ProInert Presentation
ProInert Presentation
ProInert®
Equipment Section
System Equipment
Section
Argon Nitrogen
ProInert is made up of
blends of Inert Gases
that occur naturally in
the atmosphere
Carbon
Dioxide
Fike’s ProInert Inert Agents
IG-55 IG-541
52% Nitrogen (N2)
50% Nitrogen (N2)
40 % Argon (Ar)
50% Argon (Ar)
8% Carbon Dioxide (CO2)
Globally Accepted
NFPA 2001 & ISO 140520
Safe for People
ProInert is safe for 80
use in occupied 70
spaces at 60 Argon
concentrations up to 50 Nitrogen
52%. 40 Oxygen
30 CO2
20
A ProInert discharge 10
simply alters the ratio 0
of Nitrogen, Argon & 0 .1 % 78 % 21 % 0.3 %
CO2 vs. Oxygen.
The Air we Breathe
Safe for People
Typical 42% Design 70
Concentration results 60
in an Oxygen level 50 Argon
suitable for Occupied 40 Nitrogen
Spaces 30 Oxygen
(Ref. NFPA 2001) CO2
20
10
0
17 % 70 % 12.5 % 0.3 %
• Class B: Chemical
Storage/Processes, Labs, etc.
(Consult Fike for specific
Design Concentration
requirements)
Inert Gas Application limitations:
Per NFPA 2001, Clean Agent systems shall “NOT” be used on fires
involving the following materials:
• Chemicals or mixtures of chemicals that are capable of rapid
oxidation in the absence of air.
(Examples include: Cellulose Nitrate and Gunpowder)
• Reactive metals such as Lithium, Sodium, Potassium, Magnesium,
Titanium, Zirconium, Uranium, and Plutonium
• Metal hydrides such as Sodium Hydride and Lithium Aluminum
Hydride
• Chemicals capable of undergoing auto‐thermal decomposition.
(Examples: Organic Peroxides and Hydrazine)
Inert Gas Typical Design Concentration / Oxygen Levels
80 Liter (water
69” (1753) 11-1/4” (286) Upright
capacity)
Cylinder Specifications
IG-55 IG-541
IG71-103-200-55 (200 bar) IG71-103-200-541 (200 bar)
Cylinder Part Number
IG71-103-300-55 (300 bar) IG71-103-300-541 (300 bar)
Cylinder Specifications
Cylinder Gross Weight 301 lbs. (136.5 Kg) Approx. @ 200 bar
IG-541 324 lbs. (146.9 Kg) Approx. @ 300 bar
Cylinders available in 200 or 300 bar charging capacity.
Cylinder Specifications
Shipping Cap
• Primary-Electric (PE)
Cir-Clip
Nozzle Body
Discharge Nozzle Assembly
Size Style Part Number • Available in ½” thru 2”
360° IG71-072 NPT sizes
1/2”
180° IG71-209 • 180° & 360° Styles
360° IG71-073
3/4 “
180° IG71-210
360° IG71-074
1”
180° IG71-211
360° IG71-215
1-1/4”
180° IG71-216
360° IG71-075
1-1/2”
180° IG71-212
360° IG71-214
2”
180° IG71-213
IG71-076, Manifold Safety Disc
• Used on closed manifolds to prevent entrapment of
high pressure from accidental release (used behind
check valves & selector valves)
Manifold Safety Disc Specs
Odorizer Specs
Odorizer Part Number IG71-240
Rebuild Kit Part Number IG71-241
Thread size 3/4” NPT
Material Brass Body
Listings and Approvals UL / ULC / Factory Mutual
Cylinder Mounting Hardware
• Composed of Unistrut, threaded rod and special
clamps
• Available in multiple single, double and triple row
configurations
Front Support
Rear Support
IG71-065-2 1 02-11884 1 2
IG71-065-3 1 02-11885 1 2
Tee Plate
Post Base
Selector Valve Assembly
• Provides a means of diverting agent discharge into a
designated zone
• Allows a cylinder bank to be used to protect one of
several hazards
• Must have a minimum of 2 Selector Valves
Selector Valve Assembly
Selector Valve Assembly Includes:
• Selector Valve w/ Actuator
• Valve Position Monitor
• Relief / pop-off valve
• 3’ long hose with fittings and adapters
• UVO Kit with release fitting (1/4” NPT, Male)
Selector Valve
UVO Kit
IG71-111,
Release Fitting
Selector Valve Assembly
Selector Valve Specs
Part Number Valve Size Thread Size
IG71-233-10-CD 1” 1” NPT Female (25 mm)
IG71-233-15-CD 1-1/2” 1-1/2” NPT Female (40 mm)
IG71-233-20-CD 2” 2” NPT Female (50 mm)
IG71-233-30-CD 3” 3” NPT Female (80 mm)
Material Carbon Steel or Stainless Steel (Specify)
Actuation Pressure 116 psi (8 bar) Minimum
Approvals FM Only
Selector Valve System Example
System Signs
02-11776
Caution / Exit Sign
(Black text over white and yellow
background)
02-11777
Caution – Do Not Enter Sign
(Black text over white and yellow
background)
02-11778
Manual Release Station Sign
(Black text over white background)
System Piping
• Schedule 40 or 80, Threaded,
Welded or Grooved(*)Pipe shall be
used
• Black or Galvanized Pipe is
acceptable
• Cast Iron Pipe, Steel Pipe
conforming to ASTM A120 or Non-
Metallic Pipe shall not be used
• All pipe shall conform with the
appropriate code for your
installation (NFPA 2001, ISO14520
or EN 15004)
• *Minimum piping design pressure
of 870 psi @ 68°F (60 bar @ 20°C)
• Refer to table in Manual
System Fittings
• Minimum piping design pressure of 870
psi @ 68°F (60 bar @ 20°C)
• Class 300 malleable or Ductile Iron
acceptable up to 3”
• 1,000 lb. Ductile or Forged Steel required
above 3”
• Class 600 Flanged acceptable for all pipe
sizes
• Class 150 Fittings are not acceptable
• Cast Iron Fittings are not acceptable
• Grooved Fittings MUST meet minimum
design pressure
• (*Not all grooved fittings are acceptable
for Fire Protection service. Check UL
listing for all grooved fittings)
END OF EQUIPMENT SECTION