x
Size (bits): 168 dresses 43220−43239 for the 20
Sign: C characters of this string. Uses
Unit: logical addresses 2048−6063 to
Lower Limit: store the first 16 characters. The
Upper Limit: last 4 are stored in 691−694.

43236 Genset Serial Read Multiplier: 1 Serial number of identifying this PC 2.x,
Number Only Offset: 0 generator set. Modbus uses ad- PC 3.x
Size (bits): 168 dresses 43220−43239 for the 20
Sign: C characters of this string. Uses
Unit: logical addresses 2048−6063 to
Lower Limit: store the first 16 characters. The
Upper Limit: last 4 are stored in 691−694.

43237 Genset Serial Read Multiplier: 1 Serial number of identifying this PC 2.x,
Number Only Offset: 0 generator set. Modbus uses ad- PC 3.x
Size (bits): 168 dresses 43220−43239 for the 20
Sign: C characters of this string. Uses
Unit: logical addresses 2048−6063 to
Lower Limit: store the first 16 characters. The
Upper Limit: last 4 are stored in 691−694.

43238 Genset Serial Read Multiplier: 1 Serial number of identifying this PC 2.x,
Number Only Offset: 0 generator set. Modbus uses ad- PC 3.x
Size (bits): 168 dresses 43220−43239 for the 20
Sign: C characters of this string. Uses
Unit: logical addresses 2048−6063 to
Lower Limit: store the first 16 characters. The
Upper Limit: last 4 are stored in 691−694.

43239 Genset Serial Read Multiplier: 1 Serial number of identifying this PC 2.x,
Number Only Offset: 0 generator set. Modbus uses ad- PC 3.x
Size (bits): 168 dresses 43220−43239 for the 20
Sign: C characters of this string. Uses
Unit: logical addresses 2048−6063 to
Lower Limit: store the first 16 characters. The
Upper Limit: last 4 are stored in 691−694.

43240 Alternator Mod- Read Multiplier: 1 Number indentifying this genera- PC 2.x,
el Number Only Offset: 0 tor sets alternator model number. PC 3.x
Size (bits): 168 Modbus uses addresses
Sign: C 43240−43259 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:

43241 Alternator Mod- Read Multiplier: 1 Number indentifying this genera- PC 2.x,
el Number Only Offset: 0 tor sets alternator model number. PC 3.x
Size (bits): 168 Modbus uses addresses
Sign: C 43240−43259 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:

180
Addr. Parameter Access Specifications Description Control
43242 Alternator Mod- Read Multiplier: 1 Number indentifying this genera- PC 2.x,
el Number Only Offset: 0 tor sets alternator model number. PC 3.x
Size (bits): 168 Modbus uses addresses
Sign: C 43240−43259 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43243 Alternator Mod- Read Multiplier: 1 Number indentifying this genera- PC 2.x,
el Number Only Offset: 0 tor sets alternator model number. PC 3.x
Size (bits): 168 Modbus uses addresses
Sign: C 43240−43259 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43244 Alternator Mod- Read Multiplier: 1 Number indentifying this genera- PC 2.x,
el Number Only Offset: 0 tor sets alternator model number. PC 3.x
Size (bits): 168 Modbus uses addresses
Sign: C 43240−43259 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:

43245 Alternator Mod- Read Multiplier: 1 Number indentifying this genera- PC 2.x,
el Number Only Offset: 0 tor sets alternator model number. PC 3.x
Size (bits): 168 Modbus uses addresses
Sign: C 43240−43259 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43246 Alternator Mod- Read Multiplier: 1 Number indentifying this genera- PC 2.x,
el Number Only Offset: 0 tor sets alternator model number. PC 3.x
Size (bits): 168 Modbus uses addresses
Sign: C 43240−43259 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43247 Alternator Mod- Read Multiplier: 1 Number indentifying this genera- PC 2.x,
el Number Only Offset: 0 tor sets alternator model number. PC 3.x
Size (bits): 168 Modbus uses addresses
Sign: C 43240−43259 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43248 Alternator Mod- Read Multiplier: 1 Number indentifying this genera- PC 2.x,
el Number Only Offset: 0 tor sets alternator model number. PC 3.x
Size (bits): 168 Modbus uses addresses
Sign: C 43240−43259 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:

181
Addr. Parameter Access Specifications Description Control
43249 Alternator Mod- Read Multiplier: 1 Number indentifying this genera- PC 2.x,
el Number Only Offset: 0 tor sets alternator model number. PC 3.x
Size (bits): 168 Modbus uses addresses
Sign: C 43240−43259 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43250 Alternator Mod- Read Multiplier: 1 Number indentifying this genera- PC 2.x,
el Number Only Offset: 0 tor sets alternator model number. PC 3.x
Size (bits): 168 Modbus uses addresses
Sign: C 43240−43259 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43251 Alternator Mod- Read Multiplier: 1 Number indentifying this genera- PC 2.x,
el Number Only Offset: 0 tor sets alternator model number. PC 3.x
Size (bits): 168 Modbus uses addresses
Sign: C 43240−43259 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:

43252 Alternator Mod- Read Multiplier: 1 Number indentifying this genera- PC 2.x,
el Number Only Offset: 0 tor sets alternator model number. PC 3.x
Size (bits): 168 Modbus uses addresses
Sign: C 43240−43259 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43253 Alternator Mod- Read Multiplier: 1 Number indentifying this genera- PC 2.x,
el Number Only Offset: 0 tor sets alternator model number. PC 3.x
Size (bits): 168 Modbus uses addresses
Sign: C 43240−43259 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:

43254 Alternator Mod- Read Multiplier: 1 Number indentifying this genera- PC 2.x,
el Number Only Offset: 0 tor sets alternator model number. PC 3.x
Size (bits): 168 Modbus uses addresses
Sign: C 43240−43259 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43255 Alternator Mod- Read Multiplier: 1 Number indentifying this genera- PC 2.x,
el Number Only Offset: 0 tor sets alternator model number. PC 3.x
Size (bits): 168 Modbus uses addresses
Sign: C 43240−43259 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:

182
Addr. Parameter Access Specifications Description Control
43256 Alternator Mod- Read Multiplier: 1 Number indentifying this genera- PC 2.x,
el Number Only Offset: 0 tor sets alternator model number. PC 3.x
Size (bits): 168 Modbus uses addresses
Sign: C 43240−43259 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43257 Alternator Mod- Read Multiplier: 1 Number indentifying this genera- PC 2.x,
el Number Only Offset: 0 tor sets alternator model number. PC 3.x
Size (bits): 168 Modbus uses addresses
Sign: C 43240−43259 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43258 Alternator Mod- Read Multiplier: 1 Number indentifying this genera- PC 2.x,
el Number Only Offset: 0 tor sets alternator model number. PC 3.x
Size (bits): 168 Modbus uses addresses
Sign: C 43240−43259 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43259 Alternator Mod- Read Multiplier: 1 Number indentifying this genera- PC 2.x,
el Number Only Offset: 0 tor sets alternator model number. PC 3.x
Size (bits): 168 Modbus uses addresses
Sign: C 43240−43259 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43260 Alternator Seri- Read Multiplier: 1 Unique number indentifying this PC 2.x,
al Number Only Offset: 0 generator sets alternator serial PC 3.x
Size (bits): 168 number.Modbus uses addresses
Sign: C 43260−43279 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43261 Alternator Seri- Read Multiplier: 1 Unique number indentifying this PC 2.x,
al Number Only Offset: 0 generator sets alternator serial PC 3.x
Size (bits): 168 number.Modbus uses addresses
Sign: C 43260−43279 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:

43262 Alternator Seri- Read Multiplier: 1 Unique number indentifying this PC 2.x,
al Number Only Offset: 0 generator sets alternator serial PC 3.x
Size (bits): 168 number.Modbus uses addresses
Sign: C 43260−43279 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:

183
Addr. Parameter Access Specifications Description Control
43263 Alternator Seri- Read Multiplier: 1 Unique number indentifying this PC 2.x,
al Number Only Offset: 0 generator sets alternator serial PC 3.x
Size (bits): 168 number.Modbus uses addresses
Sign: C 43260−43279 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43264 Alternator Seri- Read Multiplier: 1 Unique number indentifying this PC 2.x,
al Number Only Offset: 0 generator sets alternator serial PC 3.x
Size (bits): 168 number.Modbus uses addresses
Sign: C 43260−43279 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43265 Alternator Seri- Read Multiplier: 1 Unique number indentifying this PC 2.x,
al Number Only Offset: 0 generator sets alternator serial PC 3.x
Size (bits): 168 number.Modbus uses addresses
Sign: C 43260−43279 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43266 Alternator Seri- Read Multiplier: 1 Unique number indentifying this PC 2.x,
al Number Only Offset: 0 generator sets alternator serial PC 3.x
Size (bits): 168 number.Modbus uses addresses
Sign: C 43260−43279 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:

43267 Alternator Seri- Read Multiplier: 1 Unique number indentifying this PC 2.x,
al Number Only Offset: 0 generator sets alternator serial PC 3.x
Size (bits): 168 number.Modbus uses addresses
Sign: C 43260−43279 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43268 Alternator Seri- Read Multiplier: 1 Unique number indentifying this PC 2.x,
al Number Only Offset: 0 generator sets alternator serial PC 3.x
Size (bits): 168 number.Modbus uses addresses
Sign: C 43260−43279 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43269 Alternator Seri- Read Multiplier: 1 Unique number indentifying this PC 2.x,
al Number Only Offset: 0 generator sets alternator serial PC 3.x
Size (bits): 168 number.Modbus uses addresses
Sign: C 43260−43279 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:

184
Addr. Parameter Access Specifications Description Control
43270 Alternator Seri- Read Multiplier: 1 Unique number indentifying this PC 2.x,
al Number Only Offset: 0 generator sets alternator serial PC 3.x
Size (bits): 168 number.Modbus uses addresses
Sign: C 43260−43279 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43271 Alternator Seri- Read Multiplier: 1 Unique number indentifying this PC 2.x,
al Number Only Offset: 0 generator sets alternator serial PC 3.x
Size (bits): 168 number.Modbus uses addresses
Sign: C 43260−43279 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43272 Alternator Seri- Read Multiplier: 1 Unique number indentifying this PC 2.x,
al Number Only Offset: 0 generator sets alternator serial PC 3.x
Size (bits): 168 number.Modbus uses addresses
Sign: C 43260−43279 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43273 Alternator Seri- Read Multiplier: 1 Unique number indentifying this PC 2.x,
al Number Only Offset: 0 generator sets alternator serial PC 3.x
Size (bits): 168 number.Modbus uses addresses
Sign: C 43260−43279 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:

43274 Alternator Seri- Read Multiplier: 1 Unique number indentifying this PC 2.x,
al Number Only Offset: 0 generator sets alternator serial PC 3.x
Size (bits): 168 number.Modbus uses addresses
Sign: C 43260−43279 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43275 Alternator Seri- Read Multiplier: 1 Unique number indentifying this PC 2.x,
al Number Only Offset: 0 generator sets alternator serial PC 3.x
Size (bits): 168 number.Modbus uses addresses
Sign: C 43260−43279 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43276 Alternator Seri- Read Multiplier: 1 Unique number indentifying this PC 2.x,
al Number Only Offset: 0 generator sets alternator serial PC 3.x
Size (bits): 168 number.Modbus uses addresses
Sign: C 43260−43279 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:

185
Addr. Parameter Access Specifications Description Control
43277 Alternator Seri- Read Multiplier: 1 Unique number indentifying this PC 2.x,
al Number Only Offset: 0 generator sets alternator serial PC 3.x
Size (bits): 168 number.Modbus uses addresses
Sign: C 43260−43279 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43278 Alternator Seri- Read Multiplier: 1 Unique number indentifying this PC 2.x,
al Number Only Offset: 0 generator sets alternator serial PC 3.x
Size (bits): 168 number.Modbus uses addresses
Sign: C 43260−43279 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43279 Alternator Seri- Read Multiplier: 1 Unique number indentifying this PC 2.x,
al Number Only Offset: 0 generator sets alternator serial PC 3.x
Size (bits): 168 number.Modbus uses addresses
Sign: C 43260−43279 for the 20 charac-
Unit: ters text string.
Lower Limit:
Upper Limit:
43280 Coolant Level Read 0: Inactive Coolant Level input software state PC 2.x,
Switch Only 1: Active status. Gives software Inactive/ PC 3.x
Active state
43281 Coolant Level/ Read 0: Inactive This is the status of the Configur- PC 2.x,
Configurable Only 1: Active able Input #5. PC 3.x
Input #5 Switch
43283 Fault Reset Read 0: Inactive Fault Reset input software state PC 2.x,
Switch Only 1: Active status. Gives software Inactive/ PC 3.x
Active state
43284 Fault Reset/ Read 0: Inactive This is the status of the Configur- PC 2.x,
Configurable Only 1: Active able Input #10. PC 3.x
Input #10
Switch
43285 Genset CB In- Read 0: Inactive This is the status of the Configur- PC 3.x
hibit/Configur- Only 1: Active able Input #28.
able Input #28
Switch
43286 Genset CB Pos Read 0: Inactive This is the status of the Configur- PC 3.x
B/Configurable Only 1: Active able Input #26.
Input #26
Switch
43287 Genset CB Read 0: Inactive This is the status of the Configur- PC 3.x
Tripped/Confi- Only 1: Active able Input #27.
gurable Input
#27 Switch
43288 Genset CB In- Read 0: Inactive Genset CB Inhibit input software PC3.x
hibit Switch Only 1: Active state status. Gives software Inac-
tive/Active state

186
Addr. Parameter Access Specifications Description Control
43289 Genset CB Pos Read 0: Inactive Genset CB Pos A input software PC3.x
A Switch Only 1: Active state status. Gives software Inac-
tive/Active state
43290 Genset CB Pos Read 0: Inactive Genset CB Pos B input software PC3.x
B Switch Only 1: Active state status. Gives software Inac-
tive/Active state
43291 Genset CB Read 0: Inactive Genset CB Tripped input software PC3.x
Tripped Switch Only 1: Active state status. Gives software Inac-
tive/Active state
43292 Ground Fault Read 0: Inactive Ground Fault Switch function out- PC 2.x,
Switch Only 1: Active put status. Gives software Inac- PC 3.x
tive/Active state
43293 High Alt Temp Read 0: Inactive High Alt Temperature Switch PC 2.x,
Switch Only 1: Active function output status. Gives soft- PC 3.x
ware Inactive/Active state
43295 Load Demand Read 0: Inactive This is the status of the Configur- PC 3.x
Stop/Configur- Only 1: Active able Input #31.
able Input #31
Switch
43296 Local E−stop Read 0: Inactive Monitors the E-Stop switch. PC 2.x,
Switch Only 1: Active PC 3.x
43297 Low Coolant #2 Read 0: Inactive Low Coolant #2 Switch function PC 2.x,
Switch Only 1: Active output status. Gives software In- PC 3.x
active/Active state
43298 Low Engine Read 0: Inactive Low Engine Temperature Switch PC 2.x,
Temperature Only 1: Active function output status. Gives soft- PC 3.x
Switch ware Inactive/Active state
43299 Low Fuel In Read 0: Inactive Low Fuel In Day Tank Switch PC 2.x,
Day Tank Only 1: Active function output status. Gives soft- PC 3.x
Switch ware Inactive/Active state
43300 Genset Bus Read/ 0: Delta Delta or Wye for Utility connection PC 3.x
Delta/Wye Con- Write 1: Wye
nection
43301 Genset Bus Read Multiplier: 1 Generator set Bus nominal volt- PC 3.x
Nominal Volt- Only Offset: 0 age
age Size (bits): 16
Sign: U
Unit: Vac
Lower Limit: 110
Upper Limit: 45000
43302 Genset Delta/ Read 0: Delta Delta or Wye for Generator set PC 2.x,
Wye Connec- Only 1: Wye connection PC 3.x
tion

187
Addr. Parameter Access Specifications Description Control
43303 Genset Nomi- Read Multiplier: 1 Generator set nominal line−line PC 2.x,
nal Voltage Only Offset: 0 voltage PC 3.x
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit: 110
Upper Limit: 45000
43304 Single/3 Phase Read 0: Single Phase Setup mode interlocked. Genera- PC 2.x,
Connection Only 1: Three Phase tor set’s single phase/3 phase PC 3.x
metering setup configuration.
43306 Utility Delta/ Read/ 0: Delta Delta or Wye for Utility connection PC 3.x
Wye Connec- Write 1: Wye
tion
43307 Utility Nominal Read Multiplier: 1 Utility nominal voltage PC 3.x
Voltage Only Offset: 0
Size (bits): 16
Sign: U
Unit: Vac
Lower Limit: 110
Upper Limit: 45000
43309 Overfrequency Read/ 0: DisabledZ Enables over frequency diagnos- PC 2.x,
Enable Write 1: Enabled tic witness test. PC 3.x
43310 Overload Warn- Read/ Multiplier: 1 The time delay until an overload PC 2.x,
ing Set Time Write Offset: 0 condition is reported as a fault PC 3.x
Size (bits): 8
Sign: U
Unit: seconds
Lower Limit: 1
Upper Limit: 120
43311 Overload Warn- Read/ Multiplier: 0.01 Sets the Overload Warning fault PC 2.x,
ing Threshold Write Offset: 0 trip threshold as percentage of PC 3.x
Size (bits): 16 generator set application kW rat-
Sign: U ing.
Unit: %
Lower Limit: 80
Upper Limit: 140
43312 Overload Shut- Read / Multiplier : 1 The time delay until an overload PC3.x
down Set Time Write Offset: 0 condition is reported as Shutdown
Size (bits): 16 fault
Sign: U
Units: Seconds
Lower Limit: 1
Upper Limit: 120
Default: 60

188
Addr. Parameter Access Specifications Description Control
43313 Overload Shut- Read / Multiplier : 0.01 Sets the Overload Shutdown fault PC3.x
down threshold Write Offset: 0 trip threshold as percentage of
Size (bits): 16 genset application kW rating. To
Sign: U disable the Overload shutdown
Units: % fault set the value to 655.35 or
Lower Limit: 70 Not Available.
Upper Limit: 655.35
Default: 655.35
43314 Prelube Func- Read / 0: GCS Selects whether prelube function PC3.x
tion Owner Write 1: ECS is being controlled by GCS or
ECS
43315 Non Lubricated Read / 0: Allow Start Selects whether to allow or block PC3.x
Non−Emergen- Write 1: Block Start genset starting when not lubri-
cy Start cated in case of Non−Emergency
start. Applicable only when Pre-
lube Function Owner = ECS
43338 CAN Failure Read/ Multiplier: 1 Sets the maximum number of PC 2.x,
Retries Write Offset: 0 CAN communication retries PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 10
43339 Auto Sleep En- Read/ 0: Awake in Auto Trim that determines if the control PC 2.x,
able Write 1: Sleep in Auto will stay awake in Auto mode or PC 3.x
Fall asleep in Auto mode.
43340 Max Setup Read/ Multiplier: 1 Max time allowed in Setup Mode. PC 2.x,
Mode Time Write Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: Seconds
Lower Limit: 30
Upper Limit: 3600
43341 Power Down Read/ 0: Disable Trim to enable Sleep Mode PC 2.x,
Mode Enable Write 1: Enable PC 3.x
43342 Power Down Read/ Multiplier: 1 Timer setting for the Power Down PC 2.x,
Mode Time Write Offset: 0 delay feature PC 3.x
Delay Size (bits): 16
Sign: U
Unit: Seconds
Lower Limit: 0
Upper Limit: 600
43343 Setup Mode Read/ 0: Disable Volatile to allow entry into Setup PC 2.x,
Enable Write 1: Enable Mode PC 3.x

189
Addr. Parameter Access Specifications Description Control
43344 Clock Date Read/ Multiplier: 1 Use to set or read the current PC 2.x,
Write Offset: 0 date. PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 31
43345 Clock Hour Read/ Multiplier: 1 Use to set or read the current PC 2.x,
Write Offset: 0 hour. PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 32
43346 Clock Minute Read/ Multiplier: 1 Use to set or read the current PC 2.x,
Write Offset: 0 minute. PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 59
43347 Clock Mode Read/ 0: Normal Use to set the real time clock and PC 2.x,
Write 1: Set Clock save settings. PC 3.x
2: Save Clock
43348 Clock Month Read/ Multiplier: 1 Use to set or read the current PC 2.x,
Write Offset: 0 month. PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 12
43349 Clock Second Read/ Multiplier: 1 Use to set or read the current PC 2.x,
Write Offset: 0 second. PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 59
43350 Clock Year Read/ Multiplier: 1 Use to set or read the current PC 2.x,
Write Offset: 0 year. PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 99

190
Addr. Parameter Access Specifications Description Control
43351 Daylight Sav- Read/ Multiplier: 1 Use to set the hour of the day PC 2.x,
ings End Hour Write Offset: 0 when daylight savings time ends. PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 2
Upper Limit: 19
43352 Daylight Sav- Read/ Multiplier: 1 Use to set the month when day- PC 2.x,
ings End Month Write Offset: 0 light savings time ends. PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 12
43353 Daylight Sav- Read/ 0: First Occurrence Use to set the week of the month PC 2.x,
ings End Week Write 1: Second Occurrence when daylight savings time ends. PC 3.x
Occurrence in 2: Third Occurrence
Month 3: Fourth Occurrence
4: Last Occurrence
43354 Daylight Sav- Read/ 0: Sunday Use to set the day of the week PC 2.x,
ings Start Day Write 1: Monday when daylight savings time starts. PC 3.x
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
43355 Daylight Sav- Read/ Multiplier: 1 Use to set the hour of the day PC 2.x,
ings Start Hour Write Offset: 0 when daylight savings time starts. PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 2
Upper Limit: 19
43356 Daylight Sav- Read/ Multiplier: 1 Use to set the month when day- PC 2.x,
ings Start Write Offset: 0 light savings time starts. PC 3.x
Month Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 12
43357 Daylight Sav- Read/ 0: First Occurrence Use to set the week of the month PC 2.x,
ings Start Week Write 1: Second Occurrence when daylight savings time starts. PC 3.x
Occurrence in 2: Third Occurrence
Month 3: Fourth Occurrence
4: Last Occurrence

191
Addr. Parameter Access Specifications Description Control
43358 Daylight Sav- Read/ Multiplier: 1 Use to set the amount of daylight PC 2.x,
ings Time Ad- Write Offset: 0 savings time adjustment applied. PC 3.x
justment Size (bits): 8
Sign: U
Unit: Minutes
Lower Limit: 0
Upper Limit: 120

43359 Daylight Sav- Read/ 0: Disabled Use to enable the daylight sav- PC 2.x,
ings Time En- Write 1: Enabled ings time feature. PC 3.x
able

43360 Exercise Read/ 0: Disabled Enables the exercise scheduler. PC 2.x,


Scheduler En- Write 1: Enabled PC 3.x
able

43361 Reset Fuel Read/ 0: Inactive The reset trip fuel consumption PC 2.x,
Consumption Write 1: Active command. PC 3.x

43362 Reset Runs Read/ 0: Inactive The reset runs command. PC 2.x,
Write 1: Active PC 3.x

43363 Reset Start At- Read/ 0: Inactive The reset start attempts com- PC 2.x,
tempts Write 1: Active mand. PC 3.x

43364 Scheduler Ex- Read/ Multiplier: 1 Used to select an exception to PC 2.x,


ception Select Write Offset: 0 adjust. PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 6

43365 Scheduler Ex- Read / Multiplier : 1 Used to adjust the date for the se- PC 2.x
ception x Date Write Offset: 0 lected exception. PC3.x
Size (bits): 8
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 31

43366 Scheduler Ex- Read / Multiplier : 1 Used to adjust the length in days PC 2.x
ception x Dura- Write Offset: 0 for the selected exception. PC3.x
tion Days Size (bits): 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 44

43367 Scheduler Ex- Read / Multiplier : 1 Used to adjust the length in hours PC 2.x
ception x Dura- Write Offset: 0 for the selected exception. PC3.x
tion Hours Size (bits): 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 23

192
Addr. Parameter Access Specifications Description Control
43368 Scheduler Ex- Read / Multiplier : 1 Used to adjust the length in min- PC 2.X
ception x Dura- Write Offset: 0 utes for the selected exception. PC3.x
tion Minutes Size (bits): 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 59
Default: 0
43369 Scheduler Ex- Read / 0 : Disable Used to enable or disable the se- PC 2.x
ception x En- Write 1 : Enable lected exception. PC3.x
able
43370 Scheduler Ex- Read / Multiplier : 1 Used to adjust the starting hour PC 2.x
ception x Hour Write Offset: 0 for the selected exception. PC3.x
Size (bits): 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 23
Default: 0
43371 Scheduler Ex- Read / Multiplier : 1 Used to adjust the starting minute PC 2.X
ception x Min- Write Offset: 0 for the selected exception. PC3.X
ute Size (bits): 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 59
Default: 0
43372 Scheduler Ex- Read / Multiplier : 1 Used to adjust the starting month PC 2.X
ception x Month Write Offset: 0 for the selected exception. PC3.X
Size (bits): 8
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 12
Default: 1
43373 Scheduler Ex- Read / 0: Once Only Used to adjust the repeat interval PC 2.X
ception x Re- Write 1: Every Year for the selected exception. PC3.X
peat
43374 Scheduler Pro- Read/ Multiplier: 1 Used to select a program to ad- PC 2.x,
gram Select Write Offset: 0 just. PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 12

193
Addr. Parameter Access Specifications Description Control
43375 Scheduler Pro- Read / Multiplier : 1 Used to adjust the length in hours PC 2.X
gram x Dura- Write Offset: 0 for the selected program. PC3.X
tion Hours Size (bits): 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 23
Default: 0

43376 Scheduler Pro- Read / Multiplier : 1 Used to adjust the length in min- PC 2.X
gram x Dura- Write Offset: 0 utes for the selected program. PC3.X
tion Minutes Size (bits): 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 59
Default: 0

43377 Scheduler Pro- Read/ 0: Disable Used to enable or disable the se- PC 2.x,
gram x Enable Write 1: Enable lected program. PC 3.x

43378 Scheduler Pro- Read / 0: Once Used to adjust the repeat interval PC 2.X
gram x Repeat Write 1: Every Week for the selected program. PC3.x
Interval 2: Every 2 Weeks
3: Every 3 Weeks
4: Every 4 Weeks
5: Every 5 Weeks
6: First Week of Month
7: Second Week of Month
8: Third Week of Month
9: Fourth Week of Month
10: Last Week of Month

43379 Scheduler Pro- Read/ 0: No Load Used to adjust the run mode for PC 3.x
gram x Run Write 1: With Load the selected program.
Mode 2: Extended Parallel

43380 Scheduler Pro- Read / 0: Sunday Used to adjust the start day of the PC 2.x
gram x Start Write 1: Monday week for the selected program. PC3.x
Day 2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday

43381 Scheduler Pro- Read / Multiplier : 1 Used to adjust the start hour for PC 2.x
gram x Start Write Offset: 0 the selected program. PC3.x
Hour Size (bits): 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 23
Default: 0

194
Addr. Parameter Access Specifications Description Control
43382 Scheduler Pro- Read / Multiplier : 1 Used to adjust the start minute for PC 2.x
gram x Start Write Offset: 0 the selected program. PC3.x
Minute Size (bits): 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 59
Default: 0
43383 Daylight Sav- Read/ 0: Sunday Use to set the day of the week PC 2.x,
ings End Day Write 1: Monday when daylight savings time ends. PC 3.x
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
43501 Genset Run Read 0: Emergency Remote Start Source or type of current genset PC 2.x
Type Only 1: Non Emergency Remote Start run (if running) or previous genset PC3.x
2: Load Demand Start run (if stopped).
3: Manual Run
4: Exercise
43502 Idle Rated Read 0: Idle The output command of the Idle/ PC 2.x,
Command Only 1: Rated Rated Logic PC 3.x
43503 Idle Request Read 0: False Indicates a request to go to PC 2.x
Only 1: True manual idle. Manual idle allowed PC3.x
if breaker is open or not con-
trolled
43506 Load Dump Read 0: Inactive Monitors the software command PC 2.x
Command Only 1: Active to the load dump driver output PC3.x
2: Reserved
3: Not Available
43507 Load Dump Read 0: Inactive Monitors the state of the load PC 2.x,
Overload Con- Only 1: Active dump overload detection algo- PC 3.x
dition 2: Reserved rithm
3: Not Available
43508 Load Dump Un- Read 0: Inactive The state of the load dump under- PC 2.x,
derfrequency Only 1: Active frequency detection algorithm PC 3.x
Condition 2: Reserved
3: Not Available
43509 Low Battery Read Multiplier: 0.1 The low battery voltage threshold PC 2.x,
Voltage Run- Only Offset: 0 when the generator set is in rated PC 3.x
ning Threshold Size (bits): 16 mode
Sign: U
Unit: Vdc
Lower Limit:
Upper Limit:

195
Addr. Parameter Access Specifications Description Control
43510 Low Battery Read Multiplier: 0.1 The low battery voltage threshold PC 2.x,
Voltage Only Offset: 0 when the generator set is not in PC 3.x
Stopped Size (bits): 16 rated mode
Threshold Sign: U
Unit: Vdc
Lower Limit:
Upper Limit:

43511 Low Battery Read Multiplier: 0.1 The selection of the running or PC 2.x,
Voltage Thresh- Only Offset: 0 stopped threshold PC 3.x
old Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit:
Upper Limit:

43512 Manual Com- Read 0: Not Manual The output of the Manual Com- PC 2.x
mand Only 1: Manual mand OR logic PC3.x

43513 Manual Com- Read Multiplier : 1 Bitmask to show the inputs to the PC 2.x
mand Inputs Only Offset: 0 Command output which are cur- PC3.x
Size (bits): 8 rently on
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA

43515 Oil Priming Read 0: Inactive The Prelube Driver Command. PC 2.x
Pump Com- Only 1: Active PC3.x
mand 2: Reserved
3: Not Available

43516 Prelube Mode Read 0: Crank After Prelube Set to a required mode based on PC 2.x,
Only 1: Crank With Prelube the type of starting requirement PC 3.x
2: Prelube Only

43517 Prelube State Read 0: Complete The monitor point for the prelube PC 2.x,
Only 1: Armed state. PC 3.x
2: Prelube Output ON
3: Prelube Output OFF
4: Enable Crank

43518 PTC Genset Read 0: Off Current mode for the genset op- PC3.x
Operating Only 1: Manual eration part of the PTC function
Mode 2: Normal
3: Normal Override
4: Test
5: Exercise
6: Utility Fail
7: Extended Parallel

43519 PTC Mode Read 0: Inactive The output of the PTC Mode PC3.x
Switch Com- Only 1: Active Switch Command OR logic
mand 2: Reserved
3: Not Available

196
Addr. Parameter Access Specifications Description Control
43520 PTC Mode Read Multiplier : 1 Bitmask to show the inputs to the PC3.x
Switch Com- Only Offset: 0 Command output which are cur-
mand Inputs Size (bits): 8 rently on.
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
43521 PTC Status Read 0: Off/ Not Enabled Indicates what the current state is PC3.x
Only 1: Manual Mode of PTC control action
2: Normal Utility
3: Retransfer
4: Retransfer Override
5: Emergency Test
6: Normal Test
7: Exercise
8: Utility Failure
9: Extended Parallel
43522 PTC Transfer Read 0: Off Operation mode for the breaker PC3.x
Pair Operating Only 1: Manual pair portion of the PTC function
Mode 2: Normal
3: Normal Override
4: Test
5: Exercise
6: Utility Fail
7: Extended Parallel
43523 Ready to Load Read 0: Inactive The state that the Ready to Load PC 2.x
Command Only 1: Active Driver output is being command- PC3.x
2: Reserved ed to
3: Not Available
43524 Remote Start Read 0: Stop The output of the Remote Start PC 2.x,
Command Only 1: Start Command OR logic PC 3.x
43526 Remote Start Read 0: Off Status of remote start and load PC 2.x
State Only 1: Remote Start demand stop inputs PC3.x
2: Load Demand Stop
3: Load Demand Start
43527 RMS Regula- Read Multiplier : 0.01 The RMS voltage (or current) er- PC 2.x
tion Error Only Offset: 0 ror at the AVR PC3.x
Size (bits): 16
Sign: S
Units: %
Lower Limit: −100
Upper Limit: 100
Default: NA
43528 Run Command Read 0: Off The signal that is commanding a PC 2.x
Only 1: Run change to the run mode PC3.x
43529 Run Relay Read 0: Inactive The status of relay command PC 2.x
Command Only 1: Active when genset is in frequency and PC3.x
rated mode.

197
Addr. Parameter Access Specifications Description Control
43530 Speed and Volt- Read 0: Inactive Monitor point for the command PC 3.x
age Bias Relay Only 1: Active which closes the on−board relay
Command enabling the voltage and speed
bias outputs.
43531 Speed Bias Read Multiplier : 0.01 Indicates amount of speed bias PC3.x
Command Only Offset: 0 offset GCS is commanding to
Size (bits): 16 ECS governor or external gover-
Sign: S nor
Units: %
Lower Limit: 0
Upper Limit: NA
Default: NA
43533 Start Count- Read Multiplier: 1 Time remaining until start is initi- PC 2.x,
down Only Offset: 0 ated PC 3.x
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 300
Default: NA
43536 Start Type Read 0: Emergency The output of the Start Type PC 2.x
Command Only 1: Non Emergency Command OR logic PC3.x
43537 Start Type Read Multiplier : 1 Bitmask to show the inputs to the PC 2.x
Command In- Only Offset: 0 Command output which are cur- PC3.x
puts Size (bits): 8 rently on
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
43538 Starter Com- Read 0: Inactive State of hardware output. PC 2.x,
mand Only 1: Active PC 3.x
2: Reserved
3: Not Available
43539 Stop Count- Read Multiplier: 1 Time remaining until generator PC 2.x,
down Only Offset: 0 set stops PC 3.x
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 5000
43540 Switch Panel Read 0: None Status of run and exercise com- PC 2.x
Run Request Only 1: Manual mands from display panel PC3.x
2: Exercise

198
Addr. Parameter Access Specifications Description Control
43542 Target Voltage Read Multiplier : 0.01 The target voltage without ramp- PC 2.x
Only Offset: 0 ing and torque match voltage rol- PC3.x
Size (bits): 16 loff effects
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 150
Default: NA
43543 Time At No Read Multiplier: 1 Amount of time the generator set PC 2.x,
Load Only Offset: 0 has run at no load PC 3.x
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 600
Default: NA
43544 Time at Rated Read Multiplier: 1 Amount of time spend in Rated PC 2.x,
Cooldown Only Offset: 0 Cooldown PC 3.x
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 5000
43546 Voltage Bias Read Multiplier : 0.01 Indicates amount of voltage bias PC3.x
Command Only Offset: 0 offset GCS is commanding to an
Size (bits): 16 external regulator
Sign: S
Units: %
Lower Limit: 0
Upper Limit: NA
Default: NA
43547 Voltage Set- Read Multiplier: 0.01 The voltage setpoint command PC 2.x,
point Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 150
43550 Weak Battery Read Multiplier: 0.1 Monitor point for the weak battery PC 2.x,
Threshold Only Offset: 0 voltage threshold PC 3.x
Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: 6
Upper Limit: 16

199
Addr. Parameter Access Specifications Description Control
43551 Weak Battery Read/ Multiplier: 1 The time delay until a weak bat- PC 2.x,
Voltage Set Write Offset: 0 tery condition is reported as a PC 3.x
Time Size (bits): 16 fault
Sign: U
Unit: seconds
Lower Limit: 1
Upper Limit: 5
43552 Paralleling Volt- Read Multiplier : 0.01 Voltage offset to voltage regulator PC 2.x
age Ref Offset Only Offset: 0 for paralleling function PC3.x
Size (bits): 16
Sign: S
Units: %
Lower Limit: NA
Upper Limit: NA
43553 Synchronizer Read 0: Synchronizer Off Indicates whether synchronizer is PC 3.x
Status Only 1: Synchronizer On on or off
43554 Active Transi- Read Multiplier: 0.1 Countdown value of the active PC 3.x
tion Timer Only Offset: 0 transition timer
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit:
Upper Limit:
43555 Active Transi- Read 0: None Indicates the active transition type PC 3.x
tion Type Only 1: Programmed Transition for PTC
2: Transfer
3: Retransfer
4: Max Parallel
43556 Arbitration Read 0: Off Indicates current arbitration state PC3.x
State Only 1: Arbitrate0
2: Winner
3: Arbitrate1
4: Sleep
43557 Arbitration Tim- Read Multiplier : 1 Arbitration loop countdown timer PC3.x
er Only Offset: 0
Size (bits): 16
Sign: U
Units: msec
Lower Limit: NA
Upper Limit: NA
Default: NA
43567 Genset Current Read 0: Unknown Indicates genset breaker position PC3.x
Based Breaker Only 1: Closed based on current
Position
43558 ES State Read 0: Standby Internal paralleling status variable PC 3.x
Only 1: Dead Bus
2: Synchronize
3: Load Share
4: Load Govern

200
Addr. Parameter Access Specifications Description Control
43559 First Start State Read 0: First Start Not Allowed Indicates status of the first start PC3.x
Only 1: First Start Requested system
2: First Start Permitted
43560 Genset CB Read 0: Inactive Generator set cb close command PC 3.x
Close Com- Only 1: Active status
mand
43561 Genset CB Fail Read 0: Inactive Status of gen fail to close lockout PC3.x
To Close Lock- Only 1: Active function
out
43562 Genset CB Read 0: Open Indicates generator set breaker PC 3.x
Position Status Only 1: Closed position
2: Not Available
43563 Genset Avail- Read 0: Not Available Indicates status of the generator PC 3.x
ability Status Only 1: Available set source
2: Unknown
43564 Bus Status Read 0: Unavailable Indicates status of the bus PC 3.x
Only 1: Dead
2: Live
43565 Genset CB In- Read 0: Inactive Generator set cb inhibit command PC 3.x
hibit Command Only
1: Active
43566 Genset CB Read 0: Inactive Generator set cb tripped com- PC 3.x
Tripped Com- Only 1: Active mand
mand
43568 Genset Fre- Read Multiplier: 0.1 Indicates the lower drop−out PC 3.x
quency Lower Only Offset: 0 threshold in Hz for generator set
Drop−Out Size (bits): 16 frequency sensor
Threshold Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
43569 Genset Fre- Read Multiplier: 0.1 Indicates the lower pick−up PC 3.x
quency Lower Only Offset: 0 threshold in Hz for generator set
Pick−Up Size (bits): 16 frequency sensor
Threshold Sign: U
Unit: Hz
Lower Limit:
Upper Limit
43570 Genset Fre- Read 0: Unknown Indicates generator set frequency PC 3.x
quency Sensor Only 1: Picked Up sensor status
Status 2: Dropped Out
43571 Genset Fre- Read Multiplier: 0.1 Indicates the upper drop−out PC 3.x
quency Upper Only Offset: 0 threshold in Hz for generator set
Drop−Out Size (bits): 16 frequency sensor
Threshold Sign: U
Unit: Hz
Lower Limit:
Upper Limit

201
Addr. Parameter Access Specifications Description Control
43572 Genset Fre- Read Multiplier: 0.1 Indicates the upper pick−up PC 3.x
quency Upper Only Offset: 0 threshold in Hz for generator set
Pick−Up Size (bits): 16 frequency sensor
Threshold Sign: U
Unit: Hz
Lower Limit:
Upper Limit
43573 Genset Loss of Read 0: Unknown Indicates generator set loss of PC 3.x
Phase Sensor Only 1: Picked Up phase sensor status
Status 2: Dropped Out
43574 Genset Over- Read Multiplier: 1 Indicates the drop−out threshold PC 3.x
voltage Drop− Only Offset: 0 in volts for generator set over
Out Threshold Size (bits): 16 voltage sensor
Sign: U
Unit: Vac
Lower Limit:
Upper Limit
43575 Genset Over- Read Multiplier: 1 Indicates the pick−up threshold in PC 3.x
voltage Pick− Only Offset: 0 volts for generator set over volt-
Up Threshold Size (bits): 16 age sensor
Sign: U
Unit: Vac
Lower Limit:
Upper Limit
43576 Genset Over- Read 0: Unknown Indicates generator set over volt- PC 3.x
voltage Sensor Only 1: Picked Up age sensor status
Status 2: Dropped Out
43577 Genset Phase Read 0: Unknown Indicates generator set phase PC 3.x
Rotation Sen- Only 1: Picked Up rotation sensor status
sor Status 2: Dropped Out
43578 Genset Under- Read Multiplier: 1 Indicates the drop−out threshold PC 3.x
voltage Drop− Only Offset: 0 in volts for generator set under
Out Threshold Size (bits): 16 voltage sensor
Sign: U
Unit: Vac
Lower Limit:
Upper Limit
43579 Genset Under- Read Multiplier: 1 Indicates the pick−up threshold in PC 3.x
voltage Pick− Only Offset: 0 volts for generator set under volt-
Up Threshold Size (bits): 16 age sensor
Sign: U
Unit: Vac
Lower Limit:
Upper Limit
43580 Genset Under- Read 0: Unknown Indicates generator set under PC 3.x
voltage Sensor Only 1: Picked Up voltage sensor status
Status 2: Dropped Out
43581 Master First Read 0: Inactive Status of the first start output PC3.x
Start Output Only 1: Active command
Command

202
Addr. Parameter Access Specifications Description Control
43582 Maximum Par- Read Multiplier : 0.1 Countdown value of the maxi- PC3.x
allel Timer Only Offset: 0 mum parallel timer
Size (bits): 16
Sign: U
Units: Seconds
Lower Limit: NA
Upper Limit: NA
Default: NA
43583 Maximum Par- Read 0: Not Timing Indicates status of the maximum PC3.x
allel Timer Sta- Only 1: Timing parallel timer
tus 2: Expired
43584 Paralleling Read 0: Isochronous Indicates which speed control al- PC 2.x,
Speed Control Only 1: Droop gorithm is in effect PC 3.x
Mode 2: Synchronize
3: Load Share
4: Load Govern
43585 Paralleling Volt- Read 0: Isochronous Indicates which voltage control PC 2.x,
age Control Only 1: Droop algorithm is in effect PC 3.x
Mode 2: Synchronize
3: Load Share
4: Load Govern
43586 Programmed Read Multiplier : 0.1 Countdown value of the pro- PC3.x
Transition Tim- Only COffset: 0 grammed transition timer
er Size (bits): 16
Sign: U
Units: Seconds
Lower Limit: NA
Upper Limit: NA
Default: NA
43587 Programmed Read 0: Not Timing Indicates status of the pro- PC3.x
Transition Tim- Only 1: Timing grammed transition timer
er Status 2: Expired
43588 PTC Enable Read 0: Disable Indicates if PTC functions are PC3.x
Status Only 1: Enable running
43589 PTC Operating Read 0: Open Transition Indicates the transition type cur- PC 3.x
Transition Type Only 1: Hard Closed Transition rently in effect
2: Soft Closed Transition
43590 PTC State Read 0: PTC Not Enabled Indicates the connected state of PC 3.x
Only 1: No Source Connected the Power Transfer Control
2: Utility Connected
3: Genset Connected
4: Paralleled
43591 Retransfer Tim- Read Multipli Countdown value of the retransfer PC3.x
er Only Offset: 0 timer
Size (bits): 16
Sign: U
Units: Seconds
Lower Limit: NA
Upper Limit: NA
Default: NA

203
Addr. Parameter Access Specifications Description Control
43592 Retransfer Tim- Read 0: Not Timing Indicates status of the retransfer PC3.x
er Status Only 1: Timing timer
2: Expired
43593 Speed Droop Read 0: Inactive Command value of speed droop PC 2.x
Enable Com- Only 1: Active enable PC3.x
mand
43594 Speed Droop Read 0: Droop Disabled Indicates whether or not speed PC 2.x
Status Only 1: Droop Enabled droop is in effect PC3.x
43595 Transfer Timer Read Multiplier : 0.1 Countdown value of the transfer PC3.x
Only Offset: 0 timer
Size (bits): 16
Sign: U
Units: Seconds
Lower Limit: NA
Upper Limit: NA
Default: NA
43596 Transfer Timer Read 0: Not Timing Indicates status of the transfer PC3.x
Status Only 1: Timing timer
2: Expired
43597 Utility CB Close Read 0: Inactive Utility cb close command status PC 3.x
Command Only 1: Active
43598 Utility CB Open Read 0: Inactive Utility cb open command status PC 3.x
Command Only 1: Active
43599 Utility CB Posi- Read 0: Open Indicates utility breaker position PC 3.x
tion Status Only 1: Closed
2: Not Available
43600 Load Govern Read/ 0: Genset kW Use to select how generator set PC 3.x
kW Method Write 1: Genset kW w/Utility Constraint kW output will be controlled when
2: Utility kW paralleled to utility.
43608 Configurable Read/ Multiplier: 1 The event code for this output. PC 2.x,
Output #1 Write Offset: 0 PC 3.x
Event Code Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43610 Configurable Read/ Multiplier: 1 The event code for this output. PC 2.x,
Output #2 Write Offset: 0 PC 3.x
Event Code Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

204
Addr. Parameter Access Specifications Description Control
43613 Configurable Read/ Multiplier: 1 The event code for this output. PC 3.x
Output #20 Write Offset: 0
Event Code Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43616 Configurable Read/ Multiplier: 1 The event code for this output. PC 3.x
Output #21 Write Offset: 0
Event Code Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43619 Configurable Read/ Multiplier: 1 The event code for this output. PC 3.x
Output #22 Write Offset: 0
Event Code Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43622 Configurable Read/ Multiplier: 1 The event code for this output. PC 2.x,
Output #3 Write Offset: 0 PC 3.x
Event Code Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43625 Configurable Read/ Multiplier: 1 The event code for this output. PC 2.x,
Output #4 Write Offset: 0 PC 3.x
Event Code Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43641 Delayed Shut- Read/ 0: Disabled Enables the Delayed Shutdown PC 2.x,
down Enable Write 1: Enabled feature. PC 3.x
43642 Delayed Shut- Read/ Multiplier: 0.1 Sets the shutdown fault delayed PC 2.x,
down Time Write Offset: 0 time delay for the Delayed Shut- PC 3.x
Delay Size (bits): 16 down feature.
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 3
43643 Remote Fault Read/ 0: Disable Trim to enable Remote Fault Re- PC 2.x,
Reset Enabled Write 1: Enable set. Can only reset Warning PC 3.x
Faults

205
Addr. Parameter Access Specifications Description Control
43644 Fail To Shut- Read/ Multiplier: 1 Trim to set the time for a shut- PC 2.x,
down Delay Write Offset: 0 down fault to be active and the PC 3.x
Size (bits): 16 generator set not shutting down
Sign: U before the Fail to Shutdown fault
Unit: seconds occurs.
Lower Limit: 0
Upper Limit: 30
43645 LCL Detection Read/ 0: None Sets low coolant level fault re- PC 2.x,
Response Write 1: Warning sponse to None, Warning, or PC 3.x
2: Shutdown Shutdown.
43646 LCT Warning Read/ Multiplier: 1 Sets time to clear the low coolant PC 2.x,
Clear Time Write Offset: 0 temperature fault. PC 3.x
Size (bits): 8
Sign: U
Unit: Minutes
Lower Limit: 0
Upper Limit: 30
43647 LCT Warning Read/ Multiplier: 1 Sets time to set the low coolant PC 2.x,
Set Time Write Offset: 0 temperature fault. PC 3.x
Size (bits): 8
Sign: U
Unit: Minutes
Lower Limit: 0
Upper Limit: 30
43648 LCT Warning Read/ Multiplier: 1 Sets threshold for the low coolant PC 2.x,
Threshold Write Offset: 0 temperature fault warning. PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −20
Upper Limit: 100
43649 V/Hz Knee Fre- Read/ Multiplier: 0.1 The voltage will roll off (decrease) PC 2.x,
quency Write Offset: 0 proportionally to the V/Hz setup, PC 3.x
Size (bits): 16 once the frequency drops below
Sign: U the set point in the V/Hz Knee
Unit: Hz Frequency. This allows the gener-
Lower Limit: 0 ator set to recover faster when
Upper Limit: 10 the frequency drops.
43650 V/Hz Rolloff Read/ Multiplier: 0.1 The amount of voltage roll off PC 2.x,
Slope Write Offset: 0 when the frequency is below the PC 3.x
Size (bits): 16 knee frequency
Sign: U
Unit: % / Hz
Lower Limit: 0
Upper Limit: 10

206
Addr. Parameter Access Specifications Description Control
43651 12 V High Bat- Read Multiplier: 0.1 Sets 12V high battery voltage PC 2.x,
tery Voltage Only Offset: 0 fault threshold. PC 3.x
Threshold Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: 14
Upper Limit: 17

43652 12 V Low Bat- Read Multiplier: 0.1 Sets 12V low battery voltage fault PC 2.x,
tery Voltage Only Offset: 0 threshold for generator set opera- PC 3.x
Running Size (bits): 16 tion while in rated mode
Threshold Sign: U
Unit: Vdc
Lower Limit: 12
Upper Limit: 16

43653 12 V Low Bat- Read Multiplier: 0.1 Sets 12V low battery voltage fault PC 2.x,
tery Voltage Only Offset: 0 threshold for generator set opera- PC 3.x
Stopped Size (bits): 16 tion in all modes except rated
Threshold Sign: U
Unit: Vdc
Lower Limit: 11
Upper Limit: 13

43654 12 V Weak Bat- Read/ Multiplier: 0.1 Sets 12V weak battery voltage PC 2.x,
tery Voltage Write Offset: 0 fault threshold PC 3.x
Threshold Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: 6
Upper Limit: 10

43655 24 V High Bat- Read Multiplier: 0.1 Sets 24V high battery voltage PC 2.x,
tery Voltage Only Offset: 0 fault threshold PC 3.x
Threshold Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: 28
Upper Limit: 34

43656 24 V Low Bat- Read Multiplier: 0.1 Sets 24V low battery voltage fault PC 2.x,
tery Voltage Only Offset: 0 threshold for generator set opera- PC 3.x
Running Size (bits): 16 tion while in rated mode
Threshold Sign: U
Unit: Vdc
Lower Limit: 24
Upper Limit: 28

43657 24 V Low Bat- Read Multiplier: 0.1 Sets 24V low battery voltage fault PC 2.x,
tery Voltage Only Offset: 0 threshold for generator set opera- PC 3.x
Stopped Size (bits): 16 tion in all modes except rated
Threshold Sign: U
Unit: Vdc
Lower Limit: 24
Upper Limit: 26

207
Addr. Parameter Access Specifications Description Control
43658 24 V Weak Bat- Read/ Multiplier: 0.1 Sets 24V weak battery voltage PC 2.x,
tery Voltage Write Offset: 0 fault threshold PC 3.x
Threshold Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: 12
Upper Limit: 16
43659 Adjustable Read/ Multiplier: 0.01 Sets the RPM/Hz conversion fac- PC 2.x,
Freq/Speed Write Offset: 0 tor when the Freq to Speed Gain PC 3.x
Gain Size (bits): 16 Select trim is set to this trim
Sign: U
Unit: RPM/Hz
Lower Limit: 12
Upper Limit: 240
43660 Alternate Fre- Read 0: 50 Hz Sets the generator set nominal PC 2.x,
quency Switch Only 1: 60 Hz frequency. PC 3.x
43661 AVR Gain Ad- Read/ Multiplier: 0.01 A trim that allows the user to PC 2.x,
just Trim Write Offset: 0 modify the overall gains of the PC 3.x
Size (bits): 16 AVR.
Sign: U
Unit:
Lower Limit: 0.05
Upper Limit: 10
43662 Charging Alter- Read/ Multiplier: 0.1 Sets the time delay for the charg- PC 2.x,
nator Fault Write Offset: 0 ing alt failure fault PC 3.x
Time Delay Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 2
Upper Limit: 300
43663 Continuous Read/ Multiplier: 1 Sets the maximum amount of PC 2.x,
Crank Engage Write Offset: 0 time to engage the starter when PC 3.x
Time Size (bits): 16 using the continuous cranking
Sign: U method
Unit: seconds
Lower Limit: 40
Upper Limit: 100
43664 Controlled Read/ Multiplier: 1 Delay allowed for a shutdown PC 3.x
Shutdown Ad- Write Offset: 0 with cooldown fault prior to shut-
vance Notice Size (bits): 16 ting down the generator set
Delay Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 300

208
Addr. Parameter Access Specifications Description Control
43665 Crank Attempts Read/ Multiplier: 1 Sets the maximum number of PC 2.x,
Write Offset: 0 times to engage the starter when PC 3.x
Size (bits): 16 attempting to start engine using
Sign: U the cycle cranking method
Unit: seconds
Lower Limit: 1
Upper Limit: 7
43666 Cycle / Cont Read 0: Cycle Selects whether to use continu- PC 2.x,
Crank Select Only 1: Continuous ous cranking or cycle cranking PC 3.x
when attempting to start engine

43667 Cycle Crank Read/ Multiplier: 1 Sets the maximum amount of PC 2.x,
Engage Time Write Offset: 0 time to engage the starter during PC 3.x
Size (bits): 16 a single crank attempt when us-
Sign: U ing the cycle cranking method
Unit: seconds
Lower Limit: 2
Upper Limit: 20
43668 Cycle Crank Read/ Multiplier: 1 Sets the amount of time to wait PC 2.x,
Rest Time Write Offset: 0 between crank attempts PC 3.x
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 7
Upper Limit: 40
43669 Delayed Off Read/ Multiplier: 0.1 Time delay between when the PC 2.x,
FSO Relay Write Offset: 0 Delayed Off Command turns off PC 3.x
Time Size (bits): 16 and Run Command turns off
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 120
43670 External AVR Read / Multiplier : 0.1 Sets the knee frequency for the PC 2.x
Knee Frequen- Write Offset: 0 fixed knee freq logic. PC3.x
cy Size (bits): 16
Sign: U
Units: Hz
Lower Limit: 0
Upper Limit: 10
Default: NA
43671 External Bias Read/ 0: Disabled Enables the external bias (speed PC 3.x
Commands En- Write 1: Enabled and voltage commands) to the
able hardware outputs.

43672 Frequency Ad- Read/ Multiplier: 0.01 A method of adding in a frequen- PC 2.x,
just Write Offset: 0 cy offset to the base frequency PC 3.x
Size (bits): 16 subject to high and low limit cal-
Sign: S ibrations
Units: Hz
Lower Limit: −6
Upper Limit: 6

209
Addr. Parameter Access Specifications Description Control
43673 Genset Exer- Read/ Multiplier: 0.1 Sets the total exercise time not PC 2.x,
cise Time Write Offset: 0 including warmup at idle or idle PC 3.x
Size (bits): 16 cooldown time
Sign: U
Unit: hours
Lower Limit: 0
Upper Limit: 25

43674 Governor Gain Read Multiplier: 0.01 A trim that allows the user to PC 2.x,
Adjust Only Offset: 0 modify the overall gain of the gov- PC 3.x
Size (bits): 16 ernor
Sign: U
Unit:
Lower Limit: 0.05
Upper Limit: 15

43675 High Battery Read Multiplier: 1 The time delay until a high battery PC 2.x,
Voltage Set Only Offset: 0 voltage condition is reported as a PC 3.x
Time Size (bits): 16 fault.
Sign: U
Unit: seconds
Lower Limit: 2
Upper Limit: 60

43676 High Battery Read Multiplier: 0.1 The high battery voltage thresh- PC 2.x,
Voltage Thresh- Only Offset: 0 old PC 3.x
old Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit:
Upper Limit:

43677 Idle Cooldown Read/ Multiplier: 0.25 Sets time to run at idle before PC 2.x,
Time Write Offset: 0 shutting down generator set on PC 3.x
Size (bits): 16 normal stops
Sign: U
Unit: minutes
Lower Limit: 0
Upper Limit: 60

43678 Idle Speed Read Multiplier: 1 Sets the speed at which the en- PC 2.x,
Only Offset: 0 gine will idle subject to high and PC 3.x
Size (bits): 16 low limit calibrations
Sign: U
Unit: RPM
Lower Limit: 700
Upper Limit: 1100

43679 Idle to Rated Read/ Multiplier: 0.1 The time over which the speed PC 2.x,
Ramp Time Write Offset: 0 reference is to ramp from idle PC 3.x
Size (bits): 16 speed to rated speed
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 30

210
Addr. Parameter Access Specifications Description Control
43680 Idle Warmup Read/ Multiplier: 1 Coolant temperature threshold to PC 2.x,
Coolant Temp Write Offset: 0 end idle warmup time PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −40
Upper Limit: 300
43681 Idle Warmup Read/ Multiplier: 1 Sets maximum idle warmup time. PC 2.x,
Time Write Offset: 0 Warmup time may be less if cool- PC 3.x
Size (bits): 16 ant temperature exceeds thresh-
Sign: U old
Unit: seconds
Lower Limit: 0
Upper Limit: 3600
43682 Load Dump Ac- Read/ 0: Overload Enables the load dump output as PC 2.x,
tivation Method Write 1: Underfrequency a function of the overload and un- PC 3.x
2: Overload or Underfrequency derfrequency conditions
3: Disabled
43683 Load Dump Read/ Multiplier: 1 The time delay until the load PC 2.x,
Overload Set Write Offset: 0 dump overload condition is set PC 3.x
Time Size (bits): 16 active
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 120
43684 Load Dump Read/ Multiplier: 1 The load dump overload thresh- PC 2.x,
Overload Write Offset: 0 old as a percentage of the gener- PC 3.x
Threshold Size (bits): 16 ator set application rating
Sign: U
Unit: %
Lower Limit: 80
Upper Limit: 140
43685 Load Dump Un- Read/ Multiplier: 1 The frequency amount which the PC 2.x,
derfrequency Write Offset: 0 load dump underfrequency PC 3.x
Offset Size (bits): 16 threshold is below the final fre-
Sign: S quency reference
Unit: Hz
Lower Limit: 0
Upper Limit: 10
43686 Load Dump Un- Read/ Multiplier: 1 The time delay until the load PC 2.x,
derfrequency Write Offset: 0 dump underfrequency condition is PC 3.x
Set Time Size (bits): 16 set active
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 20

211
Addr. Parameter Access Specifications Description Control
43687 Load Dump Un- Read Multiplier: 0.1 The frequency trip threshold for PC 2.x,
derfrequency Only Offset: 0 the load dump underfrequency PC 3.x
Threshold Size (bits): 16 condition
Sign: U
Unit: Hz
Lower Limit: 0
Upper Limit: 90
43688 Low Battery Read Multiplier: 1 The time delay until a low battery PC 2.x,
Voltage Set Only Offset: 0 voltage condition is reported as a PC 3.x
Time Size (bits): 16 fault
Sign: U
Unit: seconds
Lower Limit: 2
Upper Limit: 60
43689 Low Fuel in Read/ Multiplier: 1 Low Fuel in Day Tank Fault time PC 2.x,
Day Tank Time Write Offset: 0 delay from switch input. PC 3.x
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 20
43690 Low Fuel Set/ Read/ Multiplier: 1 A trim that sets the delay time for PC 2.x,
Clear Time Write Offset: 0 generating the inactive and active PC 3.x
Size (bits): 16 faults.
Sign: U
Unit: seconds
Lower Limit: 2
Upper Limit: 60
43691 Manual War- Read/ 0: Normal Use to command idle speed or to PC 2.x,
mup Bypass Write 1: Bypass Warmup bypass idle warmup during a PC 3.x
manual run
43692 Max Idle Time Read/ Multiplier: 0.1 Sets the fault time for the Too PC 2.x,
Write Offset: 0 Long in Idle fault. PC 3.x
Size (bits): 16
Sign: U
Unit: minutes
Lower Limit: 0
Upper Limit: 20
43693 Nominal Battery Read 0: 12V Selects the generator set’s nomi- PC 2.x,
Voltage Only 1: 24V nal battery operating voltage PC 3.x
43694 Prelube Cycle Read/ 0: Disabled Enables Or Disables the cyclic PC 2.x,
Enable Write 1: Enabled mode of prelube operation PC 3.x
43695 Prelube Cycle Read/ Multiplier: 0.1 Sets the period of the Prelube PC 2.x,
Time Write Offset: 0 Cycle Iteration PC 3.x
Size (bits): 16
Sign: U
Unit: hours
Lower Limit: 1
Upper Limit: 1000

212
Addr. Parameter Access Specifications Description Control
43696 Prelube Func- Read/ 0: Disabled Selects whether the Prelube func- PC 2.x,
tion Enable Write 1: Enabled tion is enabled or disabled. This is PC 3.x
Setup mode interlocked
43697 Prelube Oil Read/ Multiplier: 0.1 The oil pressure value which PC 2.x,
Pressure Write Offset: 0 when reached the prelube driver PC 3.x
Threshold Size (bits): 16 will turn off
Sign: U
Unit: psig
Lower Limit: 0
Upper Limit: 10
43698 Prelube Time- Read/ Multiplier: 0.1 Sets the maximum time for which PC 2.x,
out Period Write Offset: 0 the Prelube Driver will Remain PC 3.x
Size (bits): 16 ON
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 30
43699 Rated to Idle Read/ Multiplier: 0.1 The time over which the speed PC 2.x,
Ramp Time Write Offset: 0 reference is to ramp from rated PC 3.x
Size (bits): 16 speed to idle speed
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 30
43700 Utility Availabil- Read 0: Not Available Indicates status of the utility PC 3.x
ity Status Only 1: Available source
2: Unknown
43701 Utility CB Inhibit Read 0: Inactive Utility cb inhibit command PC 3.x
Command Only 1: Active
43702 Utility CB Read 0: Inactive Utility cb tripped command PC 3.x
Tripped Com- Only 1: Active
mand
43703 Utility Current Read 0: Unknown Indicates utility breaker position PC 3.x
Based Breaker Only 1: Closed based on current
Position
43704 Utility Frequen- Read Multiplier: 0.1 Indicates the lower drop−out PC 3.x
cy Lower Drop− Only Offset: 0 threshold in Hz for utility frequen-
Out Threshold Size (bits): 16 cy sensor
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:
43705 Utility Frequen- Read Multiplier: 0.1 Indicates the lower pick−up PC 3.x
cy Lower Pick− Only Offset: 0 threshold in Hz for utility frequen-
Up Threshold Size (bits): 16 cy sensor
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:

213
Addr. Parameter Access Specifications Description Control
43706 Utility Frequen- Read 0: Unknown Indicates utility frequency sensor PC 3.x
cy Sensor Sta- Only 1: Picked Up status
tus 2: Dropped Out

43707 Utility Frequen- Read Multiplier: 0.1 Indicates the upper drop−out PC 3.x
cy Upper Drop− Only Offset: 0 threshold in Hz for utility frequen-
Out Threshold Size (bits): 16 cy sensor
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:

43708 Utility Frequen- Read Multiplier: 0.1 Indicates the upper pick−up PC 3.x
cy Upper Pick− Only Offset: 0 threshold in Hz for utility frequen-
Up Threshold Size (bits): 16 cy sensor
Sign: U
Unit: Hz
Lower Limit:
Upper Limit:

43709 Utility Loss of Read 0: Unknown Indicates utility loss of phase sen- PC 3.x
Phase Sensor Only 1: Picked Up sor status
Status 2: Dropped Out

43710 Utility Overvol- Read Multiplier: 1 Indicates the drop−out threshold PC 3.x
tage Drop−Out Only Offset: 0 in volts for utility over voltage sen-
Threshold Size (bits): 16 sor
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

43711 Utility Overvol- Read Multiplier: 1 Indicates the pick−up threshold in PC 3.x
tage Pick−Up Only Offset: 0 volts for utility over voltage sensor
Threshold Size (bits): 16
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

43712 Utility Overvol- Read 0: Unknown Indicates utility over voltage sen- PC 3.x
tage Sensor Only 1: Picked Up sor status
Status 2: Dropped Out

43713 Utility Phase Read 0: Unknown Indicates utility phase rotation PC 3.x
Rotation Sen- Only 1: Picked Up sensor status
sor Status 2: Dropped Out

43714 Utility Undervol- Read Multiplier: 1 Indicates the drop−out threshold PC 3.x
tage Drop−Out Only Offset: 0 in volts for utility under voltage
Threshold Size (bits): 16 sensor
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:

214
Addr. Parameter Access Specifications Description Control
43715 Utility Undervol- Read Multiplier: 1 Indicates the pick−up threshold in PC 3.x
tage Pick−Up Only Offset: 0 volts for utility under voltage sen-
Threshold Size (bits): 16 sor
Sign: U
Unit: Vac
Lower Limit:
Upper Limit:
43716 Utility Undervol- Read 0: Unknown Indicates utility under voltage PC 3.x
tage Sensor Only 1: Picked Up sensor status
Status 2: Dropped Out

43717 Voltage Droop Read 0: Inactive Command value of voltage droop PC 2.x
Enable Com- Only 1: Active enable PC3.x
mand

43719 Alternator Tem- Read Multiplier: 1 Monitor point for the Alternator PC 2.x,
perature 1 Only Offset: 0 Temperature 1 input from the Aux PC 3.x
(Aux101) Size (bits): 16 101 I/O module.
Sign: S
Unit: degF
Lower Limit: −32767
Upper Limit: 32762
43720 Alternator Tem- Read Multiplier: 1 Monitor point for the Alternator PC 2.x,
perature 2 Only Offset: 0 Temperature 2 input from the Aux PC 3.x
(Aux101) Size (bits): 16 101 I/O module.
Sign: S
Unit: degF
Lower Limit: −32767
Upper Limit: 32762
43721 Alternator Tem- Read Multiplier: 1 Monitor point for the Alternator PC 2.x,
perature 3 Only Offset: 0 Temperature 3 input from the Aux PC 3.x
(Aux101) Size (bits): 16 101 I/O module.
Sign: S
Unit: degF
Lower Limit: −32767
Upper Limit: 32762
43722 Ambient Tem- Read Multiplier: 1 Monitor point for the Ambient PC 2.x,
perature Only Offset: 0 Temperature input from the Aux PC 3.x
(Aux101) Size (bits): 16 101 I/O module.
Sign: S
Unit: degF
Lower Limit: −32767
Upper Limit: 32762
43723 Aux101 0 Ana- Read Multiplier: 0.01 Monitor point for the module 0 PC 2.x,
log Input 1 Volt- Only Offset: 0 analog input 1 in volts PC 3.x
age Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit: −500
Upper Limit: 500

215
Addr. Parameter Access Specifications Description Control
43724 Aux101 0 Ana- Read Multiplier: 0.01 Monitor point for the module 0 PC 2.x,
log Input 2 Volt- Only Offset: 0 analog input 2 in volts PC 3.x
age Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit: −500
Upper Limit: 500

43725 Aux101 0 Ana- Read Multiplier: 0.01 Monitor point for the module 0 PC 2.x,
log Input 3 Volt- Only Offset: 0 analog input 3 in volts PC 3.x
age Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:

43726 Aux101 0 Ana- Read Multiplier: 0.01 Monitor point for the module 0 PC 2.x,
log Input 4 Volt- Only Offset: 0 analog input 4 in volts PC 3.x
age Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:

43727 Aux101 0 Ana- Read Multiplier: 0.01 Monitor point for the module 0 PC 2.x,
log Input 5 Volt- Only Offset: 0 analog input 5 in volts PC 3.x
age Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:

43728 Aux101 0 Ana- Read Multiplier: 0.01 Monitor point for the module 0 PC 2.x,
log Input 6 Volt- Only Offset: 0 analog input 6 in volts PC 3.x
age Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:

43729 Aux101 0 Ana- Read Multiplier: 0.01 Monitor point for the module 0 PC 2.x,
log Input 7 Volt- Only Offset: 0 analog input 7 in volts PC 3.x
age Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:

43730 Aux101 0 Ana- Read Multiplier: 0.01 Monitor point for the module 0 PC 2.x,
log Input 8 Volt- Only Offset: 0 analog input 8 in volts PC 3.x
age Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:

216
Addr. Parameter Access Specifications Description Control
43731 Aux101 1 Ana- Read Multiplier: 0.01 Monitor point for the module 1 PC 2.x,
log Input 1 Volt- Only Offset: 0 analog input 1 in volts PC 3.x
age Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit: −500
Upper Limit: 500

43732 Aux101 1 Ana- Read Multiplier: 0.01 Monitor point for the module 1 PC 2.x,
log Input 2 Volt- Only Offset: 0 analog input 2 in volts PC 3.x
age Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit: −500
Upper Limit: 500

43733 Aux101 1 Ana- Read Multiplier: 0.01 Monitor point for the module 1 PC 2.x,
log Input 3 Volt- Only Offset: 0 analog input 3 in volts PC 3.x
age Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:

43734 Aux101 1 Ana- Read Multiplier: 0.01 Monitor point for the module 1 PC 2.x,
log Input 4 Volt- Only Offset: 0 analog input 4 in volts PC 3.x
age Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:

43735 Aux101 1 Ana- Read Multiplier: 0.01 Monitor point for the module 1 PC 2.x,
log Input 5 Volt- Only Offset: 0 analog input 5 in volts PC 3.x
age Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:

43736 Aux101 1 Ana- Read Multiplier: 0.01 Monitor point for the module 1 PC 2.x,
log Input 6 Volt- Only Offset: 0 analog input 6 in volts PC 3.x
age Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:

43737 Aux101 1 Ana- Read Multiplier: 0.01 Monitor point for the module 1 PC 2.x,
log Input 7 Volt- Only Offset: 0 analog input 7 in volts PC 3.x
age Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:

217
Addr. Parameter Access Specifications Description Control
43738 Aux101 1 Ana- Read Multiplier: 0.01 Monitor point for the module 1 PC 2.x,
log Input 8 Volt- Only Offset: 0 analog input 8 in volts PC 3.x
age Size (bits): 16
Sign: S
Unit: Vdc
Lower Limit:
Upper Limit:
43739 Battery Charger Read 0: Inactive Monitor point for the battery char- PC 2.x,
AC Failure Only 1: Active ger failure input from the PC 3.x
(HMI113) PCCNET annunciator.
43740 Drive End Bear- Read Multiplier: 1 Monitor point for the Drive End PC 2.x,
ing Tempera- Only Offset: 0 Bearing Temperature input from PC 3.x
ture (Aux101) Size (bits): 16 the I/O module.
Sign: S
Unit: degF
Lower Limit: −32767
Upper Limit: 32762
43741 Exhaust Stack Read Multiplier: 1 Monitor point for the Exhaust PC 2.x,
Temperature 1 Only Offset: 0 Stack Temperature1 input from PC 3.x
(Aux101) Size (bits): 16 the I/O module.
Sign: S
Unit: degF
Lower Limit: −32767
Upper Limit: 32762
43742 Exhaust Stack Read Multiplier: 1 Monitor point for the Exhaust PC 2.x,
Temperature 2 Only Offset: 0 Stack Temperature2 input from PC 3.x
(Aux101) Size (bits): 16 the I/O module.
Sign: S
Unit: degF
Lower Limit: −32767
Upper Limit: 32762
43745 Fuel Level % Read Multiplier: 0.1 Monitor point for the % fuel level PC 2.x,
(PCCnet) Only Offset: 0 input from the I/O module. PC 3.x
Size (bits): 16
Sign: S
Unit: %
Lower Limit:
Upper Limit:
43746 Fuel Level Read Multiplier: 1 Monitor point for the fuel level (in PC 2.x,
(PCCnet) Only Offset: 0 gallons) input from the I/O mod- PC 3.x
Size (bits): 16 ule.
Sign: S
Unit:
Lower Limit:
Upper Limit:
43747 HMI113 Fault 1 Read 0: Inactive Monitor point for input #1 from the PC 2.x,
Status Only 1: Active annunciator. PC 3.x
43748 HMI113 Fault 2 Read 0: Inactive Monitor point for input #2 from the PC 2.x,
Status Only 1: Active annunciator. PC 3.x

218
Addr. Parameter Access Specifications Description Control
43749 HMI113 Fault 3 Read 0: Inactive Monitor point for the input #3 from PC 2.x,
Status Only 1: Active the annunciator. PC 3.x
43750 Intake Manifold Read Multiplier: 1 Monitor point for the Intake Man- PC 2.x,
Temperature 1 Only Offset: 0 ifold Temperature 1 input from the PC 3.x
(Aux101) Size (bits): 16 I/O module.
Sign: S
Unit: degF
Lower Limit: −32768
Upper Limit: 32762
43751 Low Coolant Read 0: Inactive Monitor point for the Low Coolant PC 2.x,
Level (HMI113) Only 1: Active Level input from the PCCnet an- PC 3.x
nunciator.
43752 Low Fuel Level Read 0: Inactive Monitor point for the Low Fuel PC 2.x,
(HMI113) Only 1: Active Level input from the PCCnet an- PC 3.x
nunciator.
43755 Non−Drive End Read Multiplier: 1 Monitor point for the Non−Drive PC 2.x,
Bearing Tem- Only Offset: 0 End Bearing Temperature input PC 3.x
perature Size (bits): 16 from the I/O module.
(Aux101) Sign: S
Unit: degF
Lower Limit: −32768
Upper Limit: 32762
43756 Number of Read Multiplier: 1 Used to monitor the amount of PC 2.x,
Connected Bar- Only Offset: 0 connected bargraph modules. PC 3.x
graph Modules Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255
43757 Oil Tempera- Read Multiplier: 1 Monitor point for the Oil Tempera- PC 2.x,
ture (Aux101) Only Offset: 0 ture input from the I/O Module. PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −65534
Upper Limit: 65535
43758 Modbus Bus Read Multiplier: 1 Modbus bus message count PC 2.x,
Message Count Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit
43759 Modbus CRC Read Multiplier: 1 Modbus CRC errors count PC 2.x,
Errors Count Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit

219
Addr. Parameter Access Specifications Description Control
43760 Modbus Excep- Read Multiplier: 1 Modbus exception count PC 2.x,
tion Count Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit
43761 Modbus No Re- Read Multiplier: 1 Modbus no response count PC 2.x,
sponse Count Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit
43762 Modbus Slave Read Multiplier: 1 Modbus slave message count PC 2.x,
Message Count Only Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit
43763 Frequency Read Multiplier: 0.001 frequency match error value used PC 3.x
Match Error Only Offset: 0 by frequency match PI loop
Size (bits): 16
Sign: S
Unit: Hz
Lower Limit:
Upper Limit
43764 Frequency Read Multiplier : 0.001 Offset to the frequency match er- PC3.x
Match Offset Only Offset: 0 ror calculation
Size (bits): 16
Sign: S
Unit: Hz
Lower Limit:
Upper Limit
Default: NA
43765 Load Dump Re- Read 0: Inactive Indicates a load dump is desired PC 2.x
quest Only 1: Active due to load exceeding derate lev- PC3.x
el.
43766 Load Govern Read 0: Not Applicable Indicates status of load govern PC3.x
kVAR Ramp Only 1: Ramp Load kVAR ramping control
State 2: Track Target
3: Ramp Unload
4: Ramp Unload Complete

220
Addr. Parameter Access Specifications Description Control
43767 Load Govern Read Multiplier: 0.01 Indicates the final target setpoint PC 3.x
kVAR Target Only Offset: 0 for generator set kVAR output
Size (bits): 16 when paralleled to utility
Sign: S
Unit: %
Lower Limit:
Upper Limit
Default: NA
43768 Load Govern Read 0: Not Applicable Indicates status of load govern PC3.x
kW Ramp State Only 1: Ramp Load kW ramping control
2: Track Target
3: Ramp Unload
4: Ramp Unload Complete
43769 Load Govern Read Multiplier: 0.01 Indicates the final target setpoint PC 3.x
kW Target Only Offset: 0 for generator set kW output when
Size (bits): 16 paralleled to utility
Sign: S
Unit: %
Lower Limit:
Upper Limit
Default: NA
43770 Permissive Read 0: Not1: Allowed Allowed Indicates when permissive sync PC 3.x
Close Allowed Only check conditions have been met

43772 Permissive Read Multiplier : 0.01 Phase error signal for the permis- PC3.x
Phase Match Only Offset: 0 sive sync check algorithm
Error Size (bits): 16
Sign: S
Units: deg
Lower Limit: NA
Upper Limit: NA
Default: NA
43773 Phase Match Read Multiplier: 0.01 Phase error signal for the syn- PC 3.x
Error Only Offset: 0 chronizer control algorithm
Size (bits): 16
Sign: S
Units: deg
Lower Limit:
Upper Limit:
43774 Ramp Load/Un- Read 0: Load Indicates overall status of ramp PC3.x
load Command Only 1: Unload load unload inputs

43775 Utility Unloaded Read 0: Not Available Indicates unloaded status of the PC3.x
Status Only 1: Not Unloaded utility source
2: Unloaded
43776 Genset CB Read 0: Inactive Indictes if the output’s status is In- PC3.x
Close Status Only 1: Active active or Active

43777 Start Type/Con- Read 0: Inactive This is the status of the Configur- PC 2.x,
figurable Input Only 1: Active able Input #11. PC 3.x
#11 Switch

221
Addr. Parameter Access Specifications Description Control
43778 Scheduler Run Read 0: Off Indicates the current run com- PC 2.x,
Command Only 1: No Load mand coming from the scheduler. PC 3.x
2: With Load
3: Extended Parallel
43785 Start Attempts Read Multiplier: 1 Number of start attempts since PC 2.x,
Since Reset Only Offset: 0 the last reset. PC 3.x
Size (bits): 32
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967290
43786 Start Attempts Read Multiplier: 1 Number of start attempts since PC 2.x,
Since Reset Only Offset: 0 the last reset. PC 3.x
Size (bits): 32
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967290
43787 Total Start At- Read Multiplier: 1 Total number of start attempts. PC 2.x,
tempts Only Offset: 0 PC 3.x
Size (bits): 32
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967290
43788 Total Start At- Read Multiplier: 1 Total number of start attempts. PC 2.x,
tempts Only Offset: 0 PC 3.x
Size (bits): 32
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 4294967290
43789 Backup Start Read 0: Inactive This is the status of the Configur- PC 3.x
Disconnect/ Only 1: Active able Input #33.
Configurable
Input #33
Switch
43790 Backup Start Read 0: Inactive Status of the Backup Start Dis- PC3.x
Disconnnect Only 1: Active connect Switch Input
Switch
43791 Battery Charger Read 0: Inactive Battery Charger Failed Switch PC 2.x,
Failed Switch Only 1: Active function output status; gives soft- PC 3.x
ware Inactive/Active state
43792 Battle Short Read 0: Inactive Battle Short Switch function out- PC 2.x,
Switch Only 1: Active put status (Active or Inactive). PC 3.x

43793 Configurable Read 0: Inactive Configurable Input #1 input soft- PC 2.x,


Input #1 Switch Only 1: Active ware state status. Gives software PC 3.x
Inactive/Active state

222
Addr. Parameter Access Specifications Description Control
43794 Configurable Read 0: Inactive Configurable Input #2 input soft- PC 2.x,
Input #2 Switch Only 1: Active ware state status. Gives software PC 3.x
Inactive/Active state
43795 Configurable Read 0: Inactive Configurable Input #13 input soft- PC 2.x,
Input #13 Only 1: Active ware state status. Gives software PC 3.x
Switch Inactive/Active state
43796 Genset CB Read 0: Inactive generator set cb open command PC 3.x
Open Com- Only 1: Active status
mand
43797 Number of Read Multiplier : 1 Used to monitor the amount of PC 2.x
Connected Bat- Only Offset: 0 connected Battery Chargers. PC3.x
tery Chargers Size (bits): 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43800 Rated Cool- Read/ Multiplier: 1 Minimum time to spend at rated PC 2.x,
down Time Write Offset: 0 speed less than 10% load before PC 3.x
Size (bits): 16 normal shutdown is allowed
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 600
43801 Rated to Idle Read/ Multiplier: 0.1 Sets the delay time for transition- PC 2.x,
Transition Write Offset: 0 ing from Rated to Idle speed. 0 PC 3.x
Delay Size (bits): 16 seconds = feature is disabled.
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 10
43802 Rupture Basin Read/ Multiplier: 0.1 Rupture Basin fault time delay PC 2.x,
Time Write Offset: 0 PC 3.x
Size (bits): 16
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 20
43803 Start Time Read/ Multiplier: 1 Sets the time to wait from receiv- PC 2.x,
Delay Write Offset: 0 ing a valid remote start signal un- PC 3.x
Size (bits): 16 til starting the generator set
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 300

223
Addr. Parameter Access Specifications Description Control
43804 Starting to Read/ Multiplier: 0.1 The time over which the speed PC 2.x,
Rated Ramp Write Offset: 0 reference is to ramp from starting PC 3.x
Time Size (bits): 16 speed to rated speed
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 300
43805 Time Delay to Read/ Multiplier: 1 Sets time to run at rated speed PC 2.x,
Stop Write Offset: 0 before going to cooldown at idle. PC 3.x
Size (bits): 16 Does not apply to manual runs
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 600
43806 Voltage Adjust Read/ Multiplier: 0.01 A trim that allows the user to add/ PC 2.x,
Write Offset: 0 subtract an offset to the nominal PC 3.x
Size (bits): 16 voltage when calculating the volt-
Sign: S age setpoint
Unit: %
Lower Limit: −5
Upper Limit: 5
43807 Voltage Ramp Read/ Multiplier: 0.01 The time period over which the PC 2.x,
Time Write Offset: 0 voltage setpoint command should PC 3.x
Size (bits): 16 rise from 0% to the target voltage
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 5
43808 Commit to Read 0: Not Committed PTC − Indicates if system is com- PC 3.x
Transfer State Only 1: Committed mitted to transferring to generator
set
43810 Battle Short Read/ 0: Inactive Trim to enable Battle Short via PC 2.x,
Switch (Mod- Write 1: Committed Modbus. PC 3.x
bus)
43811 Exercise Switch Read/ 0: Inactive Modbus exercise switch PC 2.x,
(Modbus) Write 1: Active PC 3.x
43813 Extended Par- Read/ 0: Inactive Modbus extended parallel switch PC 2.x,
allel Switch Write 1: Active PC 3.x
(Modbus)
43814 PTC Mode Read/ 0: Inactive Modbus PTC Mode switch PC 3.x
Switch (Mod- Write 1: Active
bus)
43815 Start Type Read/ 0: Emergency Modbus start type switch PC 2.x,
(Modbus) Write 1: Non Emergency PC 3.x
43816 Sync Disable Read / 0: Inactive Use to turn off synchronizer for PC3.x
Write 1: Active testing purposes

224
Addr. Parameter Access Specifications Description Control
43817 Genset Circuit Read/ 0: Inactive Identical operation to the confi- PC 3.x
Breaker Inhibit Write 1: Active gurable input of the same name.
Opens genset breaker if closed;
inhibits closure if genset breaker
is open.
43818 Isolated Bus Read/ 0: Constant Sets the speed control method for PC 2.x,
Speed Control Write 1: Droop isolated bus paralleling. Parame- PC 3.x
Method ter is also known as Load Share
Speed Droop Control Method
43819 Isolated Bus Read/ 0: Constant Sets the voltage control method PC 2.x,
Voltage Control Write 1: Droop for isolated bus paralleling. PC 3.x
Method
43820 Maximum Par- Read/ Multiplier: 0.1 Sets the maximum time that the PC 3.x
allel Time Write Offset: 0 generator set can remain paral-
(TDMP) Size (bits): 16 leled to the utility during closed
Sign: U transition transfers.
Unit: seconds
Lower Limit: 0
Upper Limit: 1800
43821 Programmed Read/ Multiplier: 0.1 Sets the time delay from when PC 3.x
Transition Write Offset: 0 one source opens until the other
Delay (TDPT) Size (bits): 16 closes during open transition
Sign: U transfers.
Unit: seconds
Lower Limit: 0
Upper Limit: 60
43822 Retransfer Read/ Multiplier: 0.1 Sets the amount of time that the PC 3.x
Delay (TDEN) Write Offset: 0 utility source must be available
Size (bits): 16 before the control will retransfer
Sign: U to that source.
Unit: seconds
Lower Limit: 0
Upper Limit: 1800
43823 Synchronizer Read/ 0: Phase Match Sets the speed control method for PC 3.x
Speed Control Write 1: Slip Frequency synchronizing.
Method 2: External
43824 Synchronizer Read/ 0: Voltage Match Sets the voltage control method PC 3.x
Voltage Control Write 1: External for synchronizing.
Method
43825 Transfer Delay Read/ Multiplier: 0.1 Sets the amount of time that the PC 3.x
(TDNE) Write Offset: 0 generator set source must be
Size (bits): 16 available before the control will
Sign: U transfer to that source.
Unit: seconds
Lower Limit: 0
Upper Limit: 120
43826 Transition Type Read/ 0: Open Transition Sets the load transfer transition PC 3.x
Write 1: Hard Closed Transition type for use when Generator set
2: Soft Closed Transition Application Type = Power Trans-
fer Control.

225
Addr. Parameter Access Specifications Description Control
43827 Retransfer In- Read/ 0: Inactive Identical operation to the confi- PC 3.x
hibit Write 1: Active gurable input of the same name.
Normally inhibits retransfer to the
utility; under some conditions it is
ignored; not the same as utility
circuit breaker inhibit.
43828 Utility Circuit Read/ 0: Inactive Identical operation to the confi- PC 3.x
Breaker Inhibit Write 1: Active gurable input of the same name.
Opens utility main if closed; inhib-
its closure if utility main is open.

43829 Utility Parallel Read/ 0: Load Govern Sets the speed control method for PC 3.x
Speed Control Write 1: Droop utility paralleling.
Method
43830 Utility Parallel Read/ 0: Load Govern Sets the voltage control method PC 3.x
Voltage Control Write 1: Droop for utility paralleling.
Method 2: Load Govern with Droop Feed
Forward
43831 Aux101 Device Read/ 0: Critical Device Response Selects the generator set reaction PC 2.x,
0 PCCnet Fail- Write 1: Non−Critical Device Response to a loss of a Device 0 I/O module PC 3.x
ure Response as critical (Shutdown) or non−crit-
Type ical (Warning).
43832 Aux101 Device Read/ 0: Critical Device Response Selects the generator set reaction PC 2.x,
1 PCCnet Fail- Write 1: Non−Critical Device Response to a loss of a Device 1 I/O module PC 3.x
ure Response as critical (Shutdown) or non−crit-
Type ical (Warning).
43834 HMI113 Annun- Read/ 0: Critical Device Response Selects the generator set reaction PC 2.x,
ciator PCCnet Write 1: Non−Critical Device Response to a loss of an annunciator as crit- PC 3.x
Failure Re- ical or non−critical. Selecting criti-
sponse Type cal will cause a shutdown when
the annunciator looses commu-
nication.
43835 HMI1xx Read / 0: Critical Device Response Selects the genset reaction to a PC 2.x
PCCnet Failure Write 1: Non−Critical Device Response loss of an HMI1xx Operator Panel PC3.x
Response Type as critical or non−critical. A criti-
cal response will shutdown the
genset when PCCnet commu-
nication is lost.
43836 HMI220 Read/ 0: Critical Device Response Selects the generator set reaction PC 2.x,
PCCnet Failure Write 1: Non−Critical Device Response to a loss of an HMI220 operator PC 3.x
Response Type panel as critical or non−critical.. A
critical response will shutdown
the generator set when PCCnet
communication is lost.
43837 HMI320 Read/ 0: Critical Device Response Selects the generator set reaction PC 2.x,
PCCnet Failure Write 1: Non−Critical Device Response to a loss of an HMI320 operator PC 3.x
Response Type panel as critical or non−critical.. A
critical response will shutdown
the generator set when PCCnet
communication is lost.

226
Addr. Parameter Access Specifications Description Control
43838 HMI4xx Read / 0: Critical Device Response Selects the genset reaction to a PC 2.x
PCCnet Failure Write 1: Non−Critical Device Response loss of an HMI4xx Operator Panel PC3.x
Response Type as critical or non−critical.. A criti-
cal response will shutdown the
genset when PCCnet commu-
nication is lost.
43839 PCCnet Device Read/ Multiplier: 1 Selects the time allowed for ar- PC 2.x,
Failure Time Write Offset: 0 bitration to occur before a PC 3.x
Delay Size (bits): 16 PCCnet failure fault is generated.
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 250
43840 Test With Load Read/ 0: Disabled Use to choose whether a test is PC 3.x
Enable Write 1: Enabled with load or without load.
43841 Transfer Inhibit Read/ 0: Inactive Identical operation to the confi- PC 3.x
Write 1: Active gurable input of the same name.
Normally inhibits transfer to the
genset; under some conditions it
is ignored; not the same as gen-
set circuit breaker inhibit.
43842 Commit to Read/ 0: Utility Disconnect PTC − sets point at which system PC 3.x
Transfer Meth- Write 1: Genset Start commits to transfer to generator
od 2: No Commit set
43843 Commit to Read/ Multiplier: 1 PTC − sets time system will wait PC 3.x
Transfer Time- Write Offset: 0 for generator set when committed
out Size (bits): 16 to transfer
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 3200
43844 Commit to Read Multiplier: 0.05 PTC − remaining time system to PC 3.x
Transfer Timer Only Offset: 0 wait for generator set when com-
Size (bits): 16 mitted to transfer
Sign: U
Unit: sec
Lower Limit:
Upper Limit:
43845 Modbus Failure Read/ Multiplier: 1 Time delay before the control acti- PC 2.x,
Time Delay Write Offset: 0 vates the Modbus failure fault af- PC 3.x
Size (bits): 16 ter the master is sensed as no
Sign: U longer present.
Unit: seconds
Lower Limit: 0
Upper Limit: 10
43846 Modbus Com- Read/ 0: Do Nothing When set to Reset Commands PC 2.x,
munications Write 1: Reset Commands will reset the Modbus control log- PC 3.x
Lost Response icals to an inactive state when
Method Modbus communications are lost

227
Addr. Parameter Access Specifications Description Control
43847 Modbus Clear Read/ 0: Do Nothing Resets all Modbus counters, in- PC 2.x,
Counters Write 1: Clear Counters cluding J14 if applicable. PC 3.x
43848 Controlled Read/ Multiplier: 1 maximum ramp unload time dur- PC 3.x
Shutdown Max Write Offset: 0 ing a shutdown with cooldown
Ramp Unload Size (bits): 16
Time Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 300
43849 Genset kVAR Read/ Multiplier: 1 Sets the generator set load gov- PC 3.x
Setpoint Write Offset: 0 ern kVAR base load internal oper-
Size (bits): 16 ating setpoint in units of kVAR.
Sign: S Requires that Load Govern kVAR
Unit: kVAR Setpoint Source = Internal and
Lower Limit: 0 Load Govern kVAR Method =
Upper Limit: 20000 generator set kVAR.
43850 Genset kVAR Read/ Multiplier: 0.01 Sets the generator set load gov- PC 3.x
Setpoint Per- Write Offset: 0 ern kVAR base load internal oper-
cent Size (bits): 16 ating setpoint in % of standby
Sign: S kVA rating. Requires that Load
Unit: % Govern kVAR Setpoint Source =
Lower Limit: 0 Internal and Load Govern kVAR
Upper Limit: 60 Method = generator set kVAR.
43851 Genset kW Set- Read/ Multiplier: 1 Sets the generator set load gov- PC 3.x
point Write Offset: 0 ern kW base load internal operat-
Size (bits): 16 ing setpoint in units of kW. Re-
Sign: S quires that Load Govern kW Set-
Unit: kW point Source = Internal and Load
Lower Limit: 0 Govern kW Method = Genset kW.
Upper Limit: 20000
43852 Genset kW Set- Read/ Multiplier: 0.01 Sets the generator set load gov- PC 3.x
point Percent Write Offset: 0 ern kW base load internal operat-
Size (bits): 16 ing setpoint in % of standby rat-
Sign: S ing. Requires that Load Govern
Unit: % kW Setpoint Source = Internal
Lower Limit: 0 and Load Govern kW Method =
Upper Limit: 100 Genset kW.
43853 Genset Power Read/ Multiplier: 0.01 Sets the load govern setpoint for PC 3.x
Factor Setpoint Write Offset: 0 generator set power factor con-
Size (bits): 8 trol. Requires that Load Govern
Sign: S kVAR Setpoint Source = Internal
Unit: PF and Load Govern kVAR Method =
Lower Limit: 0.7 Genset Power Factor.
Upper Limit: 1
43854 Load Demand Read/ 0: Inactive Modbus input for activating load PC 3.x
Stop (Modbus) Write 1: Active demand stop on the generator set
43855 Load Govern Read/ 0: Genset kVAR Use to select how generator set PC 3.x
kVAR Method Write 1: Genset Power Factor kVAR output will be controlled
2: Utility kVAR when paralleled to utility.
3: Utility Power Factor

228
Addr. Parameter Access Specifications Description Control
43856 Load Govern Read/ Multiplier: 1 Sets load govern kVAR ramp load PC 3.x
kVAR Ramp Write Offset: 0 rate = Genset Standby kVA * 0.6/
Load Time Size (bits): 16 this time.
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 900
43857 Load Govern Read/ Multiplier: 1 Sets load govern kVAR ramp un- PC 3.x
kVAR Ramp Write Offset: 0 load rate = Genset Standby KVA *
Unload Time Size (bits): 16 0.6/ this time.
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 900
43858 Utility Breaker Read/ 0: After Transfer Delay PTC − point in time at which sys- PC 3.x
Opening Point Write 1: Upon Utility Failure tem opens utility breaker
43859 Load Govern Read/ Multiplier: 1 Sets load govern kW ramp load PC 3.x
kW Ramp Load Write Offset: 0 rate = Genset Standby kW rating/
Time Size (bits): 16 this time.
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 900
43860 Load Govern Read/ Multiplier: 1 Sets load govern kW ramp unload PC 3.x
kW Ramp Un- Write Offset: 0 rate = Genset Standby kW rating/
load Time Size (bits): 16 this time.
Sign: U
Unit: seconds
Lower Limit: 0
Upper Limit: 900
43861 Ramp Load/Un- Read / 0: Load Use to control ramp load and un- PC3.x
load (Modbus) Write 1: Unload load via Modbus
43862 Slip Frequency Read/ Multiplier: 0.001 Sets the synchronizer slip fre- PC 3.x
Write Offset: 0 quency. Requires that Sync
Size (bits): 16 Speed Control Method = Slip Fre-
Sign: S quency.
Unit: Hz
Lower Limit: −3
Upper Limit: 3
43863 Utility kVAR Read/ Multiplier: 1 Sets the utility kVAR peak shave PC 3.x
Setpoint Write Offset: 0 internal operating setpoint in units
Size (bits): 16 of kVAR. Requires that Load Gov-
Sign: S ern kVAR Setpoint Source = Inter-
Unit: kVAR nal and Load Govern kVAR Meth-
Lower Limit: −20000 od = Utility kVAR
Upper Limit: 20000

229
Addr. Parameter Access Specifications Description Control
43864 Utility kVAR Read/ Multiplier: 0.01 Sets the utility kVAR peak shave PC 3.x
Setpoint Per- Write Offset: 0 internal operating setpoint in % of
cent Size (bits): 16 generator set standby kVA rating.
Sign: S Requires that Load Govern kVAR
Unit: % Setpoint Source = Internal and
Lower Limit: −320 Load Govern kVAR Method = Util-
Upper Limit: 320 ity kVAR.

43865 Utility kW Read/ Multiplier: 1 Sets the utility kW minimum load PC 3.x
Constraint Write Offset: 0 level for constrained base load
Size (bits): 16 mode of operation. Requires that
Sign: S Load Govern kW Setpoint Source
Unit: kW = Internal and Load Govern kW
Lower Limit: −20000 Method = Genset kW w/Utility
Upper Limit: 20000 Constraint.

43866 Utility kW Read/ Multiplier: 0.01 Sets utility kW minimum load lev- PC 3.x
Constraint Per- Write Offset: 0 el for constrained base load mode
cent Size (bits): 16 in % of generator set standby rat-
Sign: S ing. Requires that Load Govern
Unit: % kW Setpoint Source = Internal
Lower Limit: −320 and Load Govern kW Method =
Upper Limit: 320 Genset kW w/Utility Constraint.

43867 Utility kW Set- Read/ Multiplier: 1 Sets the utility kW peak shave in- PC 3.x
point Write Offset: 0 ternal operating setpoint in units
Size (bits): 16 of kW. Requires that Load Govern
Sign: S kW Setpoint Source = Internal
Unit: kW and Load Govern kW Method =
Lower Limit: −20000 Utility kW.
Upper Limit: 20000

43868 Utility kW Set- Read/ Multiplier: 0.01 Sets the utility kW peak shave in- PC 3.x
point Percent Write Offset: 0 ternal operating setpoint in % of
Size (bits): 16 generator set standby rating. Re-
Sign: S quires that Load Govern kW Set-
Unit: % point Source = Internal and Load
Lower Limit: −320 Govern kW Method = Utility kW.
Upper Limit: 320

43869 Utility Power Read/ Multiplier: 0.01 Sets the internal setpoint for utility PC 3.x
Factor Setpoint Write Offset: 0 power factor control mode when
Size (bits): 16 paralleled to utility. Requires that
Sign: S Load Govern kVAR Setpoint
Unit: PF Source = Internal and Load Gov-
Lower Limit: 0.7 ern kVAR Method = Utility Power
Upper Limit: 1 Factor.

43870 Aux101 0 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 2 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

230
Addr. Parameter Access Specifications Description Control
43871 Aux101 0 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 4 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43872 Aux101 0 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 5 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43873 Aux101 0 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 6 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43874 Aux101 0 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 7 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43875 Aux101 1 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 1 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43876 Aux101 1 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 2 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43877 Aux101 1 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 3 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

231
Addr. Parameter Access Specifications Description Control
43878 Aux101 1 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 4 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43879 Aux101 1 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 5 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43880 Aux101 1 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 6 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43881 Aux101 1 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 7 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43882 Aux101 1 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 8 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43883 Aux102 0 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 10 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43884 Aux102 0 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 11 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

232
Addr. Parameter Access Specifications Description Control
43885 Aux102 0 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 12 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43886 Aux102 0 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 13 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43887 Aux102 0 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 14 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43888 Aux102 0 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 15 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43889 Aux102 0 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 16 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43890 Aux102 0 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 9 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43891 Aux102 1 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 10 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

233
Addr. Parameter Access Specifications Description Control
43892 Aux102 1 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 11 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43893 Aux102 1 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 12 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43894 Aux102 1 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 13 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43895 Aux102 1 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 14 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43896 Aux102 1 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 15 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43897 Aux102 1 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 16 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

43898 Aux102 1 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 9 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

234
Addr. Parameter Access Specifications Description Control
43900 HMI113 Output Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
1 Fault/Event Write Offset: 0 the fault/event code which will PC 3.x
Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43901 HMI113 Output Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
2 Fault/Event Write Offset: 0 the fault/event code which will PC 3.x
Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43902 HMI113 Output Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
3 Fault/Event Write Offset: 0 the fault/event code which will PC 3.x
Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43903 HMI113 Output Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
4 Fault/Event Write Offset: 0 the fault/event code which will PC 3.x
Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43905 Network Speed Read / 0: Normal Used to command a fixed 0.5 Hz PC 2.x
Adjust Com- Write 1: Active increase in the speed setpoint PC3.x
mand
43906 Speed Droop Read / 0: Inactive Speed droop enable switch input PC 2.x
Enable Switch Write 1: Active status from Modbus PC3.x
(Modbus)
43907 Voltage Droop Read / 0: Inactive Voltage droop enable switch input PC 2.x
Enable Switch Write 1: Active status from Modbus PC3.x
(Modbus)
43908 Genset CB Read / 0: Inactive Genset cb tripped from Modbus PC3.X
Tripped Switch Write 1: Active
(Modbus)
43909 Utility CB Read / 0: Inactive Utility cb tripped switch input from PC3.x
Tripped Switch Write 1: Active Modbus
(Modbus)
43910 Save Trims Read / 0: Do Nothing The save trims command PC 2.x
Write 1: Save Trims PC3.x

235
Addr. Parameter Access Specifications Description Control
43911 Aux101 0 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 3 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43912 Aux101 0 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 1 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43913 Aux101 0 Out- Read/ Multiplier: 1 Parameter to allow for the entry of PC 2.x,
put 8 Fault/ Write Offset: 0 the fault/event code which will PC 3.x
Event Size (bits): 16 turn the output relay on and off.
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
43915 Extended Par- Read/ 0: Disabled use to enable the extended paral- PC 3.x
allel Enable Write 1: Enabled leling mode of PTC
43916 V/Hz Knee Fre- Read Multiplier: 0.1 The voltage will roll off (decrease) PC 2.x,
quency 50Hz Only Offset: 0 proportionally to the V/Hz setup, PC 3.x
Size (bits): 16 once the frequency drops below
Sign: U the set point in the V/Hz Knee
Unit: Hz Frequency. This allows the gener-
Lower Limit: 0 ator set to recover faster when
Upper Limit: 10 the frequency drops. This is for
50Hz frequency.
43917 V/Hz Knee Fre- Read Multiplier: 0.1 The voltage will roll off (decrease) PC 2.x,
quency 60Hz Only Offset: 0 proportionally to the V/Hz setup, PC 3.x
Size (bits): 16 once the frequency drops below
Sign: U the set point in the V/Hz Knee
Unit: Hz Frequency. This allows the gener-
Lower Limit: 0 ator set to recover faster when
Upper Limit: 10 the frequency drops. This is for
60Hz frequency.
43918 V/Hz Rolloff Read Multiplier: 0.1 The amount of voltage roll off PC 2.x,
Slope 50Hz Only Offset: 0 when the frequency is below the PC 3.x
Size (bits): 16 knee frequency
Sign: U
Unit: % / Hz
Lower Limit: 0
Upper Limit: 10

236
Addr. Parameter Access Specifications Description Control
43919 V/Hz Rolloff Read Multiplier: 0.1 The amount of voltage roll off PC 2.x,
Slope 60Hz Only Offset: 0 when the frequency is below the PC 3.x
Size (bits): 16 knee frequency
Sign: U
Unit: % / Hz
Lower Limit: 0
Upper Limit: 10

43920 Genset Source Read/ Multiplier: 1 Name for the generator set PC 2.x,
Name Write Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit: % / Hz
Lower Limit: 0
Upper Limit: 10

43921 Genset Source Read/ Multiplier: 1 Name for the generator set PC 2.x,
Name Write Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43922 Genset Source Read/ Multiplier: 1 Name for the generator set PC 2.x,
Name Write Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43923 Genset Source Read/ Multiplier: 1 Name for the generator set PC 2.x,
Name Write Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43924 Genset Source Read/ Multiplier: 1 Name for the generator set PC 2.x,
Name Write Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43925 Genset Source Read/ Multiplier: 1 Name for the generator set PC 2.x,
Name Write Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

237
Addr. Parameter Access Specifications Description Control
43926 Genset Source Read/ Multiplier: 1 Name for the generator set PC 2.x,
Name Write Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43927 Genset Source Read/ Multiplier: 1 Name for the generator set PC 2.x,
Name Write Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43928 Genset Source Read/ Multiplier: 1 Name for the generator set PC 2.x,
Name Write Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43929 Genset Source Read/ Multiplier: 1 Name for the generator set PC 2.x,
Name Write Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43930 Genset Source Read/ Multiplier: 1 Name for the generator set PC 2.x,
Name Write Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43931 Genset Source Read/ Multiplier: 1 Name for the generator set PC 2.x,
Name Write Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

43932 Genset Source Read/ Multiplier: 1 Name for the generator set PC 2.x,
Name Write Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:

238
Addr. Parameter Access Specifications Description Control
43933 Genset Source Read/ Multiplier: 1 Name for the generator set PC 2.x,
Name Write Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:
43934 Genset Source Read/ Multiplier: 1 Name for the generator set PC 2.x,
Name Write Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:
43935 Genset Source Read/ Multiplier: 1 Name for the generator set PC 2.x,
Name Write Offset: 0 source. PC 3.x
Size (bits): 136
Sign: C
Unit:
Lower Limit:
Upper Limit:
43952 Speed/Fre- Read/ Multiplier: 0.1 Sets the delay time for generating PC 2.x,
quency Delay Write Offset: 0 the Speed/Frequency mismatch PC 3.x
Size (bits): 136 fault
Sign: U
Unit: seconds
Lower Limit: 0.5
Upper Limit: 10
43953 Speed/Fre- Read/ Multiplier: 0.1 Sets the threshold for generating PC 2.x,
quency Thresh- Write Offset: 0 the Speed/Frequency mismatch PC 3.x
old Size (bits): 16 fault
Sign: U
Unit: Hz
Lower Limit: 0.5
Upper Limit: 20
43954 Sync Enable Read / 0: Inactive Modbus input for enabling the PC3.x
(Modbus) Write 1: Active synchronizer
43955 Genset Idle En- Read 0: Disabled Enables or Disable idling of gen- PC 2.x,
able Only 1: Enabled erator set with external governor. PC 3.x
43956 Permissive Fre- Read Multiplier : 0.001 Frequency match error value PC3.x
quency Match Only Offset: 0 used by permissive sync check
Error Size (bits): 32
Sign: U
Unit: Hz
Lower Limit: NA
Upper Limit: NA
Default: NA

239
Addr. Parameter Access Specifications Description Control
43957 Permissive Fre- Read Multiplier : 0.001 Frequency match error value PC3.x
quency Match Only Offset: 0 used by permissive sync check
Error Size (bits): 32
Sign: U
Unit: Hz
Lower Limit: NA
Upper Limit: NA
Default: NA
43958 Sync Enable Read 0: Inactive Indicates overall status of sync PC3.x
Command Only 1: Active enable inputs
43959 Utility Unloaded Read/ Multiplier: 1 Sets threshold at which utility PC 3.x
Level Write Offset: 0 source is considered as un-
Size (bits): 16 loaded.
Sign: S
Unit: kW
Lower Limit: −32768
Upper Limit: 32762
43960 HMI113 Fault 1 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43961 HMI113 Fault 1 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43962 HMI113 Fault 1 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43963 HMI113 Fault 1 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

240
Addr. Parameter Access Specifications Description Control
43964 HMI113 Fault 1 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

43965 HMI113 Fault 1 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

43966 HMI113 Fault 1 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

43967 HMI113 Fault 1 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

43968 HMI113 Fault 1 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

43969 HMI113 Fault 1 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

43970 HMI113 Fault 1 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

241
Addr. Parameter Access Specifications Description Control
43971 HMI113 Fault 1 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43972 HMI113 Fault 1 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43973 HMI113 Fault 1 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43974 HMI113 Fault 1 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43975 HMI113 Fault 1 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43976 HMI113 Fault 1 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

43977 HMI113 Fault 1 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

242
Addr. Parameter Access Specifications Description Control
43978 HMI113 Fault 1 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

43979 HMI113 Fault 1 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

43980 HMI113 Fault 2 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

43981 HMI113 Fault 2 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

43982 HMI113 Fault 2 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

43983 HMI113 Fault 2 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

43984 HMI113 Fault 2 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

243
Addr. Parameter Access Specifications Description Control
43985 HMI113 Fault 2 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43986 HMI113 Fault 2 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43987 HMI113 Fault 2 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43988 HMI113 Fault 2 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43989 HMI113 Fault 2 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43990 HMI113 Fault 2 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

43991 HMI113 Fault 2 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

244
Addr. Parameter Access Specifications Description Control
43992 HMI113 Fault 2 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

43993 HMI113 Fault 2 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43994 HMI113 Fault 2 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43995 HMI113 Fault 2 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43996 HMI113 Fault 2 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43997 HMI113 Fault 2 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:
43998 HMI113 Fault 2 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

245
Addr. Parameter Access Specifications Description Control
43999 HMI113 Fault 2 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

45999 Unrecognized Read 0: All Pairs RecognizedZ Indicates whether or not all pairs PC 2.x,
SPN/FMI Sta- Only 1: Pair Not Recognized in current DM1 are recognized PC 3.x
tus

46000 Genset Phase Read 0: L1−L2−L3 Generator set phase rotation PC 2.x,
Rotation Only 1: L1−L3−L2 PC 3.x
2: Not Available

46001 Utility Phase Read 0: L1−L2−L3 Utility phase rotation PC 3.x


Rotation Only 1: L1−L3−L2
2: Not AvailablE

46002 Genset Bus Read 0: L1−L2−L3 Generator set bus phase rotation PC 3.x
Phase Rotation Only 1: L1−L3−L2
2: Not Available

46003 Base Speed Read Multiplier: 0.0625 Provides a point to monitor the PC 2.x,
Only Offset: 0 base speed PC 3.x
Size (bits): 32
Sign: U
Unit: RPM
Lower Limit:
Upper Limit:

46004 Base Speed Read Multiplier: 0.0625 Provides a point to monitor the PC 2.x,
Only Offset: 0 base speed PC 3.x
Size (bits): 32
Sign: U
Unit: RPM
Lower Limit:
Upper Limit:

46005 Final Speed Read Multiplier: 0.0625 Provides a point to monitor the fi- PC 2.x,
Reference Only Offset: 0 nal speed reference PC 3.x
Size (bits): 32
Sign: U
Unit: RPM
Lower Limit:
Upper Limit:

46006 Final Speed Read Multiplier: 0.0625 Provides a point to monitor the fi- PC 2.x,
Reference Only Offset: 0 nal speed reference PC 3.x
Size (bits): 32
Sign: U
Unit: RPM
Lower Limit:
Upper Limit:

246
Addr. Parameter Access Specifications Description Control
46008 Exhaust Port 1 Read Multiplier: 0.1 Monitor point for the Exhaust Port PC 2.x,
Temperature Only Offset: 0 1 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −459
Upper Limit: 3155

46009 Exhaust Port 2 Read Multiplier: 0.1 Monitor point for the Exhaust Port PC 2.x,
Temperature Only Offset: 0 2 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −459
Upper Limit: 3155

46010 Exhaust Port 3 Read Multiplier: 0.1 Monitor point for the Exhaust Port PC 2.x,
Temperature Only Offset: 0 3 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −460
Upper Limit: 3155

46011 Exhaust Port 4 Read Multiplier: 0.1 Monitor point for the Exhaust Port PC 2.x,
Temperature Only Offset: 0 4 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −460
Upper Limit: 3155

46012 Exhaust Port 5 Read Multiplier: 0.1 Monitor point for the Exhaust Port PC 2.x,
Temperature Only Offset: 0 5 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −460
Upper Limit: 3155

46013 Exhaust Port 6 Read Multiplier: 0.1 Monitor point for the Exhaust Port PC 2.x,
Temperature Only Offset: 0 6 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −460
Upper Limit: 3155

46014 Exhaust Port 7 Read Multiplier: 0.1 Monitor point for the Exhaust Port PC 2.x,
Temperature Only Offset: 0 7 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −460
Upper Limit: 3155

247
Addr. Parameter Access Specifications Description Control
46015 Exhaust Port 8 Read Multiplier: 0.1 Monitor point for the Exhaust Port PC 2.x,
Temperature Only Offset: 0 8 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −460
Upper Limit: 3155

46016 Exhaust Port 9 Read Multiplier: 0.1 Monitor point for the Exhaust Port PC 2.x,
Temperature Only Offset: 0 9 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −460
Upper Limit: 3155

46017 Exhaust Port 10 Read Multiplier: 0.1 Monitor point for the Exhaust Port PC 2.x,
Temperature Only Offset: 0 10 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −460
Upper Limit: 3155

46018 Exhaust Port 11 Read Multiplier: 0.1 Monitor point for the Exhaust Port PC 2.x,
Temperature Only Offset: 0 11 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −460
Upper Limit: 3155

46019 Exhaust Port 12 Read Multiplier: 0.1 Monitor point for the Exhaust Port PC 2.x,
Temperature Only Offset: 0 12 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −460
Upper Limit: 3155

46020 Exhaust Port 13 Read Multiplier: 0.1 Monitor point for the Exhaust Port PC 2.x,
Temperature Only Offset: 0 13 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −460
Upper Limit: 3155

46021 Exhaust Port 14 Read Multiplier: 0.1 Monitor point for the Exhaust Port PC 2.x,
Temperature Only Offset: 0 14 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −460
Upper Limit: 3155

248
Addr. Parameter Access Specifications Description Control
46022 Exhaust Port 15 Read Multiplier: 0.1 Monitor point for the Exhaust Port PC 2.x,
Temperature Only Offset: 0 15 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −460
Upper Limit: 3155

46023 Exhaust Port 16 Read Multiplier: 0.1 Monitor point for the Exhaust Port PC 2.x,
Temperature Only Offset: 0 16 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −460
Upper Limit: 3155

46024 Exhaust Port 17 Read Multiplier: 0.1 Monitor point for the Exhaust Port PC 2.x,
Temperature Only Offset: 0 17 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −460
Upper Limit: 3155

46025 Exhaust Port 18 Read Multiplier: 0.1 Monitor point for the Exhaust Port PC 2.x,
Temperature Only Offset: 0 18 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −460
Upper Limit: 3155

46026 Exhaust Port 19 Read Multiplier: 0.1 Monitor point for the Exhaust Port PC 2.x,
Temperature Only Offset: 0 19 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −460
Upper Limit: 3155

46027 Exhaust Port 20 Read Multiplier: 0.1 Monitor point for the Exhaust Port PC 2.x,
Temperature Only Offset: 0 20 Temperature PC 3.x
Size (bits): 16
Sign: S
Unit: degF
Lower Limit: −460
Upper Limit: 3155

46028 Knock Level Read Multiplier: 1 Knock Level for cylinder 1 PC 3.x
Cylinder 1 Only Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:

249
Addr. Parameter Access Specifications Description Control
46029 Knock Level Read Multiplier: 1 Knock Level for cylinder 2 PC 3.x
Cylinder 2 Only Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:

46030 Knock Level Read Multiplier: 1 Knock Level for cylinder 3 PC 3.x
Cylinder 3 Only Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:

46031 Knock Level Read Multiplier: 1 Knock Level for cylinder 4 PC 3.x
Cylinder 4 Only Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:

46032 Knock Level Read Multiplier: 1 Knock Level for cylinder 5 PC 3.x
Cylinder 5 Only Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:

46033 Knock Level Read Multiplier: 1 Knock Level for cylinder 6 PC 3.x
Cylinder 6 Only Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:

46034 Knock Level Read Multiplier: 1 Knock Level for cylinder 7 PC 3.x
Cylinder 7 Only Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:

46035 Knock Level Read Multiplier: 1 Knock Level for cylinder 8 PC 3.x
Cylinder 8 Only Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:

250
Addr. Parameter Access Specifications Description Control
46036 Knock Level Read Multiplier: 1 Knock Level for cylinder 9 PC 3.x
Cylinder 9 Only Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:

46037 Knock Level Read Multiplier: 1 Knock Level for cylinder 10 PC 3.x
Cylinder 10 Only Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:

46038 Knock Level Read Multiplier: 1 Knock Level for cylinder 11 PC 3.x
Cylinder 11 Only Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:

46039 Knock Level Read Multiplier: 1 Knock Level for cylinder 12 PC 3.x
Cylinder 12 Only Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:

46040 Knock Level Read Multiplier: 1 Knock Level for cylinder 13 PC 3.x
Cylinder 13 Only Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:

46041 Knock Level Read Multiplier: 1 Knock Level for cylinder 14 PC 3.x
Cylinder 14 Only Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:

46042 Knock Level Read Multiplier: 1 Knock Level for cylinder 15 PC 3.x
Cylinder 15 Only Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:

251
Addr. Parameter Access Specifications Description Control
46043 Knock Level Read Multiplier: 1 Knock Level for cylinder 16 PC 3.x
Cylinder 16 Only Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46044 Knock Level Read Multiplier: 1 Knock Level for cylinder 17 PC 3.x
Cylinder 17 Only Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46045 Knock Level Read Multiplier: 1 Knock Level for cylinder 18 PC 3.x
Cylinder 18 Only Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46046 Knock Level Read Multiplier : 1 Knock Level for cylinder 19 PC3.x
Cylinder 19 Only Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
46047 Knock Level Read Multiplier : 1 Knock Level for cylinder 20 PC3.x
Cylinder 20 Only Offset: 0
Size (bits): 8
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA
Default: NA
46048 Knock Count Read Multiplier: 1 Knock count value for Cylinder 1 PC 3.x
Cyl 1 Only Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46049 Knock Count Read Multiplier: 1 Knock count value for Cylinder 2 PC 3.x
Cyl 2 Only Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

252
Addr. Parameter Access Specifications Description Control
46050 Knock Count Read Multiplier: 1 Knock count value for Cylinder 3 PC 3.x
Cyl 3 Only Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

46051 Knock Count Read Multiplier: 1 Knock count value for Cylinder 4 PC 3.x
Cyl 4 Only Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

46052 Knock Count Read Multiplier: 1 Knock count value for Cylinder 5 PC 3.x
Cyl 5 Only Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

46053 Knock Count Read Multiplier: 1 Knock count value for Cylinder 6 PC 3.x
Cyl 6 Only Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

46054 Knock Count Read Multiplier: 1 Knock count value for Cylinder 7 PC 3.x
Cyl 7 Only Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

46055 Knock Count Read Multiplier: 1 Knock count value for Cylinder 8 PC 3.x
Cyl 8 Only Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

46056 Knock Count Read Multiplier: 1 Knock count value for Cylinder 9 PC 3.x
Cyl 9 Only Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

253
Addr. Parameter Access Specifications Description Control
46057 Knock Count Read Multiplier: 1 Knock count value for Cylinder 10 PC 3.x
Cyl 10 Only Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

46058 Knock Count Read Multiplier: 1 Knock count value for Cylinder 11 PC 3.x
Cyl 11 Only Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

46059 Knock Count Read Multiplier: 1 Knock count value for Cylinder 12 PC 3.x
Cyl 12 Only Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

46060 Knock Count Read Multiplier: 1 Knock count value for Cylinder 13 PC 3.x
Cyl 13 Only Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

46061 Knock Count Read Multiplier: 1 Knock count value for Cylinder 14 PC 3.x
Cyl 14 Only Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

46062 Knock Count Read Multiplier: 1 Knock count value for Cylinder 15 PC 3.x
Cyl 15 Only Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

46063 Knock Count Read Multiplier: 1 Knock count value for Cylinder 16 PC 3.x
Cyl 16 Only Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

254
Addr. Parameter Access Specifications Description Control
46064 Knock Count Read Multiplier: 1 Knock count value for Cylinder 17 PC 3.x
Cyl 17 Only Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46065 Knock Count Read Multiplier: 1 Knock count value for Cylinder 18 PC 3.x
Cyl 18 Only Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
46066 Knock Count Read Multiplier : 1 Knock count value for Cylinder 19 PC3.x
Cyl 19 Only Offset: 0
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA
46067 Knock Count Read Multiplier : 1 Knock count value for Cylinder 20 PC3.x
Cyl 20 Only Offset: 0
Size (bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65530
Default: NA
46068 Spark Timing Read Multiplier: 0.1 Spark timing degrees for cylinder PC 3.x
Cyl 1 Only Offset: 0 1
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit: 0
Upper Limit: 65530
Default: NA
46069 Spark Timing Read Multiplier: 0.1 Spark timing degrees for cylinder PC 3.x
Cyl 2 Only Offset: 0 2
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:

255
Addr. Parameter Access Specifications Description Control
46070 Spark Timing Read Multiplier: 0.1 Spark timing degrees for cylinder PC 3.x
Cyl 3 Only Offset: 0 3
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:

46071 Spark Timing Read Multiplier: 0.1 Spark timing degrees for cylinder PC 3.x
Cyl 4 Only Offset: 0 4
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:

46072 Spark Timing Read Multiplier: 0.1 Spark timing degrees for cylinder PC 3.x
Cyl 5 Only Offset: 0 5
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:

46073 Spark Timing Read Multiplier: 0.1 Spark timing degrees for cylinder PC 3.x
Cyl 6 Only Offset: 0 6
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:

46074 Spark Timing Read Multiplier: 0.1 Spark timing degrees for cylinder PC 3.x
Cyl 7 Only Offset: 0 7
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:

46075 Spark Timing Read Multiplier: 0.1 Spark timing degrees for cylinder PC 3.x
Cyl 8 Only Offset: 0 8
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:

46076 Spark Timing Read Multiplier: 0.1 Spark timing degrees for cylinder PC 3.x
Cyl 9 Only Offset: 0 9
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:

256
Addr. Parameter Access Specifications Description Control
46077 Spark Timing Read Multiplier: 0.1 Spark timing degrees for cylinder PC 3.x
Cyl 10 Only Offset: 0 10
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:

46078 Spark Timing Read Multiplier: 0.1 Spark timing degrees for cylinder PC 3.x
Cyl 11 Only Offset: 0 11
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:

46079 Spark Timing Read Multiplier: 0.1 Spark timing degrees for cylinder PC 3.x
Cyl 12 Only Offset: 0 12
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:

46080 Spark Timing Read Multiplier: 0.1 Spark timing degrees for cylinder PC 3.x
Cyl 13 Only Offset: 0 13
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:

46081 Spark Timing Read Multiplier: 0.1 Spark timing degrees for cylinder PC 3.x
Cyl 14 Only Offset: 0 14
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:

46082 Spark Timing Read Multiplier: 0.1 Spark timing degrees for cylinder PC 3.x
Cyl 15 Only Offset: 0 15
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:

46083 Spark Timing Read Multiplier: 0.1 Spark timing degrees for cylinder PC 3.x
Cyl 16 Only Offset: 0 16
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:

257
Addr. Parameter Access Specifications Description Control
46084 Spark Timing Read Multiplier: 0.1 Spark timing degrees for cylinder PC 3.x
Cyl 17 Only Offset: 0 17
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46085 Spark Timing Read Multiplier: 0.1 Spark timing degrees for cylinder PC 3.x
Cyl 18 Only Offset: 0 18
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46086 Spark Timing Read Multiplier : 0.1 Spark timing degres for cylinder PC3.x
Cyl 19 Only Offset: 0 19
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit:
Upper Limit:
46087 Spark Timing Read Multiplier : 0.1 Spark timing degres for cylinder PC3.x
Cyl 20 Only Offset: 0 20
Size (bits): 16
Sign: S
Unit: Degrees
Lower Limit: NA
Upper Limit: NA
Default: NA
46088 Internal Read Multiplier: 0.1 Temperature of the engine elec- PC 3.x
SSM558 1 Only Offset: 0 tronic control unit SSM558 1
Temperature Size (bits): 16
Sign: S
Unit: degF
Lower Limit:
Upper Limit:
46089 Internal Read Multiplier: 0.1 Temperature of the engine elec- PC 3.x
SSM558 2 Only Offset: 0 tronic control unit SSM558 2
Temperature Size (bits): 16
Sign: S
Unit: degF
Lower Limit:
Upper Limit
46090 Internal Read Multiplier: 0.1 Temperature of the engine elec- PC 3.x
MCM700 Tem- Only Offset: 0 tronic control unit MCM700
perature Size (bits): 16
Sign: S
Unit: degF
Lower Limit:
Upper Limit

258
Addr. Parameter Access Specifications Description Control
46091 Derate Authori- Read 0: NO Derate authorization request from PC 3.x
zation Only 1: YES customer.
2: Reserved
3: N/A
46092 Start System Read 0: Not Tripped Start system status monitor point. PC3.x
Status Only 1: Tripped
2: Reserved
3: N/A
4: Network Failure
46093 Ventilator Fan Read 0: OFF Vent Fan status monitor point. PC 3.x
Status Only 1: ON
2: TRIPPED
3: N/A
46094 Louvres Status Read 0: Open Louvres Closed monitor point. PC3.x
Only 1: Closed
2: Reserved
3: N/A
4: Network Failure
46095 Radiator Fan Read 0: OFF Radiator Fan status monitor point. PC3.x
Status Only 1: ON
2: TRIPPED
3: N/A
46096 GIB Isolator Read 0: Close GIB Isolator Open monitor point. PC 3.x
Open (Aux101) Only 1: Open
2: Reserved
3: N/A
46097 Alternator Heat- Read 0: OFF Alternator Heater status monitor PC 3.x
er Status Only 1: ON point.
2: TRIPPED
3: N/A
46099 Gearbox Oil Read 0: No Gearbox Oil Pressure monitor PC3.x
Pressure Only 1: Yes point.
(Aux101) 2: Reserved
3: N/A
4: Network Failure
46100 Gearbox Oil Read 0: No Gearbox Oil Temperature monitor PC3.x
Temperature Only 1: Yes point.
(Aux101) 2: Reserved
3: N/A
4: Network Failure
46101 Start Inhibit Read 0: Inactive Start Inhibit No1 monitor point. PC 3.x
No1 (Aux101) Only 1: Active
2: Reserved
3: N/A
46102 Start Inhibit Read 0: Inactive Start Inhibit No2 monitor point. PC 3.x
No2 (Aux101) Only 1: Active
2: Reserved
3: N/A

259
Addr. Parameter Access Specifications Description Control
46103 Start Inhibit Read 0: Inactive Start Inhibit No3 monitor point. PC 3.x
No3 (Aux101) Only 1: Active
2: Reserved
3: N/A
46104 DC PSU Un- Read 0: No Engine PSU Not Available moni- PC 3.x
available Only 1: Yes tor point.
(Aux101)
46105 Ventilator Fan Read 0: No Ventilator Fan Trip monitor point. PC 3.x
Trip (Aux101) Only 1: Yes
46106 Aux101−3 Soft- Read Multiplier: 0.01 Software version of the firmware PC 3.x
ware Version Only Offset: 0 for the Aux101−3
Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit
46107 Aux101−4 Soft- Read Multiplier: 0.01 Software version of the firmware PC 3.x
ware Version Only Offset: 0 for the Aux101−4
Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit
46108 Aux101−5 Soft- Read Multiplier: 0.01 Software version of the firmware PC 3.x
ware Version Only Offset: 0 for the Aux101−5
Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit
46109 Engine Operat- Read 0: Engine Stopped Indicate current state or mode of PC 2.x
ing State Only 1: Pre−Start operation by the engine PC3.x
2: Starting
3: Warm−Up
4: Running
5: Cool−Down
6: Engine Stopping
7: Post−Run
8: Out Of Range
9: Out Of Range
10: Out Of Range
11: Out Of Range
12: Out Of Range
13: Out Of Range
14: Out Of Range
15: N/A
46110 Fuel Pump Read 0: Inactive Fuel pump state PC3.x
Control Status Only 1: Active
2: Reserved
3: Not Available

260
Addr. Parameter Access Specifications Description Control
46112 Fuel Shutoff Read 0: Closed Fuel shutoff valve status PC3.x
Vent Valve sta- Only 1: Open
tus 2: Reserved
3: Not Available
46113 Downstream Read 0: Open The result of the FSO driver out- PC 3.x
Valve Com- Only 1: Closed put command logic for fuel shutoff
mand Status 2: Reserved valve 1
3: N/A
46114 Upstream Valve Read 0: Open The result of the FSO driver out- PC3.x
Command Sta- Only 1: Closed put command logic for fuel shutoff
tus 2: Reserved valve 2.
3: N/A
46115 VPS Status Read 0: OFF Control setting for fuel shutoff PC3.x
Only 1: ON valve proving system test
2: Reserved
3: N/A
46116 Gas Supply Read Multiplier : 0.1 Gage Pressure of gas supply to PC3.x
Pressure Only Offset: 0 fuel metering device
Size (bits): 16
Sign: U
Units: psi
Lower Limit: NA
Upper Limit: NA
Default: NA
46117 Engine Oil Pre- Read 0: OFF Engine Oil pre heater command PC 3.x
Heater Ctrl Sta- Only 1: ON status
tus 2: Reserved
3: N/A
46118 Engine Power Read 0: OFF Control setting for cutting power PC3.x
Conservation Only 1: ON to various devices when te engine
Ctrl Status 2: Reserved is not in use
3: Not Available
46119 Engine Coolant Read 0: OFF Engine coolant PreHeater states PC3.x
PreHeater Ctrl Only 1: ON
Status 2: Reserved
3: N/A
46120 Engine Coolant Read 0: OFF Engine coolant circulating pump PC 3.x
Pump Ctrl Sta- Only 1: ON status
tus 2: Reserved
3: N/A
46121 Engine Con- Read 0: Inactive Active when the engine control PC3.x
trolled Shut- Only 1: Active request a controlled shutdown
down Request 2: Reserved (shutdown with cooldown)
3: Not Available
46122 Emergency Read 0: Inactive Active when the engine control PC3.x
Shutdown Re- Only 1: Active request an emergency shutdown
quest 2: Reserved (immediate shutdown)
3: Not Available

261
Addr. Parameter Access Specifications Description Control
46123 Engine Derate Read Multiplier : 0.4 Derate request in percent made PC3.x
Request Only Offset: 0 by the engine control
Size (bits): 8
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA

46124 Coolant Pres- Read Multiplier: 0.1 Monitor point for the Coolant PC 2.x,
sure Only Offset: 0 Pressure. PC 3.x
Size (bits): 8
Sign: U
Unit: psi
Lower Limit: NA
Upper Limit: NA

46125 Coolant 2 Pres- Read Multiplier: 0.1 Monitor point for the Coolant 2 PC 3.x
sure Only Offset: 0 Pressure.
Size (bits): 16
Sign: U
Unit: psi
Lower Limit: 0
Upper Limit: 145

46127 Coolant 2 Tem- Read Multiplier: 0.1 Monitor point for the Coolant 2 PC 3.x
perature Only Offset: 0 Temperature
Size (bits): 16
Sign: S
Unit: degF
Lower Limit:
Upper Limit:

46128 Compressor Read Multiplier: 0.1 Engine turbocharger compressor PC 3.x


Bypass Position Only Offset: 0 bypass actuator position
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:

46129 Engine Oil Filter Read Multiplier : 0.1 ”Engine oil pressure at the outlet PC3.x
Outlet Pressure Only Offset: 0 of the filter
Size (bits): 16 Search ””17185”” (2 hits in 2
Sign: U files)”
Units: psi
Lower Limit: NA
Upper Limit: NA
Default: NA

46130 Oil Priming Read 0: OFF Status for the priming pump (ON PC 3.x
Pump Control Only 1: ON or OFF)
Status 2: Reserved
3: N/A

262
Addr. Parameter Access Specifications Description Control
46131 Oil Priming Read 0: Low Status of the engine before start PC 3.x
State Only 1: Optimum (Pre−Lubed or Not)
2: Reserved
3: N/A
46132 Oil Pre−Heated Read 0: Cold Status of the engine oil before PC3.x
State Only 1: Heated start (Pre−Heated or Not)
2: Reserved
3: N/A
46133 Coolant Pre− Read 0: Cold Status of the engine coolant be- PC 3.x
Heated State Only 1: Heated fore start (Pre−Heated or Not)
2: Reserved
3: N/A
46134 Ventilation Sta- Read 0: Vented Engine Ventilation Status (Vented PC3.x
tus Only 1: Not Vented or Not)
2: Ventilation Delay
3: Currently Venting
4: Reserved
5: Reserved
6: Not Able To Determine
7: Not Available
46135 Intake Manifold Read Multiplier: 0.1 Intake Manifold Pressure 1 PC 3.x
Pressure 1 Only Offset: 0
Size (bits): 16
Sign: U
Units: psi
Lower Limit: NA
Upper Limit: NA
46136 Compressor Read Multiplier: 0.1 Absolute Pressure at the outlet of PC 3.x
Outlet Pressure Only Offset: 0 the compressor.
Size (bits): 16
Sign: U
Unit: kPa
Lower Limit: NA
Upper Limit: NA
46137 Turbocharger 1 Read Multiplier : 0.1 Monitor point for the Turbochar- PC3.x
Boost Pressure Only Offset: 0 ger 1 Boost Pressure
Size (bits): 16
Sign: U
Units: psi
Lower Limit: NA
Upper Limit: NA
Default: NA
46138 Genset Avg AC Read Multiplier : 0.1 Average Genset AC frequency PC3.x
Frequency Only Offset: 0
Size (bits): 16
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA

263
Addr. Parameter Access Specifications Description Control
46139 Fuel Valve 1 In- Read Multiplier: 0.1 Absolute Pressure of Gas on the PC 3.x
let Absolutee Only Offset: 0 inlet side of the first system con-
Pressure Size (bits): 16 trol valve
Sign: U
Unit: psi
Lower Limit: NA
Upper Limit: NA

46140 Fuel Valve 1 Read Multiplier: 0.1 Absolute Pressure of Gas on the PC 3.x
Outlet Absolu- Only Offset: 0 outlet side of the first system con-
tee Pressure Size (bits): 16 trol valve
Sign: U
Unit: psi
Lower Limit: NA
Upper Limit: NA

46141 Fuel Valve 1 Read Multiplier: 0.1 PC 3.x


Position Only Offset: 0
Size (bits): 16
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA

46142 Fuel Valve 2 In- Read Multiplier: 0.1 Absolute Pressure of Gas on the PC 3.x
let Absolutee Only Offset: 0 inlet side of the second system
Pressure Size (bits): 16 control valve
Sign: U
Unit: psi
Lower Limit: NA
Upper Limit: NA

46143 Fuel Valve 2 Read Multiplier: 0.1 Absolute Pressure of Gas on the PC 3.x
Outlet Absolu- Only Offset: 0 outlet side of the second system
tee Pressure Size (bits): 16 control valve
Sign: U
Unit: psi
Lower Limit: NA
Upper Limit: NA

46144 Fuel Valve 2 Read Multiplier: 0.1 PC 3.x


Position Only Offset: 0
Size (bits): 16
Sign: U
Unit: %
Lower Limit: NA
Upper Limit: NA

46145 Gas Mass Flow Read Multiplier: 0.1 Gas Mass Flow value of the en- PC 3.x
Only Offset: 0 gine.
Size (bits): 16
Sign: U
Unit: Pounds per hour
Lower Limit:
Upper Limit:

264
Addr. Parameter Access Specifications Description Control
46146 Gas Mass Flow Read Multiplier: 0.1 Gas Mass Flow value of the en- PC 3.x
Only Offset: 0 gine.
Size (bits): 32
Sign: U
Unit: Pounds per hour
Lower Limit:
Upper Limit:
46147 Throttle 1 Posi- Read Multiplier: 0.1 Position of the throttle 1. PC 3.x
tion Only Offset: 0
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46148 Throttle 2 Posi- Read Multiplier: 0.1 Position of the throttle 2. PC 3.x
tion Only Offset: 0
Size (bits): 16
Sign: U
Unit: %
Lower Limit:
Upper Limit:
46149 Raw Value DE Read Multiplier : 1 Raw Value for the DE RTD Bear- PC3.x
RTD Bearing Only Offset: 0 ing from the Aux101
Size (bits): 16
Sign: U
Units: Count
Lower Limit: NA
Upper Limit: NA
Default: NA
46150 Raw Value Al- Read Multiplier : 1 Raw Value Alternator RTD L1 PC3.x
ternator RTD Only Offset: 0 from Aux101 (10 bits raw data)
L1 Size (bits): 16
Sign: U
Units: Count
Lower Limit: NA
Upper Limit: NA
Default: NA
46151 Raw Value Al- Read Multiplier : 1 Raw Value Alternator RTD L2 PC3.x
ternator RTD Only Offset: 0 from Aux101 (10 bits raw data)
L2 Size (bits): 16
Sign: U
Units: Count
Lower Limit: NA
Upper Limit: NA
Default: NA

265
Addr. Parameter Access Specifications Description Control
46152 Raw Value Al- Read Multiplier : 1 Raw Value Alternator RTD L3 PC3.x
ternator RTD Only Offset: 0 from Aux101 (10 bits raw data)
L3 Size (bits): 16
Sign: U
Units: Count
Lower Limit: NA
Upper Limit: NA
Default: NA

46153 Raw Value Read Multiplier : 1 Raw Value NDE RTD Bearing PC3.x
NDE RTD Only Offset: 0 from Aux101 (10 bits raw data)
Bearing Size (bits): 16
Sign: U
Units: Count
Lower Limit: NA
Upper Limit: NA
Default: NA

46155 MCM700 Bat- Read Multiplier: 0.1 Engine Control Module Battery PC 3.x
tery Voltage Only Offset: 0 Voltage.
Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA

46157 CM700 Sensor Read Multiplier : 0.1 Engine Control Module CM700 PC3.x
Voltage A Only Offset: 0 Sensor Voltage A
Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: NA
Upper Limit: NA
Default: NA

46158 CM700 Sensor Read Multiplier : 0.1 Engine Control Module CM700 PC3.x
Voltage B Only Offset: 0 Sensor Voltage B
Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: NA
Upper Limit: NA
Default: NA

46159 CM700 Sensor Read Multiplier : 0.1 Engine Control Module CM700 PC3.x
Voltage C Only Offset: 0 Sensor Voltage C
Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: NA
Upper Limit: NA
Default: NA

266
Addr. Parameter Access Specifications Description Control
46160 SSM558 1 Bat- Read Multiplier : 0.1 SSM558 1 Engine Control Mod- PC3.x
tery Voltage Only Offset: 0 ule Battery Voltage.
Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: NA
Upper Limit: NA
Default: NA
46161 SSM558 1 Iso- Read Multiplier: 0.1 SSM558 1 Engine Control Mod- PC 3.x
lated Battery Only Offset: 0 ule Isolated Battery Voltage.
Voltage Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA
46162 SSM558 2 Bat- Read Multiplier : 0.1 SSM558 2 Engine Control Mod- PC3.x
tery Voltage Only Offset: 0 ule Battery Voltage.
Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA
46163 SSM558 2 Iso- Read Multiplier: 0.1 SSM558 2 Engine Control Mod- PC 3.x
lated Battery Only Offset: 0 ule Isolated Battery Voltage.
Voltage Size (bits): 16
Sign: U
Unit: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA
46164 Intake Manifold Read Multiplier: 0.1 Intake Manifold Pressure 2 PC 3.x
Pressure 2 Only Offset: 0
Size (bits): 16
Sign: U
Unit: psi
Lower Limit:
Upper Limit:
46165 Intake Manifold Read Multiplier : 0.1 Monitor point for the Intake Man- PC3.x
Temperature 2 only Offset: 0 ifold Temperature 2
Size (bits): 16
Sign: S
Units: degF
Lower Limit: −40
Upper Limit: 410
Default: NA

267
Addr. Parameter Access Specifications Description Control
46166 Exhaust Back Read Multiplier: 0.1 Monitor point for exhaust back PC 3.x
Pressure Only Offset: 0 pressure value
Size (bits): 16
Sign: U
Unit: psi
Lower Limit: −40
Upper Limit: 410
46168 Air Filter Differ- Read Multiplier : 0.1 Monitor point for air filter differen- PC3.x
ential Pressure only Offset: 0 tial pressure value
Size (bits): 16
Sign: S
Unit: psi
Lower Limit: NA
Upper Limit: NA
Default: NA
46170 Gas Mass Flow Read Multiplier: 0.1 Gas Mass Flow 2 value of the en- PC 3.x
2 Only Offset: 0 gine.
Size (bits): 16
Sign: U
Unit: Pounds per hour
Lower Limit:
Upper Limit:
46171 Gas Mass Flow Read Multiplier: 0.1 Gas Mass Flow 2 value of the en- PC 3.x
2 Only Offset: 0 gine.
Size (bits): 32
Sign: U
Unit: Pounds per hour
Lower Limit:
Upper Limit:
46180 E−Stops disen- Read 0: Inactive PC3.x
gaged Only 1: Active
46176 Gearbox Pres- Read / 0: No Enables gearbox protection PC3.x
ent Write 1: Yes
46182 Radiator Fan Read 0: Inactive Radiator fan control command PC 3.x
control Only 1: Active
46183 Ventilator Fan Read/ 0: Limited Vent fan control mode, limited or PC 3.x
mode Write 1: Continuous continuous
46184 Louvre Control Read 0: Inactive Louvre control PC 3.x
Only 1: Active
46191 Ventilator Fan Read 0: Inactive Ventilator fan control command PC 3.x
control Only 1: Active
46192 Engine Spark Read Multiplier : 1 Spark Plug Voltage for Cylinder 1 PC3.x
Plug Voltage 1 Only Offset: 0
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA

268
Addr. Parameter Access Specifications Description Control
46193 Engine Spark Read Multiplier : 1 Spark Plug Voltage for Cylinder 2 PC3.x
Plug Voltage 2 Only Offset: 0
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA

46194 Engine Spark Read Multiplier : 1 Spark Plug Voltage for Cylinder 3 PC3.x
Plug Voltage 3 Only Offset: 0
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA

46195 Engine Spark Read Multiplier : 1 Spark Plug Voltage for Cylinder 4 PC3.x
Plug Voltage 4 Only Offset: 0
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA

46196 Engine Spark Read Multiplier : 1 Spark Plug Voltage for Cylinder 5 PC3.x
Plug Voltage 5 Only Offset: 0
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA

46197 Engine Spark Read Multiplier : 1 Spark Plug Voltage for Cylinder 6 PC3.x
Plug Voltage 6 Only Offset: 0
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA

46198 Engine Spark Read Multiplier : 1 Spark Plug Voltage for Cylinder 7 PC3.x
Plug Voltage 7 Only Offset: 0
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA

269
Addr. Parameter Access Specifications Description Control
46199 Engine Spark Read Multiplier : 1 Spark Plug Voltage for Cylinder 8 PC3.x
Plug Voltage 8 Only Offset: 0
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA

46200 Engine Spark Read Multiplier : 1 Spark Plug Voltage for Cylinder 9 PC3.x
Plug Voltage 9 Only Offset: 0
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA

46201 Engine Spark Read Multiplier : 1 Spark Plug Voltage for Cylinder PC3.x
Plug Voltage 10 Only Offset: 0 10
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA

46202 Engine Spark Read Multiplier : 1 Spark Plug Voltage for Cylinder PC3.x
Plug Voltage 11 Only Offset: 0 11
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA

46203 Engine Spark Read Multiplier : 1 Spark Plug Voltage for Cylinder PC3.x
Plug Voltage 12 Only Offset: 0 12
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA

46204 Engine Spark Read Multiplier : 1 Spark Plug Voltage for Cylinder PC3.x
Plug Voltage 13 Only Offset: 0 13
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA

270
Addr. Parameter Access Specifications Description Control
46205 Engine Spark Read Multiplier : 1 Spark Plug Voltage for Cylinder PC3.x
Plug Voltage 14 Only Offset: 0 14
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA

46206 Engine Spark Read Multiplier : 1 Spark Plug Voltage for Cylinder PC3.x
Plug Voltage 15 Only Offset: 0 15
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA

46207 Engine Spark Read Multiplier : 1 Spark Plug Voltage for Cylinder PC3.x
Plug Voltage 16 Only Offset: 0 16
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA

46208 Engine Spark Read Multiplier : 1 Spark Plug Voltage for Cylinder PC3.x
Plug Voltage 17 Only Offset: 0 17
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA

46209 Engine Spark Read Multiplier : 1 Spark Plug Voltage for Cylinder PC3.x
Plug Voltage 18 Only Offset: 0 18
Size (bits): 16
Sign: U
Units: V
Lower Limit: NA
Upper Limit: NA
Default: NA

46273 Alternator Heat- Read 0: No Alternator Heater monitor point. PC3.x


er ON (Aux101) Only 1: Yes
2: Reserved
3: N/A
4: Network Failure

46288 DE/NDE Cylin- Read/ 0: Drive End Gives reference point for engine PC 3.x
der Viewpoint Write 1: Non−Drive End cylinder numbering
Reference 2: Reserved
3: N/A

271
Addr. Parameter Access Specifications Description Control
46291 Radiator Fan Read 0: Not Tripped Radiator Fan Trip monitor point. PC 3.x
Trip (Aux 101) Only 1: Tripped
2: Reserved
3: N/A
46300 LBNG Genset Read/ 0: Disable Switch to enable or disable the PC 3.x
Enable Write 1: Enable gas specific features and parame-
ters
46301 Aux101−3 En- Read/ 0: Disable Enable the processing for PC 3.x
able Write 1: Enable Aux101−3 messages
46302 Aux101−4 En- Read/ 0: Disable Enable the processing for PC 3.x
able Write 1: Enable Aux101−4 messages
46303 Aux101−5 En- Read/ 0: Disable Enable the processing for PC 3.x
able Write 1: Enable Aux101−5 messages
46304 Aux101−6 En- Read/ 0: Disable Enable the processing for PC 3.x
able Write 1: Enable Aux101−6 messages
46308 Aux101−3 Input Read Multiplier: 1 Input Port configuration bye for PC 3.x
Port Config Only Offset: 0 the Aux101−3
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255
46309 Aux101−4 Input Read Multiplier: 1 Input Port configuration bye for PC 3.x
Port Config Only Offset: 0 the Aux101−4
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255
46310 Aux101−5 Input Read Multiplier: 1 Input Port configuration bye for PC 3.x
Port Config Only Offset: 0 the Aux101−5
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255
46311 Aux101−3 DI Read Multiplier: 1 Digital Input Port configuration ac- PC 3.x
Active High/ Only Offset: 0 tive High or active low for the
Low Selection Size (bits): 16 Aux101−3
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255

272
Addr. Parameter Access Specifications Description Control
46312 Aux101−4 DI Read Multiplier: 1 Digital Input Port configuration ac- PC 3.x
Active High/ Only Offset: 0 tive High or active low for the
Low Selection Size (bits): 16 Aux101−4
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255

46313 Aux101−5 DI Read Multiplier: 1 Digital Input Port configuration ac- PC 3.x
Active High/ Only Offset: 0 tive High or active low for the
Low Selection Size (bits): 16 Aux101−5
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255

46314 Aux101−3 DI Read Multiplier: 1 Discrete Input configuration bit PC 3.x


Config Mask Only Offset: 0 mask for the Aux101−3
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255

46315 Aux101−4 DI Read Multiplier: 1 Discrete Input configuration bit PC 3.x


Config Mask Only Offset: 0 mask for the Aux101−4
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255

46316 Aux101−5 DI Read Multiplier: 1 Discrete Input configuration bit PC 3.x


Config Mask Only Offset: 0 mask for the Aux101−5
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 255

46323 Vehicle Electri- Read/ 0: Disabled A trim that enables the Vehicle PC 3.x
cal Power 2 Write 1: Enabled Electrical Power 2 message
PGN65165 En-
able

46326 Gaseous Fuel Read/ 0: Disabled A trim that enables the Gaseous PC 3.x
Pressure Write 1: Enabled Fuel Pressure message
PGN65163 En-
able

46327 Fuel Informa- Read/ 0: Disabled A trim that enables the Fuel Infor- PC 3.x
tion 3 − Gas- Write 1: Enabled mation 3 − Gaseous message
eous
PGN64930 En-
able

273
Addr. Parameter Access Specifications Description Control
46328 Fuel Informa- Read/ 0: Disabled A trim that enables the Fuel Infor- PC 3.x
tion 2 − Gas- Write 1: Enabled mation 2 − Gaseous message
eous
PGN65153 En-
able
46332 Inlet/Exhaust Read/ 0: Disabled A trim that enables the Inlet/Ex- PC 3.x
Conditions Write 1: Enabled haust Conditions message
PGN65270 En-
able
46333 Knock Count 1 Read/ 0: Disabled A trim that enables Knock Count PC 3.x
PGN65336 En- Write 1: Enabled 1 message
able
46334 Knock Count 2 Read/ 0: Disabled A trim that enables Knock Count PC 3.x
PGN65337 En- Write 1: Enabled 2 message
able
46335 Knock Count 3 Read/ 0: Disabled A trim that enables Knock Count PC 3.x
PGN65338 En- Write 1: Enabled 3 message
able
46336 Knock Count 4 Read/ 0: Disabled A trim that enables Knock Count PC 3.x
PGN65339 En- Write 1: Enabled 4 message
able
46337 Knock Count 5 Read/ 0: Disabled A trim that enables Knock Count PC 3.x
PGN65340 En- Write 1: Enabled 5 message
able
46338 Ignition Timing Read/ 0: Disabled A trim that enables the Ignition PC 3.x
1 PGN65154 Write 1: Enabled Timing 1 message
Enable
46339 Ignition Timing Read/ 0: Disabled A trim that enables the Ignition PC 3.x
2 PGN65155 Write 1: Enabled Timing 2 message
Enable
46340 Ignition Timing Read/ 0: Disabled A trim that enables the Ignition PC 3.x
3 PGN65156 Write 1: Enabled Timing 3 message
Enable
46341 Ignition Timing Read/ 0: Disabled A trim that enables the Ignition PC 3.x
4 PGN65157 Write 1: Enabled Timing 4 message
Enable
46342 Ignition Timing Read/ 0: Disabled A trim that enables the Ignition PC 3.x
5 PGN65158 Write 1: Enabled Timing 5 message
Enable
46344 Start−Enable Read/ 0: Disable Remote MODBUS Start−Enable PC 3.x
(MODBUS In- Write 1: Enabled input.
put)

274
Addr. Parameter Access Specifications Description Control
46348 Target Speed Read Multiplier : 0.0625 The speed reference function de- PC 2.x
Only Offset: 0 sired speed before ramping PC3.x
Size (bits): 16
Sign: 32
Units: rpm
Lower Limit: NA
Upper Limit: NA
Default: NA
46349 Target Speed Read Multiplier : 0.0625 The speed reference function de- PC 2.x
Only Offset: 0 sired speed before ramping PC3.x
Size (bits): 16
Sign: 32
Units: rpm
Lower Limit: NA
Upper Limit: NA
Default: NA
46364 Modbus Regis- Read 0: Disable Modbus Register Read Only En- PC 2.x
ter Read Only Only 1: Enable able For TB15 Modbus Commu- PC3.x
Enable nication Port.
46365 Modbus Regis- Read 0: Disable Modbus Register Read Only En- PC3.x
ter Read Only Only 1: Enable able For J14 Modbus Commu-
Enable (J14) nication Port.
46366 Modbus Stop Read/ 0:01 Sets the Modbus number of stop PC 3.x
Bits (J14) Write 1:02 bits for this node Limited to 1 bit if
parity = Odd or Even
46367 Modbus Bus Read Multiplier: 1 The number of Modbus mes- PC 3.x
Message Count Only Offset: 0 sages with no response, for J14
(J14) Size (bits): 16 port only
Sign: U
Unit:
Lower Limit:
Upper Limit:
46368 Modbus CRC Read Multiplier: 1 The number of Modbus CRC er- PC 3.x
Error Count Only Offset: 0 rors, for J14 only.
(J14) Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit:
46369 Modbus Excep- Read Multiplier: 1 Modbus exception count, for J14 PC 3.x
tion Count Only Offset: 0 only.
(J14) Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit:

275
Addr. Parameter Access Specifications Description Control
46370 Modbus No Re- Read Multiplier: 1 Modbus no response count, for PC 3.x
sponse Count Only Offset: 0 J14 only.
(J14) Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit:
46371 Modbus Slave Read Multiplier: 1 The number of Modbus slave PC 3.x
Message Count Only Offset: 0 messages, for J14 only.
(J14) Size (bits): 16
Sign: U
Unit:
Lower Limit:
Upper Limit:
46372 Modbus Node Read/ Multiplier: 1 Sets the Modbus address for this PC 3.x
Address (J14) Write Offset: 0 node, for J14 only.
Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 247
46373 Modbus Baud Read/ 1.6666667 Sets the baud rate for Modbus PC 3.x
Rate (J14) Write 3.375 communications, for J14 only.
6.75
46374 Modbus Parity Read/ 0: Even Sets the Modbus parity for this PC 3.x
(J14) Write 1: Odd node, for J14 only.
2: None
46376 Modbus Baud Read/ 0: 2400 Baud Sets the Modbus baud rate. PC 2.x,
Rate Write 1: 4800 Baud PC 3.x
2: 9600 Baud
3: 19200 Baud
4: 38400 Baud
46377 Modbus Parity Read/ 0: Even Sets the Modbus parity for this PC 2.x,
Write 1: Odd node PC 3.x
2: None
46378 Modbus Node Read/ Multiplier: 1 Sets the Modbus address for this PC 2.x,
Address Write Offset: 0 node PC 3.x
Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 247
46379 Modbus Stop Read/ 0:01 Sets the Modbus number of stop PC 2.x,
Bits Write 1:02 bits for this node Limited to 1 bit if PC 3.x
parity = Odd or Even

276
Addr. Parameter Access Specifications Description Control
46380 HMI113 Fault 3 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46381 HMI113 Fault 3 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46382 HMI113 Fault 3 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46383 HMI113 Fault 3 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46384 HMI113 Fault 3 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46385 HMI113 Fault 3 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46386 HMI113 Fault 3 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

277
Addr. Parameter Access Specifications Description Control
46387 HMI113 Fault 3 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46388 HMI113 Fault 3 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46389 HMI113 Fault 3 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46390 HMI113 Fault 3 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46391 HMI113 Fault 3 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46392 HMI113 Fault 3 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46393 HMI113 Fault 3 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

278
Addr. Parameter Access Specifications Description Control
46394 HMI113 Fault 3 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46395 HMI113 Fault 3 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46396 HMI113 Fault 3 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46397 HMI113 Fault 3 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46398 HMI113 Fault 3 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46399 HMI113 Fault 3 Read/ Multiplier: 1 Twenty (20) character text string PC 2.x,
Text Write Offset: 0 to enter the configurable fault text PC 3.x
Size (bits): 168 for this fault.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46600 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

279
Addr. Parameter Access Specifications Description Control
46601 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46602 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46603 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46604 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46605 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46606 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46607 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

280
Addr. Parameter Access Specifications Description Control
46608 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46609 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46610 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46611 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46612 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46613 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46614 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

281
Addr. Parameter Access Specifications Description Control
46615 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46616 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46617 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46618 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46619 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46620 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46621 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

282
Addr. Parameter Access Specifications Description Control
46622 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46623 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46624 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46625 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46626 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46627 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46628 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

283
Addr. Parameter Access Specifications Description Control
46629 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46630 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46631 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46632 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46633 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46634 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46635 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

284
Addr. Parameter Access Specifications Description Control
46636 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46637 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46638 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46639 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46640 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46641 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46642 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

285
Addr. Parameter Access Specifications Description Control
46643 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46644 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46645 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46646 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46647 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46648 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46649 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

286
Addr. Parameter Access Specifications Description Control
46650 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46651 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46652 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46653 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46654 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46655 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46656 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

287
Addr. Parameter Access Specifications Description Control
46657 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46658 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46659 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
1 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46660 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46661 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46662 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46663 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

288
Addr. Parameter Access Specifications Description Control
46664 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46665 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46666 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46667 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46668 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46669 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46670 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

289
Addr. Parameter Access Specifications Description Control
46671 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46672 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46673 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46674 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46675 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46676 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46677 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

290
Addr. Parameter Access Specifications Description Control
46678 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46679 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
2 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46800 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46801 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46802 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46803 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46804 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

291
Addr. Parameter Access Specifications Description Control
46805 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46806 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46807 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46808 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46809 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46810 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46811 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

292
Addr. Parameter Access Specifications Description Control
46812 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46813 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46814 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46815 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46816 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46817 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46818 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

293
Addr. Parameter Access Specifications Description Control
46819 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46820 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46821 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46822 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46823 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46824 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46825 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

294
Addr. Parameter Access Specifications Description Control
46826 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46827 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46828 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46829 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46830 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46831 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46832 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

295
Addr. Parameter Access Specifications Description Control
46833 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46834 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46835 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46836 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46837 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46838 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46839 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

296
Addr. Parameter Access Specifications Description Control
46840 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46841 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46842 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46843 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46844 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46845 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46846 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

297
Addr. Parameter Access Specifications Description Control
46847 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46848 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46849 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46850 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46851 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46852 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46853 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

298
Addr. Parameter Access Specifications Description Control
46854 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46855 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46856 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46857 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46858 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46859 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46860 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

299
Addr. Parameter Access Specifications Description Control
46861 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46862 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46863 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46864 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46865 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46866 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46867 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

300
Addr. Parameter Access Specifications Description Control
46868 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46869 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46870 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46871 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46872 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46873 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46874 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

301
Addr. Parameter Access Specifications Description Control
46875 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46876 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46877 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46878 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46879 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46880 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46881 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

302
Addr. Parameter Access Specifications Description Control
46882 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46883 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46884 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46885 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46886 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46887 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46888 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

303
Addr. Parameter Access Specifications Description Control
46889 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46890 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46891 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46892 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46893 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46894 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46895 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

304
Addr. Parameter Access Specifications Description Control
46896 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46897 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46898 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46899 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
3 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46900 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
Unit:
46901 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46902 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

305
Addr. Parameter Access Specifications Description Control
46903 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46904 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46905 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46906 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46907 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46908 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46909 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

306
Addr. Parameter Access Specifications Description Control
46910 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46911 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46912 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46913 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46914 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46915 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46916 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

307
Addr. Parameter Access Specifications Description Control
46917 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46918 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46919 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
4 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46920 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46921 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46922 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46923 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

308
Addr. Parameter Access Specifications Description Control
46924 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46925 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46926 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46927 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46928 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46929 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

309
Addr. Parameter Access Specifications Description Control
46930 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46931 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46932 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46933 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46934 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46935 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

310
Addr. Parameter Access Specifications Description Control
46936 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46937 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46938 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46939 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
5 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46940 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46941 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46942 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

311
Addr. Parameter Access Specifications Description Control
46943 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46944 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46945 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46946 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46947 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46948 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46949 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

312
Addr. Parameter Access Specifications Description Control
46950 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46951 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46952 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46953 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46954 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46955 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46956 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

313
Addr. Parameter Access Specifications Description Control
46957 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46958 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46959 Aux101 1 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
6 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46960 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46961 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46962 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:
46963 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

314
Addr. Parameter Access Specifications Description Control
46964 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46965 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46966 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46967 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46968 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46969 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46970 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

315
Addr. Parameter Access Specifications Description Control
46971 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46972 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46973 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46974 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46975 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46976 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46977 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

316
Addr. Parameter Access Specifications Description Control
46978 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46979 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
7 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46980 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46981 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46982 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46983 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46984 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

317
Addr. Parameter Access Specifications Description Control
46985 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46986 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46987 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46988 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46989 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46990 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46991 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

318
Addr. Parameter Access Specifications Description Control
46992 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46993 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46994 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46995 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46996 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46997 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

46998 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

319
Addr. Parameter Access Specifications Description Control
46999 Aux101 0 Input Read/ Multiplier: 1 Twenty (20) character text field to PC 2.x,
8 Fault Text Write Offset: 0 allow for the entry of the dis- PC 3.x
Size (bits): 168 played configurable fault text.
Sign: C
Unit:
Lower Limit:
Upper Limit:

47002 GK1 (60Hz) Read Multiplier: 1 The governor 60Hz K1 gain ad- PC 2.x,
Only Offset: 0 just. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

47003 GK2 (60Hz) Read Multiplier: 1 The governor 60Hz integral gain PC 2.x,
Only Offset: 0 adjust. PC 3.x
Size (bits): 168
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

47004 GK3 (60Hz) Read Multiplier: 1 The governor 60Hz K3 gain ad- PC 2.x,
Only Offset: 0 just. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

47005 Governor Read Multiplier: 1.52587890625E−05 The governor 60Hz damping ad- PC 2.x,
Damping Effect Only Offset: 0 just. PC 3.x
(60Hz) Size (bits): 16
Sign: U
Unit:
Lower Limit: 0.6
Upper Limit: 0.95

47006 GK1 (50Hz) Read Multiplier: 1 The governor 50Hz K1 gain ad- PC 2.x,
Only Offset: 0 just. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

47007 GK2 (50Hz) Read Multiplier: 1 The governor 50Hz integral gain PC 2.x,
Only Offset: 0 adjust. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

320
Addr. Parameter Access Specifications Description Control
47008 GK3 (50Hz) Read Multiplier: 1 The governor 50Hz K3 gain ad- PC 2.x,
Only Offset: 0 just. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47009 Governor Read Multiplier: 1.52587890625E-05 The governor 50Hz damping ad- PC 2.x,
Damping Effect Only Offset: 0 just. PC 3.x
(50Hz) Size (bits): 16
Sign: U
Unit:
Lower Limit: 0.6
Upper Limit: 0.95
47010 GK1(Idle) Read Multiplier: 1 This trim is used to adjust gk1 in PC 2.x,
Only Offset: 0 idle mode. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47011 GK2(Idle) Read Multiplier: 1 This trim is used to adjust gk2 in PC 2.x,
Only Offset: 0 idle mode. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47014 Gain Window- Read 0: Disable Either enables or disables Gain PC 2.x,
ing Enable Only 1: Enable Windowing feature. PC 3.x
47015 GK1 Low(50Hz) Read Multiplier: 1 The governor 50Hz K1 low gain PC 2.x,
Only Offset: 0 adjust. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47016 GK1 Low(60Hz) Read Multiplier: 1 The governor 60Hz K1 low gain PC 2.x,
Only Offset: 0 adjust. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530

321
Addr. Parameter Access Specifications Description Control
47017 GK1 Read Multiplier: 1 The governor 50Hz K1 high gain PC 2.x,
High(50Hz) Only Offset: 0 adjust. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47018 GK1 Read Multiplier: 1 The governor 60Hz K1 high gain PC 2.x,
High(60Hz) Only Offset: 0 adjust. PC 3.x
Size (bits): 16
Sign: U
Unit:
Lower Limit: 0
Upper Limit: 65530
47019 Governor Read Multiplier: 1 The speed error higher limit. PC 2.x,
Speed Delta Only Offset: 0 PC 3.x
High Size (bits): 16
Sign: U
Unit:
Lower Limit: 50
Upper Limit: 1000
47020 Governor Read Multiplier: 1 The speed error lower limit. PC 2.x,
Speed Delta Only Offset: 0 PC 3.x
Low Size (bits): 16
Sign: U
Unit:
Lower Limit: 50
Upper Limit: 1000
47021 Intake Manifold Read 0: PGBU Either PGBU(Onan) or PC 2.x,
Temperature Only 1: EBU EBU(Cummins) sensor. PC 3.x
Sensor Type
47022 Intake Manifold Read 0: Disable Intake Manifold Temperature Sen- PC 2.x,
Temperature Only 1: Enable sor available or not. PC 3.x
Sensor Enable
47023 Oil Tempera- Read 0: PGBU Either PGBU(Onan) or PC 2.x,
ture Sensor Only 1: EBU EBU(Cummins) sensor. PC 3.x
Type
47024 Oil Tempera- Read 0: Disable High Oil Temperature Sensor PC 2.x,
ture Sensor En- Only 1: Enable available or not. PC 3.x
able
47025 AVR PWM Read Multiplier: 0.01 The AVR PWM software com- PC 2.x,
Command Only Offset: 0 mand. Linear relationship be- PC 3.x
Size (bits): 16 tween counts and % duty cycle
Sign: U with 10000 counts=100% duty
Unit: % cycle.
Lower Limit:
Upper Limit:
47026 Coolant Tem- Read 0: Disable Coolant Temperature 2 Enable PC3.x
perature 2 En- Only 1: Enable
able

322
Addr. Parameter Access Specifications Description Control
47027 Start Inhibit Read Multiplier : 0.05 Delay progress untill a fault is de- PC3.x
Delay Progress Only Offset: 0 clared for start inhibit
Size (bits): 16
Sign: U
Units: Seconds
Lower Limit: NA
Upper Limit: NA
Default: NA
47028 Genset Voltage Read 0: Close Indicates the Genset Voltage PC3.x
Sensing MCB Only 1: Open sensing MCB status.
status 2: Reserved
3: N/A
4: Network Failure
47029 Customer Gas Read 0: Open Indicates the status of the Cus- PC3.x
Valve Status Only 1: Closed tomer Gas Valve position.
2: Reserved
3: N/A
4: Network Failure
47030 Crankcase Read Multiplier : 0.01 Monitor point for the Crankcase PC 2.x
Pressure Ex- Only Offset: 0 Pressure with extended precision. PC3.x
tended Size (bits): 16
Sign: S
Units: psi
Lower Limit: −35.67
Upper Limit: 38
Default: NA

323
THIS PAGE LEFT INTENTIONALLY BLANK

324
3. PowerCommand 2.x/3.x Modbus Fault Status Bitmaps

Note: Earlier versions of software may not support all of the Modbus registers in the following table. If a particu-
lar register is not available in your installation, it is possible that the Modbus connection is working but the con-
troller software does not support that particular register.

Note: If an address or bit is not listed in this table it is not used.

Note: The external device can read 1−40 contiguous registers, write 1−40 contiguous registers, or read diagnos-
tic counters.

Addr. Bit# Name Fault Event Name Response Control


Code
40400 0 Fault Status 115 Engine Magnetic Crankshaft Speed/ Shutdown PC 2.x,
Bitmap 1 Position PC 3.x
40400 1 Fault Status 122 Intake Manifold 1 Pressure: Vtg Above Warning PC 2.x,
Bitmap 1 Normal PC 3.x
40400 2 Fault Status 123 Intake Manifold 1 Pressure: Vtg Below Warning PC 2.x,
Bitmap 1 Normal PC 3.x
40400 3 Fault Status 124 Intake Manifold 1 Pressure: Moderately Warning PC 2.x,
Bitmap 1 Severe PC 3.x
40400 4 Fault Status 135 Engine Oil Rifle Pressure 1: Vtg Above Warning PC 2.x,
Bitmap 1 Normal PC 3.x
40400 5 Fault Status 141 Engine Oil Rifle Pressure 1: Vtg Below Warning PC 2.x,
Bitmap 1 Normal PC 3.x
40400 6 Fault Status 143 Engine Oil Rifle Pressure −Moderately Warning PC 2.x,
Bitmap 1 Severe PC 3.x
40400 7 Fault Status 144 Engine Coolant Temp 1: Vtg Above Warning PC 2.x,
Bitmap 1 Normal PC 3.x
40400 8 Fault Status 145 Engine Coolant Temp 1: Vtg Below Warning PC 2.x,
Bitmap 1 Normal PC 3.x
40400 9 Fault Status 146 Engine Coolant Temp: Moderately Derate PC 2.x,
Bitmap 1 Above Normal PC 3.x
40400 10 Fault Status 151 Engine Coolant Temp: Severely Above Shutdown PC 2.x,
Bitmap 1 Normal PC 3.x
40400 11 Fault Status 153 Intake Manifold 1 Temp: Vtg Above Warning PC 2.x,
Bitmap 1 Normal PC 3.x
40400 12 Fault Status 154 Intake Manifold 1 Temp: Vtg Below Warning PC 2.x,
Bitmap 1 Normal PC 3.x
40400 13 Fault Status 155 Intake Manifold 1 Temp: Severely Shutdown PC 2.x,
Bitmap 1 Above Normal PC 3.x
40400 14 Fault Status 187 Sensor Supply 2: Vtg Below Normal Warning PC 2.x,
Bitmap 1 PC 3.x
40400 15 Fault Status 195 Coolant Level Sensor 1: Vtg Above Warning PC 2.x,
Bitmap 1 Normal PC 3.x

325
Addr. Bit# Name Fault Event Name Response Control
Code
40401 0 Fault Status 196 Coolant Level Sensor 1: Vtg Below Warning PC 2.x,
Bitmap 2 Normal PC 3.x
40401 1 Fault Status 197 Coolant Level: Below Normal − Moder- Warning PC 2.x,
Bitmap 2 ately Severe PC 3.x
40401 2 Fault Status 212 Engine Oil Temp Sensor 1: Vtg Above Warning PC 2.x,
Bitmap 2 Normal PC 3.x
40401 3 Fault Status 213 Engine Oil Temp Sensor 1: Vtg below Warning PC 2.x,
Bitmap 2 Normal PC 3.x
40401 4 Fault Status 214 Engine Oil Temp: Above Normal − Most Shutdown PC 2.x,
Bitmap 2 severe PC 3.x
40401 5 Fault Status 221 Barometric Pressure: Vtg Above Nor- Warning PC 2.x,
Bitmap 2 mal PC 3.x
40401 6 Fault Status 222 Barometric Pressure Sensor: Vtg Be- Warning PC 2.x,
Bitmap 2 low Normal PC 3.x
40401 7 Fault Status 223 Eng Oil Burn Valve Solenoid: Vtg Be- Warning PC 2.x,
Bitmap 2 low Normal PC 3.x
40401 8 Fault Status 224 Engine Oil Burn Valve Solenoid: Vtg Warning PC 2.x,
Bitmap 2 Above Normal PC 3.x
40401 9 Fault Status 227 Sensor Supply 2: Vtg Above Normal Warning PC 2.x,
Bitmap 2 PC 3.x
40401 10 Fault Status 228 Coolant Pressure: Below Normal−Most Shutdown PC 2.x,
Bitmap 2 Severe PC 3.x
40401 11 Fault Status 231 Coolant Pressure Sensor: Vtg Above Warning PC 2.x,
Bitmap 2 Normal PC 3.x
40401 12 Fault Status 232 Coolant Pressure Sensor: Vtg Below Warning PC 2.x,
Bitmap 2 Normal PC 3.x
40401 13 Fault Status 234 Engine Crankshaft Speed/Posn: Above Shutdown PC 2.x,
Bitmap 2 Normal PC 3.x
40401 14 Fault Status 235 Coolant Level: Below Normal−Most Se- Shutdown PC 2.x,
Bitmap 2 vere PC 3.x
40401 15 Fault Status 238 Sensor Supply 3: Vtg Below Normal Warning PC 2.x,
Bitmap 2 PC 3.x
40402 0 Fault Status 239 Voltage Supply C High Error Warning PC 2.x,
Bitmap 3 PC 3.x
40402 1 Fault Status 245 Radiator Fan Control Driver Low Error Warning PC 2.x,
Bitmap 3 PC 3.x
40402 2 Fault Status 261 Engine Fuel Temp: Above Normal− Warning PC 2.x,
Bitmap 3 Moderately Severe PC 3.x
40402 3 Fault Status 263 Engine Fuel Temp Sensor 1: Vtg Above Warning PC 2.x,
Bitmap 3 Normal PC 3.x
40402 4 Fault Status 265 Engine Fuel Temp Sensor 1: Vtg Below Warning PC 2.x,
Bitmap 3 Normal PC 3.x

326
Addr. Bit# Name Fault Event Name Response Control
Code
40402 5 Fault Status 266 Engine Fuel Temp: Above Normal− Shutdown PC 2.x,
Bitmap 3 Most severe PC 3.x
40402 6 Fault Status 271 Fuel Pump Pressurizing Assembly 1: Warning PC 2.x,
Bitmap 3 Vtg Below Normal PC 3.x
40402 7 Fault Status 272 Fuel Pump Pressurizing Assembly 1: Warning PC 2.x,
Bitmap 3 Vtg Above Normal PC 3.x
40402 8 Fault Status 281 APC_Diesel_CYL_PRS_IMBAL_Error Warning PC 2.x,
Bitmap 3 PC 3.x
40402 9 Fault Status 285 SAE J1939 Muxing PGN Timeout: Ab- Warning PC 2.x,
Bitmap 3 normal Update Rate PC 3.x
40402 10 Fault Status 286 SAE J1939 Muxing Config: Out of Cal- Warning PC 2.x,
Bitmap 3 ibration PC 3.x
40402 13 Fault Status 295 Ambient_Air_Press_KeyOn_Error Warning PC 2.x,
Bitmap 3 PC 3.x
40402 14 Fault Status 319 RTC PWR Intr: Data Erratic Intermittent Warning PC 2.x,
Bitmap 3 or Wrong PC 3.x
40402 15 Fault Status 322 Injector Solenoid Driver Cylinder 1: Un- Warning PC 2.x,
Bitmap 3 derCurrent PC 3.x
40403 0 Fault Status 323 Injector Solenoid Driver Cylinder 5: Un- Warning PC 2.x,
Bitmap 4 derCurrent PC 3.x
40403 1 Fault Status 324 Injector Solenoid Driver Cylinder 3: Un- Warning PC 2.x,
Bitmap 4 derCurrent PC 3.x
40403 2 Fault Status 325 Injector Solenoid Driver Cylinder 6: Un- Warning PC 2.x,
Bitmap 4 derCurrent PC 3.x
40403 3 Fault Status 331 Injector Solenoid Driver Cylinder 2: Un- Warning PC 2.x,
Bitmap 4 derCurrent PC 3.x
40403 4 Fault Status 332 Injector Solenoid Driver Cylinder 4: Un- Warning PC 2.x,
Bitmap 4 derCurrent PC 3.x
40403 6 Fault Status 342 Electronic Calibration Code: Out of Cal- Shutdown PC 2.x,
Bitmap 4 ibration PC 3.x
40403 7 Fault Status 343 Eng Ctrl: internal h/w failure−Bad De- Warning PC 2.x,
Bitmap 4 vice/Component PC 3.x
40403 8 Fault Status 351 Injector Power Supply: Bad Device/ Warning PC 2.x,
Bitmap 4 Component PC 3.x
40403 9 Fault Status 352 Sensor Supply 1: Vtg Below Normal Warning PC 2.x,
Bitmap 4 PC 3.x
40403 10 Fault Status 359 Fail To Start Fault Shutdown PC 2.x,
Bitmap 4 PC 3.x
40403 11 Fault Status 386 Sensor Supply 1: Vtg Above Normal Warning PC 2.x,
Bitmap 4 PC 3.x
40403 12 Fault Status 415 Eng Oil Rifle Pressure: Below Normal− Shutdown PC 2.x,
Bitmap 4 Most Severe PC 3.x

327
Addr. Bit# Name Fault Event Name Response Control
Code
40403 13 Fault Status 418 Water in Fuel Indicator: Above Normal− Warning PC 2.x,
Bitmap 4 Least Severe PC 3.x
40403 14 Fault Status 421 Eng Oil Temp: Above Normal−Moder- Warning PC 2.x,
Bitmap 4 ately Severe PC 3.x
40403 15 Fault Status 422 Coolant_Level_Reading_Incorrect Warning PC 2.x,
Bitmap 4 PC 3.x
40404 0 Fault Status 425 OIL_Temperature_In_Range_Error Warning PC 2.x,
Bitmap 5 PC 3.x
40404 1 Fault Status 426 J1939 Datalink: Data Erratic/Intermit- NONE PC 2.x,
Bitmap 5 tent/Wrong PC 3.x
40404 2 Fault Status 427 CAN Datalink Degraded Warning PC 2.x,
Bitmap 5 PC 3.x
40404 3 Fault Status 435 OIL_Pressure_Switch_Error Warning PC 2.x,
Bitmap 5 PC 3.x
40404 4 Fault Status 441 Low Battery Voltage Warning PC 2.x,
Bitmap 5 PC 3.x
40404 5 Fault Status 442 High Battery Voltage Warning PC 2.x,
Bitmap 5 PC 3.x
40404 6 Fault Status 449 Injector Metering Rail 1 Pressure: Shutdown PC 2.x,
Bitmap 5 Above Normal PC 3.x
40404 7 Fault Status 451 Injector Metering Rail 1 Pressure: Vtg Warning PC 2.x,
Bitmap 5 Above Normal PC 3.x
40404 8 Fault Status 452 Injector Metering Rail 1 Pressure: Vtg Warning PC 2.x,
Bitmap 5 Below Normal PC 3.x
40404 9 Fault Status 488 Intake Manifold 1 Temp: Above Nor- Derate PC 2.x,
Bitmap 5 mal−Moderate PC 3.x
40404 10 Fault Status 546 Fuel Delivery Pressure: Vtg Above Nor- Warning PC 2.x,
Bitmap 5 mal PC 3.x
40404 11 Fault Status 547 Fuel Delivery Pressure: Vtg Below Nor- Warning PC 2.x,
Bitmap 5 mal PC 3.x
40404 12 Fault Status 553 APC_Diesel_High_PRS_Error Warning PC 2.x,
Bitmap 5 PC 3.x
40404 13 Fault Status 554 APC_DieselL_PRS_SIR_Error Warning PC 2.x,
Bitmap 5 PC 3.x
40404 15 Fault Status 559 Injector Metering Rail 1 Pressure: Be- Warning PC 2.x,
Bitmap 5 low Normal PC 3.x
40405 1 Fault Status 611 Engine Shut Down Hot Condition Ex- Warning PC 2.x,
Bitmap 6 ists PC 3.x
40405 2 Fault Status 698 ECM Internal Temperature Low Error Warning PC 2.x,
Bitmap 6 PC 3.x
40405 3 Fault Status 689 Eng Crankshaft Speed/Pos Warning Warning PC 2.x,
Bitmap 6 PC 3.x

328
Addr. Bit# Name Fault Event Name Response Control
Code
40405 4 Fault Status 731 Eng Speed: Cam/Crankshaft Misalign- Warning PC 2.x,
Bitmap 6 ment PC 3.x
40405 5 Fault Status 2661 At Least One ACK: Most Severe Fault Shutdown PC 2.x,
Bitmap 6 PC 3.x
40405 6 Fault Status 781 CAN Datalink Failed Shutdown PC 2.x,
Bitmap 6 PC 3.x
40405 7 Fault Status 1117 Power Lost With Ignition On Warning PC 2.x,
Bitmap 6 PC 3.x
40405 8 Fault Status 1122 Rated to Idle Transition NONE PC 2.x,
Bitmap 6 PC 3.x
40405 9 Fault Status 1124 Delayed Shutdown Fault Warning PC 2.x,
Bitmap 6 PC 3.x
40405 10 Fault Status 1131 Battle Short Mode Active Warning PC 2.x,
Bitmap 6 PC 3.x
40405 11 Fault Status 1132 Controlled Shutdown In Process Warning PC 3.x
Bitmap 6
40405 13 Fault Status 1243 Engine Derate Derate PC 2.x,
Bitmap 6 PC 3.x
40405 14 Fault Status 1244 Engine Normal Shutdown Shutdown PC 2.x,
Bitmap 6 w/Cooldown PC 3.x
40405 15 Fault Status 1245 Engine Shutdown Shutdown PC 2.x,
Bitmap 6 PC 3.x
40406 0 Fault Status 1246 Unrecognized Engine Fault Warning PC 2.x,
Bitmap 7 PC 3.x
40406 1 Fault Status 1247 Engine Shutdown – Unannounced Shutdown PC 2.x,
Bitmap 7 PC 3.x
40406 2 Fault Status 1248 Engine Warning Warning PC 2.x,
Bitmap 7 PC 3.x
40406 3 Fault Status 1256 Ctrl Module ID Input State Warning Er- Warning PC 2.x,
Bitmap 7 ror PC 3.x
40406 4 Fault Status 1257 Ctrl Module ID I/P State shutdown Er- Shutdown PC 2.x,
Bitmap 7 ror PC 3.x
40406 5 Fault Status 1322 kW Load Setpoint OOR High Warning PC 3.x
Bitmap 7
40406 6 Fault Status 1323 kW Load Setpoint OOR Low Warning PC 3.x
Bitmap 7
40406 7 Fault Status 1324 kVAR Load Setpoint OOR High Warning PC 3.x
Bitmap 7
40406 8 Fault Status 1325 kVAR Load Setpoint OOR Low Warning PC 3.x
Bitmap 7
40406 9 Fault Status 1336 Cooldown Completed Fault Shutdown PC 2.x,
Bitmap 7 PC 3.x

329
Addr. Bit# Name Fault Event Name Response Control
Code
40406 10 Fault Status 1357 Eng Oil Lvl Remote Reservoir: Below Warning PC 2.x,
Bitmap 7 Normal PC 3.x
40406 11 Fault Status 219 Eng Oil Level Remote Reservoir: Least Warning PC 2.x,
Bitmap 7 Severe Level PC 3.x
40406 12 Fault Status 233 HT Coolant Pressure Moderate Low Warning PC 2.x,
Bitmap 7 PC 3.x
40406 13 Fault Status 254 FSO NON Low Control Error Shutdown PC 2.x,
Bitmap 7 PC 3.x
40406 14 Fault Status 686 Turbo 1 Speed Incorrect Warning PC 2.x,
Bitmap 7 PC 3.x
40406 15 Fault Status 697 ECM Internal Temperature High Error Warning PC 2.x,
Bitmap 7 PC 3.x
40407 0 Fault Status 1376 Eng Camshaft Speed/Pos Warning Warning PC 2.x,
Bitmap 8 PC 3.x
40407 1 Fault Status 3611 Custom Overcurrent Fault Warning PC 3.x
Bitmap 8
40407 2 Fault Status 3513 Negative Sequence Overcurrent Warning PC 3.x
Bitmap 8
40407 3 Fault Status 1416 Fail to Shutdown Warning PC 2.x,
Bitmap 8 PC 3.x
40407 4 Fault Status 1417 Power Down Failure Warning PC 2.x,
Bitmap 8 PC 3.x
40407 5 Fault Status 1433 Local E−Stop Shutdown PC 2.x,
Bitmap 8 PC 3.x
40407 6 Fault Status 1434 Remote E−Stop Shutdown PC 2.x,
Bitmap 8 PC 3.x
40407 7 Fault Status 1435 Low Coolant Temperature Warning PC 2.x,
Bitmap 8 PC 3.x
40407 8 Fault Status 1438 Fail To Crank Fault Shutdown PC 2.x,
Bitmap 8 PC 3.x
40407 9 Fault Status 1439 Low Fuel in Day Tank Warning PC 2.x,
Bitmap 8 PC 3.x
40407 10 Fault Status 1441 Low Fuel Level Warning PC 2.x,
Bitmap 8 PC 3.x
40407 11 Fault Status 1442 Weak Battery Warning PC 2.x,
Bitmap 8 PC 3.x
40407 12 Fault Status 1443 Dead Battery Shutdown PC 2.x,
Bitmap 8 PC 3.x
40407 13 Fault Status 1444 Overload Warning PC 2.x,
Bitmap 8 PC 3.x
40407 14 Fault Status 1445 Short Circuit Shutdown PC 2.x,
Bitmap 8 PC 3.x

330
Addr. Bit# Name Fault Event Name Response Control
Code
40407 15 Fault Status 1446 High AC Voltage Shutdown PC 2.x,
Bitmap 8 PC 3.x
40408 0 Fault Status 1447 Low AC Voltage Shutdown PC 2.x,
Bitmap 9 PC 3.x
40408 1 Fault Status 1448 Underfrequency Shutdown PC 2.x,
Bitmap 9 PC 3.x
40408 2 Fault Status 1449 Overfrequency Warning PC 2.x,
Bitmap 9 PC 3.x
40408 3 Fault Status 1459 Reverse kW Shutdown PC 2.x,
Bitmap 9 PC 3.x
40408 4 Fault Status 1461 Loss of Field Shutdown PC 2.x,
Bitmap 9 PC 3.x
40408 5 Fault Status 1463 Not In Auto NONE PC 2.x,
Bitmap 9 PC 3.x
40408 6 Fault Status 1464 Load Dump Warning PC 2.x,
Bitmap 9 PC 3.x
40408 7 Fault Status 1465 Ready To Load NONE PC 2.x,
Bitmap 9 PC 3.x
40408 8 Fault Status 1469 Speed/Frequency Mismatch Fault Shutdown PC 2.x,
Bitmap 9 PC 3.x
40408 9 Fault Status 1471 High Current Warning Warning PC 2.x,
Bitmap 9 PC 3.x
40408 10 Fault Status 1472 Overcurrent Shutdown Shutdown PC 2.x,
Bitmap 9 PC 3.x
40408 11 Fault Status 1483 Common Alarm None PC 2.x,
Bitmap 9 PC 3.x
40408 12 Fault Status 1548 Injector Solenoid Driver Cylinder 7: Un- Warning PC 2.x,
Bitmap 9 derCurrent PC 3.x
40408 13 Fault Status 1549 Injector Solenoid Driver Cylinder 8: Un- Warning PC 2.x,
Bitmap 9 derCurrent PC 3.x
40408 14 Fault Status 1551 Injector Solenoid Driver Cylinder 10: Warning PC 2.x,
Bitmap 9 UnderCurrent PC 3.x
40408 15 Fault Status 1552 Injector Solenoid Driver Cylinder 11: Warning PC 2.x,
Bitmap 9 UnderCurrent PC 3.x
40409 0 Fault Status 1553 Injector Solenoid Driver Cylinder 12: Warning PC 2.x,
Bitmap 10 UnderCurrent PC 3.x
40409 1 Fault Status 1554 Injector Solenoid Driver Cylinder 13: Warning PC 2.x,
Bitmap 10 UnderCurrent PC 3.x
40409 2 Fault Status 1555 Injector Solenoid Driver Cylinder 14: Warning PC 2.x,
Bitmap 10 UnderCurrent PC 3.x
40409 3 Fault Status 1556 Injector Solenoid Driver Cylinder 15: Warning PC 2.x,
Bitmap 10 UnderCurrent PC 3.x

331
Addr. Bit# Name Fault Event Name Response Control
Code
40409 4 Fault Status 1557 Injector Solenoid Driver Cylinder 16: Warning PC 2.x,
Bitmap 10 UnderCurrent PC 3.x
40409 7 Fault Status 1622 Injector Solenoid Driver Cylinder 9: Un- Warning PC 2.x,
Bitmap 10 derCurrent PC 3.x
40409 8 Fault Status 1689 Real Time Clock Power Interrupt Fault Warning PC 2.x,
Bitmap 10 PC 3.x
40409 9 Fault Status 1695 Sensor_Supply_5_Voltage_High_Error Warning PC 2.x,
Bitmap 10 PC 3.x
40409 10 Fault Status 1696 SENSOR_SUPPLY_5_VOLT- Warning PC 2.x,
Bitmap 10 AGE_LOW_ERROR PC 3.x
40409 11 Fault Status 1843 Crankcase Pressure: Vtg Above Nor- Warning PC 2.x,
Bitmap 10 mal PC 3.x
40409 12 Fault Status 1844 Crankcase Pressure: Vtg Below Nor- Warning PC 2.x,
Bitmap 10 mal PC 3.x
40409 13 Fault Status 1845 Water in Fuel Indicator: Vtg Above Nor- Warning PC 2.x,
Bitmap 10 mal PC 3.x
40409 14 Fault Status 1846 Water in Fuel Indicator: Vtg Below Nor- Warning PC 2.x,
Bitmap 10 mal PC 3.x
40409 15 Fault Status 1847 Eng Coolant Temp − Shutdown w/Cool Shutdown PC 2.x,
Bitmap 10 w/Cooldown PC 3.x
40410 0 Fault Status 1852 Water in Fuel Indicator: Above Normal− Warning PC 2.x,
Bitmap 11 Moderate PC 3.x
40410 1 Fault Status 1853 HMI113 Fault 1 NONE PC 2.x,
Bitmap 11 PC 3.x
40410 2 Fault Status 1854 HMI113 Fault 2 NONE PC 2.x,
Bitmap 11 PC 3.x
40410 3 Fault Status 1855 HMI113 Fault 3 NONE PC 2.x,
Bitmap 11 PC 3.x
40410 5 Fault Status 1891 Eng Oil Change Interval Warning PC 2.x,
Bitmap 11 PC 3.x
40410 6 Fault Status 1893 J39_EGR_Valve_Comm_Timeout_Er- Warning PC 2.x,
Bitmap 11 ror PC 3.x
40410 7 Fault Status 1894 J39_VGT_Comm_Timeout_Error Warning PC 2.x,
Bitmap 11 PC 3.x
40410 8 Fault Status 1896 EGR_DL_Valve_Stuck_Error Warning PC 2.x,
Bitmap 11 PC 3.x
40410 9 Fault Status 1899 EGR_Delta_P_IR_Low_Error Warning PC 2.x,
Bitmap 11 PC 3.x
40410 11 Fault Status 1912 Utility Loss Of Phase Warning PC 3.x
Bitmap 11
40410 12 Fault Status 1913 Genset Loss Of Phase Warning PC 3.x
Bitmap 11

332
Addr. Bit# Name Fault Event Name Response Control
Code
40410 13 Fault Status 1914 Utility Phase Rotation Warning PC 3.x
Bitmap 11
40410 14 Fault Status 1915 Genset Phase Rotation Warning PC 3.x
Bitmap 11
40410 15 Fault Status 1916 Sync Check OK NONE PC 3.x
Bitmap 11
40411 0 Fault Status 1917 High Fuel Level Warning PC 2.x,
Bitmap 12 PC 3.x
40411 1 Fault Status 1918 Very Low Fuel Level Shutdown PC 2.x,
Bitmap 12 PC 3.x
40411 2 Fault Status 1933 EGR_DL_Voltage_High_Error Warning PC 2.x,
Bitmap 12 PC 3.x
40411 3 Fault Status 1934 EGR_DL_Voltage_Low_Error Warning PC 2.x,
Bitmap 12 PC 3.x
40411 4 Fault Status 1935 EGR_DL_Command_Source_Error Warning PC 2.x,
Bitmap 12 PC 3.x
40411 5 Fault Status 1942 Beyond_THD_AZ_Error Warning PC 2.x,
Bitmap 12 PC 3.x
40411 6 Fault Status 1943 CBR_Density_Detrat_Error_ID NONE PC 2.x,
Bitmap 12 PC 3.x
40411 7 Fault Status 1944 HMI113 Output Configuration Fault Warning PC 2.x,
Bitmap 12 PC 3.x
40411 8 Fault Status 1961 EGR_DL_EDU_TMPTR_High_Error Warning PC 2.x,
Bitmap 12 PC 3.x
40411 9 Fault Status 1974 Crankcase_Pressure_Least_Sev_High Warning PC 2.x,
Bitmap 12 PC 3.x
40411 10 Fault Status 1992 Eng Crankshaft Speed/Posn: Above Shutdown PC 2.x,
Bitmap 12 Normal PC 3.x
40411 11 Fault Status 1999 Maximum Parallel Time Warning PC 3.x
Bitmap 12
40411 12 Fault Status 2185 Sensor Supply 4: Vtg Above Normal Warning PC 2.x,
Bitmap 12 PC 3.x
40411 13 Fault Status 2186 Sensor Supply 4: Vtg Below Normal Warning PC 2.x,
Bitmap 12 PC 3.x
40411 14 Fault Status 2215 Fuel Pump Delivery Pressure: Below Warning PC 2.x,
Bitmap 12 Normal PC 3.x
40411 15 Fault Status 2249 APC_Diesel_Low2_Prs_Error Warning PC 2.x,
Bitmap 12 PC 3.x
40412 0 Fault Status 2261 Fuel Pump Delivery Pressure: Above Warning PC 2.x,
Bitmap 13 Normal PC 3.x
40412 1 Fault Status 2262 Fuel Pump Delivery−Below Normal Warning PC 2.x,
Bitmap 13 PC 3.x

333
Addr. Bit# Name Fault Event Name Response Control
Code
40412 2 Fault Status 2265 Electric Lift Pump for Eng Fuel: Vtg Warning PC 2.x,
Bitmap 13 Above Normal PC 3.x
40412 3 Fault Status 2266 Electric Lift Pump for Eng Fuel: Vtg Be- Warning PC 2.x,
Bitmap 13 low Normal PC 3.x
40412 4 Fault Status 2292 APC_Diesel_Flow_High_Error Warning PC 2.x,
Bitmap 13 PC 3.x
40412 5 Fault Status 2293 APC_Diesel_Flow_Low_Error Warning PC 2.x,
Bitmap 13 PC 3.x
40412 6 Fault Status 2311 Electronic Fuel Injection Control Valve Warning PC 2.x,
Bitmap 13 PC 3.x
40412 7 Fault Status 2328 Utility Available NONE PC 3.x
Bitmap 13
40412 8 Fault Status 2331 Utility Undervoltage Warning PC 3.x
Bitmap 13
40412 9 Fault Status 2332 Utility Connected NONE PC 3.x
Bitmap 13
40412 10 Fault Status 2333 Genset Connected NONE PC 3.x
Bitmap 13
40412 11 Fault Status 2335 Excitation/Loss of AC Voltage Sensing Shutdown PC 2.x,
Bitmap 13 PC 3.x
40412 13 Fault Status 2342 Too Long in Idle Warning PC 2.x,
Bitmap 13 PC 3.x
40412 14 Fault Status 2358 Utility Overvoltage Warning PC 3.x
Bitmap 13
40412 15 Fault Status 2377 Fan Control: Vtg Above Normal Warning PC 2.x,
Bitmap 13 PC 3.x
40413 0 Fault Status 2396 Utility Breaker Fail To Close Warning PC 3.x
Bitmap 14
40413 1 Fault Status 2397 Utility Breaker Fail To Open Warning PC 3.x
Bitmap 14
40413 2 Fault Status 3226 Base Load NONE PC 3.x
Bitmap 14
40413 3 Fault Status 3227 Peak Shave NONE PC 3.x
Bitmap 14
40413 4 Fault Status 2555 GHC_Low_Voltage_Error_1 Warning PC 2.x,
Bitmap 14 PC 3.x
40413 5 Fault Status 2556 GHC_High_Voltage_Error_1 Warning PC 2.x,
Bitmap 14 PC 3.x
40413 6 Fault Status 2678 Charging Alternator Failure Fault Warning PC 2.x,
Bitmap 14 PC 3.x
40413 7 Fault Status 2965 Genset Available NONE PC 3.x
Bitmap 14

334
Addr. Bit# Name Fault Event Name Response Control
Code
40413 8 Fault Status 2971 Test/Exercise is Active Fault NONE PC 2.x,
Bitmap 14 PC 3.x
40413 9 Fault Status 2972 Field Overload Shutdown PC 2.x,
Bitmap 14 PC 3.x
40413 10 Fault Status 2973 Charge_Press_IR_Error Warning PC 2.x,
Bitmap 14 PC 3.x
40413 11 Fault Status 2943 Manual Switch Configuration Fault Warning PC 2.x,
Bitmap 14 PC 3.x
40413 12 Fault Status 2944 Auto Switch Configuration Fault Warning PC 2.x,
Bitmap 14 PC 3.x
40413 13 Fault Status 2914 Genset AC Meter Failed Shutdown PC 2.x,
Bitmap 14 PC 3.x
40413 14 Fault Status 2915 Genset Bus AC Meter Failed Warning PC 3.x
Bitmap 14
40413 15 Fault Status 2916 Utility AC Meter Failed Warning PC 3.x
Bitmap 14
40414 0 Fault Status 2814 Genset CT Ratio Too Small Shutdown PC 2.x,
Bitmap 15 PC 3.x
40414 1 Fault Status 2815 Genset CT Ratio Too Large Warning PC 2.x,
Bitmap 15 PC 3.x
40414 2 Fault Status 2816 Genset PT Ratio Too Small Shutdown PC 2.x,
Bitmap 15 PC 3.x
40414 3 Fault Status 2817 Genset PT Ratio Too Large Warning PC 2.x,
Bitmap 15 PC 3.x
40414 4 Fault Status 2818 Genset Bus PT Ratio Too Small Shutdown PC 3.x
Bitmap 15
40414 5 Fault Status 2819 Genset Bus PT Ratio Too Large Warning PC 3.x
Bitmap 15
40414 6 Fault Status 2821 Utility PT Ratio Too Small Shutdown PC 3.x
Bitmap 15
40414 7 Fault Status 2822 Utility PT Ratio Too Large Warning PC 3.x
Bitmap 15
40414 8 Fault Status 2619 Aux101 0 Input 1 Fault Warning PC 2.x,
Bitmap 15 PC 3.x
40414 9 Fault Status 2621 Aux101 0 Input 2 Fault Warning PC 2.x,
Bitmap 15 PC 3.x
40414 10 Fault Status 2622 Aux101 0 Input 3 Fault Warning PC 2.x,
Bitmap 15 PC 3.x
40414 11 Fault Status 2623 Aux101 0 Input 4 Fault Warning PC 2.x,
Bitmap 15 PC 3.x
40414 12 Fault Status 2624 Aux101 0 Input 5 Fault Warning PC 2.x,
Bitmap 15 PC 3.x

335
Addr. Bit# Name Fault Event Name Response Control
Code
40414 13 Fault Status 2625 Aux101 0 Input 6 Fault Warning PC 2.x,
Bitmap 15 PC 3.x
40414 14 Fault Status 2626 Aux101 0 Input 7 Fault Warning PC 2.x,
Bitmap 15 PC 3.x
40414 15 Fault Status 2627 Aux101 0 Input 8 Fault Warning PC 2.x,
Bitmap 15 PC 3.x
40415 0 Fault Status 2882 Aux101 1 Input 1 Fault Warning PC 2.x,
Bitmap 16 PC 3.x
40415 1 Fault Status 2883 Aux101 1 Input 2 Fault Warning PC 2.x,
Bitmap 16 PC 3.x
40415 2 Fault Status 2884 Aux101 1 Input 3 Fault Warning PC 2.x,
Bitmap 16 PC 3.x
40415 3 Fault Status 2885 Aux101 1 Input 4 Fault Warning PC 2.x,
Bitmap 16 PC 3.x
40415 4 Fault Status 2886 Aux101 1 Input 5 Fault Warning PC 2.x,
Bitmap 16 PC 3.x
40415 5 Fault Status 2887 Aux101 1 Input 6 Fault Warning PC 2.x,
Bitmap 16 PC 3.x
40415 6 Fault Status 2888 Aux101 1 Input 7 Fault Warning PC 2.x,
Bitmap 16 PC 3.x
40415 7 Fault Status 2889 Aux101 1 Input 8 Fault Warning PC 2.x,
Bitmap 16 PC 3.x
40415 8 Fault Status 2628 Aux102 0 Expansion Input 9 Fault Warning PC 2.x,
Bitmap 16 PC 3.x
40415 9 Fault Status 2629 Aux102 0 Expansion Input 10 Fault Warning PC 2.x,
Bitmap 16 PC 3.x
40415 10 Fault Status 2631 Aux102 0 Expansion Input 11 Fault Warning PC 2.x,
Bitmap 16 PC 3.x
40415 11 Fault Status 2632 Aux102 0 Expansion Input 12 Fault Warning PC 2.x,
Bitmap 16 PC 3.x
40415 12 Fault Status 2891 Aux102 1 Expansion Input 9 Fault Warning PC 2.x,
Bitmap 16 PC 3.x
40415 13 Fault Status 2892 Aux102 1 Expansion Input 10 Fault Warning PC 2.x,
Bitmap 16 PC 3.x
40415 14 Fault Status 2893 Aux102 1 Expansion Input 11 Fault Warning PC 2.x,
Bitmap 16 PC 3.x
40415 15 Fault Status 2894 Aux102 1 Expansion Input 12 Fault Warning PC 2.x,
Bitmap 16 PC 3.x
40416 0 Fault Status 2895 PCCnet Device Failed Warning Warning PC 2.x,
Bitmap 17 PC 3.x
40416 1 Fault Status 2896 PCCnet Device Failed Shutdown Shutdown PC 2.x,
Bitmap 17 PC 3.x

336
Addr. Bit# Name Fault Event Name Response Control
Code
40416 2 Fault Status 2917 Genset Bus Voltage OOR Warning Warning PC 3.x
Bitmap 17
40416 3 Fault Status 2918 Utility Voltage OOR Warning Warning PC 3.x
Bitmap 17
40416 4 Fault Status 2919 Utility Current OOR Warning Warning PC 3.x
Bitmap 17
40416 5 Fault Status 2921 Genset Bus Current OOR Warning Warning PC 3.x
Bitmap 17
40416 6 Fault Status 2922 Genset Neutral Current OOR Warning Warning PC 3.x
Bitmap 17
40416 7 Fault Status 2923 Genset Bus kW OOR Warning Warning PC 3.x
Bitmap 17
40416 8 Fault Status 2924 Genset Bus kVAR OOR Warning Warning PC 3.x
Bitmap 17
40416 9 Fault Status 2925 Genset Bus kVA OOR Warning Warning PC 3.x
Bitmap 17
40416 10 Fault Status 2926 Utility kW OOR Warning Warning PC 3.x
Bitmap 17
40416 11 Fault Status 2927 Utility kVAR OOR Warning Warning PC 3.x
Bitmap 17
40416 12 Fault Status 2928 Utility kVA OOR Warning Warning PC 3.x
Bitmap 17
40416 13 Fault Status 3599 Ground Current OOR Warning Warning PC 3.x
Bitmap 17
40416 14 Fault Status 2931 AUX101 Device ID Fault Shutdown PC 2.x,
Bitmap 17 PC 3.x
40416 15 Fault Status 2779 Utility Unloaded Event NONE PC 3.x
Bitmap 17
40417 3 Fault Status 2932 AUX101 Oil Temp OOR Hi Warning PC 2.x,
Bitmap 18 PC 3.x
40417 4 Fault Status 2933 AUX101 Oil Temp OOR Low Warning PC 2.x,
Bitmap 18 PC 3.x
40417 5 Fault Status 2657 Exhaust Stack Temp 1 OOR High Warning PC 2.x,
Bitmap 18 PC 3.x
40417 6 Fault Status 2947 Exhaust Stack Temp 1 OOR Low Warning PC 2.x,
Bitmap 18 PC 3.x
40417 7 Fault Status 2949 High Exhaust Stack Temperature 1 Warning PC 2.x,
Bitmap 18 PC 3.x
40417 8 Fault Status 2653 Exhaust Stack Temp 2 OOR High Warning PC 2.x,
Bitmap 18 PC 3.x
40417 9 Fault Status 2946 Exhaust Stack Temp 2 OOR Low Warning PC 2.x,
Bitmap 18 PC 3.x

337
Addr. Bit# Name Fault Event Name Response Control
Code
40417 10 Fault Status 2948 High Exhaust Stack Temperature 2 Warning PC 2.x,
Bitmap 18 PC 3.x
40417 11 Fault Status 2934 Ambient Temp OOR High Warning PC 2.x,
Bitmap 18 PC 3.x
40417 12 Fault Status 2935 Ambient Temp OOR Low Warning PC 2.x,
Bitmap 18 PC 3.x
40417 13 Fault Status 2936 Fuel Level OOR High Warning PC 2.x,
Bitmap 18 PC 3.x
40417 14 Fault Status 2937 Fuel Level OOR Low Warning PC 2.x,
Bitmap 18 PC 3.x
40417 15 Fault Status 2951 Alternator Temp 1 OOR High Warning PC 2.x,
Bitmap 18 PC 3.x
40418 0 Fault Status 2952 Alternator Temp 1 OOR Low Warning PC 2.x,
Bitmap 19 PC 3.x
40418 1 Fault Status 2953 High Alternator Temp 1 Warning PC 2.x,
Bitmap 19 PC 3.x
40418 2 Fault Status 2954 Alternator Temp 2 OOR High Warning PC 2.x,
Bitmap 19 PC 3.x
40418 3 Fault Status 2955 Alternator Temp 2 OOR Low Warning PC 2.x,
Bitmap 19 PC 3.x
40418 4 Fault Status 2956 High Alternator Temp 2 Warning PC 2.x,
Bitmap 19 PC 3.x
40418 5 Fault Status 2957 Alternator Temp 3 OOR High Warning PC 2.x,
Bitmap 19 PC 3.x
40418 6 Fault Status 2958 Alternator Temp 3 OOR Low Warning PC 2.x,
Bitmap 19 PC 3.x
40418 7 Fault Status 2959 High Alternator Temp 3 Warning PC 2.x,
Bitmap 19 PC 3.x
40418 8 Fault Status 2992 Intake Manifold Temp 1 OOR High Warning PC 2.x,
Bitmap 19 PC 3.x
40418 9 Fault Status 2978 Intake Manifold Temp 1 OOR Low Warning PC 2.x,
Bitmap 19 PC 3.x
40418 10 Fault Status 2981 Drive End Bearing Temp OOR High Warning PC 2.x,
Bitmap 19 PC 3.x
40418 11 Fault Status 2982 Drive End Bearing Temp OOR Low Warning PC 2.x,
Bitmap 19 PC 3.x
40418 12 Fault Status 2983 High Drive End Bearing Temperature Warning PC 2.x,
Bitmap 19 PC 3.x
40418 13 Fault Status 2984 Non−Drive End Bearing Temp OOR Warning PC 2.x,
Bitmap 19 High PC 3.x
40418 14 Fault Status 2985 Non−Drive End Bearing Temp OOR Warning PC 2.x,
Bitmap 19 Low PC 3.x

338
Addr. Bit# Name Fault Event Name Response Control
Code
40418 15 Fault Status 2986 High Non−Drive End Bearing Tempera- Warning PC 2.x,
Bitmap 19 ture PC 3.x
40419 0 Fault Status 2945 Rupture Basin Warning PC 2.x,
Bitmap 20 PC 3.x
40419 1 Fault Status 2979 High Alternator Temp Switch fault Warning PC 2.x,
Bitmap 20 PC 3.x
40419 2 Fault Status 2993 Battery Charger Failed Fault Warning PC 2.x,
Bitmap 20 PC 3.x
40419 3 Fault Status 2938 Earth/Ground Fault Warning PC 2.x,
Bitmap 20 PC 3.x
40419 4 Fault Status 2939 Modbus Failure Fault Warning PC 2.x,
Bitmap 20 PC 3.x
40419 5 Fault Status 2977 Low Coolant Level #2 Warning PC 2.x,
Bitmap 20 PC 3.x
40419 6 Fault Status 1978 Speed Bias OOR High Warning PC 2.x,
Bitmap 20 PC 3.x
40419 7 Fault Status 2541 Voltage Bias OOR Low Warning PC 2.x,
Bitmap 20 PC 3.x
40419 8 Fault Status 2539 Voltage Bias OOR High Warning PC 2.x,
Bitmap 20 PC 3.x
40419 9 Fault Status 1573 Configurable Input #1 NONE PC 2.x,
Bitmap 20 PC 3.x
40419 10 Fault Status 1312 Configurable Input #2 NONE PC 2.x,
Bitmap 20 PC 3.x
40419 11 Fault Status 1317 Configurable Input #13 NONE PC 2.x,
Bitmap 20 PC 3.x
40419 12 Fault Status 1318 Configurable Input #14 NONE PC 2.x,
Bitmap 20 PC 3.x
40419 13 Fault Status 1979 Speed Bias OOR Low Warning PC 2.x,
Bitmap 20 PC 3.x
40419 14 Fault Status 236 Both Engine Speed Signals Lost: Most Shutdown PC 2.x,
Bitmap 20 Severe Level PC 3.x
40419 15 Fault Status 3629 Less Severe Response−Warning Warning PC 3.x
Bitmap 20
40420 0 Fault Status 3631 Most Severe−Shutdown Shutdown PC 3.x
Bitmap 21
40427 1 Fault Status 4872 System Network Failure Warning PC 3.x
Bitmap 26
40427 2 Fault Status 4873 Genset Failed to Come Online Warning PC 3.x
Bitmap 26
40427 3 Fault Status 4874 Load Demand SW Version Incompati- Warning PC 3.x
Bitmap 26 bility

339
Addr. Bit# Name Fault Event Name Response Control
Code
40427 4 Fault Status 4875 Genset Ineligible for Load Demand None PC 3.x
Bitmap 26
40427 5 Fault Status 4876 Genset Lost on System Network Warning PC 3.x
Bitmap 26
40427 6 Fault Status 4877 System Settings Not Synchronized Warning PC 3.x
Bitmap 26
40427 7 Fault Status 4878 Check System Network Installation Warning PC 3.x
Bitmap 26
40427 8 Fault Status 4879 Load Demand Setup Error Warning PC 3.x
Bitmap 26
40427 9 Fault Status 4881 System Genset ID Conflict Warning PC 3.x
Bitmap 26
40427 10 Fault Status 4882 Genset Bus Overload Warning PC 3.x
Bitmap 26
40427 11 Fault Status 5145 Load Demand Genset Bus Failure Warning PC 3.x
Bitmap 26
40430 0 Event Status 1540 Common Warning NONE PC 2.x,
Bitmap 1 PC 3.x
40430 1 Event Status 1541 Common Shutdown NONE PC 2.x,
Bitmap 1 PC 3.x
40431 0 Fault Status 121 EPS Main Channel Lost Error Warning PC 3.x
Gas Bitmap 1
40431 1 Fault Status 136 Oil Inlet Pressure High Error Warning PC 3.x
Gas Bitmap 1
40431 2 Fault Status 137 Oil Inlet Pressure Low Error Warning PC 3.x
Gas Bitmap 1
40431 3 Fault Status 142 Oil Overpressure Error Warning PC 3.x
Gas Bitmap 1
40431 4 Fault Status 156 Intake Manifold Temp 2 OORH Warning PC 3.x
Gas Bitmap 1
40431 5 Fault Status 157 Intake Manifold Temp 2 OORL Warning PC 3.x
Gas Bitmap 1
40431 6 Fault Status 158 Intake Manifold Temp 2 High Shutdown PC 3.x
Gas Bitmap 1
40431 7 Fault Status 159 Intake Manifold 3 Temp OORH Warning PC 3.x
Gas Bitmap 1
40431 8 Fault Status 161 Intake Manifold 3 Temp OORL Warning PC 3.x
Gas Bitmap 1
40431 9 Fault Status 162 Intake Manifold 3 Temp High Shutdown PC 3.x
Gas Bitmap 1
40431 10 Fault Status 163 Intake Manifold 4 Temp OORH Warning PC 3.x
Gas Bitmap 1

340
Addr. Bit# Name Fault Event Name Response Control
Code
40431 11 Fault Status 164 Intake Manifold 4 Temp OORL Warning PC 3.x
Gas Bitmap 1
40431 12 Fault Status 165 Intake Manifold 4 Temp High Shutdown PC 3.x
Gas Bitmap 1
40431 13 Fault Status 175 Throttle_Driver_Feedback_High_Error Shutdown PC 3.x
Gas Bitmap 1 w/Cooldown
40431 14 Fault Status 176 Throttle_Driver_Feedback_Low_Error Shutdown PC 3.x
Gas Bitmap 1 w/Cooldown
40431 15 Fault Status 177 Throttle_Actuator_Error Shutdown PC 3.x
Gas Bitmap 1 w/Cooldown
40432 2 Fault Status 244 Red Stop Lamp Driver OORL Warning PC 3.x
Gas Bitmap 2
40432 3 Fault Status 246 Exhaust Gas Temp Sensor 1 OORH Warning PC 3.x
Gas Bitmap 2
40432 4 Fault Status 247 Exhaust Gas Temp Sensor 1 OORL Warning PC 3.x
Gas Bitmap 2
40432 5 Fault Status 248 Exhaust Gas Temp Sensor 1 High Warning PC 3.x
Gas Bitmap 2
40432 6 Fault Status 253 Oil Level Low Error Shutdown PC 3.x
Gas Bitmap 2 w/Cooldown
40432 8 Fault Status 277 Fuel Control Valve Out of Adj Warning PC 3.x
Gas Bitmap 2
40432 9 Fault Status 346 Powerdown Data Lost Error Warning PC 3.x
Gas Bitmap 2
40432 10 Fault Status 354 Manifold_Absolute_Pres- Warning PC 3.x
Gas Bitmap 2 sure_1_High_Error
40432 11 Fault Status 355 Manifold_Absolute_Pres- Warning PC 3.x
Gas Bitmap 2 sure_1_Low_Error
40432 12 Fault Status 412 J1708 Link Cannot Transmit Error NONE PC 3.x
Gas Bitmap 2
40432 13 Fault Status 414 J1708 Link Not Fast Enough Error NONE PC 3.x
Gas Bitmap 2
40432 14 Fault Status 453 Gas_Mass_Flow_High_Error Warning PC 3.x
Gas Bitmap 2
40432 15 Fault Status 454 Gas_Mass_Flow_Low_Error Warning PC 3.x
Gas Bitmap 2
40433 0 Fault Status 458 Spark_Timing_B_Error Shutdown PC 3.x
Gas Bitmap 3 w/Cooldown
40433 1 Fault Status 459 Spark_Timing_A_Error Shutdown PC 3.x
Gas Bitmap 3 w/Cooldown
40433 2 Fault Status 461 Spark_Reference_B_Error Shutdown PC 3.x
Gas Bitmap 3 w/Cooldown

341
Addr. Bit# Name Fault Event Name Response Control
Code
40433 3 Fault Status 462 Spark_Reference_A_Error Shutdown PC 3.x
Gas Bitmap 3 w/Cooldown
40433 4 Fault Status 477 Isolated Battery Voltage Low Error Warning PC 3.x
Gas Bitmap 3
40433 5 Fault Status 478 Isolated Battery Voltage High Error Warning PC 3.x
Gas Bitmap 3
40433 6 Fault Status 512 Throttle Pos 1 Feedback OOR High Warning PC 3.x
Gas Bitmap 3
40433 7 Fault Status 513 Throttle Pos 1 Feedback OOR Low Warning PC 3.x
Gas Bitmap 3
40433 8 Fault Status 557 Fuel Control Valve 2 OORH Shutdown PC 3.x
Gas Bitmap 3 w/Cooldown
40433 9 Fault Status 558 Fuel Control Valve 2 OORL Warning PC 3.x
Gas Bitmap 3
40433 10 Fault Status 561 Heavy_Knock_Error_1_(A1) Shutdown PC 3.x
Gas Bitmap 3 w/Cooldown
40433 11 Fault Status 562 Heavy_Knock_Error_2_(B1) Shutdown PC 3.x
Gas Bitmap 3 w/Cooldown
40433 12 Fault Status 563 Heavy_Knock_Error_3_(A2) Shutdown PC 3.x
Gas Bitmap 3 w/Cooldown
40433 13 Fault Status 564 Heavy_Knock_Error_4_(B2) Shutdown PC 3.x
Gas Bitmap 3 w/Cooldown
40433 14 Fault Status 565 Heavy_Knock_Error_5_(A3) Shutdown PC 3.x
Gas Bitmap 3 w/Cooldown
40433 15 Fault Status 566 Heavy_Knock_Error_6_(B3) Shutdown PC 3.x
Gas Bitmap 3 w/Cooldown
40434 0 Fault Status 567 Heavy_Knock_Error_7_(A4) Shutdown PC 3.x
Gas Bitmap 4 w/Cooldown
40434 1 Fault Status 568 Heavy_Knock_Error_8_(B4) Shutdown PC 3.x
Gas Bitmap 4 w/Cooldown
40434 2 Fault Status 569 Heavy_Knock_Error_9_(A5) Shutdown PC 3.x
Gas Bitmap 4 w/Cooldown
40434 3 Fault Status 571 Knock Cyl 1 (A1) OORL Warning PC 3.x
Gas Bitmap 4
40434 4 Fault Status 572 Knock Cyl 2 (B1) OORL Warning PC 3.x
Gas Bitmap 4
40434 5 Fault Status 573 Knock Cyl 3 (A2) OORL Warning PC 3.x
Gas Bitmap 4
40434 6 Fault Status 574 Knock Cyl 4 (B2) OORL Warning PC 3.x
Gas Bitmap 4
40434 7 Fault Status 575 Knock Cyl 5 (A3) OORL Warning PC 3.x
Gas Bitmap 4

342
Addr. Bit# Name Fault Event Name Response Control
Code
40434 8 Fault Status 576 Knock Cyl 6 (B3) OORL Warning PC 3.x
Gas Bitmap 4
40434 9 Fault Status 577 Knock Cyl 7 (A4) OORL Warning PC 3.x
Gas Bitmap 4
40434 10 Fault Status 578 Knock Cyl 8 (B4) OORL Warning PC 3.x
Gas Bitmap 4
40434 11 Fault Status 579 Knock Cyl 9 (A5) OORL Warning PC 3.x
Gas Bitmap 4
40434 12 Fault Status 584 High Side DRV3 High Control Error Warning PC 3.x
Gas Bitmap 4
40434 13 Fault Status 585 High Side DRV3 Low Control Error Warning PC 3.x
Gas Bitmap 4
40434 14 Fault Status 591 Exhaust_Backpressure_High_Error Warning PC 3.x
Gas Bitmap 4
40434 15 Fault Status 592 Exhaust_Backpressure_Low_Error Warning PC 3.x
Gas Bitmap 4
40435 0 Fault Status 595 Turbo 1 Overspeed Warning Error Warning PC 3.x
Gas Bitmap 5
40435 1 Fault Status 618 Turbo 1 Inlet Pressure High Warning PC 3.x
Gas Bitmap 5
40435 2 Fault Status 619 Turbo 2 Inlet Press High Warning PC 3.x
Gas Bitmap 5
40435 3 Fault Status 641 Exhaust Temp 1 (A1) High Serious Er- Shutdown PC 3.x
Gas Bitmap 5 ror w/Cooldown
40435 4 Fault Status 642 Exhaust Temp 3 (A2) High Serious Er- Shutdown PC 3.x
Gas Bitmap 5 ror w/Cooldown
40435 5 Fault Status 643 Exhaust Temp 5 (A3) High Serious Er- Shutdown PC 3.x
Gas Bitmap 5 ror w/Cooldown
40435 6 Fault Status 644 Exhaust Temp 7 (A4) High Serious Er- Shutdown PC 3.x
Gas Bitmap 5 ror w/Cooldown
40435 7 Fault Status 645 Exhaust Temp 9 (A5) High Serious Er- Shutdown PC 3.x
Gas Bitmap 5 ror w/Cooldown
40435 8 Fault Status 646 Exhaust Temp 11 (A6) High Serious Er- Shutdown PC 3.x
Gas Bitmap 5 ror w/Cooldown
40435 9 Fault Status 647 Exhaust Temp 13 (A7) High Serious Shutdown PC 3.x
Gas Bitmap 5 Error w/Cooldown
40435 10 Fault Status 648 Exhaust Temp 15 (A8) High Serious Shutdown PC 3.x
Gas Bitmap 5 Error w/Cooldown
40435 11 Fault Status 651 Exhaust Temp 17 (A9) High Serious Shutdown PC 3.x
Gas Bitmap 5 Error w/Cooldown
40435 12 Fault Status 652 Exhaust Temp 2 (B1) High Serious Er- Shutdown PC 3.x
Gas Bitmap 5 ror w/Cooldown

343
Addr. Bit# Name Fault Event Name Response Control
Code
40435 13 Fault Status 653 Exhaust Temp 4 (B2) High Serious Er- Shutdown PC 3.x
Gas Bitmap 5 ror w/Cooldown
40435 14 Fault Status 654 Exhaust Temp 6 (B3) High Serious Er- Shutdown PC 3.x
Gas Bitmap 5 ror w/Cooldown
40435 15 Fault Status 655 Exhaust Temp 8 (B4) High Serious Er- Shutdown PC 3.x
Gas Bitmap 5 ror w/Cooldown
40436 0 Fault Status 656 Exhaust Temp 10 (B5) High Serious Shutdown PC 3.x
Gas Bitmap 6 Error w/Cooldown
40436 1 Fault Status 657 Exhaust Temp 12 (B6) High Serious Shutdown PC 3.x
Gas Bitmap 6 Error w/Cooldown
40436 2 Fault Status 658 Exhaust Temp 14 (B7) High Serious Shutdown PC 3.x
Gas Bitmap 6 Error w/Cooldown
40436 3 Fault Status 671 Exhaust Gas Temp Cyl 1 (A1) OORL Warning PC 3.x
Gas Bitmap 6
40436 4 Fault Status 672 Exhaust Gas Temp Cyl 3 (A2) OORL Warning PC 3.x
Gas Bitmap 6
40436 5 Fault Status 673 Exhaust Gas Temp Cyl 5 (A3) OORL Warning PC 3.x
Gas Bitmap 6
40436 6 Fault Status 674 Exhaust Gas Temp Cyl 7 (A4) OORL Warning PC 3.x
Gas Bitmap 6
40436 7 Fault Status 675 Exhaust Gas Temp Cyl 9 (A5) OORL Warning PC 3.x
Gas Bitmap 6
40436 8 Fault Status 676 Exhaust Gas Temp Cyl 11 (A6) OORL Warning PC 3.x
Gas Bitmap 6
40436 9 Fault Status 677 Exhaust Gas Temp Cyl 13 (A7) OORL Warning PC 3.x
Gas Bitmap 6
40436 10 Fault Status 678 Exhaust Gas Temp Cyl 15 (A8) OORL Warning PC 3.x
Gas Bitmap 6
40436 11 Fault Status 683 Turbo 2 Speed Moderate High Warning PC 3.x
Gas Bitmap 6
40436 12 Fault Status 684 Turbo 2 Speed Moderate Low Warning PC 3.x
Gas Bitmap 6
40436 13 Fault Status 685 Turbo 2 Speed Incorrect Warning PC 3.x
Gas Bitmap 6
40436 15 Fault Status 687 Turbo 1 Speed Low Warning PC 3.x
Gas Bitmap 6
40437 2 Fault Status 721 Exhaust Gas Temp 2 (B1) OORL Warning PC 3.x
Gas Bitmap 7
40437 3 Fault Status 722 Exhaust Gas Temp 4 (B2) OORL Warning PC 3.x
Gas Bitmap 7
40437 4 Fault Status 723 Exhaust Gas Temp 6 (B3) OORL Warning PC 3.x
Gas Bitmap 7

344
Addr. Bit# Name Fault Event Name Response Control
Code
40437 5 Fault Status 724 Exhaust Gas Temp 8 (B4) OORL Warning PC 3.x
Gas Bitmap 7
40437 6 Fault Status 725 Exhaust Gas Temp 10 (B5) OORL Warning PC 3.x
Gas Bitmap 7
40437 7 Fault Status 726 Exhaust Gas Temp 12 (B6) OORL Warning PC 3.x
Gas Bitmap 7
40437 8 Fault Status 727 Exhaust Gas Temp 14 (B7) OORL Warning PC 3.x
Gas Bitmap 7
40437 9 Fault Status 728 Exhaust Gas Temp 16 (B8) OORL Warning PC 3.x
Gas Bitmap 7
40437 10 Fault Status 736 Starter Air Pressure OORL Warning PC 3.x
Gas Bitmap 7
40437 11 Fault Status 737 Starter Air Pressure OORH Warning PC 3.x
Gas Bitmap 7
40437 12 Fault Status 738 Starter Air Press Underpressure Error Warning PC 3.x
Gas Bitmap 7
40437 13 Fault Status 741 Air Filter Restriction Pressure High Er- Warning PC 3.x
Gas Bitmap 7 ror
40437 14 Fault Status 742 Air Filter Restriction Pressure Low Er- Warning PC 3.x
Gas Bitmap 7 ror
40437 15 Fault Status 751 Gas_Mass_Flow_In_Range_Error Warning PC 3.x
Gas Bitmap 7
40438 0 Fault Status 752 Exhaust_Gas_Oxygen_In_Range_Er- Warning PC 3.x
Gas Bitmap 8 ror
40438 1 Fault Status 783 Intake Manifold 1 Temp Abnormal Shutdown PC 3.x
Gas Bitmap 8 w/Cooldown
40438 2 Fault Status 1213 COP_Overboost_Error Shutdown PC 3.x
Gas Bitmap 8 w/Cooldown
40438 3 Fault Status 1274 Heavy_Knock_Error_10_(B5) Shutdown PC 3.x
Gas Bitmap 8 w/Cooldown
40438 4 Fault Status 1281 Heavy_Knock_Error_12_(B6) Shutdown PC 3.x
Gas Bitmap 8 w/Cooldown
40438 5 Fault Status 1285 Continuous_Light_Knock_Er- Shutdown PC 3.x
Gas Bitmap 8 ror_13_(A7) w/Cooldown
40438 6 Fault Status 1286 Heavy_Knock_Error_13_(A7) Shutdown PC 3.x
Gas Bitmap 8 w/Cooldown
40438 7 Fault Status 1291 Heavy_Knock_Error_14_(B7) Shutdown PC 3.x
Gas Bitmap 8 w/Cooldown
40438 8 Fault Status 1295 Continuous_Light_Knock_Er- Shutdown PC 3.x
Gas Bitmap 8 ror_15_(A8) w/Cooldown
40438 9 Fault Status 1296 Heavy_Knock_Error_15_(A8) Shutdown PC 3.x
Gas Bitmap 8 w/Cooldown

345
Addr. Bit# Name Fault Event Name Response Control
Code
40438 10 Fault Status 1311 Heavy_Knock_Error_18_(B9) Shutdown PC 3.x
Gas Bitmap 8 w/Cooldown
40438 11 Fault Status 1362 Oil Filter Restriction Error Warning PC 3.x
Gas Bitmap 8
40438 12 Fault Status 1452 Genset Breaker Fail To Close Shutdown PC 3.x
Gas Bitmap 8
40438 13 Fault Status 1457 Fail To Synchronize Warning PC 3.x
Gas Bitmap 8
40438 14 Fault Status 1458 Sync Phase Rotation Mismatch Warning PC 3.x
Gas Bitmap 8
40438 15 Fault Status 1474 ECM Software mismatch Shutdown PC 3.x
Gas Bitmap 8 w/Cooldown
40439 0 Fault Status 1521 Exhaust Gas Temp 3 (A2) OORH Warning PC 3.x
Gas Bitmap 9
40439 1 Fault Status 1522 Exhaust Gas Temp 5 (A3) OORH Warning PC 3.x
Gas Bitmap 9
40439 2 Fault Status 1523 Exhaust Gas Temp 7 (A4) OORH Warning PC 3.x
Gas Bitmap 9
40439 3 Fault Status 1524 Exhaust Gas Temp 9 (A5) OORH Warning PC 3.x
Gas Bitmap 9
40439 4 Fault Status 1525 Exhaust Gas Temp 11 (A6) OORH Warning PC 3.x
Gas Bitmap 9
40439 5 Fault Status 1526 Exhaust Gas Temp 13 (A7) OORH Warning PC 3.x
Gas Bitmap 9
40439 6 Fault Status 1527 Exhaust Gas Temp 15 (A8) OORH Warning PC 3.x
Gas Bitmap 9
40439 7 Fault Status 1528 Exhaust Gas Temp 17 (A9) OORH Warning PC 3.x
Gas Bitmap 9
40439 8 Fault Status 1529 Exhaust Gas Temp 2 (B1) OORH Warning PC 3.x
Gas Bitmap 9
40439 9 Fault Status 1531 Exhaust Gas Temp 6 (B3) OORH Warning PC 3.x
Gas Bitmap 9
40439 10 Fault Status 1532 Exhaust Gas Temp 8 (B4) OORH Warning PC 3.x
Gas Bitmap 9
40439 11 Fault Status 1533 Exhaust Gas Temp 10 (B5) OORH Warning PC 3.x
Gas Bitmap 9
40439 12 Fault Status 1534 Exhaust Gas Temp 12 (B6) OORH Warning PC 3.x
Gas Bitmap 9
40439 13 Fault Status 1535 Exhaust Gas Temp 14 (B7) OORH Warning PC 3.x
Gas Bitmap 9
40439 14 Fault Status 1536 Exhaust Gas Temp 16 (B8) OORH Warning PC 3.x
Gas Bitmap 9

346
Addr. Bit# Name Fault Event Name Response Control
Code
40439 15 Fault Status 1537 Exhaust Gas Temp 18 (B9) OORH Warning PC 3.x
Gas Bitmap 9
40440 0 Fault Status 1545 EPS Backup Channel Lost Warning PC 3.x
Gas Bitmap
10
40440 1 Fault Status 1546 EPS Main Channel Lost Warning PC 3.x
Gas Bitmap
10
40440 2 Fault Status 1579 Continuous_Light_Knock_Er- Shutdown PC 3.x
Gas Bitmap ror_12_(B6) w/Cooldown
10
40440 3 Fault Status 1581 Continuous_Light_Knock_Er- Shutdown PC 3.x
Gas Bitmap ror_14_(B7) w/Cooldown
10
40440 4 Fault Status 1582 Continuous_Light_Knock_Er- Shutdown PC 3.x
Gas Bitmap ror_16_(B8) w/Cooldown
10
40440 5 Fault Status 1583 Heavy_Knock_Error_16_(B8) Shutdown PC 3.x
Gas Bitmap w/Cooldown
10
40440 6 Fault Status 1587 Continuous_Light_Knock_Er- Shutdown PC 3.x
Gas Bitmap ror_17_(A9) w/Cooldown
10
40440 7 Fault Status 1588 Heavy_Knock_Error_17_(A9) Shutdown PC 3.x
Gas Bitmap w/Cooldown
10
40440 8 Fault Status 1593 Continuous_Light_Knock_Er- Shutdown PC 3.x
Gas Bitmap ror_18_(B9) w/Cooldown
10
40440 9 Fault Status 1618 Exhaust Gas Temp, Cyl 1 (A1) OORH Warning PC 3.x
Gas Bitmap
10
40440 10 Fault Status 1619 Exhaust Gas Temp, Cyl 4 (B2) OORH Warning PC 3.x
Gas Bitmap
10
40440 11 Fault Status 1636 Intake Manif Press 2 OORH Warning PC 3.x
Gas Bitmap
10
40440 12 Fault Status 1637 Intake Manif Press 2 OORL Warning PC 3.x
Gas Bitmap
10
40440 13 Fault Status 1737 CAN_Throttle_Internal_Failure_Error Shutdown PC 3.x
Gas Bitmap w/Cooldown
10

347
Addr. Bit# Name Fault Event Name Response Control
Code
40440 14 Fault Status 1738 CAN_Throttle_Internal_Fault_Error Warning PC 3.x
Gas Bitmap
10
40440 15 Fault Status 1739 Engine Throttle Control Condition Ex- Warning PC 3.x
Gas Bitmap ists
10
40441 0 Fault Status 1741 CAN_Throttle_High_Temp_Warn- Warning PC 3.x
Gas Bitmap 11 ing_Error
40441 1 Fault Status 1742 CAN_Throttle_Temp_Limiting_Error Warning PC 3.x
Gas Bitmap 11
40441 2 Fault Status 1743 Throttle Ctrl 2 OOR High Shutdown PC 3.x
Gas Bitmap 11 w/Cooldown
40441 3 Fault Status 1744 Throttle Ctrl 2 OOR Low Shutdown PC 3.x
Gas Bitmap 11 w/Cooldown
40441 4 Fault Status 1745 Throttle Ctrl 2 Incorrect Shutdown PC 3.x
Gas Bitmap 11 w/Cooldown
40441 5 Fault Status 1746 Throttle Ctrl 2 Out of Adjustment Shutdown PC 3.x
Gas Bitmap 11 w/Cooldown
40441 6 Fault Status 1747 Throttle Ctrl 2 Bad Device Shutdown PC 3.x
Gas Bitmap 11 w/Cooldown
40441 7 Fault Status 1748 Throttle Ctrl 2 Root Unknown Warning PC 3.x
Gas Bitmap 11
40441 8 Fault Status 1749 Throttle Ctrl 2 Condition Exists Warning PC 3.x
Gas Bitmap 11
40441 9 Fault Status 1751 Throttle Ctrl 2 Warning High Warning PC 3.x
Gas Bitmap 11
40441 10 Fault Status 1752 Throttle Ctrl 2 Moderate High Warning PC 3.x
Gas Bitmap 11
40441 11 Fault Status 1753 Fuel Shutoff 2 OOR High Warning PC 3.x
Gas Bitmap 11
40441 12 Fault Status 1754 Fuel Tmp 2 OOR High Warning PC 3.x
Gas Bitmap 11
40441 13 Fault Status 1755 Fuel Tmp 2 OOR Low Warning PC 3.x
Gas Bitmap 11
40441 14 Fault Status 1756 Gas Flow 2 OOR High Warning PC 3.x
Gas Bitmap 11
40441 15 Fault Status 1757 Gas Flow 2 OOR Low Warning PC 3.x
Gas Bitmap 11
40442 0 Fault Status 1758 Gas Flow 2 Incorrect Data Warning PC 3.x
Gas Bitmap
12

348
Addr. Bit# Name Fault Event Name Response Control
Code
40442 1 Fault Status 1759 FCV 2 Pos Feedback Incorrect Shutdown PC 3.x
Gas Bitmap w/Cooldown
12
40442 2 Fault Status 1761 FCV_Actuator_Error_1761 Shutdown PC 3.x
Gas Bitmap w/Cooldown
12
40442 3 Fault Status 1984 Int Man 2 Tmp Moderate High Warning PC 3.x
Gas Bitmap
12
40442 4 Fault Status 1765 FCV 2 In Pr OOR High Warning PC 3.x
Gas Bitmap
12
40442 5 Fault Status 1766 FCV 2 In Pr OOR Low Warning PC 3.x
Gas Bitmap
12
40442 6 Fault Status 1767 FCV 2 Out Pr OOR High Warning PC 3.x
Gas Bitmap
12
40442 7 Fault Status 1768 FCV 2 Out Pr OOR Low Warning PC 3.x
Gas Bitmap
12
40442 8 Fault Status 1769 E_Shutd Indication OORH Warning PC 3.x
Gas Bitmap
12
40442 9 Fault Status 1771 E_Shutd Indication OORL Warning PC 3.x
Gas Bitmap
12
40442 10 Fault Status 1772 Eng Derate Request OORH Warning PC 3.x
Gas Bitmap
12
40442 11 Fault Status 1773 Eng Derate Request OORL Warning PC 3.x
Gas Bitmap
12
40442 12 Fault Status 1774 Oil Priming Pump OORH Warning PC 3.x
Gas Bitmap
12
40442 13 Fault Status 1775 Oil Priming Pump OORL Warning PC 3.x
Gas Bitmap
12
40442 14 Fault Status 3362 Power Conservation Control OORH Warning PC 3.x
Gas Bitmap
12

349
Addr. Bit# Name Fault Event Name Response Control
Code
40442 15 Fault Status 3363 Power Conservation Control OORL Warning PC 3.x
Gas Bitmap
12
40443 0 Fault Status 1778 Engine_Heater_Control_Driv- Warning PC 3.x
Gas Bitmap er_High_Error
13
40443 1 Fault Status 1779 Engine_Heater_Control_Driv- Warning PC 3.x
Gas Bitmap er_Low_Error
13
40443 2 Fault Status 1781 Shutd Request OOR High Warning PC 3.x
Gas Bitmap
13
40443 3 Fault Status 1782 Shutd Request OOR Low Warning PC 3.x
Gas Bitmap
13
40443 4 Fault Status 1783 Coolant_Pump_Control_Driv- Warning PC 3.x
Gas Bitmap er_High_Error
13
40443 5 Fault Status 1784 Coolant_Pump_Control_Driv- Warning PC 3.x
Gas Bitmap er_Low_Error
13
40443 6 Fault Status 1785 Oil_Priming_Pump_Manual_Over- Warning PC 3.x
Gas Bitmap ride_Input_On
13
40443 7 Fault Status 1786 Oil_Priming_Pump_Stuck_On_Error Warning PC 3.x
Gas Bitmap
13
40443 8 Fault Status 1787 Post_Lube_Oil_Priming_Error Warning PC 3.x
Gas Bitmap
13
40443 9 Fault Status 1788 Maintenance_Lube_Oil_Priming_Error Warning PC 3.x
Gas Bitmap
13
40443 10 Fault Status 1789 Pre_Start_Lube_Oil_Priming_Error Shutdown PC 3.x
Gas Bitmap w/Cooldown
13
40443 11 Fault Status 1791 Failure_To_Meet_Load_Speed_Error Shutdown PC 3.x
Gas Bitmap w/Cooldown
13
40443 12 Fault Status 1792 Idle when CB Closed Warning PC 3.x
Gas Bitmap
13

350
Addr. Bit# Name Fault Event Name Response Control
Code
40443 13 Fault Status 1793 Speed/Posit sensor out of Adj Warning PC 3.x
Gas Bitmap
13
40443 14 Fault Status 1794 Fire Detected Shutdown PC 3.x
Gas Bitmap w/Cooldown
13
40443 15 Fault Status 1795 Compressor_Bypass_Posi- Warning PC 3.x
Gas Bitmap tion_High_Error
13
40444 0 Fault Status 1796 Compressor_Bypass_Posi- Warning PC 3.x
Gas Bitmap tion_Low_Error
14
40444 1 Fault Status 1797 Compressor Bypass ctrl OORH Warning PC 3.x
Gas Bitmap
14
40444 2 Fault Status 1798 Compressor Bypass ctrl OORL Warning PC 3.x
Gas Bitmap
14
40444 3 Fault Status 1799 CB_Position_Err_Status Warning PC 3.x
Gas Bitmap
14
40444 4 Fault Status 1811 HIGH_SIDE_DRV2_High_Control_Er- Warning PC 3.x
Gas Bitmap ror (VPS)
14
40444 5 Fault Status 1812 HIGH_SIDE_DRV2_Low_Control_Er- Warning PC 3.x
Gas Bitmap ror (VPS)
14
40444 6 Fault Status 1813 Valve_Proving_Sys- Warning PC 3.x
Gas Bitmap tem_Test_Failed_Warning_Error
14
40444 7 Fault Status 1814 Valve_Proving_Sys- Shutdown PC 3.x
Gas Bitmap tem_Test_Failed_Shutdown_Error w/Cooldown
14
40444 8 Fault Status 1815 RLY14_High_Control_Error Warning PC 3.x
Gas Bitmap
14
40444 9 Fault Status 1816 Oil PreHtr Ctrl OOR Low Warning PC 3.x
Gas Bitmap
14
40444 10 Fault Status 1817 Oil_Pre−Heater_Tripped_Error Warning PC 3.x
Gas Bitmap
14

351
Addr. Bit# Name Fault Event Name Response Control
Code
40444 11 Fault Status 1818 Oil_Pre−Heater_Not_Warming_Error Warning PC 3.x
Gas Bitmap
14
40444 12 Fault Status 1819 Common AC Aux CB tripped Warning PC 3.x
Gas Bitmap
14
40444 13 Fault Status 1821 Min_FSO_Speed_Error Shutdown PC 3.x
Gas Bitmap w/Cooldown
14
40444 14 Fault Status 1822 LT Coolant Level Low Shutdown Error Shutdown PC 3.x
Gas Bitmap w/Cooldown
14
40444 15 Fault Status 1823 LT Coolant Level Low Warning Error Warning PC 3.x
Gas Bitmap
14
40445 0 Fault Status 1824 Idle_Rated_Trans_Oil_Temp_Low_Er- Warning PC 3.x
Gas Bitmap ror
15
40445 1 Fault Status 1825 Dirty_Oil_Level_Error Warning PC 3.x
Gas Bitmap
15
40445 2 Fault Status 1826 ECM Software incompatible Shutdown PC 3.x
Gas Bitmap w/Cooldown
15
40445 3 Fault Status 1827 Fuel_Inlet_Pressure_High_Error Warning PC 3.x
Gas Bitmap
15
40445 4 Fault Status 1828 Fuel_Inlet_Pressure_Low_Error Warning PC 3.x
Gas Bitmap
15
40445 5 Fault Status 1829 Vent_Gas_Valve_Error Shutdown PC 3.x
Gas Bitmap w/Cooldown
15
40445 6 Fault Status 1831 Upstream_FSO_Valve_Error Shutdown PC 3.x
Gas Bitmap w/Cooldown
15
40445 7 Fault Status 1832 Downstream_FSO_Valve_Error Shutdown PC 3.x
Gas Bitmap w/Cooldown
15
40445 8 Fault Status 1833 Engine_Heater_Trip_Error Warning PC 3.x
Gas Bitmap
15

352
Addr. Bit# Name Fault Event Name Response Control
Code
40445 9 Fault Status 1834 Coolant_Pump_Trip_Error Warning PC 3.x
Gas Bitmap
15
40445 10 Fault Status 1835 Oil_Priming_Pump_Tripped_Error Warning PC 3.x
Gas Bitmap
15
40445 11 Fault Status 1836 LCP_(LT)_Low_Serious_Error Shutdown PC 3.x
Gas Bitmap w/Cooldown
15
40445 12 Fault Status 1837 Permanent_FS_Cam_Sync_Lost_Error Shutdown PC 3.x
Gas Bitmap w/Cooldown
15
40445 13 Fault Status 1838 Partial_Engine_Overload_Shut- Shutdown PC 3.x
Gas Bitmap down_Error w/Cooldown
15
40445 14 Fault Status 1839 Fuel_Supply_Pressure_High_Error Warning PC 3.x
Gas Bitmap
15
40445 15 Fault Status 1841 Fuel_Supply_Pressure_Low_Error Warning PC 3.x
Gas Bitmap
15
40446 0 Fault Status 1842 Radiator_Fan_Trip_Error Warning PC 3.x
Gas Bitmap
16
40446 1 Fault Status 1858 Exhaust Aft Inlet O2 OOR High Warning PC 3.x
Gas Bitmap
16
40446 2 Fault Status 1859 Exhaust Aft Inlet O2 OOR Low Warning PC 3.x
Gas Bitmap
16
40446 3 Fault Status 1861 Exhaust Aft Inlet O2 Incorrect Warning PC 3.x
Gas Bitmap
16
40446 4 Fault Status 1862 Exhaust Aft Out O2 OOR High Warning PC 3.x
Gas Bitmap
16
40446 5 Fault Status 1863 Exhaust Aft Outlet O2 OOR Low Warning PC 3.x
Gas Bitmap
16
40446 6 Fault Status 1864 Exhaust Aft Outlet O2 Incorrect Warning PC 3.x
Gas Bitmap
16

353
Addr. Bit# Name Fault Event Name Response Control
Code
40446 7 Fault Status 1985 Int Man 3 Tmp Moderate High Warning PC 3.x
Gas Bitmap
16
40446 8 Fault Status 1986 Int Man 4 Tmp Moderate High Warning PC 3.x
Gas Bitmap
16
40446 9 Fault Status 2111 Coolant_Inlet_Tempera- Warning PC 3.x
Gas Bitmap ture_(LT)_High_Error
16
40446 10 Fault Status 2112 Coolant_Inlet_Tempera- Warning PC 3.x
Gas Bitmap ture_(LT)_Low_Error
16
40446 11 Fault Status 2113 CIT_(LT)_High_Warning_Error Warning PC 3.x
Gas Bitmap
16
40446 12 Fault Status 2114 CIT_(LT)_High_Serious_Error Shutdown PC 3.x
Gas Bitmap w/Cooldown
16
40446 13 Fault Status 2115 LT_Coolant_Pressure_High_Error Warning PC 3.x
Gas Bitmap
16
40446 14 Fault Status 2116 LT_Coolant_Pressure_Low_Error Warning PC 3.x
Gas Bitmap
16
40446 15 Fault Status 2117 LCP_(LT)_Low_Warning_Error Warning PC 3.x
Gas Bitmap
16
40447 0 Fault Status 2121 Exhaust_Temp_1_(A1)_High_Warn- Warning PC 3.x
Gas Bitmap ing_Error
17
40447 1 Fault Status 2122 Exhaust_Temp_3_(A2)_High_Warn- Warning PC 3.x
Gas Bitmap ing_Error
17
40447 2 Fault Status 2123 Exhaust_Temp_5_(A3)_High_Warn- Warning PC 3.x
Gas Bitmap ing_Error
17
40447 3 Fault Status 2124 Exhaust_Temp_7_(A4)_High_Warn- Warning PC 3.x
Gas Bitmap ing_Error
17
40447 4 Fault Status 2125 Exhaust_Temp_9_(A5)_High_Warn- Warning PC 3.x
Gas Bitmap ing_Error
17

354
Addr. Bit# Name Fault Event Name Response Control
Code
40447 5 Fault Status 2126 Exhaust_Temp_11_(A6)_High_Warn- Warning PC 3.x
Gas Bitmap ing_Error
17
40447 6 Fault Status 2127 Exhaust_Temp_13_(A7)_High_Warn- Warning PC 3.x
Gas Bitmap ing_Error
17
40447 7 Fault Status 2128 Exhaust_Temp_15_(A8)_High_Warn- Warning PC 3.x
Gas Bitmap ing_Error
17
40447 8 Fault Status 2129 Exhaust_Temp_17_(A9)_High_Warn- Warning PC 3.x
Gas Bitmap ing_Error
17
40447 9 Fault Status 2131 Exhaust_Temp_2_(B1)_High_Warn- Warning PC 3.x
Gas Bitmap ing_Error
17
40447 10 Fault Status 2132 Exhaust_Temp_4_(B2)_High_Warn- Warning PC 3.x
Gas Bitmap ing_Error
17
40447 11 Fault Status 2133 Exhaust_Temp_6_(B3)_High_Warn- Warning PC 3.x
Gas Bitmap ing_Error
17
40447 12 Fault Status 2134 Exhaust_Temp_8_(B4)_High_Warn- Warning PC 3.x
Gas Bitmap ing_Error
17
40447 13 Fault Status 2135 Exhaust_Temp_10_(B5)_High_Warn- Warning PC 3.x
Gas Bitmap ing_Error
17
40447 14 Fault Status 2136 Exhaust_Temp_12_(B6)_High_Warn- Warning PC 3.x
Gas Bitmap ing_Error
17
40447 15 Fault Status 2137 Exhaust_Temp_14_(B7)_High_Warn- Warning PC 3.x
Gas Bitmap ing_Error
17
40448 0 Fault Status 2138 Exhaust_Temp_16_(B8)_High_Warn- Warning PC 3.x
Gas Bitmap ing_Error
18
40448 1 Fault Status 2139 Exhaust_Temp_18_(B9)_High_Warn- Warning PC 3.x
Gas Bitmap ing_Error
18
40448 2 Fault Status 2141 Start_Air_Pressure_High_Error Warning PC 3.x
Gas Bitmap
18

355
Addr. Bit# Name Fault Event Name Response Control
Code
40448 3 Fault Status 2142 Start_Air_Pressure_Low_Error Warning PC 3.x
Gas Bitmap
18
40448 4 Fault Status 2143 SAP_Overpressure_Error Warning PC 3.x
Gas Bitmap
18
40448 5 Fault Status 2144 Exhaust Temp 16 (B8) High Serious Shutdown PC 3.x
Gas Bitmap Error w/Cooldown
18
40448 6 Fault Status 2145 Exhaust Temp 18 (B9) High Serious Shutdown PC 3.x
Gas Bitmap Error w/Cooldown
18
40448 7 Fault Status 2146 EGT 17 (A9) OOR Low Warning PC 3.x
Gas Bitmap
18
40448 8 Fault Status 2147 EGT 18 (B9) OOR Low Warning PC 3.x
Gas Bitmap
18
40448 9 Fault Status 2154 Oil_Filter_Outlet_Pressure_High_Error Warning PC 3.x
Gas Bitmap
18
40448 10 Fault Status 2155 Oil_Filter_Outlet_Pressure_Low_Error Warning PC 3.x
Gas Bitmap
18
40448 11 Fault Status 2157 Int Man 2 Tmp Abnormal Rate Shutdown PC 3.x
Gas Bitmap w/Cooldown
18
40448 12 Fault Status 2158 Int Man 3 Tmp Abnormal Rate Shutdown PC 3.x
Gas Bitmap w/Cooldown
18
40448 13 Fault Status 2159 Int Man 4 Tmp Abnormal Rate Shutdown PC 3.x
Gas Bitmap w/Cooldown
18
40448 14 Fault Status 2188 Exhaust O2 OOR High Warning PC 3.x
Gas Bitmap
18
40448 15 Fault Status 2191 ST_Throttle_Press_Err_Status Warning PC 3.x
Gas Bitmap
18
40449 0 Fault Status 2192 Exhaust O2 OOR Low Warning PC 3.x
Gas Bitmap
19

356
Addr. Bit# Name Fault Event Name Response Control
Code
40449 1 Fault Status 2217 RAM_Image_Word_Error Warning PC 3.x
Gas Bitmap
19
40449 2 Fault Status 2219 Exhaust O2 Moderate High Warning PC 3.x
Gas Bitmap
19
40449 3 Fault Status 2221 Exhaust O2 Moderate Low Warning PC 3.x
Gas Bitmap
19
40449 4 Fault Status 2281 Knock 11 (A6) Moderate High Shutdown PC 3.x
Gas Bitmap w/Cooldown
19
40449 5 Fault Status 2282 Knock 11 (A6) Critical High Shutdown PC 3.x
Gas Bitmap w/Cooldown
19
40449 6 Fault Status 2298 Fuel Shutoff 2 OOR Low Warning PC 3.x
Gas Bitmap
19
40449 7 Fault Status 2315 Red Lamp OOR High Warning PC 3.x
Gas Bitmap
19
40449 8 Fault Status 2316 Amber Lamp OOR High Warning PC 3.x
Gas Bitmap
19
40449 9 Fault Status 2317 Amber Lamp OOR Low Warning PC 3.x
Gas Bitmap
19
40449 10 Fault Status 2427 Fuel_Outlet_Pressure_High_Error Warning PC 3.x
Gas Bitmap
19
40449 11 Fault Status 2428 Fuel_Outlet_Pressure_Low_Error Warning PC 3.x
Gas Bitmap
19
40449 12 Fault Status 2453 Total Real Power Circuit OORH Warning PC 3.x
Gas Bitmap
19
40449 13 Fault Status 2454 Total Real Power Circuit OORL Warning PC 3.x
Gas Bitmap
19
40449 14 Fault Status 2455 Speed_Bias_Low_Error Warning PC 3.x
Gas Bitmap
19

357
Addr. Bit# Name Fault Event Name Response Control
Code
40449 15 Fault Status 2456 Speed_Bias_High_Error Warning PC 3.x
Gas Bitmap
19
40450 0 Fault Status 2457 Max_Total_Misfire_Error Shutdown PC 3.x
Gas Bitmap w/Cooldown
20
40450 1 Fault Status 2458 Cylinder_2_(B1)_Total_Misfire_Error Warning PC 3.x
Gas Bitmap
20
40450 2 Fault Status 2459 Cylinder_4_(B2)_Total_Misfire_Error Warning PC 3.x
Gas Bitmap
20
40450 3 Fault Status 2461 Cylinder_6_(B3)_Total_Misfire_Error Warning PC 3.x
Gas Bitmap
20
40450 4 Fault Status 2462 Cylinder_8_(B4)_Total_Misfire_Error Warning PC 3.x
Gas Bitmap
20
40450 5 Fault Status 2463 Cylinder_10_(B5)_Total_Misfire_Error Warning PC 3.x
Gas Bitmap
20
40450 6 Fault Status 2464 Cylinder_12_(B6)_Total_Misfire_Error Warning PC 3.x
Gas Bitmap
20
40450 7 Fault Status 2465 Cylinder_14_(B7)_Total_Misfire_Error Warning PC 3.x
Gas Bitmap
20
40450 8 Fault Status 2466 Cylinder_16_(B8)_Total_Misfire_Error Warning PC 3.x
Gas Bitmap
20
40450 9 Fault Status 2467 Cylinder_18_(B9)_Total_Misfire_Error Warning PC 3.x
Gas Bitmap
20
40450 10 Fault Status 2469 Cylinder_1_(A1)_Total_Misfire_Error Warning PC 3.x
Gas Bitmap
20
40450 11 Fault Status 2471 Cylinder_3_(A2)_Total_Misfire_Error Warning PC 3.x
Gas Bitmap
20
40450 12 Fault Status 2472 Cylinder_5_(A3)_Total_Misfire_Error Warning PC 3.x
Gas Bitmap
20

358
Addr. Bit# Name Fault Event Name Response Control
Code
40450 13 Fault Status 2473 Cylinder_7_(A4)_Total_Misfire_Error Warning PC 3.x
Gas Bitmap
20
40450 14 Fault Status 2475 Cylinder_9_(A5)_Total_Misfire_Error Warning PC 3.x
Gas Bitmap
20
40450 15 Fault Status 2476 Cylinder_11_(A6)_Total_Misfire_Error Warning PC 3.x
Gas Bitmap
20
40451 0 Fault Status 2477 Cylinder_13_(A7)_Total_Misfire_Error Warning PC 3.x
Gas Bitmap
21
40451 1 Fault Status 2478 Cylinder_15_(A8)_Total_Misfire_Error Warning PC 3.x
Gas Bitmap
21
40451 2 Fault Status 2479 Cylinder_17_(A9)_Total_Misfire_Error Warning PC 3.x
Gas Bitmap
21
40451 3 Fault Status 2482 Start_Before_Ready_Error Shutdown PC 3.x
Gas Bitmap w/Cooldown
21
40451 4 Fault Status 2483 Continuous_Starter_Failure_Error Shutdown PC 3.x
Gas Bitmap w/Cooldown
21
40451 5 Fault Status 2484 Exhaust Temperature 1 (A1) Abnormal Shutdown PC 3.x
Gas Bitmap Rate w/Cooldown
21
40451 6 Fault Status 2485 Exhaust Temperature 3 (A2) Abnormal Shutdown PC 3.x
Gas Bitmap Rate w/Cooldown
21
40451 7 Fault Status 2486 Exhaust Temperature 5 (A3) Abnormal Shutdown PC 3.x
Gas Bitmap Rate w/Cooldown
21
40451 8 Fault Status 2487 Exhaust Temperature 7 (A4) Abnormal Shutdown PC 3.x
Gas Bitmap Rate w/Cooldown
21
40451 9 Fault Status 2488 Exhaust Temperature 9 (A5) Abnormal Shutdown PC 3.x
Gas Bitmap Rate w/Cooldown
21
40451 10 Fault Status 2489 Exhaust Temperature 11 (A6) Abnor- Shutdown PC 3.x
Gas Bitmap mal Rate w/Cooldown
21

359
Addr. Bit# Name Fault Event Name Response Control
Code
40451 11 Fault Status 2491 Exhaust Temperature 13 (A7) Abnor- Shutdown PC 3.x
Gas Bitmap mal Rate w/Cooldown
21
40451 12 Fault Status 2492 Exhaust Temperature 15 (A8) Abnor- Shutdown PC 3.x
Gas Bitmap mal Rate w/Cooldown
21
40451 13 Fault Status 2493 Exhaust Temperature 17 (A9) Abnor- Shutdown PC 3.x
Gas Bitmap mal Rate w/Cooldown
21
40451 14 Fault Status 2494 Exhaust Temperature 2 (B1) Abnormal Shutdown PC 3.x
Gas Bitmap Rate w/Cooldown
21
40451 15 Fault Status 2495 Exhaust Temperature 4 (B2) Abnormal Shutdown PC 3.x
Gas Bitmap Rate w/Cooldown
21
40452 0 Fault Status 2496 Exhaust Temperature 6 (B3) Abnormal Shutdown PC 3.x
Gas Bitmap Rate w/Cooldown
22
40452 1 Fault Status 2497 Exhaust Temperature 8 (B4) Abnormal Shutdown PC 3.x
Gas Bitmap Rate w/Cooldown
22
40452 2 Fault Status 2498 Exhaust Temperature 10 (B5) Abnor- Shutdown PC 3.x
Gas Bitmap mal Rate w/Cooldown
22
40452 3 Fault Status 2499 Exhaust Temperature 12 (B6) Abnor- Shutdown PC 3.x
Gas Bitmap mal Rate w/Cooldown
22
40452 4 Fault Status 2511 Exhaust Temperature 14 (B7) Abnor- Shutdown PC 3.x
Gas Bitmap mal Rate w/Cooldown
22
40452 5 Fault Status 2512 Exhaust Temperature 16 (B8) Abnor- Shutdown PC 3.x
Gas Bitmap mal Rate w/Cooldown
22
40452 6 Fault Status 2513 Exhaust Temperature 18 (B9) Abnor- Shutdown PC 3.x
Gas Bitmap mal Rate w/Cooldown
22
40452 7 Fault Status 2517 Compressor_Outlet_Pres- Warning PC 3.x
Gas Bitmap sure_High_Error
22
40452 8 Fault Status 2518 Compressor_Outlet_Pressure_Low_Er- Warning PC 3.x
Gas Bitmap ror
22

360
Addr. Bit# Name Fault Event Name Response Control
Code
40452 9 Fault Status 2521 Bank_Id_Error Shutdown PC 3.x
Gas Bitmap w/Cooldown
22
40452 10 Fault Status 2522 Continuous_Light_Knock_Error_1_(A1) Shutdown PC 3.x
Gas Bitmap w/Cooldown
22
40452 11 Fault Status 2523 Continuous_Light_Knock_Error_2_(B1) Shutdown PC 3.x
Gas Bitmap w/Cooldown
22
40452 12 Fault Status 2524 Continuous_Light_Knock_Error_3_(A2) Shutdown PC 3.x
Gas Bitmap w/Cooldown
22
40452 13 Fault Status 2525 Continuous_Light_Knock_Error_4_(B2) Shutdown PC 3.x
Gas Bitmap w/Cooldown
22
40452 14 Fault Status 2526 Continuous_Light_Knock_Error_5_(A3) Shutdown PC 3.x
Gas Bitmap w/Cooldown
22
40452 15 Fault Status 2527 Continuous_Light_Knock_Error_6_(B3) Shutdown PC 3.x
Gas Bitmap w/Cooldown
22
40453 0 Fault Status 2528 Continuous_Light_Knock_Error_7_(A4) Shutdown PC 3.x
Gas Bitmap w/Cooldown
23
40453 1 Fault Status 2529 Continuous_Light_Knock_Error_8_(B4) Shutdown PC 3.x
Gas Bitmap w/Cooldown
23
40453 2 Fault Status 2531 Continuous_Light_Knock_Error_9_(A5) Shutdown PC 3.x
Gas Bitmap w/Cooldown
23
40453 3 Fault Status 2532 Continuous_Light_Knock_Er- Shutdown PC 3.x
Gas Bitmap ror_10_(B5) w/Cooldown
23
40453 4 Fault Status 2544 ECM_Overtemp_Error Shutdown PC 3.x
Gas Bitmap w/Cooldown
23
40453 5 Fault Status 2567 DG_Air_Compressor_Trip_Error Warning PC 3.x
Gas Bitmap
23
40453 6 Fault Status 2643 Throttle Pos 2 Feedback OOR High Warning PC 3.x
Gas Bitmap
23

361
Addr. Bit# Name Fault Event Name Response Control
Code
40453 7 Fault Status 2644 Throttle Pos 2 Feedback OOR Low Warning PC 3.x
Gas Bitmap
23
40453 9 Fault Status 2724 Gas Supply Pr Moderate High Warning PC 3.x
Gas Bitmap
23
40453 10 Fault Status 2725 Gas Supply Pr Moderate Low Warning PC 3.x
Gas Bitmap
23
40453 11 Fault Status 2737 Exh Gas Tmp Critical High Shutdown PC 3.x
Gas Bitmap w/Cooldown
23
40453 12 Fault Status 2766 Bank_A_CCD_Failed_Error Shutdown PC 3.x
Gas Bitmap w/Cooldown
23
40453 13 Fault Status 2767 Bank_B_CCD_Failed_Error Shutdown PC 3.x
Gas Bitmap w/Cooldown
23
40453 14 Fault Status 2768 CAN Parent Communication Incorrect Shutdown PC 3.x
Gas Bitmap w/Cooldown
23
40453 15 Fault Status 2769 CAN Child Com Incorrect Shutdown PC 3.x
Gas Bitmap w/Cooldown
23
40454 0 Fault Status 2789 COT_Low_Error Warning PC 3.x
Gas Bitmap
24
40454 1 Fault Status 2793 COT_Low_Serious_Error Shutdown PC 3.x
Gas Bitmap w/Cooldown
24
40454 2 Fault Status 2794 Ign Shutd Relay OOR High Warning PC 3.x
Gas Bitmap
24
40454 3 Fault Status 2795 Ign Shutd Relay OOR Low Warning PC 3.x
Gas Bitmap
24
40454 4 Fault Status 2796 Partial_Engine_Overload_Warning_Er- Warning PC 3.x
Gas Bitmap ror
24
40454 5 Fault Status 2797 Inlet Gas Diff Pressure OOR High Warning PC 3.x
Gas Bitmap
24

362
Addr. Bit# Name Fault Event Name Response Control
Code
40454 6 Fault Status 2798 Inlet Gas Diff Pressure OOR Low Warning PC 3.x
Gas Bitmap
24
40454 7 Fault Status 2799 IMOP_Compressor_Outlet_Pres- Shutdown PC 3.x
Gas Bitmap ure_Delta_Error w/Cooldown
24
40454 8 Fault Status 2811 IMOP_Compressor_Outlet_Pres- Shutdown PC 3.x
Gas Bitmap sure_Maximum_Error w/Cooldown
24
40454 9 Fault Status 2837 Exhaust_Temp_1_(A1)_Deviation_Er- Warning PC 3.x
Gas Bitmap ror
24
40454 10 Fault Status 2838 Exhaust_Temp_3_(A2)_Deviation_Er- Warning PC 3.x
Gas Bitmap ror
24
40454 11 Fault Status 2839 Exhaust_Temp_5_(A3)_Deviation_Er- Warning PC 3.x
Gas Bitmap ror
24
40454 12 Fault Status 2841 Exhaust_Temp_7_(A4)_Deviation_Er- Warning PC 3.x
Gas Bitmap ror
24
40454 13 Fault Status 2842 Exhaust_Temp_9_(A5)_Deviation_Er- Warning PC 3.x
Gas Bitmap ror
24
40454 14 Fault Status 2843 Exhaust_Temp_11_(A6)_Deviation_Er- Warning PC 3.x
Gas Bitmap ror
24
40454 15 Fault Status 2844 Exhaust_Temp_13_(A7)_Deviation_Er- Warning PC 3.x
Gas Bitmap ror
24
40455 0 Fault Status 2845 Exhaust_Temp_15_(A8)_Deviation_Er- Warning PC 3.x
Gas Bitmap ror
25
40455 1 Fault Status 2846 Exhaust_Temp_17_(A9)_Deviation_Er- Warning PC 3.x
Gas Bitmap ror
25
40455 2 Fault Status 2847 Exhaust_Temp_2_(B1)_Deviation_Er- Warning PC 3.x
Gas Bitmap ror
25
40455 3 Fault Status 2848 Exhaust_Temp_4_(B2)_Deviation_Er- Warning PC 3.x
Gas Bitmap ror
25

363
Addr. Bit# Name Fault Event Name Response Control
Code
40455 4 Fault Status 2849 Exhaust_Temp_6_(B3)_Deviation_Er- Warning PC 3.x
Gas Bitmap ror
25
40455 5 Fault Status 2851 Exhaust_Temp_8_(B4)_Deviation_Er- Warning PC 3.x
Gas Bitmap ror
25
40455 6 Fault Status 2852 Exhaust_Temp_10_(B5)_Deviation_Er- Warning PC 3.x
Gas Bitmap ror
25
40455 7 Fault Status 2853 Exhaust_Temp_12_(B6)_Deviation_Er- Warning PC 3.x
Gas Bitmap ror
25
40455 8 Fault Status 2854 Exhaust_Temp_14_(B7)_Deviation_Er- Warning PC 3.x
Gas Bitmap ror
25
40455 9 Fault Status 2855 Exhaust_Temp_16_(B8)_Deviation_Er- Warning PC 3.x
Gas Bitmap ror
25
40455 10 Fault Status 2856 Exhaust_Temp_18_(B9)_Deviation_Er- Warning PC 3.x
Gas Bitmap ror
25
40455 11 Fault Status 2857 Turbo_1_Overspeed_Critical_Error Shutdown PC 3.x
Gas Bitmap w/Cooldown
25
40455 12 Fault Status 2858 Turbo_2_Overspeed_Critical_Error Shutdown PC 3.x
Gas Bitmap w/Cooldown
25
40455 13 Fault Status 2859 Alt Heater Ctrl OOR High Warning PC 3.x
Gas Bitmap
25
40455 14 Fault Status 2861 Alt Heater Ctrl OOR Low Warning PC 3.x
Gas Bitmap
25
40455 15 Fault Status 2862 Gen Alternator 1st Start Cond Exists Warning PC 3.x
Gas Bitmap
25
40456 0 Fault Status 2863 Genset to Engine Com Incorrect Shutdown PC 3.x
Gas Bitmap w/Cooldown
26
40456 1 Fault Status 2864 FSO_NON_High_Control_Error Shutdown PC 3.x
Gas Bitmap w/Cooldown
26

364
Addr. Bit# Name Fault Event Name Response Control
Code
40456 2 Fault Status 3364 Power Conservation Control Cond Ex- Warning PC 3.x
Gas Bitmap ists
26
40456 3 Fault Status 2866 FCV_Position_High_Error Warning PC 3.x
Gas Bitmap
26
40456 4 Fault Status 2867 FCV_Position_Low_Error Warning PC 3.x
Gas Bitmap
26
40456 5 Fault Status 2868 Engine_Heater_Over−Tempera- Warning PC 3.x
Gas Bitmap ture_Alarm_Error
26
40456 6 Fault Status 2869 HT Cool Temp Driver OOR High Warning PC 3.x
Gas Bitmap
26
40456 7 Fault Status 2871 HT Cool Temp Driver OOR Low Warning PC 3.x
Gas Bitmap
26
40456 8 Fault Status 2872 HT Cool Temp Driver Cond Exists Warning PC 3.x
Gas Bitmap
26
40456 9 Fault Status 2873 LT Cool Temp Driver OOR High Warning PC 3.x
Gas Bitmap
26
40456 10 Fault Status 2874 LT Cool Temp Driver OOR Low Warning PC 3.x
Gas Bitmap
26
40456 11 Fault Status 2875 LT Cool Temp Driver Cond Exists Warning PC 3.x
Gas Bitmap
26
40456 12 Fault Status 2876 Comp_Surge_Shutdown_Error Shutdown PC 3.x
Gas Bitmap w/Cooldown
26
40456 13 Fault Status 2877 Comp_Surge_Derate_Error Warning PC 3.x
Gas Bitmap
26
40456 14 Fault Status 2994 MC68302_Error Warning PC 3.x
Gas Bitmap
26
40456 15 Fault Status 2995 Int Man Pressure 1 Critical High Shutdown PC 3.x
Gas Bitmap w/Cooldown
26

365
Addr. Bit# Name Fault Event Name Response Control
Code
40457 0 Fault Status 2996 Int Man Pressure 1 Moderate High Warning PC 3.x
Gas Bitmap
27
40457 1 Fault Status 2997 Exhaust O2 Critical Low Shutdown PC 3.x
Gas Bitmap w/Cooldown
27
40457 2 Fault Status 3111 Excessive_Mech_Vibration_1_(A1) Shutdown PC 3.x
Gas Bitmap w/Cooldown
27
40457 3 Fault Status 3112 Excessive_Mech_Vibration_2_(B1) Shutdown PC 3.x
Gas Bitmap w/Cooldown
27
40457 4 Fault Status 3113 Excessive_Mech_Vibration_3_(A2) Shutdown PC 3.x
Gas Bitmap w/Cooldown
27
40457 5 Fault Status 3114 Excessive_Mech_Vibration_4_(B2) Shutdown PC 3.x
Gas Bitmap w/Cooldown
27
40457 6 Fault Status 3115 Excessive_Mech_Vibration_5_(A3) Shutdown PC 3.x
Gas Bitmap w/Cooldown
27
40457 7 Fault Status 3116 Excessive_Mech_Vibration_6_(B3) Shutdown PC 3.x
Gas Bitmap w/Cooldown
27
40457 8 Fault Status 3117 Excessive_Mech_Vibration_7_(A4) Shutdown PC 3.x
Gas Bitmap w/Cooldown
27
40457 9 Fault Status 3118 Excessive_Mech_Vibration_8_(B4) Shutdown PC 3.x
Gas Bitmap w/Cooldown
27
40457 10 Fault Status 3119 Excessive_Mech_Vibration_9_(A5) Shutdown PC 3.x
Gas Bitmap w/Cooldown
27
40457 11 Fault Status 3121 Excessive_Mech_Vibration_10_(B5) Shutdown PC 3.x
Gas Bitmap w/Cooldown
27
40457 12 Fault Status 3122 Excessive_Mech_Vibration_11_(A6) Shutdown PC 3.x
Gas Bitmap w/Cooldown
27
40457 13 Fault Status 3123 Excessive_Mech_Vibration_12_(B6) Shutdown PC 3.x
Gas Bitmap w/Cooldown
27

366
Addr. Bit# Name Fault Event Name Response Control
Code
40457 14 Fault Status 3124 Excessive_Mech_Vibration_13_(A7) Shutdown PC 3.x
Gas Bitmap w/Cooldown
27
40457 15 Fault Status 3125 Excessive_Mech_Vibration_14_(B7) Shutdown PC 3.x
Gas Bitmap w/Cooldown
27
40458 0 Fault Status 3126 Excessive_Mech_Vibration_15_(A8) Shutdown PC 3.x
Gas Bitmap w/Cooldown
28
40458 1 Fault Status 3127 Excessive_Mech_Vibration_16_(B8) Shutdown PC 3.x
Gas Bitmap w/Cooldown
28
40458 2 Fault Status 3128 Excessive_Mech_Vibration_17_(A9) Shutdown PC 3.x
Gas Bitmap w/Cooldown
28
40458 3 Fault Status 3129 Excessive_Mech_Vibration_18_(B9) Shutdown PC 3.x
Gas Bitmap w/Cooldown
28
40458 4 Fault Status 1275 Knock Cyl 10 (B5) OORL Warning PC 3.x
Gas Bitmap
28
40458 5 Fault Status 1277 Knock Cyl 11 (A6) OORL Warning PC 3.x
Gas Bitmap
28
40458 6 Fault Status 1282 Knock Cyl 12 (B6) OORL Warning PC 3.x
Gas Bitmap
28
40458 7 Fault Status 1287 Knock Cyl 13 (A7) OORL Warning PC 3.x
Gas Bitmap
28
40458 8 Fault Status 1292 Knock Cyl 14 (B7) OORL Warning PC 3.x
Gas Bitmap
28
40458 9 Fault Status 1297 Knock Cyl 15 (A8) OORL Warning PC 3.x
Gas Bitmap
28
40458 10 Fault Status 1584 Knock Cyl 16 (B8) OORL Warning PC 3.x
Gas Bitmap
28
40458 11 Fault Status 1589 Knock Cyl 17 (A9) OORL Warning PC 3.x
Gas Bitmap
28

367
Addr. Bit# Name Fault Event Name Response Control
Code
40458 12 Fault Status 1338 Knock Cyl 18 (B9) OORL Warning PC 3.x
Gas Bitmap
28
40459 0 Fault Status 189 HT Coolant Temperature Root Cause Shutdown PC 3.x
Gas Bitmap Unknown w/Cooldown
29
40459 1 Fault Status 229 HT Coolant Pressure Incorrect Warning PC 3.x
Gas Bitmap
29
40459 2 Fault Status 334 HT Coolant Temperature Incorrect Warning PC 3.x
Gas Bitmap
29
40459 4 Fault Status 831 Spark Plug 1 (A1) OORL Warning PC 3.x
Gas Bitmap
29
40459 5 Fault Status 832 Spark Plug 2 (B1) OORL Warning PC 3.x
Gas Bitmap
29
40459 6 Fault Status 833 Spark Plug 3 (A2) OORL Warning PC 3.x
Gas Bitmap
29
40459 7 Fault Status 834 Spark Plug 4 (B2) OORL Warning PC 3.x
Gas Bitmap
29
40459 8 Fault Status 835 Spark Plug 5 (A3) OORL Warning PC 3.x
Gas Bitmap
29
40459 9 Fault Status 836 Spark Plug 6 (B3) OORL Warning PC 3.x
Gas Bitmap
29
40459 10 Fault Status 837 Spark Plug 7 (A4) OORL Warning PC 3.x
Gas Bitmap
29
40459 11 Fault Status 838 Spark Plug 8 (B4) OORL Warning PC 3.x
Gas Bitmap
29
40459 12 Fault Status 839 Spark Plug 9 (A5) OORL Warning PC 3.x
Gas Bitmap
29
40459 13 Fault Status 841 Spark Plug 10 (B5) OORL Warning PC 3.x
Gas Bitmap
29

368
Addr. Bit# Name Fault Event Name Response Control
Code
40459 14 Fault Status 842 Spark Plug 11 (A6) OORL Warning PC 3.x
Gas Bitmap
29
40459 15 Fault Status 843 Spark Plug 12 (B6) OORL Warning PC 3.x
Gas Bitmap
29
40460 0 Fault Status 844 Spark Plug 13 (A7) OORL Warning PC 3.x
Gas Bitmap
30
40460 1 Fault Status 845 Spark Plug 14 (B7) OORL Warning PC 3.x
Gas Bitmap
30
40460 2 Fault Status 846 Spark Plug 15 (A8) OORL Warning PC 3.x
Gas Bitmap
30
40460 3 Fault Status 847 Spark Plug 16 (B8) OORL Warning PC 3.x
Gas Bitmap
30
40460 4 Fault Status 848 Spark Plug 17 (A9) OORL Warning PC 3.x
Gas Bitmap
30
40460 5 Fault Status 849 Spark Plug 18 (B9) OORL Warning PC 3.x
Gas Bitmap
30
40460 7 Fault Status 891 Spark Plug 1 (A1) Root Cause Un- Warning PC 3.x
Gas Bitmap known
30
40460 8 Fault Status 892 Spark Plug 2 (B1) Root Cause Un- Warning PC 3.x
Gas Bitmap known
30
40460 9 Fault Status 893 Spark Plug 3 (A2) Root Cause Un- Warning PC 3.x
Gas Bitmap known
30
40460 10 Fault Status 894 Spark Plug 4 (B2) Root Cause Un- Warning PC 3.x
Gas Bitmap known
30
40460 11 Fault Status 895 Spark Plug 5 (A3) Root Cause Un- Warning PC 3.x
Gas Bitmap known
30
40460 12 Fault Status 896 Spark Plug 6 (B3) Root Cause Un- Warning PC 3.x
Gas Bitmap known
30

369
Addr. Bit# Name Fault Event Name Response Control
Code
40460 13 Fault Status 897 Spark Plug 7 (A4) Root Cause Un- Warning PC 3.x
Gas Bitmap known
30
40460 14 Fault Status 898 Spark Plug 8 (B4) Root Cause Un- Warning PC 3.x
Gas Bitmap known
30
40460 15 Fault Status 899 Spark Plug 9 (A5) Root Cause Un- Warning PC 3.x
Gas Bitmap known
30
40461 0 Fault Status 911 Spark Plug 10 (B5) Root Cause Un- Warning PC 3.x
Gas Bitmap known
31
40461 1 Fault Status 912 Spark Plug 11 (A6) Root Cause Un- Warning PC 3.x
Gas Bitmap known
31
40461 2 Fault Status 913 Spark Plug 12 (B6) Root Cause Un- Warning PC 3.x
Gas Bitmap known
31
40461 3 Fault Status 914 Spark Plug 13 (A7) Root Cause Un- Warning PC 3.x
Gas Bitmap known
31
40461 4 Fault Status 915 Spark Plug 14 (B7) Root Cause Un- Warning PC 3.x
Gas Bitmap known
31
40461 5 Fault Status 916 Spark Plug 15 (A8) Root Cause Un- Warning PC 3.x
Gas Bitmap known
31
40461 6 Fault Status 917 Spark Plug 16 (B8) Root Cause Un- Warning PC 3.x
Gas Bitmap known
31
40461 7 Fault Status 918 Spark Plug 17 (A9) Root Cause Un- Warning PC 3.x
Gas Bitmap known
31
40461 8 Fault Status 919 Spark Plug 18 (B9) Root Cause Un- Warning PC 3.x
Gas Bitmap known
31
40461 10 Fault Status 1276 Knock Cyl 10 (B5) OORH Warning PC 3.x
Gas Bitmap
31
40461 11 Fault Status 1278 Knock Cyl 11 (A6) OORH Warning PC 3.x
Gas Bitmap
31

370
Addr. Bit# Name Fault Event Name Response Control
Code
40461 12 Fault Status 1279 Knock 12 (B6) High Warning Warning PC 3.x
Gas Bitmap
31
40461 13 Fault Status 1283 Knock Cyl 12 (B6) OORH Warning PC 3.x
Gas Bitmap
31
40461 14 Fault Status 1284 Knock 13 (A7) High Warning Warning PC 3.x
Gas Bitmap
31
40461 15 Fault Status 1288 Knock Cyl 13 (A7) OORH Warning PC 3.x
Gas Bitmap
31
40462 0 Fault Status 1289 Knock 14 (B7) High Warning Warning PC 3.x
Gas Bitmap
32
40462 1 Fault Status 1293 Knock Cyl 14 (B7) OORH Warning PC 3.x
Gas Bitmap
32
40462 2 Fault Status 1294 Knock 15 (A8) High Warning Warning PC 3.x
Gas Bitmap
32
40462 3 Fault Status 1298 Knock Cyl 15 (A8) OORH Warning PC 3.x
Gas Bitmap
32
40462 4 Fault Status 1299 Knock 16 (B8) High Warning Warning PC 3.x
Gas Bitmap
32
40462 6 Fault Status 1339 Knock Cyl 18 (B9) OORH Warning PC 3.x
Gas Bitmap
32
40462 7 Fault Status 1352 Knock 20 (B10) High Warning Warning PC 3.x
Gas Bitmap
32
40462 8 Fault Status 1353 Continuous_Light_Knock_Er- Shutdown PC 3.x
Gas Bitmap ror_20_(B10) w/Cooldown
32
40462 9 Fault Status 1354 Heavy_Knock_Error_20_(B10) Shutdown PC 3.x
Gas Bitmap w/Cooldown
32
40462 10 Fault Status 1355 Knock Cyl 20 (B10) OORL Warning PC 3.x
Gas Bitmap
32

371
Addr. Bit# Name Fault Event Name Response Control
Code
40462 11 Fault Status 1356 Knock Cyl 20 (B10) OORH Warning PC 3.x
Gas Bitmap
32
40462 12 Fault Status 1572 Continuous_Light_Knock_Er- Shutdown PC 3.x
Gas Bitmap ror_19_(A10) w/Cooldown
32
40462 13 Fault Status 1574 Heavy_Knock_Error_19_(A10) Shutdown PC 3.x
Gas Bitmap w/Cooldown
32
40462 14 Fault Status 1575 Knock Cyl 19 (A10) OORL Warning PC 3.x
Gas Bitmap
32
40462 15 Fault Status 1576 Knock Cyl 19 (A10) OORH Warning PC 3.x
Gas Bitmap
32
40463 0 Fault Status 1585 Knock Cyl 16 (B8) OORH Warning PC 3.x
Gas Bitmap
33
40463 1 Fault Status 1586 Knock 17 (A9) High Warning Warning PC 3.x
Gas Bitmap
33
40463 2 Fault Status 1591 Knock Cyl 17 (A9) OORH Warning PC 3.x
Gas Bitmap
33
40463 3 Fault Status 1592 Knock 18 (B9) High Warning Warning PC 3.x
Gas Bitmap
33
40463 4 Fault Status 1594 Knock 19 (A10) High Warning Warning PC 3.x
Gas Bitmap
33
40463 6 Fault Status 2193 HT Coolant Level Moderate High Warning PC 3.x
Gas Bitmap
33
40463 7 Fault Status 2231 Knock Cyl 1 (A1) OORH Warning PC 3.x
Gas Bitmap
33
40463 8 Fault Status 2232 Knock Cyl 2 (B1) OORH Warning PC 3.x
Gas Bitmap
33
40463 9 Fault Status 2233 Knock Cyl 3 (A2) OORH Warning PC 3.x
Gas Bitmap
33

372
Addr. Bit# Name Fault Event Name Response Control
Code
40463 10 Fault Status 2234 Knock Cyl 4 (B2) OORH Warning PC 3.x
Gas Bitmap
33
40463 11 Fault Status 2235 Knock Cyl 5 (A3) OORH Warning PC 3.x
Gas Bitmap
33
40463 12 Fault Status 2236 Knock Cyl 6 (B3) OORH Warning PC 3.x
Gas Bitmap
33
40463 13 Fault Status 2237 Knock Cyl 7 (A4) OORH Warning PC 3.x
Gas Bitmap
33
40463 14 Fault Status 2238 Knock Cyl 8 (B4) OORH Warning PC 3.x
Gas Bitmap
33
40463 15 Fault Status 2239 Knock Cyl 9 (A5) OORH Warning PC 3.x
Gas Bitmap
33
40464 0 Fault Status 2279 Knock 11 (A6) High Warning Warning PC 3.x
Gas Bitmap
34
40464 1 Fault Status 2431 Knock 1 (A1) High Warning Warning PC 3.x
Gas Bitmap
34
40464 2 Fault Status 2432 Knock 2 (B1) High Warning Warning PC 3.x
Gas Bitmap
34
40464 3 Fault Status 2433 Knock 3 (A2) High Warning Warning PC 3.x
Gas Bitmap
34
40464 4 Fault Status 2434 Knock 4 (B2) High Warning Warning PC 3.x
Gas Bitmap
34
40464 5 Fault Status 2435 Knock 5 (A3) High Warning Warning PC 3.x
Gas Bitmap
34
40464 6 Fault Status 2436 Knock 6 (B3) High Warning Warning PC 3.x
Gas Bitmap
34
40464 7 Fault Status 2437 Knock 7 (A4) High Warning Warning PC 3.x
Gas Bitmap
34

373
Addr. Bit# Name Fault Event Name Response Control
Code
40464 8 Fault Status 2438 Knock 8 (B4) High Warning Warning PC 3.x
Gas Bitmap
34
40464 9 Fault Status 2439 Knock 9 (A5) High Warning Warning PC 3.x
Gas Bitmap
34
40464 10 Fault Status 2441 Knock 10 (B5) High Warning Warning PC 3.x
Gas Bitmap
34
40464 11 Fault Status 2514 Exhaust Temperature 19 (A10) Abnor- Shutdown PC 3.x
Gas Bitmap mal Rate w/Cooldown
34
40464 12 Fault Status 2515 Exhaust Temperature 20 (B10) Abnor- Shutdown PC 3.x
Gas Bitmap mal Rate w/Cooldown
34
40464 13 Fault Status 2553 Engine Oil Level Low Warning Error Warning PC 3.x
Gas Bitmap
34
40464 14 Fault Status 2568 Gas Supply Pressure Critical High Shutdown PC 3.x
Gas Bitmap w/Cooldown
34
40464 15 Fault Status 2569 Gas Supply Pressure Critical Low Shutdown PC 3.x
Gas Bitmap w/Cooldown
34
40465 0 Fault Status 2586 Spark Plug 1 (A1) High Warning NONE PC 3.x
Gas Bitmap
35
40465 1 Fault Status 2587 Spark Plug 2 (B1) High Warning NONE PC 3.x
Gas Bitmap
35
40465 2 Fault Status 2588 Spark Plug 3 (A2) High Warning NONE PC 3.x
Gas Bitmap
35
40465 3 Fault Status 2589 Spark Plug 4 (B2) High Warning NONE PC 3.x
Gas Bitmap
35
40465 4 Fault Status 2591 Spark Plug 5 (A3) High Warning NONE PC 3.x
Gas Bitmap
35
40465 5 Fault Status 2592 Spark Plug 6 (B3) High Warning NONE PC 3.x
Gas Bitmap
35

374
Addr. Bit# Name Fault Event Name Response Control
Code
40465 6 Fault Status 2593 Spark Plug 1 (A1) Low Warning NONE PC 3.x
Gas Bitmap
35
40465 7 Fault Status 2594 Spark Plug 2 (B1) Low Warning NONE PC 3.x
Gas Bitmap
35
40465 8 Fault Status 2595 Spark Plug 3 (A2) Low Warning NONE PC 3.x
Gas Bitmap
35
40465 9 Fault Status 2596 Spark Plug 4 (B2) Low Warning NONE PC 3.x
Gas Bitmap
35
40465 10 Fault Status 2597 Spark Plug 5 (A3) Low Warning NONE PC 3.x
Gas Bitmap
35
40465 11 Fault Status 2598 Spark Plug 6 (B3) Low Warning NONE PC 3.x
Gas Bitmap
35
40465 12 Fault Status 2646 HT Coolant Temperature Condition Ex- Warning PC 3.x
Gas Bitmap ists
35
40466 0 Fault Status 3262 Spark Plug 7 (A4) High Warning NONE PC 3.x
Gas Bitmap
36
40466 1 Fault Status 3263 Spark Plug 7 (A4) Low Warning NONE PC 3.x
Gas Bitmap
36
40466 2 Fault Status 3264 Spark Plug 8 (B4) High Warning NONE PC 3.x
Gas Bitmap
36
40466 3 Fault Status 3265 Spark Plug 8 (B4) Low Warning NONE PC 3.x
Gas Bitmap
36
40466 4 Fault Status 3266 Spark Plug 9 (A5) High Warning NONE PC 3.x
Gas Bitmap
36
40466 5 Fault Status 3267 Spark Plug 9 (A5) Low Warning NONE PC 3.x
Gas Bitmap
36
40466 6 Fault Status 3268 Spark Plug 10 (B5) High Warning NONE PC 3.x
Gas Bitmap
36

375
Addr. Bit# Name Fault Event Name Response Control
Code
40466 7 Fault Status 3269 Spark Plug 10 (B5) Low Warning NONE PC 3.x
Gas Bitmap
36
40466 8 Fault Status 3271 Spark Plug 11 (A6) High Warning NONE PC 3.x
Gas Bitmap
36
40466 9 Fault Status 3272 Spark Plug 11 (A6) Low Warning NONE PC 3.x
Gas Bitmap
36
40466 10 Fault Status 3273 Spark Plug 12 (B6) High Warning NONE PC 3.x
Gas Bitmap
36
40466 11 Fault Status 3274 Spark Plug 12 (B6) Low Warning NONE PC 3.x
Gas Bitmap
36
40466 12 Fault Status 3275 Spark Plug 13 (A7) High Warning NONE PC 3.x
Gas Bitmap
36
40466 13 Fault Status 3276 Spark Plug 13 (A7) Low Warning NONE PC 3.x
Gas Bitmap
36
40466 14 Fault Status 3277 Spark Plug 14 (B7) High Warning NONE PC 3.x
Gas Bitmap
36
40466 15 Fault Status 3278 Spark Plug 14 (B7) Low Warning NONE PC 3.x
Gas Bitmap
36
40467 0 Fault Status 3279 Spark Plug 15 (A8) High Warning NONE PC 3.x
Gas Bitmap
37
40467 1 Fault Status 3281 Spark Plug 15 (A8) Low Warning NONE PC 3.x
Gas Bitmap
37
40467 2 Fault Status 3282 Spark Plug 16 (B8) High Warning NONE PC 3.x
Gas Bitmap
37
40467 3 Fault Status 3283 Spark Plug 16 (B8) Low Warning NONE PC 3.x
Gas Bitmap
37
40467 4 Fault Status 3284 Spark Plug 17 (A9) High Warning NONE PC 3.x
Gas Bitmap
37

376
Addr. Bit# Name Fault Event Name Response Control
Code
40467 5 Fault Status 3285 Spark Plug 17 (A9) Low Warning NONE PC 3.x
Gas Bitmap
37
40467 6 Fault Status 3286 Spark Plug 18 (B9) High Warning NONE PC 3.x
Gas Bitmap
37
40467 7 Fault Status 3287 Spark Plug 18 (B9) Low Warning NONE PC 3.x
Gas Bitmap
37
40467 8 Fault Status 3288 Exhaust Aft Outlet Oxygen Relay Warning PC 3.x
Gas Bitmap OORH
37
40467 9 Fault Status 3289 Exhaust Aft Outlet Oxygen Relay Warning PC 3.x
Gas Bitmap OORL
37
40467 10 Fault Status 3291 Exhaust Aft Inlet Oxygen Relay OORH Warning PC 3.x
Gas Bitmap
37
40467 11 Fault Status 3292 Exhaust Aft Inlet Oxygen Relay OORL Warning PC 3.x
Gas Bitmap
37
40467 12 Fault Status 3293 Exhaust Oxygen Relay OORH Warning PC 3.x
Gas Bitmap
37
40467 13 Fault Status 3294 Exhaust Oxygen Relay OORL Warning PC 3.x
Gas Bitmap
37
40468 3 Fault Status 3365 External Air Pressure Low Warning Er- Warning PC 3.x
Gas Bitmap ror
38
40468 4 Fault Status 3384 Manifold_Absolute_Pres- Warning PC 3.x
Gas Bitmap sure_2_High_Error
38
40468 5 Fault Status 3391 Manifold_Absolute_Pres- Warning PC 3.x
Gas Bitmap sure_2_Low_Error
38
40468 6 Fault Status 3392 Int Man Pressure 2 Critical High Shutdown PC 3.x
Gas Bitmap w/Cooldown
38
40468 7 Fault Status 3393 Int Man Pressure 2 Moderate High Warning PC 3.x
Gas Bitmap
38

377
Addr. Bit# Name Fault Event Name Response Control
Code
40468 9 Fault Status 3397 Low Gearbox Oil Pressure − Condition Shutdown PC 3.x
Gas Bitmap Exists
38
40468 10 Fault Status 3398 High Gearbox Oil Temperature − Con- Shutdown PC 3.x
Gas Bitmap dition Exists w/Cooldown
38
40468 11 Fault Status 3399 Differential Fault − Condition Exists Shutdown PC 3.x
Gas Bitmap
38
40468 12 Fault Status 3411 DC Power Supply Fault − Condition Ex- Warning PC 3.x
Gas Bitmap ists
38
40468 13 Fault Status 3412 GIB Isolator Open Fault − Condition Warning PC 3.x
Gas Bitmap Exists
38
40468 14 Fault Status 3413 Radiator Fan Trip Fault − Condition Ex- Warning PC 3.x
Gas Bitmap ists
38
40468 15 Fault Status 3414 Ventilator Fan Trip Fault − Condition Warning PC 3.x
Gas Bitmap Exists
38
40469 0 Fault Status 3415 Louvres Closed Fault − Condition Ex- Warning PC 3.x
Gas Bitmap ists
39
40469 1 Fault Status 3416 Start System Fault − Condition Exists Warning PC 3.x
Gas Bitmap
39
40469 2 Fault Status 3417 Alternator Heater Trip Fault − Condition Warning PC 3.x
Gas Bitmap Exists
39
40469 4 Fault Status 9971 ECM Derate Fault NONE PC 3.x
Gas Bitmap
39
40469 5 Fault Status 3479 Start−Inhibit Shutdown Fault Shutdown PC 3.x
Gas Bitmap
39
40469 6 Fault Status 3481 Start−Inhibit Warning Fault Event Warning PC 3.x
Gas Bitmap
39
40469 7 Fault Status 3483 High Alternator Temperature 1 Shut- Shutdown PC 3.x
Gas Bitmap down Fault
39

378
Addr. Bit# Name Fault Event Name Response Control
Code
40469 8 Fault Status 3484 High Alternator Temperature 2 Shut- Shutdown PC 3.x
Gas Bitmap down Fault
39
40469 9 Fault Status 3485 High Alternator Temperature 3 Shut- Shutdown PC 3.x
Gas Bitmap down Fault
39
40469 10 Fault Status 3486 High Drive End Bearing Temperature Shutdown PC 3.x
Gas Bitmap Shutdown Fault
39
40469 11 Fault Status 3487 High Non−Drive End Bearing Temp Shutdown PC 3.x
Gas Bitmap Shutdown Fault
39
40469 12 Fault Status 3482 Off Load Running Fault Shutdown PC 3.x
Gas Bitmap
39
40470 0 Fault Status 3491 Oil Filter Restriction High Shutdown PC 3.x
Gas Bitmap w/Cooldown
40
40470 1 Fault Status 2313 Fuel Control Valve Error Warning PC 3.x
Gas Bitmap
40
40470 2 Fault Status 3475 Engine Electronic Fuel Valve #2 OORH Warning PC 3.x
Gas Bitmap
40
40470 3 Fault Status 3476 Engine Electronic Fuel Valve #2 OORL Warning PC 3.x
Gas Bitmap
40
40470 4 Fault Status 2812 Throttle Control Actuator Error Shutdown PC 3.x
Gas Bitmap w/Cooldown
40
40470 5 Fault Status 3489 Compressor Bypass Actuator Error Warning PC 3.x
Gas Bitmap
40
40470 6 Fault Status 3458 Knock Engine Derate Warning PC 3.x
Gas Bitmap
40
40470 8 Fault Status 3499 Throttle Actuator 2− Special Instruction Shutdown PC 3.x
Gas Bitmap w/Cooldown
40
40470 9 Fault Status 3511 Throttle Actuator 2− Shorted High Shutdown PC 3.x
Gas Bitmap w/Cooldown
40

379
Addr. Bit# Name Fault Event Name Response Control
Code
40470 10 Fault Status 3512 Throttle Actuator 2− Shorted Low Shutdown PC 3.x
Gas Bitmap w/Cooldown
40
40470 11 Fault Status 2752 Throttle Actuator − Shorted High Shutdown PC 3.x
Gas Bitmap w/Cooldown
40
40470 12 Fault Status 3514 Throttle Actuator − Shorted Low Shutdown PC 3.x
Gas Bitmap w/Cooldown
40
40470 13 Fault Status 3515 Throttle Actuator − Special instruction Shutdown PC 3.x
Gas Bitmap w/Cooldown
40
40470 14 Fault Status 3521 Throttle Actuator − Temperature low Warning PC 3.x
Gas Bitmap
40
40470 15 Fault Status 3522 Throttle Actuator 2− Temp low Warning PC 3.x
Gas Bitmap
40
40474 10 Fault Status 4686 Connector Cap Not Present Warning PC 3.x
Gas Bitmap
40

380
4. NFPA 110 & Extended Annunciation Bitmap

Table 4-1 NFPA110 bitmap (See Section 1 Reg Table 4-2 Extended Annunciation Bitmap (See Sec-
40016, Section 2 Reg 40716, 40717and Section 5) tion 1 Reg. 40017 and Section 5)
BIT DESCRIPTION
BIT DESCRIPTION
15 Common Alarm
15 Check Genset
14 Genset Supplying Load
14 Ground Fault
13 Genset Running
13 High AC Voltage
12 Not in Auto
12 Low AC Voltage
11 High Battery Voltage
11 Under Frequency
10 Low Battery Voltage 10 Overload
9 Charger AC Failure 9 Overcurrent
8 Fail to Start 8 Short Circuit
7 Low Coolant Temperature 7 Reverse KW
6 Pre-high Engine Temperature 6 Reverse KVAR
5 High Engine Temperature 5 Fail to Sync
4 Pre-low Oil Pressure 4 Fail to Close
3 Low Oil Pressure 3 Load Demand
2 Overspeed 2 Genset Circuit Breaker Tripped
1 Low Coolant Level 1 Utility Circuit Breaker Tripped
0 Low Fuel Level 0 Emergency Stop

Table 4-3 NFPA110 bitmap (See Section 6) Table 4-4 Extended Annunciation Bitmap (See Sec-
tion 6)
BIT DESCRIPTION
BIT DESCRIPTION
15 Source 1 Connected
15 Source 1 Available
14 Source 2 Connected
14 Source 2 Available
13 NA
13 Source 1 Connected
12 Not in Auto
12 Source 2 Connected
11 NA
11 ATS Common Alarm
10 NA
10 Not In Auto
9 Charger AC Failure
9 Test / Exercise In Progress
8 NA 8 Low Battery Voltage
7 NA 7 Load Shed
6 NA 6 Transfer Inhibit
5 NA 5 Retransfer Inhibit
4 NA 4 Fail To Close
3 NA 3 Fail To Disconnect
2 NA 2 Fail To Synchronize
1 NA 1 Bypass to Source 1
0 NA 0 Bypass to Source 2

381
THIS PAGE LEFT INTENTIONALLY BLANK

382
5. DMC 1000 Modbus Parametric Data

Addr. System Name Access Specifications Description Function


42001 MB Logical Read/ Multiplier: Unit: Logical address Communica-
Read Address Write 1.000000000000 Lower Limit: .000 to be read via tions
Offset: 0 Upper Limit: Modbus
Size (bits): 16 65535.000
Sign: U Default: 0
42002 MB Logical Read Multiplier: Unit: Logical data to Communica-
Read Data Only 1.000000000000 Lower Limit: be read via Mod- tions
Offset: 0 Upper Limit: bus
Size (bits): 32 Default:
Sign: U
42009 Device Type Read Multiplier: Unit: Hard coded de- Communica-
Only 1.000000000000 Lower Limit: vice type id = 52 tions
Offset: 0 Upper Limit: (0x0034)
Size (bits): 16 Default:
Sign: U
42010 Software Ver- Read Multiplier: Unit: Software version Controller In-
sion Only 0.000100000000 Lower Limit: number formation
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42012 Current Fault Read Multiplier: Unit: The most recent- Fault and
Status Only 1.000000000000 Lower Limit: ly occurring fault Event Info
Offset: 0 Upper Limit: which is still ac-
Size (bits): 16 Default: tive
Sign: U
42018 Genset L1N Read Multiplier: Unit: Volts Generator set Voltage
Voltage Only 1.000000000000 Lower Limit: L1N voltage
Offset: 0 Upper Limit:
Size (bits): 16 Default
Sign: U
42019 Genset L2N Read Multiplier: Unit: Volts Generator set Voltage
Voltage Only 1.000000000000 Lower Limit: L2N voltage
Offset: 0 Upper Limit:
Size (bits): 16 Default
Sign: U

42020 Genset L3N Read Multiplier: Unit: Volts Generator set Voltage
Voltage Only 1.000000000000 Lower Limit: L3N voltage
Offset: 0 Upper Limit:
Size (bits): 16 Default
Sign: U
42021 Genset LN Av- Read Multiplier: Unit: Volts Generator set LN Voltage
erage Voltage Only 1.000000000000 Lower Limit: average voltage
Offset: 0 Upper Limit:
Size (bits): 16 Default
Sign: U

383
Addr. System Name Access Specifications Description Function
42022 Genset L1L2 Read Multiplier: Unit: Volts Generator set Voltage
Voltage Only 1.000000000000 Lower Limit: L1L2 voltage
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42023 Genset L2L3 Read Multiplier: Unit: Volts Generator set Voltage
Voltage Only 1.000000000000 Lower Limit: L2L3 voltage
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42024 Genset L3L1 Read Multiplier: Unit: Volts Generator set Voltage
Voltage Only 1.000000000000 Lower Limit: L3L1 voltage
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42025 Genset LL Av- Read Multiplier: Unit: Volts Generator set LL Voltage
erage Voltage Only 1.000000000000 Lower Limit: average voltage
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42026 Genset L1 Read Multiplier: Unit: Amps Generator set L1 Current
Current Only 1.000000000000 Lower Limit: current
Offset: 0 Upper Limit:
Size (bits): 16 Default
Sign: U
42027 Genset L2 Read Multiplier: Unit: Amps Generator set L2 Current
Current Only 1.000000000000 Lower Limit: current
Offset: 0 Upper Limit:
Size (bits): 16 Default
Sign: U
42028 Genset L3 Read Multiplier: Unit: Amps Generator set L3 Current
Current Only 1.000000000000 Lower Limit: current
Offset: 0 Upper Limit:
Size (bits): 16 Default
Sign: U
42029 Genset Aver- Read Multiplier: Unit: Amps Generator set av- Current
age Current Only 1.000000000000 Lower Limit: erage current
Offset: 0 Upper Limit:
Size (bits): 16 Default
Sign: U
42030 Genset L1 kW Read Multiplier: Unit: kW Generator set L1 Current
Only 1.000000000000 Lower Limit: kW
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: S
42031 Genset L2 kW Read Multiplier: Unit: kW Generator set L2 Current
Only 1.000000000000 Lower Limit: kW
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: S

384
Addr. System Name Access Specifications Description Function
42032 Genset L3 kW Read Multiplier: Unit: kW Generator set L3 Power
Only 1.000000000000 Lower Limit: kW
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: S
42033 Genset Total Read Multiplier: Unit: kW Generator set to- Power
kW Only 1.000000000000 Lower Limit: tal kW
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: S
42034 Genset L1 Read Multiplier: Unit: kVAR Generator set L1 Power
kVAR Only 1.000000000000 Lower Limit: kVAR
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: S
42035 Genset L2 Read Multiplier: Unit: kVAR Generator set L2 Power
kVAR Only 1.000000000000 Lower Limit: kVAR
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: S
42036 Genset L3 Read Multiplier: Unit: kVAR Generator set L3 Power
kVAR Only 1.000000000000 Lower Limit: kVAR
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: S
42037 Genset Total Read Multiplier: Unit: kVAR Generator set to- Power
kVAR Only 1.000000000000 Lower Limit: tal kVAR
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: S
42038 Genset Total Read Multiplier: Unit: Generator set to- Power
Power Factor Only 0.010000000000 Lower Limit: tal power factor
Offset: 0 Upper Limit:
Size (bits): 8 Default:
Sign: S
42039 Genset L1 Read Multiplier: Unit: kVA Generator set L1 Power
kVA Only 1.000000000000 Lower Limit: kVA
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42040 Genset L2 Read Multiplier: Unit: kVA Generator Set L2 Power
kVA Only 1.000000000000 Lower Limit: kVA
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42041 Genset L3 Read Multiplier: Unit: kVA Generator set L3 Power
kVA Only 1.000000000000 Lower Limit: kVA
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U

385
Addr. System Name Access Specifications Description Function
42042 Genset Total Read Multiplier: Unit: kVA Generator set to- Power
kVA Only 1.000000000000 Lower Limit: kVA tal kVA
Offset: 0 Upper Limit: kVA
Size (bits): 16 Default:
Sign: U
42043 MB Genset Read Multiplier: Unit: Hz Generator set Communica-
Frequency Only 0.100000000000 Lower Limit: Hz line frequency tions
Offset: 0 Upper Limit: Hz scaled by 10 =
Size (bits): 16 Default: 1Hz for Modbus
Sign: U
42044 Genset Total Read Multiplier: Unit: kWh Generator set to- Energy
Negative kWh Only 1.000000000000 Lower Limit: kWh tal negative kWh
Offset: 0 Upper Limit: kWh accumulation
Size (bits): 32 Default:
Sign: U
42046 Genset Total Read Multiplier: Unit: kWh Generator set to- Energy
Positive kWh Only .100000000000 Lower Limit: kWh tal positive kWh
Offset: 0 Upper Limit: kWh accumulation
Size (bits): 32 Default:
Sign: U
42048 Genset Total Read Multiplier: Unit: kWh Generator set to- Energy
Net kWh Only 1.000000000000 Lower Limit: kWh tal net kWh accu-
Offset: 0 Upper Limit: kWh mulation
Size (bits): 32 Default:
Sign: S
42050 Genset Total Read Multiplier: Unit: kVARh Generator set to- Energy
Negative Only 1.000000000000 Lower Limit: kVARh tal negative
kVARh Offset: 0 Upper Limit: kVARh kVARh accu-
Size (bits): 32 Default: mulation
Sign: U
42052 Genset Total Read Multiplier: Unit: kVARh Generator set to- Energy
Positive Only 1.000000000000 Lower Limit: kVARh tal positive
kVARh Offset: 0 Upper Limit: kVARh kVARh accu-
Size (bits): 32 Default: mulation
Sign: U
42054 Genset Total Read Multiplier: Unit: kVARh Generator set to- Energy
Net kVARh Only 1.000000000000 Lower Limit: kVARh tal net kVARh ac-
Offset: 0 Upper Limit: kVARh cumulation
Size (bits): 32 Default:
Sign: S
40056 Genset Total Read Multiplier: Unit: kVAh Generator set to- Energy
kVAh Only 1.000000000000 Lower Limit: kVAh tal kVAh accu-
Offset: 0 Upper Limit: kVAh mulation
Size (bits): 32 Default:
Sign: U

386
Addr. System Name Access Specifications Description Function
42058 Genset Avail- Read Multiplier: Unit: Amps Calculated Amps Current
able Current Only 1.000000000000 Lower Limit: which represent
Offset: 0 Upper Limit: 100% generator
Size (bits): 16 Default: set bus current
Sign: U −− used by baro-
graph
42059 Genset L1 Read Multiplier: Unit: % Generator set L1 Current
Current Per- Only 0.100000000000 Lower Limit: current as per-
cent Offset: 0 Upper Limit: cent of generator
Size (bits): 16 Default: set total current
Sign: U capacity−−used
by barograph
42060 Genset L2 Read Multiplier: Unit: % Generator set L2 Current
Current Per- Only 0.100000000000 Lower Limit: current as per-
cent Offset: 0 Upper Limit: cent of generator
Size (bits): 16 Default: set total current
Sign: U capacity−−used
by barograph
42061 Genset L3 Read Multiplier: Unit: % Generator set L3 Current
Current Per- Only 0.100000000000 Lower Limit: current as per-
cent Offset: 0 Upper Limit: cent of generator
Size (bits): 16 Default: set total current
Sign: U capacity−−used
by barograph
42062 Genset Total Read Multiplier: Unit: % Generator set to- Power
kW Percent Only 0.100000000000 Lower Limit: tal kW as percent
Offset: 0 Upper Limit: of total generator
Size (bits): 16 Default: set capacity −−
Sign: S used by baro-
graph
42063 Genset Fre- Read Multiplier: Unit: % Generator set Frequency
quency Per- Only 0.100000000000 Lower Limit: frequency as per-
cent Offset: 0 Upper Limit: cent of system
Size (bits): 16 Default: frequency −−
Sign: U used by baro-
graph
42064 Genset L1L2 Read Multiplier: Unit: % Generator set Voltage
Voltage% Only 0.100000000000 Lower Limit: L1L2 voltage%
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42065 Genset L2L3 Read Multiplier: Unit: % Generator set Voltage
Voltage% Only 0.100000000000 Lower Limit: L2L3 voltage%
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U

387
Addr. System Name Access Specifications Description Function
42066 Genset L3L1 Read Multiplier: Unit: % Generator set Voltage
Voltage% Only 0.100000000000 Lower Limit: L3L1 voltage%
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42118 Utility L1N Vol- Read Multiplier: Unit: Volts Utility L1N vol- Voltage
tage Only 1.000000000000 Lower Limit: tage
Offset: 0 Upper Limit:
Size (bits): 16 Default: 0
Sign: U
42119 Utility L2N Vol- Read Multiplier: Unit: Volts Utility L2N vol- Voltage
tage Only 1.000000000000 Lower Limit: tage
Offset: 0 Upper Limit:
Size (bits): 16 Default: 0
Sign: U
42120 Utility L3N Vol- Read Multiplier: Unit: Volts Utility L3N volta- Voltage
tage Only 1.000000000000 Lower Limit: ge
Offset: 0 Upper Limit:
Size (bits): 16 Default: 0
Sign: U
42121 Utility LN Av- Read Multiplier: Unit: Volts Utility LN aver- Voltage
erage Voltage Only 1.000000000000 Lower Limit: age voltage
Offset: 0 Upper Limit:
Size (bits): 16 Default: 0
Sign: U
42122 Utility L1L2 Read Multiplier: Unit: Volts Utility L1L2 vol- Voltage
Voltage Only 1.000000000000 Lower Limit: tage
Offset: 0 Upper Limit:
Size (bits): 16 Default: 0
Sign: U
42123 Utility L2L3 Read Multiplier: Unit: Volts Utility L2L3 volta- Voltage
Voltage Only 1.000000000000 Lower Limit: ge
Offset: 0 Upper Limit:
Size (bits): 16 Default: 0
Sign: U
42124 Utility L3L1 Read Multiplier: Unit: Volts Utility L3L1 volta- Voltage
Voltage Only 1.000000000000 Lower Limit: ge
Offset: 0 Upper Limit:
Size (bits): 16 Default: 0
Sign: U
42125 Utility LL Aver- Read Multiplier: Unit: Volts Utility LL average Voltage
age Voltage Only 1.000000000000 Lower Limit: voltage
Offset: 0 Upper Limit:
Size (bits): 16 Default: 0
Sign: U
42126 Utility L1 Cur- Read Multiplier: Unit: Amps Utility L1 current Current
rent Only 1.000000000000 Lower Limit:
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U

388
Addr. System Name Access Specifications Description Function
42127 Utility L2 Cur- Read Multiplier: Unit: Amps Utility L2 current Current
rent Only 1.000000000000 Lower Limit:
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42128 Utility L3 Cur- Read Multiplier: Unit: Amps Utility L3 current Current
rent Only 1.000000000000 Lower Limit:
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42129 Utility Average Read Multiplier: Unit: Amps Utility average Current
Current Only 1.000000000000 Lower Limit: current
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42130 Utility L1 kW Read Multiplier: Unit: kW Utility L1 kW Power
Only 1.000000000000 Lower Limit:
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: S
42131 Utility L2 kW Read Multiplier: Unit: kW Utility L2 kW Power
Only 1.000000000000 Lower Limit:
Offset: 0 Upper Limit:
Size (bits): 16 Default
Sign: S
42132 Utility L3 kW Read Multiplier: Unit: kW Utility L3 kW Power
Only 1.000000000000 Lower Limit:
Offset: 0 Upper Limit:
Size (bits): 16 Default
Sign: S
42133 Utility Total kW Read Multiplier: Unit: kW Utility total kW Power
Only 1.000000000000 Lower Limit:
Offset: 0 Upper Limit:
Size (bits): 16 Default
Sign: S
42134 Utility L1 Read Multiplier: Unit: kVAR Utility L1 kVAR Power
kVARt Only 1.000000000000 Lower Limit:
Offset: 0 Upper Limit:
Size (bits): 16 Default
Sign: S
42135 Utility L2 kVAR Read Multiplier: Unit: kVAR Utility L2 kVAR Power
Only 1.000000000000 Lower Limit:
Offset: 0 Upper Limit:
Size (bits): 16 Default
Sign: S
42136 Utility L3 kVAR Read Multiplier: Unit: kVAR Utility L3 kVAR Power
Only 1.000000000000 Lower Limit:
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: S

389
Addr. System Name Access Specifications Description Function
42137 Utility Total Read Multiplier: Unit: kVAR Utility total kVAR Power
kVAR Only 1.000000000000 Lower Limit:
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: S
42138 Utility Total Read Multiplier: Unit: Utility total power Power
Power Factor Only .010000000000 Lower Limit: factor
Offset: 0 Upper Limit:
Size (bits): 8 Default:
Sign: S
42139 Utility L1 kVA Read Multiplier: Unit: kVA Utility L1 kVA Power
Only 1.000000000000 Lower Limit:
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42140 Utility L2 kVA Read Multiplier: Unit: kVA Utility L2 kVA Power
Only 1.000000000000 Lower Limit:
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42141 Utility L3 kVA Read Multiplier: Unit: kVA Utility L3 kVA Power
Only 1.000000000000 Lower Limit:
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42142 Utility Total Read Multiplier: Unit: kVA Utility total kVA Power
kVA Only 1.000000000000 Lower Limit:
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42143 MB Utility Fre- Read Multiplier: Unit: Hz Utility line fre- Communica-
quency Only .100000000000 Lower Limit: quency scaled by tions
Offset: 0 Upper Limit: 10 = 1Hz for
Size (bits): 16 Default: Modbus
Sign: U
42144 Utility Total Read Multiplier: Unit: kWh Utility total nega- Energy
Negative kWh Only 1.000000000000 Lower Limit: tive kWh accu-
Offset: 0 Upper Limit: mulation
Size (bits): 32 Default:
Sign: U
42146 Utility Total Read Multiplier: Unit: kWh Utility total posi- Energy
Positive kWh Only 1.000000000000 Lower Limit: tive kWh accu-
Offset: 0 Upper Limit: mulation
Size (bits): 32 Default:
Sign: U
42148 Utility Total Read Multiplier: Unit: kWh Utility total net Energy
Net kWh Only 1.000000000000 Lower Limit: kWh accumula-
Offset: 0 Upper Limit: tion
Size (bits): 32 Default:
Sign: S

390
Addr. System Name Access Specifications Description Function
42150 Utility Total Read Multiplier: Unit: kVARh Utility total nega- Energy
Negative Only 1.000000000000 Lower Limit: tive kVARh accu-
kVARh Offset: 0 Upper Limit: mulation
Size (bits): 32 Default:
Sign: U
42152 Utility Total Read Multiplier: Unit: kVARh Utility total posi- Energy
Positive Only 1.000000000000 Lower Limit: tive kVARh accu-
kVARh Offset: 0 Upper Limit: mulation
Size (bits): 32 Default:
Sign: U
42154 Utility Total Read Multiplier: Unit: kVARh Utility total net Energy
Net kVARh Only 1.000000000000 Lower Limit: kVARh accu-
Offset: 0 Upper Limit: mulation
Size (bits): 32 Default:
Sign: S
42156 Utility Total Read Multiplier: Unit: kVARh Utility total kVAh Energy
kVAh Only 1.000000000000 Lower Limit: accumulation
Offset: 0 Upper Limit:
Size (bits): 32 Default:
Sign: U
42158 System Total Read Multiplier: Unit: kW Sum of generator Power
kW Only 1.000000000000 Lower Limit: set bus and utility
Offset: 0 Upper Limit: bus kW
Size (bits): 16 Default:
Sign: S
42159 System Total Read Multiplier: Unit: kVAR Sum of generator Power
kVAR Only 1.000000000000 Lower Limit: set bus and utility
Offset: 0 Upper Limit: bus kVAR
Size (bits): 16 Default:
Sign: S
42160 System Total Read Multiplier: Unit: System total Power
Power Factor Only 0.010000000000 Lower Limit: power factor
Offset: 0 Upper Limit: (totalized value of
Size (bits): 8 Default: utility bus plus
Sign: S generator set
bus)
42161 System Total Read Multiplier: Unit: kVA Sum of generator Power
kVA Only 1.000000000000 Lower Limit: set bus and utility
Offset: 0 Upper Limit: bus kVA
Size (bits): 16 Default:
Sign: U
42162 Utility L1 Cur- Read Multiplier: Unit: % barograph Current
rent Percent Only .100000000000 Lower Limit:
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U

391
Addr. System Name Access Specifications Description Function
42163 Utility L2 Cur- Read Multiplier: Unit: % barograph Current
rent Percent Only .100000000000 Lower Limit:
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42164 Utility L3 Cur- Read Multiplier: Unit: % barograph Current
rent Percent Only .100000000000 Lower Limit:
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U

42165 Utility Total kW Read Multiplier: Unit: % Utility total kW as Power


Percent Only .100000000000 Lower Limit: percent of total
Offset: 0 Upper Limit: utility capacity −−
Size (bits): 16 Default: used by baro-
Sign: S graph

42166 Utility Fre- Read Multiplier: Unit: % Utility frequency Frequency


quency Per- Only .100000000000 Lower Limit: as percent of
cent Offset: 0 Upper Limit: System Frequen-
Size (bits): 16 Default: cy −− used by
Sign: U barograph
42167 Utility L1L2 Read Multiplier: Unit: % Utility L1L2 volt- Voltage
Voltage% Only .100000000000 Lower Limit: age%
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42168 Utility L2L3 Read Multiplier: Unit: % Utility L2L3 volt- Voltage
Voltage% Only .100000000000 Lower Limit: age%
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42169 Utility L3L1 Read Multiplier: Unit: % Utility L3L1 volt- Voltage
Voltage% Only .100000000000 Lower Limit: age%
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42200 Total Number Read Multiplier: Unit: NA Number of gener- System Infor-
of Gensets Only 1.000000000000 Lower Limit: ator sets with mation
Offset: 0 Upper Limit: non−zero ratings
Size (bits): 16 Default: entered
Sign: U
42201 Total System Read Multiplier: Unit: kW Sum of the gen- System Infor-
Capacity Only 1.000000000000 Lower Limit: erator set kW ra- mation
Offset: 0 Upper Limit: tings
Size (bits): 16 Default:
Sign: S

392
Addr. System Name Access Specifications Description Function
42202 Total Online Read Multiplier: Unit: kW Sum of the gen- System In-
Capacity Only 1.000000000000 Lower Limit: erator set kW rat- formation
Offset: 0 Upper Limit: ings for generator
Size (bits): 16 Default: sets which are
Sign: S online
42203 Programmed Read Multiplier: Unit: seconds Countdown value PTC Timers
Transition Tim- Only .100000000000 Lower Limit: of the pro-
er Offset: 0 Upper Limit: grammed transi-
Size (bits): 16 Default: tion timer
Sign: U
42204 Transfer Timer Read Multiplier: Unit: seconds Countdown value PTC Timers
Only .100000000000 Lower Limit: of the transfer
Offset: 0 Upper Limit: timer
Size (bits): 16 Default: 0
Sign: U
42205 Retransfer Read Multiplier: Unit: seconds Countdown value PTC Timers
Timer Only .100000000000 Lower Limit: of the retransfer
Offset: 0 Upper Limit: timer
Size (bits): 16 Default:
Sign: U
42206 Maximum Par- Read Multiplier: Unit: seconds Countdown value PTC Timers
allel Timer Only .100000000000 Lower Limit: of the maximum
Offset: 0 Upper Limit: parallel timer
Size (bits): 16 Default:
Sign: U
42207 kW Load Re- Read Multiplier: Unit: kW kW control refer- Master Load
ference Only 1.000000000000 Lower Limit: ence value for Control
Offset: 0 Upper Limit: utility paralleling
Size (bits): 16 Default:
Sign: S
42212 Active Transi- Read Multiplier: Unit: seconds Countdown timer PTC Timers
tion Timer Only .010000000000 Lower Limit: value of active
Offset: 0 Upper Limit: timer
Size (bits): 16 Default:
Sign: U
42213 Hardware Ver- Read Multiplier: Unit: Indicates the Discrete In-
sion Only 1.000000000000 Lower Limit: hardware version puts
Offset: 0 Upper Limit: of the board
Size (bits): 8 Default:
Sign: U
42214 Controller On Read Multiplier: Unit: seconds Amount of time in Controller In-
Time Only 1.000000000000 Lower Limit: 0.000 seconds control- formation
Offset: 0 Upper Limit: ler has been
Size (bits): 32 4294967295.000 powered
Sign: U Default: 0.000
42220 kVAR Load Read Multiplier: Unit: kVAR kVAR control ref- Master Load
Reference Only 1.000000000000 Lower Limit: erence value for Control
Offset: 0 Upper Limit: extended paralle-
Size (bits): 16 Default: ling
Sign: S

393
Addr. System Name Access Specifications Description Function
42221 kVAR Load Read Multiplier: Unit: % Engineering units Analog Inputs
Setpoint Engr Only .010000000000 Lower Limit: value for the
Units Display Offset: 0 Upper Limit: kVAR load set-
Value Size (bits): 16 Default point analog in-
Sign: S put
42222 kW Load Set- Read Multiplier: Unit: % Engineering units Analog Inputs
point Engr Only .010000000000 Lower Limit: value for the kW
Units Display Offset: 0 Upper Limit: load setpoint
Value Size (bits): 16 Default: analog input
Sign: S
42223 Power Factor Read Multiplier: Unit: Power factor set- Analog Inputs
Setpoint Only .010000000000 Lower Limit: point analog in-
Offset: 0 Upper Limit: put value (uses
Size (bits): 8 Default: kVAR load set-
Sign: S point analog in-
put)
42226 Sync Phase Read Multiplier: Unit: degrees Utility to genera- Phase
Difference Only .010000000000 Lower Limit: tor set L1 voltage
Offset: 0 Upper Limit: phase angle
Size (bits): 16 Default:
Sign: S
42250 Current Add Read Multiplier: Unit: Indicates the next Load Add
Level Only 1.000000000000 Lower Limit: level to add Shed Control
Offset: 0 Upper Limit:
Size (bits): 8 Default:
Sign: U
42251 Current Shed Read Multiplier: Unit: Indicates the next Load Add
Level Only 1.000000000000 Lower Limit: level to shed Shed Control
Offset: 0 Upper Limit:
Size (bits): 8 Default
Sign: U
42291 Battery Volt- Read Multiplier: Unit: VDC Engineering units Analog Inputs
age Engr Units Only .010000000000 Lower Limit: value for the bat-
Display Value Offset: 0 Upper Limit: tery voltage ana-
Size (bits): 16 Default log input
Sign: U
42292 kVAR Master Read Multiplier: Unit: VDC Voltage level Analog Out-
Load Control Only .010000000000 Lower Limit: commanded to puts
Output Predic- Offset: 0 Upper Limit: kVAR master
tor Value Size (bits): 16 Default load control ana-
Sign: S log output
42293 kW Master Read Multiplier: Unit: VDC Voltage level Analog Out-
Load Control Only .010000000000 Lower Limit: commanded to puts
Output Predic- Offset: 0 Upper Limit: kW master load
tor Value Size (bits): 16 Default control analog
Sign: S output

394
Addr. System Name Access Specifications Description Function
42294 Master Fre- Read Multiplier: Unit: VDC Voltage level Analog Out-
quency Bias Only .010000000000 Lower Limit: commanded to puts
Output Predic- Offset: 0 Upper Limit: master frequency
tor Value Size (bits): 16 Default bias analog out-
Sign: S put
42295 Master Volt- Read Multiplier: Unit: VDC Voltage level Analog Out-
age Bias Out- Only .010000000000 Lower Limit: commanded to puts
put Predictor Offset: 0 Upper Limit: master voltage
Value Size (bits): 16 Default: bias analog out-
Sign: S put
42305 Genset 01 kW Read/ Multiplier: Unit: kW Sets gen1 kW ra- System In-
Rating Write 1.000000000000 Lower Limit: 0.000 ting formation
Offset: 0 kW
Size (bits): 16 Upper Limit:
Sign: S 32000.00 kW
Default: 1000.000
42306 Genset 02 kW Read/ Multiplier: Unit: kW Sets gen2 kW ra- System In-
Rating Write 1.000000000000 Lower Limit: 0.000 ting formation
Offset: 0 kW
Size (bits): 16 Upper Limit:
Sign: S 32000.00 kW
Default: 0.000
42307 Genset 03 kW Read/ Multiplier: Unit: kW Sets gen3 kW ra- System In-
Rating Write 1.000000000000 Lower Limit: 0.000 ting formation
Offset: 0 kW
Size (bits): 16 Upper Limit:
Sign: S 32000.00 kW
Default: 0.000
42308 Genset 04 kW Read/ Multiplier: Unit: kW Sets gen4 kW ra- System In-
Rating Write 1.000000000000 Lower Limit: 0.000 ting formation
Offset: 0 kW
Size (bits): 16 Upper Limit:
Sign: S 32000.00 kW
Default: 0.000
42309 Genset 05 kW Read/ Multiplier: Unit: kW Sets gen5 kW ra- System In-
Rating Write 1.000000000000 Lower Limit: 0.000 ting formation
Offset: 0 kW
Size (bits): 16 Upper Limit:
Sign: S 32000.00 kW
Default: 0.000
42310 Genset 06 kW Read/ Multiplier: Unit: kW Sets gen6 kW ra- System In-
Rating Write 1.000000000000 Lower Limit: 0.000 ting formation
Offset: 0 kW
Size (bits): 16 Upper Limit:
Sign: S 32000.00 kW
Default: 0.000

395
Addr. System Name Access Specifications Description Function
42311 Genset 07 kW Read/ Multiplier: Unit: kW Sets gen7 kW ra- System In-
Rating Write 1.000000000000 Lower Limit: 0.000 ting formation
Offset: 0 kW
Size (bits): 16 Upper Limit:
Sign: S 32000.00 kW
Default: 0.000

42312 Genset 08 kW Read/ Multiplier: Unit: kW Sets gen8 kW ra- System In-
Rating Write 1.000000000000 Lower Limit: 0.000 ting formation
Offset: 0 kW
Size (bits): 16 Upper Limit:
Sign: S 32000.00 kW
Default: 0.000

42313 Genset 09 kW Read/ Multiplier: Unit: kW Sets gen9 kW ra- System In-
Rating Write 1.000000000000 Lower Limit: 0.000 ting formation
Offset: 0 kW
Size (bits): 16 Upper Limit:
Sign: S 32000.00 kW
Default: 0.000

42314 Genset 10 kW Read/ Multiplier: Unit: kW Sets gen10 kW System In-


Rating Write 1.000000000000 Lower Limit: 0.000 rating formation
Offset: 0 kW
Size (bits): 16 Upper Limit:
Sign: S 32000.00 kW
Default: 0.000

42315 Genset 11 kW Read/ Multiplier: Unit: kW Sets gen11 kW System In-


Rating Write 1.000000000000 Lower Limit: 0.000 rating formation
Offset: 0 kW
Size (bits): 16 Upper Limit:
Sign: S 32000.00 kW
Default: 0.000

42316 Genset 12 kW Read/ Multiplier: Unit: kW Sets gen12 kW System Infor-


Rating Write 1.000000000000 Lower Limit: 0.000 rating mation
Offset: 0 kW
Size (bits): 16 Upper Limit:
Sign: S 32000.00 kW
Default: 0.000

42317 Programmed Read/ Multiplier: Unit: seconds Sets the pro- PTC Timers
Transition Write 0.100000000000 Lower Limit: 0.000 grammed transi-
Delay (TDPT) Offset: 0 seconds tion time delay
Size (bits): 16 Upper Limit: 60 sec-
Sign: U onds
Default: 3.000

42318 Transfer Delay Read/ Multiplier: Unit: seconds Sets the transfer PTC Timers
(TDNE) Write 0.100000000000 Lower Limit: 0.000 time delay
Offset: 0 seconds
Size (bits): 16 Upper Limit: 120 sec-
Sign: U onds
Default: 10.000

396
Addr. System Name Access Specifications Description Function
42319 Retransfer Read/ Multiplier: Unit: seconds Sets the retran- PTC Timers
Delay (TDEN) Write 0.100000000000 Lower Limit: 0.000 sfer time delay
Offset: 0 seconds
Size (bits): 16 Upper Limit: 1800
Sign: U seconds
Default: 600.000

42320 Maximum Par- Read/ Multiplier: Unit seconds Sets the maxi- PTC Timers
allel Time Write 0.000000000000 Lower Limit: 0.000 mum parallel
(TDMP) Offset: 0 seconds time for soft load
Size (bits): 16 Upper Limit: 1800 transfers
Sign: U seconds
Default: 20.000

42321 Genset Bus Read/ Multiplier: Unit: % Sets %kW gener- Master Load
%kW Setpoint Write .010000000000 Lower Limit: -5.000 ator set output Control
Offset: 0 % level for open
Size (bits): 16 Upper Limit: 105.000 loop base load
Sign: S % extended paralle-
Default: 80.000 ling

42322 Genset Nomi- Read/ Multiplier: Unit: Volts Generator set AC Setup
nal Voltage Write 1.000000000000 Lower Limit: 110.000 nominal voltage
Offset: 0 Volts
Size (bits): 16 Upper Limit:
Sign: U 45000.000 Volts
Default: 480.000

42323 Utility Nominal Read/ Multiplier: Unit: Volts Utility nominal AC Setup
Voltage Write 1.000000000000 Lower Limit: 110.000 voltage
Offset: 0 Volts
Size (bits): 16 Upper Limit:
Sign: U 45000.000 Volts
Default: 480.000

42324 Genset Center Read/ Multiplier: Unit: Hz Sets the center PTC Sensors
Frequency Write 0.100000000000 Lower Limit: 45.000 frequency for the
Offset: 0 Hz generator set fre-
Size (bits): 16 Upper Limit: 65.000 quency sensor
Sign: U Default: 60.000 bandwidth set-
tings

42325 Utility Center Read/ Multiplier: Unit: Hz Sets the center PTC Sensors
Frequency Write 0.100000000000 Lower Limit: 45.000 frequency for the
Offset: 0 Hz utility frequency
Size (bits): 16 Upper Limit: 65.000 sensor bandwidth
Sign: U Hz settings
Default: 60.000

42327 System Fre- Read/ Multiplier: Unit: Hz Use to define the System Infor-
quency Write 0.100000000000 Lower Limit: 45.000 system nominal mation
Offset: 0 Hz frequency
Size (bits): 16 Upper Limit: 65.000
Sign: U Hz
Default: 60.000

397
Addr. System Name Access Specifications Description Function
42330 Genset Bus Read/ Multiplier: Unit: kW Sets the base Master Load
kW Setpoint Write 1.000000000000 Lower Limit: 0.000 load kW setpoint Control
Offset: 0 kW in closed loop ex-
Size (bits): 16 Upper Limit: tended paralle-
Sign: S 32767.000 kW ling
Default: 0.000

42331 Genset Bus Read/ Multiplier: Unit: kVAR Sets the base Master Load
kVAR Setpoint Write 1.000000000000 Lower Limit: 0.000 load kVAR set- Control
Offset: 0 kVAR point in closed
Size (bits): 16 Upper Limit: 32767 loop extended
Sign: S kVAR paralleling
Default: 0.000

42332 Genset Bus Read/ Multiplier: Unit: % Sets %kVAR Master Load
%kVAR Set- Write .010000000000 Lower Limit: -5.000 generator set Control
point Offset: 0 % output level for
Size (bits): 16 Upper Limit: 105.000 open loop base
Sign: S % load extended
Default: 0.000 paralleling

42333 Genset Bus Read/ Multiplier: Unit: Sets the desired Master Load
Power Factor Write .010000000000 Lower Limit: 0.700 generator set bus Control
Setpoint Offset: 0 Upper Limit: 1.000 power factor in
Size (bits): 8 Default: 1.000 closed loop ex-
Sign: S tended paralle-
ling

42334 Genset Un- Read/ Multiplier: Unit: kW Setpoint for gen- Master Load
loaded Level Write 1.000000000000 Lower Limit: erator set un- Control
Offset: 0 −32768.000 kW loaded level
Size (bits): 16 Upper Limit: 32767
Sign: S kW
Default: 50.000

42337 Utility Bus kW Read/ Multiplier: Unit: kW Sets the peak Master Load
Setpoint Write 1.000000000000 Lower Limit: shave kW set- Control
Offset: 0 −32768.000 kW point in closed
Size (bits): 16 Upper Limit: 32767 loop extended
Sign: S kW paralleling
Default: 100.000

42338 Utility Bus kW Read/ Multiplier: Unit: kW Sets the utility Master Load
Constraint Le- Write 1.000000000000 Lower Limit: kW constraint Control
vel Offset: 0 -32768.000 kW level for base
Size (bits): 16 Upper Limit: load extended
Sign: S 32767.000 kW paralleling
Default: 100.000

42339 Utility Bus Read/ Multiplier: Unit: kVAR Sets the peak Master Load
kVAR Setpoint Write 1.000000000000 Lower Limit: shave kVAR set- Control
Offset: 0 32768.000 kVAR point in closed
Size (bits): 16 Upper Limit: loop extended
Sign: S 32767.000 kVAR paralleling
Default: 100.000

398
Addr. System Name Access Specifications Description Function
42340 Utility Bus Read/ Multiplier: Unit: Sets the desired Master Load
Power Factor Write .010000000000 Lower Limit: 0.700 utility bus power Control
Setpoint Offset: 0 Upper Limit: 1.000 factor in closed
Size (bits): 8 Default: 1.000 loop extended
Sign: S paralleling
42341 Utility Un- Read/ Multiplier: Unit: kW Setpoint for utility Master Load
loaded Level Write 1.000000000000 Lower Limit: unloaded level Control
Offset: 0 -32768.000 kW
Size (bits): 16 Upper Limit:
Sign: S 32767.000 kVAR
Default: 50.000
42348 Extended Par- Read/ Multiplier: Unit: seconds Sets ramp load Master Load
allel Ramp Write .100000000000 Lower Limit: 10.000 time for extended Control
Load Time Offset: 0 seconds paralleling
Size (bits): 16 Upper Limit: 900.000
Sign: U seconds
Default: 60.000
42351 Fail To Syn- Read/ Multiplier: Unit: seconds Sets the fail to Master Sync
chronize Time Write .200000000000 Lower Limit: 10.000 synchronize diag- Control
Offset: 0 seconds nostic time delay
Size (bits):16 Upper Limit: 900.000
Sign: U seconds
Default: 120.000
42354 Slip Fre- Read/ Multiplier: Unit: Hz Sets the synchro- Master Sync
quency Write .00100000000 Lower Limit: -3.000 nizer slip fre- Control
Offset: 0 Hz quency (used
Size (bits):16 Upper Limit: 3.000 when sync meth-
Sign: S Hz od is slip)
Default: 0.100
42355 Start Time Read/ Multiplier: Unit: seconds Sets the genera- PTC Operat-
Delay (TDES) Write .10000000000 Lower Limit: 0.000 tor sets start time ing Mode
Offset: 0 seconds delay
Size (bits):16 Upper Limit:
Sign: U 3600.000 seconds
Default: 0.000
42356 Stop Time Read/ Multiplier: Unit: seconds Sets the genera- PTC Operat-
Delay (TDEC) Write .100000000000 Lower Limit: 0.000 tor sets stop time ing Mode
Offset: 0 seconds delay
Size (bits):16 Upper Limit:
Sign: U 3600.000 seconds
Default: 0.000
42364 Genset Bus Read/ Multiplier: Unit: seconds Indicates delay Load Add
Load Add De- Write 1.000000000000 Lower Limit: 0.000 between add lev- Shed Control
lay Offset: 0 seconds els when all gen-
Size (bits): 16 Upper Limit: 60.000 erator sets are
Sign: U seconds online and no uti-
Default: 1.000 lity

399
Addr. System Name Access Specifications Description Function
42365 Utility Bus Read/ Multiplier: Unit: seconds Indicates delay Load Add
Load Add De- Write 1.000000000000 Lower Limit: 0.000 between add lev- Shed Control
lay Offset: 0 seconds els when on utili-
Size (bits): 16 Upper Limit: 60.000 ty
Sign: U seconds
Default: 1.000

42366 Load Shed Read/ Multiplier: Unit: seconds Indicates delay Load Add
Delay Write .100000000000 Lower Limit: 1.000 between shed Shed Control
Offset: 0 seconds levels when on
Size (bits): 8 Upper Limit: 10.000 generator sets
Sign: U seconds
Default: 1.000

42373 Load 1 Add Read/ Multiplier: Unit: Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 add level load 1 Shed Control
Offset: 0 Upper Limit: 6.000 is assigned to
Size (bits): 8 Default: 1.000
Sign: U

42374 Load 2 Add Read/ Multiplier: Unit: Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 add level load 2 Shed Control
Offset: 0 Upper Limit: 6.000 is assigned to
Size (bits): 8 Default: 2.000
Sign: U

42375 Load 3 Add Read/ Multiplier: Unit: Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 add level load 3 Shed Control
Offset: 0 Upper Limit: 6.000 is assigned to
Size (bits): 8 Default: 3.000
Sign: U

42376 Load 4 Add Read/ Multiplier: Unit: Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 add level load 4 Shed Control
Offset: 0 Upper Limit: 6.000 is assigned to
Size (bits): 8 Default: 4.000
Sign: U

42377 Load 5 Add Read/ Multiplier: Unit: Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 add level load 5 Shed Control
Offset: 0 Upper Limit: 6.000 is assigned to
Size (bits): 8 Default: 5.000
Sign: U

42378 Load 6 Add Read/ Multiplier: Unit: Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 add level load 6 Shed Control
Offset: 0 Upper Limit: 6.000 is assigned to
Size (bits): 8 Default: 6.000
Sign: U

42379 Load 1 Shed Read/ Multiplier: Unit: Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 0.000 shed level load 1 Shed Control
Offset: 0 Upper Limit: 5.000 is assigned to
Size (bits): 8 Default: 0.000
Sign: U

400
Addr. System Name Access Specifications Description Function
42380 Load 2 Shed Read/ Multiplier: Unit: Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 0.000 shed level load 2 Shed Control
Offset: 0 Upper Limit: 5.000 is assigned to
Size (bits): 8 Default: 5.000
Sign: U
42381 Load 3 Shed Read/ Multiplier: Unit: Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 0.000 shed level load 3 Shed Control
Offset: 0 Upper Limit: 5.000 is assigned to
Size (bits): 8 Default: 4.000
Sign: U
42382 Load 4 Shed Read/ Multiplier: Unit: Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 0.000 shed level load 4 Shed Control
Offset: 0 Upper Limit: 5.000 is assigned to
Size (bits): 8 Default: 3.000
Sign: U
42383 Load 5 Shed Read/ Multiplier: Unit: Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 0.000 shed level load 5 Shed Control
Offset: 0 Upper Limit: 5.000 is assigned to
Size (bits): 8 Default: 2.000
Sign: U
42384 Load 6 Shed Read/ Multiplier: Unit: Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 0.000 shed level load 6 Shed Control
Offset: 0 Upper Limit: 5.000 is assigned to
Size (bits): 8 Default: 1.000
Sign: U
42386 Genset Bus Read/ Multiplier: Unit: % Use to set the System In-
%kW Over- Write 1.000000000000 Lower Limit: 80.000 %kW threshold formation
load Threshold Offset: 0 % for gen bus over-
Size (bits): 8 Upper Limit: 140.000 load condition
Sign: U %
Default: 105.000
42387 Genset Bus Read/ Multiplier: Unit: second Sets the delay System In-
kW Overload Write 1.000000000000 Lower Limit: 0.000 time for overload formation
Delay Offset: 0 second based on kW
Size (bits): 8 Upper Limit: 120.000
Sign: U second
Default: 60.000
42388 Genset Bus Read/ Multiplier: Unit: Hz Use to set the System In-
Underfrequen- Write .100000000000 Lower Limit: 0.100 underfrequency formation
cy Overload Offset: 0 Hz offset threshold
Threshold Size (bits): 16 Upper Limit: 10.000 for gen bus over-
Sign: U Hz load condition
Default: 3.000
42389 Genset Bus Read/ Multiplier: Unit: second Sets the delay System Infor-
Underfrequen- Write 1.000000000000 Lower Limit: 0.000 time for overload mation
cy Overload Offset: 0 Hz based on fre-
Delay Size (bits): 8 Upper Limit: 20.000 quency
Sign: U Hz
Default: 3.000

401
Addr. System Name Access Specifications Description Function
42395 Load Demand Read/ Multiplier: Unit: minute Sets the initial Load Demand
Initial Delay Write 1.000000000000 Lower Limit: 1.000 delay time before Control
Offset: 0 minute load demand will
Size (bits): 8 Upper Limit: 60.000 operate
Sign: U minute
Default: 5.000
42396 Load Demand Read/ Multiplier: Unit: % Sets the load de- Load Demand
Restart Per- Write 1.000000000000 Lower Limit: 20 % mand restart Control
cent Offset: 0 Upper Limit: 100 % threshold (make
Size (bits): 8 Default: 80.000 larger than shut-
Sign: U down percent)
42397 Load Demand Read/ Multiplier: Unit: Hours Sets run hours Load Demand
Run Hours Dif- Write 1.000000000000 Lower Limit: 1.000 differential for re- Control
ferential Offset: 0 Hours starting a genera-
Size (bits): 16 Upper Limit: 500 tor set stopped
Sign: S Hours due to load de-
Default: 50.000 mand
42398 Load Demand Read/ Multiplier: Unit: minute Sets the delay Load Demand
Shutdown De- Write 1.000000000000 Lower Limit: 1.000 time between Control
lay Offset: 0 minute stopping genera-
Size (bits): 8 Upper Limit: 60.000 tor sets due to
Sign: U minute load demand
Default: 5.000
42399 Load Demand Read/ Multiplier: Unit: % Sets the load de- Load Demand
Shutdown Per- Write 1.000000000000 Lower Limit: 20 % mand shutdown Control
cent Offset: 0 Upper Limit: 100 % threshold (make
Size (bits): 8 Default: 60.000 smaller than re-
Sign: U start percent)
42400 Genset Fail Read/ Multiplier: Unit: seconds Sets how long to Load Demand
Time Delay Write 1.000000000000 Lower Limit: 10.000 wait for a genera- Control
Offset: 0 seconds tor set to come
Size (bits): 16 Upper Limit: 900.000 online before de-
Sign: U seconds claring it failed
Default: 60.000
42401 Util CB Fail to Read/ Multiplier: Unit: seconds Sets the utility Breaker Con-
Close Delay Write .020000000000 Lower Limit: 0.100 breaker fail to trol
Offset: 0 seconds close time delay
Size (bits): 16 Upper Limit: 1.000
Sign: U seconds
Default: 0.26
42402 Util CB Fail to Read/ Multiplier: Unit: seconds Sets the utility Breaker Con-
Open Delay Write .200000000000 Lower Limit: 0.200 breaker fail to trol
Offset: 0 seconds open time delay
Size (bits): 8 Upper Limit: 5.000
Sign: U seconds
Default: 1

402
Addr. System Name Access Specifications Description Function
42403 Util CB Re- Read/ Multiplier: Unit: seconds Sets the time to Breaker Con-
charge Delay Write .020000000000 Lower Limit: 0.000 allow for utility trol
Offset: 0 seconds breaker recharge
Size (bits): 16 Upper Limit: 60 sec-
Sign: U onds
Default: 10.000

42404 Gen CB Fail to Read/ Multiplier: Unit: seconds Sets the genera- Breaker Con-
Close Delay Write .020000000000 Lower Limit: 0.100 tor set breaker trol
Offset: 0 seconds fail to close time
Size (bits): 16 Upper Limit: 1.000 delay
Sign: U seconds
Default: 0.260

42405 Gen CB Fail to Read/ Multiplier: Unit: seconds Sets the genera- Breaker Con-
Open Delay Write 0.200000000000 Lower Limit: 0.200 tor set breaker trol
Offset: 0 seconds fail to open time
Size (bits): 8 Upper Limit: 5.000 delay
Sign: U seconds
Default: 1.000

42406 Gen CB Re- Read/ Multiplier: Unit: seconds Sets the time to Breaker Con-
charge Delay Write .020000000000 Lower Limit: 0.000 allow for genera- trol
Offset: 0 seconds tor set breaker
Size (bits): 16 Upper Limit: 60.000 recharge
Sign: U seconds
Default: 10.000

42407 Permissive Read/ Multiplier: Unit: degrees Sets the permis- Master Sync
Phase Win- Write 0.01000000000 Lower Limit: 0.100 sive +/− phase Control
dow 0Offset: 0 degrees angle window for
Size (bits): 16 Upper Limit: 20.000 the sync check
Sign: S degrees function
Default: 10.000

42408 Permissive Read/ Multiplier: Unit: % Sets the permis- Master Sync
Voltage Win- Write .100000000000 Lower Limit: 0.5000 sive +/− voltage Control
dow Offset: 0 % acceptance win-
Size (bits): 16 Upper Limit: 10.000 dow for the sync
Sign: U % check function
Default: 5.000

42409 Permissive Read/ Multiplier: Unit: seconds Sets the permis- Master Sync
Window Time Write .020000000000 Lower Limit: 0.500 sive acceptance Control
Offset: 0 seconds window dwell
Size (bits): 16 Upper Limit: 5.000 time for the sync
Sign: U seconds check function
Default: 0.500

42410 Permissive Read/ Multiplier: Unit: Hz Sets the maxi- Master Sync
Frequency Write .001000000000 Lower Limit: 0.001 mum frequency Control
Window Offset: 0 Hz difference al-
Size (bits): 32 Upper Limit: 1.000 lowed for permis-
Sign: U Hz sive close
Default: 1.000

403
Addr. System Name Access Specifications Description Function
42412 Sync Phase Read/ Multiplier: Unit: degrees Sets a sync Master Sync
Offset Write 0.010000000000 Lower Limit: -50.000 phase offset to Control
Offset: 0 degrees accommodate
Size (bits): 16 Upper Limit: 50.000 sync across
Sign: S degrees transformer with
Default: 0.000 phase shift
42414 kW Kp Read/ Multiplier: Unit: Proportional gain Master Load
Write 1.000000000000 Lower Limit: 0.000 for kW closed Control
Offset: 0 Upper Limit: loop control in
Size (bits): 16 1000.000 extended paralle-
Sign: U Default: 60.000 ling
42415 kW KI Read/ Multiplier: Unit: Integral gain for Master Load
Write 1.000000000000 Lower Limit: 0.000 kW closed loop Control
Offset: 0 Upper Limit: 255.000 control in ex-
Size (bits): 8 Default: 60.000 tended paralle-
Sign: U ling
42416 kVAR Kp Read/ Multiplier: Unit: Proportional gain Master Load
Write 1.000000000000 Lower Limit: 0.000 for kVAR closed Control
Offset: 0 Upper Limit: loop control in
Size (bits): 16 1000.000 extended paralle-
Sign: U Default: 120.000 ling
42417 kVAR KI Read/ Multiplier: Unit: Integral gain for Master Load
Write 1.000000000000 Lower Limit: 0.000 kVAR closed loop Control
Offset: 0 Upper Limit: 255.000 control in ex-
Size (bits): 8 Default: 50.000 tended paralle-
Sign: U ling
42418 Scheduler Read/ Multiplier: Unit: Selects which System Sche-
Program Se- Write 1.000000000000 Lower Limit: 1.000 scheduler pro- duler
lect Offset: 0 Upper Limit: 12.000 gram to view or
Size (bits): 8 Default: 1.000 edit
Sign: U
42423 Scheduler Read/ Multiplier: Unit: hour Use to adjust System Sche-
Program x Write 1.000000000000 Lower Limit: 0.000 start hour for the duler
Start Hour Offset: 0 hour selected program
Size (bits): 8 Upper Limit: 23.000
Sign: U hour
Default: 0.000
42424 Scheduler Read/ Multiplier: Unit: minute Use to adjust System Sche-
Program x Write 1.000000000000 Lower Limit: 0.000 start minute for duler
Start Minute Offset: 0 minute the selected pro-
Size (bits): 8 Upper Limit: 59.000 gram
Sign: U minute
Default: 0.000
42425 Scheduler Read/ Multiplier: Unit: hour Use to adjust System Sche-
Program x Write 1.000000000000 Lower Limit: 0.000 duration hours for duler
Duration Offset: 0 hour the selected pro-
Hours Size (bits): 8 Upper Limit: 23.000 gram
Sign: U hour
Default: 0.000

404
Addr. System Name Access Specifications Description Function
42426 Scheduler Read / Multiplier: Unit: minute Use to adjust System Sche-
Program x Write 1.000000000000 Lower Limit: 0.000 duration minutes duler
Duration Minu- Offset: 0 minute for the selected
tes Size (bits): 8 Upper Limit: 59.000 program
Sign: U minute
Default: 0.000
42427 Scheduler Ex- Read/ Multiplier: Unit: Selects which System Sche-
ception Select Write 1.000000000000 Lower Limit: 1.000 scheduler excep- duler
Offset: 0 Upper Limit: 6.000 tion to view or
Size (bits): 8 Default: 1.000 edit
Sign: U
42430 Scheduler Ex- Read/ Multiplier: Unit: month Use to adjust the System Sche-
ception x Write 1.000000000000 Lower Limit: 1.000 month of the se- duler
Month Offset: 0 month lected exception
Size (bits): 8 Upper Limit: 12.000
Sign: U month
Default: 1.000
42431 Scheduler Ex- Read/ Multiplier: Unit: date Use to adjust the System Sche-
ception x Date Write 1.000000000000 Lower Limit: 1.000 date of the se- duler
Offset: 0 date lected exception
Size (bits): 8 Upper Limit: 31.000
Sign: U date
Default: 1.000
42432 Scheduler Ex- Read/ Multiplier: Unit: hour Use to adjust the System Sche-
ception x Hour Write 1.000000000000 Lower Limit: 0.000 start hour of the duler
Offset: 0 hour selected excep-
Size (bits):8 Upper Limit: 23.000 tion
Sign: U hour
Default: 0.000
42433 Scheduler Ex- Read/ Multiplier: Unit: minute Use to adjust the System Sche-
ception x Mi- Write 1.000000000000 Lower Limit: 0.000 start minute of duler
nute Offset: 0 minute the selected ex-
Size (bits): 8 Upper Limit: 59.000 ception
Sign: U minute
Default: 0.000
42434 Scheduler Ex- Read/ Multiplier: Unit: days Use to adjust the System Sche-
ception x Write 1.000000000000 Lower Limit: 0.000 duration days of duler
Duration Days Offset: 0 days the selected ex-
Size (bits): 8 Upper Limit: 44.000 ception
Sign: U days
Default: 0.000
42435 Scheduler Ex- Read/ Multiplier: Unit: hour Use to adjust the System Sche-
ception x Write 1.000000000000 Lower Limit: 0.000 duration hours of duler
Duration Offset: 0 hour the selected ex-
Hours Size (bits): 8 Upper Limit: 23 hour ception
Sign: U Default: 0.000

405
Addr. System Name Access Specifications Description Function
42436 Scheduler Ex- Read/ Multiplier: Unit: minute Use to adjust the System
ception x Write 1.000000000000 Lower Limit: 0.000 duration minutes Scheduler
Duration Minu- Offset: 0 minute of the selected
tes Size (bits): 8 Upper Limit: 59.000 exception
Sign: U minute
Default: 0.000
42440 Genset PT Pri- Read/ Multiplier: Unit: Volts Generator Set PT AC Setup
mary Voltage Write 1.000000000000 Lower Limit: 110.000 primary voltage
Offset: 0 Volts
Size (bits): 16 Upper Limit:
Sign: U 45000.000 Volts
Default: 480
42441 Genset PT Read/ Multiplier: Unit: Volts Generator set PT AC Setup
Secondary Write 1.000000000000 Lower Limit: 110.000 secondary volt-
Voltage Offset: 0 Volts Upper Limit: age
Size (bits): 16 500 Volts
Sign: U Default: 120
42442 Genset CT Read/ Multiplier: Unit: Amp Generator set CT AC Setup
Primary Cur- Write 1.000000000000 Lower Limit: 5.000 primary current
rent Offset: 0 Amp
Size (bits): 16 Upper Limit:
Sign: U 10000.000 Amp
Default: 100
42445 Utility PT Pri- Read/ Multiplier: Unit: Volts Utility PT primary AC Setup
mary Voltage Write 1.000000000000 Lower Limit: 110.000 voltage
Offset: 0 Volts
Size (bits): 16 Upper Limit:
Sign: U 45000.000 Volts
Default: 480
42446 Utility PT Sec- Read/ Multiplier: Unit: Volts Utility PT secon- AC Setup
ondary Volta- Write 1.000000000000 Lower Limit: 110.000 dary voltage
ge Offset: 0 Volts
Size (bits): 16 Upper Limit: 500.000
Sign: U Volts
Default: 120
42447 Utility CT Pri- Read/ Multiplier: Unit: Amps Utility primary AC Setup
mary Current Write 1.000000000000 Lower Limit: 5.000 current
Offset: 0 Amps
Size (bits): 16 Upper Limit:
Sign: U 10000.00 Amps
Default: 100
42449 Load Add Read/ Multiplier: Unit: kW Generator set kW Load Add
Shed Re- Write 1.000000000000 Lower Limit: 0.000 capacity that Shed Control
quired Online Offset: 0 kW must be online to
Capacity Size (bits): 16 Upper Limit: start timed load
Sign: S 32000.000 kW add; 0 disables
Default: 0 this

406
Addr. System Name Access Specifications Description Function
42450 Load Demand Read/ Multiplier: Unit: kW Sets how much Load Demand
Minimum On- Write 1.000000000000 Lower Limit: 0.000 capacity must al- Control
line Capacity Offset: 0 kW ways be online
Size (bits): 16 Upper Limit: regardless of
Sign: S 32767.000 kW what the load is
Default: 0
42451 Load Demand Read/ Multiplier: Unit: seconds Sets generator Load Demand
Restart Delay Write 0.100000000000 Lower Limit: 0.000 restart delay time Control
Offset: 0 seconds to avoid nuisance
Size (bits): 8 Upper Limit: 25.000 restarts due to
Sign: U seconds load transients
Default: 1
42452 Utility Avail- Read/ Multiplier: Unit: Amps barograph AC Setup
able Current Write 1.000000000000 Lower Limit: 1.000
Offset: 0 Amps
Size (bits): 16 Upper Limit:
Sign: U 32000.000 Amps
Default: 1000
42453 Total Utility Read/ Multiplier: Unit: kW Use to set how AC Setup
Capacity Write 1.000000000000 Lower Limit: 1.000 kW = 100% utility
Offset: 0 kW kW −− Used by
Size (bits): 16 Upper Limit: barograph
Sign: S 32000.00 kW
Default: 1000
42455 24 V High Bat- Read/ Multiplier: Unit: VDC Sets 24V high Battery Volt-
tery Voltage Write 0.010000000000 Lower Limit: 28.000 battery voltage age Protec-
Threshold Offset: 0 VDC fault threshold tion
Size (bits): 16 Upper Limit: 34.000
Sign: U VDC
Default: 32
42456 24 V Low Bat- Read/ Multiplier: Unit: VDC Sets 24V low bat- Battery Volt-
tery Voltage Write 0.010000000000 Lower Limit: 22.000 tery voltage fault age Protec-
Threshold Offset: 0 VDC threshold tion
Size (bits): 16 Upper Limit: 26.000
Sign: U VDC
Default: 24
42457 12 V High Bat- Read/ Multiplier: Unit: VDC Sets 12V high Battery Volt-
tery Voltage Write 0.010000000000 Lower Limit: 14.000 battery voltage age Protec-
Threshold Offset: 0 VDC fault threshold tion
Size (bits): 16 Upper Limit: 17.000
Sign: U VDC
Default: 16
42458 12 V Low Bat- Read/ Multiplier: Unit: VDC Sets 12V low bat- Battery Volt-
tery Voltage Write 0.010000000000 Lower Limit: 11.000 tery voltage fault age Protec-
Threshold Offset: 0 VDC threshold tion
Size (bits): 16 Upper Limit: 13.000
Sign: U VDC
Default: 12

407
Addr. System Name Access Specifications Description Function
42459 High Battery Read/ Multiplier: Unit: second Sets high battery Battery Volt-
Voltage Set Write 1.000000000000 Lower Limit: 2 se- voltage set time age Protec-
time Offset: 0 cond tion
Size (bits): 8 Upper Limit: 60 sec-
Sign: U ond
Default: 60
42460 Low Battery Read/ Multiplier: Unit: second Sets low battery Battery Volt-
Voltage Set Write 1.000000000000 Lower Limit: 2 sec- voltage set time age Protec-
Time Offset: 0 ond tion
Size (bits): 8 Upper Limit: 60 sec-
Sign: U ond
Default: 60
42462 Genset Online Read/ Multiplier: Unit: kW Sets the online PTC Sensors
Capacity Sen- Write 1.000000000000 Lower Limit: 0.000 kW threshold at
sor Threshold Offset: 0 kW which generator
Size (bits): 16 Upper Limit: set bus is avail-
Sign: S 32000.000 kW able for loading
Default: 0
42500 Fault Status Read Multiplier: Unit: Bitmapped state Fault and
BitMap 1 Only 1.000000000000 Lower Limit: of utility and oth- Event Info
Offset: 0 Upper Limit: er faults − 32 bits
Size (bits): 32 Default:
Sign: U
42502 Fault Status Read Multiplier: Unit: Bitmapped state Fault and
BitMap 2 Only 1.000000000000 Lower Limit: of generator set Event Info
Offset: 0 Upper Limit: and other faults −
Size (bits): 32 Default: 32 bits
Sign: U
42504 Event Status Read Multiplier: Unit: Bitmapped state Fault and
BitMap 1 Only 1.000000000000 Lower Limit: of events − 32 Event Info
Offset: 0 Upper Limit: bits
Size (bits): 32 Default:
Sign: U
42506 Genset Meter- Read Multiplier: Unit: Bitmapped word AC Interrupt
ing Fault Sta- Only 1.000000000000 Lower Limit: with status of Service
tus Offset: 0 Upper Limit: generator set AC
Size (bits): 16 Default: metering out of
Sign: U range conditions
42507 Utility Metering Read Multiplier: Unit: Bitmapped word AC Interrupt
Fault Status Only 1.000000000000 Lower Limit: with status of util- Service
Offset: 0 Upper Limit: ity AC metering
Size (bits): 16 Default: out of range
Sign: U conditions
42704 Gen1 Online Read Multiplier: Unit: Hours Total online time System Infor-
Time Only 0.000277778 Lower Limit: 0.000 for Gen1 mation
Offset: 0 Hours
Size (bits): 32 Upper Limit:
Sign: U 1193046.000 Hours
Default: 0

408
Addr. System Name Access Specifications Description Function
42706 Gen2 Online Read Multiplier: Unit: Hours Total online time System Infor-
Time Only 0.000277778 Lower Limit: 0.000 for Gen2 mation
Offset: 0 Hours
Size (bits): 32 Upper Limit:
Sign: U 1193046.000 Hours
Default: 0
42708 Gen3 Online Read Multiplier: Unit: Hours Total online time System Infor-
Time Only 0.000277778 Lower Limit: 0.000 for Gen3 mation
Offset: 0 Hours
Size (bits): 32 Upper Limit:
Sign: U 1193046.000 Hours
Default: 0
42710 Gen4 Online Read Multiplier: Unit: Hours Total online time System Infor-
Time Only 0.000277778 Lower Limit: 0.000 for Gen4 mation
Offset: 0 Hours
Size (bits): 32 Upper Limit:
Sign: U 1193046.000 Hours
Default: 0
42717 Total Number Read Multiplier: Unit: Indicates how System Infor-
of Gensets Only 1.000000000000 Lower Limit: many of the de- mation
Online Offset: 0 Upper Limit: fined Gen1 thru
Size (bits): 8 Default: Gen4 generator
Sign: U sets are online
42718 Total Spare Read Multiplier: Unit: kW Difference be- System Infor-
Online Capaci- Only 1.000000000000 Lower Limit: tween online ca- mation
ty Offset: 0 Upper Limit: pacity (4 genera-
Size (bits): 16 Default: tor sets) and
Sign: S Genset Bus Total
kW
42719 Next Gen Re- Read Multiplier: Unit: kW Indicates kW Load Demand
start Thre- Only 1.000000000000 Lower Limit: threshold for gen Control
shold Offset: 0 Upper Limit: bus at which the
Size (bits): 16 Default: next generator
Sign: S set will restart
42720 Next Gen Read Multiplier: Unit: kW Indicates kW Load Demand
Shutdown Only 1.000000000000 Lower Limit: threshold for gen Control
Threshold Offset: 0 Upper Limit: bus at which the
Size (bits): 16 Default: next generator
Sign: S set will load de-
mand stop
42727 Genset Bus Read Multiplier: Unit: kW Calculated kW System In-
kW Overload Only 1.000000000000 Lower Limit: overload thresh- formation
Threshold Offset: 0 Upper Limit: old based on on-
Size (bits): 16 Default: line capacity and
Sign: S % setting
42732 Modbus Bus Read Multiplier: Unit: Modbus bus Communica-
Message Only 1.000000000000 Lower Limit: message count tions
Count Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U

409
Addr. System Name Access Specifications Description Function
42733 Modbus CRC Read Multiplier: Unit: Modbus CRC Communica-
Error Count Only 1.000000000000 Lower Limit: error count tions
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42734 Modbus Ex- Read Multiplier: Unit: Modbus excep- Communica-
ception Count Only 1.000000000000 Lower Limit: tion count tions
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42735 Modbus No Read Multiplier: Unit: Modbus no re- Communica-
Response Only 1.000000000000 Lower Limit: sponse count tions
Count Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42736 Modbus Slave Read Multiplier: Unit: Modbus slave Communica-
Message Only 1.000000000000 Lower Limit: message count tions
Count Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42739 Clock Year Read/ Multiplier: Unit: year Use to set or Real Time
Write 1.000000000000 Lower Limit: .000 read current year Clock
Offset: 0 year
Size (bits): 8 Upper Limit: 99.000
Sign: U year
Default:
42740 Clock Month Read/ Multiplier: Unit: month Use to set or Real Time
Write 1.000000000000 Lower Limit: 1.000 read current Clock
Offset: 0 month month
Size (bits): 8 Upper Limit: 12.000
Sign: U month
Default:
42741 Clock Date Read/ Multiplier: Unit: date Use to set or Real Time
Write 1.000000000000 Lower Limit: 1.000 read current date Clock
Offset: 0 date
Size (bits): 8 Upper Limit: 31.000
Sign: U date
Default:
42742 Clock Hour Read/ Multiplier: Unit: hour Use to set or Real Time
Write 1.000000000000 Lower Limit: .000 read current hour Clock
Offset: 0 hour
Size (bits): 8 Upper Limit: 23.000
Sign: U hour
Default:
42743 Clock Minute Read/ Multiplier: Unit: minute Use to set or Real Time
Write 1.000000000000 Lower Limit: .000 read current mi- Clock
Offset: 0 minute nute
Size (bits): 8 Upper Limit: 59.000
Sign: U minute
Default:

410
Addr. System Name Access Specifications Description Function
42744 Clock Second Read/ Multiplier: Unit: seconds Use to set or Real Time
Write 1.000000000000 Lower Limit: .000 read current se- Clock
Offset: 0 seconds conds
Size (bits): 8 Upper Limit: 59.000
Sign: U seconds
Default:
42746 Start Timer Read Multiplier: Unit: seconds Countdown timer PTC Operat-
Only 0.100000000000 Lower Limit: value for genera- ing Mode
Offset: 0 Upper Limit: tor set start timer
Size (bits): 16 Default:
Sign: U
42747 Stop Timer Read Multiplier: Unit: seconds Countdown timer PTC Operat-
Only .100000000000 Lower Limit: value for genera- ing Mode
Offset: 0 Upper Limit: tor set stop timer
Size (bits): 16 Default:
Sign: U
42748 Low Battery Read Multiplier: Unit: VDC Battery voltage Battery Volt-
Voltage Thre- Only 0.010000000000 Lower Limit: with respect to age Protec-
shold Offset: 0 Upper Limit: the set low bat- tion
Size (bits): 16 Default: tery threshold
Sign: U
42749 High Battery Read Multiplier: Unit: VDC Battery voltage Battery Volt-
Voltage Thre- Only 0.010000000000 Lower Limit: with respect to age Protec-
shold Offset: 0 Upper Limit: set high battery tion
Size (bits): 16 Default: threshold
Sign: U

411
THIS PAGE LEFT INTENTIONALLY BLANK

412
6. DMC 1000 Modbus Enumerated Data

Addr. System Name Access Specifications Description Function


42004 Save Adjust- Read / Size (bits): 8 0: Do Nothing Use to save ad- Controller In-
ments Write Number of Fields: 2 1: Save Trims justments directly formation
Default: Do Nothing in non-volatile
memory
42011 Genset Run Read Size (bits): 8 0: Time Delay Start Indicates state of PTC Operat-
Sequence Only Number of Fields: 4 1: Time Delay Stop the generator set ing Mode
State 2: Stop run sequence
3: Run
Default:
42017 Genset Bus Read Size (bits): 8 0: Unavailable Energization sta- PTC Sensors
Status Only Number of Fields: 3 1: Dead tus of the genera-
2: Live tor set bus
Default:
42117 Utility Bus Sta- Read Size (bits): 8 0: Unavailable Energization sta- PTC Sensors
tus Only Number of Fields: 3 1: Dead tus of the utility
2: Live bus
Default:
42208 Utility Unload Read Size (bits): 8 0: Not Available Indicates utility Master Load
Status Only Number of Fields: 3 1: Not Unloaded unloaded status Control
2: Unloaded
Default:
42209 Genset Un- Read Size (bits): 8 0: Not Available Indicates genera- Master Load
load Status Only Number of Fields: 3 1: Not Unloaded tor set unloaded Control
2: Unloaded status
Default:
42210 System State Read / Size (bits): 8 0: Not Available Indicates what System Infor-
Write Number of Fields: 18 1: TD Start state the control mation
2: TD Stop is currently in
3: TD Programmed
Transition
4: TD Transfer
5: TD Retranfer
6: Synchronizing
7: Sync Check OK
8: Inhibit
9: Unassigned
10: Ramp Unload
11: Ramp Load
12: Manual
13: Utility Failure
14: Test
15: Standby
16: Factory Test
17: Extended Parallel
Default: Not Available

413
Addr. System Name Access Specifications Description Function
42211 PTC Operat- Read Size (bits): 8 0: Manual Indicates the cur- PTC Operat-
ing Mode Only Number of Fields: 6 1: Normal rent PTC operat- ing Mode
2: Normal Override ing mode. Read/
3: Test Write in Comp
4: Utility Fail mode
5: Extended Parallel
Default:
42216 Genset Avail- Read Size (bits): 8 0: Not Available Indicates avail- Availability
ability Status Only Number of Fields: 3 1: Available ability of genera-
2: Unknown tor set for loading
Default: as determined by
generator set
sensors
42217 Utility Avail- Read Size (bits): 8 0: Not Available Indicates avail- Availability
ability Status Only Number of Fields: 3 1: Available ability of utility for
2: Unknown loading as deter-
Default: mined by utility
sensors
42218 Gen CB Posi- Read Size (bits): 8 0: Open Generator set Breaker Con-
tion Status Only Number of Fields: 3 1: Closed breaker position trol
2: Not Available
Default:

42219 Util CB Posi- Read Size (bits): 8 0: Open Utility breaker Breaker Con-
tion Status Only Number of Fields: 3 1: Closed position trol
2: Not Available
Default:

42224 PTC State Read Size (bits): 8 0: Not Enabled Indicates the PTC State
Only Number of Fields: 5 1: No Source Con- connected state Machine
nected of the power
2: Utility Connected transfer control
3: Genset Connected Read/Write in
4: Paralleled Comp.
Default:
42225 Sync Check Read Size (bits):8 0: Not Allowed Indicates whether Master Sync
Close Allowed Only Number of Fields: 2 1: Allowed any sync check Control
Default: conditions for
have been met

42227 Synchronizer Read Size (bits): 8 0: Synchronizer Off Indicates state of Master Sync
Status Only Number of Fields: 2 1: Synchronizer On the synchronizer Control
Default:

42228 System Lock- Read Size (bits): 8 0: Inactive Faults have oc- System In-
out Status Only Number of Fields: 2 1: Active curred which pre- formation
Default: vent normal sys-
tem operation;
reset faults

414
Addr. System Name Access Specifications Description Function
42229 Breaker 1 Read Size (bits): 8 0: Open Indicates position Load Add
Position Only Number of Fields: 3 1: Closed status of breaker Shed Control
2: Not Available 1
Default: Not Available

42230 Breaker 2 Read Size (bits): 8 0: Open Indicates position Load Add
Position Only Number of Fields: 3 1: Closed status of breaker Shed Control
2: Not Available 2
Default: Not Available

42231 Breaker 3 Read Size (bits): 8 0: Open Indicates position Load Add
Position Only Number of Fields: 3 1: Closed status of breaker Shed Control
2: Not Available 3
Default: Not Available

42232 Breaker 4 Read Size (bits): 8 0: Open Indicates position Load Add
Position Only Number of Fields: 3 1: Closed status of breaker Shed Control
2: Not Available 4
Default: Not Available

42233 Breaker 5 Read Size (bits): 8 0: Open Indicates position Load Add
Position Only Number of Fields: 3 1: Closed status of breaker Shed Control
2: Not Available 5
Default: Not Available

42234 Breaker 6 Read Size (bits): 8 0: Open Indicates position Load Add
Position Only Number of Fields: 3 1: Closed status of breaker Shed Control
2: Not Available 6
Default: Not Available

42235 Breaker 1 Trip Read Size (bits): 8 0: Not Available Indicates trip sta- Load Add
Status Only Number of Fields: 3 1: Normal tus of breaker 1 Shed Control
2: Tripped
Default: Not Available

42236 Breaker 2 Trip Read Size (bits): 8 0: Not Available Indicates trip sta- Load Add
Status Only Number of Fields: 3 1: Normal tus of breaker 2 Shed Control
2: Tripped
Default: Not Available

42237 Breaker 3 Trip Read Size (bits): 8 0: Not Available Indicates trip sta- Load Add
Status Only Number of Fields: 3 1: Normal tus of breaker 3 Shed Control
2: Tripped
Default: Not Available

42238 Breaker 4 Trip Read Size (bits): 8 0: Not Available Indicates trip sta- Load Add
Status Only Number of Fields: 3 1: Normal tus of breaker 4 Shed Control
2: Tripped
Default: Not Available

42239 Breaker 5 Trip Read Size (bits): 8 0: Not Available Indicates trip sta- Load Add
Status Only Number of Fields: 3 1: Normal tus of breaker 5 Shed Control
2: Tripped
Default: Not Available

415
Addr. System Name Access Specifications Description Function
42240 Breaker 6 Trip Read Size (bits): 8 0: Not Available Indicates trip sta- Load Add
Status Only Number of Fields: 3 1: Normal tus of breaker 6 Shed Control
2: Tripped
Default: Not Available

42241 ATS 1 Position Read Size (bits): 8 0: Not Available Indicates position Load Add
Only Number of Fields: 5 1: No Source Con- status of ATS 1 Shed Control
nected
2: Source 1 Con-
nected
3: Source 2 Con-
nected
4: Paralleled
Default: Not Available

42242 ATS 2 Position Read Size (bits): 8 0: Not Available Indicates position Load Add
Only Number of Fields: 5 1: No Source Con- status of ATS 3 Shed Control
nected
2: Source 1 Con-
nected
3: Source 2 Con-
nected
4: Paralleled
Default: Not Available

42243 ATS 3 Position Read Size (bits): 8 0: Not Available Indicates position Load Add
Only Number of Fields: 5 1: No Source Con- status of ATS 3 Shed Control
nected
2: Source 1 Con-
nected
3: Source 2 Con-
nected
4: Paralleled
Default: Not Available

42244 ATS 4 Position Read Size (bits):8 0: Not Available Indicates position Load Add
Only Number of Fields: 5 1: No Source Con- status of ATS 4 Shed Control
nected
2: Source 1 Con-
nected
3: Source 2 Con-
nected
4: Paralleled
Default: Not Available

42245 ATS 5 Position Read Size (bits): 8 0: Not Available Indicates position Load Add
Only Number of Fields: 5 1: No Source Con- status of ATS 5 Shed Control
nected
2: Source 1 Con-
nected
3: Source 2 Con-
nected
4: Paralleled
Default: Not Available

416
Addr. System Name Access Specifications Description Function
42246 ATS 6 Position Read Size (bits): 8 0: Not Available Indicates position Load Add
Only Number of Fields: 5 1: No Source Con- status of ATS 6 Shed Control
nected
2: Source 1 Con-
nected
3: Source 2 Con-
nected
4: Paralleled
Default: Not Available
42248 PCCNet Com- Read Size (bits): 8 0: Failed Indicates status Communica-
munications Only Number of Fields: 3 1: Good of PCCNet tions
Status 2: Wait
Default: Wait
42249 Expansion Read Size (bits): 8 0: Disabled Indicates the sta- Communica-
Board Com- Only Number of Fields: 2 1: Enabled tus of the SID to tions
munications Default: Disabled expansion board
connection
42252 Add Level 1 Read Size (bits): 8 0: Do Nothing Indicates status Load Add
Command Only Number of Fields: 2 1: Add Level of add level 1 Shed Control
Default: Do Nothing
42253 Add Level 2 Read Size (bits):8 0: Do Nothing Indicates status Load Add
Command Only Number of Fields: 2 1: Add Level of add level 2 Shed Control
Default: Do Nothing
42254 Add Level 3 Read Size (bits): 8 0: Do Nothing Indicates status Load Add
Command Only Number of Fields: 2 1: Add Level of add level 3 Shed Control
Default: Do Nothing
42255 Add Level 4 Read Size (bits): 8 0: Do Nothing Indicates status Load Add
Command Only Number of Fields: 2 1: Add Level of add level 4 Shed Control
Default: Do Nothing
42256 Add Level 5 Read Size (bits): 8 0: Do Nothing Indicates status Load Add
Command Only Number of Fields: 2 1: Add Level of add level 5 Shed Control
Default: Do Nothing
42257 Add Level 6 Read Size (bits): 8 0: Do Nothing Indicates status Load Add
Command Only Number of Fields: 2 1: Add Level of add level 6 Shed Control
Default: Do Nothing
42258 Shed Level 1 Read / Size (bits): 8 0: Do Nothing Indicates status Load Add
Command Write Number of Fields: 2 1: Shed Level of shed level 1 Shed Control
Default: Do Nothing
42259 Shed Level 2 Read Size (bits): 8 0: Do Nothing Indicates status Load Add
Command Only Number of Fields: 2 1: Shed Level of shed level 2 Shed Control
Default: Do Nothing
42260 Shed Level 3 Read / Size (bits): 8 0: Do Nothing Indicates status Load Add
Command Write Number of Fields: 2 1: Shed Level of shed level 3 Shed Control
Default: Do Nothing
42261 Shed Level 4 Read Size (bits): 8 0: Do Nothing Indicates status Load Add
Command Only Number of Fields: 2 1: Shed Level of shed level 4 Shed Control
Default: Do Nothing

417
Addr. System Name Access Specifications Description Function
42262 Shed Level 5 Read Size (bits): 8 0: Do Nothing Indicates status Load Add
Command Only Number of Fields: 2 1: Shed Level of shed level 5 Shed Control
Default: Do Nothing
42263 Manual add Read / Size (bits): 8 0: Do Nothing Operator input to Load Add
Level 1 Com- Write Number of Fields: 2 1: Add Level add loads as- Shed Control
mand Default: Do Nothing signed to level 1
42264 Manual add Read / Size (bits): 8 0: Do Nothing Operator input to Load Add
Level 2 Com- Write Number of Fields: 2 1: Add Level add loads as- Shed Control
mand Default: Do Nothing signed to level 2
42265 Manual add Read / Size (bits): 8 0: Do Nothing Operator input to Load Add
Level 3 Com- Write Number of Fields: 2 1: Add Level add loads as- Shed Control
mand Default: Do Nothing signed to level 3
42266 Manual add Read / Size (bits): 8 0: Do Nothing Operator input to Load Add
Level 4 Com- Write Number of Fields: 2 1: Add Level add loads as- Shed Control
mand Default: Do Nothing signed to level 4
42267 Manual add Read / Size (bits): 8 0: Do Nothing Operator input to Load Add
Level 5 Com- Write Number of Fields: 2 1: Add Level add loads as- Shed Control
mand Default: Do Nothing signed to level 5
42268 Manual add Read / Size (bits): 8 0: Do Nothing Operator input to Load Add
Level 6 Com- Write Number of Fields: 2 1: Add Level add loads as- Shed Control
mand Default: Do Nothing signed to level 6
42269 Manual Shed Read / Size (bits): 8 0: Do Nothing Operator input to Load Add
Level 1 Write Number of Fields: 2 1: Shed Level shed loads as- Shed Control
Default: Do Nothing signed to level 1
42270 Manual Shed Read / Size (bits): 8 0: Do Nothing Operator input to Load Add
Level 2 Write Number of Fields: 2 1: Shed Level shed loads as- Shed Control
Default: Do Nothing signed to level 2
42271 Manual Shed Read / Size (bits): 8 0: Do Nothing Operator input to Load Add
Level 3 Write Number of Fields: 2 1: Shed Level shed loads as- Shed Control
Default: Do Nothing signed to level 3
42272 Manual Shed Read / Size (bits): 8 0: Do Nothing Operator input to Load Add
Level 4 Write Number of Fields:2 1: Shed Level shed loads as- Shed Control
Default: Do Nothing signed to level 4
42273 Manual Shed Read / Size (bits): 8 0: Do Nothing Operator input to Load Add
Level 5 Write Number of Fields: 2 1: Shed Level shed loads as- Shed Control
Default: Do Nothing signed to level 5
42274 Restore Shed Read / Size (bits): 8 0: Do Nothing Indicates if shed Load Add
Level 1 Com- Write Number of Fields: 2 1: Restore Level level 1 has been Shed Control
mand Default: Do Nothing restored
42275 Restore Shed Read / Size (bits): 8 0: Do Nothing Indicates if shed Load Add
Level 2 Com- Write Number of Fields: 2 1: Restore Level level 2 has been Shed Control
mand Default: Do Nothing restored
42276 Restore Shed Read / Size (bits): 8 0: Do Nothing Indicates if shed Load Add
Level 3 Com- Write Number of Fields: 2 1: Restore Level level 3 has been Shed Control
mand Default: Do Nothing restored
42277 Restore Shed Read / Size (bits): 8 0: Do Nothing Indicates if shed Load Add
Level 4 Com- Write Number of Fields: 2 1: Restore Level level 4 has been Shed Control
mand Default: Do Nothing restored

418
Addr. System Name Access Specifications Description Function
42278 Restore Shed Read / Size (bits): 8 0: Do Nothing Indicates if shed Load Add
Level 5 Com- Write Number of Fields: 2 1: Restore Level level 5 has been Shed Control
mand Default: Do Nothing restored
42279 Add Load 1 Read Size (bits): 8 0: Do Nothing Indicates add Load Add
Command Only Number of Fields: 2 1: Add Load command for Shed Control
Default: Do Nothing load 1
42280 Add Load 2 Read Size (bits): 8 0: Do Nothing Indicates add Load Add
Command Only Number of Fields: 2 1: Add Load command for Shed Control
Default: Do Nothing load 2
42281 Add Load 3 Read Size (bits): 8 0: Do Nothing Indicates add Load Add
Command Only Number of Fields: 2 1: Add Load command for Shed Control
Default: Do Nothing load 3
42282 Add Load 4 Read Size (bits): 8 0: Do Nothing Indicates add Load Add
Command Only Number of Fields: 2 1: Add Load command for Shed Control
Default: Do Nothing load 4
42283 Add Load 5 Read Size (bits): 8 0: Do Nothing Indicates add Load Add
Command Only Number of Fields: 2 1: Add Load command for Shed Control
Default: Do Nothing load 5
42284 Add Load 6 Read Size (bits): 8 0: Do Nothing Indicates add Load Add
Command Only Number of Fields: 2 1: Add Load command for Shed Control
Default: Do Nothing load 6
42285 Shed Load 1 Read Size (bits): 8 0: Do Nothing Indicates shed Load Add
Command Only Number of Fields: 2 1: Shed Load command for Shed Control
Default: Do Nothing load 1
42286 Shed Load 2 Read Size (bits): 8 0: Do Nothing Indicates shed Load Add
Command Only Number of Fields: 2 1: Shed Load command for Shed Control
Default: Do Nothing load 2
42287 Shed Load 3 Read Size (bits): 8 0: Do Nothing Indicates shed Load Add
Command Only Number of Fields: 2 1: Shed Load command for Shed Control
Default: Do Nothing load 3
42288 Shed Load 4 Read Size (bits): 8 0: Do Nothing Indicates shed Load Add
Command Only Number of Fields: 2 1: Shed Load command for Shed Control
Default: Do Nothing load 4
42289 Shed Load 5 Read Size (bits): 8 0: Do Nothing Indicates shed Load Add
Command Only Number of Fields: 2 1: Shed Load command for Shed Control
Default: Do Nothing load 5
42290 Shed Load 6 Read Size (bits): 8 0: Do Nothing Indicates shed Load Add
Command Only Number of Fields: 2 1: Shed Load command for Shed Control
Default: Do Nothing load 6
42296 PTC Genset Read Size (bits):8 0: Manual Indicates the cur- PTC Operat-
Operating Only Number of Fields: 6 1: Normal rent operating ing Mode
Mode 2: Normal Override mode of the gen-
3: Test erator sets
4: Utility Fail
5: Extended Parallel
Default:

419
Addr. System Name Access Specifications Description Function
42297 PTC Transfer Read Size (bits):8 0: Manual Indicates the PTC Operat-
Pair Operating Only Number of Fields: 6 1: Normal current operating ing Mode
Mode 2: Normal Override mode of the
3: Test transfer pair
4: Utility Fail
5: Extended Parallel
Default:
42298 PTC Operat- Read Size (bits): 8 0: Open Transition Indicates the PTC Operat-
ing Transition Only Number of Fields: 3 1: Hard Closed Tran- transition type ing Mode
Type sition currently applica-
2: Soft Closed Tran- ble to the PTC
sition function opera-
Default: tion
42300 System Topol- Read / Size (bits): 8 0: Master Synchro- Main setting: Application
ogy Write Number of Fields: 6 nize Only Sets system to- Configuration
1: Isolated Bus w/out pology; control
GM must be in manu-
2: Isolated Bus w/GM al to set
3: Common Bus
4: Transfer Pair
5: Component Mode
Default: Master Syn-
chronize Only
42301 Transition Read / Size (bits):8 0: Open Transition Sets the type of Application
Type Write Number of Fields: 3 1: Hard Closed Tran- transition that will Configuration
sition be used
2: Soft Closed Tran-
sition
Default: Open Transi-
tion
42302 Extended Par- Read / Size (bits): 8 0: Disabled Use to enable ex- Application
allel Enable Write Number of Fields: 2 1: Enabled tended parallel- Configuration
Default: Disabled ing operation
42303 Load Demand Read / Size (bits): 8 0: None Sets load de- Load Demand
Type Write Number of Fields: 3 1: Fixed Sequence mand type Control
2: Run Hours
Default: None

42304 Priority Control Read / Size (bits): 8 0: Manual Sets priority con- Priority Con-
Method Write Number of Fields: 2 1: Automatic trol method trol
Default: Manual
42326 Test With Load Read / Size (bits): 8 0: Disabled Use to enable or Application
Enable Write Number of Fields: 2 1: Enabled disable load Configuration
Default: Disabled transfer during a
test

420
Addr. System Name Access Specifications Description Function
42328 Genset Bus Read / Size (bits):8 0: Internal selects where the Master Load
kW Setpoint Write Number of Fields: 2 1: Analog Input generator set kW Control
Source Default: Internal setpoint will
come from for ex-
tended parallel-
ing
42329 Genset Bus Read / Size (bits):8 0: Internal Selects where Master Load
kVAR Setpoint Write Number of Fields: 2 1: Analog Input the generator set Control
Source Default: Internal kVAR setpoint
will come from
extended paral-
leling
42335 Utility Bus kW Read / Size (bits):8 0: Internal Selects where Master Load
Setpoint Write Number of Fields: 2 1: Analog Input the utility kW set- Control
Source Default: Internal point will come
from for extended
paralleling
42336 Utility Bus Read / Size (bits):8 0: Internal Selects where Master Load
kVAR Setpoint Write Number of Fields: 2 1: Analog Input the utility kVAR Control
Source Default: Internal setpoint will
come from ex-
tended paralle-
ling
42342 Clear Fault Read / Size (bits):8 0: Inactive Use to complete- Fault and
History Table Write Number of Fields: 2 1: Active ly clear the fault Event Info
Default: Inactive history table
42343 Clear Occur- Read / Size (bits):8 0: Inactive Use to complete- Fault and
rence Table Write Number of Fields: 2 1: Active ly clear the Event Info
Default: Inactive counts in faults
and events occu-
rance tables
42344 Genset Reset Read / Size (bits):8 0: Do Nothing Use to perma- Energy
All Energy Me- Write Number of Fields: 2 1: Clear Counters nently clear all
ters Default: Do Nothing generator set en-
ergy meter val-
ues
42345 Utility Reset Read / Size (bits):8 0: Do Nothing Use to perma- Energy
All Energy Me- Write Number of Fields: 2 1: Clear Counters nently clear all
ters Default: Do Nothing utility energy me-
ter values
42346 Extended Par- Read / Size (bits):8 0: Genset % Level Sets how and Master Load
alleling kW Write Number of Fields: 4 (Open Loop) where the kW will Control
Load Control 1: Genset Bus kW be controlled for
Type (Closed Loop) extended parallel
2: Genset Bus kW w/ operation
Utility (open Loop)
3: Utility Bus kW
(Closed Loop)
Default: Genset Bus
% Level (Open Loop)

421
Addr. System Name Access Specifications Description Function
42347 Extended Par- Read / Size (bits):8 0: Genset Controllers Sets how and Master Load
alleling kVAR Write Number of Fields: 7 1: Genset Bus % where the kVAR Control
Load Control Level (Open Loop) will be controlled
Type 2: Genset Bus Power for extended par-
Factor allel operation
3: Genset Bus kVAR
(Closed Loop)
4: Genset Bus Power
Factor (Closed Loop)
5: Utility Bus kVAR
(Closed Loop)
6:Utility Bus Power
Factor(Closed Loop)
Default: Genset
Controllers
42349 Fail To Sync Read / Size (bits):8 0: Disabled Enable if want Master Sync
Lockout En- Write Number of Fields: 2 1: Enabled synchronizing to Control
able Default: Disabled stop if fail to sync
occurs
42350 Fail to Sync Read / Size (bits):16 0: Disabled Use to enable or PTC State
Open Transi- Write Number of Fields: 2 1: Enabled disable an open Machine
tion Retransfer Default: Disabled transition retran-
Enable sfer upon a fail to
sync
42352 Gen CB Read / Size (bits):8 0: Closed Requested In manual mode, Breaker Con-
Manual Con- Write Number of Fields: 3 1: No Command can be used to trol
trol 2: Open Command semi-manually
Default: No Com- control the gener-
mand ator set breaker
42353 Util CB Manu- Read / Size (bits):8 0: Closed Requested In manual mode, Breaker Con-
al Control Write Number of Fields: 3 1: No Command can be used to trol
2: Open Command semi-manually
Default: No Com- control the utility
mand breaker
42357 Synchronizer Read / Size (bits):8 0: Normal Use to invert syn- Master Sync
Polarity Write Number of Fields: 2 1: Invert chronizer polarity Control
Default: Normal
42358 Synchronize Read / Size (bits):8 0: Phase Match Sets the synchro- Master Sync
Method Write Number of Fields: 2 1: Slip Frequency nizing method Control
Default: Phase Match
42359 Port Protocol Read / Size (bits): 8 0: PCCNet Allows protocol Communica-
Selection Write Number of Fields: 2 1: MON CT the PCCNet tions
Default: PCCNet port to be
changed to MON
for troubleshoot-
ing
42360 System Read / Size (bits): 8 0: Disabled Use to enable or System
Scheduler En- Write Number of Fields: 2 1: Enabled disable the sys- Scheduler
able Default: Disabled tem scheduler

422
Addr. System Name Access Specifications Description Function
42361 Load Add Read / Size (bits): 8 0: Disabled Use to enable or Load Add
Shed Enable Write Number of Fields: 2 1: Enabled disable the load Shed Control
Default: Disabled add shed feature

42362 Open Transi- Read / Size (bits): 8 0: Disabled Use to enable or Load Add
tion Retransfer Write Number of Fields: 2 1: Enabled disable the shed- Shed Control
Load Shed Default: Disabled ding of loads dur-
Enable ing open transi-
tion retransfer
42363 Auto/Manual Read / Size (bits): 8 0: Auto Indicates auto- Load Add
Load Add Re- Write Number of Fields: 2 1: Manual matic or manual Shed Control
store Mode Default: Auto load add restore
operation
42367 Load 1 Device Read / Size (bits): 8 0: None Indicates type of Load Add
Type Write Number of Fields: 3 1: Breaker load connection Shed Control
2: ATS to load 1 add
Default: None shed control and
status I/O
42368 Load 2 Device Read / Size (bits): 8 0: None Indicates type of Load Add
Type Write Number of Fields: 3 1: Breaker load connection Shed Control
2: ATS to load 2 add
Default: None shed control and
status I/O
42369 Load 3 Device Read / Size (bits): 8 0: None Indicates type of Load Add
Type Write Number of Fields: 3 1: Breaker load connection Shed Control
2: ATS to load 3 add
Default: None shed control and
status I/O
42370 Load 4 Device Read / Size (bits): 8 0: None Indicates type of Load Add
Type Write Number of Fields: 3 1: Breaker load connection Shed Control
2: ATS to load 4 add
Default: None shed control and
status I/O
42371 Load 5 Device Read / Size (bits): 8 0: None Indicates type of Load Add
Type Write Number of Fields: 3 1: Breaker load connection Shed Control
2: ATS to load 5 add
Default: None shed control and
status I/O
42372 Load 6 Device Read / Size (bits):8 0: None Indicates type of Load Add
Type Write Number of Fields: 3 1: Breaker load connected Shed Control
2: ATS to load 6 add
Default: None shed control and
status I/O
42385 Genset Bus Read / Size (bits):8 0: Both kW and Fre- Use to choose System Infor-
Overload Write Number of Fields: 3 quency method for deter- mation
Method 1: kW Only mining generator
2: Frequency Only bus overload
Default: Both kW and condition
Frequency

423
Addr. System Name Access Specifications Description Function
42390 Load Demand Read / Size (bits):8 0: Disabled Use to enable or Load Demand
Enable Write Number of Fields: 2 1: Enabled disable the load Control
Default: Disabled demand feature
42391 Load Demand Read / Size (bits): 8 0: Gen1 Sets GenA for Load Demand
GenA Write Number of Fields: 4 1: Gen2 fixed sequence Control
2: Gen3 load demand
3: Gen4
Default: Gen1
42392 Load Demand Read / Size (bits):8 0: Gen1 Sets GenB for Load Demand
GenB Write Number of Fields: 4 1: Gen2 fixed sequence Control
2: Gen3 load demand
3: Gen4
Default: Gen2
42393 Load Demand Read / Size (bits):8 0: Gen1 Sets GenC for Load Demand
GenC Write Number of Fields: 4 1: Gen2 fixed sequence Control
2: Gen3 load demand
3: Gen4
Default: Gen3
42394 Load Demand Read / Size (bits):8 0: Gen1 Sets GenD (first Load Demand
GenD Write Number of Fields: 4 1: Gen2 to stop) for fixed Control
2: Gen3 sequence load
3: Gen4 demand
Default: Gen4
42413 System Phase Read / Size (bits):8 0: L1-L2-L3 Defines what the System Infor-
Rotation Write Number of Fields: 2 1:L1-L3-L2 system phase mation
Default: L1-L2-L3 rotation se-
quence is
42419 Scheduler Read / Size (bits):8 0: Disable Use to enable or System
Program x En- Write Number of Fields: 2 1: Enable disable the se- Scheduler
able Default: Disable lected program
42420 Scheduler Read / Size (bits):8 0: Once Use to adjust re- System Sche-
Program x Re- Write Number of Fields: 11 1: Every Week peat interval for duler
peat Interval 2: Every 2 Weeks the selected pro-
3: Every 3 Weeks gram
4: Every 4 Weeks
5: Every 5 Weeks
6: First Week of
Month
7: Second Week of
Month
8: Third Week of
month
9: Forth Week of the
Month
10: Last Week of the
Month
Default: Once

424
Addr. System Name Access Specifications Description Function
42421 Scheduler Read / Size (bits): 8 0: No Load Use to adjust run System Sche-
Program x Write Number of Fields: 3 1: With Load mode for the se- duler
Run Mode 2: Extended Parallel lected program
Default: No Load
42422 Scheduler Read / Size (bits): 8 0: Sunday Use to adjust System Sche-
Program x Write Number of Fields: 7 1: Monday start day of week duler
Start Day 2: Tuesday for the selected
3: Wednesday program
4: Thursday
5: Friday
6: Saturday
Default: Sunday
42428 Scheduler Ex- Read / Size (bits): 8 0: Disable Use to enable or System Sche-
ception x En- Write Number of Fields: 2 1: Enable disable the se- duler
able Default: Disable lected exception
42429 Scheduler Ex- Read / Size (bits): 8 0: Once Only Use to adjust the System Sche-
ception x Re- Write Number of Fields: 2 1: Every Year repeat setting of duler
peat Default: Once Only the selected ex-
ception
42437 Daylight Sav- Read / Size (bits): 8 0: Disabled Enables the day- Real Time
ing Time En- Write Number of Fields: 2 1: Enabled light savings time Clock
able Default: Disabled feature
42438 Load Demand Read / Size (bits): 8 0: Do Nothing Use to force a re- Load Demand
Refresh Se- Write Number of Fields: 2 1: Refresh Sequence fresh of the ac- Control
quence Com- Default: Do Nothing tive load demand
mand sequence
42439 Genset Con- Read / Size (bits):8 0: Wye Delta or Wye for AC Setup
nection Type Write Number of Fields: 2 1: Delta generator set
Default: Wye connection
42443 Genset CT Read / Size (bits): 8 0: 1 Amp Generator set CT AC Setup
Secondary Write Number of Fields: 2 1: 5 Amp secondary cur-
Current Default: 5 Amp rent
42444 Utility Connec- Read / Size (bits): 8 0: Wye Delta or Wye for AC Setup
tion Type Write Number of Fields: 2 1: Delta utility connection
Default: Wye
42448 Utility CT Sec- Read / Size (bits): 8 0: 1 Amp Utility CT secon- AC Setup
ondary Cur- Write Number of Fields: 2 1: 5 Amp dary current
rent Default: 5 Amp
42454 Nominal Bat- Read / Size (bits): 8 0: 12V DC voltage pro- Battery Volt-
tery Voltage Write Number of Fields: 2 1: 24V vided to the con- age Protec-
Default: 24V trol tion
42461 Genset Online Read / Size (bits): 8 0: Disable Use to enable or PTC Sensors
Capacity Sen- Write Number of Fields: 2 1: Enable disable the gen-
sor Enable Default: Disable erator set online
capacity sensor

425
Addr. System Name Access Specifications Description Function
42472 Gen Bus Base Read Size (bits):8 0: Inactive Indicates that the System Infor-
Load Status Only Number of Fields: 2 1: Active generator bus is mation
Default: on base load ex-
tended paralle-
ling
42473 Util Bus Peak Read Size (bits): 8 0: Inactive Indicates that the System In-
Shave Status Only Number of Fields: 2 1: Active utility bus is on formation
Default: peak shave ex-
tended parallel-
ing
42600 Extended Par- Read / Size (bits): 8 0: Stop State of extended Discrete In-
allel Start Vol Write Number of Fields: 2 1: Start parallel start vol- puts
Default: Stop atile input
42601 Synchronizer Read / Size (bits): 8 0: inactive State of synchro- Discrete In-
Enable Vol Write Number of Fields: 2 1: Active nizer enable vol- puts
Default: inactive atile input
42602 Utility Source Read / Size (bits): 8 0: inactive State of utility Discrete In-
Failure Vol Write Number of Fields: 2 1: Active source failure puts
Default: inactive volatile input
42603 Transfer Inhib- Read / Size (bits):16 0: No Inhibit State of transfer Discrete In-
it Vol Write Number of Fields: 2 1: Inhibit inhibit volatile in- puts
Default: No Inhibit put
42604 Retranfer In- Read / Size (bits):8 0: No Inhibit State of retran- Discrete In-
hibit Vol Write Number of Fields: 2 1: Inhibit sfer inhibit vola- puts
Default: No Inhibit tile input
42605 Gen CB Inhibit Read / Size (bits): 8 0: No Inhibit State of genera- Discrete In-
Vol Write Number of Fields: 2 1: Inhibit tor CB inhibit vol- puts
Default: No Inhibit atile input
42606 Util CB Inhibit Read / Size (bits): 8 0: No Inhibit State of utility CB Discrete In-
Vol Write Number of Fields: 2 1: Inhibit inhibit volatile in- puts
Default: No Inhibit put
42607 Auto/Manual Read / Size (bits): 8 0: Auto State of auto/ Discrete In-
Vol Write Number of Fields: 2 1: Manual manual volatile puts
Default: Auto input
42608 Test Start Vol Read / Size (bits): 8 0: Stop State of test start Discrete In-
Write Number of Fields: 2 1: Start volatile input puts
Default: Stop
42609 Fault Reset Read / Size (bits): 8 0: Not Reset State of fault re- Discrete In-
Vol Write Number of Fields: 2 1: Reset set volatile input puts
Default: Not Reset
42610 Override Vol Read / Size (bits): 8 0: No Override State of override Discrete In-
Write Number of Fields: 2 1: Override volatile input puts
Default: No Override
42611 Extended Par- Read Size (bits): 8 0: Start State of extended Discrete In-
allel Start Sw Only Number of Fields: 2 1: Stop parallel start in- puts
Default: put

426
Addr. System Name Access Specifications Description Function
42612 Synchronizer Read Size (bits): 8 0: Inactive State of synchro- Discrete In-
Enable Sw Only Number of Fields: 2 1: Active nizer enable in- puts
Default: put
42613 Utility Source Read Size (bits): 8 0: Inactive State of utility Discrete In-
Failure Sw Only Number of Fields: 2 1: Active source failure in- puts
Default: put
42614 Transfer Inhib- Read Size (bits): 8 0: No Inhibit State of transfer Discrete In-
it Sw Only Number of Fields: 2 1: Inhibit inhibit input puts
Default:
42615 Retransfer In- Read Size (bits): 8 0: No Inhibit State of retran- Discrete In-
hibit Sw Only Number of Fields: 2 1: Inhibit sfer inhibit input puts
Default:
42616 Gen CB Inhibit Read Size (bits): 8 0: No Inhibit Sate of generator Discrete In-
Sw Only Number of Fields: 2 1: Inhibit CB inhibit input puts
Default:
42617 Util CB Inhibit Read Size (bits): 8 0: No Inhibit State of utility CB Discrete In-
Sw Only Number of Fields: 2 1: Inhibit inhibit input puts
Default:
42618 Auto/Manual Read Size (bits): 8 0: Auto State of auto/ Discrete In-
Sw Only Number of Fields: 2 1: Manual manual input puts
Default:
42619 Test Start Sw Read Size (bits): 8 0: Stop State of test Discrete In-
Only Number of Fields: 2 1: Start start input puts
Default:
42620 Fault Reset Read Size (bits): 8 0: No Reset State of fault re- Discrete In-
Sw Only Number of Fields: 2 1: Reset set input puts
Default:
42621 Override Sw Read Size (bits): 8 0: No Override State of override Discrete In-
Only Number of Fields: 2 1: Override input puts
Default:
42622 Master Inhibit Read Size (bits): 8 0: No Inhibit Indicates state of Priority Con-
Only Number of Fields: 2 1: Inhibit master priority in- trol
Default: hibit
42623 Gen CB Read Size (bits): 8 0: Inactive State of genera- Discrete In-
Tripped Sw Only Number of Fields: 2 1: Active tor CB tripped in- puts
Default: put
42624 Gen CB Read / Size (bits): 8 0: Inactive State of genera- Discrete In-
Tripped Vol Write Number of Fields: 2 1: Active tor CB tripped puts
Default: Inactive volatile input
42625 Util CB Read Size (bits): 8 0: Inactive State of utility CB Discrete In-
Tripped Sw Only Number of Fields: 2 1: Active tripped input puts
Default:
42626 Util Cb Tripped Read / Size (bits): 8 0: Inactive State of utility CB Discrete In-
Vol Write Number of Fields: 4 1: Active tripped volatile in- puts
Default: Inactive put
42627 Genset Phase Read Size (bits): 8 0: L1-L2-L3 Generator set Phase
Rotation Only Number of Fields: 2 1: L1-L3-L2 phase rotation
Default:

427
Addr. System Name Access Specifications Description Function
42628 Utility Phase Read Size (bits): 8 0: L1-L2-L3 Utility phase rota- Phase
Rotation Only Number of Fields: 2 1: L1-L3-L2 tion
Default:
42629 Gen1 CB Read Size (bits): 8 0: Breaker Open State of Gen1 CB Discrete In-
Position Sw Only Number of Fields: 2 1: Breaker Closed position input puts
Default:
42630 Gen1 CB Read / Size (bits): 8 0: Breaker Open State of Gen1 CB Discrete In-
Position Vol Write Number of Fields: 2 1: Breaker Closed position volatile puts
Default: Open input
42631 Gen2 CB Read Size (bits): 8 0: Breaker Open State of Gen2 CB Discrete In-
Position Sw Only Number of Fields: 2 1: Breaker Closed position input puts
Default:
42632 Gen2 CB Read / Size (bits): 8 0: Breaker Open State of Gen2 CB Discrete In-
Position Vol Write Number of Fields: 2 1: Breaker Closed position volatile puts
Default: Open input
42633 Gen3 CB Read Size (bits):16 0: Breaker Open State of Gen3 CB Discrete In-
Position Sw Only Number of Fields: 2 1: Breaker Closed position input puts
Default:
42634 Gen3 CB Read / Size (bits): 8 0: Breaker Open State of Gen3 CB Discrete In-
Position Vol Write Number of Fields: 2 1: Breaker Closed position volatile puts
Default: Open input
42635 Gen4 CB Read Size (bits): 8 0: Breaker Open State of Gen4 CB Discrete In-
Position Sw Only Number of Fields: 2 1: Breaker Closed position input puts
Default:
42636 Gen4 CB Read / Size (bits): 8 0: Breaker Open State of Gen4 CB Discrete In-
Position Vol Write Number of Fields: 2 1: Breaker Closed position volatile puts
Default: Open input
42637 Network Mas- Read / Size (bits): 8 0: No Inhibit Use to manually Priority Con-
ter Inhibit Write Number of Fields: 2 1: Inhibit inhibit the module trol
Default: No Inhibit
42700 Gen1 Avail- Read Size (bits): 8 0: Gen Does Not Ex- For load demand Load Demand
ability State Only Number of Fields: 5 ist use − Indicates Control
1: Offline status of Gen1
2: Waiting for Gen
3: Online
4: Failed
Default:
42701 Gen2 Avail- Read Size (bits): 8 0: Gen Does Not Ex- For load demand Load Demand
ability State Only Number of Fields: 5 ist use − Indicates Control
1: Offline status of Gen2
2: Waiting for Gen
3: Online
4: Failed
Default:

428
Addr. System Name Access Specifications Description Function
42702 Gen3 Avail- Read Size (bits): 8 0:Gen Does Not Exist For load demand Load Demand
ability State Only Number of Fields: 5 1: Offline use − Indicates Control
2: Waiting for Gen status of Gen3
3: Online
4: Failed
Default:
42703 Gen4 Avail- Read Size (bits): 8 0:Gen Does Not Exist For load demand Load Demand
ability State Only Number of Fields: 5 1: Offline use − Indicates Control
2: Waiting for Gen status of Gen4
3: Online
4: Failed
Default:
42712 GenA Read Size (bits): 8 0: Gen1 Indicates which Load Demand
Only Number of Fields: 4 1: Gen2 generator set is Control
2: Gen3 currently GenA
3: Gen4 for load demand
Default:
42713 GenB Read Size (bits): 8 0: Gen1 Indicates which Load Demand
Only Number of Fields: 4 1: Gen2 generator set is Control
1: Gen3 currently GenB
1: Gen4 for load demand
Default:
42714 GenC Read Size (bits): 8 0: Gen1 Indicates which Load Demand
Only Number of Fields: 4 1: Gen2 generator set is Control
1: Gen3 currently GenC
1: Gen4 for load demand
Default:
42715 GenD Read Size (bits): 8 0: Gen1 Indicates which Load Demand
Only Number of Fields: 4 1: Gen2 generator set is Control
1: Gen3 currently GenD
1: Gen4 (first to stop) for
Default: load demand
42716 Load Demand Read Size (bits): 8 0: Off Indicates operat- Load Demand
State Only Number of Fields: 3 1: Initial Delay Timing ing state of the Control
2: Load Monitor load demand
Default: control

42721 Next Gen To Read Size (bits): 8 0: Gen1 Indicates which Load Demand
Restart Only Number of Fields: 5 1: Gen2 generator set is Control
2: Gen3 next to be re-
3: Gen4 started if load
4: None conditions are
Default: met
42722 Next Gen To Read Size (bits): 8 0: Gen1 Indicates which Load Demand
Shutdown Only Number of Fields: 5 1: Gen2 generator set is Control
2: Gen3 next to be
3: Gen4 stopped if load
4: None conditions are
Default: met

429
Addr. System Name Access Specifications Description Function
42723 Load Demand Read Size (bits): 8 0: Run Status of the load Discrete Out-
Gen1 Driver Only Number of Fields: 2 1: Load Demand demand Gen1 puts
Status Stop driver output
Default:

42724 Load Demand Read Size (bits): 8 0: Run Status of the load Discrete Out-
Gen2 Driver Only Number of Fields: 2 1: Load Demand demand Gen2 puts
Status Stop driver output
Default:
42725 Load Demand Read Size (bits): 8 0: Run Status of the load Discrete Out-
Gen3 Driver Only Number of Fields: 2 1: Load Demand demand Gen3 puts
Status Stop driver output
Default:
42726 Load Demand Read Size (bits): 8 0: Run Status of the load Discrete Out-
Gen4 Driver Only Number of Fields: 2 1: Load Demand demand Gen4 puts
Status Stop driver output
Default:

42728 Genset Bus Read Size (bits): 8 0: No Overload Indicates whether System In-
kW Overload Only Number of Fields: 2 1: Overload generator bus is formation
Status Default: overloaded
based on kW
42729 Genset Bus Read Size (bits): 8 0: No Overload Indicates whether System Infor-
Underfrequen- Only Number of Fields: 2 1: Overload generator bus is mation
cy Overload Default: overloaded
Status based on fre-
quency
42730 Active Sched- Read Size (bits): 8 0: None Indicates the cur- System Sche-
ule Only Number of Fields: 19 1: Program 1 rently active duler
2: Program 2 scheduler pro-
3: Program 3 gram or excep-
4: Program 4 tion
5: Program 5
6: Program 6
7: Program 7
8: Program 8
9: Program 9
10: Program 10
11: Program 11
12: Program 12
13: Exception 1
14: Exception 2
15: Exception 3
16: Exception 4
17: Exception 5
18: Exception 6
Default:

430
Addr. System Name Access Specifications Description Function
42731 Scheduler Run Read Size (bits): 8 0: Off Indicates current System
Command Only Number of Fields: 4 1: No Load run command Scheduler
2: With Load coming from the
3: Extended Parallel scheduler func-
Default: tion
42737 Modbus Clear Read / Size (bits): 8 0: Do Nothing Clears all the Communica-
Counters Write Number of Fields: 2 1: Clear Counters Modbus counters tions
Default: Do Nothing
42738 Clock Mode Read / Size (bits): 8 0: Normal Use to set clock Real Time
Write Number of Fields: 3 1: Set Clock and save setting Clock
2: Save Clock
Default: Normal

42745 Clock Day Read Size (bits): 8 0: Sunday Indicates day of Real Time
Only Number of Fields: 7 1: Monday week for current Clock
2: Tuesday date
3: Wednesday
4: Thursday
5: Friday
6: Saturday
Default:

431
THIS PAGE LEFT INTENTIONALLY BLANK

432
7. DMC 1000 Modbus Bitmap Data

Note: Earlier versions of software may not support all of the Modbus registers in the following table. If a particu-
lar register is not available in your installation, it is possible that the Modbus connection is working but the con-
troller software does not support that particular register.

Note: If an address or bit is not listed in this table, it is not used.

Addr. Bit# System Name Fault Event Name Response


Code
42500 0 Fault Status Bit- 1455 Utility Main Breaker Position Contact Warning Warning
map 1
42500 1 Fault Status Bit- 2396 Utility Main Breaker Fail To Close Warning Warning
map 1
42500 2 Fault Status Bit- 2397 Utility Main Breaker Fail To Open Warning Warning
map 1
42500 3 Fault Status Bit- 1219 Utility Main Breaker Tripped Warning Warning
map 1
42500 4 Fault Status Bit- 1914 Utility Bus Phase Rotation Warning Warning
map 1
42500 5 Fault Status Bit- 1912 Utility Bus Loss Of Phase Warning Warning
map 1
42500 6 Fault Status Bit- 2331 Utility Bus Undervoltage Warning Warning
map 1
42500 7 Fault Status Bit- 2358 Utility Bus Overvoltage Warning Warning
map 1
42500 8 Fault Status Bit- 1223 Utility Bus Frequency Warning Warning
map 1
42500 24 Fault Status Bit- 2648 Remote I/O Communication Failure Warning Warning
map 1
42500 25 Fault Status Bit- 1689 Real Time Clock Power Interrupt Warning Warning
map 1
42500 26 Fault Status Bit- 1335 AC Metering Out Of Range Warning Warning
map 1
42500 27 Fault Status Bit- 1999 Maximum Parallel Time Warning Warning
map 1
42500 28 Fault Status Bit- 343 Hardware Failure Warning Warning
map 1
42500 29 Fault Status Bit- 1456 Synchronizer Output Limit Warning Warning
map 1
42500 30 Fault Status Bit- 2416 Calibration Checksum Warning Warning
map 1
42500 31 Fault Status Bit- 353 EEPROM Write Error Warning Warning
map 1

433
Addr. Bit# System Name Fault Event Name Response
Code
42502 0 Fault Status Bit- 1454 Genset Main Breaker Position Contact Warning Warning
map 2
42502 1 Fault Status Bit- 1452 Genset Main Breaker Fail To Close Warning Warning
map 2
42502 2 Fault Status Bit- 1453 Genset Main Breaker Tripped Warning Warning
map 2
42502 3 Fault Status Bit- 1328 Genset Bus Phase Rotation Warning Warning
map 2
42502 4 Fault Status Bit- 1915 Genset Bus Phase Rotation Warning Warning
map 2
42502 5 Fault Status Bit- 1913 Genset Bus Loss Of Phase Warning Warning
map 2
42502 6 Fault Status Bit- 1225 Genset Bus Undervoltage Warning Warning
map 2
42502 7 Fault Status Bit- 1224 Genset Bus Overvoltage Warning Warning
map 2
42502 8 Fault Status Bit- 1226 Genset Bus Frequency Warning Warning
map 2
42502 24 Fault Status Bit- 1541 Genset Failed To Come Online Warning Warning
map 2
42502 25 Fault Status Bit- 2647 Load Demand Setup Warning Warning
map 2
42502 26 Fault Status Bit- 1444 Genset Bus Overload Warning Warning
map 2
42502 27 Fault Status Bit- 1989 kW Load Control Output Limit Warning Warning
map 2
42502 28 Fault Status Bit- 1991 kVAR Load Control Output Limit Warning Warning
map 2
42502 29 Fault Status Bit- 1121 Fail To Disconnect Warning Warning
map 2
42502 30 Fault Status Bit- 1458 Synchronizer Phase Rotation Mismatch Warn- Warning
map 2 ing
42502 31 Fault Status Bit- 1457 Fail To Synchronizer Warning Warning
map 2
42504 0 Event Status Bit- 1222 Not in Automatic Event Event
map 1
42504 1 Event Status Bit- 1483 Common Warning Event Event
map 1
42504 2 Event Status Bit- 2965 Genset Bus Available Event Event
map 1
42504 3 Event Status Bit- 2328 Utility Bus Available Event Event
map 1

434
Addr. Bit# System Name Fault Event Name Response
Code
42504 4 Event Status Bit- 2333 Genset Bus Connected Event Event
map 1
42504 5 Event Status Bit- 2332 Utility Bus Connected Event Event
map 1
42504 6 Event Status Bit- 2971 Test / Extended Parallel Event Event
map 1
42504 7 Event Status Bit- 1916 Synchronized Event Event
map 1
42504 8 Event Status Bit- 1534 Load Control Output Event Event
map 1

435
THIS PAGE LEFT INTENTIONALLY BLANK

436
8. DMC 1500 Communication Server 1

Modbus Address: 2 (Slave).


Note: If an address or bit is not listed in this table, it is not used.

Note: The external device can read 1−40 contiguous registers, write 1−40 contiguous registers, or read diagnos-
tic counters.

Modbus Address Bit # Alarm Event


40001 0 (LSB) Utility Main Breaker Position Contact Warning
40001 1 Utility Main Breaker Fail To Close Warning
40001 2 Utility Main Breaker Fail To Open Warning
40001 3 Utility Main Breaker Tripped Warning
40001 4 Utility Bus Phase Rotation Warning
40001 5 Utility Bus Loss of Phase Warning
40001 6 Utility Bus Undervoltage Warning
40001 7 Utility Bus Overvoltage Warning
40001 8 Utility Bus Frequency Warning
40001 9 Remote IO Comm Failure Warning
40001 10 Real Time Clock Power Interrupt Warning
40001 11 AC Metering Out Of Range Warning
40001 12 Maximum Parallel Time Warning
40001 13 Unused
40001 14 Synchronizer Output Limit Warning
40001 15 (MSB) Calibration Checksum Warning MCM 3320

Modbus Address Bit # Alarm Event


40002 0 (LSB) EEPROM Write Error Warning MCM 3320
40002 1 Genset Main Breaker Position Contact Warning
40002 2 Genset Main Breaker Fail to Close Warning
40002 3 Genset Main Breaker Fail to Open Warning
40002 4 Genset Main Breaker Tripped Warning
40002 5 Genset Bus Phase Rotation Warning
40002 6 Genset Bus Loss of Phase Warning
40002 7 Genset Bus Undervoltage Warning
40002 8 Genset Bus Overvoltage Warning
40002 9 Genset Bus Frequency Warning
40002 10 Low Battery Voltage Warning MCM 3320
40002 11 High Battery Voltage Warning MCM 3320
40002 12 Genset Failed to Come Online Warning
40002 13 Load Demand Setup Warning

437
Modbus Address Bit # Alarm Event
40002 14 Genset Bus Over Load Limit Warning
40002 15 (MSB) kW Load Control Output Limit Warning

Modbus Address Bit # Alarm Event


40003 0 (LSB) KVAR Load Control Output Limit Warning
40003 1 Fail to Disconnect Warning
40003 2 Synchronizer Phase Rotation Mismatch Warning
40003 3 Fail to Synchronize Warning
40003 4 Normal Operation Lockout
40003 5 Common Warning MCM 3320
40003 6 Common Server 1 to Network ATS Comm Failure
40003 7 Common Server 1 to MCM3320 Comm Failure
40003 8 Common Server 1 Battery Warning
40003 9 Common Server 1 Comm Server 2 Comm Failure
40003 10 Unused
40003 11 Unused
40003 12 Unused
40003 13 Unused
40003 14 Unused
40003 15 (MSB) Unused

Modbus Address Bit # Alarm Event


40004 0 (LSB) Feeder Breaker 1 Trip
40004 1 Feeder Breaker 2 Trip
40004 2 Feeder Breaker 3 Trip
40004 3 Feeder Breaker 4 Trip
40004 4 Feeder Breaker 5 Trip
40004 5 Feeder Breaker 6 Trip
40004 6 Feeder Breaker 7 Trip
40004 7 Feeder Breaker 8 Trip
40004 8 Feeder Breaker 9 Trip
40004 9 Feeder Breaker 10 Trip
40004 10 Unused
40004 11 Unused
40004 12 Unused
40004 13 Unused
40004 14 Unused
40004 15 (MSB) Unused

Note: 40405 is unused.

Modbus Address Bit # Alarm Event


40006 0 (LSB) System in Auto−Opened Transition
40006 1 System in Auto−Hard Closed Transition

438
Modbus Address Bit # Alarm Event
40006 2 System in Auto−Soft Closed Transition
40006 3 System Manual Mode Active
40006 4 System Automatic Mode Active
40006 5 Common Warning Event
40006 6 Genset Bus Available Event
40006 7 Utility Bus Available Event
40006 8 Genset Bus Connected Event
40006 9 Utility Bus Connected Event
40006 10 Synchronized Event
40006 11 Load Control Output Event
40006 12 Genset Source Unloaded Event
40006 13 Utility Source Unloaded Event
40006 14 Genset Bus Load Event
40006 15 (MSB) Utility Bus Peak Shave Event

Modbus Address Bit # Alarm Event


40007 0 (LSB) Extended Paralleling Enable
40007 1 Extended Paralleling Disable
40007 2 System in Extended Parallel
40007 3 System in Test with Load
40007 4 System in Test without Load
40007 5 System Test Off
40007 6 Load Demand Enable
40007 7 Load Demand Disable
40007 8 Extended Parallel Off
40007 9 Unused
40007 10 Unused
40007 11 Unused
40007 12 Unused
40007 13 Unused
40007 14 Unused
40007 15 (MSB) Unused

Generator Set Bus Data


Generator Bus Data MB Address Data Type Multiplier Units
Generator Set L1N Volts 40009 16U 1 Volts
Generator Set L2N Volts 40010 16U 1 Volts
Generator Set L3N Volts 40011 16U 1 Volts
Generator Set LN Average Volt 40012 16U 1 Volts
Generator set L1L2 Volts 40013 16U 1 Volts
Generator Set L2L3 Volts 40014 16U 1 Volts
Generator Set L3L1 Volts 40015 16U 1 Volts
Generator Set LL Average Volts 40016 16U 1 Volts

439
Generator Bus Data MB Address Data Type Multiplier Units
Generator Set L1 Current 40017 16U 1 Amps
Generator Set L2 Current 40018 16U 1 Amps
Generator Set L3 Current 40019 16U 1 Amps
Generator Set Average Current 40020 16U 1 Amps
Generator Set L1 kW 40021 16S 1 kW
Generator Set L2 kW 40022 16S 1 kW
Generator Set L3 kW 40023 6S 1 kW
Generator Set Total kW 40024 16S 1 kW
Generator Set L1 kVAR 40025 16S 1 kVAR
Generator Set L2 kVAR 40026 16S 1 kVAR
Generator Set L3 kVAR 40027 16S 1 kVAR
Generator Set Total kVAR 40028 16S 1 kVAR
Generator Set Total Power Factor 40029 16S 0.01
Generator Set L1 kVA 40030 16U 1 kVA
Generator Set L2 kVA 40031 16U 1 kVA
Generator Set L3 kVA 40032 16U 1 kVA
Generator Set Total kVA 40033 16U 1 kVA
MB Generator Set Frequency 40034 16U 0.1 Hz
Generator Set Total Negative kWh 40035 32U 1 kWh
40036
Generator Set Total Positive kWh 40037 32U 1 kWh
40038
Generator Set Total Net kWh 40039 32S 1 kWh
40040
Generator Set Total Negative kVARh 40041 32U 1 kVARh
40042
Generator Set Total Positive kVARh 40043 32U 1 kVARh
40044
Generator Set Total Net kVARh 40045 32S 1 kVARh
40046
Generator Set Total kVAh 40047 32U 1 kVAh
40048
Generator Set Available Current 40049 16U 1 Amps
Generator Set L1 Current Percent 40050 16U 0.1 %
Generator Set L2 Current Percent 40051 16U 0.1 %
Generator Set L3 Current Percent 40052 16U 0.1 %
Generator Set Total kW Percent 40053 16U 0.1 %
Generator Set Frequency Percent 40054 16S 0.1 %
Generator Set L1L2 Voltage Percent 40055 16U 0.1 %
Generator Set L2L3 Voltage Percent 40056 16U 0.1 %
Generator Set L3L1 Voltage Percent 40057 16U 0.1 %

440
Utility Bus Data
Utility Bus Data MB Address Data Type Multiplier Units
Utility L1N Voltage 40059 16U 1 Volts
Utility L2N Voltage 40060 16U 1 Volts
Utility L3N Voltage 40061 16U 1 Volts
Utility LN Average Voltage 40062 16U 1 Volts
Utility L1L2 Voltage 40063 16U 1 Volts
Utility L2L3 Voltage 40064 16U 1 Volts
Utility L3L1 Voltage 40065 16U 1 Volts
Utility LL Average Voltage 40066 16U 1 Volts
Utility L1 Current 40067 16U 1 Amps
Utility L2 Current 40068 16U 1 Amps
Utility L3 Current 40069 16U 1 Amps
Utility Average Current 40070 16U 1 Amps
Utility L1 kW 40071 16S 1 kW
Utility L2 kW 40072 16S 1 kW
Utility L3 kW 40073 16S 1 kW
Utility Total kW 40074 16S 1 kW
Utility L1 kVAR 40075 16S 1 kVAR
Utility L2 kVAR 40076 16S 1 kVAR
Utility L3 kVAR 40077 16S 1 kVAR
Utility Total kVAR 40078 16S 1 kVAR
Utility Total Power Factor 40079 16S 0.01
Utility L1 kVA 40080 16U 1 kVA
Utility L2 kVA 40081 16U 1 kVA
Utility L3 kVA 40082 16U 1 kVA
Utility Total kVA 40083 16U 1 kVA
MB Utility Frequency 40084 16U 0.1 Hz
Utility Total Negative kWh 40085 32U 1 kWh
40086
Utility Total Positive kWh 40087 32U 1 kWh
40088
Utility Total Net kWh 40089 32S 1 kWh
40090
Utility Total Negative kVARh 40091 32U 1 kVARh
40092
Utility Total Positive kVARh 40093 32U 1 kVARh
40094
Utility Total Net kVARh 40095 32S 1 kVARh
40096
Utility Total kVAh 40097 32U 1 kVAh
40098
System Total kW 40099 16S 1 kW

441
Utility Bus Data MB Address Data Type Multiplier Units
System Total kVAR 40100 16S 0.01 kVAR
System Total Power Factor 40101 16S 1
System Total kVA 40102 16U 1 KVA

ATS 1−5 DATA


ATS Raw Data ATS 1 ATS 2 ATS 3 ATS 4 ATS 5 Multiplier Units
Device Type 40257 40317 40377 40437 40497
Mode (See table 8−2 page 443) 40258 40318 40378 40438 40498
State (See Table 8−1 page 443) 40259 40319 40379 40439 40499
Fault Code 40260 40320 40380 40440 40500
Fault Type (See table 8−3 page 443) 40261 40321 40381 40441 40501
Percent Amps 40262 40322 40382 40442 40502 0.5 %
Total kW 40263 40323 40383 40443 40503
NFPA 110 (See Section 4 Table 1-1 40264 40324 40384 40444 40504
page 30)
NFPA Extended(See Section 4 Table 40265 40325 40385 40445 40505
4-2 page 381)
Frequency Load 40266 40326 40386 40446 40506 0.1 Hz
Total pf Load 40267 40327 40387 40447 40507 0.00005 pf
Total KVA Load 40268 40328 40388 40448 40508 KVA
Total kW Load 40269 40329 40389 40449 40509 kW
Total KVAR Load 40270 40330 40390 40450 40510 kVAR
Volts ab Load 40271 40331 40391 40451 40511 Volts
Volts bc Load 40272 40332 40392 40452 40512 Volts
Volts ca Load 40273 40333 40393 40453 40513 Volts
Volts a Load 40274 40334 40394 40454 40514 Volts
Volts b Load 40275 40335 40395 40455 40515 Volt
Volts c Load 40276 40336 40396 40456 40516 Volts
Amps a Load 40277 40337 40397 40457 40517 Amps
Amps b Load 40278 40338 40398 40458 40518 Amps
Amps c Load 40279 40339 40399 40459 40519 Amps
Percent Amps a Load 40280 40340 40400 40460 40520 0.5 %
Percent Amps b Load 40281 40341 40401 40461 40521 0.5 %
Percent Amps c Load 40282 40342 40402 40462 40522 0.5 %
Frequency SRC1 40283 40343 40403 40463 40523 0.1 Hz
Total pf SRC1 40284 40344 40404 40464 40524 0.00005 PF
Total KVA SRC1 40285 40345 40405 40465 40525
Total kW SRC1 40286 40346 40406 40466 40526
Total KVAR SRC1 40287 40347 40407 40467 40527
Volts ab SRC1 40288 40348 40408 40468 40528
Volts bc SRC1 40289 40349 40409 40469 40529
Volts ca SRC1 40290 40350 40410 40470 40530
Volts a SRC1 40291 40351 40411 40471 40531

442
ATS Raw Data ATS 1 ATS 2 ATS 3 ATS 4 ATS 5 Multiplier Units
Volts b SRC1 40292 40352 40412 40472 40532 Volts
Volts c SRC1 40293 40353 40413 40473 40533
Amps a SCR1 40294 40354 40414 40474 40534 Amps
Amps b SCR1 40295 40355 40415 40475 40535
Amps c SRC1 40296 40356 40416 40476 40536
Percent Amps a SCR1 40297 40357 40417 40477 40537 0.5 %
Percent Amps b SCR1 40298 40358 40418 40478 40538 0.5 %
Percent Amps c SCR1 40299 40359 40419 40479 40539 0.5 %
Frequency SRC2 40300 40360 40420 40480 40540 0.1 Hz
Total pf SRC2 40301 40361 40421 40481 40541 0.00005 pf
Total KVA SRC2 40302 40362 40422 40482 40542 KVA
Total kW SRC2 40303 40363 40423 40483 40543 kW
Total KVAR SRC2 40304 40364 40424 40484 40544 KVAR
Volts ab SRC2 40305 40365 40425 40485 40545 Volts
Volts bc SRC2 40306 40366 40426 40486 40546 Volts
Volts ca SRC2 40307 40367 40427 40487 40547 Volts
Volts a SRC2 40308 40368 40428 40488 40548 Volts
Volts b SRC2 40309 40369 40429 40489 40549 Volts
Volts c SRC2 40310 40370 40430 40490 40550 Volts
Amps a SRC2 40311 40371 40431 40491 40551 Amps
Amps b SRC2 40312 40372 40432 40492 40552 Amps
Amps c SRC2 40313 40373 40433 40493 40553 Amps
Percent Amps a SRC2 40314 40374 40434 40494 40554 0.5 %
Percent Amps b SRC2 40315 40375 40435 40495 40555 0.5 %
Percent Amps c SRC2 40316 40376 40436 40496 40556 0.5 %

Word Data (Reference Tables ATS 1-5 and


6-10)
Table 8−2
Table 8−1
Digital Mode
0 Test
Digital State
1 Utility / Genset
0 Neutral
2 Utility / Utility
1 Source 1 Connected
3 Genset / Genset
2 Source 2 Connected
3 Source 1 and 2 Connected Table 8−3

Digital Fault Type


0 No Faults
1 Warning

443
ATS 6−10 DATA
ATS Raw Data ATS 6 ATS 7 ATS 8 ATS 9 ATS 10 Multiplier Units
Device Type 40557 40617 40677 40737 40797
Mode (See table 8−2 page 443) 40558 40618 40678 40738 40798
State (See table 8−1 page 443) 40559 40619 40679 40739 40799
Fault Code 40560 40620 40680 40740 40800
Fault Type (See table 8−3 page 40561 40621 40681 40741 40801
443)
Percent Amps 40562 40622 40682 40742 40802 0.5 %
Total kW 40563 40623 40683 40743 40803
NFPA 110 (See Section 4 Table 1-1 40564 40624 40684 40744 40804
page 30)
NFPA Extended (See Section 4 Table 40565 40625 40685 40745 40805
4-2 page 381)
Frequency Load 40566 40626 40686 40746 40806 0.1 Hz
Total pf Load 40567 40627 40687 40747 40807 0.00005 PF
Total KVA Load 40568 40628 40688 40748 40808 KVA
Total kW Load 40569 40629 40689 40749 40809 kW
Total KVAR Load 40570 40630 40690 40750 40810 kVAR
Volts ab Load 40571 40631 40691 40751 40811 Volts
Volts bc Load 40572 40632 40692 40752 40812 Volts
Volts ca Load 40573 40633 40693 40753 40813 Volts
Volts a Load 40574 40634 40694 40754 40814 Volts
Volts b Load 40575 40635 40695 40755 40815 Volts
Volts c Load 40576 40636 40696 40756 40816 Volts
Amps a Load 40577 40637 40697 40757 40817 Amps
Amps b Load 40578 40638 40698 40758 40818 Amps
Amps c Load 40579 40639 40699 40759 40819 Amps
Percent Amps a Load 40580 40640 40700 40760 40820 0.5 %
Percent Amps b Load 40581 40641 40701 40761 40821 0.5 %
Percent Amps c Load 40582 40642 40702 40762 40822 0.5 %
Frequency SRC1 40583 40643 40703 40763 40823 0.1 Hz
Total pf SRC1 40584 40644 40704 40764 40824 0.00005 PF
Total KVA SRC1 40585 40645 40705 40765 40825 KVA
Total kW SRC1 40586 40646 40706 40766 40826 kW
Total KVAR SRC1 40587 40647 40707 40767 40827 kVAR
Volts bc SRC1 40588 40648 40708 40868 40828 Volts
Volts bc SRC1 40589 40649 40709 40869 40829 Volts
Volts ca SRC1 40590 40650 40710 40870 40830 Volts
Volts a SRC1 40591 40651 40711 40871 40831 Volts
Volts b SRC1 40592 40652 40712 40872 40832 Volts
Volts c SRC1 40593 40653 40713 40873 40833 Volts
Amps a SCR1 40594 40654 40714 40874 40834 Amps
Amps b SCR1 40595 40655 40715 40875 40835 Amps

444
ATS Raw Data ATS 6 ATS 7 ATS 8 ATS 9 ATS 10 Multiplier Units
Amps c SRC1 40596 40656 40716 40876 40836 Amps
Percent Amps a SCR1 40597 40657 40717 40777 40837 0.5 %
Percent Amps b SCR1 40598 40658 40718 40778 40838 0.5 %
Percent Amps c SCR1 40599 40659 40719 40779 40839 0.5 %
Frequency SRC2 40600 40660 40720 40780 40840 0.1 Hz
Total pf SRC2 40601 40661 40721 40781 40841 0.00005 pf
Total KVA SRC2 40602 40662 40722 40782 40842 KVA
Total kW SRC2 40603 40663 40723 40783 40843 kW
Total KVAR SRC2 40604 40664 40724 40784 40844 KVAR
Volts ab SRC2 40605 40665 40725 40785 40845 Volts
Volts bc SRC2 40606 40666 40726 40786 40846 Volts
Volts ca SRC2 40607 40667 40727 40787 40847 Volts
Volts a SRC2 40608 40668 40728 40788 40848 Volts
Volts b SRC2 40609 40669 40729 40789 40849 Volts
Volts c SRC2 40610 40670 40730 40790 40850 Volts
Amps a SRC2 40611 40671 40731 40791 40851 Amps
Amps b SRC2 40612 40672 40732 40792 40852 Amps
Amps c SRC2 40613 40673 40733 40793 40853 Amps
Percent Amps a SRC2 40614 40674 40734 40794 40854 0.5 %
Percent Amps b SRC2 40615 40675 40735 40795 40855 0.5 %
Percent Amps c SRC2 40616 40676 40736 40796 40856 0.5 %

445
THIS PAGE LEFT INTENTIONALLY BLANK

446
9. DMC 1500 Communication Server 2

Modbus Address: 1 (Slave).


Note: If an address or bit is not listed in this table, it is not used.

Note: The external device can read 1−40 contiguous registers, write 1−40 contiguous registers, or read diagnos-
tic counters.

Modbus Address Bit # Alarm Event


40001 0 (LSB) Neutral Earthing 1 Fail to Open Warning
40001 1 Neutral Earthing 2 Fail to Open Warning
40001 2 Neutral Earthing 3 Fail to Open Warning
40001 3 Neutral Earthing 4 Fail to Open Warning
40001 4 Neutral Earthing 5 Fail to Open Warning
40001 5 Neutral Earthing 6 Fail to Open Warning
40001 6 Neutral Earthing 7 Fail to Open Warning
40001 7 Neutral Earthing 8 Fail to Open Warning
40001 8 Neutral Earthing 1 Fail to Closed Warning
40001 9 Neutral Earthing 2 Fail to Closed Warning
40001 10 Neutral Earthing 3 Fail to Closed Warning
40001 11 Neutral Earthing 4 Fail to Closed Warning
40001 12 Neutral Earthing 5 Fail to Closed Warning
40001 13 Neutral Earthing 6 Fail to Closed Warning
40001 14 Neutral Earthing 7 Fail to Closed Warning
40001 15 (MSB) Neutral Earthing 8 Fail to Closed Warning

Modbus Address Bit # Alarm Event


40002 0 (LSB) Neutral Earthing 1 Tripped Warning
40002 1 Neutral Earthing 2 Tripped Warning
40002 2 Neutral Earthing 3 Tripped Warning
40002 3 Neutral Earthing 4 Tripped Warning
40002 4 Neutral Earthing 5 Tripped Warning
40002 5 Neutral Earthing 6 Tripped Warning
40002 6 Neutral Earthing 7 Tripped Warning
40002 7 Neutral Earthing 8 Tripped Warning
40002 8 Undergrounded Bus Warning
40002 9 Undergrounded Bus Failure − System Shutdown
40002 10 Multiple NECs Connected
40002 11 Multiple System Grounds Connected
40002 12 Unused
40002 13 Unused

447
Modbus Address Bit # Alarm Event
40002 14 Unused
40002 15 (MSB) Unused

Modbus Address Bit # Alarm Event


40003 0 (LSB) Station Battery Power Supply Fault
40003 1 UPS Fault
40003 2 On Station Battery Warning
40003 3 System Manual Mode Active
40003 4 Utility Failure
40003 5 Utility Out of Limits for Extended Parallel
40003 6 Common Server 2 Battery Warning
40003 7 System Emergency Stop
40003 8 Hardware Failure Warning MCM 3320
40003 9 Unused
40003 10 Unused
40003 11 Unused
40003 12 Unused
40003 13 Unused
40003 14 Unused
40003 15 (MSB) Unused

Modbus Address Bit # Alarm Event


40004 0 (LSB) Illegal Genset Node Address Assignment
40004 1 Unused
40004 2 Unused
40004 3 Comm Server 2 to Comm Server 1 Comm Failure
40004 4 Manufacturing Test Mode Active
40004 5 Unused
40004 6 Unused
40004 7 Unused
40004 8 Comm Server 2 to Genset 1 Comm Failure
40004 9 Comm Server 2 to Genset 2 Comm Failure
40004 10 Comm Server 2 to Genset 3 Comm Failure
40004 11 Comm Server 2 to Genset 4 Comm Failure
40004 12 Comm Server 2 to Genset 5 Comm Failure
40004 13 Comm Server 2 to Genset 6 Comm Failure
40004 14 Comm Server 2 to Genset 7 Comm Failure
40004 15 (MSB) Comm Server 2 to Genset 8 Comm Failure

Note: 40005 is unused.

Modbus Address Bit # Alarm Event


40006 0 (LSB) Gen 1 Breaker Closed
40006 1 Gen 2 Breaker Closed

448
Modbus Address Bit # Alarm Event
40006 2 Gen 3 Breaker Closed
40006 3 Gen 4 Breaker Closed
40006 4 Gen 5 Breaker Closed
40006 5 Gen 6 Breaker Closed
40006 6 Gen 7 Breaker Closed
40006 7 Gen 8 Breaker Closed
40006 8 Gen 1 Breaker Open
40006 9 Gen 2 Breaker Open
40006 10 Gen 3 Breaker Open
40006 11 Gen 4 Breaker Open
40006 12 Gen 5 Breaker Open
40006 13 Gen 6 Breaker Open
40006 14 Gen 7 Breaker Open
40006 15 (MSB) Gen 8 Breaker Open

Modbus Address Bit # Alarm Event


40007 0 (LSB) Gen 1 Running
40007 1 Gen 2 Running
40007 2 Gen 3 Running
40007 3 Gen 4 Running
40007 4 Gen 5 Running
40007 5 Gen 6 Running
40007 6 Gen 7 Running
40007 7 Gen 8 Running
40007 8 Gen 1 Fault
40007 9 Gen 2 Fault
40007 10 Gen 3 Fault
40007 11 Gen 4 Fault
40007 12 Gen 5 Fault
40007 13 Gen 6 Fault
40007 14 Gen 7 Fault
40007 15 (MSB) Gen 8 Fault

Modbus Address Bit # Alarm Event


40008 0 (LSB) Gen 1 Shut Down in Load Demand
40008 1 Gen 2 Shut Down in Load Demand
40008 2 Gen 3 Shut Down in Load Demand
40008 3 Gen 4 Shut Down in Load Demand
40008 4 Gen 5 Shut Down in Load Demand
40008 5 Gen 6 Shut Down in Load Demand
40008 6 Gen 7 Shut Down in Load Demand
40008 7 Gen 8 Shut Down in Load Demand
40008 8 Gen Start Signal On MCM 3320

449
Modbus Address Bit # Alarm Event
40008 9 Gen Start Signal Off MCM 3320
40008 10 Gen Main Breaker Closed
40008 11 Gen Main Breaker Opened
40008 12 Utility Main Breaker Closed
40008 13 Utility Main Breaker Opened
40008 14 Utility Failure
40008 15 (MSB) Return to Utility

Modbus Address Bit # Alarm Event


40009 0 (LSB) Remote Commands Enable
40009 1 Remote Commands Disable
40009 2 Remote Test On
40009 3 Remote Test Off
40009 4 Remote Extended Parallel On
40009 5 Remote Extended Parallel Off
40009 6 Remote Transfer Inhibit On
40009 7 Remote Transfer Inhibit Off
40009 8 Remote Retransfer Inhibit On
40009 9 Remote Retransfer Inhibit Off
40009 10 Auto Genset Start Inhibit in Manual Mode Enable
40009 11 Auto Genset Start Inhibit in Manual Mode Disable
40009 12 Unused
40009 13 Unused
40009 14 Unused
40009 15 (MSB) Unused

Generator Raw Data Gen 1-5


Generator Raw Data Gen 1 Gen 2 Gen 3 Gen 4 Gen 5 Multiplier Units
Device Type 40011 40066 40121 40176 40231
Control Switch (See table 9−7 page 40012 40067 40122 40177 40232
452)
State (See table 9−1 page 452) 40013 40068 40123 40178 40233
Fault Code 40014 40069 40124 40179 40234
Fault Type (See table 9−6 page 452) 40015 40070 40125 40180 40235
Percent kW Standby 40016 40071 40126 40181 40236 0.5 %
Total kW 40017 40072 40127 40182 40237
NFPA 110 (See Section 4, Table 4-3 on 40018 40073 40128 40183 40238
page 381)
NFPA Extended (See Section 4, Table 40019 40074 40129 40184 40239
4-4 on page 381)
Frequency 40020 40075 40130 40185 40240 0.1 Hz
Total pf 40021 40076 40131 40186 40241 0.00005 pf
Total KVA 40022 40077 40132 40187 40242 KVA
Total kW 40023 40078 40133 40188 40243 kW

450
Generator Raw Data Gen 1 Gen 2 Gen 3 Gen 4 Gen 5 Multiplier Units
Total KVAR 40024 40079 40134 40189 40244 kVAR
Volts ab 40025 40080 40135 40190 40245 Volts
Volts bc 40026 40081 40136 40191 40246 Volts
Volts ca 40027 40082 40137 40192 40247 Volts
Volts a 40028 40083 40138 40193 40248 Volts
Volts b 40029 40084 40139 40194 40249 Volt
Volts c 40030 40085 40140 40195 40250 Volts
Amps a 40031 40086 40141 40196 40251 Amps
Amps b 40032 40087 40142 40197 40252 Amps
Amps c 40033 40088 40143 40198 40253 Amps
Percent Amps a 40034 40089 40144 40199 40254 0.5 %
Percent Amps b 40035 40090 40145 40200 40255 0.5 %
Percent Amps c 40036 40091 40146 40201 40256 0.5 %
Battery Voltage 40037 40092 40147 40202 40257 0.1 Volts
Oil Pressure 40038 40093 40148 40203 40258 0.1 KPA
Oil Temp 40039 40094 40149 40204 40259 0.1 Deg K
Coolant Temp 40040 40095 40150 40205 40260 0.1 Deg K
Fuel Rate 40041 40096 40151 40206 40261 0.001 GPH
Engine RPM 40042 40097 40152 40207 40262 RPM
Engine Starts 40043 40098 40153 40208 40263 Starts
Engine Runtime High 40044 40099 40154 40209 40264
Engine Runtime Low 40045 40100 40155 40210 40265 0.1 Sec
Total kWH High 40046 40101 40156 40211 40266
Total kWH Low 40047 40102 40157 40212 40267 KWH
Total Fuel High 40048 40103 40158 40213 40268
Total Fuel Low 40049 40104 40159 40214 40269 0.01 GAL
Bus Frequency 40050 40105 40160 40215 40270 0.1 Hz
Bus Volts ab 40051 40106 40161 40216 40271 Volts
Bus Volts bc 40052 40107 40162 40217 40272 Volts
Bus Volts ca 40053 40108 40163 40218 40273 Volts
Bus Volts a 40054 40109 40164 40219 40274 Volts
Bus Volts b 40055 40110 40165 40220 40275 Volts
Bus Volts c 40056 40111 40166 40221 40276 Volts
Customer Faults 40057 40112 40167 40222 40277
Network Faults 40058 40113 40168 40223 40278
Customer Faults 40059 40114 40169 40224 40279
ES State (See Table 9−2 page 452) 40060 40115 40170 40225 40280
Load Share State (See Table 9−3 page 40061 40116 40171 40226 40281
452)
Load Govern State kW (See Table 9−7 40062 40117 40172 40227 40282
page 452)
Load Govern State kVAR (See Table 9−5 40063 40118 40173 40228 40283
Page 452)

451
Word Data (Reference the ATS 6−1 and 6−10 tables
in Section 8)
Table 9−1 Table 9−4

Digital State Digital Load Govern State kW


0 Stopped 0 NA
1 Start Pending 1 Ramp Load
2 Warm−up at Idle 2 Track Target Load
3 Running 3 Ramp Unload
4 Cooldown at Rated 4 Ramp Unload Done
5 Cooldown at idle

Table 9−2
Table 9−5

Digital ES State Digital Load Govern State kVAR


0 Standby 0 NA
1 Dead Bus Close 1 Ramp Load
2 Synchronizing 2 Track Target Load
3 Load Share 3 Ramp Unload
4 Load Govern 4 Ramp Unload Done
Table 9−3 Table 9−6

Digital Load Share State Digital Fault Type


0 Not in Load Share 0 Normal
1 Track Load 1 Warning
2 Ramp Load 2 Derate
3 Ramp Unload 3 Shutdown with Cooldown
4 Load Demand Shutdown 4 Shutdown

Table 9−7

Digital Control Switch


0 Off
1 Manual
2 Automatic

452
Generator Raw Data Gen 6-8
Generator Raw Data Gen 6 Gen 7 Gen 8 Multiplier Units
Device Type 40286 40341 40396
Control Switch (See Table 9−7 page 452) 40287 40342 40397
State (See Table 9−1 page 452) 40288 40343 40398
Fault Code 40289 40344 40399
Fault Type (See Table 9−6 page 452) 40290 40345 40400
Percent kW Standby 40291 40346 40401 0.5 %
Total kW 40292 40347 40402
NFPA 110 (See Section 4, Table 4-3 on 40293 40348 40403
page 381)
NFPA Extended (See Section 4, Table 40294 40349 40404
4-4 on page 381)
Frequency 40295 40350 40405 0.1 Hz
Total pf 40296 40351 40406 0.00005 PF
Total KVA 40297 40352 40407 KVA
Total kW 40298 40353 40408 kW
Total KVAR 40299 40354 40409 kVAR
Volts ab 40300 40355 40410 Volts
Volts bc 40301 40356 40411 Volts
Volts ca 40302 40357 40412 Volts
Volts a 40303 40358 40413 Volts
Volts b 40304 40359 40414 Volts
Volts c 40305 40360 40415 Volts
Amps a 40306 40361 40416 Amps
Amps b 40307 40362 40417 Amps
Amps c 40308 40363 40418 Amps
Percent Amps a 40309 40364 40419 0.5 %
Percent Amps b 40310 40365 40420 0.5 %
Percent Amps c 40311 40366 40421 0.5 %
Battery Voltage 40312 40367 40422 0.1 Volts
Oil Pressure 40313 40368 40423 0.1 KPA
Oil Temp 40314 40369 40424 0.1 Deg K
Coolant Temp 40315 40370 40425 0.1 Deg K
Fuel Rate 40316 40371 40426 0.001 GPH
Engine RPM 40317 40372 40427 RPM
Engine Starts 40318 40373 40428 Starts
Engine Runtime High 40319 40374 40429
Engine Runtime Low 40320 40375 40430 0.1 Sec
Total kWH High 40321 40376 40431
Total kWH Low 40322 40377 40432 KWH
Total Fuel High 40323 40378 40433
Total Fuel Low 40324 40379 40434 0.01 GAL
Bus Frequency 40325 40380 40435 0.1 Hz

453
Generator Raw Data Gen 6 Gen 7 Gen 8 Multiplier Units
Bus Volts ab 40326 40381 40436 Volts
Bus Volts bc 40327 40382 40437 Volts
Bus Volts ca 40328 40383 40438 Volts
Bus Volts a 40329 40384 40439 Volts
Bus Volts b 40330 40385 40440 Volts
Bus Volts c 40331 40386 40441 Volts
Customer Faults 40332 40387 40442
Network Faults 40333 40388 40443
Customer Faults 40334 40389 40444
ES State (See Table 9−2 page 452) 40335 40390 40445
Load Share State (See Table 9−3 page 40336 40391 40446
452)
Load Govern State kW (See Table 9−4 40337 40392 40447
page 452)
Load Govern State kVAR (See Table 9−5 40338 40393 40448
page 452)

454
10. MCM3320 Modbus Register Map

Modbus Communications All data parameters are transmitted as registers. All


registers are two 8 bit bytes in length (16 bits per reg-
This section defines the Modbus communications in- ister). If a register requires more than 16 bits, then,
terface. Serial communications use an RTU (Remote the subsequent registers are also used. Therefore,
Terminal Unit) two-wire RS−485, master/slave multi− with a 32 bit register X and X+1, the X register con-
drop network configuration described in the Modbus tains the upper 16 bits of data and the X+1 register
Protocol Reference Guide. The controller is defined contains the lower 16 bits. A register with 1 bit of data
as a slave. uses the least significant bit of a 16 bit register.

For all discrete data referenced a by bit number, the


Reference Documents
least significant bit for the register is numbered as “0”
and the most significant bit as “15”. For all fault sta-
1. Modicon “Modbus Protocol Reference Guide PI-
tuss and event statuss, a “1” indicates the fault or
MBUS-300 Rev. G” describes the serial transmission
event is active and a “0” indicates inactive.
modes.

2. “Modbus Over Serial Line Specification and Imple-


Modbus Activity LED
mentation Guide v1.0” describes the lower levels of
The modbus activity LED is on when either the con-
modbus protocol.
trol is receiving a modbus packet or sending a mod-
bus packet. It is also on when a protocol timer is in
3. “Modbus Application Protocol Specification v1.1a”
timer mode. This precedes a protocol switch on the
describes the application layer of the modbus proto-
SCI1 port. Otherwise, the LED is off.
col.
Supported Functions
Serial Port Configuration
The controller is only capable of processing the fol-
The port communications occur, by default, at a baud
lowing modbus data and control function queries
rate of 19200 using eight data bits, one stop-bit with
from the master:
even parity, and are configurable via MON and
PCCnet logically.  Read holding registers (Function Code 03)
 Preset single register (Function Code 06)
Device Addresses
 Diagnostics (Function Code 08)
The PLC is the master device in the modbus network.  Preset multiple registers (Function Code 16)
The modbus node address is configurable and is set
to node 1 by default. The control responds to any query containing a func-
tion code, other than codes 03, 06, 08 and 16 #by
Power-Up Time sending an exception response with the exception
code set to “01” (Illegal Function).
The MCM3320 is capable of supporting communica-
tion transactions within 10 seconds following initial The control responds to any read of a single address
power-up. that is not specified in this specification by sending an
exception response with the exception code set to
Response Time “02” (Illegal Address).

The controller responds within 100 ms of a request The control responds to any read of a block of 2 or
for information the master. more addresses containing an address that is not
specified in this specification by returning data of
Data Formatting 0xFF for that address.

The format for each register is defined in the modbus The control responds to Preset Single Register and
register table. Preset

455
Multiple Register functions when the data is out of Register Maps
bounds by sending an exception response with the
exception code set to “03” (Illegal Data Value). Addresses were assigned to maintain compatibility
with the existing Modlon gateway where applicable
The following conventions are followed:
Holding Register Function
40xxx − Genset control registers
The control provides the ability to read all read only 41xxx − Transfer switch control register
and read/write registers in the Modbus Registers
Table via the Holding Register function. From 1 to 40 42xxx − Master control registers (MCM3320)
contiguous registers can be read at a time. If an at-
tempt is made to read a register that’s not available, 4x0xx − General data registers (volts, cur
then an error is returned and none of the data will be rent, etc.) primarily for genset bus
returned. 4x1xx − General data registers (volts, cur
rent, etc.) primarily for utility bus
Preset Single/Preset Multiple Registers
4x2xx − Configuration and status registers −
Function
Block 1

The control provides the ability to write to (preset) 4x3xx − Settings − Block 1
Read/Write registers in the modbus registers table 4x4xx − Settings − Block 2
via both the present single register (Function Code
06) and the preset multiple registers (Function Code 4x5xx − Bitmap
16). A write to a single register can be performed by
the master using the modbus data and control func- 4x6xx − Switch I/O
tion query preset single register (Function Code 06).
4x7xx − Configuration and status registers −
For writes requiring writes to 1 to 40 contiguous reg-
Block 2
isters, the master uses the modbus data and control
function query called preset multiple registers (Func- Application Layer
tion Code 16). If a write attempt is made and any of
the data is invalid or if an attempt is made to write to a The application layer processes the packet. Four
register that’s not available, then an error is returned functions are supported: Read Hold Registers, Set
and none of the data will be written. Single Register, Modbus Loopback, and Set Multiple
Registers. If the request packet specifies an unsup-
ported function, then an illegal function response is
Diagnostic Counters
returned. See the “Modbus Application Protocol
Specification” to see how the request and response
The following diagnostic counters is also available packets are formatted and how each function pro-
via the modbus diagnostic function (Function Code cesses the data.
08). The following parameters are updated and avail-
able via MON and modbus logical access. A single Read Hold Registers
logical is also available to clear all counters.
Given a starting address and the quantity of registers
 Bus Message Count − Total Modbus packets on desired, this function gets the data, formats it if re-
bus quired, and writes it to the TX buffer. If any register in
the range is not supported, then an error is returned.
 CRC Errors Count − Total Modbus packets re-
ceived with a bad CRC Set Single Register
 Exception Count − Total Modbus packets re- Given a register address and data, this function veri-
ceived where an exception was sent back fies that the data is within range; then if OK, writes the
data.
 No Response Count − Total Modbus packets re-
ceived where no response sent back Modbus Loopback
 Slave Message Count − Total Modbus packets This function performs Modbus diagnostic function-
on bus addressed to this node ality. Some of the functionality defined here is also

456
available via MON and PCCnet logicals. See the 0x0F Return Slave No Response Count
“Diagnostic Counters” section of this document for
details. The Loopback function supports: Set Multiple Registers
0x00 Return Query Data
Given a starting address, the quantity of registers,
0x01 Restart and two bytes of data for each register, this function
verifies that all the data is within range; then if OK,
0x04 Force Listen Only Mode writes all data. If any register in the range is not sup-
ported or any of the data is out of range then an error
0x0A Clear Counter is returned and no data is written. A 32-bit parameter
is written using “Write Multiple Register” (Command
0x0B Return Bus Message Count Code 16) only. Using “Write Single Register” (Com-
mand Code 06) returns an exception code 2 − Illegal
0x0C Return Bus Communication Error Address. If both registers are not in the same block,
Count (bad CRC) the control sends an exception code 2−Illegal Ad-
dress.
0x0D Return Bus Exception Error Count

0x0E Return Slave Message Count Modbus Register Table


Note: For bitmapped quantities, refer to table in section 8 on page 425. For 32 bit quantities, the register address
listed (X) is the high 16 bit. The low 16 bits are at register X+1. If an address or bit is not listed in this table, it is not
used.

Addr. System Name Access Specifications Description Function


42001 MB logical Read / Multiplier: Unit: NA Logical address Communica-
Read Address Write 1.000000000000 Lower Limit: .000 to be read via tions
Offset: 0 Upper Limit: modbus
Size (bits):16 65535.000
Sign: U Default: 0
42002 MB Logical Read Multiplier: Unit: NA Logical data to Communica-
Read Data Only 1.000000000000 Lower Limit: be read via mod- tions
Offset: 0 Upper Limit: bus
Size (bits): 32 Default:
Sign: U
42004 Save Adjust- Read / 0: Do Nothing Use to save ad- Controller In-
ments Write 1: Save Trims justments directly formation
Default: Do Nothing in non-volatile
memory
42009 Device Type Read Multiplier: Unit: NA Hard coded de- Communica-
Only 1.000000000000 Lower Limit: vice type id= 52 tions
Offset: 0 Upper Limit: (0x0034)
Size (bits):16 Default:
Sign: U
42010 Software Ver- Read Multiplier: Unit: NA Software version Controller In-
sion Only .000100000000 Lower Limit: number formation
Offset: 0 Upper Limit:
Size (bits):16 Default:
Sign: U
42011 Genset Run Read 0: Time Delay Start Indicates state of PTC Operat-
Sequence Only 1: Time Delay Stop the generator set ing Mode
State 2: Stop run sequence
3: Run
Default:

457
Addr. System Name Access Specifications Description Function
42012 Current Fault Read Multiplier: Unit: NA The most recent- Fault and
Status Only 1.000000000000 Lower Limit: ly occurring fault Event Infor-
Offset: 0 Upper Limit: which is still ac- mation
Size (bits):16 Default: tive
Sign: U
42017 Genset Bus Read 0: Unavailable Energization sta- PTC Sensors
Status Only 1: Dead tus of generator
2: Live Set bus
Default:
42018 Genset L1N Read Multiplier: Unit: Volts Generator set Voltage
Voltage Only 1.000000000000 Lower Limit: Volts L1N voltage
Offset: 0 Upper Limit: Volts
Size (bits): 16 Default
Sign: U
42019 Genset L2N Read Multiplier: Unit: Volts Generator set Voltage
Voltage Only 1.000000000000 Lower Limit: Volts L2N voltage
Offset: 0 Upper Limit: Volts
Size (bits): 16 Default:
Sign: U
42020 Genset L3N Read Multiplier: Unit: Volts Generator set Voltage
Voltage Only 1.000000000000 Lower Limit: Volts L3N voltage
Offset: 0 Upper Limit: Volts
Size (bits): 16 Default:
Sign: U
42021 Genset LN Av- Read Multiplier: Unit: Volts Generator set LN Voltage
erage Voltage Only 1.000000000000 Lower Limit: Volts average voltage
Offset: 0 Upper Limit: Volts
Size (bits): 16 Default:
Sign: U
42022 Genset L1L2 Read Multiplier: Unit: Volts Generator set Voltage
Voltage Only 1.000000000000 Lower Limit: Volts L1L2 voltage
Offset: 0 Upper Limit: Volts
Size (bits): 16 Default:
Sign: U
42023 Genset L2L3 Read Multiplier: Unit: Volts Generator set Voltage
Voltage Only 1.000000000000 Lower Limit: Volts L2L3 voltage
Offset: 0 Upper Limit: Volts
Size (bits): 16 Default
Sign: U
42024 Genset L3L1 Read Multiplier: Unit: Volts Generator set Voltage
Voltage Only 1.000000000000 Lower Limit: Volts L3L1 voltage.
Offset: 0 Upper Limit: Volts
Size (bits): 16 Default
Sign: U
42025 Genset LL Av- Read Multiplier: Unit: Volts Generator set LL Voltage
erage Voltage Only 1.000000000000 Lower Limit: Volts Average voltage
Offset: 0 Upper Limit: Volts
Size (bits): 16 Default
Sign: U

458
Addr. System Name Access Specifications Description Function
42026 Genset L1 Read Multiplier: Unit: Amps Generator set L1 Current
Current Only 1.000000000000 Lower Limit: Amps current
Offset: 0 Upper Limit: Amps
Size (bits): 16 Default
Sign: U
42027 Genset L2 Read Multiplier: Unit: Amps Generator set L2 Current
Current Only 1.000000000000 Lower Limit: Amps current
Offset: 0 Upper Limit: Amps
Size (bits): 16 Default
Sign: U
42028 Genset L3 Read Multiplier: Unit: Amps Generator set L3 Current
Current Only 1.000000000000 Lower Limit: Amps current
Offset: 0 Upper Limit: Amps
Size (bits): 16 Default:
Sign: U
42029 Genset Aver- Read Multiplier: Unit: Amps Generator set av- Current
age Current Only 1.000000000000 Lower Limit: Amps erage current
Offset: 0 Upper Limit:Amps
Size (bits): 16 Default:
Sign: U
42030 Genset L1 kW Read Multiplier: Unit: kW Generator set L1 Power
Only 1.000000000000 Lower Limit: kW kW
Offset: 0 Upper Limit: kW
Size (bits): 16 Default:
Sign: S
42031 Genset L2 kW Read Multiplier: Unit: kW Generator set L2 Power
Only 1.000000000000 Lower Limit: kW kW
Offset: 0 Upper Limit: kW
Size (bits): 16 Default:
Sign: S
42032 Genset L3 kW Read Multiplier: Unit: kW Generator set L3 Power
Only 1.000000000000 Lower Limit: kW kW
Offset: 0 Upper Limit: kW
Size (bits): 16 Default:
Sign: S
42033 Genset Total Read Multiplier: Unit: kW Generator set to- Power
kW Only 1.000000000000 Lower Limit: kW tal kW
Offset: 0 Upper Limit: kW
Size (bits): 16 Default:
Sign: S
42034 Genset L1 Read Multiplier: Unit: kVAR Generator set L1 Power
kVAR Only 1.000000000000 Lower Limit: kVAR kVAR
Offset: 0 Upper Limit: kVAR
Size (bits): 16 Default:
Sign: S
42035 Genset L2 Read Multiplier: Unit: kVAR Generator set L2 Power
kVAR Only 1.000000000000 Lower Limit: kVAR kVAR
Offset: 0 Upper Limit: kVAR
Size (bits): 16 Default:
Sign: S

459
Addr. System Name Access Specifications Description Function
42036 Genset L3 Read Multiplier: Unit: kVAR Generator set L3 Power
kVAR Only 1.000000000000 Lower Limit: kVAR kVAR
Offset: 0 Upper Limit: kVAR
Size (bits): 16 Default:
Sign: S
42037 Genset Total Read Multiplier: Unit: kVAR Generator set to- Power
kVAR Only 1.000000000000 Lower Limit: kVAR tal kVAR
Offset: 0 Upper Limit: kVAR
Size (bits): 16 Default:
Sign: S
42038 Genset Total Read Multiplier: Unit: NA Generator set L1 Power
Power Factor Only 1.000000000000 Lower Limit: power factor
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: S
42039 Genset L1 Read Multiplier: Unit: kVA Generator set L1 Power
kVA Only 1.000000000000 Lower Limit: kVA kVA
Offset: 0 Upper Limit: kVA
Size (bits): 16 Default:
Sign: U
42040 Genset L2 Read Multiplier: Unit: kVA Generator set L2 Power
kVA Only 1.000000000000 Lower Limit: kVA kVA
Offset: 0 Upper Limit: kVA
Size (bits): 16 Default:
Sign: U
42041 Genset L3 Read Multiplier: Unit: kVA Generator set L3 Power
kVA Only 1.000000000000 Lower Limit: kVA kVA
Offset: 0 Upper Limit: kVA
Size (bits): 16 Default:
Sign: U
42042 Genset Total Read Multiplier: Unit: kVA Generator set to- Power
kVA Only 1.000000000000 Lower Limit: kVA tal kVA
Offset: 0 Upper Limit: kVA
Size (bits): 16 Default:
Sign: U
42043 MB Genset Read Multiplier: Unit: Hz Generator set Communica-
Frequency Only .100000000000 Lower Limit: Hz line frequency tions
Offset: 0 Upper Limit: Hz scaled by 10 =
Size (bits): 16 Default: 1Hz for modbus
Sign: U
42044 Genset Total Read Multiplier: Unit: kWh Generator set to- Energy
Negative kWh Only 1.000000000000 Lower Limit: kWh tal negative kWh
Offset: 0 Upper Limit: kWh accumulation
Size (bits): 32 Default:
Sign: U
42046 Genset Total Read Multiplier: Unit: kWh Generator set to- Energy
Positive kWh Only 1.000000000000 Lower Limit: kWh tal positive kWh
Offset: 0 Upper Limit: kWh accumulation
Size (bits): 32 Default:
Sign: U

460
Addr. System Name Access Specifications Description Function
42048 Genset Total Read Multiplier: Unit: kWh Generator set to- Energy
Net kWh Only 1.000000000000 Lower Limit: kWh tal net kWh accu-
Offset: 0 Upper Limit: kWh mulation
Size (bits): 32 Default:
Sign: S

42050 Genset Total Read Multiplier: Unit: kVARh Generator set to- Energy
Negative Only 1.000000000000 Lower Limit: kVARh tal negative
kVARh Offset: 0 Upper Limit: kVARh kVARh accu-
Size (bits): 32 Default: mulation
Sign: U

40052 Genset Total Read Multiplier: Unit: kVARh Generator set to- Energy
Positive Only 1.00000000000 Lower Limit: kVARh tal positive
kVARh 0Offset: 0 Upper Limit: kVARh kVARh accu-
Size (bits): 32 Default: mulation
Sign: U

42054 Genset Total Read Multiplier: Unit: kVARh Generator set to- Energy
Net kVARh Only 1.000000000000 Lower Limit: kVARh tal net kVARh ac-
Offset: 0 Upper Limit: kVARh cumulation
Size (bits): 32 Default:
Sign: S

42056 Genset Total Read Multiplier: Unit: kVARh Generator set to- Energy
kVAh Only 1.000000000000 Lower Limit: kVARh tal kVAh accu-
Offset: 0 Upper Limit: kVARh mulation
Size (bits): 32 Default:
Sign: U

42058 Genset Avail- Read Multiplier: Unit: Amps Calculated amps Current
able Current Only 1.000000000000 Lower Limit: Amps which represent
Offset: 0 Upper Limit: Amps 100−% generator
Size (bits): 16 Default: set bus current −
Sign: U used by bargraph

42059 Genset L1 Read Multiplier: Unit: % Generator set L1 Current


Current Per- Only .100000000000 Lower Limit: % current as per-
cent Offset: 0 Upper Limit: % cent of generator
Size (bits): 16 Default: Set total current
Sign: S capacity − used
by bargraph

42060 Genset L2 Read Multiplier: Unit: % Generator set L2 Current


Current Per- Only .100000000000 Lower Limit: % current as per-
cent Offset: 0 Upper Limit: % cent of generator
Size (bits): 16 Default: Set total current
Sign: U capacity − used
by bargraph

42061 Genset L3 Read Multiplier: Unit: % Generator set L3 Current


Current Per- Only .100000000000 Lower Limit: % current as per-
cent Offset: 0 Upper Limit: % cent of generator
Size (bits): 16 Default: Set total current
Sign: U capacity − used
by bargraph

461
Addr. System Name Access Specifications Description Function
42062 Genset Total Read Multiplier: Unit: % Generator set kW Power
kW Percent Only .100000000000 Lower Limit: % as percent of to-
Offset: 0 Upper Limit: % tal generator set
Size (bits): 16 Default: capacity − used
Sign: S by bargraph
42063 Genset Fre- Read Multiplier: Unit: % Generator set Frequency
quency Per- Only .100000000000 Lower Limit: % frequency as per-
cent Offset: 0 Upper Limit: % cent of system
Size (bits): 16 Default: frequency − used
Sign: U by bargraph
42064 Genset L1L2 Read Multiplier: Unit: % Generator set Voltage
Voltage% Only .100000000000 Lower Limit: % L1L2 voltage%
Offset: 0 Upper Limit: %
Size (bits): 16 Default:
Sign: U
42065 Genset L2L3 Read Multiplier: Unit: % Generator set Voltage
Voltage% Only .100000000000 Lower Limit: % L2L3 voltage %
Offset: 0 Upper Limit: %
Size (bits): 16 Default:
Sign: U
42066 Genset L3L1 Read Multiplier: Unit: % Generator set Voltage
Voltage% Only .100000000000 Lower Limit: % L3L1 voltage%
Offset: 0 Upper Limit: %
Size (bits): 16 Default:
Sign: U
42070 Genset Total Read Multiplier: Unit: kW Generator set to- Power
kW_32bit Only 1.000000000000 Lower Limit: kW tal kW in 32 bit
Offset: 0 Upper Limit: kW
Size (bits): 32 Default:
Sign: S
42072 Genset Total Read Multiplier: Unit: kVAR Generator set to- Power
kVAR_32bit Only 1.000000000000 Lower Limit: kVAR tal kVAR in 32 bit
Offset: 0 Upper Limit: kVAR
Size (bits): 32 Default:
Sign: S
42074 Genset Total Read Multiplier: Unit: kVA Generator set to- Power
kVA_32bit Only 1.000000000000 Lower Limit: kVA tal kVA in 32 bit
Offset: 0 Upper Limit: kVA
Size (bits): 32 Default:
Sign: U
42117 Utility Bus Sta- Read 0: Unavailable Energization sta- PTC Sensors
tus Only 1: Dead tus of the utilitiy
2: Live bus
Default:
42118 Utility L1N Read Multiplier: Unit: Volts Utility L1N volt- Voltage
Voltage Only 1.000000000000 Lower Limit: Volts age
Offset: 0 Upper Limit: Volts
Size (bits): 16 Default:
Sign:U

462
Addr. System Name Access Specifications Description Function
42119 Utility L2N Vol- Read Multiplier: Unit: Volts Utility L2N volt- Voltage
tage Only 1.000000000000 Lower Limit: Volts age
Offset: 0 Upper Limit: Volts
Size (bits): 16 Default:
Sign: U
42120 Utility L3N Read Multiplier: Unit: Volts Utility L3N volt- Voltage
Voltage Only 1.000000000000 Lower Limit: Volts age
Offset: 0 Upper Limit: Volts
Size (bits): 16 Default:
Sign: U
42121 Utility LN Av- Read Multiplier: Unit: Volts Utility LN aver- Voltage
erage Voltage Only 1.000000000000 Lower Limit: Volts age voltage
Offset: 0 Upper Limit: Volts
Size (bits): 16 Default:
Sign: U
42122 Utility L1L2 Read Multiplier: Unit: Volts Utility L1L2 volt- Voltage
Voltage Only 1.000000000000 Lower Limit: Volts age
Offset: 0 Upper Limit: Volts
Size (bits): 16 Default:
Sign: U
42123 Utility L2L3 Read Multiplier: Unit: Volts Utility L2L3 volt- Voltage
Voltage Only 1.000000000000 Lower Limit: Volts age
Offset: 0 Upper Limit: Volts
Size (bits): 16 Default:
Sign: U
42124 Utility L3L1 Read Multiplier: Unit: Volts Utility L3L1 volt- Voltage
Voltage Only 1.000000000000 Lower Limit: Volts age
Offset: 0 Upper Limit: Volts
Size (bits): 16 Default:
Sign: U
42125 Utility LL Aver- Read Multiplier: Unit: Volts Utility LL average Voltage
age Voltage Only 1.000000000000 Lower Limit: Volts voltage
Offset: 0 Upper Limit: Volts
Size (bits): 16 Default:
Sign: U
42126 Utility L1 Cur- Read Multiplier: Unit: Amps Utility L1 current Current
rent Only 1.000000000000 Lower Limit: Amps
Offset: 0 Upper Limit: Amps
Size (bits): 16 Default:
Sign: U
42127 Utility L2 Cur- Read Multiplier: Unit: Amps Utility L2 current Current
rent Only 1.000000000000 Lower Limit: Amps
Offset: 0 Upper Limit: Amps
Size (bits): 16 Default:
Sign: U
42128 Utility L3 Cur- Read Multiplier: Unit: Amps Utility L3 current Current
rent Only 1.000000000000 Lower Limit: Amps
Offset: 0 Upper Limit: Amps
Size (bits): 16 Default:
Sign: U

463
Addr. System Name Access Specifications Description Function
42129 Utility Average Read Multiplier: Unit: Amps Utility average Current
Current Only 1.000000000000 Lower Limit: Amps current
Offset: 0 Upper Limit: Amps
Size (bits): 16 Default:
Sign: U
42130 Utility L1 kW Read Multiplier: Unit: kW Utility L1 kW Power
Only 1.000000000000 Lower Limit: kW
Offset: 0 Upper Limit: kW
Size (bits): 16 Default:
Sign: S
42131 Utility L2 kW Read Multiplier: Unit: kW Utility L2 kW Power
Only 1.000000000000 Lower Limit: kW
Offset: 0 Upper Limit: kW
Size (bits): 16 Default:
Sign: S
42132 Utility L3 kW Read Multiplier: Unit: kW Utility L3 kW Power
Only 1.000000000000 Lower Limit: kW
Offset: 0 Upper Limit: kW
Size (bits): 16 Default:
Sign: S
42133 Utility Total kW Read Multiplier: Unit: kW Utility total kW Power
Only 1.000000000000 Lower Limit: kW
Offset: 0 Upper Limit: kW
Size (bits): 16 Default:
Sign: S
42134 Utility L1 kVAR Read Multiplier: Unit: kVAR Utility L1 kVAR Power
Only 1.000000000000 Lower Limit: kVAR
Offset: 0 Upper Limit: kVAR
Size (bits): 16 Default:
Sign: S
42135 Utility L2 kVAR Read Multiplier: Unit: kVAR Utility L2 kVAR Power
Only 1.000000000000 Lower Limit: kVAR
Offset: 0 Upper Limit: kVAR
Size (bits): 16 Default:
Sign: S
42136 Utility L3 kVAR Read Multiplier: Unit: kVAR Utility L3 kVAR Power
Only 1.000000000000 Lower Limit: kVAR
Offset: 0 Upper Limit: kVAR
Size (bits): 16 Default:
Sign: S
42137 Utility Total Read Multiplier: Unit: kVAR Utility total kVAR Power
kVAR Only 1.000000000000 Lower Limit: kVAR
Offset: 0 Upper Limit: kVAR
Size (bits): 16 Default:
Sign: S
42138 Utility Total Read Multiplier: Unit: NA Utility L1 power Power
Power Factor Only 1.000000000000 Lower Limit: factor
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: S

464
Addr. System Name Access Specifications Description Function
42139 Utility L1 kVA Read Multiplier: Unit: kVA Utility L1 kVA Power
Only 1.000000000000 Lower Limit: kVA
Offset: 0 Upper Limit: kVA
Size (bits): 16 Default:
Sign: U
42140 Utility L2 kVA Read Multiplier: Unit: kVA Utility L2 kVA Power
Only 1.000000000000 Lower Limit: kVA
Offset: 0 Upper Limit: kVA
Size (bits): 16 Default:
Sign: U
42141 Utility L3 kVA Read Multiplier: Unit: kVA Utility L3 kVA Power
Only 1.000000000000 Lower Limit: kVA
Offset: 0 Upper Limit: kVA
Size (bits): 16 Default:
Sign: U
42142 Utility Total Read Multiplier: Unit: kVA Utility total kVA Power
kVA Only 1.000000000000 Lower Limit: kVA
Offset: 0 Upper Limit: kVA
Size (bits): 16 Default:
Sign: U
42143 MB Utility Fre- Read Multiplier: Unit: Hz Utility line fre- Communica-
quency Only 1.000000000000 Lower Limit: Hz quency scaled by tions
Offset: 0 Upper Limit: Hz 10 = 1Hz for
Size (bits): 16 Default: modbus
Sign: U
42144 Utility Total Read Multiplier: Unit: kWh Utility total nega- Energy
Negative kWh Only 1.000000000000 Lower Limit: kWh tive kWh accu-
Offset: 0 Upper Limit: kWh mulation
Size (bits): 32 Default:
Sign: U
42146 Utility Total Read Multiplier: Unit: kWh Utility total posi- Energy
Positive kWh Only 1.000000000000 Lower Limit: kWh tive kWh accu-
Offset: 0 Upper Limit: kWh mulation
Size (bits): 32 Default:
Sign: U
42148 Utility Total Read Multiplier: Unit: kWh Utility total net Energy
Net kWh Only 1.000000000000 Lower Limit: kWh kWh accumula-
Offset: 0 Upper Limit: kWh tion
Size (bits): 32 Default:
Sign: S
42150 Utility Total Read Multiplier: Unit: kVARh Utility total nega- Energy
Negative Only 1.000000000000 Lower Limit: kVARh tive kVARh accu-
Offset: 0 Upper Limit: kVARh mulation
Size (bits): 32 Default:
Sign: U
42152 Utility Total Read Multiplier: Unit: kVARh Utility total posi- Energy
Positive Only 1.000000000000 Lower Limit: kVARh tive kVARh accu-
kVARh Offset: 0 Upper Limit: kVARh mulation
Size (bits): 32 Default:
Sign: U

465
Addr. System Name Access Specifications Description Function
42154 Utility Total Read Multiplier: Unit: kVARh Utility total net Energy
Net kVARh Only 1.000000000000 Lower Limit: kVARh kVARh accu-
Offset: 0 Upper Limit: kVARh mulation
Size (bits): 32 Default:
Sign: S
42156 Utility Total Read Multiplier: Unit: kVAh Utility total Energy
kVAh Only 1.000000000000 Lower Limit: kVAh kVARh accu-
Offset: 0 Upper Limit: kVAh mulation
Size (bits): 32 Default:
Sign: U
42158 System Total Read Multiplier: Unit: kW Sum of generator Power
kW Only 1.000000000000 Lower Limit: kW set bus and utility
Offset: 0 Upper Limit: kW bus kW
Size (bits): 16 Default:
Sign: S
42159 System Total Read Multiplier: Unit: kVAR Sum of generator Power
kVAR Only 1.000000000000 Lower Limit: kVAR set bus and utility
Offset: 0 Upper Limit: kVAR bus kVAR
Size (bits): 16 Default:
Sign: S
42160 System Total Read Multiplier: Unit: NA System total Power
Power Factor Only .010000000000 Lower Limit: power factor
Offset: 0 Upper Limit: (totalized value of
Size (bits): 16 Default: utility bus plus
Sign: S generator set
bus)
42161 System Total Read Multiplier: Unit: kVA Sum of generator Power
kVA Only 1.000000000000 Lower Limit: kVA set bus and utility
Offset: 0 Upper Limit: kVA bus kVA
Size (bits): 16 Default:
Sign: U
42162 Utility L1 Cur- Read Multiplier: Unit: % Utility L1 current Current
rent Percent Only .100000000000 Lower Limit: % as % of utility to-
Offset: 0 Upper Limit: % tal current capac-
Size (bits): 16 Default: ity − used by bar-
Sign: U graph
42163 Utility L2 Cur- Read Multiplier: Unit: % Utility L2 current Current
rent Percent Only .100000000000 Lower Limit: % as % of utility to-
Offset: 0 Upper Limit: % tal current capac-
Size (bits): 16 Default: ity − used by bar-
Sign: U graph
42164 Utility L3 Cur- Read Multiplier: Unit: % Utility L3 current Current
rent Percent Only .100000000000 Lower Limit: % as as % of utility
Offset: 0 Upper Limit: % total current ca-
Size (bits): 16 Default: pacity − used by
Sign: U bargraph

466
Addr. System Name Access Specifications Description Function
42165 Utility Total kW Read Multiplier: Unit: % Utility total kW as Power
Percent Only .100000000000 Lower Limit % percent of total
Offset: 0 Upper Limit: % utility capacity −
Size (bits): 16 Default: used by bargraph
Sign: S
42166 Utility Fre- Read Multiplier: Unit: % Utility frequency Frequency
quency Per- Only .100000000000 Lower Limit: % as percent of
cent Offset: 0 Upper Limit: % system frequency
Size (bits): 16 Default: − used by bar-
Sign: U graph
42167 Utility L1L2 Read Multiplier: Unit: % Utility L1L2 volt- Voltage
Voltage % Only .100000000000 Lower Limit: % age %
Offset: 0 Upper Limit: %
Size (bits): 16 Default:
Sign: U
42168 Utility L2L3 Read Multiplier: Unit: % Utility L2L3 volt- Voltage
Voltage % Only .100000000000 Lower Limit: % age %
Offset: 0 Upper Limit: %
Size (bits): 16 Default:
Sign: U
42169 Utility L3L1 Read Multiplier: Unit:% Utility L3L1 volt- Voltage
Voltage % Only .100000000000 Lower Limit: % age %
Offset: 0 Upper Limit: %
Size (bits): 16 Default:
Sign: U
42170 Utility Total kW Read Multiplier: Unit: kW Utility total kW Power
_32 bit Only 1.000000000000 Lower Limit: kW
Offset: 0 Upper Limit: kW
Size (bits): 32 Default:
Sign: S
42172 Utility total Read Multiplier: Unit: kVAR Utility total kVAR Power
kVAR_32 bit Only 1.000000000000 Lower Limit: kVAR in 32 bit
Offset: 0 Upper Limit: kVAR
Size (bits): 32 Default:
Sign: S
42174 Utility total Read Multiplier: Unit: kVA Utility total kVA Power
kVA_32 bit Only 1.000000000000 Lower Limit: kVA in 32 bit
Offset: 0 Upper Limit: kVA
Size (bits): 32 Default:
Sign: U
42176 System Total Read Multiplier: Unit: kW Sum of generator Power
kW_32 bit Only 1.000000000000 Lower Limit: kW bus and utility
Offset: 0 Upper Limit: kW bus kW in 32 bit
Size (bits): 32 Default:
Sign: S
42178 System Total Read Multiplier: Unit: kVAR Sum of generator Power
kVAR_32 bit Only 1.000000000000 Lower Limit: kVAR bus and utility
Offset: 0 Upper Limit: kVAR bus kVAR in 32
Size (bits): 32 Default: bit
Sign: S

467
Addr. System Name Access Specifications Description Function
42180 System Total Read Multiplier: Unit: kVA Sum of generator Power
kVA_32 bit Only 1.000000000000 Lower Limit: kVA set and utility bus
Offset: 0 Upper Limit: kVA kVA in 32 bit
Size (bits): 32 Default:
Sign: U
42200 Total Number Read Multiplier: Unit: NA Number of gener- System Infor-
of Gensets Only 1.000000000000 Lower Limit: ator sets with mation
Offset: 0 Upper Limit: non-zero rating
Size (bits): 16 Default: entered
Sign: U
42201 Total System Read Multiplier: Unit: kW Sum of the gen- System Infor-
Capacity Only 1.000000000000 Lower Limit: kW erator set kW rat- mation
Offset: 0 Upper Limit: kW ings
Size (bits): 16 Default:
Sign: U
42202 Total Online Read Multiplier: Unit: kW Sum of the gen- System In-
Capacity Only 1.000000000000 Lower Limit: kW erator set kW rat- formation
Offset: 0 Upper Limit: kW ings for generator
Size (bits): 16 Default: sets which are
Sign: S Online
42203 Programmed Read Multiplier: Unit: seconds Countdown value PTC Timers
Transition Tim- Only .100000000000 Lower Limit: seconds of the pro-
er Offset: 0 Upper Limit: seconds grammed transi-
Size (bits): 16 Default: tion timer
Sign: U
42204 Transfer Timer Read Multiplier: Unit: seconds Countdown value PTC Timers
Only .100000000000 Lower Limit: seconds of the transfer
Offset: 0 Upper Limit: seconds timer
Size (bits): 16 Default:
Sign: U
42205 Retransfer Read Multiplier: Unit: seconds Countdown value PTC Timers
Timer Only .100000000000 Lower Limit: seconds of the retransfer
Offset: 0 Upper Limit: seconds timer
Size (bits): 16 Default:
Sign: U
42206 Maximum Par- Read Multiplier: Unit: seconds Countdown value PTC Timers
allel Timer Only .100000000000 Lower Limit: seconds of the maximum
Offset: 0 Upper Limit: seconds parallel timer
Size (bits): 16 Default:
Sign: U
42207 kW Reference Read Multiplier: Unit: kW kW Control refer- Master Load
Only 1.000000000000 Lower Limit: kW ence value for Control
Offset: 0 Upper Limit: kW utility paralleling
Size (bits): 16 Default:
Sign: S
42208 Utility Un- Read 0: Not Available Indicates utility Master Load
loaded Status Only 1: Not Unloaded unloaded status Control
2: Unloaded
Default:

468
Addr. System Name Access Specifications Description Function
42209 Genset Un- Read 0: Not Available Indicates genera- Master Load
loaded Status Only 1: Not Unloaded tor set unloaded Control
2: Unloaded status
Default:
42210 System State Read 0: Not Available Indicates what System Infor-
Only 1: TD Start state the control mation
2: TD Stop is currently IN
3: TD Programmed Transition
4: TD Transfer
5: TD Retransfer
6: Synchronizing
7: Sync Check OK
8: Inhibit
9: Unassigned
10: Ramp Upload
11. Ramp Load
12: Manual
13: Utility Failure
14: Test
15: Standby
16: Factory Test
17: Extended Parallel
Default: Not Available
42211 PTC Operat- Read 0: Manual Indicates the PTC Operat-
ing Mode Only 1: Normal Current PTC Op- ing Mode
2: Normal Override erating mode.
3: Test Read/Write on
4: Utility Fail comp mode.
5: Extended Parallel
Default:
42212 Active Transi- Read Multiplier: Unit: seconds Countdown timer PTC Timers
tion Timer Only .100000000000 Lower Limit: seconds value of active
Offset: 0 Upper Limit: seconds timer
Size (bits): 16 Default:
Sign: U
42213 Hardware Ver- Read Multiplier: Unit: NA Indicates the Discrete In-
sion Only 1.000000000000 Lower Limit: hardware version puts
Offset: 0 Upper Limit: of the board
Size (bits): 16 Default:
Sign: U
42214 Controller On Read Multiplier: Unit: seconds Amount of time in Controller In-
Time Only 1.000000000000 Lower Limit: .000 seconds the con- formation
Offset: 0 sec. troller has been
Size (bits): 32 Upper Limit: powered
Sign: U 4294967295.000 sec
Default: 0

469
Addr. System Name Access Specifications Description Function
42216 Genset Avail- Read 0: Not Available Indicates avail- PTC Availabil-
ability Status Only 1: Available ability of genera- ity
2: Unknown tor set for Load-
Default: ing, as deter-
mined by the
generator set
sensors
42217 Utility Avail- Read 0: Not Available Indicates avail- PTC Availabil-
ability Status Only 1: Available ability of utility for ity
2: Unknown loading as deter-
Default: mined by the util-
ity sensors
42218 Gen CB Posi- Read 0: Open Generator set Breaker Con-
tion Status Only 1: Closed breaker position trol
2: Not Available
Default:
42219 Util CB Posi- Read 0: Open Utility breaker Breaker Con-
tion Status Only 1: Closed position trol
2: Not Available
Default:
42220 kVAR Load Read Multiplier: Unit: kVAR kVAR control ref- Master Load
Reference Only 1.000000000000 Lower Limit: kVAR erence value for Control
Offset: 0 Upper Limit: kVAR extended paral-
Size (bits): 16 Default: leling
Sign: S
42221 kVAR Load Read Multiplier: Unit: % Engineering units Analog Inputs
Setpoint Engr Only .010000000000 Lower Limit: % value for the
Units Display Offset: 0 Upper Limit: % kVAR load set-
Value Size (bits): 16 Default: point analog In-
Sign: U put
42222 kW Load Set- Read Multiplier: Unit: % Engineering units Analog Inputs
point Engr Only .010000000000 Lower Limit: % value for the kW
Units Display Offset: 0 Upper Limit: % load setpoint
Value Size (bits): 16 Default: analog input
Sign: S
42223 Power Factor Read Multiplier: Unit: NA Power factor set- Analog Inputs
Setpoint Only .010000000000 Lower Limit: point analog in-
Offset: 0 Upper Limit: put value (uses
Size (bits): 16 Default: kVAR load set-
Sign: S point analog in-
put)
42224 PTC State Read 0: Not Enabled Indicates the PTC State
Only 1: No Source Connected connected state Machine
2: Utility Connected of power transfer
3: Genset Connected control. read /
4: Paralleled write in comp.
Default:

470
Addr. System Name Access Specifications Description Function
42225 Sync Check Read 0: Not Allowed Indicates whether Master Sync
Close Allowed Only 1: Allowed any sync check Control
Default: conditions have
been met
42226 Sync Phase Read Multiplier: Unit: degrees Utility to genera- Phase
Difference Only .010000000000 Lower Limit: degrees tor set L1 voltage
Offset: 0 Upper Limit: degrees phase angle
Size (bits): 16 Default:
Sign: S
42227 Synchronizer Read 0: Synchronizer Off Indicates state of Master Sync
Status Only 1: Synchronizer On the synchronizer Control
Default:
42228 System Lock- Read 0: Inactive Faults have oc- System Infor-
out Status Only 1: Active curred which pre- mation
Default: vent normal sys-
tem operation;
reset faults
42229 Breaker 1 Read 0: Open Indicates the Load Add
Position Only 1: Closed position status of Shed Control
2: Not Available breaker 1
Default: Not Available
42230 Breaker 2 Read 0: Open Indicates the Load Add
Position Only 1: Closed position status of Shed Control
2: Not Available breaker 2
Default: Not Available
42231 Breaker 3 Read 0: Open Indicates the Load Add
Position Only 1: Closed position status of Shed Control
2: Not Available breaker 3
Default: Not Available
42232 Breaker 4 Read 0: Open Indicates the Load Add
Position Only 1: Closed position status of Shed Control
2: Not Available breaker 4
Default: Not Available
42233 Breaker 5 Read 0: Open Indicates the Load Add
Position Only 1: Closed position status of Shed Control
2: Not Available breaker 5
Default: Not Available
42234 Breaker 6 Read 0: Open Indicates the Load Add
Position Only 1: Closed position status of Shed Control
2: Not Available breaker 6
Default: Not Available
42235 Breaker 1 Trip Read 0: Not Available Indicates trip sta- Load Add
Status Only 1: Normal tus of breaker 1 Shed Control
2: Tripped
Default: Not Available
42236 Breaker 2 Trip Read 0: Not Available Indicates trip sta- Load Add
Status Only 1: Normal tus of breaker 2 Shed Control
2: Tripped
Default: Not Available

471
Addr. System Name Access Specifications Description Function
42237 Breaker 3 Trip Read 0: Not Available Indicates trip sta- Load Add
Status Only 1: Normal tus of breaker 3 Shed Control
2: Tripped
Default: Not Available
42238 Breaker 4 Trip Read 0: Not Available Indicates trip sta- Load Add
Status Only 1: Normal tus of breaker 4 Shed Control
2: Tripped
Default: Not Available
42239 Breaker 5 Trip Read 0: Not Available Indicates trip sta- Load Add
Status Only 1: Normal tus of breaker 5 Shed Control
2: Tripped
Default: Not Available
42240 Breaker 6 Trip Read 0: Not Available Indicates trip sta- Load Add
Status Only 1: Normal tus of breaker 6 Shed Control
2: Tripped
Default: Not Available
42241 ATS 1 Position Read 0: Not Available Indicates position Load Add
Only 1: No Source Connected status of ATS 1 Shed Control
2: Source 1 Connected
3: Source 2 Connected
4: Paralleled
Default: Not Available
42242 ATS 2 Position Read 0: Not Available Indicates position Load Add
Only 1: No Source Connected status of ATS 2 Shed Control
2: Source 1 Connected
3: Source 2 Connected
4: Paralleled
Default: Not Available
42243 ATS 3 Position Read 0: Not Available Indicates position Load Add
Only 1: No Source Connected status of ATS 3 Shed Control
2: Source 1 Connected
3: Source 2 Connected
4: ParalleledDefault: Not Available
42244 ATS 4 Position Read 0: Not Available Indicates position Load Add
Only 1: No Source Connected status of ATS 4 Shed Control
2: Source 1 Connected
3: Source 2 Connected
4: Paralleled
Default: Not Available
42245 ATS 5 Position Read 0: Not Available Indicates position Load Add
Only 1: No Source Connected status of ATS 5 Shed Control
2: Source 1 Connected
3: Source 2 Connected
4: Paralleled
Default: Not Available

472
Addr. System Name Access Specifications Description Function
42246 Position Read 0: Not Available Indicates position Load Add
Only 1: No Source Connected status of ATS 6 Shed Control
2: Source 1 Connected
3: Source 2 Connected
4: Paralleled
Default: Not Available

42247 SID1 Status Read 0: Missing Indicates status Communica-


Only 1: Good of SID1 (AUX tions
2: Connecting 101 / 102 module
3: No EXP Board 1)
4: Not Applicable
Default:

42248 SID0 Status Read 0: Missing Indicates status Communica-


Only 1: Good of SID0 (AUX tions
2: Connecting 101 / 102 module
3: No EXP Board 0)
4: Not Applicable
Default:

42249 Expansion Read 0: Disable Indicates the sta- Communica-


Board Com- Only 1: Enable tus of SIDO to tions
munications Default: Disable expansion board
connection

42250 Current Add Read Multiplier: Unit: NA Indicates the next Load Add
Level Only 1.000000000000 Lower Limit: level to add Shed Control
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42251 Current Shed Read Multiplier: Unit: NA Indicates the next Load Add
Level Only 1.000000000000 Lower Limit: level to shed Shed Control
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42252 Add Level 1 Read 0: Do Nothing Indicates status Load Add
Command Only 1: Add Level of add level 1 Shed Control
Default: Do Nothing

42253 Add Level 2 Read 0: Do Nothing Indicates status Load Add


Command Only 1: Add Level of add level 2 Shed Control
Default: Do Nothing

42254 Add Level 3 Read 0: Do Nothing Indicates status Load Add


Command Only 1: Add Level of add level 3 Shed Control
Default: Do Nothing

42255 Add Level 4 Read 0: Do Nothing Indicates status Load Add


Command Only 1: Add Level of add level 4 Shed Control
Default: Do Nothing

42256 Add Level 5 Read 0: Do Nothing Indicates status Load Add


Command Only 1: Add Level of add level 5 Shed Control
Default: Do Nothing

473
Addr. System Name Access Specifications Description Function
42257 Add Level 6 Read 0: Do Nothing Indicates status Load Add
Command Only 1: Add Level of add level 6 Shed Control
Default: Do Nothing
42258 Shed Level 1 Read 0: Do Nothing Indicates status Load Add
Command Only 1: Add Level of shed level 1 Shed Control
Default: Do Nothing
42259 Shed Level 2 Read 0: Do Nothing Indicates status Load Add
Command Only 1: Add Level of shed level 2 Shed Control
Default: Do Nothing
42260 Shed Level 3 Read 0: Do Nothing Indicates status Load Add
Command Only 1: Add Level of shed level 3 Shed Control
Default: Do Nothing
42261 Shed Level 4 Read 0: Do Nothing Indicates status Load Add
Command Only 1: Add Level of shed level 4 Shed Control
Default: Do Nothing
42262 Shed Level 5 Read 0: Do Nothing Indicates status Load Add
Command Only 1: Add Level of shed level 5 Shed Control
Default: Do Nothing
42263 Manual Add Read 0: Do Nothing Operator input to Load Add
Level 1 Com- Only 1: Add Level add level 1 Shed Control
mand Default: Do Nothing
42264 Manual Add Read 0: Do Nothing Operator input to Load Add
Level 2 Com- Only 1: Add Level add level 2 Shed Control
mand Default: Do Nothing
42265 Manual Add Read 0: Do Nothing Operator input to Load Add
Level 3 Com- Only 1: Add Level add level 3 Shed Control
mand Default: Do Nothing
42266 Manual Add Read 0: Do Nothing Operator input to Load Add
Level 4 Com- Only 1: Add Level add level 4 Shed Control
mand Default: Do Nothing
42267 Manual Add Read 0: Do Nothing Operator input to Load Add
Level 5 Com- Only 1: Add Level add level 5 Shed Control
mand Default: Do Nothing
42268 Manual Add Read 0: Do Nothing Operator input to Load Add
Level 6 Com- Only 1: Add Level add level 6 Shed Control
mand Default: Do Nothing
42269 Manual Shed Read 0: Do Nothing Operator input to Load Add
Level 1 Com- Only 1: Add Level shed loads as- Shed Control
mand Default: Do Nothing signed to level 1
42270 Manual Shed Read 0: Do Nothing Operator input to Load Add
Level 2 Com- Only 1: Add Level shed loads as- Shed Control
mand Default: Do Nothing signed to level 2
42271 Manual Shed Read 0: Do Nothing Operator input to Load Add
Level 3 Com- Only 1: Add Level shed loads as- Shed Control
mand Default: Do Nothing signed to level 3
42272 Manual Shed Read 0: Do Nothing Operator input to Load Add
Level 4 Com- Only 1: Add Level shed loads as- Shed Control
mand Default: Do Nothing signed to level 4

474
Addr. System Name Access Specifications Description Function
42273 Manual Shed Read 0: Do Nothing Operator Input to Load Add
Level 5 Com- Only 1: Add Level Shed Loads As- Shed Control
mand Default: Do Nothing signed to Level 5
42274 Restored Read 0: Do Nothing Indicates if shed Load Add
Shed Level 1 Only 1: Add Level level 1 has been Shed Control
Command Default: Do Nothing restored
42275 Restored Read 0: Do Nothing Indicates if shed Load Add
Shed Level 2 Only 1: Add Level level 2 has been Shed Control
Command Default: Do Nothing restored

42276 Restored Read 0: Do Nothing Indicates if shed Load Add


Shed Level 3 Only 1: Add Level level 3 has been Shed Control
Command Default: Do Nothing restored

42277 Restored Read 0: Do Nothing Indicates if shed Load Add


Shed Level 4 Only 1: Add Level level 4 has been Shed Control
Command Default: Do Nothing restored
42278 Restored Read 0: Do Nothing Indicates if shed Load Add
Shed Level 5 Only 1: Add Level level 5 has been Shed Control
Command Default: Do Nothing restored

42279 Add Load 1 Read 0: Do Nothing Indicates add Load Add


Command Only 1: Add Level command for Shed Control
Default: Do Nothing load 1
42280 Add Load 2 Read 0: Do Nothing Indicates add Load Add
Command Only 1: Add Level command for Shed Control
Default: Do Nothing load 2
42281 Add Load 3 Read 0: Do Nothing Indicates add Load Add
Command Only 1: Add Level command for Shed Control
Default: Do Nothing load 3

42282 Add Load 4 Read 0: Do Nothing Indicates add Load Add


Command Only 1: Add Level command for Shed Control
Default: Do Nothing load 4.

42283 Add Load 5 Read 0: Do Nothing Indicates add Load Add


Command Only 1: Add Level command for Shed Control
Default: Do Nothing load 5
42284 Add Load 6 Read 0: Do Nothing Indicates add Load Add
Command Only 1: Add Level command for Shed Control
Default: Do Nothing load 6
42285 Shed Load 1 Read 0: Do Nothing Indicates shed Load Add
Command Only 1: Add Level command for Shed Control
Default: Do Nothing load 1
42286 Shed Load 2 Read 0: Do Nothing Indicates shed Load Add
Command Only 1: Add Level command for Shed Control
Default: Do Nothing load 2

475
Addr. System Name Access Specifications Description Function
42287 Shed Load 3 Read 0: Do Nothing Indicates shed Load Add
Command Only 1: Add Level command for Shed Control
Default: Do Nothing load 3
42288 Shed Load 4 Read 0: Do Nothing Indicates Shed Load Add
Command Only 1: Add Level Command for Shed Control
Default: Do Nothing Load 4
42289 Shed Load 5 Read 0: Do Nothing Indicates shed Load Add
Command Only 1: Add Level command for Shed Control
Default: Do Nothing load 5

42290 Shed Load 6 Read 0: Do Nothing Indicates shed Load Add


Command Only 1: Add Level command for Shed Control
Default: Do Nothing load 6
42291 Battery Volt- Read Multiplier: Unit: VDC Engineering units Analog Inputs
age Engr Units Only .010000000000 Lower Limit: VDC value for the bat-
Display Value Offset: 0 Upper Limit: VDC tery voltage ana-
Size (bits): 16 Default log Input
Sign: U
42292 kVAR Master Read Multiplier: Unit: VDC Voltage level Analog Inputs
Load Control Only .010000000000 Lower Limit: VDC commanded to
Output Predic- Offset: 0 Upper Limit: VDC kVAR master
tor Value Size (bits): 16 Default load control ana-
Sign: S log output
42293 kW Master Read Multiplier: Unit: VDC Voltage level Analog Inputs
Load Control Only .010000000000 Lower Limit: VDC commanded to
Output Predic- Offset: 0 Upper Limit: VDC kW master load
tor Value Size (bits): 16 Default control analog
Sign: S output
42294 Master Fre- Read Multiplier: Unit: VDC Voltage level Analog Inputs
quency Bias Only .010000000000 Lower Limit: VDC commanded to
Output Predic- Offset: 0 Upper Limit: VDC master frequency
tor Value Size (bits): 16 Default bias analog out-
Sign: S put
42295 Master Volt- Read Multiplier: Unit: VDC Voltage level Analog Inputs
age Bias Out- Only .010000000000 Lower Limit: VDC commanded to
put Predictor Offset: 0 Upper Limit: VDC master voltage
Value Size (bits): 16 Default bias analog out-
Sign: S put
42296 PTC Genset Read 0: Manual Indicates the cur- PTC Genset
Operating Only 1: Normal rent operating Operating
Mode 2: Normal Override mode of the gen- Mode
3: Test erator set
4: Utility Fail
5: Extended Parallel
Default

476
Addr. System Name Access Specifications Description Function
42297 PTC Transfer Read 0: Manual Indicates the cur- PTC Genset
Pair Operating Only 1: Normal rent operating Operating Mo-
Mode 2: Normal Override mode of the de
3: Test transfer pair
4: Utility Fail
5: Extended Parallel
Default:
42298 PTC Operat- Read 0: Open Transition Indicates the PTC Genset
ing Transition Only 1: Hard Closed Transition transition type Operating Mo-
Type 2: Soft Closed Transition currently applica- de
Default: ble to the PTC
function opera-
tion

42299 Expansion Read 0: Disabled Indicates the sta- Communica-


Board Com- Only 1: Enabled tus of the SID1 to tions
munications 1 Default: Disabled expansion board
connection
42300 System Topol- Read/ 0: Master Synchronize Only Main setting: sets Application
ogy Write 1: Isolated Bus w/ out GM system topology; Configuration
2: Isolated Bus w/GM control must be
3: Common Bus in manual to set
4: Transfer Pair
5: Component Mode
Default: Master Synchronize Only
42301 Transition Read/ 0: Open Transition Sets the type of Application
Type Write 1: Hard Closed Transition transition that Configuration
2: Soft Closed Transition will be used
Default: Open Transition
42302 Extended Par- Read/ 0: Disabled Use to enable ex- Application
allel Enable Write 1: Enabled tended parallel- Configuration
Default: Disabled ing operation
42303 Load Demand Read/ 0: None Sets the load de- Load Demand
Type Write 1: Fixed Sequence mand type Control
2: Run Hours
Default: None
42304 Priority Control Read/ 0: Manual Set the priority Priority Con-
Method Write 1: Automatic control method trol
Default: Manual
42305 Genset 01 kW Read/ Multiplier: Unit: kW Sets generator 1 System Infor-
Rating Write 1.000000000000 Lower Limit: .000 kW kW rating mation
Offset: 0 Upper Limit:
Size (bits): 16 32000.000 kW
Sign: S Default: 1000
42306 Genset 02 kW Read/ Multiplier: Unit: kW Sets generator 2 System In-
Rating Write 1.000000000000 Lower Limit: .000 kW kW rating formation
Offset: 0 Upper Limit:
Size (bits): 16 32000.000 kW
Sign: S Default: 0

477
Addr. System Name Access Specifications Description Function
42307 Genset 03 kW Read/ Multiplier: Unit: kW Sets generator 3 System In-
Rating Write 1.000000000000 Lower Limit: .000 kW kW rating formation
Offset: 0 Upper Limit:
Size (bits): 16 32000.000 kW
Sign: S Default: 0
42308 Genset 04 kW Read/ Multiplier: Unit: kW Sets generator 4 PC 3.x
Rating Write 1.000000000000 Lower Limit: .000 kW kW rating
Offset: 0 Upper Limit:
Size (bits): 16 32000.000 kW
Sign: S Default: 0
42309 Genset 05 kW Read/ Multiplier: Unit: kW Sets generator 5 System In-
Rating Write 1.000000000000 Lower Limit: .000 kW kW rating formation
Offset: 0 Upper Limit:
Size (bits): 16 32000.000 kW
Sign: S Default: 0
42310 Genset 06 kW Read/ Multiplier: Unit: kW Sets generator 6 System In-
Rating Write 1.000000000000 Lower Limit: .000 kW kW rating formation
Offset: 0 Upper Limit:
Size (bits): 16 32000.000 kW
Sign: S Default: 0

42311 Genset 07 kW Read/ Multiplier: Unit: kW Sets generator 7 System In-


Rating Write 1.000000000000 Lower Limit: .000 kW kW rating formation
Offset: 0 Upper Limit:
Size (bits): 16 32000.000 kW
Sign: S Default: 0
42312 Genset 08 kW Read/ Multiplier: Unit: kW Sets generator 8 System In-
Rating Write 1.000000000000 Lower Limit: .000 kW kW rating formation
Offset: 0 Upper Limit:
Size (bits): 16 32000.000 kW
Sign: S Default: 0
42313 Genset 09 kW Read/ Multiplier: Unit: kW Sets generator 9 System In-
Rating Write 1.000000000000 Lower Limit: .000 kW kW rating formation
Offset: 0 Upper Limit:
Size (bits): 16 32000.000 kW
Sign: S Default: 0
42314 Genset 10 kW Read/ Multiplier: Unit: kW Sets generator System In-
Rating Write 1.000000000000 Lower Limit: .000 kW 10 kW rating formation
Offset: 0 Upper Limit:
Size (bits): 16 32000.000 kW
Sign: S Default: 0
42315 Genset 11 kW Read/ Multiplier: Unit: kW Sets generator 11 System In-
Rating Write 1.000000000000 Lower Limit: .000 kW kW rating formation
Offset: 0 Upper Limit:
Size (bits): 16 32000.000 kW
Sign: S Default: 0

478
Addr. System Name Access Specifications Description Function
42316 Genset 12 kW Read/ Multiplier: Unit: kW Sets generator System Infor-
Rating Write 1.000000000000 Lower Limit: .000 kW 12 kW rating mation
Offset: 0 Upper Limit:
Size (bits): 16 32000.000 kW
Sign: S Default: 0
42317 Programmed Read/ Multiplier: Unit: Seconds Set the pro- PTC Timers
Transition Write .100000000000 Lower Limit: .000 grammed transi-
Delay (TDPT) Offset: 0 Seconds tion time delay
Size (bits): 16 Upper Limit: 60.000
Sign: U Seconds
Default: 3
42318 Transfer Delay Read/ Multiplier: Unit: Seconds Sets the transfer PTC Timers
(TDNE) Write .100000000000 Lower Limit: .000 time delay
Offset: 0 Seconds
Size (bits): 16 Upper Limit: 120.000
Sign: U Seconds
Default: 10
42319 Retransfer Read/ Multiplier: Unit: Seconds Sets the transfer PTC Timers
Delay (TDEN) Write .100000000000 Lower Limit: .000 time delay
Offset: 0 Seconds
Size (bits): 16 Upper Limit:
Sign: U 1800.000 Seconds
Default: 600
42320 Maximum Par- Read/ Multiplier: Unit: Seconds Sets the maxi- PTC Timers
allel Time Write .100000000000 Lower Limit: .000 mum parallel
(TDMP) Offset: 0 Seconds time for soft load
Size (bits): 16 Upper Limit: transfers
Sign: U 1800.000 Seconds
Default: 20
42321 Genset Bus Read/ Multiplier: Unit: % Generator set Master Load
%kW Setpoint Write .010000000000 Lower Limit: nominal voltage Control
Offset: 0 −5.000%
Size (bits): 16 Upper Limit:
Sign: S 105.000%
Default: 80
42322 Genset Nomi- Read/ Multiplier: Unit: Volts Generator set AC Setup
nal Voltage Write 1.000000000000 Lower Limit: 100.000 nominal voltage
Offset: 0 Volts
Size (bits): 16 Upper Limit:
Sign: U 45000.000 Volts
Default: 480
42323 Utility Nominal Read/ Multiplier: Unit: Volts Utility nominal AC Setup
Voltage Write 1.000000000000 Lower Limit: 100.000 voltage
Offset: 0 Volts
Size (bits): 16 Upper Limit:
Sign: U 45000.000 Volts
Default: 480

479
Addr. System Name Access Specifications Description Function
42324 Genset Center Read/ Multiplier: Unit: Hz Sets the center PTC Sensors
Frequency Write .100000000000 Lower Limit: 45.000 frequency sensor
Offset: 0 Hz bandwidth set-
Size (bits): 16 Upper Limit: 65.000 tings
Sign: U Hz
Default: 60
42325 Utility Center Read/ Multiplier: Unit: Hz Sets the center PTC Sensors
Frequency Write .100000000000 Lower Limit: 45.000 frequency sensor
Offset: 0 Hz bandwidth set-
Size (bits): 16 Upper Limit: 65.000 tings
Sign: U Hz
Default: 60
42326 test With Load Read/ 0: Disable Use to enable or Application
Enable Write 1: Enable disable load Configuration
Default: Disable transfer durning a
Test
42327 System Fre- Read/ Multiplier: Unit: Hz Use to define the System Infor-
quency Write .100000000000 Lower Limit: 45.000 system nominal mation
Offset: 0 Hz frequency
Size (bits): 16 Upper Limit: 65.000
Sign: U Hz
Default: 60
42328 Genset Bus Read/ 0: Internal Selects where Master Load
kW Setpoint Write 1: Analog Input the generator set Control
Source Default Internal kW setpoint will
come from for ex-
tended parallel-
ing
42329 Genset Bus Read/ 0: Internal Selects where Master Load
kVAR Setpoint Write 1: Analog Input the generator set Control
Source Default Internal kVAR setpoint
will come from for
extended paral-
leling
42330 Genset Bus Read/ Multiplier: Unit: kW Set the base load Master Load
kW Setpoint Write 1.000000000000 Lower Limit: .000 kW kW setpoint in Control
Offset: 0 Upper Limit: closed loop ex-
Size (bits): 16 32767.000 kW tended parallel-
Sign: S Default: 0 ing
42331 Genset Bus Read/ Multiplier: Unit: kVAR Sets the base Master Load
kVAR Setpoint Write 1.000000000000 Lower Limit: .000 load kVAR set- Control
Offset: 0 kVAR point in closed
Size (bits): 16 Upper Limit: loop extended
Sign: S 32767.000 kVAR paralleling
Default: 0

480
Addr. System Name Access Specifications Description Function
42332 Genset Bus % Read/ Multiplier: Unit: % Sets % kVAR Master Load
kVAR Setpoint Write .010000000000 Lower Limit: generator output Control
Offset: 0 −5.000% level for open
Size (bits): 16 Upper Limit: loop base load
Sign: S 105.000% extended paral-
Default: 0 leling
42333 Genset Bus Read/ Multiplier: Unit: NA Sets the desired Master Load
Power Factor Write .010000000000 Lower Limit: .700 generator set bus Control
Setpoint Offset: 0 Upper Limit: 1.000 power factor in
Size (bits): 16 Default: 1.00 closed loop ex-
Sign: S tended parallel-
ing
42334 Genset Un- Read/ Multiplier: Unit: kW Setpoint for gen- Master Load
loaded Level Write 1.000000000000 Lower Limit: erator set un- Control
Offset: 0 −32768.000kW loaded level
Size (bits): 16 Upper Limit:
Sign: S 32767.000 kW
Default: 50
42335 Utility Bus kW Read/ 0: Internal Selects where Master Load
Setpoint Write 1: Analog Input the utility kW set- Control
Source Default: Internal point will come
from for extended
paralleling
42336 Utility Bus Read/ 0: Internal Selects where Master Load
kVAR Setpoint Write 1: Analog Input the utility kVAR Control
Source Default: Internal setpoint will
come from for
extended paralle-
ling
42337 Utility Bus kW Read/ Multiplier: Unit: kW Sets the peak Master Load
Setpoint Write 1.000000000000 Lower Limit: Shave kW set- Control
Offset: 0 −32768.000kW point in closed
Size (bits): 16 Upper Limit: loop extended
Sign: S 32767.000 kW paralleling
Default: 100
42338 Utility Bus kW Read/ Multiplier: Unit: kW Sets the utility Master Load
Constraint Write 1.000000000000 Lower Limit: kW constraint Control
Level Offset: 0 −32768.000kW level for base
Size (bits): 16 Upper Limit: load extended
Sign: S 32767.000 kW paralleling
Default: 100
42339 Utility Bus Read/ Multiplier: Unit: kW Sets the peak Master Load
kVAR Setpoint Write 1.000000000000 Lower Limit: shave kVAR set- Control
Offset: 0 −32768.000 kVAR point in closed
Size (bits): 16 Upper Limit: loop extended
Sign: S 32767.000 kVAR paralleling
Default: 100

481
Addr. System Name Access Specifications Description Function
42340 Utility Bus Read/ Multiplier: Unit: NA Sets the desired Master Load
Power Factor Write .010000000000 Lower Limit: .700 utility bus power Control
Setpoint Offset: 0 Upper Limit: 1.000 factor in loop ex-
Size (bits): 16 Default: 1.00 tended parallel-
Sign: S ing
42341 Utility Un- Read/ Multiplier: Unit: kW Setpoint for utility Master Load
loaded Level Write 1.000000000000 Lower Limit: unloaded level Control
Offset: 0 −32768.000kW
Size (bits): 16 Upper Limit:
Sign: S 32767.000 kW
Default: 50
42342 Clear Fault Read/ 0: Inactive Use to complete- Fault and
History Table Write 1: Active ly clear the fault Event Info
Default: Inactive history table

42343 Clear Occur- Read/ 0: Inactive Use to complete- Fault and


rence Tables Write 1: Active ly clear the Event Info
Default: Inactive counters in faults
and events oc-
currence tables
42344 Genset Reset Read/ 0: Do Nothing Use to perma- Energy
All Energy Me- Write 1: Clear Counters nently clear all
ters Default: Do Nothing generator set en-
ergy meter val-
ues

42345 Utility Reset Read/ 0: Do Nothing Use to perma- Energy


All Energy Me- Write 1: Clear Counters nently clear all
ters Default: Do Nothing utility energy me-
ter values
42346 Extended Par- Read/ 0: Genset Bus % Level (Open Loop) Sets how and Master Load
alleling kW Write 1: Genset Bus kW (Closed Loop) where the kW will Control
Load Control 2: Genset Bus kW w/ Utility Constraint be controlled for
Type (Closed Loop) extended parallel
3: Utility Bus kW (Closed Loop) operation
Default: Genset Bus % Level (Open Loop)
42347 Extended Par- Read/ 0: Genset Controllers Sets how and Master Load
alleling kVAR Write 1: Genset Bus % Level (Open Loop) where the kVAR Control
Load Control 2: Genset Bus Power Factor (Open Loop) will be controlled
Type 3: Genset Bus kVAR (Closed Loop) for extended par-
4: Genset Bus Power Factor (Closed Loop) allel operation
5: Utility Bus kVAR (Closed Loop)
6: Utility Bus Power Factor (Closed Loop)
Default: Genset Controllers
42348 Extended Par- Read/ Multiplier: Unit: seconds Set ramp load Master Load
allel Ramp Write .10000000000 Lower Limit: 10.000 time for extended Control
Load Time Offset: 0 seconds paralleling
Size (bits): 16 Upper Limit: 900.000
Sign: U seconds
Default:60

482
Addr. System Name Access Specifications Description Function
42349 Fail To Sync Read/ 0:Disabled Enable if want Master Sync
Lockout En- Write 1:Enabled synchronizing to Control
able Default:Disable stop if fail to sync
occurs

42350 Fail To Sync Read/ 0:Disabled Use to enable or PTC State


Open Transi- Write 1:Enabled disable an open Machine
tion Retransfer Default:Disable transition retran-
Enable sfer upon fail to
sync

42351 Fail To Syn- Read/ Multiplier: Unit: seconds Set the fill to syn- Master Sync
chronize Time Write .200000000000 Lower Limit: 10.000 chronize diag- Control
Offset: 0 seconds nostic time delay
Size (bits): 16 Upper Limit: 900.000
Sign: U seconds
Default:120

42352 Gen CB Read/ 0: Closed Requested In manual mode Breaker Con-


Manual Con- Write 1: No Command can be used to trol
trol 2: Open Commanded semi−manually
Default: No Command control the gener-
ator set breaker

42353 Util CB Manu- Read/ 0: Closed Requested In Manual Mode Breaker Con-
al Control Write 1: No Command can be used to trol
2: Open Commanded Semi−Manually
Default: No Command Control the Utility
Breaker

42354 Slip Frequen- Read/ Multiplier: Unit: seconds Sets the Syn- Master Sync
cy Write .001000000000 Lower Limit: −3.000 chronizer Slip Control
Offset: 0 Hz Frequency (used
Size (bits): 16 Upper Limit: 3.000 when Sync Meth-
Sign: S Hz od is Slip)
Default:0.1

42355 Start Time Read/ Multiplier: Unit: seconds Sets the genera- PTC Operat-
Delay (TDES) Write .100000000000 Lower Limit: .000 tor set Start Time ing Mode
Offset: 0 seconds Delay
Size (bits): 16 Upper Limit:
Sign: U 3600.000 seconds
Default: 0

42356 Stop Time Read/ Multiplier: Unit: seconds Sets the genera- PTC Operat-
Delay (TDEC) Write .100000000000 Lower Limit: .000 tor set Stop Time ing Mode
Offset: 0 seconds Delay
Size (bits): 16 Upper Limit:
Sign: U 3600.000 seconds
Default: 0

42357 Synchronizer Read/ 0: Normal Use to Invert Master Sync


Polarity Write 1: Invert Synchronizer Po- Control
Default: Normal larity

483
Addr. System Name Access Specifications Description Function
42358 Synchronize Read/ 0: Phase Match Sets the synchro- Master Sync
Method Write 1: Slip Frequency nizing method Control
Default: Phase Match

42359 Port Protocol Read/ 0: PCCNet Allows protocol of Communica-


Selection Write 1: MON the PCCNet port tions
Default: PCCNet to be changed to
MON for trouble-
shooting
42360 System Read/ 0: Disabled Use to enable or System
Scheduler En- Write 1: Enabled disable the sys- Scheduler
able Default: Disabled tem scheduler

42361 Load Add Read/ 0: Disabled Use the enable Load Add
Shed Enable Write 1: Enabled or disable the Shed Control
Default: Disabled load add shed
feature
42362 Open Transi- Read/ 0: Disabled Use to enable or Load Add
tion Retransfer Write 1: Enabled disable the shed- Shed Control
Load Shed Default: Disabled ding of loads dur-
Enable ing open transi-
tion retransfer
42363 Auto/Manual Read/ 0: Auto Indicates auto- Load Add
Load Add Re- Write 1: Manual matic or manual Shed Control
store Mode Default: Auto load add restore
operation
42364 Genset Bus Read/ Multiplier: Unit: second Indicates delay Load Add
Load Add Write 1.000000000000 Lower Limit: .000 between add lev- Shed Control
Delay Offset: 0 second els when all gen-
Size (bits): 16 Upper Limit: 60.000 erator sets are
Sign: U second online and no
Default: 1 utility
42365 Utility Bus Read/ Multiplier: Unit: second Indicates delay Load Add
Load Add Write 1.000000000000 Lower Limit: .000 between add lev- Shed Control
Delay Offset: 0 second els when on util-
Size (bits): 16 Upper Limit: 60.000 ity
Sign: U second
Default: 1
42366 Load Shed Read/ Multiplier: Unit: seconds Indicates delay Load Add
Delay Write 1.000000000000 Lower Limit: 1.000 between shed Shed Control
Offset: 0 seconds levels when on
Size (bits): 16 Upper Limit: 10.000 generator sets
Sign: U seconds
Default: 1
42367 Load 1 Device Read/ 0: None Indicates type of Load Add
Type Write 1: Breaker load connected Shed Control
2: ATS to load 1 add
Default: None shed control and
status I/O

484
Addr. System Name Access Specifications Description Function
42368 Load 2 Device Read/ 0: None Indicates type of Load Add
Type Write 1: Breaker load connected Shed Control
2: ATS to load 2 add
Default: None shed control and
status I/O
42369 Load 3 Device Read/ 0: None Indicates type of Load Add
Type Write 1: Breaker load connected Shed Control
2: ATS to load 3 add
Default: None shed control and
status I/O
42370 Load 4 Device Read/ 0: None Indicates type of Load Add
Type Write 1: Breaker load connected Shed Control
2: ATS to load 4 add
Default: None shed control and
status I/O
42371 Load 5 Device Read/ 0: None Indicates type of Load Add
Type Write 1: Breaker load connected Shed Control
2: ATS to load 5 add
Default: None shed control and
status I/O
42372 Load 6 Device Read/ 0: None Indicates type of Load Add
Type Write 1: Breaker load connected Shed Control
2: ATS to load 6 add
Default: None shed control and
status I/O
42373 Load 1 Add Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 add level load 1 Shed Control
Offset: 0 Upper Limit: 18.000 is assigned to
Size (bits): 16 Default: 1
Sign: U
42374 Load 2 Add Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 add level load 2 Shed Control
Offset: 0 Upper Limit: 18.000 is assigned to
Size (bits): 16 Default: 2
Sign: U
42375 Load 3 Add Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 add level load 3 Shed Control
Offset: 0 Upper Limit: 18.000 is assigned to
Size (bits): 16 Default: 3
Sign: U
42376 Load 4 Add Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 add level load 4 Shed Control
Offset: 0 Upper Limit: 18.000 is assigned to
Size (bits): 16 Default: 4
Sign: U
42377 Load 5 Add Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 add level load 5 Shed Control
Offset: 0 Upper Limit: 18.000 is assigned to
Size (bits): 16 Default: 5
Sign: U

485
Addr. System Name Access Specifications Description Function
42378 Load 6 Add Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 add level load 6 Shed Control
Offset: 0 Upper Limit: 18.000 is assigned to
Size (bits): 16 Default: 6
Sign: U
42379 Load 1 Shed Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 shed level load 1 Shed Control
Offset: 0 Upper Limit: 17.000 is assigned to
Size (bits): 16 Default: 1
Sign: U
42380 Load 2 Shed Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 shed level load 2 Shed Control
Offset: 0 Upper Limit: 17.000 is assigned to
Size (bits): 16 Default: 2
Sign: U
42381 Load 3 Shed Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 shed level load 3 Shed Control
Offset: 0 Upper Limit: 17.000 is assigned to
Size (bits): 16 Default: 3
Sign: U
42382 Load 4 Shed Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 shed level load 4 Shed Control
Offset: 0 Upper Limit: 17.000 is assigned to
Size (bits): 16 Default: 4
Sign: U
42383 Load 5 Shed Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 shed level load 5 Shed Control
Offset: 0 Upper Limit: 17.000 is assigned to
Size (bits): 16 Default: 5
Sign: U
42384 Load 6 Shed Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 shed level load 6 Shed Control
Offset: 0 Upper Limit: 17.000 is assigned to
Size (bits): 16 Default: 6
Sign: U
42385 Genset Bus Read/ 0: Both kW and Frequency Use to choose System In-
Overload Write 1: kW Only method for deter- formation
Method 2: Frequency Only mining generator
Default: Both kW and Frequency bus overload
condition
42386 Genset Bus Read/ Multiplier: Unit: % Use to set the % System In-
kW Overload Write 1.000000000000 Lower Limit: kW threshold for formation
Delay Offset: 0 80.000% generator bus
Size (bits): 16 Upper Limit: overload condi-
Sign: U 140.000% tion
Default: 105

486
Addr. System Name Access Specifications Description Function
42387 Genset Bus Read/ Multiplier: Unit: second Sets the delay System In-
kW Overload Write 1.000000000000 Lower Limit: .000 time for overload formation
Delay Offset: 0 second based on kW
Size (bits): 16 Upper Limit: 120.000
Sign: U second
Default: 60
42388 Genset Bus Read/ Multiplier: Unit: Hz Use to set the System In-
Underfrequen- Write 1.000000000000 Lower Limit: .1000 underfrequency formation
cy Overload Offset: 0 Hz offset threshold
Threshold Size (bits): 16 Upper Limit: 10.000 for generator bus
Sign: U Hz overload condi-
Default: 3 tion
42389 Genset Bus Read/ Multiplier: Unit: second Sets the delay System Infor-
Underfrequen- Write 1.000000000000 Lower Limit:.000 sec- time for overload mation
cy Overload Offset: 0 ond based on fre-
Delay Size (bits): 16 Upper Limit: 20.000 quency
Sign: U second
Default: 3
42390 Load Demand Read/ 0: Disable Use enable or Load Demand
Enable Write 1: Enable disable the load Control
Default: Disable demand feature
42391 Load Demand Read/ 0: Gen1 Sets GenA (nev- Load Demand
GenA Write 1: Gen2 er stop) for fixed Control
2: Gen3 sequence load
3: Gen4 demand
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen1

487
Addr. System Name Access Specifications Description Function
42392 Load Demand Read/ 0: Gen1 Sets GenB (nev- Load Demand
GenB Write 1: Gen2 er stop) for fixed Control
2: Gen3 sequence load
3: Gen4 demand
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen2

42393 Load Demand Read/ 0: Gen1 Sets GenC (nev- Load Demand
GenC Write 1: Gen2 er stop) for fixed Control
2: Gen3 sequence load
3: Gen4 demand
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen3

42394 Load Demand Read/ 0: Gen1 Sets GenD (nev- Load Demand
GenD Write 1: Gen2 er stop) for fixed Control
2: Gen3 sequence load
3: Gen4 demand
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen4

488
Addr. System Name Access Specifications Description Function
42395 Load Demand Read/ Multiplier: Unit: minute Sets the Initial Load Demand
Initial Delay Write 1.000000000000 Lower Limit: 1.000 delay time before Control
Offset: 0 minute load demand will
Size (bits): 16 Upper Limit: 60.000 operate
Sign: U minute
Default: 5

42396 Load Demand Read/ Multiplier: Unit: % Sets load de- Load Demand
Restart Per- Write 1.000000000000 Lower Limit: mand restart Control
cent Offset: 0 20.000% threshold when
Size (bits): 16 Upper Limit: method is %kW
Sign: U 100.000%
Default: 80

42397 Load Demand Read/ Multiplier: Unit: Hours Sets run hours Load Demand
Run Hours Dif- Write 1.000000000000 Lower Limit: 1.000 differential for re- Control
ferential Offset: 0 Hours start a generator
Size (bits): 16 Upper Limit: 500.000 set stopped due
Sign: U Hours to load demand
Default: 50

42398 Load Demand Read/ Multiplier: Unit: minute Sets the delay Load Demand
Shutdown De- Write 1.000000000000 Lower Limit: 1.000 time between Control
lay Offset: 0 minute stopping genera-
Size (bits): 16 Upper Limit: 60.000 tor sets due to
Sign: U minute load demand
Default: 5

42399 Load Demand Read/ Multiplier: Unit: % Sets load de- Load Demand
Shutdown Per- Write 1.000000000000 Lower Limit: 20.000 mand shutdown Control
cent Offset: 0 % threshold when
Size (bits): 16 Upper Limit: 100.000 method is %kW
Sign: U %
Default: 60

42400 General Fail Read/ Multiplier: Unit: seconds Sets how long to Load Demand
Time Delay Write 1.000000000000 Lower Limit: 10.000 wait for a genera- Control
Offset: 0 seconds tor set to come
Size (bits): 16 Upper Limit: 900.000 online before de-
Sign: U second claring it failed
Default: 59

42401 Util CB Fail to Read/ Multiplier: Unit: seconds Sets the utility Breaker Con-
Close Delay Write .020000000000 Lower Limit: .100 breaker fail to trol
Offset: 0 seconds close time delay
Size (bits): 16 Upper Limit: 1.000
Sign: U seconds
Default: 0.26

42402 Util CB Fail to Read/ Multiplier: Unit: seconds Sets the utility Breaker Con-
Open Delay Write .200000000000 Lower Limit: .200 breaker fail to trol
Offset: 0 seconds open time delay
Size (bits): 16 Upper Limit: 5.000
Sign: U seconds
Default: 1

489
Addr. System Name Access Specifications Description Function
42403 Util CB Re- Read/ Multiplier: Unit: seconds Sets time to allow Breaker Con-
charge Delay Write .020000000000 Lower Limit: .000 for utility breaker trol
Offset: 0 seconds recharge
Size (bits): 16 Upper Limit: 60.000
Sign: U seconds
Default: 10
42404 Gen CB Fail to Read/ Multiplier: Unit: seconds Sets the genera- Breaker Con-
Close Delay Write .020000000000 Lower Limit: .100 se- tor Set breaker trol
Offset: 0 conds fail to close time
Size (bits): 16 Upper Limit: 1.000 delay
Sign: S seconds
Default: 0.26
42405 Gen CB Fail to Read/ Multiplier: Unit: seconds Sets generator Breaker Con-
Open Delay Write .200000000000 Lower Limit: .200 set breaker fail to trol
Offset: 0 seconds open time delay
Size (bits): 16 Upper Limit: 5.000
Sign: U seconds
Default: 1
42406 Gen CB Re- Read/ Multiplier: Unit: seconds Sets the time to Breaker Con-
charge Delay Write .020000000000 Lower Limit: .000 allow for genera- trol
Offset: 0 seconds tor set breaker
Size (bits): 16 Upper Limit: 60.000 recharge
Sign: U second
Default: 10
42407 Permissive Read/ Multiplier: Unit: degrees Sets the permis- Master Sync
Phase Win- Write .010000000000 Lower Limit: .100 de- sive +/− phase Control
dow Offset: 0 grees angle window for
Size (bits): 16 Upper Limit: 20.000 sync check func-
Sign: S degrees tion
Default: 10
42408 Permissive Read/ Multiplier: Unit: % Sets the permis- Master Sync
Voltage Win- Write .100000000000 Lower Limit: .500 % sive +/− voltage Control
dow Offset: 0 Upper Limit: 10.000 acceptance win-
Size (bits): 16 % dow for sync
Sign: U Default: 5 check function
42409 Permissive Read/ Multiplier: Unit: seconds Sets the permis- Master Sync
Window Time Write .020000000000 Lower Limit: .500 sive acceptance Control
Offset: 0 seconds window dwell
Size (bits): 16 Upper Limit: 5.000 time for sync
Sign: U seconds check function
Default: 0.5
42410 Permissive Read/ Multiplier: Unit: Hz Sets maximum Master Sync
Frequency Write .001000000000 Lower Limit: .001 Hz frequency differ- Control
Window Offset: 0 Upper Limit: 1.000 ence allowed for
Size (bits): 32 Hz permissive close
Sign: U Default: 1

490
Addr. System Name Access Specifications Description Function
42412 Sync Phase Read/ Multiplier: Unit: degrees Sets a sync Master Sync
Offset Write .010000000000 Lower Limit: −50.000 phase offset to Control
Offset: 0 degrees accommodate
Size (bits): 16 Upper Limit: 50.000 sync across
Sign: S degrees transformer with
Default: 0 phase shift
42413 System Phase Read/ 0: L1−L2−L3 Defines what the System Infor-
Rotation Write 1: L1−L3−L2 system phase mation
Default: L1−L2−L3 rotation se-
quence is
42414 kW Kp Read/ Multiplier: Unit: NA Proportional gain Master Load
Write 1.00000000000 Lower Limit: .000 for kW closed Control
Offset: 0 Upper Limit: loop control in
Size (bits): 16 1000.000 extended paral-
Sign: U Default: 60 leling
42415 kW KI Read/ Multiplier: Unit: NA Integral gain for Master Load
Write 1.00000000000 Lower Limit: .000 kW coled loop Control
Offset: 0 Upper Limit: 255.000 control in ex-
Size (bits): 16 Default: 60 tended parallel-
Sign: U ing
42416 kVAR Kp Read/ Multiplier: Unit: NA Proportional gain Master Load
Write .100000000000 Lower Limit: .000 for kVAR closed Control
Offset: 0 Upper Limit: loop control in
Size (bits): 16 1000.000 extended paral-
Sign: U Default: 120 leling
42417 kVAR K1 Read/ Multiplier: Unit: NA Integral gain for Master Load
Write 1.00000000000 Lower Limit: .000 kVAR closed loop Control
Offset: 0 Upper Limit: 255.000 control in ex-
Size (bits): 16 Default: 50 tended parallel-
Sign: U ing
42418 Scheduler Read/ Multiplier: Unit: NA Selects which System Sche-
Program Se- Write 1.00000000000 Lower Limit: 1.000 scheduler pro- duler
lect Offset: 0 Upper Limit: 12.000 gram to view or
Size (bits): 16 Default: 1 edit
Sign: U
42419 Scheduler Read/ 0: Disable Use to enable or System Sche-
Program En- Write 1: Enable disable the se- duler
able Default: Disable lected program
42420 Scheduler Read/ 0: Once use to adjust re- System Sche-
Program x Re- Write 1: Every Week peat interval for duler
peats Interval 2: Every 2 Weeks the selected pro-
3: Every 3 Weeks gram
4: Every 4 Weeks
5: Every 5 Weeks
6: First Week of the Month
7: Second Week of the Month
8: Third Week of the Month
9: Forth Week of the Month
10: Last Week of the Month
Default: Once

491
Addr. System Name Access Specifications Description Function
42421 Scheduler Read/ 0: No Load Use to adjust run System Sche-
Program x Write 1: With Load mode for the se- duler
Run Mode 2: Extended Parallel lected program
Default: No Load
42422 Scheduler Read/ 0: Sunday Use to adjust System Sche-
Program x Write 1: Monday start day of week duler
Start Day 2: Tuesday for the selected
3: Wednesday program
4: Thursday
5: Friday
6: Saturday
Default: Sunday
42423 Scheduler Read/ Multiplier: Unit: hour Use to adjust System Sche-
Program x Write 1.00000000000 Lower Limit: .000 start hour for the duler
Start Hour Offset: 0 hour selected program
Size (bits): 16 Upper Limit: 23.000
Sign: U hour
Default: 0
42424 Scheduler Read/ Multiplier: Unit: minute Use to adjust System Sche-
Program x Write 1.00000000000 Lower Limit: .000 start minute for duler
Start Minute Offset: 0 minute the selected pro-
Size (bits): 16 Upper Limit: 59.000 gram
Sign: U minute
Default: 0
42425 Scheduler Read/ Multiplier: Unit: hour Use to adjust System Sche-
Program x Write 1.00000000000 Lower Limit: .000 duration hours for duler
Duration Offset: 0 hour the selected pro-
Hours Size (bits): 16 Upper Limit: 23.000 gram
Sign: U hour
Default: 0
42426 Scheduler Read/ Multiplier: Unit: minute Use to adjust System
Program x Write 1.000000000000 Lower Limit: .000 duration minute Scheduler
Duration Min- Offset: 0 minute for the selected
utes Size (bits): 16 Upper Limit: 59.000 program
Sign: U minute
Default: 0
42427 Scheduler Ex- Read/ Multiplier: Unit: NA Selects which System Sche-
ception Select Write 1.000000000000 Lower Limit: 1.000 scheduler excep- duler
Offset: 0 Upper Limit: 6.000 tion to view or
Size (bits): 16 Default: 1 edit
Sign: U
42428 Scheduler Ex- Read/ 0: Disable Use to enable or System Sche-
ception x En- Write 1: Enable disable the se- duler
able Default: Disable lected exception

42429 Scheduler Ex- Read/ 0: Once Only Use to adjust the System Sche-
ception x Re- Write 1: Every Year repeat setting of duler
peat Default: Only Once the selected ex-
ception

492
Addr. System Name Access Specifications Description Function
42430 Scheduler Ex- Read/ Multiplier: Unit: month Use to adjust the System Sche-
ception x Write 1.000000000000 Lower Limit: 1.000 month of the se- duler
Month Offset: 0 month lected exception
Size (bits): 16 Upper Limit: 12.000
Sign: U month
Default: 1
42431 Scheduler Ex- Read/ Multiplier: Unit: date Use to adjust the System Sche-
ception x Date Write 1.000000000000 Lower Limit: 1.000 start date of the duler
Offset: 0 date selected excep-
Size (bits): 16 Upper Limit: 31.000 tion
Sign: U date
Default: 1
42432 Scheduler Ex- Read/ Multiplier: Unit: hour Use to adjust the System Sche-
ception x Hour Write 1.000000000000 Lower Limit: .000 start hour of the duler
Offset: 0 hour selected excep-
Size (bits): 16 Upper Limit: 23.000 tion
Sign: U hour
Default: 0
42433 Scheduler Ex- Read/ Multiplier: Unit: minute Use to adjust the System Sche-
ception x Write 1.000000000000 Lower Limit: .000 mi- start minute of duler
Duration Min- Offset: 0 nute the selected ex-
ute Size (bits): 16 Upper Limit: 59.000 ception
Sign: U minute
Default: 0
42434 Scheduler Ex- Read/ Multiplier: Unit: days Use to adjust the System Sche-
ception x Write 1.000000000000 Lower Limit: .000 duration days of duler
Duration Days Offset: 0 days the selected ex-
Size (bits): 16 Upper Limit: 44.000 ception
Sign: U days
Default: 0
42435 Scheduler Ex- Read/ Multiplier: Unit: hour Use to adjust the System Sche-
ception x Write 1.000000000000 Lower Limit: .000 duration hours of duler
Duration Offset: 0 hour the selected ex-
Hours Size (bits): 16 Upper Limit: 23.000 ception
Sign: U hour
Default: 0
42436 Scheduler Ex- Read/ Multiplier: Unit: minute Use to adjust the System
ception x Write 1.000000000000 Lower Limit: .000: duration minutes Scheduler
Duration Min- Offset: 0 minute of the selected
utes Size (bits): 16 Upper Limit: 59.000: exception
Sign: U minute
Default: 0
42437 Daylight Sav- Read/ 0: Disable Enables the day- Real Time
ing Time En- Write 1: Enable light savings time Clock
able Default: Disable feature

42438 Load Demand Read/ 0: Do Nothing Use to force a re- Load Demand
Refresh Se- Write 1: Refresh Sequence fresh of the ac- Control
quence Com- Default: Do Nothing tive load demand
mand sequence

493
Addr. System Name Access Specifications Description Function
42439 Genset Con- Read/ 0: Wye Delta or wye for AC Setup
nection Type Write 1: Delta generator set
Default: Wye connection
42440 Genset PT Pri- Read/ Multiplier: Unit: Volts Generator set PT AC Setup
mary Voltage Write 1.000000000000 Lower Limit: 100.000 primary voltage
Offset: 0 Volts
Size(bits): 16 Upper Limit:
Sign: U 45000.000 Volts
Default: 480
42441 Genset PT Read/ Multiplier: Unit: Volts Generator set PT AC Setup
Secondary Write 1.000000000000 Lower Limit: 100.000 secondary volt-
Voltage Offset: 0 Volts age
Size(bits): 16 Upper Limit: 500.000
Sign: U Volts
Default: 120
42442 Genset CT Read/ Multiplier: Unit: Amps Generator set CT AC Setup
Primary Cur- Write 1.000000000000 Lower Limit: 5.000 primary current
rent Offset: 0 Amps
Size(bits): 16 Upper Limit:
Sign: U 25000.000 Volts
Default: 100
42443 Genset CT Read/ 0: 1 Amp Generator set CT AC Setup
Secondary Write 1: 5 Amp secondary cur-
Current Default: 5 Amp rent

42444 Utility Connec- Read/ 0: Wye Delta or wye for AC Setup


tion Type Write 1: Delta utility connection
Default: Wye
42445 Utility PT Pri- Read/ Multiplier: Unit: Volts Utility PT primary AC Setup
mary Voltage Write 1.000000000000 Lower Limit: 100.000 voltage
Offset: 0 Volts
Size(bits): 16 Upper Limit:
Sign: U 45000.000 Volts
Default: 480
42446 Utility PT Sec- Read/ Multiplier: Unit: Volts Utility PT secon- AC Setup
ondary Volt- Write 1.000000000000 Lower Limit: 100.000 dary voltage
age Offset: 0 Volts
Size(bits): 16 Upper Limit: 500.000
Sign: U Volts
Default: 120
42447 Utility CT Pri- Read/ Multiplier: Unit: Amps Utility CT primary AC Setup
mary Current Write 1.000000000000 Lower Limit: 5.000 current
Offset: 0 Amps
Size(bits): 16 Upper Limit:
Sign: U 25000.000 Amps
Default: 100
42448 Utility CT Sec- Read/ 0: 1 Amp Utility CT secon- AC Setup
ondary Cur- Write 1: 5 Amp dary current
rent Default: 5 Amp

494
Addr. System Name Access Specifications Description Function
42449 Load Add Read/ Multiplier: Unit: kW Generator set kW Load Add
Shed Re- Write 1.000000000000 Lower Limit: .000 kW capacity that Shed Control
quired Online Offset: 0 Upper Limit: must be online to
Capacity Size(bits): 16 32767.000 kW start timed load
Sign: S Default: 0 add : 0 disables
this
42450 Load Demand Read/ Multiplier: Unit: kW Sets how much Load Demand
Minimum On- Write 1.000000000000 Lower Limit: .000 kW capacity must al- Control
line Capacity Offset: 0 Upper Limit: ways be online
Size(bits): 16 32767.000 kW regardless of
Sign: S Default: 0 what the load is
42451 Load Demand Read/ Multiplier: Unit: second Sets generator Load Demand
Restart Delay Write .100000000000 Lower Limit: .000 restart delay time Control
Offset: 0 second to avoid nuisance
Size(bits): 16 Upper Limit: 25.000 restarts due to
Sign: U second load transients
Default: 1
42452 Utility Avail- Read/ Multiplier: Unit: Amps Use to set how AC Setup
able Current Write 1.000000000000 Lower Limit: 1.000 many amps =
Offset: 0 Amps 100% utility kW −
Size(bits): 16 Upper Limit: used by bargraph
Sign: U 32000.000 Amps
Default: 1000
42453 Total Utility Read/ Multiplier: Unit: kW Use to set hoe AC Setup
Capacity Write 1.000000000000 Lower Limit: 1.000 many kW = 100%
Offset: 0 kW utility kW − used
Size(bits): 16 Upper Limit: by bargraph
Sign: S 32000.000 kW
Default: 1000
42454 Nominal Bat- Read/ 0: 12V DC voltage pro- Battery Volt-
tery Voltage Write 1: 24V vided to the con- age Protec-
Default: 24V trol tion
42455 24V High Bat- Read/ Multiplier: Unit: VDC Sets 24V high Battery Volt-
tery Voltage Write .0100000000000 Lower Limit: 28.000 battery voltage age Protec-
Threshold Offset: 0 VDC fault threshold tion
Size(bits): 16 Upper Limit: 34.000
Sign: U VDC
Default: 32
42456 24V Low Bat- Read/ Multiplier: Unit: VDC Sets 24V low bat- Battery Volt-
tery Voltage Write .0100000000000 Lower Limit: 22.000 tery voltage fault age Protec-
Threshold Offset: 0 VDC threshold tion
Size(bits): 16 Upper Limit: 26.000
Sign: U VDC
Default: 24
42457 12V High Bat- Read/ Multiplier: Unit: VDC Sets 12V high Battery Volt-
tery Voltage Write .0100000000 Lower Limit: 14.000 battery voltage age Protec-
Threshold Offset: 0 VDC fault threshold tion
Size(bits): 16 Upper Limit: 17.000
Sign: U VDC
Default: 16

495
Addr. System Name Access Specifications Description Function
42458 12 V Low Bat- Read/ Multiplier: Unit: VDC Sets 12V low bat- Battery Volt-
tery Voltage Write .010000000000 Lower Limit: 11.000 tery voltage fault age Protec-
Threshold Offset: 0 VDC threshold tion
Size(bits): 16 Upper Limit: 13.000
Sign: U VDC
Default: 12
42459 High Battery Read/ Multiplier: Unit: second Sets high battery Battery Volt-
Voltage Set Write 1.000000000000 Lower Limit: 2.000 voltage set time age Protec-
Time Offset: 0 second tion
Size(bits): 16 Upper Limit: 60.000
Sign: U second
Default: 60
42460 Low Battery Read/ Multiplier: Unit: second Sets low battery Battery Volt-
Voltage Set Write 1.000000000000 Lower Limit: 2.000 voltage set time age Protec-
Time Offset: 0 second tion
Size(bits): 16 Upper Limit: 60.000
Sign: U second
Default: 60
42461 Genset Online Read/ 0: Disable Used to enable PTC Sensors
Capacity Sen- Write 1: Enable or disable the
sor Enable Default: Disable generator set on-
line capacity sen-
sor
42462 Genset Online Read/ Multiplier: Unit: kW Sets the online PTC Sensors
Capacity Sen- Write 1.000000000000 Lower Limit: .000 kW kW threshold at
sor Threshold Offset: 0 Upper Limit: which generator
Size(bits): 16 32000.000 kW set bus is avail-
Sign: S Default: 0 able for loading
42463 Nominal Bat- Read/ 0: Disable Use to enable or Battery Volt-
tery Voltage Write 1: Enable disable the nomi- age Protec-
Check Enable Default: Disable nal battery volt- tion
age monitoring
42464 Configurable Read/ Multiplier: Unit: NA Event or fault Discrete Out-
Output1 Code Write 1.000000000000 Lower Limit: .000 code tied to con- puts
Offset: 0 Upper Limit: figurable output 1
Size(bits): 16 65535.000
Sign: U Default: 1483
42465 Configurable Read/ Multiplier: Unit: NA Event or fault Discrete Out-
Output2 Code Write 1.000000000000 Lower Limit: .000 code tied to con- puts
Offset: 0 Upper Limit: figurable output 2
Size(bits): 16 65535.000
Sign: U Default: 1457
42466 Configurable Read/ Multiplier: Unit: NA Event or fault Discrete Out-
Output3 Code Write 1.000000000000 Lower Limit: .000 code tied to con- puts
Offset: 0 Upper Limit: figurable output 3
Size(bits): 16 65535.000
Sign: U Default: 2965

496
Addr. System Name Access Specifications Description Function
42467 Configurable Read/ Multiplier: Unit: NA Event or fault Discrete Out-
Output4 Code Write 1.000000000000 Lower Limit: .000 code tied to con- puts
Offset: 0 Upper Limit: figurable output 4
Size(bits): 16 65535.000
Sign: U Default: 2328
42468 Configurable Read/ Multiplier: Unit: NA Event or fault Discrete Out-
Output5 Code Write 1.000000000000 Lower Limit: .000 code tied to con- puts
Offset: 0 Upper Limit: figurable output 5
Size(bits): 16 65535.000
Sign: U Default: 1121

42469 Configurable Read/ Multiplier: Unit: NA Event or fault Discrete Out-


Output6 Code Write 1.000000000000 Lower Limit: .000 code tied to con- puts
Offset: 0 Upper Limit: figurable output 6
Size(bits): 16 65535.000
Sign: U Default: 1916
42470 Configurable Read/ Multiplier: Unit: NA Event or fault Discrete Out-
Output7 Code Write 1.000000000000 Lower Limit: .000 code tied to con- puts
Offset: 0 Upper Limit: figurable output 7
Size(bits): 16 65535.000
Sign: U Default: 0
42471 Configurable Read/ Multiplier: Unit: NA Event or fault Discrete Out-
Output8 Code Write 1.000000000000 Lower Limit: .000 code tied to con- puts
Offset: 0 Upper Limit: figurable output 8
Size(bits): 16 65535.000
Sign: U Default: 343
42472 Gen Bus Base Read/ 0: None Indicates that the System Infor-
Load Status Write 1: Breaker generator bus is mation
2: ATS on base load ex-
Default: None tended parallel-
ing
42473 Util Bus Peak Read/ 0: None Indicates that the System In-
Shave Status Write 1: Breaker utility bus is on formation
2: ATS peak shave ex-
Default: None tended parallel-
ing
42474 Load 7 Device Read/ 0: None Indicates type of Load Add
Type Write 1: Breaker load connected Shed Control
2: ATS to load 7 add
Default: None shed control and
status I/O
42475 Load 8 Device Read/ 0: None Indicates type of Load Add
Type Write 1: Breaker load connected Shed Control
2: ATS to load 8 add
Default: None shed control and
status I/O

497
Addr. System Name Access Specifications Description Function
42476 Load 9 Device Read/ 0: None Indicates type of Load Add
Type Write 1: Breaker load connected Shed Control
2: ATS to load 9 add
Default: None shed control and
status I/O
42477 Load 10 De- Read/ 0: None Indicates type of Load Add
vice Type Write 1: Breaker load connected Shed Control
2: ATS to load 10 add
Default: None shed control and
status I/O
42478 Load 7 Add Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: .000 add level load 7 Shed Control
Offset: 0 Upper Limit: 17.000 is assigned to
Size (bits): 16 Default: 7
Sign: U
42479 Load 8 Add Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 add level load 8 Shed control
Offset: 0 Upper Limit: 18.000 is assigned to
Size (bits): 16 Default: 8
Sign: U
42480 Load 9 Add Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 add level load 9 Shed control
Offset: 0 Upper Limit: 18.000 is assigned to
Size (bits): 16 Default: 9
Sign: U
42481 Load 10 Add Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 add level load 10 Shed control
Offset: 0 Upper Limit: 18.000 is assigned to
Size (bits): 16 Default: 10
Sign: U
42482 Load 7 Shed Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: .000 shed level load 7 Shed control
Offset: 0 Upper Limit: 17.000 is assigned to
Size (bits): 16 Default: 6
Sign: U
42483 Load 8 Shed Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: .000 shed level load 8 Shed control
Offset: 0 Upper Limit: 17.000 is assigned to
Size (bits): 16 Default: 7
Sign: U
42484 Load 9 Shed Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: .000 shed level load 9 Shed control
Offset: 0 Upper Limit: 17.000 is assigned to
Size (bits): 16 Default: 8
Sign: U
42485 Load 10 Shed Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: .000 shed level load Shed control
Offset: 0 Upper Limit: 17.000 10 is assigned to
Size (bits): 16 Default: 9
Sign: U

498
Addr. System Name Access Specifications Description Function
42486 Load Demand Read/ 0: %kW Selects whether Load Add
Threshold Write 1: kW to shutdown / re- Shed control
Method Default: %kW start generator
sets based on
%kW or absolute
kW

42487 Load Demand Read/ Multiplier: Unit: kW Sets minimum Load Add
Restart kW Write 1.000000000000 Lower Limit: .000 kW kW reserve ca- Shed control
Threshold Offset: 0 Upper Limit: pacity when
Size (bits): 16 32000.000 kW threshold method
Sign: S Default: 500 is absolute kW

42488 Load Demand Read/ Multiplier: Unit: kW Sets maximum Load Add
Shutdown kW Write 1.000000000000 Lower Limit: .000 kW kW reserve ca- Shed control
Threshold Offset: 0 Upper Limit: pacity when
Size (bits): 16 32000.000 kW threshold method
Sign: S Default: 1000 is absolute kW

42489 Load Demand Read/ 0: Gen1 Sets GenE for Load Demand
GenE Write 1: Gen2 fixed sequence Control
2: Gen3 load demand
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen5

42490 Load Demand Read/ 0: Gen1 Sets GenF for Load Demand
GenF Write 1: Gen2 fixed sequence Control
2: Gen3 load demand
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen6

499
Addr. System Name Access Specifications Description Function
42491 Load Demand Read/ 0: Gen1 Sets GenG for Load Demand
GenG Write 1: Gen2 fixed sequence Control
2: Gen3 load demand
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen7

42492 Load Demand Read/ 0: Gen1 Sets GenH for Load Demand
GenH Write 1: Gen2 fixed sequence Control
2: Gen3 load demand
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen8

42494 Virtual Gen Read/ Multiplier: Unit: second Sets how long to Breaker Con-
Main Fail to Write .200000000000 Lower Limit: 2.000 wait for generator trol
Open Delay Offset: 0 second set paralleling cir-
Size (bits): 16 Upper Limit: 30.000 cuit breakers to
Sign: U second open when no
Default: 5 generator main

42495 Genset 13 kW Read/ Multiplier: Unit: kW Sets generator System Infor-


Rating Write 1.000000000000 Lower Limit: .000 kW 13 kW rating mation
Offset: 0 Upper Limit:
Size (bits): 16 32000.000 kW
Sign: S Default: 0

42496 Genset 14kW Read/ Multiplier: Unit: kW Sets generator System In-
Rating Write 1.000000000000 Lower Limit: .000 kW 14 kW rating formation
Offset: 0 Upper Limit:
Size (bits): 16 32000.000 kW
Sign: S Default: 0

500
Addr. System Name Access Specifications Description Function
42497 Genset 15kW Read/ Multiplier: Unit: kW Sets generator System In-
Rating Write 1.000000000000 Lower Limit: .000 kW 15 kW rating formation
Offset: 0 Upper Limit:
Size (bits): 16 32000.000 kW
Sign: S Default: 0
42498 Genset 16kW Read/ Multiplier: Unit: kW Sets generator System In-
Rating Write 1.000000000000 Lower Limit: .000 kW 16 kW rating formation
Offset: 0 Upper Limit:
Size (bits): 16 32000.000 kW
Sign: S Default: 0
42500 Fault Status Read Multiplier: Unit: NA Bitmapped state Fault and
BitMap 1 Only 1.000000000000 Lower Limit: of utility and oth- Event Info
Offset: 0 Upper Limit: er faults − 32
Size (bits): 32 Default: 0 bits
Sign: U
42502 Fault Status Read Multiplier: Unit: NA Bitmapped state Fault and
BitMap 2 Only 1.000000000000 Lower Limit: of generator set Event Info
Offset: 0 Upper Limit: and other faults −
Size (bits): 32 Default: 0 32 bits
Sign: U
42504 Event Status Read Multiplier: Unit: NA Bitmapped state Fault and
BitMap 1 Only 1.000000000000 Lower Limit: of events − 32 Event Info
Offset: 0 Upper Limit: bits
Size (bits): 32 Default: 0
Sign: U
42506 Genset Meter- Read Multiplier: Unit: NA Bit mapped word AC Interrupt
ing Fault Sta- Only 1.000000000000 Lower Limit: with status of Service
tus Offset: 0 Upper Limit: generator set AC
Size (bits): 16 Default: 0 metering out of
Sign: U range conditions
42507 Utility Metering Read Multiplier: Unit: NA Bit mapped word AC Interrupt
Fault Status Only 1.000000000000 Lower Limit: with status of util- Service
Offset: 0 Upper Limit: ity AC metering
Size (bits): 16 Default: 0 out of range con-
Sign: U ditions
42600 Extended Par- Read / 0: Stop State of extended Discrete In-
allel Start Vol Write 1: Start parallel start vol- puts
Default: Stop atile input
42601 Synchronizer Read / 0: Inactive State of synchro- Discrete In-
Enable Vol Write 1: Active nizer enable vol- puts
Default: Inactive atile input
42602 Utility Source Read / 0: Inactive State of utility Discrete In-
Fail Vol Write 1: Active source failure vo- puts
Default: Inactive latile input
42603 Transfer In- Read / 0: No Inhibit State of transfer Discrete In-
hibit Vol Write 1: Inhibit inhibit volatile in- puts
Default: No Inhibit put
42604 Retransfer In- Read / 0: No Inhibit State of retran- Discrete In-
hibit Vol Write 1: Inhibit sfer inhibit vola- puts
Default: No Inhibit tile input

501
Addr. System Name Access Specifications Description Function
42605 Gen CB Inhibit Read / 0: No Inhibit State of genera- Discrete In-
Vol Write 1: Inhibit tor CB inhibit vol- puts
Default: No Inhibit atile input
42606 Util CB Inhibit Read / 0: No Inhibit State of utility CB Discrete In-
Vol Write 1: Inhibit inhibit volatile in- puts
Default: No Inhibit put
42607 Auto/Manual Read/ 0: Auto State of auto/ Discrete In-
Vol Write 1: Manual manual volatile puts
Default: Auto input
42608 Test Start Vol Read/ 0: Stop state of test start Discrete In-
Write 1: Start volatile input puts
Default: Stop
42609 Fault Reset Read/ 0: No Reset state of fault re- Discrete In-
Vol Write 1: Reset set volatile input puts
Default: No Reset
42610 Override Vol Read/ 0: No Override State of override Discrete In-
Write 1: Override volatile input puts
Default: No Override
42611 Extended Par- Read 0: Stop State of extended Discrete In-
allel Start Sw Only 1: Start parallel start in- puts
Default: put
42612 Synchronizer Read 0: Inactive State of synchro- Discrete In-
Enable Sw Only 1: Active nizer enable in- puts
Default: put
42613 Utility Source Read 0: Inactive State of utility Discrete In-
Failure Sw Only 1: Active source failure in- puts
Default: put
42614 Transfer Inhib- Read 0: No Inhibit Status of transfer Discrete In-
it Sw Only 1: Inhibit inhibit input puts
Default:
42615 Retransfer In- Read 0: No Inhibit Status of retran- Discrete In-
hibit Sw Only 1: Inhibit sfer inhibit input puts
Default:
42616 Gen CB Inhibit Read 0: No Inhibit State of genera- Discrete In-
Sw Only 1: Inhibit tor CB inhibit in- puts
Default: put
42617 Unitl CB Inhibit Read 0: No Inhibit State of utility CB Discrete In-
Sw Only 1: Inhibit inhibit input puts
Default:
42618 Auto/Manual Read 0: Auto State of auto / Discrete In-
Sw Only 1: Manual manual input puts
Default:
42619 Test Start Sw Read 0: Stop State of test start Discrete In-
Only 1: Start input puts
Default:
42620 Fault Reset Read 0: No Reset State of fault re- Discrete In-
Sw Only 1: Reset set input puts
Default:

502
Addr. System Name Access Specifications Description Function
42621 Override Sw Read 0: No Override State of override Discrete In-
Only 1: Override input puts
Default:
42622 Master Inhibit Read 0: No Inhibit Indicates state of Priority Con-
Only 1: Inhibit master priority in- trol
Default: hibit
42623 Genset CB Read 0: Inactive State of genera- Discrete In-
Tripped Sw Only 1: Active tor CB tripped in- puts
Default: put
42624 Genset CB Read/ 0: Inactive State of genera- Discrete In-
Tripped Vol Write 1: Active tor CB tripped puts
Default: Inactive volatile input
42625 Util CB Read 0: Inactive State of Utility CB Discrete In-
Tripped Sw Only 1: Active tripped input puts
Default:
42626 Util CB Read/ 0: Inactive State of Utility CB Discrete In-
Tripped Vol Write 1: Active tripped volatile in- puts
Default: Inactive put
42627 Genset Phase Read 0: L1−L2−L3 Generator set Phase
Rotation Only 1: L1−L3−L2 phase rotation
Default:
42628 Utility Phase Read 0: L1−L2−L3 Utility phase rota- Phase
Rotation Only 1: L1−L3−L2 tion
Default:
42929 Gen1 CB Read 0: Breaker Open State of Gen1 CB Discrete In-
Position Sw Only 1: Breaker Closed position input puts
Default: Open
42630 Gen1 CB Read/ 0: Breaker Open State of Gen1 CB Discrete In-
Position Vol Write 1: Breaker Closed volatile input puts
Default: Open
42631 Gen2 CB Read 0: Breaker Open State of Gen2 CB Discrete In-
Position Sw Only 1: Breaker Closed position input puts
Default:
42632 Gen2 CB Read/ 0: Breaker Open State of Gen2 CB Discrete In-
Position Vol Write 1: Breaker Closed volatile input puts
Default: Open
42633 Gen3 CB Read 0: Breaker Open State of Gen3 CB Discrete In-
Position Sw Only 1: Breaker Closed position input puts
Default:
42634 Gen3 CB Read/ 0: Breaker Open State of Gen3 CB Discrete In-
Position Vol Write 1: Breaker Closed volatile input puts
Default: Open
42635 Gen4 CB Read 0: Breaker Open State of Gen4 CB Discrete In-
Position Sw Only 1: Breaker Closed position input puts
Default:
42636 Gen4 CB Read/ 0: Breaker Open State of Gen4 CB Discrete In-
Position Vol Write 1: Breaker Closed volatile input puts
Default: Open

503
Addr. System Name Access Specifications Description Function
42637 Network Mas- Read/ 0: No Inhibit Use to manually Priority Con-
ter Inhibit Write 1: Inhibit inhibit the module trol
Default: No Inhibit
42638 Gen5 CB Read 0: Breaker Open State of Gen5 CB Discrete In-
Position Sw Only 1: Breaker Closed position input puts
Default:
42639 Gen5 CB Read/ 0: Breaker Open State of Gen5 CB Discrete In-
Position Vol Write 1: Breaker Closed position volatile puts
Default: Open input
42640 Gen6 CB Read 0: Breaker Open State of Gen6 CB Discrete In-
Position Sw Only 1: Breaker Closed position input puts
Default:
42641 Gen6 CB Read/ 0: Breaker Open State of Gen6 CB Discrete In-
Position Vol Write 1: Breaker Closed position volatile puts
Default: Open input
42642 Gen7 CB Read 0: Breaker Open State of Gen7 CB Discrete In-
Position Sw Only 1: Breaker Closed position input puts
Default:
42643 Gen7 CB Read/ 0: Breaker Open State of Gen7 CB Discrete In-
Position Vol Write 1: Breaker Closed position volatile puts
Default: Open input
42644 Gen8 CB Read 0: Breaker Open State of Gen8 CB Discrete In-
Position Sw Only 1: Breaker Closed position input puts
Default:
42645 Gen8 CB Read/ 0: Breaker Open State of Gen8 CB Discrete In-
Position Vol Write 1: Breaker Closed position volatile puts
Default: Open input
42646 ATS 7 Position Read 0: Not Available Indicates position Load Add
Only 1: No Source Connected status of ATS 7 Shed Control
2: Source 1 Connected
3: Source 2 Connected
4: Paralleled
Default: Not Available
42647 ATS 8 Position Read 0: Not Available Indicates position Load Add
Only 1: No Source Connected status of ATS 8 Shed Control
2: Source 1 Connected
3: Source 2 Connected
4: Paralleled
Default: Not Available
42648 ATS 9 Position Read 0: Not Available Indicates position Load Add
Only 1: No Source Connected status of ATS 9 Shed Control
2: Source 1 Connected
3: Source 2 Connected
4: Paralleled
Default: Not Available

504
Addr. System Name Access Specifications Description Function
42649 ATS 10 Posi- Read 0: Not Available Indicates position Load Add
tion Only 1: No Source Connected status of ATS 10 Shed Control
2: Source 1 Connected
3: Source 2 Connected
4: Paralleled
Default: Not Available
42650 Breaker 7 Read 0: Open Indicates position Load Add
Position Only 1: Closed status of breaker Shed Control
2: Not Available 7
Default: Not Available
42651 Breaker 8 Read 0: Open Indicates position Load Add
Position Only 1: Closed status of breaker Shed Control
2: Not Available 8
Default: Not Available
42652 Breaker 9 Read 0: Open Indicates position Load Add
Position Only 1: Closed status of breaker Shed Control
2: Not Available 9
Default: Not Available
42653 Breaker 10 Read 0: Open Indicates position Load Add
Position Only 1: Closed status of breaker Shed Control
2: Not Available 10
Default: Not Available
42654 Breaker 7 Trip Read 0: Not Available Indicates trip sta- Load Add
Status Only 1: Normal tus of breaker 7 Shed Control
2: Tripped
Default: Not Available
42655 Breaker 8 Trip Read 0: Not Available Indicates trip sta- Load Add
Status Only 1: Normal tus of breaker 8 Shed Control
2: Tripped
Default: Not Available
42656 Breaker 9 Trip Read 0: Not Available Indicates trip sta- Load Add
Status Only 1: Normal tus of breaker 9 Shed Control
2: Tripped
Default: Not Available
42657 Breaker 10 trip Read 0: Not Available Indicates trip sta- Load Add
Status Only 1: Normal tus of breaker 10 Shed Control
2: Tripped
Default: Not Available
42658 Gen9 CB Read 0: Breaker Open State of Gen9 CB Discrete In-
Position Sw Only 1: Breaker Closed position input puts
Default:
42659 Gen9 CB Read/ 0: Breaker Open State of Gen9 CB Discrete In-
Position Vol Write 1: Breaker Closed position volatile puts
Default: Open input
42660 Gen10 CB Read 0: Breaker Open State of Gen10 Discrete In-
Position Sw Only 1: Breaker Closed CB position input puts
Default:

505
Addr. System Name Access Specifications Description Function
42661 Gen10 CB Read/ 0: Breaker Open State of Gen10 Discrete In-
Position Vol Write 1: Breaker Closed CB position vola- puts
Default: Open tile input
42662 Gen11 CB Read 0: Breaker Open State of Gen11 Discrete In-
Position Sw Only 1: Breaker Closed CB position input puts
Default:
42663 Gen11 CB Read/ 0: Breaker Open State of Gen11 Discrete In-
Position Vol Write 1: Breaker Closed CB position vola- puts
Default: Open tile input
42664 Gen12 CB Read 0: Breaker Open State of Gen12 Discrete In-
Position Sw Only 1: Breaker Closed CB position input puts
Default:
42665 Gen12 CB Read/ 0: Breaker Open State of Gen12 Discrete In-
Position Vol Write 1: Breaker Closed CB position vola- puts
Default: Open tile input
42666 Gen13 CB Read 0: Breaker Open State of Gen13 Discrete In-
Position Sw Only 1: Breaker Closed CB position input puts
Default:
42667 Gen13 CB Read/ 0: Breaker Open State of Gen13 Discrete In-
Position Vol Write 1: Breaker Closed CB position vola- puts
Default: Open tile input
42668 Gen14 CB Read 0: Breaker Open State of Gen 14 Discrete In-
Position Sw Only 1: Breaker Closed CB position input puts
Default:
42669 Gen14 CB Read/ 0: Breaker Open State of Gen 14 Discrete In-
Position Vol Write 1: Breaker Closed CB position vola- puts
Default: Open tile input
42670 Gen15 CB Read 0: Breaker Open State of Gen 15 Discrete In-
Position Sw Only 1: Breaker Closed CB position input puts
Default:
42671 Gen15 CB Read/ 0: Breaker Open State of Gen 15 Discrete In-
Position Vol Write 1: Breaker Closed CB position vola- puts
Default: Open tile input
42672 Gen16 CB Read 0: Breaker Open State of Gen 16 Discrete In-
Position Sw Only 1: Breaker Closed CB position input puts
Default:
42673 Gen16 CB Read/ 0: Breaker Open State of Gen 16 Discrete In-
Position Vol Write 1: Breaker Closed CB position vola- puts
Default: Open tile input
42674 ATS 11 Posi- Read 0: Not Available Indicates position Load Add
tion Only 1: No Source Connected status of ATS 11 Shed Control
2: Source 1 Connected
3: Source 2 Connected
4: Paralleled
Default: Not Available

506
Addr. System Name Access Specifications Description Function
42675 ATS 12 Posi- Read 0: Not Available Indicates position Load Add
tion Only 1: No Source Connected status of ATS 12 Shed Control
2: Source 1 Connected
3: Source 2 Connected
4: Paralleled
Default: Not Available
42676 ATS 13 Posi- Read 0: Not Available Indicates position Load Add
tion Only 1: No Source Connected status of ATS 13 Shed Control
2: Source 1 Connected
3: Source 2 Connected
4: Paralleled
Default: Not Available
42677 ATS 14 Posi- Read 0: Not Available Indicates position Load Add
tion Only 1: No Source Connected status of ATS 14 Shed Control
2: Source 1 Connected
3: Source 2 Connected
4: Paralleled
Default: Not Available
42678 ATS 15 Posi- Read 0: Not Available Indicates position Load Add
tion Only 1: No Source Connected status of ATS 15 Shed Control
2: Source 1 Connected
3: Source 2 Connected
4: Paralleled
Default: Not Available
42679 ATS 16 Posi- Read 0: Not Available Indicates position Load Add
tion Only 1: No Source Connected status of ATS 16 Shed Control
2: Source 1 Connected
3: Source 2 Connected
4: Paralleled
Default: Not Available
42680 ATS 17 Posi- Read 0: Not Available Indicates position Load Add
tion Only 1: No Source Connected status of ATS 17 Shed Control
2: Source 1 Connected
3: Source 2 Connected
4: Paralleled
Default: Not Available
42681 ATS 18 Posi- Read 0: Not Available Indicates position Load Add
tion Only 1: No Source Connected status of ATS 18 Shed Control
2: Source 1 Connected
3: Source 2 Connected
4: Paralleled
Default: Not Available
42682 Breaker 11 Read 0: Open Indicates position Load Add
Position Only 1: Closed status of breaker Shed Control
2: Not Available 11
Default: Not Available
42683 Breaker 12 Read 0: Open Indicates position Load Add
Position Only 1: Closed status of breaker Shed Control
2: Not Available 12
Default: Not Available

507
Addr. System Name Access Specifications Description Function
42684 Breaker 13 Read 0: Open Indicates position Load Add
Position Only 1: Closed status of breaker Shed Control
2: Not Available 13
Default: Not Available
42685 Breaker 14 Read 0: Open Indicates position Load Add
Position Only 1: Closed status of breaker Shed Control
2: Not Available 14
Default: Not Available
42686 Breaker 15 Read 0: Open Indicates position Load Add
Position Only 1: Closed status of breaker Shed Control
2: Not Available 15
Default: Not Available
42687 Breaker 16 Read 0: Open Indicates position Load Add
Position Only 1: Closed status of breaker Shed Control
2: Not Available 16
Default: Not Available
42688 Breaker 17 Read 0: Open Indicates position Load Add
Position Only 1: Closed status of breaker Shed Control
2: Not Available 17
Default: Not Available
42689 Breaker 18 Read 0: Open Indicates position Load Add
Position Only 1: Closed status of breaker Shed Control
2: Not Available 18
Default: Not Available
42690 Breaker 11 Read 0: Not Available Indicates trip sta- Load Add
Trip Status Only 1: Normal tus of breaker 11 Shed Control
2: Tripped
Default: Not Available
42691 Breaker 12 Read 0: Not Available Indicates trip sta- Load Add
Trip Status Only 1: Normal tus of breaker 12 Shed Control
2: Tripped
Default: Not Available
42692 Breaker 13 Read 0: Not Available Indicates trip sta- Load Add
Trip Status Only 1: Normal tus of breaker 13 Shed Control
2: Tripped
Default: Not Available
42693 Breaker 14 Read 0: Not Available Indicates trip sta- Load Add
Trip Status Only 1: Normal tus of breaker 14 Shed Control
2: Tripped
Default: Not Available
42694 Breaker 15 Read 0: Not Available Indicates trip sta- Load Add
Trip Status Only 1: Normal tus of breaker 15 Shed Control
2: Tripped
Default: Not Available
42695 Breaker 16 Read 0: Not Available Indicates trip sta- Load Add
Trip Status Only 1: Normal tus of breaker 16 Shed Control
2: Tripped
Default: Not Available

508
Addr. System Name Access Specifications Description Function
42696 Breaker 17 Read 0: Not Available Indicates trip sta- Load Add
Trip Status Only 1: Normal tus of breaker 17 Shed Control
2: Tripped
Default: Not Available
42697 Breaker 18 Read 0: Not Available Indicates trip sta- Load Add
Trip Status Only 1: Normal tus of breaker 18 Shed Control
2: Tripped
Default: Not Available
42698 Load Add Read 0: Disabled Indicates the Load Add
Shed Enable Only 1: Enabled overall state of Shed Control
Status 2: Paused the load add
Default: shed function
42699 PCCNet Sta- Read 0: No Connection Indicates overall Communica-
tus Only 1: Connected state of the tions
2: Connecting PCCNet commu-
Default: nications bus
42700 Gen1 Avail- Read 0: Gen Does Not Exist For load demand Load Demand
ability State Only 1: Offline use − indicates Control
2: Waiting For Gen status of Gen1
3: Online
4: Failed
Default:
42701 Gen2 Avail- Read 0: Gen Does Not Exist For load demand Load Demand
ability State Only 1: Offline use − indicates Control
2: Waiting For Gen status of Gen2
3: Online
4: Failed
Default:
42702 Gen3 Avail- Read 0: Gen Does Not Exist For load demand Load Demand
ability State Only 1: Offline use − indicates Control
2: Waiting For Gen status of Gen3
3: Online 4: Failed
Default:
42703 Gen4 Avail- Read 0: Gen Does Not Exist For load demand Load Demand
ability State Only 1: Offline use − indicates Control
2: Waiting For Gen status of Gen4
3: Online
4: Failed
Default:
42704 Gen1 Online Read Multiplier: Unit:Hours Total online time System In-
Time Only .000277777780 Lower Limit:.000 for Gen1 formation
Offset: 0 Hours
Size (bits): 32 Upper Limit:
Sign:U 1193046.000 Hours
Default:0

509
Addr. System Name Access Specifications Description Function
42706 Gen2 Online Read Multiplier: Unit:Hours Total online time System In-
Time Only .000277777780 Lower Limit: .000 for Gen2 formation
Offset: 0 Hours
Size (bits): 32 Upper Limit:
1193046.000 Hours
Default:0
42708 Gen3 Online Read Multiplier: Unit:Hours Total online time System In-
Time Only .000277777780 Lower Limit: .000 for Gen3 formation
Offset: 0 Hours
Size (bits): 32 Upper Limit:
1193046.000 Hours
Default:0
42710 Gen4 Online Read Multiplier: Unit:Hours Total online time System Infor-
Time Only .000277777780 Lower Limit: .000 for Gen4 mation
Offset: 0 Hours
Size (bits): 32 Upper Limit:
1193046.000 Hours
Default:0
42712 GenA Read 0: Gen1 Indicates which Load Demand
Only 1: Gen2 generator set is Control
2: Gen3 currently GenA
3: Gen4 (never stops) for
4: Gen5 load demand
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

510
Addr. System Name Access Specifications Description Function
42713 GenB Read 0: Gen1 Indicates which Load Demand
Only 1: Gen2 generator set is Control
2: Gen3 currently GenB
3: Gen4 for load demand
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
42714 GenC Read 0: Gen1 Indicates which Load Demand
Only 1: Gen2 generator set is Control
2: Gen3 currently GenC
3: Gen4 for load demand
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
42715 GenD Read 0: Gen1 Indicates which Load Demand
Only 1: Gen2 generator sets is Control
2: Gen3 currently GenD
3: Gen4 for load demand
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

511
Addr. System Name Access Specifications Description Function
42716 Load Demand Read 0: Off Indicates operat- Load Demand
State Only 1: Initial Delay Timing ing state of the Control
2: Load Monitor load demand
Default control
42717 Total Number Read Multiplier: Unit: NA Indicates how System In-
of Gensets Only 1.000000000000 Lower Limit: many of the gen- formation
Online Offset: 0 Upper Limit: erator sets are
Size (bits): 16 Default: online which are
Sign: U sensed by CB
position
42718 Total Spare Read Multiplier: Unit: kW Difference be- System In-
Online Capac- Only 1.000000000000 Lower Limit: kW tween sensed formation
ity Offset: 0 Upper Limit: kW online capacity
Size (bits): 16 Default: and generator set
Sign: S bus total kW
42719 Next Gen Read Multiplier: Unit: kW Indicates kW Load Demand
Shutdown Only 1.000000000000 Lower Limit: kW threshold for gen- Control
Threshold Offset: 0 Upper Limit: kW erator bus at
Size (bits): 16 Default: which next gen-
Sign: S erator set will re-
start
42720 Next Gen Read Multiplier: Unit: kW Indicates kW Load Demand
Shutdown Only 1.000000000000 Lower Limit: kW threshold for gen- Control
Threshold Offset: 0 Upper Limit: kW erator bus at
Size (bits): 16 Default: which the next
Sign: S generator set will
load demand
stop
42721 Next Gen Re- Read 0: Gen1 Indicates which Load Demand
start Only 1: Gen2 generator set is Control
2: Gen3 next to be re-
3: Gen4 started if load
4: Gen5 conditions are
5: Gen6 met
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

512
Addr. System Name Access Specifications Description Function
42722 Next Gen Read 0: Gen1 Indicates which Load Demand
Shutdown Only 1: Gen2 generator set is Control
2: Gen3 next to be
3: Gen4 stopped if load
4: Gen5 conditions are
5: Gen6 met
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
42723 Load Demand Read 0: Run Status of the load Discrete Out-
Gen1 Driver Only 1: Load Demand Stop demand Gen1 puts
Status Default: driver output
42724 Load Demand Read 0: Run Status of the load Discrete Out-
Gen2 Driver Only 1: Load Demand Stop demand Gen2 puts
Status Default: driver output
42725 Load Demand Read 0: Run Status of the load Discrete Out-
Gen3 Driver Only 1: Load Demand Stop demand Gen3 puts
Status Default: driver output
42726 Load Demand Read 0: Run Status of the load Discrete Out-
Gen4 Driver Only 1: Load Demand Stop demand Gen4 puts
Status Default: driver output
42727 Genset Bus Read Multiplier: Unit: kW Calculated kW System Infor-
kW Overload Only 1.000000000000 Lower Limit: kW overload thresh- mation
Status Offset: 0 Upper Limit: kW old based on on-
Size (bits): 16 Default: line capacity and
Sign: S % setting
42728 Genset Bus Read 0: No Overload Indicates whether System In-
kW Overload Only 1: Overload generator bus is formation
Status Default: overloaded
based on kW
42729 Genset Bus Read 0: No Overload Indicates whether System In-
Underfrequen- Only 1: Overload generator bus is formation
cy Overload Default: overloaded
Status based on fre-
quency

513
Addr. System Name Access Specifications Description Function
42730 Active Sched- Read 0: None Indicates the cur- System
ule Only 1: Program 1 rently active Scheduler
2: Program 2 scheduler pro-
3: Program 3 gram or excep-
4: Program 4 tion
5: Program 5
6: Program 6
7: Program 7
8: Program 8
9: Program 9
10: Program 10
11: Program 11
12: Program 12
13: Exception 1
14: Exception 2
15: Exception 3
16: Exception 4
17: Exception 5
18: Exception 6
Default:
42731 Scheduler Run Read 0: Off Indicates current System Sche-
Command Only 1: No Load run command duler
2: With Load coming from
3: Extended Parallel scheduler func-
Default: tion
42732 Modbus Bus Read Multiplier: Unit: NA Modbus mes- Communica-
Message Only 1.000000000000 Lower Limit: sage count tions
Count Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42733 Modbus CRC Read Multiplier: Unit: NA Modbus CRC er- Communica-
Error Count Only 1.000000000000 Lower Limit: ror count tions
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42734 Modbus Ex- Read Multiplier: Unit: NA Modbus excep- Communica-
ception Count Only 1.000000000000 Lower Limit: tion count tions
Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42735 Modbus No Read Multiplier: Unit: NA Modbus no re- Communica-
Response Only 1.000000000000 Lower Limit: sponse count tions
Count Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U
42736 Modbus Slave Read Multiplier: Unit: NA Modbus slave Communica-
Message Only 1.000000000000 Lower Limit: message count tions
Count Offset: 0 Upper Limit:
Size (bits): 16 Default:
Sign: U

514
Addr. System Name Access Specifications Description Function
42737 Modbus Clear Read/ 0: Do Nothing Clears all mod- Communica-
Counters Write 1: Clear Counters bus counters tions
Default: Do Nothing

42738 Clock Mode Read/ 0: Normal Use to set clock Real Time
Write 1: Set Clock and save setting Clock
2: Save Clock
Default: Normal
42739 Clock Year Read/ Multiplier: Unit: year Use to set or Real Time
Write 1.000000000000 Lower Limit: .000 read current year Clock
Offset: 0 year
Size (bits): 16 Upper Limit: 99.000
Sign: U year
Default: Read from
RTC chip
42740 Clock Month Read/ Multiplier: Unit: month Use to set or Real Time
Write 1.000000000000 Lower Limit: 1.000 read current Clock
Offset: 0 month month
Size (bits): 16 Upper Limit: 12.000
Sign: U month
Default: Read from
RTC chip
42741 Clock Date Read/ Multiplier: Unit: date Use to set or Real Time
Write 1.000000000000 Lower Limit: 1.000 read current date Clock
Offset: 0 date
Size (bits): 16 Upper Limit: 31.000
Sign: U date
Default: Read from
RTC chip
42742 Clock Hour Read/ Multiplier: Unit: hour Use to set or Real Time
Write 1.000000000000 Lower Limit: 1.000 read current hour Clock
Offset: 0 hour
Size (bits): 16 Upper Limit: 23.000
Sign: U hour
Default: Read from
RTC chip
42743 Clock Minute Read/ Multiplier: Unit: minute Use to set or Real Time
Write 1.000000000000 Lower Limit: 1.000 read current min- Clock
Offset: 0 minute ute
Size (bits): 16 Upper Limit: 59.000
Sign: U minute
Default: Read from
RTC chip
42744 Clock Second Read/ Multiplier: Unit: second Use to set or Real Time
Write 1.000000000000 Lower Limit: .000 read current sec- Clock
Offset: 0 second ond
Size (bits): 16 Upper Limit: 59.000
Sign: U second
Default: Read from
RTC chip

515
Addr. System Name Access Specifications Description Function
42745 Clock Day Read 0: Sunday Indicates day of Real Time
Only 1: Monday the week for cur- Clock
2: Tuesday rent date
3: Wednesday
4: Thursday
5: Friday
6: Saturday
Default:
42746 Start Timer Read Multiplier: Unit: seconds Countdown timer PTC Operat-
Only .100000000000 Lower Limit: seconds value for genera- ing Mode
Offset: 0 Upper Limit: seconds tor set start timer
Size (bits): 16 Default:
Sign: U
42747 Stop Timer Read Multiplier: Unit: seconds Countdown timer PTC Operat-
Only .100000000000 Lower Limit: seconds value for genera- ing Mode
Offset: 0 Upper Limit: seconds tor set stop timer
Size (bits): 16 Default:
Sign: U
42748 Low Battery Read Multiplier: Unit: VDC Battery voltage Battery Volt-
Voltage Only .010000000000 Lower Limit: VDC with respect to age Protec-
Threshold Offset: 0 Upper Limit: VDC set low battery tion
Size (bits): 16 Default: threshold
Sign: U
42749 High Battery Read Multiplier: Unit: VDC Battery voltage Battery Volt-
Voltage Only .010000000000 Lower Limit: VDC with respect to age Protec-
Threshold Offset: 0 Upper Limit: VDC set high battery tion
Size (bits): 16 Default: threshold
Sign: U
42750 Gen5 Avail- Read 0: Gen Does Not Exist For load demand Load Demand
ability State Only 1: Offline use − indicates Control
2: Waiting for Gen status of Gen5
3: Online
4: Failed
Default:
42751 Gen6 Avail- Read 0: Gen Does Not Exist For load demand Load Demand
ability State Only 1: Offline use − indicates Control
2: Waiting for Gen status of Gen6
3: Online
4: Failed
Default:
42752 Gen7 Avail- Read 0: Gen Does Not Exist For load demand Load Demand
ability State Only 1: Offline use − indicates Control
2: Waiting for Gen status of Gen7
3: Online
4: Failed
Default:

516
Addr. System Name Access Specifications Description Function
42753 Gen8 Avail- Read 0: Gen Does Not Exist For load demand Load Demand
ability State Only 1: Offline use − indicates Control
2: Waiting for Gen status of Gen8
3: Online
4: Failed
Default:
42754 Load Demand Read 0: Run Status of the load Discrete Out-
Gen5 Driver Only 1: Load Demand Stop demand Gen5 puts
Status Default: driver output
42755 Load Demand Read 0: Run Status of the load Discrete Out-
Gen6 Driver Only 1: Load Demand Stop demand Gen6 puts
Status Default: driver output
42756 Load Demand Read 0: Run Status of the load Discrete Out-
Gen7 Driver Only 1: Load Demand Stop demand Gen7 puts
Status Default: driver output
42757 Load Demand Read 0: Run Status of the load Discrete Out-
Gen8 Driver Only 1: Load Demand Stop demand Gen8 puts
Status Default: driver output
42758 GenE Read 0: Gen 1 Indicates which Load Demand
Only 1: Gen 2 generator set is Control
2: Gen 3 currently GenE
3: Gen 4 for load demand
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8
8: Gen 9
9: Gen 10
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default:

517
Addr. System Name Access Specifications Description Function
42759 GenF Read 0: Gen 1 Indicates which Load Demand
Only 1: Gen 2 generator set is Control
2: Gen 3 currently GenF
3: Gen 4 for load demand
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8
8: Gen 9
9: Gen 10
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default:

42760 GenG Read 0: Gen 1 Indicates which Load Demand


Only 1: Gen 2 generator set is Control
2: Gen 3 currently GenG
3: Gen 4 for load demand
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8
8: Gen 9
9: Gen 10
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default:

42761 GenH Read 0: Gen 1 Indicates which Load Demand


Only 1: Gen 2 generator set is Control
2: Gen 3 currently GenH
3: Gen 4 for load demand
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8
8: Gen 9
9: Gen 10
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default:

518
Addr. System Name Access Specifications Description Function
42762 Add Level 7 Read 0: Do Nothing Indicates status Load Add
Command Only 1: Add Level of add level 7 Shed Control
Default: Do Nothing
42763 Add Level 8 Read 0: Do Nothing Indicates status Load Add
Command Only 1: Add Level of add level 8 Shed Control
Default: Do Nothing
42764 Add Level 9 Read 0: Do Nothing Indicates status Load Add
Command Only 1: Add Level of add level 9 Shed Control
Default: Do Nothing
42765 Add Level 10 Read 0: Do Nothing Indicates status Load Add
Command Only 1: Add Level of add level 10 Shed Control
Default: Do Nothing
42766 Add Load 7 Read 0: Do Nothing Indicates add Load Add
Command Only 1: Add Level command for Shed Control
Default: Do Nothing load 7
42767 Add Load 8 Read 0: Do Nothing Indicates add Load Add
Command Only 1: Add Level command for Shed Control
Default: Do Nothing load 8
42768 Add Load 9 Read 0: Do Nothing Indicates add Load Add
Command Only 1: Add Level command for Shed Control
Default: Do Nothing load 9
42769 Add Load 10 Read 0: Do Nothing Indicates add Load Add
Command Only 1: Add Level command for Shed Control
Default: Do Nothing load 10
42770 Shed Level 6 Read 0: Do Nothing Indicates status Load Add
Command Only 1: Shed Level of shed level 6 Shed Control
Default: Do Nothing
42771 Shed Level 7 Read 0: Do Nothing Indicates status Load Add
Command Only 1: Shed Level of shed level 7 Shed Control
Default: Do Nothing
42772 Shed Level 8 Read 0: Do Nothing Indicates status Load Add
Command Only 1: Shed Level of shed level 8 Shed Control
Default: Do Nothing
42773 Shed Level 9 Read 0: Do Nothing Indicates status Load Add
Command Only 1: Shed Level of shed level 9 Shed Control
Default: Do Nothing
42774 Shed Load 7 Read 0: Do Nothing Indicates shed Load Add
Command Only 1: Shed Load command for Shed Control
Default: Do Nothing load 7
42775 Shed Load 8 Read 0: Do Nothing Indicates shed Load Add
Command Only 1: Shed Load command for Shed Control
Default: Do Nothing load 8
42776 Shed Load 9 Read 0: Do Nothing Indicates shed Load Add
Command Only 1: Shed Load command for Shed Control
Default: Do Nothing load 9
42777 Shed Load 10 Read 0: Do Nothing Indicates shed Load Add
Command Only 1: Shed Load command for Shed Control
Default: Do Nothing load 10

519
Addr. System Name Access Specifications Description Function
42778 Restore Shed Read 0: Do Nothing Indicates if shed Load Add
Level 6 Com- Only 1: Restore Level level 6 has been Shed Control
mand Default: Do Nothing restored
42779 Restore Shed Read/ 0: Do Nothing Indicates if shed Load Add
Level 7 Com- Write 1: Restore Level level 7 has been Shed Control
mand Default: Do Nothing restored
42780 Restore Shed Read/ 0: Do Nothing Indicates if shed Load Add
Level 8 Com- Write 1: Restore Level level 8 has been Shed Control
mand Default: Do Nothing restored
42781 Restore Shed Read/ 0: Do Nothing Indicates if shed Load Add
Level 9 Com- Write 1: Restore Level level 9 has been Shed Control
mand Default: Do Nothing restored
42782 Gen5 Online Read Multiplier: Unit: hours Total online time System Infor-
Time Only .000277777780 Lower Limit: .000 for Gen5 mation
Offset: 0 hours
Size (bits): 32 Upper Limit:
Sign: U 1193046.000 hours
Default: 0
42784 Gen6 Online Read Multiplier: Unit: hours Total online time System In-
Time Only .000277777780 Lower Limit: .000 for Gen6 formation
Offset: 0 hours
Size (bits): 32 Upper Limit:
Sign: U 1193046.000 hours
Default: 0
42786 Gen7 Online Read Multiplier: Unit: hours Total online time System In-
Time Only .000277777780 Lower Limit: .000 for Gen7 formation
Offset: 0 hours
Size (bits): 32 Upper Limit:
Sign: U 1193046.000 hours
Default: 0
42788 Gen8 Online Read Multiplier: Unit: hours Total online time System In-
Time Only .000277777780 Lower Limit: .000 for Gen8 formation
Offset: 0 hours
Size (bits): 32 Upper Limit:
Sign: U 1193046.000 hours
Default: 0
42790 Manual Add Read/ 0: Do Nothing Operator input to Load Add
Level 7 Com- Write 1: Add Level add loads as- Shed Control
mand Default: Do Nothing signed to level 7
42791 Manual Add Read/ 0: Do Nothing Operator input to Load Add
Level 8 Com- Write 1: Add Level add loads as- Shed Control
mand Default: Do Nothing signed to level 8
42792 Manual Add Read/ 0: Do Nothing Operator input to Load Add
Level 9 Com- Write 1: Add Level add loads as- Shed Control
mand Default: Do Nothing signed to level 9
42793 Manual Add Read/ 0: Do Nothing Operator input to Load Add
Level 10 Com- Write 1: Add Level add loads as- Shed Control
mand Default: Do Nothing signed to level 10

520
Addr. System Name Access Specifications Description Function
42794 Manual Shed Read/ 0: Do Nothing Operator input to Load Add
Level 6 Com- Write 1: Shed Level shed loads as- Shed Control
mand Default: Do Nothing signed to level 6
42795 Manual Shed Read/ 0: Do Nothing Operator input to Load Add
Level 7 Com- Write 1: Shed Level shed loads as- Shed Control
mand Default: Do Nothing signed to level 7
42796 Manual Shed Read/ 0: Do Nothing Operator input to Load Add
Level 8 Com- Write 1: Shed Level shed loads as- Shed Control
mand Default: Do Nothing signed to level 8
42797 Manual Shed Read/ 0: Do Nothing Operator input to Load Add
Level 9 Com- Write 1: Shed Level shed loads as- Shed Control
mand Default: Do Nothing signed to level 9
42798 Gen9 Avail- Read 0: Gen Does Not Exist For load demand Load Demand
ability State Only 1: Offline use − indicates Control
2: Waiting For Gen status of Gen9
3: Online4: FailedDefault:
42799 Gen10 Avail- Read 0: Gen Does Not Exist For load demand Load Demand
ability State Only 1: Offline use − indicates Control
2: Waiting For Gen status of Gen10
3: Online
4: FailedDefault:
42800 Gen11 Avail- Read 0: Gen Does Not Exist For load demand Load Demand
ability State Only 1: Offline use − indicates Control
2: Waiting For Gen status of Gen11
3: Online
4: FailedDefault:
42801 Gen12 Avail- Read 0: Gen Does Not Exist For load demand Load Demand
ability State Only 1: Offline use − indicates Control
2: Waiting For Gen status of Gen12
3: Online
4: FailedDefault:
42802 Gen13 Avail- Read 0: Gen Does Not Exist For load demand Load Demand
ability State Only 1: Offline use − indicates Control
2: Waiting For Gen status of Gen13
3: Online
4: Failed
Default:
42803 Gen14 Avail- Read 0: Gen Does Not Exist For load demand Load Demand
ability State Only 1: Offline use − indicates Control
2: Waiting for Gen status of Gen14
3: Online
4: Failed
Default:
42804 Gen15 Avail- Read 0: Gen Does Not Exist For load demand Load Demand
ability State Only 1: Offline use − indicates Control
2: Waiting for Gen status of Gen15
3: Online
4: Failed
Default:

521
Addr. System Name Access Specifications Description Function
42805 Gen16 Avail- Read 0: Gen Does Not Exist For load demand Load Demand
ability State Only 1: Offline use − indicates Control
2: Waiting for Gen status of Gen16
3: Online
4: Failed
Default:

42806 Load Demand Read 0: Run Status of load de- Discrete Out-
Gen9 Driver Only 1: Load Demand Stop mand Gen9 driv- puts
Status Default: er output

42807 Load Demand Read 0: Run Status of load de- Discrete Out-
Gen10 Driver Only 1: Load Demand Stop mand Gen10 puts
Status Default: driver output

42808 Load Demand Read 0: Run Status of load de- Discrete Out-
Gen11 Driver Only 1: Load Demand Stop mand Gen11 puts
Status Default: driver output

42809 Load Demand Read 0: Run Status of load de- Discrete Out-
Gen12 Driver Only 1: Load Demand Stop mand Gen12 puts
Status Default: driver output

42810 Load Demand Read 0: Run Status of load de- Discrete Out-
Gen13 Driver Only 1: Load Demand Stop mand Gen13 puts
Status Default: driver output

42811 Load Demand Read 0: Run Status of load de- Discrete Out-
Gen14 Driver Only 1: Load Demand Stop mand Gen14 puts
Status Default: driver output

42812 Load Demand Read 0: Run Status of load de- Discrete Out-
Gen15 Driver Only 1: Load Demand Stop mand Gen15 puts
Status Default: driver output

42813 Load Demand Read 0: Run Status of load de- Discrete Out-
Gen16 Driver Only 1: Load Demand Stop mand Gen16 puts
Status Default: driver output

42814 GenI Read 0: Gen1 Indicates which Load Demand


Only 1: Gen2 generator set is Control
2: Gen3 currently GenI for
3: Gen4 load demand
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

522
Addr. System Name Access Specifications Description Function
42815 GenJ Read 0: Gen1 Indicates which Load Demand
Only 1: Gen2 generator set is Control
2: Gen3 currently GenJ
3: Gen4 for load demand
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

42816 GenK Read 0: Gen1 Indicates which Load Demand


Only 1: Gen2 generator set is Control
2: Gen3 currently GenK
3: Gen4 for load demand
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

42817 GenL Read 0: Gen1 Indicates which Load Demand


Only 1: Gen2 generator set is Control
2: Gen3 currently GenL
3: Gen4 for load demand
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

523
Addr. System Name Access Specifications Description Function
42818 GenM Read 0: Gen1 Indicates which Load Demand
Only 1: Gen2 generator set is Control
2: Gen3 currently GenM
3: Gen4 for load demand
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

42819 GenN Read 0: Gen1 Indicates which Load Demand


Only 1: Gen2 generator set is Control
2: Gen3 currently GenN
3: Gen4 for load demand
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

42820 GenO Read 0: Gen1 Indicates which Load Demand


Only 1: Gen2 generator set is Control
2: Gen3 currently GenO
3: Gen4 for load demand
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

524
Addr. System Name Access Specifications Description Function
42821 GenP Read 0: Gen1 Indicates which Load Demand
Only 1: Gen2 generator set is Control
2: Gen3 currently GenP
3: Gen4 for load demand
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

42822 Add Level 11 Read 0: Do Nothing Indicates status Load Add


Command Only 1: Add Level of add level 11 Shed Control
Default: Do Nothing

42823 Add Level 12 Read 0: Do Nothing Indicates status Load Add


Command Only 1: Add Level of add level 12 Shed Control
Default: Do Nothing

42824 Add Level 13 Read 0: Do Nothing Indicates status Load Add


Command Only 1: Add Level of add level 13 Shed Control
Default: Do Nothing

42825 Add Level 14 Read 0: Do Nothing Indicates status Load Add


Command Only 1: Add Level of add level 14 Shed Control
Default: Do Nothing

42826 Add Level 15 Read 0: Do Nothing Indicates status Load Add


Command Only 1: Add Level of add level 15 Shed Control
Default: Do Nothing

42827 Add Level 16 Read 0: Do Nothing Indicates status Load Add


Command Only 1: Add Level of add level 16 Shed Control
Default: Do Nothing

42828 Add Level 17 Read 0: Do Nothing Indicates status Load Add


Command Only 1: Add Level of add level 17 Shed Control
Default: Do Nothing

42829 Add Level 18 Read 0: Do Nothing Indicates status Load Add


Command Only 1: Add Level of add level 18 Shed Control
Default: Do Nothing

42830 Add Load 11 Read 0: Do Nothing Indicates add Load Add


Command Only 1: Add Load command for Shed Control
Default: Do Nothing load 11

42831 Add Load 12 Read 0: Do Nothing Indicates add Load Add


Command Only 1: Add Load command for Shed Control
Default: Do Nothing load 12

525
Addr. System Name Access Specifications Description Function
42832 Add Load 13 Read 0: Do Nothing Indicates add Load Add
Command Only 1: Add Load command for Shed Control
Default: Do Nothing load 13
42833 Add Load 14 Read 0: Do Nothing Indicates add Load Add
Command Only 1: Add Load command for Shed Control
Default: Do Nothing load 14
42834 Add Load 15 Read 0: Do Nothing Indicates add Load Add
Command Only 1: Add Load command for Shed Control
Default: Do Nothing load 15
42835 Add Load 16 Read 0: Do Nothing Indicates add Load Add
Command Only 1: Add Load command for Shed Control
Default: Do Nothing load 16
42836 Add Load 17 Read 0: Do Nothing Indicates add Load Add
Command Only 1: Add Load command for Shed Control
Default: Do Nothing load 17
42837 Add Load 18 Read 0: Do Nothing Indicates add Load Add
Command Only 1: Add Load command for Shed Control
Default: Do Nothing load 18
42838 Shed Level 10 Read 0: Do Nothing Indicates status Load Add
Command Only 1: Shed Level of shed level 10 Shed Control
Default: Do Nothing
42839 Shed Level 11 Read 0: Do Nothing Indicates status Load Add
Command Only 1: Shed Level of shed level 11 Shed Control
Default: Do Nothing
42840 Shed Level 12 Read 0: Do Nothing Indicates status Load Add
Command Only 1: Shed Level of shed level 12 Shed Control
Default: Do Nothing
42841 Shed Level 13 Read 0: Do Nothing Indicates status Load Add
Command Only 1: Shed Level of shed level 13 Shed Control
Default: Do Nothing
42842 Shed Level 14 Read 0: Do Nothing Indicates status Load Add
Command Only 1: Shed Level of shed level 14 Shed Control
Default: Do Nothing
42843 Shed Level 15 Read 0: Do Nothing Indicates status Load Add
Command Only 1: Shed Level of shed level 15 Shed Control
Default: Do Nothing
42844 Shed Level 16 Read 0: Do Nothing Indicates status Load Add
Command Only 1: Shed Level of shed level 16 Shed Control
Default: Do Nothing
42845 Shed Level 17 Read 0: Do Nothing Indicates status Load Add
Command Only 1: Shed Level of shed level 17 Shed Control
Default: Do Nothing
42846 Shed Load 11 Read 0: Do Nothing Indicates shed Load Add
Command Only 1: Shed Load command for Shed Control
Default: Do Nothing load 11
42847 Shed Load 12 Read 0: Do Nothing Indicates shed Load Add
Command Only 1: Shed Load command for Shed Control
Default: Do Nothing load 12

526
Addr. System Name Access Specifications Description Function
42848 Shed Load 13 Read 0: Do Nothing Indicates shed Load Add
Command Only 1: Shed Load command for Shed Control
Default: Do Nothing load 13
42849 Shed Load 14 Read 0: Do Nothing Indicates shed Load Add
Command Only 1: Shed Load command for Shed Control
Default: Do Nothing load 14
42850 Shed Load 15 Read 0: Do Nothing Indicates shed Load Add
Command Only 1: Shed Load command for Shed Control
Default: Do Nothing load 15
42851 Shed Load 16 Read 0: Do Nothing Indicates shed Load Add
Command Only 1: Shed Load command for Shed Control
Default: Do Nothing load 16
42852 Shed Load 17 Read 0: Do Nothing Indicates shed Load Add
Command Only 1: Shed Load command for Shed Control
Default: Do Nothing load 17
42853 Shed Load 18 Read 0: Do Nothing Indicates shed Load Add
Command Only 1: Shed Load command for Shed Control
Default: Do Nothing load 18
42854 Restore Shed Read/ 0: Do Nothing Indicates if shed Load Add
Level 10 Com- Write 1: Restore Level level 10 has been Shed Control
mand Default: Do Nothing restored
42855 Restore Shed Read/ 0: Do Nothing Indicates if shed Load Add
Level 11 Com- Write 1: Restore Level level 11 has been Shed Control
mand Default: Do Nothing restored
42856 Restore Shed Read/ 0: Do Nothing Indicates if shed Load Add
Level 12 Com- Write 1: Restore Level level 12 has been Shed Control
mand Default: Do Nothing restored
42857 Restore Shed Read/ 0: Do Nothing Indicates if shed Load Add
Level 13 Com- Write 1: Restore Level level 13 has been Shed Control
mand Default: Do Nothing restored
42858 Restore Shed Read/ 0: Do Nothing Indicates if shed Load Add
Level 14 Com- Write 1: Restore Level level 14 has been Shed Control
mand Default: Do Nothing restored
42859 Restore Shed Read/ 0: Do Nothing Indicates if shed Load Add
Level 15 Com- Write 1: Restore Level level 15 has been Shed Control
mand Default: Do Nothing restored
42860 Restore Shed Read/ 0: Do Nothing Indicates if shed Load Add
Level 16 Com- Write 1: Restore Level level 16 has been Shed Control
mand Default: Do Nothing restored
42861 Restore Shed Read/ 0: Do Nothing Indicates if shed Load Add
Level 17 Com- Write 1: Restore Level level 17 has been Shed Control
mand Default: Do Nothing restored
42862 Gen9 Online Read Multiplier: Unit: Hours Total online time System Infor-
Time Only .000277777780 Lower Limit: .000 for Gen9 mation
Offset: 0 Hours
Size (bits): 32 Upper Limit:
Sign: U 1193046.00 Hours
Default: 0

527
Addr. System Name Access Specifications Description Function
42864 Gen10 Online Read Multiplier: Unit: Hours Total online time System Infor-
Time Only .000277777780 Lower Limit: .000 for Gen10 mation
Offset: 0 Hours
Size (bits): 32 Upper Limit:
Sign: U 1193046.00 Hours
Default: 0

42866 Gen11 Online Read Multiplier: Unit: Hours Total online time System In-
Time Only .000277777780 Lower Limit: .000 for Gen11 formation
Offset: 0 Hours
Size (bits): 32 Upper Limit:
Sign: U 1193046.00 Hours
Default: 0

42868 Gen12 Online Read Multiplier: Unit: Hours Total online time System In-
Time Only .000277777780 Lower Limit: .000 for Gen12 formation
Offset: 0 Hours
Size (bits): 32 Upper Limit:
Sign: U 1193046.00 Hours
Default: 0

42870 Gen13 Online Read Multiplier: Unit: Hours Total online time System In-
Time Only .000277777780 Lower Limit: .000 for Gen13 formation
Offset: 0 Hours
Size (bits): 32 Upper Limit:
Sign: U 1193046.00 Hours
Default: 0

42872 Gen14 Online Read Multiplier: Unit: Hours Total online time System In-
Time Only .000277777780 Lower Limit: .000 for Gen14 formation
Offset: 0 Hours
Size (bits): 32 Upper Limit:
Sign: U 1193046.00 Hours
Default: 0

42874 Gen15 Online Read Multiplier: Unit: Hours Total online time System In-
Time Only .000277777780 Lower Limit: .000 for Gen15 formation
Offset: 0 Hours
Size (bits): 32 Upper Limit:
Sign: U 1193046.00 Hours
Default: 0

42876 Gen16 Online Read Multiplier: Unit: Hours Total online time System In-
Time Only .000277777780 Lower Limit: .000 for Gen16 formation
Offset: 0 Hours
Size (bits): 32 Upper Limit:
Sign: U 1193046.00 Hours
Default: 0

42878 Manual Add Read/ 0: Do Nothing Operator input to Load Add


Level 11 Com- Write 1: Add Level add loads as- Shed Control
mand Default: Do Nothing signed to level 11

42879 Manual Add Read/ 0: Do Nothing Operator input to Load Add


Level 12 Com- Write 1: Add Level add loads as- Shed Control
mand Default: Do Nothing signed to level 12

528
Addr. System Name Access Specifications Description Function
42880 Manual Add Read/ 0: Do Nothing Operator input to Load Add
Level 13 Com- Write 1: Add Level add loads as- Shed Control
mand Default: Do Nothing signed to level 13
42881 Manual Add Read/ 0: Do Nothing Operator input to Load Add
Level 14 Com- Write 1: Add Level add loads as- Shed Control
mand Default: Do Nothing signed to level 14
42882 Manual Add Read/ 0: Do Nothing Operator input to Load Add
Level 15 Com- Write 1: Add Level add loads as- Shed Control
mand Default: Do Nothing signed to level 15
42883 Manual Add Read/ 0: Do Nothing Operator input to Load Add
Level 16 Com- Write 1: Add Level add loads as- Shed Control
mand Default: Do Nothing signed to level 16
42884 Manual Add Read/ 0: Do Nothing Operator input to Load Add
Level 17 Com- Write 1: Add Level add loads as- Shed Control
mand Default: Do Nothing signed to level 17
42885 Manual Add Read/ 0: Do Nothing Operator input to Load Add
Level 18 Com- Write 1: Add Level add loads as- Shed Control
mand Default: Do Nothing signed to level 18
42886 Manual Shed Read/ 0: Do Nothing Operator input to Load Add
Level 10 Com- Write 1: Shed Level shed loads as- Shed Control
mand Default: Do Nothing signed to level 10
42887 Manual Shed Read/ 0: Do Nothing Operator input to Load Add
Level 11 Com- Write 1: Shed Level shed loads as- Shed Control
mand Default: Do Nothing signed to level 11
42888 Manual Shed Read/ 0: Do Nothing Operator input to Load Add
Level 12 Com- Write 1: Shed Level shed loads as- Shed Control
mand Default: Do Nothing signed to level 12
42889 Manual Shed Read/ 0: Do Nothing Operator input to Load Add
Level 13 Com- Write 1: Shed Level shed loads as- Shed Control
mand Default: Do Nothing signed to level 13
42890 Manual Shed Read/ 0: Do Nothing Operator input to Load Add
Level 14 Com- Write 1: Shed Level shed loads as- Shed Control
mand Default: Do Nothing signed to level 14
42891 Manual Shed Read/ 0: Do Nothing Operator input to Load Add
Level 15 Com- Write 1: Shed Level shed loads as- Shed Control
mand Default: Do Nothing signed to level 15
42892 Manual Shed Read/ 0: Do Nothing Operator input to Load Add
Level 16 Com- Write 1: Shed Level shed loads as- Shed Control
mand Default: Do Nothing signed to level 16
42893 Manual Shed Read/ 0: Do Nothing Operator input to Load Add
Level 17 Com- Write 1: Shed Level shed loads as- Shed Control
mand Default: Do Nothing signed to level 17
42894 Load 11 De- Read/ 0: None Indicates type of Load Add
vice Type Write 1: Breaker load connected Shed Control
2: ATS to load 11 add
Default: None shed control and
status I/O

529
Addr. System Name Access Specifications Description Function
42895 Load 12 De- Read/ 0: None Indicates type of Load Add
vice Type Write 1: Breaker load connected Shed Control
2: ATS to load 12 add
Default: None shed control and
status I/O
42896 Load 13 De- Read/ 0: None Indicates type of Load Add
vice Type Write 1: Breaker load connected Shed Control
2: ATS to load 13 add
Default: None shed control and
status I/O
42897 Load 14 De- Read/ 0: None Indicates type of Load Add
vice Type Write 1: Breaker load connected Shed Control
2: ATS to load 14 add
Default: None shed control and
status I/O
42898 Load 15 De- Read/ 0: None Indicates type of Load Add
vice Type Write 1: Breaker load connected Shed Control
2: ATS to load 15 add
Default: None shed control and
status I/O
42899 Load 16 De- Read/ 0: None Indicates type of Load Add
vice Type Write 1: Breaker load connected Shed Control
2: ATS to load 16 add
Default: None shed control and
status I/O
42900 Load 17 De- Read/ 0: None Indicates type of Load Add
vice Type Write 1: Breaker load connected Shed Control
2: ATS to load 17 add
Default: None shed control and
status I/O
42901 Load 18 De- Read/ 0: None Indicates type of Load Add
vice Type Write 1: Breaker load connected Shed Control
2: ATS to load 18 add
Default: None shed control and
status I/O
42902 Load 11 Add Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 add level load 11 Shed Control
Offset: 0 Upper Limit: 18.000 is assigned to
Size (bits): 0 Default: 11
Sign: U
42903 Load 12 Add Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 add level load 12 Shed Control
Offset: 0 Upper Limit: 18.000 is assigned to
Size (bits): 0 Default: 12
Sign: U
42904 Load 13 Add Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 add level load 13 Shed Control
Offset: 0 Upper Limit: 18.000 is assigned to
Size (bits): 0 Default: 13
Sign: U

530
Addr. System Name Access Specifications Description Function
42905 Load 14 Add Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 add level load 14 Shed Control
Offset: 0 Upper Limit: 18.000 is assigned to
Size (bits): 0 Default: 14
Sign: U
42906 Load 15 Add Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 add level load 15 Shed Control
Offset: 0 Upper Limit: 18.000 is assigned to
Size (bits): 0 Default: 15
Sign: U
42907 Load 16 Add Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 add level load 16 Shed Control
Offset: 0 Upper Limit: 18.000 is assigned to
Size (bits): 0 Default: 16
Sign: U
42908 Load 17 Add Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 add level load 17 Shed Control
Offset: 0 Upper Limit: 18.000 is assigned to
Size (bits): 0 Default: 17
Sign: U
42909 Load 18 Add Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: 1.000 add level load 18 Shed Control
Offset: 0 Upper Limit: 18.000 is assigned to
Size (bits): 0 Default: 18
Sign: U
42910 Load 11 Shed Read/ Multiplier: Unit: NA Indicates which Load Add
Level Write 1.000000000000 Lower Limit: .000 shed level load Shed Control
Offset: 0 Upper Limit: 17.000 11 is assigned to
Size (bits): 0 Default: 10
Sign: U
42911 Load 12 Shed Read Multiplier: Unit: NA Indicates which Load Add
Level /Write 1.000000000000 Lower Limit: .000 shed level load Shed Control
Offset: 0 Upper Limit: 17.000 12 is assigned to
Size (bits): 0 Default: 11
Sign: U
42912 Load 13 Shed Read Multiplier: Unit: NA Indicates which Load Add
Level /Write 1.000000000000 Lower Limit: .000 shed level load Shed Control
Offset: 0 Upper Limit: 17.000 13 is assigned to
Size (bits): 16 Default: 12
Sign: U
42913 Load 14 Shed Read Multiplier: Unit: NA Indicates which Load Add
Level /Write 1.000000000000 Lower Limit: .000 shed level load Shed Control
Offset: 0 Upper Limit: 17.000 14 is assigned to
Size (bits): 16 Default: 13
Sign: U
42914 Load 15 Shed Read Multiplier: Unit: NA Indicates which Load Add
Level /Write 1.000000000000 Lower Limit: .000 shed level load Shed Control
Offset: 0 Upper Limit: 17.000 15 is assigned to
Size (bits): 16 Default: 14
Sign: U

531
Addr. System Name Access Specifications Description Function
42915 Load 16 Shed Read Multiplier: Unit: NA Indicates which Load Add
Level /Write 1.000000000000 Lower Limit: .000 shed level load Shed Control
Offset: 0 Upper Limit: 17.000 16 is assigned to
Size (bits): 16 Default: 15
Sign: U

42916 Load 17 Shed Read Multiplier: Unit: NA Indicates which Load Add
Level /Write 1.000000000000 Lower Limit: .000 shed level load Shed Control
Offset: 0 Upper Limit: 17.000 17 is assigned to
Size (bits): 16 Default: 16
Sign: U

42917 Load 18 Shed Read Multiplier: Unit: NA Indicates which Load Add
Level /Write 1.000000000000 Lower Limit: .000 shed level load Shed Control
Offset: 0 Upper Limit: 17.000 18 is assigned to
Size (bits): 16 Default: 17
Sign: U

42918 Load Demand Read 0: Gen 1 Sets GenI for Load Demand
GenI /Write 1: Gen 2 fixed sequence Shed Control
2: Gen 3 load demand
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8
8: Gen 9
9: Gen 10
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen9

42919 Load Demand Read 0: Gen 1 Sets GenJ for Load Demand
GenJ /Write 1: Gen 2 fixed sequence Shed Control
2: Gen 3 load demand
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8
8: Gen 9
9: Gen 10
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen10

532
Addr. System Name Access Specifications Description Function
42920 Load Demand Read 0: Gen 1 Sets GenK for Load Demand
GenK /Write 1: Gen 2 fixed sequence Shed Control
2: Gen 3 load demand
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8
8: Gen 9
9: Gen 10
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen11

42921 Load Demand Read 0: Gen 1 Sets GenL for Load Demand
GenL /Write 1: Gen 2 fixed sequence Shed Control
2: Gen 3 load demand
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8
8: Gen 9
9: Gen 10
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen12

42922 Load Demand Read 0: Gen 1 Sets GenM for Load Demand
GenM /Write 1: Gen 2 fixed sequence Control
2: Gen 3 load demand
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8
8: Gen 9
9: Gen 10
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen13

533
Addr. System Name Access Specifications Description Function
42923 Load Demand Read 0: Gen 1 Sets GenN for Load Demand
GenN /Write 1: Gen 2 fixed sequence Control
2: Gen 3 load demand
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8
8: Gen 9
9: Gen 10
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen14

42924 Load Demand Read 0: Gen 1 Sets GenO for Load Demand
GenO /Write 1: Gen 2 fixed sequence Control
2: Gen 3 load demand
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8
8: Gen 9
9: Gen 10
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen15

42925 Load Demand Read 0: Gen 1 Sets GenP for Load Demand
GenP /Write 1: Gen 2 fixed sequence Control
2: Gen 3 load demand
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8
8: Gen 9
9: Gen 10
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen16

534
Addr. System Name Access Specifications Description Function
42926 SID2 Status Read 0: Missing Indicates status Communica-
Only 1: Good of SID2 tions
2: Connecting (aux101/102
3: No Exp Board module 2)
4: Not Applicable
Default:
42927 SID3 Status Read 0: Missing Indicates status Communica-
Only 1: Good of SID3 tions
2: Connecting (aux101/102
3: No Exp Board module 3)
4: Not Applicable
Default:
42928 Expansion Read 0: Disabled Indicates the sta- Communica-
Board Com- Only 1: Enabled tus of the SID2 to tions
munications 2 2: Connecting expansion board
Default: Disabled connection
42929 Expansion Read 0: Disabled Indicates the sta- Communica-
Board Com- Only 1: Enabled tus of the SID3 to tions
munications 3 2: Connecting expansion board
Default: Disabled connection
42930 Utility Breaker Read 0: After Transfer Delay PTC − point in PTC Con-
Opening Point /Write 1: Upon Utility Failure time at which nected
Default: After Transfer Delay system opens
utility breaker
42931 Commit To Read 0: Utility Disconnect PTC − sets point PTC Operat-
Transfer Meth- /Write 1: Genset Start at which system ing Mode
od 2: No Commit commits to trans-
Default: Utility Disconnect fer to generator
set
42932 Commit To Read 0: Not Committed PTC − indicates if PTC Operat-
Transfer State Only 1: Committed system is com- ing Mode
Default: mitted to transfer-
ring to generator
set
42933 Total System Read Multiplier: Unit: kW Sum of the gen- System In-
Capacity 32bit Only 1.000000000000 Lower Limit: kW erator set kW rat- formation
Offset: 0 Upper Limit: kW ings in 32bit
Size (bits): 32 Default:
Sign: S
42935 Total Online Read Multiplier: Unit: kW Sum of the gen- System Infor-
Capacity 32bit Only 1.000000000000 Lower Limit: kW erator set kW rat- mation
Offset: 0 Upper Limit: kW ings in 32bit for
Size (bits): 32 Default: generator sets
Sign: S which are online
42937 kW Load Ref- Read Multiplier: Unit: kW kW control refer- Master Load
erence 32bit Only 1.000000000000 Lower Limit: kW ence value in Control
Offset: 0 Upper Limit: kW 32bit for ex-
Size (bits): 3 Default: tended paralel-
2Sign: S ling

535
Addr. System Name Access Specifications Description Function
42939 kVAR Load Read Multiplier: Unit: kVAR kVAR control ref- Master Load
Reference Only 1.000000000000 Lower Limit: kVAR erence value in Control
32bit Offset: 0 Upper Limit: kVAR 32bit for ex-
Size (bits): 32 Default: tended parallel-
Sign: S ing
42943 Genset Bus Read Multiplier: Unit: kW Sets the base Master Load
kW Setpoint /Write 1.000000000000Off- Lower Limit: .000 kW load kW setpoint Control
32bit set: 0Size (bits): Upper Limit: in 32bit in closed
32Sign: S 2147483647.000 loop extended
kW paralleling
Default:0
42945 Genset Bus Read Multiplier: Unit: kVAR Sets the base Master Load
kVAR Setpoint /Write 1.000000000000 Lower Limit: .000 load kVAR set- Control
32bit Offset: 0 kVAR point in 32bit in
Size (bits): 32 Upper Limit: closed loop ex-
Sign: S 2147483647.000 tended parallel-
kVAR ing
Default:0
42947 Genset Un- Read Multiplier: Unit: kW Setpoint for gen- Master Load
loaded Level /Write 1.000000000000 Lower Limit: erator set un- Control
32bit Offset: 0 −2147483648.000 loaded level in
Size (bits): 32 kW 32bit
Sign: S Upper Limit:
2147483647.000
kWDefault:50
42949 Utility Bus kW Read Multiplier: Unit: kW Sets the peak Master Load
Setpoint 32bit /Write 1.000000000000 Lower Limit: shave kW set- Control
Offset: 0 −2147483648.000 point in 32bit in
Size (bits): 32 kW closed loop ex-
Sign: S Upper Limit: tended parallel-
2147483647.000 ing
kWDefault: 100
42951 Utility Bus kW Read / Multiplier: Unit: kW sets the utility kW Master Load
Constraint write 1.000000000000 Lower Limit: constraint level in Control
Level 32bit Offset: 0 −2147483648.000 32bit for base
Size (bits): 32 kW load extended
Sign: S Upper Limit: paralleling
2147483647.000
kWDefault: 100
42953 Utility Bus Read / Multiplier: Unit: kVAR Sets the peak Master Load
kVAR Setpoint write 1.000000000000 Lower Limit: shave kVAR set- Control
32bit Offset: 0 −2147483648.000 point in 32bit in
Size (bits): 32 kVAR closed loop ex-
Sign: S Upper Limit: tended parallel-
2147483647.000 ing
kVAR
Default: 100

536
Addr. System Name Access Specifications Description Function
42955 Utility Un- Read / Multiplier: Unit: kW Setpoint for utility Master Load
loaded Level write 1.000000000000 Lower Limit: unload level in Control
32bit Offset: 0 −2147483648.000 32bit
Size (bits): 32 kW
Sign: S Upper Limit:
2147483647.000
kWDefault: 50
42957 Load Add Read / Multiplier: Unit: kW generator set kW Load Demand
Shed Re- write 1.000000000000 Lower Limit: .000 kW capacity that Control
quired Online Offset: 0 Upper Limit: must be online to
Capacity 32bit Size (bits): 32 2147483647.000 start timed load
Sign: S kWDefault: 0 add; 0 disables
this
42959 Load Demand Read / Multiplier: Unit: kW Sets how much Load Demand
Minimum On- write 1.000000000000 Lower Limit: .000 kW capacity must al- Control
line Capacity Offset: 0 Upper Limit: ways be online
32bit Size (bits): 32 2147483647.000 regardless of
Sign: S kWDefault: 0 what the load is
42961 Total Utility Read / Multiplier: Unit: kW Use to set how AC Setup
Capacity 32bit write 1.000000000000 Lower Limit: 1.000 many kW (32bit)
Offset: 0 kW =100% utility kW
Size (bits): 32 Upper Limit: −− used by bar-
Sign: S 2147483647.000 graph
kWDefault: 1000
42963 Genset Online Read / Multiplier: Unit: kW Set the online kW PTC Sensors
Capacity Sen- write 1.000000000000 Lower Limit: .000 kW threshold 32bit at
sor Threshold Offset: 0 Upper Limit: which generator
32bit Size (bits): 32 2147483647.000 set but is avail-
Sign: S kWDefault: 0 able for loading
42965 Load Demand Read Multiplier: Unit: kW Set minimum kW Load Demand
Restart kW /Write 1.000000000000 Lower Limit: .000 kW reserve capacity Control
Threshold Offset: 0 Upper Limit: when kW in 32bit
32bit Size (bits): 32 2147483647.000
Sign: S kWDefault: 500
42967 Load Demand Read / Multiplier: Unit: kW Sets maximum Load Demand
Shutdown kW write 1.000000000000 Lower Limit: .000 kW kW reserve ca- Control
Threshold Offset: 0 Upper Limit: pacity when
32bit Size (bits): 32 2147483647.000 kw threshold method
Sign: S Default: 1000 is absolute kW in
32bit
42971 Total Spare Read Multiplier: Unit: kW Difference be- System In-
Online Capac- Only 1.000000000000 Lower Limit: kW tween sensed formation
ity 32bit Offset: 0 Upper Limit: kW online capacity
Size (bits): 32 Default: and generator
Sign: S Set bus total kW
in 32bit

537
Addr. System Name Access Specifications Description Function
42973 Next Gen Re- Read Multiplier: Unit: kW Shows 32 bit kW Load Demand
start Thresh- Only 1.000000000000 Lower Limit: kW threshold for gen- Control
old 32bit Offset: 0 Upper Limit: kW erator bus at
Size (bits): 32 Default: which next gen-
Sign: S erator set will re-
start
42975 Next Gen Read Multiplier: Unit: kW Shows 32 bit kW Load Demand
Shutdown Only 1.000000000000 Lower Limit: kW threshold for gen- Control
Threshold Offset: 0 Upper Limit: kW erator bus at
32bit Size (bits): 32 Default: which next gen-
Sign: S erator set load
demand stops in

42977 Genset Bus Read Multiplier: Unit: kW Calculated kW System Infor-


kW Overload Only 1.000000000000 Lower Limit: kW overload thresh- mation
Threshold Offset: 0 Upper Limit: kW old in 32bit based
32bit Size(bits): 32 Default: on online capac-
Sign:S ity and % setting

538
11. MCM3320 Modbus Fault Status Bitmaps

Note: Earlier versions of software may not support all of the Modbus registers in the following table. If a particu-
lar register is not available in your installation, it is possible that the Modbus connection is working but the con-
troller software does not support that particular register.

Note: If an address or bit is not listed in this table it is not used.

Addr. Bit# System Name Fault Event Name Response


Code
42500 0 Fault Status Bit- 1455 Utility Main Breaker Position Contact Warning Warning
map 1
42500 1 Fault Status Bit- 2396 Utility Main Breaker Fail To Close Warning Warning
map 1
42500 2 Fault Status Bit- 2397 Utility Main Breaker Fail To Open Warning Warning
map 1
42500 3 Fault Status Bit- 1219 Utility Main Breaker Tripped Warning Warning
map 1
42500 4 Fault Status Bit- 1914 Utility Bus Phase Rotation Warning Warning
map 1
42500 5 Fault Status Bit- 1912 Utility Bus Loss Of Phase Warning Warning
map 1
42500 6 Fault Status Bit- 2331 Utility Bus Undervoltage Warning Warning
map 1
42500 7 Fault Status Bit- 2358 Utility Bus Overvoltage Warning Warning
map 1
42500 8 Fault Status Bit- 1223 Utility Bus Frequency Warning Warning
map 1
42500 21 Fault Status Bit- 4137 Advanced Grid Protection Warning Warning
map 1
42500 22 Fault Status Bit- 3924 Utility Reverse kW Warning Warning
map 1
42500 23 Fault Status Bit- 2939 Modbus Communication Failure Warning Warning
map 1
42500 24 Fault Status Bit- 2648 Remote IO Communication Failure Warning Warning
map 1
42500 25 Fault Status Bit- 1689 Real Time Clock Power Interrupt Warning Warning
map 1
42500 26 Fault Status Bit- 1335 AC Metering Out Of Range Warning Warning
map 1
42500 27 Fault Status Bit- 1999 Maximum Parallel Time Warning Warning
map 1
42500 28 Fault Status Bit- 343 Hardware Failure Warning Warning
map 1

539
Addr. Bit# System Name Fault Event Name Response
Code
42500 29 Fault Status Bit- 1456 Synchronizer Output Limit Warning Warning
map 1
42500 30 Fault Status Bit- 2416 Calibration Checksum Warning Warning
map 1
42500 31 Fault Status Bit- 353 EEPROM Write Error Warning Warning
map 1
42502 0 Fault Status Bit- 1454 Genset Main Breaker Position Contact Warning Warning
map 2
42502 1 Fault Status Bit- 1452 Genset Main Breaker Fail To Close Warning Warning
map 2
42502 2 Fault Status Bit- 1453 Genset Main Breaker Fail To Open Warning
map 2
42502 3 Fault Status Bit- 1328 Genset Main Breaker Tripped Warning Warning
map 2
42502 4 Fault Status Bit- 1915 Genset Bus Phase Rotation Warning Warning
map 2
42502 5 Fault Status Bit- 1913 Genset Bus Loss Of Phase Warning Warning
map 2
42502 6 Fault Status Bit- 1225 Genset Bus Undervoltage Warning Warning
map 2
42502 7 Fault Status Bit- 1224 Genset Bus Overvoltage Warning Warning
map 2
42502 8 Fault Status Bit- 1226 Genset Bus Frequency Warning Warning
map 2
42502 22 Fault Status Bit- 441 Low Battery Voltage Warning Warning
map 2
42502 23 Fault Status Bit- 442 High Battery Voltage Warning Warning
map 2
42502 24 Fault Status Bit- 1541 Genset Failed To Come Online Warning Warning
map 2
42502 25 Fault Status Bit- 2647 Load Demand Setup Warning Warning
map 2
42502 26 Fault Status Bit- 1444 Genset Bus Overload Warning Warning
map 2
42502 27 Fault Status Bit- 1989 kW Load Control Output Limit Warning Warning
map 2
42502 28 Fault Status Bit- 1991 kVAR Load Control Output Limit Warning Warning
map 2
42502 29 Fault Status Bit- 1121 Failure To Disconnect Warning Warning
map 2
42502 30 Fault Status Bit- 1458 Synchronizer Phase Rotation Mismatch Warn- Warning
map 2 ing

540
Addr. Bit# System Name Fault Event Name Response
Code
42502 31 Fault Status Bit- 1457 Fail To Synchronize Warning Warning
map 2
42504 0 Fault Status Bit- 1222 Not In Automatic Event Event
map 1
42504 1 Fault Status Bit- 1483 Common Warning Event Event
map 1
42504 2 Fault Status Bit- 2965 Genset Bus Available Event Event
map 1
42504 3 Fault Status Bit- 2328 Utility Bus Available Event Event
map 1
42504 4 Fault Status Bit- 2333 Genset Bus Connected Event Event
map 1
42504 5 Fault Status Bit- 2332 Utility Bus Connected Event Event
map 1
42504 6 Fault Status Bit- 2971 Test / Extended Parallel Event Event
map 1
42504 7 Fault Status Bit- 1916 Synchronized Event Event
map 1
42504 8 Fault Status Bit- 1534 Load Control Output Event Event
map 1
42504 9 Fault Status Bit- 2781 Genset Source Unloaded Event Event
map 1
42504 10 Event Status Bit- 2779 Utility Source Unloaded Event Event
map 1
42504 11 Event Status Bit- 3226 Genset Bus Base Load Event Event
map 1
42504 12 Event Status Bit- 3227 Utility Bus Peak Shave Event Event
map 1

541
THIS PAGE LEFT INTENTIONALLY BLANK

542
12. MCM3320 Modbus Address 42506, 42507

Metering Fault Status Bitmaps


Bit (LSB = 0) Parameter Description
0 ZXA Timeout Zero Crossing cannot be detected on L1 voltage signal
1 ZXB Timeout Zero Crossing cannot be detected on L2 voltage signal
2 ZXC Timeout Zero Crossing cannot be detected on L3 voltage signal
3 (See Note 1) Voltage Out o Voltage scaling error due to incompatible combination of
Range settings for Nominal Voltage, PT Primary Voltage, and PT
Secondary Voltage
4 (See Note 1) Current Out of Current Input is saturated; actual current cannot be deter-
Range mined
5 Frequency Out Frequency input is out of range; valid range 24−80 Hz
of Range
6 Loss Phase Out One or more zero crossings of voltage cannot be de-
of Range tected; loss phase cannot be determined
7 Sync Phase Out Synchronizer phase difference cannot be measured due
of Range to any of the following: genset frequency out of range, util-
ity frequency out of range, genset L1 voltage zero cross-
ing not detected, or utility L1 voltage zero crossing not
detected
8 (See Note 1) kW Out of kW is out of range; valid range is − 2147483648 to
Range +2147483647 kW
9 (See Note 1) kVAR Out of kVAR is out of range; valid range is − 2147483648 to
Range +2147483647 kVAR
10 (See Note 1) kVA Out of kVA is out of range; valid range is 0 to 4294867295 kVA
Range
11 (See Note 1) Power Factor Power factor is out of range due to either kW > kVA or
Out of Range kVA = 0; should not normally occur
12 AC Metering Main processor is unable to communicate with metering
Failure processor
13 Not Used
14 Not Used
15 Not Used
Note:
1. If any of bits are active (1), the “AC Metering Out of Range Warning” fault will be active.
2. If Bit 12 is active (1), the “Hardware Failure Warning” fault will be active.
3. Some bits do not generate warning faults because they are a normal occurance (e.g. if a source is dead).

543
THIS PAGE LEFT INTENTIONALLY BLANK

544
13. PC500/550 Modbus TCP Register Map

PC500/550 (PC5xx)
Parameter Modbus Sign Units Comments
Register
Device Type in Configuration 40001 U ENUM 64= PC500/PC550
Device Model 40002 U ENUM 0=N/A, 1=3300, 2=2300, 4=1301,
8=1302, 16=2100, 32=3100, 64=3200,
128=3201
Modbus TCP Unit ID 40003 U Configurable from User Interface
Modbus Communication Status 40004 U ENUM 0=Communicating,
2=Not Communicating
Communications Error Counter 40005 U
Last Successful Communication 40006 U Bitfield See Note 5
(Year, Month)
Last Successful Communication 40007 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication 40008 U Bitfield See Note 5
(Seconds, Milliseconds)

PC500/550 (Device 1)
Parameter Modbus Sign Units Comments
Register
Device Type in Configuration 40011 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
Device Model 40012 U ENUM 0=N/A, 1=3300, 2=2300, 4=1301,
8=1302, 16=2100, 32=3100, 64=3200,
128=3201
Modbus TCP Unit ID 40013 U Configurable from User Interface
Modbus Communication Status 40014 U ENUM 0=Communicating,
2=Not Communicating
Communications Error Counter 40015 U
Last Successful Communication 40016 U Bitfield See Note 5
(Year, Month)
Last Successful Communication 40017 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication 40018 U Bitfield See Note 5
(Seconds, Milliseconds)

PC500/550 (Device 2)
Parameter Modbus Sign Units Comments
Register
Device Type in Configuration 40021 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
Device Model 40022 U ENUM 0=N/A, 1=3300, 2=2300, 4=1301,
8=1302, 16=2100, 32=3100, 64=3200,
128=3201
Modbus TCP Unit ID 40023 U Configurable from User Interface

545
Parameter Modbus Sign Units Comments
Register
Modbus Communication Status 40024 U ENUM 0=Communicating,
2=Not Communicating
Communications Error Counter 40025 U
Last Successful Communication 40026 U Bitfield See Note 5
(Year, Month)
Last Successful Communication 40027 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication 40028 U Bitfield See Note 5
(Seconds, Milliseconds)

PC500/550 (Device 3)
Parameter Modbus Sign Units Comments
Register
Device Type in Configuration 40031 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
Device Model 40032 U ENUM 0=N/A, 1=3300, 2=2300, 4=1301,
8=1302, 16=2100, 32=3100, 64=3200,
128=3201
Modbus TCP Unit ID 40033 U Configurable from User Interface
Modbus Communication Status 40034 U ENUM 0=Communicating,
2=Not Communicating
Communications Error Counter 40035 U
Last Successful Communication 40036 U Bitfield See Note 5
(Year, Month)
Last Successful Communication 40037 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication 40038 U Bitfield See Note 5
(Seconds, Milliseconds)

PC500/550 (Device 4)
Parameter Modbus Sign Units Comments
Register
Device Type in Configuration 40041 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
Device Model 40042 U ENUM 0=N/A, 1=3300, 2=2300, 4=1301,
8=1302, 16=2100, 32=3100, 64=3200,
128=3201
Modbus TCP Unit ID 40043 U Configurable from User Interface
Modbus Communication Status 40044 U ENUM 0=Communicating,
2=Not Communicating
Communications Error Counter 40045 U
Last Successful Communication 40046 U Bitfield See Note 5
(Year, Month)
Last Successful Communication 40047 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication 40048 U Bitfield See Note 5
(Seconds, Milliseconds)

546
PC500/550 (Device 5)
Parameter Modbus Sign Units Comments
Register
Device Type in Configuration 40051 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
Device Model 40052 U ENUM 0=N/A, 1=3300, 2=2300, 4=1301,
8=1302, 16=2100, 32=3100, 64=3200,
128=3201
Modbus TCP Unit ID 40053 U Configurable from User Interface
Modbus Communication Status 40054 U ENUM 0=Communicating,
2=Not Communicating
Communications Error Counter 40055 U
Last Successful Communication 40056 U Bitfield See Note 5
(Year, Month)
Last Successful Communication 40057 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication 40058 U Bitfield See Note 5
(Seconds, Milliseconds)

PC500/550 (Device 6)
Parameter Modbus Sign Units Comments
Register
Device Type in Configuration 40061 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
Device Model 40062 U ENUM 0=N/A, 1=3300, 2=2300, 4=1301,
8=1302, 16=2100, 32=3100, 64=3200,
128=3201
Modbus TCP Unit ID 40063 U Configurable from User Interface
Modbus Communication Status 40064 U ENUM 0=Communicating,
2=Not Communicating
Communications Error Counter 40065 U
Last Successful Communication 40066 U Bitfield See Note 5
(Year, Month)
Last Successful Communication 40067 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication 40068 U Bitfield See Note 5
(Seconds, Milliseconds)

PC500/550 (Device 7)
Parameter Modbus Sign Units Comments
Register
Device Type in Configuration 40071 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
Device Model 40072 U ENUM 0=N/A, 1=3300, 2=2300, 4=1301,
8=1302, 16=2100, 32=3100, 64=3200,
128=3201
Modbus TCP Unit ID 40073 U Configurable from User Interface
Modbus Communication Status 40074 U ENUM 0=Communicating,
2=Not Communicating
Communications Error Counter 40075 U

547
Parameter Modbus Sign Units Comments
Register
Last Successful Communication 40076 U Bitfield See Note 5
(Year, Month)
Last Successful Communication 40077 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication 40078 U Bitfield See Note 5
(Seconds, Milliseconds)

PC500/550 (Device 8)
Parameter Modbus Sign Units Comments
Register
Device Type in Configuration 40081 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
Device Model 40082 U ENUM 0=N/A, 1=3300, 2=2300, 4=1301,
8=1302, 16=2100, 32=3100, 64=3200,
128=3201
Modbus TCP Unit ID 40083 U Configurable from User Interface
Modbus Communication Status 40084 U ENUM 0=Communicating,
2=Not Communicating
Communications Error Counter 40085 U
Last Successful Communication 40086 U Bitfield See Note 5
(Year, Month)
Last Successful Communication 40087 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication 40088 U Bitfield See Note 5
(Seconds, Milliseconds)

PC500/550 (Device 9)
Parameter Modbus Sign Units Comments
Register
Device Type in Configuration 40091 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
Device Model 40092 U ENUM 0=N/A, 1=3300, 2=2300, 4=1301,
8=1302, 16=2100, 32=3100, 64=3200,
128=3201
Modbus TCP Unit ID 40093 U Configurable from User Interface
Modbus Communication Status 40094 U ENUM 0=Communicating,
2=Not Communicating
Communications Error Counter 40095 U
Last Successful Communication 40096 U Bitfield See Note 5
(Year, Month)
Last Successful Communication 40097 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication 40098 U Bitfield See Note 5
(Seconds, Milliseconds)

548
PC500/550 (Device 10)
Parameter Modbus Sign Units Comments
Register
Device Type in Configuration 40101 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
Device Model 40102 U ENUM 0=N/A, 1=3300, 2=2300, 4=1301,
8=1302, 16=2100, 32=3100, 64=3200,
128=3201
Modbus TCP Unit ID 40103 U Configurable from User Interface
Modbus Communication Status 40104 U ENUM 0=Communicating,
2=Not Communicating
Communications Error Counter 40105 U
Last Successful Communication 40106 U Bitfield See Note 5
(Year, Month)
Last Successful Communication 40107 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication 40108 U Bitfield See Note 5
(Seconds, Milliseconds)

PC500/550 (Device 11)


Parameter Modbus Sign Units Comments
Register
Device Type in Configuration 40111 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
Device Model 40112 U ENUM 0=N/A, 1=3300, 2=2300, 4=1301,
8=1302, 16=2100, 32=3100, 64=3200,
128=3201
Modbus TCP Unit ID 40113 U Configurable from User Interface
Modbus Communication Status 40114 U ENUM 0=Communicating,
2=Not Communicating
Communications Error Counter 40115 U
Last Successful Communication 40116 U Bitfield See Note 5
(Year, Month)
Last Successful Communication 40117 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication 40118 U Bitfield See Note 5
(Seconds, Milliseconds)

PC500/550 (Device 12)


Parameter Modbus Sign Units Comments
Register
Device Type in Configuration 40121 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
Device Model 40122 U ENUM 0=N/A, 1=3300, 2=2300, 4=1301,
8=1302, 16=2100, 32=3100, 64=3200,
128=3201
Modbus TCP Unit ID 40123 U Configurable from User Interface
Modbus Communication Status 40124 U ENUM 0=Communicating,
2=Not Communicating
Communications Error Counter 40125 U

549
Parameter Modbus Sign Units Comments
Register
Last Successful Communication 40126 U Bitfield See Note 5
(Year, Month)
Last Successful Communication 40127 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication 40128 U Bitfield See Note 5
(Seconds, Milliseconds)

Notes:
1. Modbus TCP can be enabled/disabled in the PC500/550 User Interface (Setup > Modbus Settings).
2. Default Modbus TCP port is 502 and is configurable in the PC500/550 User Inferface (Setup >
Modbus Settings). No more than 2 Modbus TCP sessions can be established at a time.
3. PC5xx provides READ ONLY access over Modbus TCP
4. PC500/550 registers return details about all configured devices in PC5xx (Generator Set, ATS
AUX101/102) and can be accessed using Modbus TCP Unit ID 255 (default for PC500/550).
5. In PC500/550 registers, Devices 1 through 12 are numbered in the same order as they are arranged in
the Interface Device Configuration grid. To access details of these devices over Modbus TCP, the user
must use the Modbus TCP Unit ID (returned by register 4xxx3) in the query.
6. Bitmap registers indicating Last Successful Communication (4xxx6, 4xxx7, 4xxx8) are formatted as below:

7. Site IOs (sensors) and AUX101/102 data cannot be accessed over Modbus TCP.

Generator Set
Modbus Scale Sign Units Description Comments
Register
40001 1 U ENUM Switch Position 0=Off, 1=AUTO, 2=Manual
40002 1 U ENUM Control State 0=Stopped, 1=Pending,
2=Warm Up, 3=Running,
4=Cool Down (rated),
5=Cool Down (idle)
40003 1 U Fault Code
40004 1 U ENUM Fault Type 0=Normal, 1=Warning,
2=Derate,
3=Shutdown w/Cooldown,
4=Shutdown
40005 1 U Bitfield NFPA110 See Section 4, Table 4−1
40006 1 U Bitfield NFPAExtended See Section 4, Table 4−2
40007 1 U Volts L1N Voltage
40008 1 U Volts L2N Voltage
40009 1 U Volts L3N Voltage
40010 1 U Volts L1L2 Voltage

550
Modbus Scale Sign Units Description Comments
Register
40011 1 U Volts L2L3 Voltage
40012 1 U Volts L3L1 Voltage
40013 1 U Amps L1 Current
40014 1 U Amps L2 Current
40015 1 U Amps L3 Current
40016 1 S kVA Total kVA
40017 0.01 U Hz Frequency
40018 0.1 U % PercentAmps APhase
40019 0.1 U % PercentAmps BPhase
40020 0.1 U % PercentAmps CPhase
40021 1 S kW Total kW
40022 0.01 S Total Power Factor
40023 0.01 S Volts Battery Voltage
40024 0.1 S psi Oil Pressure
40025 0.1 S F Oil Temperature
40026 0.1 S F Coolant Temperature
40027 1 U GPH Fuel Rate
40028 0.1 U Gallons Fuel Level
40029 1 U RPM Average Engine Speed
40030 1 U Engine Starts
40031 0.1 U Hours Engine Runtime

ATS
Modbus Scale Sign Units Description Comments
Register
40001 1 U ENUM Mode 0=Test 1=Utility/Genset,
2=Utility/Utility,
3=Genset/Genset
40002 1 U ENUM Active Transfer Timer 0=None,
1=EngineStartASource2,
2=EngineStartBSource1,
3=NormaltoEmergency (TDNE),
4=EmergencytoNormal (TDEN),
5=EngineCooldownA (TDECa),
6=EngineCooldownB (TDECb),
7=ProgramTransition (TDPT),
8=Transfer Pend./Elevator
(TDEL),
255=Unknown
40003 1 U Fault Code
40004 1 U ENUM Fault Type 0=No Faults, 1=Warning
40005 1 U Bitfield NFPA110 See Section 4, Table 4−3
40006 1 U Bitfield NFPAExtended See Section 4, Table 4−4

551
Modbus Scale Sign Units Description Comments
Register
40007 1 U Volts L1N Voltage (Load)
40008 1 U Volts L2N Voltage (Load)
40009 1 U Volts L3N Voltage (Load)
40010 1 U Volts L1L2 Voltage (Load)
40011 1 U Volts L2L3 Voltage (Load)
40012 1 U Volts L3L1 Voltage (Load)
40013 1 U Amps L1 Current (Load)
40014 1 U Amps L2 Current (Load)
40015 1 U Amps L3 Current (Load)
40016 1 S kW Total kW (Load)
40017 0.01 S Total Power Factor (Load)
40018 1 S kVAR Total kVAR (Load)
40019 1 S kVA Total kVA (Load)
40020 0.01 U Hz Frequency (Load)
40021 0.1 U % PercentAmps APhase (Load)
40022 0.1 U % PercentAmps BPhase (Load)
40023 0.1 U % PercentAmps CPhase (Load)
40024 1 U Volts L1N Voltage Source1
40025 1 U Volts L2N Voltage Source1
40026 1 U Volts L3N Voltage Source1
40027 1 U Volts L1L2 Voltage Source1
40028 1 U Volts L2L3 Voltage Source1
40029 1 U Volts L3L1 Voltage Source1
40037 0.01 U Hz Frequency Source1
40041 1 U Volts L1N Voltage Source2
40042 1 U Volts L2N Voltage Source2
40043 1 U Volts L3N Voltage Source2
40044 1 U Volts L1L2 Voltage Source2
40045 1 U Volts L2L3 Voltage Source2
40046 1 U Volts L3L1 Voltage Source2
40054 0.01 U Hz Frequency Source2

552
14. AUX101/102 Modbus Register Map

Addr. System Name Access Specifications Comments


43044 Modbus De- Read As supported by Default: Modbus Ad- Changing the address causes no
vice ID Only Modbus protocol dress 13 communication with the annun-
ciator until the Modbus Master
Type: Trim also changes its sending address.
43045 Modbus Baud Read 0: 2400 Baud Default: 3 Changing
g g the baud rate causes
Rate Only 1: 4800 Baud Type: Trim no communication with the an-
nunciator until the Modbus Master
2: 9600 Baud
also changes its baud rate.
3: 19200 Baud
4: 38400 Baud
5: 57600 Baud
43046 Modbus Parity Read 0: Even Default: 2 Changing the parity causes no
O l
Only communication
i ti with ith the
th annun-
1: Odd
ciator until the Modbus Master
2: None Type: Trim also changes its parity.
43047 Modbus Stop Read 1 Default: 1 Changing the stop bits causes no
Bit
Bits O l
Only T
Type: T
Trim
i communication
i ti with ith the
th annun-
2
ciator until the Modbus Master
also changes its stop bits.
43048 Protocol Read 0: RS485 Default: 0 Changes the communication pro-
Only Type: Trim tocol between RS485 and Mod-
1: Modbus bus.
43049 Software Ver- Read Default: NA Sends AUX101 current firmware
sion Only Type: Trim version.

43050 Device Type


yp Read Default: 59 AUX101 Device Type
yp
Only Type: Trim
43051 AUX 102 Read 0: Not Available Default: 0 Indicates if AUX102 expansion
p
Available Only 1: Available Type: Trim board is available.

43052 Save Trims Read/ 0: Do Nothing Do Nothing Saves adjustments to non−vola-


Write tile memory. Perform Save Trims
1: Save Trims Type: Trim after all configurations have been
updated.
42001 Relay 1 Read/ 0: Inactive Default: 0 Parameters to allow the Relay to
W it
Write 1 A
1: Active
ti b turned
be t d on/off.
/ ff The
Th lower
l 8 bits
bit
Relay 2
are used to store out relay values.
Relay 3 Relayy 1 is stored in bit 0 and
Relay 4 Relay 8 is stored in bit 7. The up-
per 8 bits are 0
0. In the event of a
Relay 5 po e cycle
power cyc e or
o reboot,
eboot, all
a the
t e out-
out
Relay 6 put values are reset to 0. This re-
giseter is used as heartbit for
Relay 7
AUX101 and indicates a secure
Relay 8 communication.

553
Addr. System Name Access Specifications Comments
42009 Relay 9 Read/ 0: Inactive Default: 0 Parameters to allow the Relayy to
Relay 10 Write 1: Active be turned on/off.
Relay 11
Relay 12
Relay 13
Relay 14
Relay 15
Relay 16
42017 Input 1 Read Default: NA Register that contains the value
Only of Input 1.
42018 Input 2 Read Default: NA Register that contains the value
Only of Input 2.
42019 Input 3 Read Default: NA Register that contains the value
Only of Input 3.
42020 Input 4 Read Default: NA Register that contains the value
Only of Input 4.
42021 Input 5 Read Default: NA Register that contains the value
Only of Input 5.
42022 Input 6 Read Default: NA Register that contains the value
Only of Input 6.
42023 Input 7 Read Default: NA Register that contains the value
Only of Input 7.
42024 Input 8 Read Default: NA Register that contains the value
Only of Input 8.
42025 Input 9 Read Default: NA Bit 0 of this register is used for In-
Only put 9 when AUX102 is available.
Input 10 Bit 1 of this register is used for In-
put 10 when AUX102 is available.
Input 11 Bit 2 of this register is used for In-
put 11 when AUX102 is available.
Input 12 Bit 3 of this register is used for In-
put 12 when AUX102 is available.
42029 Current Read/ mA = CS/10 Default: NA Set for Analog Input 3.
Source 1 Set- Write
tings Type: Trim

42030 Current Read/ mA = CS/10 Default: NA Set for Analog Input 4.


Source 2 Set- Write
tings Type: Trim

42031 Current Read/ mA = CS/10 Default: NA Set for Analog Input 5.


Source 3 Set- Write
tings Type: Trim

42032 Current Read/ mA = CS/10 Default: NA Set for Analog Input 6.


Source 4 Set- Write
tings Type: Trim

554
Addr. System Name Access Specifications Comments
42033 Input
p 1 Set- Read/ 0: Sender Default: NA Register
g to configure
g Input
p 1.
tings Write 1: Switch − Active Type: Trim
Low
2: Switch − Active
High
42034 Input
p 2 Set- Read/ 0: Sender Default: NA Register
g to configure
g Input
p 2.
tings Write 1: Switch − Active Type: Trim
Low
2: Switch − Active
High
42035 Input
p 3 Set- Read/ 0: Sender Default: NA Register
g to configure
g Input
p 3.
tings Write 1: Switch − Active Type: Trim
Low
2: Switch − Active
High
42036 Input
p 4 Set- Read/ 0: Sender Default: NA Register
g to configure
g Input
p 4.
tings Write 1: Switch − Active Type: Trim
Low
2: Switch − Active
High
42037 Input
p 5 Set- Read/ 0: Sender Default: NA Register
g to configure
g Input
p 5.
tings Write 1: Switch − Active Type: Trim
Low
2: Switch − Active
High
42038 Input
p 6 Set- Read/ 0: Sender Default: NA Register
g to configure
g Input
p 6.
tings Write 1: Switch − Active Type: Trim
Low
2: Switch − Active
High
42039 Input
p 7 Set- Read/ 0: Sender Default: NA Register
g to configure
g Input
p 7.
tings Write 1: Switch − Active Type: Trim
Low
2: Switch − Active
High
42040 Input
p 8 Set- Read/ 0: Sender Default: NA Register
g to configure
g Input
p 8.
tings Write 1: Switch − Active Type: Trim
Low
2: Switch − Active
High

555
THIS PAGE LEFT INTENTIONALLY BLANK

556
www.power.cummins.com
Copyright  2015 Cummins Power Generation Inc. All rights reserved.
Cummins Power Generation, the “C” logo, and Cummins are registered trademarks of
Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.”
are trademarks of Cummins Power Generation. Other company, product, or service names
may be trademarks or service marks of others. Specifications are subject to change without notice.